Sunteți pe pagina 1din 2

ETAP

Project:

Page:

7.0.0

Location:
Contract:
Engineer:
Filename:

Study Case: SC
ff

987654321

Date:

09-24-2013

SN:

12345678

Revision:

Base

Config.:

Normal

SHORT
-Adjustments
CIRCUIT
REPORT
Short
Branch
-Circuit
Bus
Input
Connections
Summary
Data
Report
Synchronous
Lumped
Generator
Load
Input
Input
Data
Data
Line/Cable
Input Data
Electrical Transient
Analyzer
Program
Positive
Seq. Impedance

1/2 Cycle
Apply
Individual
Fault
at bus:- 3-Phase,
Bus4 LG, LL, & LLG Fault Currents
Impedance,
MVAb
SynchronousCKT/Branch
GeneratorLumped Load
Rating
GroundingPos. Seq., 100
Zero
Seq. Impedance
BusConnected Bus ID % Xd"
Initial
Voltage
Motor%
Loads
Tolerance
Adjustments
/Global(Cable)Percent
Ohms
or
Siemens
per
1000
ft
per
Conductor
orRper Phase (Line)
ID
Type
From
Bus
To
Bus
X
Z
Y% R0
Prefault Voltage
=
100
%
of
the
Bus
Nominal
Voltage
Short-Circuit
Analysis
ID
Type
MVA
kV% Load
RPM
% R BaseAdj.
Tol.
% Xd'%Mag.
Conn.
X/R
% X0
ID
Type X"/R
Nom.
kV
kVX/R Ratio
Sub-sys
Ang. TypeBase) Amp
Rating
Loading
Imp.
(Machine
Grounding
Load
Prefault Line/Cable
voltageLumped
= 11.000
kV
= 100.00 Impedance:
% of nominal
bus kV ( 11.000
kV) Yes
Individual
Length
Transformer
Line2
Line
Bus1
Bus2
0.70
1.68
1.82
0.0000092
= 100.00
% Turbo
of base Bus1
kV kVA
( 11.000
kV)
ID
kV
MTR STAT
kW 11.000
kvar 11.000
X"/R 0.01X'/R 28.00 100.00
% R Wye %
X"
% X'
Conn.
Load 19.00
0.00
Gen1
235.294
11.000
1800
1.000
19.00
Solid
19.00 Type
0.368 Amp.7.00
ID
Library
Size
Adj. (ft)
% Tol.
#/Phase
R1
X10.70
Y11.68
R01.82
X0
Y0
Yes T (C) Individual
Line3
Line Reactor Impedance:
Bus2
Bus3
0.0000092
ANSI
Standard
Lump1Synchronous
11.000
80
20Load 6800.0
4214.3 11.000
10.00
10.00
1.538 Fault
15.38
23.08
Delta
11.000
1 Line-to-Line
100.00
0.00
Bus Generators ( = Bus2
3-Phase Fault
Line-to-Ground
Fault
*Line-to-Line-to-Ground
Total Connected
1 10000.0
): 235.294 MVA
Line2 Line4
250
100.0
0.0
1
75
0.0849349
0.2028771
0.0000008
0.1351471
0.4218097
0.0000006
Line Overload Heater
Bus3Resistance:
0.70
1.68
1.82
0.0000092
No Fault Currents
&Bus4
LLG
Lump2 ID
30000.0Real 11.000Imag. 80 3-Phase,
20Load LG,
20400.0
12642.8
10.00
10.00
1.538
15.38
23.08
Bus3
11.000
11.000
1 Real
100.00
0.00
Line-To-Line-To-Ground
kV
Mag.
RealLL,
Imag.
Mag.
Imag.Fault
Mag.
Real DeltaImag.
Mag.
Line3 Line5
250
100.0
0.0
1
75 0.0849349 0.2028771
0.0000008
0.1351471
0.4218097
Line
Bus4
Bus5
0.70
1.68
1.82
0.0000092 0.0000006
No11.000
Transmission
Line
Length:
%
Voltage
at
From
1/2
Bus
Cycle
Network
Current
at
From
Bus
(kA)
Contribution
Lump3
15000.0
11.000
80
20
10200.0
6321.4
10.00
10.00
1.538
15.38
23.08
Delta
Bus4
Load
11.000
1
100.00
0.00
Bus4
11.00
10.619
-51.552
52.634
10.202
-40.808
42.064
44.783
9.666
45.815
-49.168
7.228
49.697
Line4 Line6
250
100.0
0.0
1
75 0.0849349
Line
Bus7
Bus1
From
Bus
To BusBus5
Va
Vb 17000.011.000
Vc No11.000
Ia
Cable Length:
Lump4
25000.0
11.000
80
20Load
10535.7
10.00
10.00
1
Line5
250
100.0
0.0
1
0.0849349
ID
ID
Mag.
Ang. 75Mag.
Ang.
All fault currents
are symmetrical momentary
(1/2 CycleMag.
network) Ang.
values in Mag.
rms kA Ang.
Lump5
5000.0
11.000
80
20SWNG 3400.011.0002107.1 11.000
10.00
10.00
Bus7
1
Line6
250 -1.4 100.0
0.0
1 Apply
0.0849349
Bus4
Total
116.50
0.00
0.0
0.00
0.0 75 0.000
0.0
Individual
20000.0
11.000
80
20
13600.0
8428.5
10.00
10.00
* LLG Lump6
fault current is the larger of the two faulted
line currents
6 Buses Total
Temperature Correction
Adjustments
/Global
Bus3 Total Connected Lumped
Bus4 Loads ( = 6 ): 105000.0111.79
-1.5
17.37 -133.5
15.79 118.4
kVA
Transmission
Line
Resistance:
Line / Cable resistances are listed at the specified
temperatures.
All voltages
reported by
ETAP
are in % of bus Nominal kV. Yes
Bus5
Bus4
-1.4
0.41
-114.2
0.40
80.5
Swing
V116.60
-of
Control
Load
Total
Base
kV values
buses are
calculated
and used
internally
by ETAP.
Yes
Cable Resistance:
Lump4
Bus4
100.00
0.0
100.00 -120.0
100.00 120.0

