Sunteți pe pagina 1din 10

IS 2026 ( Part 6 ) : 1994

( Reaffirmed 1999 )

Indian Standard
POWERTRANSFORMERS
PART 5 TRANSFORMER/REACTOR BUSHINGS - MINIMUM EXTERNAL
CLEARANCE IN AIR - SPECIFICATION

( Second Reprint OCTOBER 1997 )

UDC 621*315*626*042*4 : 621*314.212+621-318.43

Q BIS 1994

BUREAU OF INDIAN STANDARDS


MANAK BHAVAN, 9 BAHADUR SljAH ZAFAR MARG
NEW DELHI 110002

May 1994 Price Group 4


Transformers Sectional Committee, ETD 16

FOREWORD

This Ir,dian Standard was adopted by the Bureau of Indian Standards, after the draft finalized by the
Transformers Sectional Committee had been approved by the Electrotechnical Division Council.
In the preparation of this standard considerable assistance has been derived from IEC Pub 76-3-l
( 1987 ) ‘Power Transformer : Part 3 lnsulation levels and dielectric tests External clearances in air’
issued by the International Electrotechninal Commission ( IEC ).
For the purpose of deciding whether a particular requirement of this standard is complied wilh, the final
value, observed or calculated, expressing the result of a test or analvsis shall be rounded off in accordance
with IS 2 : 1960 ‘Rules for rounding off numerical values ( revised )‘. The number of significant places
retained in the rounded off value shall be the same as that of the specified value in this standard.
IS 2026 ( Part 5 ) : 1994

Indian Standard
POWERTRANSFORMERS
PART 5 TRANSFORMER/REACTOR BUSHINGS-MINIMUM EXTERNAL
CLEARANCE IN AIR - SPECIFICATION

P SCOPE rounded electrodes. It is assumed that conduc-


tor clamps with their associated shield electrodes
This Indian Standard specifies clearances in air are suitably shaped so that they do not reduce
between live paIts of bushings on oil-immer;sed the flashover voltage. It is also assumed that the
power transformers and reactors and to object at arrangement of incoming conductors does not
earth potential. reduce the effective clearances provided by the
NOTE - Wherever the word ‘transformer’ appears transformer itself.
in the text, read as ‘transformer/reactor’.
NOTE - If the user intends to make his connection
in a particular way which is likely to reduce the
2 REFERENCES effective clearances, this should be mentioned in the
enquiry.
The Indian Standards listed in Annex A are
necessary adjuncts to this standard. 3.5 In general, the provision of adequate
clearances in air becomes technically difficult
3 GENERAL mainly at high system voltages, particularly for
3.1 Clearances m air are understood to mean, in relatively small units, or when the installation
this standard, distances where the electrostatic space is restricted. The principle follo\bed in the
field is free from disturbance by insulator recommendations of this standard is to provide
bodies. The standard does not deal with the ample, non-critical clearances which are satis-
requirements of effective flashover distance or factory without further discussion or proof
creepage distance along the bushing insulators under various system conditions and in different
nor does it consider the risk From intrusion of climates. Where extensive previous experience
birds or animals. has indicated that smaller clearances are
adequate, there is obviously no need to change.
3.2 The insulation levels and dielectric tests
which are specified in IS 2026 ( Part 3 ) : 1981 3.6 The recommended clearances are referred
shall apply for oil immersed transformers to the to the rated withstand voltage values of the
internal insulation only. internal insulation of the transformer, unless
otherwise specified in the enquiry and order.
3.3 It is reasonable that the rated withstand When the clearances of the transformer are
voltage values which are specified for the inter- equal to or larger than the values specified in
nal insulation of the transformer should also be this standard and the bushings have properly
taken as a reference for its external insulation. selected ratings according to IS 2099 : 1986
This may, however, not be true in all cases. A then the external insulation of the transformer
failure of the non-self-restoring internal insula- shall be regarded satisfactory without further
tion is catastrophic and normally leads to the testing.
transformer being out of service for a long
period, while an external flashover may involve NOTES
only a short interruption of service without 1 The impulse withstand strength of the external
causing lasting damage. Therefore, it may be insulation is polarity dependent, in contract to what
that, for increased safety, higher test voltages is assumed for the internal insulation. The tests
are specified by the user for the internal insula- prescribed for the internal insulation of the trans-
former do not automatically verify that the external
tion of the transformer than for the external insulation is satisfactory. The recommended
insulation of other components in the system. clearances are dimensioned for the more onerous
If such a distinction is made, the external polarity ( positive ).
clearances on the transformer should be referred 2 It is recognised that in some cases’good experience
instead to those specified for external insulation with well documented national practice allows the
withstand voltages. continuing use of established smaller clearances with-
out further discussion or testing.
3.4 When establishing the requirements of the
present standard in the higher voltage ranges, it 3.7 If a clearance smaller than that according
has been recognised that the bushing ends to the paragraph above has been used for a
normally have a rounded electrode shape. The contract, a type test may be required on an
clearance requirements are valid between such arrangement simulating the actual clearance, or

