September 2011
Sheet 10 001
10.0-1
Contents
Motor Control (AMPGARD)Medium Voltage Motor Starters General Description Application and Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-1 Personnel Safety Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-1 Mechanical Non-Loadbreak Isolating Switch . . . . . . . . . . . . . . . . . . . 10.1-2 400A, 7.2 kV Vacuum ContactorBolt-in, Type SL. . . . . . . . . . . . . . . 10.1-3 400A, 7.2 kV Vacuum ContactorStab-in, Type SL . . . . . . . . . . . . . . 10.1-4 Current Limiting Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-4 Isolated Low Voltage Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-5 Bus and Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-6 Reduced Voltage StartersMechanical . . . . . . . . . . . . . . . . . . . . . . . 10.1-7 Reduced Voltage StartersSolid-State . . . . . . . . . . . . . . . . . . . . . . . . 10.1-8 Synchronous Motor Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-10 Incoming Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-11 Potential Transformers and Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-11 Type LBS Loadbreak Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-11 Main Breaker AMPGARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-12 Technical Data Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-14 LBS Loadbreak Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-17 Type SL, 400A, 7.2 kV Vacuum Contactor . . . . . . . . . . . . . . . . . . . . . . 10.1-17 Type SJ, 800A, 7.2 kV Vacuum Contactor . . . . . . . . . . . . . . . . . . . . . . 10.1-18 Type SL, 250A, 15 kV Vacuum Contactor. . . . . . . . . . . . . . . . . . . . . . . 10.1-19 Main Breaker Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-20 Contactor-Fuse Coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-21 Protection Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-22 Starter Fuse Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-23 Layout Dimensions Full Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-24 Primary Reactor, Reduced Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-27 Autotransformer, Reduced Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-29 Synchronous Brush Type Mark V Controller . . . . . . . . . . . . . . . . . . . 10.1-30 Solid-State Reduced Voltage AMPGARD MV4S . . . . . . . . . . . . . . . . . 10.1-32 Incoming Line Switch/PT Layouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-35 Tie Switch Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-37 Arc-Resistant Starter Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-38 Main Breaker AMPGARD Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1-39 Adjustable Frequency Drives General Description Application and Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2-1 AMPGARD SC 9000 Fully Integrated AE-Frame AFD . . . . . . . . . . . . 10.2-2 Synchronous Transfer Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2-13 15 kV Input Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2-15 Integrated VCPW Main Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2-16 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2-17 Personnel Safety Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2-19 Component Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2-20 Optional Output Filters and Reactors . . . . . . . . . . . . . . . . . . . . . . . . . 10.2-23 Technical Data and Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2-24 Specications See Eatons Product Specication Guide, available on CD or on the Web. CSI Format: . . . . . . . . . . . . . . . . . . . . . . . . 1995 2010 AMPGARD Motor Starters . . . . . . . . . . Section 16349 Section 26 18 39 SC 9000 . . . . . . . . . . . . . . . . . . . . . . . . . Section 16349B Section 26 18 39.13
Florettgatan 33 SE-254 67 Helsingborg, Sweden Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
CHS Controls AB
CA08104001E
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
CA08104001E
CHS Controls AB
September 2011
Sheet 10 003
10.1-1
The low voltage compartment is painted white as standard to maximize serviceability. Simplicity of design: Componentto-component design eliminates half of the electrical connections. Time-proven contactor technology: Three vacuum contactor ratings are used, 400A and 800A 7.2 kV and 250A 15 kV. 400A 7.2 kV contactors are available as stab-in or bolt-in design. 800A 7.2 kV and 250A 15 kV contactors are available as stab-in design only. High degree of isolation: Main bus is located in separate compartment on top of lineup. Vertical bus is barriered in rear of starter and auxiliary compartments. Load cables are isolated from adjacent starter in two-high sections. A vertical low voltage wireway is provided for isolation of customer control wiring. The low voltage control compartment is isolated from medium voltage by steel barriers. Starter catalog types are available for the following applications:
of the starters in the enclosure. Refer to Table 10.1-4 on Page 10.1-17 for specic ratings for each enclosure type.
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Arc-Resistant AMPGARD
When specied, AMPGARD is available in special arc-resistant construction. Two ratings are available, 30 kA and 50 kA. Both designs have been tested and veried to meet the requirements of IEEE C37.20.7 for Type 2B construction. Type 2B construction is dened as arc-resistant at front, back and sides of the enclosure with the low voltage compartment door open. Most types of 400A and 800A starters, as well as 24-inch (610 mm) wide incoming cable sections are available in arc-resistant construction. A common plenum design to close couple to Eaton arc-resistant switchgear is also available. Consult factory for ratings on this design. Main breaker AMPGARD, SC 9000 AFD, LBS load break switches are not available in arc-resistant construction. Due to the specic nature of arc-resistant testing, no modications may be made to the enclosure while maintaining the arc-resistant rating. Consult Eaton for more details.
General Description
Eatons medium voltage metal-enclosed control family provides control and protection of medium voltage motors and equipment rated 230013,800V nominal/15,000V maximum. AMPGARD
Application Description
AMPGARD control has a complete metal-enclosed offering:
Full and reduced voltage starting of medium voltage motors up to 8000 hp Main breaker metal-enclosed switchgear, a smaller footprint, single integrated assembly direct coupled to the AMPGARD control Integral LBS loadbreak switches available as main, tie or feeder. The LBS can be supplied as fused or un-fused Adjustable frequency drives (SC 9000) up to 4160V, 6000 hp
Squirrel cage, full voltage (reversing and non-reversing) Squirrel cage, primary reactor Squirrel cage, autotransformer Solid-state reduced voltage Synchronous full voltage Synchronous primary reactor Synchronous auto-transformer (reversing and non-reversing) Two-speed, two winding Two-speed, one winding
Interlocks
Interlocking on AMPGARD starters includes: Isolating switch mechanism locks the medium voltage door closed when the switch is in the ON position Provision for optional key interlocks When door is open, interlock prevents operating handle from being moved inadvertently to ON position When contactor is energized, isolating switch cannot be opened or closed
Enclosures
AMPGARD products are available in NEMA 1 general purpose enclosures as standard. NEMA 12 (dust tight), NEMA 3R (outdoor) and arc-resistant enclosures are available options for most products. Contact the factory for exceptions. Enclosure type affects the maximum continuous current rating
MV4S SSRV
2-High FVNR
21
CHS Controls AB
September 2011
Sheet 10 004
i ii 1 2 3 4
Features
A positive mechanical interlock between the isolating switch handle mechanism and contactor prevents the isolating switch from being opened when the contactor is closed or from being closed if the contactor is closed. An operating lever in the isolating switch handle mechanism is designed to shear off if the operator uses too much force in trying to open the non-loadbreak isolating switch when the contactor is closed. This feature ensures that the operator cannot open the switch with the main contactor closed, even if excessive force is used on the operating handle. To operate the isolating switch, the operating handle is moved through a 180 vertical arc from the ON to the OFF position. In the ON position, an operator on the back of the handle housing extends through a bracket on the rear of the starter high voltage door, preventing the door from being opened with the switch closed. When the high voltage door is open, a door interlock prevents the handle from being inadvertently returned to the ON position. When the operating handle is moved from ON to OFF, copper stabs are withdrawn from incoming line ngers. As the stabs withdraw, they are visible above the top of the fuses when viewed from the front, and simultaneously grounded. As the ngers are withdrawn, a spring-driven isolating shutter moves across the back barrier to prevent front access to the line connections. As the shutter slides into position, distinctive markings appear on the back barrier, making it easier to check the position of the shutter.
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Provision for a padlock on the isolating switch handle in OFF position Shutter barrier between line terminals and isolation switch stabs is mechanically driven Distinctive marking on back of switch assembly appears when shutter barrier is in position and starter is completely isolated from the line Grounding clips provide a positive grounding of the starter and main fuses when the isolating switch is opened High and low voltage circuits are compartmentalized and isolated from each other The drawout isolation switch is easily removed by loosening two bolts in the back of the switch. The shutter remains in place when the switch is withdrawn
Control Plug
A remote operator for the starter isolation switch is an available option. The AMPGARD Remote Operator (ARO) enables users to open or close the switch through the use of a pushbutton station operated up to 30 feet away from the starter. Users can mount the ARO on the front of the starter, plug it into any available 120 Vac source, then easily operate the isolation switch from outside the starter arc ash boundary.
Isolation Switch
Eatons Type JMT-4/8 and JMT-15 are each a drawout, lightweight, three-pole, manually operated isolating switch mounted in the top of the starter enclosure. They may be easily removed by loosening two bolts in the rear of the switch. The JMT-4 is rated 400A continuous while the JMT-8 is rated 800A continuous. The JMT-15 is rated 250A continuous at 15 kV. All isolation switches have a mechanical life rating of 10,000 operations. The component-to-component circuitry concept includes the mountings for the current limiting fuses as part of the isolating switch.
21
For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
CA08104001E
CHS Controls AB
September 2011
Sheet 10 005
10.1-3
Design
Eaton Vacuum Contactors are highly versatile, low-chop contactors that have been designed to meet all applicable NEMA standards and are UL recognized components. The contactors accommodate mechanical interlocks that function with the starter isolation switch and with other contactors. These interlocks provide unmatched safety and service protection. The contactors consist of a molded frame with moving armature, magnet and vacuum interrupters. The contactor is easily positioned into the starter and long-life vacuum interrupters provide many operations with a minimal maintenance program. The SL operating coils are energized by a control board that provides a pulsewidth-modulated DC output. Control voltages and contactor dropout times are programmed using a DIP switch located on the control board. The control board is mounted in a protected cavity in the molded contactor frame to prevent inadvertent access to the voltage and dropout DIP switch. Four auxiliary contacts (2NO, 2NC) are supplied with each contactor and are wired to terminal blocks on the starter control panel. The vacuum interrupters employ special main contact materials that exhibit a low chop current plus other specially engineered characteristics that minimize switching surges. Surge protection is therefore not required due to the use of the vacuum contactor. Surge protection may be required for other reasons such as the high probability of lightning strike, etc.
Maintenance
Reduced maintenance is one of the outstanding features of Eatons Vacuum Contactor line. The special contact material in the vacuum interrupters provides long life even under severe operating conditions. The main coils operate with a very low temperature rise to maximize insulation life. Steel bearings on the main shaft provide long, troublefree operation.
i ii 1 2 3 4 5 6 7 8
A simple go/no-go gauge is used for checking contact wear. Wear can be checked without removing the contactor from the starter. The vacuum contactor is much lighter than previous generation airbreak or vacuum contactors, which allows for easier insertion and removal from the starter structure.
General Description
Eatons Type SL Vacuum Contactors were designed and engineered specically for use in AMPGARD starters. 7.2 kV SL 400A Vacuum Contactors are self-supporting, compact, drawout, three-pole, DC magnet closed contactors. To permit application matching of the starter to the motor rating, the SL Contactor is available in 400A standard and high interrupting ratings. SL Contactors are available in the standard bolt-in conguration and optional stab-in design. Either bolt-in or stab-in designs can be supplied in a two-high conguration, with a starter maximum of 400 full load amperes. The total NEMA 1 structure rating cannot exceed 720A for a combination of two starters. Refer to Table 10.1-4 on Page 10.1-17 for other ratings.