Number of Buses:

Degree C

42.570

170.5

41.652

36.5

27.255

17.513

11.572

1.193

178.5

1.168

13.2

0.827

0.525

0.000

5.993

178.4

5.864

13.1

4.154

2.636

0.000

XFMR2

XFMR3

Reactor

Line/Cable

Impedance

Tie PD

Total

# Indicates fault current contribution is from three-winding transformers

Number of Branches:

1.827 100.6
Individual
0.303
-79.3
Individual
1.524
-79.4

0.2028771
0.70 0.0000008
1.68 0.1351471
1.82 0.4218097
0.0000092 0.0000006
Ic
1.538 Ib 0.00
15.38
23.08
Delta Sequence Current (kA)
100.00
0.2028771
0.0000008
0.1351471
0.4218097
Mag.
Ang.
Mag.
Ang.
I1
I20.0000006I0
1.538
15.38
23.08
Delta
100.00
0.00
0.2028771
0.0000008
0.4218097
0.0000006
49.697 171.6
48.1910.1351471
33.1
32.205
20.646
11.572
1.538
15.38
23.08
Delta

* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta-Y transformer

Synchronous
Generator

Power
Grid

Synchronous
Motor

Induction
Machines

Lumped
Load

Total

Number of Machines:

System Frequency:

60 Hz

Unit System:

English

Project Filename:

ff

Output Filename:

G:\ff\report1.SA2

ETAP

Project:

Page:

7.0.0

Location:
Contract:
Engineer:
Filename:

Study Case: SC
ff

10

Date:

09-24-2013

SN:

12345678

Revision:

Base

Config.:

Normal

Sequence Impedance Summary Report


Bus
ID
Bus4

Positive Seq. Imp. (ohm)


kV
11.000

Negative Seq. Imp. (ohm)

Zero Seq. Imp. (ohm)

Fault Zf (ohm)

Resistance

Reactance

Impedance

Resistance

Reactance

Impedance

Resistance

Reactance

Impedance

Resistance

Reactance

Impedance

0.02434

0.11818

0.12066

0.02631

0.11651

0.11945

0.05920

0.20472

0.21311

0.00000

0.00000

0.00000

S-ar putea să vă placă și