1
IS 2026 ( Part 5 ) : 1994

Table 1 Recommeded Minimum Clearances from Bushing Live Parts on Power Transformers
Having Windings witb Highest Voltage for Equipment U, <’ 300 kV
( Altitude Up to 1 000 m )
( Clause 4.1 )

Highest Voltage Rated Short Rated Lighthing Impulse Withstand Minimum Clearance
for Equipment Duration Voltage r_--_---_- h_-- _-__ __~
Power Fre- ( peak ) With Reference Wit:oRgr$ernce
Crms ) quency With- r---- ----_h_--_--_.-_ to Distribution
stand Voltage Distribution Other Trans- Transformers Transformers
( rms ) Transformers formers
(1) (2) (3) (4) (5) (6)
kV kV kV kV mm mm

< 1’1 3 - - - -

3’6 10 20 40 - 60
7’2 20 40 60 60 90

12 28 60 75 90 125

17.5 38 1.5 95 125 170

24 50 95 125 170 225

36 70 145 170 275 315


52 95 0
I
L15t3

72’5 140 325 630


165
450 830
123

230 550 1 050

650 1 250
275

750 1 450
325

245
850 1 600
360

395 950 1 800

Table 2 Recommended Minimum Clearances from Bushing Live Parts on Power Transformers
Having Windings with Highest Voltage for Equipment U, > 300 kV, Specified
According to Method 1 ( Altitude Up to 1 000 m )
( Clauses 4.1 and 4.2 )
Highest Voltage Rated Short Dura- Rated Lightn- Minimum Clearance
for EF;pment tion Power Fre- ing Impulse r------- h-_-----~
quency Withstand Withstand Phase-to- Phase-to-
( rms ) Voltage Voltage Earth Earth
( rms )
(1) (2) (p3) (4) (5)
kV kV . kV mm mm
9.50 1 900 2 250

460 1 050 2 300 2 650

1 050 2 300 2 650

1 175 2 700 3 100

1 300 2 700 3 100

1 425 3 100 3 500

3
IS 2026 ( Part 5 ) : 1994

Table 1 Recommeded Minimum Clearances from Bushing Live Parts on Power Transformers
Having Windings witb Highest Voltage for Equipment U, <’ 300 kV
( Altitude Up to 1 000 m )
( Clause 4.1 )

Highest Voltage Rated Short Rated Lighthing Impulse Withstand Minimum Clearance
for Equipment Duration Voltage r_--_---_- h_-- _-__ __~
Power Fre- ( peak ) With Reference Wit:oRgr$ernce
Crms ) quency With- r---- ----_h_--_--_.-_ to Distribution
stand Voltage Distribution Other Trans- Transformers Transformers
( rms ) Transformers formers
(1) (2) (3) (4) (5) (6)
kV kV kV kV mm mm

< 1’1 3 - - - -

3’6 10 20 40 - 60
7’2 20 40 60 60 90

12 28 60 75 90 125

17.5 38 1.5 95 125 170

24 50 95 125 170 225

36 70 145 170 275 315


52 95 0
I
L15t3

72’5 140 325 630


165
450 830
123

230 550 1 050

650 1 250
275

750 1 450
325

245
850 1 600
360

395 950 1 800

Table 2 Recommended Minimum Clearances from Bushing Live Parts on Power Transformers
Having Windings with Highest Voltage for Equipment U, > 300 kV, Specified
According to Method 1 ( Altitude Up to 1 000 m )
( Clauses 4.1 and 4.2 )
Highest Voltage Rated Short Dura- Rated Lightn- Minimum Clearance
for EF;pment tion Power Fre- ing Impulse r------- h-_-----~
quency Withstand Withstand Phase-to- Phase-to-
( rms ) Voltage Voltage Earth Earth
( rms )
(1) (2) (p3) (4) (5)
kV kV . kV mm mm
9.50 1 900 2 250