9 10 11 12 13
14 15 16 17 18 19 20 21
CA08104001E For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
CHS Controls AB
September 2011
Sheet 10 006
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
400A Stab-in Contactor
7200V Maximum
800A Vacuum Break Contactor 7200V Maximum Stab-in with Wheels, and Line and Load Fingers
CA08104001E
CHS Controls AB
September 2011
Sheet 10 007
10.1-5
i ii
Bolted Main Fuses Customer Terminal Blocks for Remote Control Connections
1 2 3
Horizontal Wireway Vertical Control Wireway Control Power Transformer (750 VA Standard, up to 4 kVA Available)
4 5 6 7 8 9 10
The device panel, MP-3000 and MP-4000 motor protective relays all t in this same size low voltage door cutout. The low voltage control panel is behind the low voltage door and is completely isolated from the medium voltage compartment. A standard viewing window allows visual verication of the isolation switch status before attempting to open the medium voltage door. The medium voltage door is locked closed whenever the isolation switch is closed.
Predrilled Holes for Additional Control Devices
Standard Isolation Switch Viewing Window Isolation Switch Operating Handle (Mechanism Locks Medium Voltage Door When Switch is Closed)
11 12 13 14 15 16 17 18 19 20
21
CA08104001E
CHS Controls AB
September 2011
Sheet 10 008
i ii 1
Phase A
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
Phase B
Phase C
Seismic Certication
AMPGARD starters have been tested and seismically qualied against requirements dened within the International Building Code 2009 (IBC). The equipment manufacturer, specier, Authority Having Jurisdiction (AHJ), and installer have a shared responsibility to ensure that the installation will meet the seismic requirements of the code. Eaton has determined via testing that the equipment will function following a seismic event provided that the installation instructions are adhered to. The equipment specier and installer must ensure that the equipment is rigidly supported and will not leave its point(s) of attachment during a seismic event. The AHJ shall conrm that the installation method conforms to the manufacturers guidelines. For seismic certicates and product specic information, visit www.eaton.com/seismic.
Main Bus
When starters are grouped together in a lineup, a typical option is the main bus. The AMPGARD main bus is mounted in its own 12-inch (305 mm) high top-mounted enclosure, which isolates it from the starter. The connection from the main bus to the starter is done with rigid vertical bus. Insulated barriers are provided for separate top entry of power and control cables. The main bus is top, side and front accessible, which allows for ease of maintenance or extension of lineup without disassembling the starters. Main bus is available for 1000, 1200, 2000 and 3000A. Main bus is uninsulated as standard. Fully insulated bus is an available option for up to 7.2 kV starters and is standard on 15 kV starters. Bus may be supplied with either tin or silver plating. Crossover bus, busway entry, and pull boxes are not available for the 3000A design (3000A bus duct provisions are available with the Main Breaker AMPGARD, see Page 10.1-12). The standard bus short circuit rating is 50 kA per NEMA standards and is based on the let-through current of the largest fuse used in any starter. An optional 50 kA, 2-second bus rating is available for customers that require a higher rating for the main bus.
Vertical Bus
Vertical bus is located behind a xed barrier in the rear of the enclosure. It is fully insulated as standard, with plating to match that of the main bus.
The major components, i.e., contactor, isolating switch, fuses, EMR-3000 and EMR-4000 are UL recognized. UL or CSA labeling of a specic starter requires review to ensure that all requested modications and auxiliary devices meet the appropriate standards. Refer to factory when specied. AMPGARD starters meet the requirements of IEC standards 60694, 60298 and 60470.
Bus and cable entrance enclosures Transformers Power factor correction capacitors Operators and pilot devices Instruments and meters Control relays and timers Solid-state or selected electromechanical protection devices
CA08104001E
CHS Controls AB
September 2011
Sheet 10 009
10.1-7
i ii 1 2 3 4
Reactor Starter
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Advantages
Reduces starting currents Least costly reduced voltage starting method
Advantages
Produces the most torque per incoming line ampere of any reduced voltage starting method Less costly than RVSS
Disadvantages
Large footprint: 1-1/2 structures at 400A Bump on transition to full voltage Not as efcient as autotransformer Due to reduced torque during starting, motor must typically be unloaded during the start sequence
Disadvantages
Large footprint: 1-1/2 structures at 400A More costly than reactor Bump on transition to full voltage Due to reduced torque during starting, motor must typically be unloaded during the start sequence
Sequence of Operation
Main contactor (M) closes Current ows through reactor reducing voltage to motor (based on tap setting) When motor current reaches ~125%, the run contactor (R) closes providing full voltage to the motor
Note: Care should be taken when selecting the motor for reduced voltage starting to ensure that there is sufcient torque to accelerate the load at reduced voltage. Motors that do not fully accelerate at reduced voltage will generate high voltages at transition that can damage the autotransformer and void the factory warranty.
Sequence of Operation
Shorting contactor (S) closes Main contactor (M) closes Current ows through autotransformer reducing voltage to motor (based on tap setting) When motor current reaches ~125%, the shorting contactor (S) opens and the run contactor (R) closes providing full voltage to the motor
Note: Because the motor is never disconnected from the supply voltage, the starting is closed transition.
CA08104001E
CHS Controls AB
September 2011
Sheet 10 010
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Starting Characteristics
The soft start controller provides a number of selectable starting characteristics as standard:
Kick Start
Provides an initial boost of current to overcome motor and system inertia.
Ramp Start
Operator sets the initial starting voltage and ramp time. Factory setting for starting voltage is 20%. Range is 0 to 100%. Factory setting for starting time is 10 seconds. Range is 0 to 120 seconds.
Load CablesNormal
Current Limit
Limits the maximum starting current. Used in long start time applications and motor protection applications. Factory setting is 350% of motor FLA. Range is 200 to 600%.
Eliminate shock to your mechanical components Avoid coupling and shaft damage Prevent rotor and winding failure Stop drive belt squeal and breakage Prevent water hammer in pipes Soft stop the pump motors Reduce pressure so valves close gently Avoid the surge wave Reduce peak starting currents Reduce voltage drop on motor start
Ratings
23004160 Vac grounded systems 60 kV BIL impulse rating Horsepower: to 5000 hp
Refer to Table 10.1-19 on Page 10.1-32 for more detailed ratings information. The AMPGARD solid-state soft starter is recommended for application only on power systems that are solidly grounded or resistance grounded. Ungrounded systems are not recommended.
Industry Standards
The AMPGARD solid-state starter is designed and built to meet all applicable industry standards. The 400A starter is available as a UL listed assembly. NEMA ICS3 UL 347 CSA EEMAC E14-1 Manufactured in an ISO 9001 and ISO 14001 certied facility
CA08104001E
CHS Controls AB
September 2011
Sheet 10 011
10.1-9
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13
3. The SCRs are on for only a short time therefore no MCC venting or cooling is required. 4. When a stop command is received, the SCRs can be programmed to ramp down, providing a soft stop.
Design
Soft start components and bypass contactor are mounted in a easyto-remove roll-out truck assembly. Maintenance can be performed with the truck on a bench away from the starter cubicle.
14 15 16 17 18 19 20
21
CA08104001E For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
CHS Controls AB
September 2011
Sheet 10 012
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Basic Brushless
The Basic Brushless starter includes a three-phase DC power supply to generate exciter eld current up to 10A plus a control board that provides basic protection. A solid-state motor protective relay is supplied for pullout protection. Output voltage is adjustable from 62125 Vdc. Stator protection is provided by an EMR-4000 solid-state motor protection relay.
Enhanced Brushless
The Enhanced Brushless starter includes all features of the Basic starter plus premium protection, metering and communications. Features include: Power factor regulation Auto-loading Enhanced metering Event recorder Communications with Modbus TCP/Modbus RTU, Serial Interface (RS-232)
Basic Brush-type
The Basic Brush-type starter includes a three-phase exciter to generate DC rotor current up to 200A plus a control board that determines the proper time to apply the DC eld while also providing basic protection, including:
Locked rotor protection Incomplete sequence Failure to synchronize Blown fuse protection Pullout protection Field loss protection
The protective features are displayed on an Eaton GP02 interface module. Stator protection is provided by an EMR-3000 solid-state motor protection relay.
The standard enhanced display is an Eaton GP04 interface module. An Eaton PanelMate is available as a high-end display.
Enhanced Brush-type
The Enhanced Brush-type starter includes all features of the Basic starter plus premium protection, metering and communications. Features include: Power factor regulation/ VAR regulation Auto-loading Field forcing Enhanced metering Event recorder Communications with Modbus TCP/Modbus RTU, Serial Interface (RS-232) The standard enhanced display is an Eaton GP04 interface module. An Eaton PanelMate is available as a high-end display.
CA08104001E
CHS Controls AB
September 2011
Sheet 10 013
10.1-11
Incoming Line
Depending on the size and number of incoming cables, an incoming line enclosure may be necessary. Different designs are available for incoming power for top or bottom entry. When incoming line metering is specied, an additional 24-inch (610 mm) wide metering structure is typically supplied.
i ii 1 2 3 4 5 6 7 8 9
Potential Transformers, Control Power Transformer and Fuses Mounted in a Disconnect Assembly, Height 20 Inches (508 mm)
10 11 12
Type LBS Loadbreak Switch Shown in Upper or Lower Half of 36-Inch (914 mm) Wide Structure, Height 40 Inches (1016 mm)
13 14 15 16 17 18 19 20
21
CA08104001E
CHS Controls AB
September 2011
Sheet 10 014
i ii 1 2 3 4
Ratings
23006600 Vac systems (7200 Vac maximum), three-phase 60 kV BIL impulse withstand rating ANSI interrupting ratings250, 350 and 500 MVA. 500 MVA rating available for 6600V systems only Continuous current1200, 2000 and 3000A
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
MVA 250
kV 4.16
kV Peak 60 kV BIL
General Description
Eatons Main Breaker AMPGARD (MBA) is a fully integrated metalenclosed medium voltage Type VCP-W Drawout Vacuum Circuit Breaker that is bus connected (close-coupled) to AMPGARD Medium Voltage Starters in a single integrated assembly.
Note: MBA sections are 100 inches (2540 mm) high.
350
4.16
60 kV BIL
500
7.2
60 kV BIL
Main Breaker AMPGARD (7.2 kV max.) is suitable for service entrance. Utility metering sections are not available. Main Breaker AMPGARD is designed and built to meet the following standards where applicable: NEMA ICS-1 and NEMA ICS-3, Part 2 ANSI/IEEE C37.20.3 UL 347 and UL 869A CSA C22.2, No. 31 and No.14 EEMAC G8.2 and E14.1
Listing/Certication
UL listing and CSA certication is available, depending on the specic bill of material.
CA08104001E
CHS Controls AB
Continuous Current at 60 Hz Amperes 1200 2000 3000 1200 2000 3000 1200 2000 3000
September 2011
Sheet 10 015
10.1-13
Microprocessor-Based Relays
Eatons protective relays provide programmable circuit protection, information and operator conducted testing. Refer to Tab 4 for more information.
Enclosures
The MBA is available in NEMA/ EEMAC 1, NEMA/EEMAC 1G/1A, and NEMA/EEMAC 12 enclosures.
i ii 1 2 3
Low Voltage Equipment Cell Compartment for Metering and Protection Devices
Metering
IQ and Power Xpert meters are available for multi-function metering. Refer to Tab 3.
Communications
Eatons Power Xpert Architecture communications provides for monitoring and controlling complete electrical distribution systems of those parts of a system selected by the operator. Refer to Tab 2.
AMPGARD 2-High Structure Bus Connected to Main Breaker Section
4 5 6 7 8 9 10
11 12 13 14 15 16 17 18 19 20 21
CA08104001E
CHS Controls AB
September 2011
Sheet 10 016
i ii 1
Technical Data
Typical Wiring Diagram for Full Voltage FVNR Starter
Motor
2 3 4
1CT
T3
T2
T1
X2 X1
X2 X1 X1
CG GND
MP
H1A H2A
DP
H1C H2A
5 6
C3
1B
H2B
H1B H2B
C12
1C 25
IQ DP4130
7
GFCT
GND
X2 X1
3000 24
G2 G1
DP V3 PF1
V2 V2
8 9 10 11
C H2 H1
B A
GND
SF2 1Amp
MP
Set Point System 11 Trip Mode 1 (X2) Run RIL Off (X2)
2 4
12 13 14 15 16 17
1T3
1T2
1T1
50
+
DC COIL 2
3
Coil Controller
(X1) MX
(X1)
(BLK)
M 5
C B MA A PF1 1 Amp X1 CPT 750 1 Plug 120 V X1 SF1 8 Amp MX 12 Ground X2
M7
M5
*
Start
Start
Ma
Main Fuse
18 19 20 21
ISW
4160 Vac 60 Hz
Figure 10.1-1. Induction Motor Across-the-Line Starter, Vacuum Contactor with Optional EMR-3000 Motor Protection and IQ Metering, Start-Stop Pushbuttons, and Red and Green Indicating Lights
For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
CA08104001E
CHS Controls AB
September 2011
Sheet 10 017
10.1-15
i ii
MOTOR
1
T3 T2 T1
2 3 4
Ground MP EMR-3000
5 6
DP
X1 X2
X1 X2
1CT
Grou
C1 C2 C3
G2
7 8
Ground R4
H3 H2 V11
9
PT SF2 1 AMP Set Point Sys TP Mode 1 11 Set MP3000 Set Point "START" to the Following; TRNC(100), TRNT (Max 30 Sec), and TRN(I).
Ground
H1
10
SB
6 2 6 2
L 0 T2
VC VB VA
12
11 12 13
X2 RUN OFF X2
3SA
1SA
MP
DC
(WHT)
+ -
(BLK)
R 5 1 5 1
(BLK)
Autotransformer
COIL CONTROLLER
14 15 16
MP
SX 52 MA RA SA MP S5
R3
X1
X1
51 RX SF1 MX 8 RX SX 3 M7 Ground M7 M5
17
M4
START 2
ISW
18 19 20 21
L3
L2 4160 Vac 60 Hz
L1 9 4 MP P1 G
STOP 1A
Figure 10.1-2. Induction Motor Reduced Voltage Autotransformer Starter, Vacuum Contactor with Optional EMR-3000 Motor Protection and IQ Metering, Start-Stop Pushbuttons, and Red and Green Indicating Lights
CA08104001E For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
CHS Controls AB
September 2011
Sheet 10 018
i ii 1
Motor
Ground Fault, Instantaneous Overcurrent and Differential (if used). These Trip Conditions Will Result in the Immediate Opening of the Main Contactor (Uncontrolled Shutdown) All Other Trip Functions Will Operate the Trip Output and Allow the Softstart Module to Open the Circuit (Controlled Shutdown)
MAX
24 23 MAX 22
26 21
31 TRPX MP AUX 3 30
B7 Ba TCB
B6
20
71
T3
T2
T1
2 3
Refer to MP4000 Manual IB02602002E, Pages 4-12 Through 4-13, Setpoints 10-2, 10-15 and 10-19.
SS2 Softstart Bypass Position Cont Normal Bypass 1 X 2 X 3 X 4 X X2
Off
12
SCTB CG
X2
4 5 6
CG
White
TB1
1 2
TB2
1 2
EMR-3000
H1C H2C
1
TB3
2
25 24 CIB
MP G2 GF11 EMR-3000 G1 M3 Ma M2 Mb M4 M5 Ba B2 B3
7 8
X1
1T3 1T2 1T1 B 1 SCR ASSY SCR ASSY 400 AMP Pole ASSY SCR ASSY B
9 10 11 12
F
B D E V3
H2 H1 H2 H1 X2 X1 X2 X1
68 TB2-1 TB2-2 Emergency Bypass MP G V31 C GND V2 V11 V1 SF2 1 AMP 12 NEU B MP4000 A V13 V2 V11 V13 BLK V2 GRY V11 YEL J2-1 J2-4 J2-7 MCB See MP Programming Notes SS2 3 TCB GND
Reset
TB8-5
TB8-6
MAX
Capacitors (Power Factor or Surge) Must not be Connected to the Load Side of the RVSS Starter. If Capacitors are Supplied in the Motor Terminal Box, They Must be Removed.
25
27
72
CR
TCB
CPU
*
TX
= = = =
Remote Device Internal Term. Blk(s) Term. Blk. for Customer Conn. TX Type Light
PT
67
65
63
BB
Mode 1
(White)
6 (Black) +
2 12 MP TRIP
Coil Controller
(Black)
VA D
+ M 5
(White)
+ B MX 5
(White)
(Black)
13 14
M F E
(Black) + VC VB
DC Coil 1
DC Coil 2
DC Coil 1
DC Coil 2
1 MA
1 BA
BX
SS2
MCB TB2-1
TRPX
M CUST ACN RCPT CUST 120V Test Power 51 TRPX 50 TCB TB1-9 TB1-1
15
C
16 17 18 19 20 21
Main Fuse
B A
VB VA PF1 3 AMP
H2 H1
69 BA
70 CIB 3 62
CPT 2K VA
ISW
ISW IS1 SF1 AMP 15 1 TB8-9 MX TB8-7 A1 SS2 TCB 4 A1 Main Coil SS2 TCB 2 * Start Bypass Coil Reset 2 55 BX CR * Stop 1A Stop TB3-11 Start 3
CR
GND ISW
L3
L2
L1
TRPX 1 G
MP 4160 VAC 60 HZ
4 1
GND 1
1
TB3-10
TCB
Figure 10.1-3. Induction Motor Reduced Voltage Solid-State Starter, Vacuum Contactor with EMR-3000 Motor Protection, Local and Remote Start-Stop Pushbuttons, and Local and Remote Red and Green Indicating Lights
TB4-1
TB4-3
12
CR
Continued at Right
CA08104001E
CHS Controls AB
September 2011
Sheet 10 019
10.1-17
i
NEMA 12/NEMA 3R 330 top 330 bottom 230 top 370 bottom 650 200 Arc Resistant 320 top 320 bottom 210 top 350 bottom 600 N/A
360 top 360 bottom 320 top 400 bottom 720 200
ii 1 2 3
Limited acceleration time and locked rotor current. Contact Eaton for details.
4 5 6 7 8
1200A rating is for NEMA 1 enclosure with vented covers. NEMA 3R/12 rating is 1000A.
9 10 11 12 13 14 15 16 17 18 19 20 21
8.5 kA 50 kA 200 MVA at 2400V 1750 hp 1750 hp 2000 hp 1500 kVA 1200 kVAR
8.5 kA 50 kA 285 MVA at 3300V 2250 hp 2250 hp 2500 hp 2000 kVA 1650 kVAR Arcing time Pickup voltage Dropout voltage Control voltages AC DC Control circuit burden Closing (AC)/(DC) Holding (AC)/(DC) Auxiliary contact rating Voltage (maximum) Continuous current Making capacity (AC) Making capacity (DC) Breaking capacity (AC) Breaking capacity (DC) Latch (when specied) Mechanical life Trip voltages (DC) Trip voltages (AC) Minimum trip voltage Trip burden 24 Vdc 125 Vdc 110/120 Vac Trip time Weight
8.5 kA 50 kA 400 MVA at 4600V 3000 hp 3000 hp 3500 hp 2500 kVA 2100 kVAR
8.5 kA 50 kA 570 MVA at 6600V 4500 hp 4500 hp 5500 hp 4000 kVA 3300 kVAR
CA08104001E
CHS Controls AB
September 2011
Sheet 10 020
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
CA08104001E
CHS Controls AB
September 2011
Sheet 10 021
10.1-19
i ii 1 2 3 4
Rating 15,000V 5000A 250A enclosed 250A open AC3make 2500 AC3break 2000 1500A 3750A 25 kA peak 250,000 operations 250,000 operations 36 kV (1 minute) 80 milliseconds 130 to 330 milliseconds (selectable) 95 lbs (43 kg) 12 milliseconds (3/4 cycle) or less 80% rated coil voltage 60% rated coil voltage 110/120/220/240V (50/60 Hz) 125V 2600 VA 80 VA 600V 10A 7200 VA 200 VA 720 VA 200 VA 250,000 operations 24/48/96V 110/220V (50/60 Hz) 80% rated coil voltage 1200 VA 400 VA 500 VA 95 lbs (43 kg)
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
CA08104001E
CHS Controls AB
September 2011
Sheet 10 022
i ii 1 2
3
Nominal Three-Phase MVA Class
6 7 8 9 10 11 12 13
Normal Frequency
kV rms
kV Crest
kA rms
4.16
250
4.76
1.24 19
60
29
8.9
50
30
3.85
36
36
97 58 132 78 132
4.16
350
4.76
1.19 19
60
41
8.9
50
30
4.0
49
49
7.2
500
8.25
1.25 36
95
33
15.5
60
30
6.6
41
41
111
14 15 16 17 18 19 20 21
For reclosing service, there is No Derating necessary for Eatons type VCP-W family of circuit breakers. R = 100%. Type VCP-W breaker can perform the O-C-O per ANSI C37.09; O-0.3s-CO-15s-CO per IEC 56; and some VCP-Ws have performed O-0.3s-CO-15s-CO-15s-CO-15s-CO; all with no derating. Contact Eaton for special reclosing requirements. V For three-phase and line-to-line faults, the symmetrical interrupting capability at an operating voltage, Vo = (Rated Short-Circuit Current) Vo But not to exceed KI. V (Rated Short-Circuit Current) Single line-to-ground fault capability at an operating voltage, Vo = 1.15 Vo But not to exceed KI. The above apply on predominately inductive or resistive three-phase circuits with normal-frequency line-to-line recovery voltage equal to the operating voltage. 4000A continuous rating is available for 5/15 kV. Contact Eaton for details. 3-cycle rating available. Tripping may be delayed beyond the rated permissible tripping delay at lower values of current in accordance with the following formula: (K Times Rated Short-Circuit current) 2 T (seconds) =Y Short-Circuit Current Through Breaker
The aggregate tripping delay on all operations within any 30-minute period must not exceed the time obtained from the above formula. Included for reference only. Asymmetrical interrupting capability = S times symmetrical interrupting capability, both at specied operating voltage. Non-standard breakers with high momentary rating available for special applications. Note: Contact Eaton for capacitor switching, low inductive switching, and cable charging ratings.