460 1 050 2 300 2 650

1 050 2 300 2 650

1 175 2 700 3 100

1 300 2 700 3 100

1 425 3 100 3 500

3
IS 2025 ( Part 5 ) : 1994

Table 3 Recommended Minimum Clearances from Bushing Live Parts on Power Transformers
Having Windings with Highest Voltage for Equipment iJ, > 300 kV, Specified
According to Method 2 ( Altitude Up to 1 000 m )
( Clauses 4.3, 4.3.1.3.~ and-4.3.2 )
Highest Voltage Rated Switching Rated Lightning LMinimum Clearance
for Eq;i;ment Impulse Withstand Impulse With- ~---_-----_----h ---------7
Voltage stand Voltage Phase-to-Earth, Phase-to-Phase, To Other
(rms) ( peak ) ( peak 1 Based on Swit- Based on Swit- Winding,
thing Impulse thing Impulse Based on
Withstand Withstand Lightning
Vojtage Voltage Impulse
Withstand
Voltage
(1) (2) (3) (4) (5) (6)
kV kV kV mm mm mm
650 1600
750
300
1 900 2 250
950 1 750
650
362 2 300 2 650
1050 1 950
950
420
2 700 3 100
1175 2200

1300 2400
1050
3 100 3 5co
525 1425 2 650
1175
3 700 4 200
1550 2 850
5 000 5 800
765
1800 3 300
5 800 6700
1950 3 600

Dm
1

I i i i i i i i kV

500 1000 1500 2ooq


Fan. I CLEARANCE PHASE-TO-EARTH BASEDON RATED SWITCHING IMPULSE
WITHSTANDVOLTAGE
4
IS 2026 ( Part 5 ) : 1994

Om

1000 1500 2000 2500

FIG. 2 CLEARANCE
PHASE-TO-PHASEBASEDON SWITCHING IMPULSEVOLTAGE APPEARING
BETWEENPHASE

to IS 2165 ( Part 2 ) : 1983 ( see Table 4 ). An between the two terminals under consideration
appropriate test procedure involves positive during the switching impulse test [ see 14 of
polarity impulses for a configuration phase-to- IS 2026 ( Part 3 ) : 1981 ] according to the turns
earth, and opposite polarity impulses for phase- ratio between the windings. This voltage.value
to-phase clearances ( see 4.3.3 ). This has been gives the clearance which is required with regard
considered for the clearance values given in to the switching impulse condition. Fig. 2 is
Table 3. used to find the recommended clearance if the
terminals receive opposite polarity voltages and
4.3.1 Clearance Phase-to-Earth, Phase-to-Neutral the ratio between their voltage amplitudes is 2
and Phase-to-Phase Between Phases of the Same or less. In other cases, Fig. 1 applies.
Winding
NOTE;If Fig. 1and Fig. 2 are compared, it appenrs
The clearance from the high voltage bushing that a phase-to-phase clearance withstands a higher
top to earth ( tank, conservator, cooling equip- voltage difference than the same.distance would do
in a phase-to-earth configuration. The reason is that
ment, switchyard structures ) or to the neutral in the phase-to-phase configuration the two terminals
terminal is determined from column 4 of are supposed to have opposite polarity, and the
Table 3. The clearance between bushing caps of maximum dielectric gradient at either of them ( which
difference phases is determined from column 5 is largely determined by the voltage to earth ) is
relatively lower.
of Table 3.
It is assumed also that the electrodes have a
4.3.2 Clearance Between Terminals of Different
rounded shape. The clearance however,
shall,
Windings also fulfil the lightning impulse withstand
The clearance between terminals of different requirement, which presupposes that the lower
windings of the transformer shall be checked voltage winding terminal is at earth potential
with regard to both switching, impulse and when rated lightning impulse withstand voltage is
lightning impulse conditions. The switching applied to the high voltage terminal. The dis-
impulse withstand requirement is based on the tance requirement in column 6 of Table 3 and
precalculated difference voltage which appears Fig. 3 corresponding to this rated lightning