Table 10.1-11. VCP-W Breaker Stored Energy Mechanism Control Power Requirements
Rated Control Voltage 48 Vdc 125 Vdc 250 Vdc 120 Vac 240 Vac Spring Charge Motor Run Amperes 9.0 4.0 2.0 4.0 2.0 Time (Seconds) 6 6 6 6 6 Close or Trip Amperes 16 7 4 6 3 UV Trip mA (Maximum) Voltage Range Close 3856 100140 200280 104127 208254 Trip 2856 70140 140280 104127 208254 Indicating Light Amperes 0.35 0.35 0.35 0.35 0.35
200 80 40
CA08104001E
CHS Controls AB
4
Nominal Voltage Class
September 2011
Sheet 10 023
10.1-21
Contactor-Fuse Coordination
The AMGARD starter provides ensured coordination between its fuses, contactor, current transformers, protective relays, and the motor it is controlling. One of the most critical coordination issues is between the contactor and the starter fuses. The fuses must interrupt faults greater than the interrupting rating of the contactor. The AMPGARD 400A high interrupting contactor (SL400A-HI) has an 8-cycle dropout time factory setting as standard and will interrupt at 8500A. The maximum size fuse used with an SL400A-HI contactor is a 450-24R. By comparing the fuse curve with the contactor rating, it can be observed that for faults greater than 8500A, the fuse will open before the contactor. With faults less than 8500A, the contactor may clear the fault before the fuse blows, depending on the settings of the protective relays. Refer to Figure 10.1-4 for an illustration of AMPGARD coordination. Other vacuum contactors available today may have lower interrupting ratings than the AMPGARD Type SL vacuum contactors. Dropout times also vary, and may be as short as two cycles on other starter designs. Lower interrupting ratings and shorter dropout times can result in fault current levels where the contactor may be required to interrupt a fault greater than its rating. This can result in equipment failure. Refer to Figure 10.1-5 for an illustration of an improperly coordinated starter.
AMPGARD starters also ensure coordination between other starter components. The current transformers and protective relays are selected to work properly with each other, and to protect the motor. Protective relays like Eatons EMR-3000 provide optimal motor protection, while also rapidly opening the contactor during fault conditions. This rapid opening signal cannot open the contactor in less than its set dropout time, but it will take the motor off-line in the shortest possible time. This will help minimize
mechanical damage to the motor and may prevent the starter fuses from blowing by allowing the contactor to clear the fault (only if the fault is less than the contactor interrupting rating). AMPGARD starters use 400A standard interrupting contactors (SL400-SI) when the contactor is not required to coordinate with the starter main fuse. An example of this application is the run contactor of a reduced voltage starter.
i ii 1 2 3 4 5 6
Time
7
Contactor Dropout Contactor Interrupting Rating 24R Fuse Curve
8 9
Current
10 11 12 13
24R Fuse Curve
14 15
Time
Contactor Dropout
16 17
Fault Current Range where Contactor can Attempt to Open on a Fault Greater than its Rating
Current
18 19 20 21
CA08104001E
CHS Controls AB
September 2011
Sheet 10 024
i ii 1 2 3 4 5 6 7 8 9 10 11
Protection Considerations
Coordinated with the motors characteristics, the protective devices in the AMPGARD starter provide motor protection from overload to full system capacity faults. AMPGARD starters are supplied with an adjustable thermal overload relay as standard. Multi-function solid-state motor protection relays are a common option on AMPGARD starters. The EMR-3000 is typically provided when a multi-function relay is specied. The EMR-3000 provides many types of protection including overload, locked rotor, ground fault and phase loss/ phase unbalance. The EMR-3000 also provides start control logic to protect the motor against excessive starting. The relay may be applied to either across-the-line or reduced voltage starters. On reduced voltage starters, the EMR-3000 can control the transition from reduced to full voltage, offering the greatest protection for the motor and starter. An optional RTD module can be supplied for motors with built-in RTDs. The EMR-4000 can be supplied when voltage monitoring and protection are required. Eatons MD-3000 can be supplied when motor differential protection is required.
InsulGard relays are an available option on AMPGARD starters. The InsulGard provides early warning of increasing partial discharge levels in
the starting equipment, cables and motor. This early warning will help the user to better schedule maintenance and avoid unplanned downtime.
Ultimate Trip
MP-3000 Motor Protection Curve Programmed to Follow Specific Motor Damage Curve Providing Maximum Motor Utilization
Time In Seconds
Instantaneous Overcurrent
12 13 14
Contactor Dropout 24R Fuse
15 16 17 18 19 20 21
For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
Asymmetrical Offset Compensation Contactor Interrupting Capacity
Figure 10.1-6. Full Range Coordinated Protection Between Current Limiting Type CLS Fuses, Vacuum Contactor and Motor Protection Relay
CA08104001E
CHS Controls AB
September 2011
Sheet 10 025
10.1-23
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Specic motor acceleration time and locked rotor current must be reviewed to ensure 24R fuse has sufcient capacity for start cycle.
CA08104001E
CHS Controls AB
September 2011
Sheet 10 026
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Layout Dimensions
Full Voltage Squirrel Cage Starters Catalog S210 Non-Reversing Catalog S310 Reversing
Equipment Details Mounted in the Medium Voltage Section
Specications
Table 10.1-13. Starter Selection InformationDimensions in Inches (mm)
Contactor Ampere Rating (Enclosed) Starter Interrupting Rating (kVA) Height Width Depth Additional Starter Spaces Equipment Arrangement Number Horsepower Volts Dimensions Weight Lbs (kg)
22002400V Non-Reversing
700/800 1500/1750 3000 700/800 1500/1750 3000 1250/1500 2500/3000 5500 1250/1500 2500/3000 5500 2000/2250 4000/4500 8000 2300 2300 2300 2300 2300 2300 4600 4600 4600 4600 4600 4600 400 400 720 400 400 720 400 400 720 400 400 720 200,000 200,000 200,000 200,000 200,000 200,000 400,000 400,000 400,000 400,000 400,000 400,000 570,000 570,000 570,000 570,000 570,000 570,000 1 1 2 3 3 4 1 1 2 3 3 4 1 1 2 3 3 4 80 (2032) 36 (914) 30 (762) 1 80 (2032) 36 (914) 30 (762) 1 80 (2032) 36 (914) 30 (762) 0 80 (2032) 36 (914) 30 (762) 0 80 (2032) 36 (914) 30 (762) 0 80 (2032) 36 (914) 30 (762) 0 80 (2032) 36 (914) 30 (762) 1 80 (2032) 36 (914) 30 (762) 1 80 (2032) 36 (914) 30 (762) 0 80 (2032) 36 (914) 30 (762) 0 80 (2032) 36 (914) 30 (762) 0 80 (2032) 36 (914) 30 (762) 0 80 (2032) 36 (914) 30 (762) 1 80 (2032) 36 (914) 30 (762) 1 80 (2032) 36 (914) 30 (762) 0 80 (2032) 36 (914) 30 (762) 0 80 (2032) 36 (914) 30 (762) 0 80 (2032) 36 (914) 30 (762) 0 1350 (613) 1350 (613) 1700 (772) 1800 (817) 1800 (817) 2400 (1090) 1350 (613) 1350 (613) 1700 (772) 1800 (817) 1800 (817) 2400 (1090) 1500 (681) 1500 (681) 1800 (817) 1800 (817) 1800 (817) 2400 (1090)
Three incoming line connectors Drawout three-pole gang-operated line isolating switch assembly with isolating shutter, external operating handle interlocked to prevent opening the medium voltage compartment door until the isolating switch is open and grounded Vertically mounted current limiting power fuses with pop-up blown fuse indicators One magnetic three-pole vacuum contactor with DC operating coils and mechanical interlock to prevent opening the isolating switch when contactor is closed One control power transformer (115V secondary) Two CPT primary current limiting fuses Four electrical interlocks (2NO, 2NC) Three current transformers
22002400V Reversing
40004800V Non-Reversing
40004800V Reversing
6600V Non-Reversing
6600 400 6600 400 6600 720 6600 400 6600 400 6600 720
6600V Reversing
2000/2250 4000/4500 8000
Reversing Starter
One additional magnetic three-pole vacuum contactor (duplicate of above), both contactors are mechanically and electrically interlocked.
Horsepower based on NEMA standard design B motor at 1800 rpm. When horizontal bus is added, height becomes 92.00 inches (2336.8 mm). At higher hp rating, maximum acceleration time is 3.5 seconds. At higher hp rating, maximum acceleration time is 6 seconds. Maximum current for two starters in a single structure is 720A. May be applied on 6900V systems where maximum voltage does not exceed 7200V.
Control panel with: One EMR-3000 motor protection relay One interposing control relay Set of control circuit terminal blocks One control circuit secondary fuse One run-test circuit
M Arrangement 1 Arrangement 2
15 16 17 18 19 20 21
RVS RVS
Arrangement 3
Arrangement 4
Dimensions for estimating purposes only. For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
CA08104001E
CHS Controls AB
September 2011
Sheet 10 027
10.1-25
13.50 (343)
1.25 (32)
i
30.00 (762) 5.50 (140)
Note T
9.32 (237)
ii 1 2 3
Control
2.00 (51)
Main Bus Note C1 3.00 (76) 6.00 (152) 36.00 (914) Top View 36.00 (914) 4.50 (114) Note B 13.75 (349)
Control
61.00 (1549)
Gnd 1.45
2.50 (64)
4 5 6 7
36.00 (914)
Front View
Detail A Load Terms T1 T3
2.00 (51)
4.50 (114)
4.38 (111)
4.38 (111)
1200A Main Bus
For seismic installations, mount a minimum of 6.00 inches (152.4 mm) from wall.
8 9 10
Figure 10.1-8. Arrangement 1 Detail (Full Voltage 400A)See Table 10.1-20 on Page 10.1-34 for Notes
1.25 (32)
1.50 (38)
3.50 (89)
a Ph c
13.50 (343)
Note E
11
30.00 (762) 5.50 (140)
Main Bus
(237)
12 13 14 15
5.50 (140)
Main Bus
6.80 (173)
80.00 (2032)
Load Term Detail A Note L
29.00 (737) 5.81 (148) 1.45 (37) 22.85 (580) 30.00 (762)
Side View
7.39 (188)
16 17 18 19
2.00 (51)
4.50 (114)
36.00 (914)
Front View
Detail A Load Term T3
4.3 (109)
4.3 (109)
800A Starter
For seismic installations, mount a minimum of 6.00 inches (152.4 mm) from wall.
20 21
Figure 10.1-9. Arrangement 2 Detail (Full Voltage 800A)See Table 10.1-20 on Page 10.1-34 for Notes
CA08104001E For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
CHS Controls AB
September 2011
Sheet 10 028
i ii
1 2 3.50 (88.9)
PH PH PH Main A B C Bus
30.00 (762.0)
1 2
0.90 (22.9)
3 4 5 6 7 8 9 10
UNIT 1D 1 24.00 (609.6) UNIT 2D 2
24.00 (609.6) 4.50 (114.3) 19.00 2.00 (482.6) (50.8) 1.00 (25.4)
Note F
22.00 (558.8)
30.00 (762.0)
Note A
Structure #1
Note E
11 12 13 14 15
24.00 (609.6) 36.00 (914.4) 60.00 (1524.0) Shipping Section 1 1500 Lbs Base Plan View 56.43 (1433.3)
1.85 (47.0)
6.00 (152.4) 1.18 (30.0) 36.00 (914.4) Top View 36.00 (914.4)
59.00 (1498.6)
2.00 (50.8)
13.75 (349.3)
22.85 (580.4)
Note E
9.25 (235.0)
Note A
16 17 18 19 20 21
Load Term T1 T2 T3
2.50 (63.5)
28.00 2.31 (58.7) 1.00 21.67 (711.3) 30.00 (762.0) (25.4) (550.5) 4.50 (114.3)
Note G
4.38 (111.3)
2.00 (50.8)
27.00 (685.9)
Detail A Structure #2
Figure 10.1-10. Arrangement 1 Detail (Full Voltage 15 kV)See Table 10.1-20 on Page 10.1-34 for Notes
CA08104001E
CHS Controls AB
September 2011
Sheet 10 029
10.1-27
Volts
Primary Reactor, Reduced Voltage Starters Catalog S510 Non-Reversing Catalog S710 Reversing
Mounted in the Medium Voltage Section
Specications
Table 10.1-15. Starter Selection InformationDimensions in Inches (mm)
Horsepower Dimensions Height Width Depth Weight Lbs (kg)
i ii 1
Three incoming line connectors One drawout three-pole gangoperated line isolation switch assembly with isolating shutter, external operating handle interlocked to prevent opening the medium voltage compartment door until the isolating switch is open and grounded One vertically mounted current limiting power fuse with pop-up blown fuse indicators One magnetic three-pole vacuum contactor with DC operating coils and mechanical interlock to prevent opening the isolation switch when the contactor is closed One control power transformer (115V secondary) Two CPT primary current limiting fuses Four electrical interlocks (2NO, 2NC)
22002400V Non-Reversing
700/800 1500/1750 3000 700/800 1500/1750 3000 1250/1500 2500/3000 5500 1250/1500 2500/3000 5500 2000/2250 4000/4500 8000 2300 2300 2300 2300 2300 2300 4600 4600 4600 4600 4600 4600 6600 6600 6600 6600 6600 6600 400 400 720 400 400 720 400 400 720 400 400 720 400 400 720 400 400 720 200,000 200,000 200,000 200,000 200,000 200,000 400,000 400,000 400,000 400,000 400,000 400,000 570,000 570,000 570,000 570,000 570,000 570,000 1 1 2 3 3 4 1 1 2 3 3 4 1 1 2 3 3 4 80 (2032) 80 (2032) 80 (2032) 80 (2032) 80 (2032) 80 (2032) 80 (2032) 80 (2032) 80 (2032) 80 (2032) 80 (2032) 80 (2032) 80 (2032) 80 (2032) 80 (2032) 80 (2032) 80 (2032) 80 (2032) 72 (1829) 72 (1829) 72 (1829) 72 (1829) 72 (1829) 72 (1829) 72 (1829) 72 (1829) 72 (1829) 72 (1829) 72 (1829) 72 (1829) 72 (1829) 72 (1829) 72 (1829) 72 (1829) 72 (1829) 72 (1829) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 2800 (1271) 2800 (1271) 4000 (1816) 3250 (1476) 3250 (1476) 4650 (2111) 2800 (1271) 2800 (1271) 4000 (1816) 3250 (1476) 3250 (1476) 4650 (2111) 3300 (1498) 3300 (1498) 4650 (2111) 3250 (1476) 3250 (1476) 4650 (2111)
2 3 4 5 6 7 8 9 10 11
22002400V Reversing
40004800V Non-Reversing
40004800V Reversing
6600V Non-Reversing
Reversing Starter
One additional magnetic contactor (duplicate of above), both contactors are mechanically and electrically interlocked.
6600V Reversing
2000/2250 4000/4500 8000
One control panel with: One EMR-3000 motor protection relay Two interposing relays One set of control circuit terminal blocks One control circuit secondary fuse One run-test circuit
Horsepower based on NEMA standard design B motor at 1800 rpm. When horizontal bus is added, height becomes 92.00 inches (2336.8 mm). At higher hp rating maximum acceleration time is 3.5 seconds. At higher hp rating maximum acceleration time is 6 seconds.
Run Contactor
Run Contactor
Run Contactor
Run Contactor
12 13 14 15 16 17 18 19 20
M
Reactor Reactor Reversing Reactor Contactor Arrangement 3
M
Reversing Reactor Contactor Arrangement 4
M
Arrangement 1 Arrangement 2
Starting Characteristics
Table 10.1-14. Type 502 Reactor Starting Characteristics
Starter Type % % % % Motor Motor Line Torque Voltage Current Current 80 65 50 80 65 50 64 42 25
Dimensions for estimating purposes only. CA08104001E For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
21
CHS Controls AB
September 2011
Sheet 10 030
i ii 1 2 3 4 5 6
Front View 3.50 (89)
1.25 (32) 9.32 (237) 2.00 (51) 30.00 (762) 5.50 (140) 5.50 (140)
Note L1
12.00 (305) 2.88 2.00 (73) (51) 1.70 (43) 1.00 (25) 80.00 (2032)
Load Term
4.38 (111) 4.38 (111) 2.92 (74)
Control
61.00 (1549)
61.00 (1549)
13.75 ( ) (349)
22.00 (559)
5.81 (148)
30.00 (762)
2.50 (64)
7 8
Side View
For seismic installations, mount a minimum of 6.00 inches (152.4 mm) from wall.
9 10 11 12 13 14 15 16 17 18 19 20 21
Figure 10.1-12. Arrangement 1 Detail (Reduced Voltage, 400A)See Table 10.1-20 on Page 10.1-34 for Notes
CA08104001E
CHS Controls AB
September 2011
Sheet 10 031
10.1-29
Reduced Voltage Autotransformer Starters Catalog S610 Non-Reversing Catalog S810 Reversing
Mounted in the Medium Voltage Section
Starting Characteristics
Table 10.1-16. Type 602 Auto-transformer Starting Characteristics
Starter Type % % % % Motor Motor Line Torque Voltage Current Current 80 65 50 67 45 28 64 42 25
i ii 1 2 3
Number of Structures Weight Lbs (kg)
Three incoming line connectors One drawout three-pole gangoperated line isolation switch assembly with isolating shutter, external operating handle interlocked to prevent opening the medium voltage compartment door until the isolating switch is open and grounded Three vertically mounted current limiting power fuses with pop-up blown fuse indicators One magnetic three-pole vacuum contactor with DC operating coils and mechanical interlock to prevent opening the isolation switch when the contactor is closed One control power transformer (115V secondary) Two CPT primary current limiting fuses Four electrical interlocks (2NO, 2NC)
Specications
Table 10.1-17. Starter Selection InformationDimensions in Inches (mm)
Equipment Arrangement Number Horsepower Volts Contactor Ampere Rating (Enclosed)
4 5
22002400V Non-Reversing
700/800 1500/1750 3000 700/800 1500/1750 3000 1250/1500 2500/3000 5500 1250/1500 2500/3000 5500 2000/2250 4000/4500 8000 2300 400 2300 400 2300 720 2300 400 2300 400 2300 720 4600 400 4600 400 4600 720 4600 400 4600 400 4600 720 6600 400 6600 400 6600 720 6600 400 6600 400 6600 720 200,000 200,000 200,000 200,000 200,000 200,000 400,000 400,000 400,000 400,000 400,000 400,000 570,000 570,000 570,000 570,000 570,000 570,000 1 1 2 3 3 4 1 1 2 3 3 4 1 1 2 3 3 4 80 (2032) 72 (1829) 30 (762) 2 80 (2032) 72 (1829) 30 (762) 2 80 (2032) 108 (2743) 30 (762) 3 80 (2032) 72 (1829) 30 (762) 2 80 (2032) 72 (1829) 30 (762) 2 80 (2032) 108 (2743) 30 (762) 3 80 (2032) 72 (1829) 30 (762) 2 80 (2032) 72 (1829) 30 (762) 2 80 (2032) 108 (2743) 30 (762) 3 80 (2032) 72 (1829) 30 (762) 2 80 (2032) 72 (1829) 30 (762) 2 80 (2032) 108 (2743) 30 (762) 3 80 (2032) 72 (1829) 30 (762) 2 80 (2032) 72 (1829) 30 (762) 2 80 (2032) 108 (2743) 30 (762) 3 80 (2032) 72 (1829) 30 (762) 3 80 (2032) 72 (1829) 30 (762) 3 80 (2032) 108 (2743) 30 (762) 4 3100 (1407) 3100 (1407) 4800 (2179) 3650 (1657) 3650 (1657) 5650 (2565) 3100 (1407) 3100 (1407) 4800 (2179) 3650 (1657) 3650 (1657) 5650 (2565) 3100 (1407) 3100 (1407) 4800 (2179) 3650 (1657) 3650 (1657) 5650 (2565)
6 7 8 9 10 11 12 13 14 15
22002400V Reversing
Reversing Starter
One additional magnetic contactor (duplicate of above), both contactors are mechanically and electrically interlocked.
40004800V Non-Reversing
40004800V Reversing
One control panel with: One EMR-3000 motor protection relay Three interposing relays One set of control circuit terminal blocks One control circuit secondary fuse One run-test circuit One magnetic three-pole vacuum run contactor with DC operating coil and electrically and mechanically interlocked with the starting contactor One magnetic two-pole vacuum start contactor with DC operating coil and electrical and mechanical interlocks Three current transformers One medium-duty starting autotransformer with 506580% taps Three distribution class lightning arresters for high voltage stress protection on the transformer zero tap
6600V Non-Reversing
6600V Reversing
2000/2250 4000/4500 8000
Horsepower based on NEMA standard design B motor at 1800 rpm. When horizontal bus is added, height becomes 92.00 inches (2336.8 mm). At higher hp rating, maximum acceleration time is 3.5 seconds. At higher hp rating, maximum acceleration time is 6 seconds.