5
----

IS 2026 ( Part 5 ) : 1994

FIG. 3 CLEARANCE BASEDON LIGHTNING IMPULSEVOLTAGE

impulse voltage, has therefore, to be fulfilled test voltage, positive, on one line terminal, the
between the two terminals. The higher of the other half, negative on another line terminal,
two clearance estimates shall apply. The and the third terminal earth [ see 10, 12 and 14
s\\,itching impulse test on the transformer will of IS 2165 ( Part 2 ) : 1983 ] The combinations
induce voltages between phases of other star- of phase-to-earth and phase-to-phase test volt-
connected windings as well. It shall be checked ages, according to IS 2165 ( Part 2 ) : 1983 are
wliether this condition requires a larger phase- reproduced in Table 4. The values for
to-phase clearance in such a winding than as U, = 525 kV and 800 kV are subject to
prescribed for this \vinding alone such as in 4.1. review.
4.3.3 Type Test Procedure
If a tape test on a reduce clearance is to be When the outer phases are placed symmetrically
conducted, the test procedure shall be as with respect to the middle phase, it is sufficient
foilows: to make two separate tests, one with positive
polarity on the middle phase, and the other
A test on a configuration phase-to-earth or with positive polarity on an outer phase, the
phase-to-netural, or towards a terminal of a middle phase having negative polarity. If the
lower voltage winding shall consist of a line terminal arrangement is asymmetrical, it
switching impulse test, dry, with positive may be necessary to perform more than two
polarity on the line terminal of the winding tests.
( the higher voltage winding ). The counter
electrode shall be earthed. If the tested
terminal belongs to a three-phase winding, Each test shall consist of 15 applications of
the other line terminals shall also be impulse voltage with wave shape 250/2 500 in
earthed. accordance with IS 2071 ( Part 1 ) : 1993.
NOTE - This test ih not generally feasible on
complete three-phase transformers and may, thcre- NOTE - The above test procedure for phase-to-
for-e, have to be conducted on ;I model simulating the phase external clearances, which follows IS 2165
actual configuration of the transformer. ( Part 2 ) : 1983 differs in several’ respects from the
Tests on the phase-to-phase clearances of a switching impulse test procedure specified for the
internal insulation of the transformer in 14 of
three-phase transformer shall consist of switch- IS 2165 ( Part 2 ) . 1983. The two test procedures do
ing impulse tests, dry, with half of the specified not replace each other.

6
Burenti of Indian Standards

BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods and
attending to connected matters in the country.

Copyright

BIS has the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BPS. This does not preclude the free use, in the course of
implementing the standard, of necessary details, such as symbols and sizes, type or grade designations.
Enquiries relating to copyright be addressed to the Director (Publication), BIS.

Review of Indian Standards

Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue
of ‘BIS Handbook’ and ‘Standards Monthly Additions’.
This Indian Standard has been developed from Dot: No. ETD 16 ( 3486 J

Amendments Issued Since Publication

Amend No. Date of Issue Text Affected

BUREAU OF INDIAN STANDARDS


Headquarters:
Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002 Telegrams: Manaksanstha
Telephones: 323 0131,323 33 75,323 94 02 (Common to all offices)
Regional Offices: Telephone
Central : Manak Bhavan, 9 Bahadur Shah Afar Marg 323 76 17,323 38 41
NEW DELHI 110002
Eastern : l/14 C.I.T. Scheme VII M, V.I.P. Road, Maniktola 337 84 99,337 85 61
CALCUTTA 700054 337 86 26,337 9120
Northern : SC0 335336, Sector 34-A, CHANDIGARH 160022 60 38 43
{ 60 20 25
Southern : C.I.T. Campus, IV Cross Road, CHENNAI 600113 235 02 16,235 04 42
{ 235 15 19,235 23 15
Western : Manakalaya,E9 MIDC, Marol, Andheri (East) 832 92 95,832 78 58
MUMBAI 400093 { 832 78 91,832 78 92
Branches : AHMADABAD. BANGALORE. BHOPAL. BHUBANESHWAR.
COIMBATORE. FARIDABAD. GHAZIABAD. GUWAHATI.
HYDERABAD. JAIPUR. KANPUR. LUCKNOW. NAGPUR.
PATNA. PUNE. THIRUVANANTHAPyRAM.
Printed at Dee Kay Printers, New Delhi, India

S-ar putea să vă placă și