M
Rev
Short
16
Auto Transformer
Run
17 18 19 20
Arrangement 1
Arrangement 3
Arrangement 4
Dimensions for estimating purposes only. CA08104001E For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
21
CHS Controls AB
September 2011
Sheet 10 032
i ii 1 2 3 4
Full Voltage Synchronous Starters Brush Type Mark V Controller Catalog S241 Non-Reversing Catalog S341 Reversing
Mounted in the Medium Voltage Section
6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Three incoming line connectors One drawout three-pole gangoperated line isolation switch assembly with isolating shutter. External operating handle interlocked to prevent opening the medium voltage compartment door until the isolating switch is open and grounded Three vertically mounted current limiting power fuses with pop-up blown fuse indicators One magnetic three-pole vacuum contactor with DC operating coils and mechanical interlock to prevent opening the isolation switch when the contactor is closed One control power transformer (115V secondary) Two CPT primary current limiting fuses Four electrical interlocks (2NO, 2NC) Three current transformers
Mounted on inside compartment: One step-down exciter transformer three-phase One SCR power supply panel One synchronous control board MOV surge protection One three-phase CT
One ELC controller One set of control circuit blocks Three primary fuses Three secondary fuses
22002400V Non-Reversing
900/1000 2300 400 700/800 1500/1750 1750/2000 2300 400 3000 3500 2300 720 200,000 1 200,000 1 200,000 2 200,000 3 200,000 3 200,000 4 400,000 1 400,000 1 400,000 2 400,000 3 400,000 3 400,000 4 570,000 1 570,000 1 570,000 2 570,000 3 570,000 3 570,000 4 80 (2032) 36 (914) 30 (762) 1500 (681) 80 (2032) 36 (914) 30 (762) 1500 (681) 80 (2032) 72 (1829) 30 (762) 2350 (1067) 80 (2032) 72 (1829) 30 (762) 2100 (953) 80 (2032) 72 (1829) 30 (762) 2100 (953) 80 (2032) 72 (1829) 30 (762) 2900 (1317) 80 (2032) 36 (914) 30 (762) 1550 (704) 80 (2032) 36 (914) 30 (762) 1550 (704) 80 (2032) 72 (1829) 30 (762) 2350 (1067) 80 (2032) 72 (1829) 30 (762) 2100 (953) 80 (2032) 72 (1829) 30 (762) 2100 (953) 80 (2032) 72 (1829) 30 (762) 2900 (1317) 80 (2032) 36 (914) 30 (762) 1700 (772) 80 (2032) 36 (914) 30 (762) 1700 (772) 80 (2032) 72 (1829) 30 (762) 2500 (1135) 80 (2032) 72 (1829) 30 (762) 2100 (953) 80 (2032) 72 (1829) 30 (762) 2100 (953) 80 (2032) 72 (1829) 30 (762) 2900 (1317)
22002400V Reversing
900/1000 2300 400 700/800 1500/1750 1750/2000 2300 400 3000 3500 2300 720
40004800V Non-Reversing
1250/1500 1500/1750 4600 400 2500/3000 3000/3500 4600 400 5500 6000 4600 720
40004800V Reversing
1250/1500 1500/1750 4600 400 2500/3000 3000/3500 4600 400 5500 6000 4600 720
Reversing Starter
One additional magnetic contactor (duplicate of above), both contactors are mechanically and electrically interlocked.
6600V Non-Reversing
2000/2250 2500/2750 7200 400 4000/4500 5000/5500 7200 400 8000 10,000 7200 720
6600V Reversing
2000/2250 2500/2750 7200 400 4000/4500 5000/5500 7200 400 8000 10,000 7200 720
One control panel with: One EMR-3000 motor protection relay One interposing relay One set of control circuit terminal blocks One control circuit secondary fuse One run-test circuit
Horsepower based on NEMA standard design B motor at 1800 rpm. When horizontal bus is added, height becomes 92.00 inches (2336.8 mm). Starting and discharge resistors are mounted on top, add 13.00 inches (330.2 mm) to the height. At higher hp rating maximum acceleration time is 3.5 seconds. At higher hp rating maximum acceleration time is 6 seconds.
Field Panel
Field Panel M
Field Panel M
Field Panel
Rev
Rev
Mounted on door: One AC line ammeter, panel type One DC eld ammeter, panel type One exciter eld potentiometer One set of externally ventilated heatsinks One graphic display
Arrangement 1
Arrangement 2
Arrangement 3
Arrangement 4
When the eld panel requirement exceeds 88A at 125 Vdc or 44A at 250 Vdc, an auxiliary structure 36.00 inches (914.4 mm) wide is required. Mounting location of exciter transformer when eld panel requirement exceeds 88A at 125 Vdc or 44A at 250 Vdc. Otherwise compartment is blank.
Dimensions for estimating purposes only. For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
CA08104001E
CHS Controls AB
September 2011
Sheet 10 033
10.1-31
25.0 (635) Starting & Discharge res. 3.50 (90) 1000 Amp p - 3.00" X 1/Ph / Ph Ph a b DC Field Conn's MTD on rh Side c 12.25 (311) Main Bus 12.00 (305) 3.00 (76) 2.00 (51) 2.00 (51) Main Bus Note G 1.18 (30) 80.00 (2032) Low Voltage Control Load Term Detail A Note L 3.00 (76) 36.00 (914) Top View 36.00 (914) 4.50 (114) Note A Note E 7.39 (188) 1.45 (37) 21.00 (533) 2.50 (64) 1.00 (25) 6.00 (152) Note G 27.00 (686)
Floor Plan Note D
i
1.50 (38) 13.50 (343) Note E 1.25 (32)
ii
30.00 (762) 5.50 (140) 5.50 6.80 (173)
1 2 3 4 5
4.13 (105)
2.31 (59)
Gnd Bus
6 7 8 9 10
2.00 (51)
4.50 (114)
Detail A Load Term T1 T2 T3 4.38 (111) 4.38 (111) Synchronous Starter 1000A Main Bus
For seismic installations, mount a minimum of 6.00 inches (152.4 mm) from wall.
11 12 13 14 15 16 17 18 19 20 21
Figure 10.1-15. Arrangement 1 Detail (400A, Synchronous)See Table 10.1-20 on Page 10.1-34 for Notes
CA08104001E
CHS Controls AB
September 2011
Sheet 10 034
i ii 1 2
Equipment Details
Mounted in the Medium Voltage Sections
3 4 5
6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Dimensions for estimating purposes only.
Volts
Three incoming line connectors Drawout three-pole gang-operated line isolating switch assembly with isolating shutter, external operating handle interlocked to prevent opening the medium voltage compartment door until the isolating switch is open and grounded Vertically mounted current limiting power fuses with pop-up blown fuse indicators One magnetic three-pole vacuum contactor with DC operating coils and mechanical interlock to prevent opening the isolating switch when contactor is closed One control power transformer (115V secondary) Two CPT primary current limiting fuses Four electrical interlocks (2NO, 2NC) Three current transformers Withdrawable SCR truck with fully rated vacuum bypass contactor
Control panel with: One EMR-3000 motor protection relay One interposing control relay Set of control circuit terminal blocks One control circuit secondary fuse One run-test circuit
Horsepower based on NEMA standard design B motor at 1800 rpm. Based on maximum acceleration time of 30 seconds. Includes horizontal bus. Does not include incoming line provisions.
CA08104001E
CHS Controls AB
September 2011
Sheet 10 035
10.1-33
1.25 (32.0)
i ii
12.00 (305.0)
Load Term Detail A Note: L Low Voltage Control 7.39 Ground (188.0) Bus 1.45 (36.8) Low Voltage Control
3.50 (89.0)
30.00 (762.0)
1 2 3 4
1.36 (345.4) 1.18 (30.0) 80.00 (203.2) 61.00 (155.0) 2.00 (51.0)
5.81 (148.0)
3.00 Note: C1 (76.2) 6.00 (152.4) 36.00 (914.4) Top View 36.00 (914.4) 4.10 (104.1) 4.50 (114.3)
62.00 (1575.0)
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
10.00 (254.0)
Note: A Note: E 1.00 (25.4) 6.00 (152.4) Note: G 28.00 (711.2) 30.00 (762.0)
Ground Bus 1.45 (36.8) 36.00 (914.4) 22.85 (580.4) 30.00 (762.0) For seismic installations, mount a minimum of 6.00 inches (152.4 mm) from wall. Side View
2.50 (64.0)
1.00 (25.4)
2.00 (51.0)
Floor Plan
Figure 10.1-16. Arrangement Detail (400A Solid-State Reduced Voltage)See Table 10.1-20 on Page 10.1-34 for Notes
CA08104001E
CHS Controls AB
September 2011
Sheet 10 036
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Cable Notes
Arrangement Notes
HV conduit space, load cables for two-high starters. Cables for lower starter enter in front half of conduit space, and cables for upper starter enter in rear half. HV conduit space, line and load cables for bottom entry stand-alone starters. Line cables should enter in rear half of conduit space, and load cables should enter in front half of conduit space. LV conduit space for two-high starters with bottom entry control conduit. Control wiring for upper starter should enter in left half of conduit space, and lower starter control wiring should enter in right half of conduit space. LV conduit space for two-high starters with top entry control conduit. Control wiring for upper starter should enter in right half of conduit space, and lower starter control wiring should enter in left half of conduit space. 90 door swing requires 12.00 inches (304.8 mm) for 12.00-inch (304.8 mm) wide structure, 18.00 inches (457.2 mm) for 18.00-inch (457.2 mm) wide structure, 24.00 inches (609.6 mm) for 24.00-inch (609.6 mm) wide structure, 36.00 inches (914.4 mm) for 36.00-inch (914.4 mm) wide structure and 40.00 inches (1016.0 mm) for 40.00-inch (1016.0 mm) wide structure. HV conduit space, load. HV conduit space, line only. HV conduit space, line only. Line cables to enter in rear half of conduit space only. LV conduit space only. Load terminations located on rear wall of starter mounted on a load panel. Terminations are arranged horizontally from left to right. T1, T2, T3 left to right at 4.38-inch (111.3 mm) centers. Load terminations located on rear wall of reduced voltage enclosure mounted on a load panel. Terminations are arranged horizontally from left to right. T1, T2, T3 left to right at 4.38-inch (111.3 mm) centers. HV conduit space, load cables for two-high starters. Cables for lower starter enter in rear half of conduit space, and cables for upper starter enter in front half. Steel bottom with removable lead plates. Tolerances 0.0 inches +0.25 inches per structure. Conduits to extend a maximum of 2.00 inches (50.8 mm) into structure.
C1 D
E F F1 G L L1 T X Y Z
CA08104001E
CHS Controls AB
September 2011
Sheet 10 037
10.1-35
i ii 1 2 3 4 5
30.00 28.00 (762.0) (711.2) 1.00 (25.4)
3.00 (76.2)
PH PH PH MAIN A B C BUS
12.00 (304.8)
3.50 (88.9)
36.0 (914.4) 2.00 (50.8) 80.00 (2,032.0) Unit 1B Unit 2B 59.00 (1,498.6) Line Term 19.00 (482.6) 34.00 (863.6) Note F 7.75 (196.9) 1.45 (36.8) 1.00 (25.4) 24.00 (609.6) 27.00 (685.8) Floor Plan Note D 2 24.00 (609.6) 60.00 (1,524) Shipping Section 1 - 1750 Lbs 9.32 (236.7) PH PH PH MAIN A B C BUS 12.00 (304.8) 2.00 (50.8) 3.50 (88.9) MAIN BUS 24.00 (609.6) Top View 6.70 (170.2) 2.00 (50.8) 5.50 (139.7) 5.50 (139.7) 30.00 (762.0) 22.85 (580.4) 30.00 (762.0) Side View Structure 1 1.50 (38.1) 21.00 (533.4) 1.25 (31.8) 4.50 (114.3)
6 7 8 9 10 11 12 13 14
Unit 2C
4.50 (114.3)
Unit 2D
24.00 (609.6) 4.50 (114.3) 22.00 (558.8) 28.00 (711.2) 1.00 (25.4) 15.00 (381.0) 30.00 (762.0)
30.00 (762.0)
0.90 (22.9)
19.00 (482.6)
15 16 17 18 19 20 21
GND BUS
1.00 (25.4)
4.50 (114.3)
Figure 10.1-17. Incoming LBS, Bottom Entry up to 450A Fuse, Unfused with Metering Section
CA08104001E
CHS Controls AB
September 2011
Sheet 10 038
i ii 1 2 3 4
1.50 (38.1) PH PH PH MAIN A B C BUS 3.50 (88.9) 12.00 (304.8) 9.32 (236.7)
4.50 (114.3)
36.00 (914.4)
Unit 2B
Unit 3B
5
Unit 3C
6
Unit 1D
4.50 (114.3)
7 8 9 10 11 12 13 14 15 16 17 18 19 20
Unit 2D
Unit 3D 2 24.00 (609.6) 3 PH PH PH MAIN A B C BUS 12.00 (304.8) 3.50 (88.9) 1.36 (34.5) 1.18 (30.0) 80.00 (2,032.0) 59.00 (1,498.6) 0.90 (22.9) Line Term 7.75 (196.9) GND 1.45 BUS (36.8) 24.00 (609.6) 2.00 (50.8) 19.00 (482.6) 3.00 NOTE C1 (76.2) 2.00 (50.8) 2.00 (50.8)
5.50 (139.7) 30.00 (762.0)
36.00 (914.4)
5.50 (139.7)
34.00 Note F
22.85 (580.4) 30.00 (762.0) Side View Structure 2 1.50 (38.1) 12.00 (304.8) 3.50 (88.9) 9.32 (236.7) 2.00 (50.8)
4.50 (114.3)
PH PH PH MAIN A B C BUS
30.00 (762.0)
2.00 (50.8) MAIN BUS 24.00 (609.6) Top View 80.00 (2,032.0) 2.00 (50.8) 24.00 (609.6) 4.50 (114.3) 22.00 (558.8)
5.50 (139.7)
1.00 (25.4)
15.00 (381.0)
4.50 (114.3)
Figure 10.1-18. Incoming LBS, Bottom Entry, 600E/750E/1100E/1350E Fused with Metering Section
21
For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
CA08104001E
CHS Controls AB
September 2011
Sheet 10 039
10.1-37
i ii 1
10.25 (260.4) 5.27 1.50 (133.9) (38.1)
2
1.25 (31.8)
5.50 (139.7)
3
5.50 (139.7) 30.00 (762.0)
PH PH PH MAIN A B C BUS
24.50 (622.3)
4 5 6 7
1.45 (36.8)
36.00 (914.4)
Top View
Unit 1B
1.45 (36.8) 2.00 (50.8) GND BUS 22.85 (580.4) 30.00 (762.0) Side View 36.00 (914.4) Shipping Section 1 - 1200 lbs.
4.50 (114.3)
9.00 (228.6)
36.00 (914.4)
8 9
28.00 (711.2) 1.00 (25.4)
30.00 (762.0)
Unit 1D
19.50 (495.3)
10 11
4.50 (114.3)
12 13 14
15 16 17 18 19 20 21
CA08104001E For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
CHS Controls AB
September 2011
Sheet 10 040
i ii 1 2 3 4 5 6 7 8
Notes: For non-seismic installations, mount a minimum of 3.00 inches (76.2 mm) from wall.
Flap Assy.
For seismic installations, mount a minimum of 6.00 inches (152.4 mm) from wall.
Side Covers
80.00 (2032.0) Continuation of Bus from Adjacent Structure Unit 2B 52.25 (1327.2) 30.51 (775.0) Cable Chimney through Plenum 17.75 (450.9) 123.62 (3139.9) 4.00 (101.6) 51.00 50.00 0.75 (1295.4) (1270.0) (19.1) 5.50 TYP (139.7) 52.25 5.50 (1327.2) (139.7) Bolting Flange
16.00 (406.4)
PH PH PH A B C
Note F
Rear Supports Protrude 1.00" from Rear Please Consider Dimension Before Locating Equipment
Front
Rear Sprt.
0.90 (22.9)
9 10 11 12 13 14
Low Voltage Control Low Voltage Conduit
62.00 (1574.8)
25.23 (640.8)
42.85 (1078.2) 50.00 (1270.0) 51.00 (1295.4) Side View Structure 1 52.25 (1327.2)
19.82 (503.4)
Note X Note 28.00 30.00 F 10.00 (711.2)(762.0) 1.00 (254.0) (25.4) Note A 15.00 (381.0) 4.50 (114.3)
6.98 (177.3)
20.06 (509.5)
1.13 (28.7)
13.60 (345.4) Note B 2.00 (50.8) MAIN BUS Note C1 5.38 (136.7) 36.00 (914.4) Top View
8.68 (220.5) 1.70 (43.2) 1.85 (47.0) PH PH PH A B C Load Term Detail A Note L MAIN BUS 123.62 (3139.9) 3.50 (88.9) 27.39 (695.7) Rear Sprt. Load Term Detail A Note L 1.45 (36.8) 27.39 (695.7) 21.00 (533.4) 80.00 (2032.0) 61.00 (1549.4) 1.24 (31.5)
6.70 (170.2)
Rear Supports Protrude 1.00" from Rear Please Consider Dimension Before Locating Equipment
15 16 17 18 19 20 21
5.81 (147.6) 62.00 (1574.8) 1.85 (47.0)
36.00 (914.4) 22.09 (561.1) 50.00 51.00 (1270.0) (1295.4) At Floor Level
22.00 (558.8)
4.50 (114.3)
Note B Note A
GND BUS
13.75 (349.3)
2.31 (58.7)
Note X
4.50 (114.3)
Rear Supports Protrude 1.00" from Rear Please Consider Dimension Before Locating Equipment
Figure 10.1-20. 50 kA Arc-Resistant, 24.00-Inch (609.6 mm) Incoming Cable Section and Two-High 400A Starter Section
For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
CA08104001E
CHS Controls AB
September 2011
Sheet 10 041
10.1-39
i ii 1 2
90.00 (2286.0)
6.50 (165.1)
Disc SW (if reqd.) 17.00 (431.8) High Voltage Access Removable Barrier
6.50 (165.1)
3
Main Breaker Compartment 3.00 (76.2) GND BUS 24.62 (625.3)
Customer 29.55 Terminal (750.6) Block Low Voltage Wireway GND BUS 24.62 (625.3) 60.00 (1524.0) 3.00 (76.2)
4 5 6 7
5.50 (139.7) 30.00 (762.0) 5.50 (139.7) 6.70 (170.2)
Unit 1B
60.00 (1524.0)
Unit 1C
Unit 2C Unit 4B
52
26.00 (660.4) 6.00 (152.4) 1.63 (41.4) Note G PH C PH B PH A MAIN BUS 11.88 (301.8) 14.00 (355.6) HV Conduit Area 22.00 (558.8)
36.00 (914.4)
1.50 (38.1)
13.50 (342.9)
1.25 (1.8)
1.50 (38.1) Unit 1F 1 26.00 (660.4) Unit 2F 2 36.00 (914.4) 3 Unit 4D 4 36.00 (914.4) 4.00 (101.6) 102.00 (2590.8) Shipping Section 1 7900 lbs. 6.25 (158.8)
9.32 (236.7) 3.00 (76.2) 31.12 (790.4) 4.63 (117.6) 2.00 (50.8) Note C1 3.00 (76.2) 1.18 (30.0)
Note T
3.00 (76.2)
8 9 10
11.00 (279.4)
Top View
PH PH PH MAIN A B C BUS Low Voltage Control 1.85 (47.0) Load Term Detail A Note L
12.00 (304.8)
11
80.00 (2032.0)
36.00 (914.4) 26.00 (660.4) 5.00 (127.0) 62.00 (1574.8) 5.81 (147.6) 1.85 (47.0)
12 13 14 15 16 17
61.00 (1549.4) Load Term Detail A Note L 7.39 (187.7) 21.00 (533.4)
40.00 (1016.0) 60.00 (1,524) 0.56 dia. (TYP) 6.00 (152.4) 4.75 (120.6) 3.00 (76.2) 1.25 (31.8) 0.00 (0.00) 0.00 (0.00) 3.00 (76.2) 5.00 (127.0) 2.75 (69.9) 11.25 (285.8)
5.81 (147.6)
1.45 (36.8)
36.00 (914.4) 4.50 (114.3) Note B 9.25 (235.0) 2.31 (58.7) 1.00 (25.4) 21.67 (550.4) Note A
1.00 (25.4)
Floor Plan
18 19 20 21
2.00 (50.8)
2.50 (63.5)
4.50 (114.3)
Figure 10.1-21. AMPGARD Main Breaker and Two-High 400A Starter Section
CA08104001E
CHS Controls AB
September 2011
Sheet 10 042
i ii
PH PH PH Main A B C Bus
12.00 (304.8)
1 2 3 4 5 6 7
Unit 1B 30.00 (762) 5.81 (147.6) 0.90 (22.9) 1.45 GND (36.8) BUS 80.00 (2032.0)
5.50 (139.7)
30.00 (762.0)
5.50 (139.7)
2.00 (50.8)
19.00 (482.6)
22.00 (558.8)
8 9 10
Unit 1D Un it 2D 2 24.00 (609.6) Unit 1C
4.50 (114.3)
1.25 (31.8)
11.50 (292.1)
1.50 (38.1)
PH PH PH MAIN A B C BUS
12.00 (304.8)
11 12 13 14 15 16 17 18 19 20 21
1 24.00 (609.6)
30.00 (762.0) 5.50 (139.7) 5.50 (139.7) 6.70 (170.9) Note F 27.50 (698.5)
3.50 (88.9)
MAIN BUS 24.00 (609.6) Top View 80.00 (2032.0) 0.90 (22.9) 62.00 (1574.8) 2.00 (50.8) 24.00 (609.6) 4.50 (114.3)
Note F GND BUS 1.45 (36.8) 19.00 (482.6) 22.00 (558.8) 1.00 (25.4) Note A 28.00 (711.2) 1.00 (25.4) 30.00 (762.0)
4.50 (114.3)
Figure 10.1-22. 24.00-Inch (609.6 mm) Incoming Cable Section with 24.00-Inch (609.6 mm) Metering Section (for Right End of Lineup)
CA08104001E
CHS Controls AB
September 2011
Sheet 10 043
10.2-1
Clean and quiet: The SC 9000s integrated 24-pulse converter coupled to a 3-level inverter topology results in minimum component usage and ensures compliance with IEEE 519 no matter what the power source is. Heat pipe technology improves cooling efciency and allows the SC 9000 to run at a 75 dB noise level or less, making it the quietest drive in the industry. Output lters are required for non-inverter duty motors with cable lengths greater than 100 feet and for inverter duty motors with cable lengths greater than 300 feet. See Table 10.2-2 on Page 10.2-22 for detailed output lter application recommendations. Noise pollution is minimized with the quiet operation. Easy AMPGARD integration: Available as a fully integrated drive, the SC 9000 can be supplied as a stand-alone drive or directly connected to other AMPGARD products in a conguration known as Integrated Control-Gear. This integrated solution aligns the SC 9000 with a host of other motor control products, such as motor starters, load break switches and main breakers all connected via a common bus. Protection through technology: The encapsulated roll-out inverter employs a patented insulation system, which reduces the potential of environmental contamination. This modular inverter design coupled with a spare inverter option reduces MTTR and results in maximum uptime.
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
AMPGARD SC 9000
General Description
Eatons AMPGARD SC 9000 medium voltage adjustable frequency drive (AFD) family provides precise control and protection of medium voltage motors and equipment rated 2400V, 3300V and 4160V nominal.
Application Description
AMPGARD SC 9000 AFD has a complete offering: Precise control of medium voltage motors up to 6000 hp A smaller footprint, 24-pulse front end, and integrated assembly direct coupled through a common power bus to the entire AMPGARD product family as Integrated Control-Gear Fully integrated package with isolation switch, main contactor, multi-pulse isolation transformer, rectier and inverter
CA08104001E
CHS Controls AB
September 2011
Sheet 10 044
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
AMPGARD SC 9000 Fully Integrated Frame A AFD (3001150 hp at 4160V) (300700 hp at 3300V) (300500 hp at 2400V)
Type HLE Current Limiting Fuses Mechanical Non-Loadbreak Isolating Switch Top Entry Control Conduit Area
Line and Load Cable Termination Type SL Vacuum Contactor Assembly Encapsulated Roll-Out Inverter (in the Rear) 24-Pulse Rectier Bridge 24-Pulse Isolation Transformer
CA08104001E
CHS Controls AB
September 2011
Sheet 10 045
10.2-3
i ii
Detail Notes: A - 0.875 dia. typ. 4 holes. mounting studs to extend a maximum of 2.00 inches (50.8 mm) above grade. D - 90 door swing requires: 12.00 inches (304.8 mm) for 12.00 inch (304.8 mm) wide structure, 18.00 inches (457.2 mm) for 18.00 inch (457.2 mm) wide structure, 24.00 inches (609.6 mm) for 24.00 inch (609.6 mm) structure, 30.00 inches (762.0 mm) for 30.00 inch (762.0 mm) wide drive structure, 36.00 inches (914.4 mm) for 36.00 inch (914.4 mm) wide structure, 40.00 inches (1016.0 mm) for 40.00 inch (1016.0 mm) wide structure, 32.50 inches (825.5 mm) for 65.00 inch (1651.0 mm) wide drive structure. E - HV conduit space, load. F - HV conduit space, line only. G - LV conduit space only. J - Load terminals located on left-hand side of enclosure. Y - Tolerances: 0.0 inches (0.0 mm) +0.25 inches (6.35 mm) per structure. Z - Conduits to extend a maximum of 2.00 inches (50.8 mm) into structure.
1 2 3 4 5
Recommend 24.00 Inch 24.00 (609.6 mm) Clearance (609.6) for Blower Removal
6 7 8 9
80.00 (2032.0
K2
User Interface
12.00 (304.8)
MP4000
K1
Window
3.50 (88.9)
K1 K2 K3
1 3
2 4 5 CTB
10 11 12 13
Unit 1D
Elevation View
1 65.00 (1651.0) Shipping Section 2 Approx. Weight 6225 lbs (2826 kg) 59.00 (1498.6) 29.50 (749.3) Note A 21.81 (554.0) 5.00 (127.0) F E 1.50 (38.1) 32.50 (825.5) Front 1.38 (35.1) 2.80 (71.1) G 4.00 (101.6) 2.69 (68.3)
12.81 7.50 (190.5) 62.00 (325.4) L2 (1574.8) 2.50 L3 7.50 (190.5) (63.5) 3.25 2.50 (82.6) 16.90 (63.5) (429.3) Ground Bus 22.49 (571.2)
Main Bus End 1000A 0.25 x 3.00 1/ph 38.63 (981.2) 0.75 (19.1) 1.50 3.00 (38.1) (76.2) 0.75 (19.1) 0.437 x 0.688 Slot Main Bus End 2000A 0.25 x 4.00 2/ph 0.75 (19.1) 2.50 4.00 (63.5) (101.6) 0.50 (12.7) 0.25 (6.4)
Main Bus End 1200A 0.25 x 4.00 1/ph 0.75 (19.1) 2.50 4.00 (63.5) (101.6) 0.75 (19.1) 0.437 x 0.688 Slot 0.25 (6.4)
14 15 16 17 18
0.25 (6.4)
12.75 (323.9)
43.63 (1108.2)
Ground Bus End 600A 0.25 x 2.00 3.63 Inches (92.2 mm) from Each Side of the Structure 0.562 Dia. Hole
C L
3.00 (76.2)
29.30 (744.2)
0.25 (6.4)
0.63 (16.0)
19 20 21
60.00 Inches (1524.0 mm) Clear in Front of Drive Unit for Removal of Drive Inverter
Figure 10.2-1. AMPGARD SC 9000 AFD Frame A Maximum Dimensions and Incoming Line LayoutsDimensions in Inches (mm)
CA08104001E For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
CHS Controls AB
September 2011
Sheet 10 046
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
AMPGARD SC 9000 Fully Integrated Frame B AFD (10002000 hp at 4160V) (8001500 hp at 3300V) (6001000 hp at 2400V)
Type HLE Current Limiting Fuses Top Entry HV Conduit Area Mechanical Non-Loadbreak Isolating Switch Top Entry Control Conduit Area
Line and Load Cable Termination Type SL Vacuum Contactor Assembly DC Link Pre-Charge Circuit
CA08104001E
CHS Controls AB
September 2011
Sheet 10 047
10.2-5
i ii
Main Bus Main Bus 12.27 (311.7) 2.00 2.00 (50.8) (50.8) 12.27 (311.7) 5.50 31.88 (139.7) (809.8)
E
1 2
50.00 (1270.0)
12.27 (311.7)
5.00 (127.0)
39.27 (997.5) 5.50 50.00 (139.7) (1270.0) 7.00 G (177.8) 1.25 (31.8)
3 4
6.00 (152.4)
5 6
K2
K3
1.85 (47.0)
MP4000
K1
7
3.50 (88.9)
WINDOW K1 K2 K3
Inverter
1 3 2 4 8
4.38 (111.3) 4.38 (111.3) 12.00 (304.8) 66.00 (1676.4) 2.86 (72.6) 80.00 (2032.0) Recommend 24.00 Inch (609.6 mm) Clearance for Blower Removal
Converter Unit 1D
4.13 (104.9)
CTB
Approx. 120.00 Inches (3048.0 mm) Tall Redundant 24.00 Blowers (609.6)
7 8 9 10 11 12 13 14 15 16 17 18 19
0.90 (22.9)
1 65.00 (1651.0) Shipping Section 1 Approx. Weight 8025 lbs (3643 kg)
2 30.00 (762.0) Shipping Section 2 Approx. Weight 900 lbs (409 kg)
Ground Bus
49.00 (1244.6)
PH PH PH Main A B C Bus
3.50 (88.9)
Right Side View 59.00 (1498.6) 2.40 (61.0) 4.75 (120.7) 44.20 (1122.7) 2.50 (63.5) F 7.00 (177.8) 3.00 (76.2) E 33.50 (850.9) 4.75 Front (120.7) 33.50 (850.9) G 7.00 (177.8) 2.50 (63.5) 25.00 (635.0)
Front Note A
36.80 (934.7)
38.30 (972.8)
Note A
1.58 (40.1)
12.00 (304.8)
30.00 (762.0)
2.50 (63.5)
36.00 (914.4)
Front
60.00 (1524.0)
60.00 (1524.0)
Optional With Redundant Blowers 60.00 Inches (1524.0 mm) Clear in Front of Drive Unit for Removal of Drive Inverter 60.00 Inches (1524.0 mm) Clear in Front of Drive Unit for Removal of Drive Inverter
Detail Notes: A - 0.875 dia. typ. 4 holes. Mounting studs to extend a maximum of 2.00 inches (50.8 mm) above grade. D - 90 door swing requires: 12.00 inches (304.8 mm) for 12.00 inch (304.8 mm) wide structure, 18.00 inches (457.2 mm) for 18.00 inch (457.2 mm) wide structure, 24.00 inches (609.6 mm) for 24.00 inch (609.6 mm) structure, 30.00 inches (762.0 mm) for 30.00 inch (762.0 mm) wide drive structure, 36.00 inches (914.4 mm) for 36.00 inch (914.4 mm) wide structure, 40.00 inches (1016.0 mm) for 40.00 inch (1016.0 mm) wide structure, 32.50 inches (825.5 mm) for 65.00 inch (1651.0 mm) wide drive structure. E - HV conduit space, load. F - HV conduit space, line only. . G - LV conduit space only. J - 30.00 inch (762.0 mm) inverter load terminals located on left side of converter. 36.00 inch (914.4 mm) inverter load terminals located on right side of inverter. Y - Tolerances: 0.00 inches (0.0 mm) +0.25 inches (6.35 mm) per structure. Z - Conduits to extend a maximum of 2.00 inches (50.8 mm) into structure.
Main Bus End 1000A 0.25 x 3.00 1/ph 0.75 (19.1) 1.50 3.00 (38.1) (76.2) 0.437 x 0.688 0.75 (19.1) Slot 0.25 (6.4)
Main Bus End 1200A 0.25 x 4.00 1/ph 0.75 (19.1) 2.50 4.00 (63.5) (101.6) 0.437 x 0.688 Slot 0.75 (19.1) 0.25 (6.4)
Main Bus End 2000A 0.25 x 4.00 2/ph 0.75 (19.1) 2.50 4.00 (63.5) (101.6) 0.437 x 0.688 Slot 0.75 (19.1) 0.25 (6.4) 0.50 (12.7)
Ground Bus End 600A 0.25 x 2.00 3.63 Inches (92.2 mm) from Each Side of the Structure 0.562 Dia. Hole 0.63 (16.0) 0.50 (12.7)
C L
20 21
Figure 10.2-2. AMPGARD SC 9000 AFD Frame B Maximum Dimensions and Incoming Line LayoutsDimensions in Inches (mm)
CA08104001E
CHS Controls AB
September 2011
Sheet 10 048
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
AMPGARD SC 9000 Fully Integrated Frame C AFD (22503000 hp at 4160V) (17502000 hp at 3300V) (12501750 hp at 2400V)
Type HLE Current Limiting Fuses Top Entry HV Conduit Area Mechanical Non-Loadbreak Isolating Switch Top Entry Control Conduit Area DC Link Pre-Charge Circuit
CA08104001E
CHS Controls AB
September 2011
Sheet 10 049
10.2-7
i ii 1
Main Bus 2.00 (50.8) 12.27 (311.7) 31.88 (809.8) 5.50 (139.7) 12.00 (304.8) E 6.00 (152.4) 50.00 (1270.0)
2 3 4
7.00 (177.8)
30.00 (762.0) Optional 36.00 (914.4) Top View Main Bus End 1000A 0.25 x 3.00 1/ph
5 6
0.75 (19.1) 3.00 (76.2) 12.00 (304.8) 3.50 (88.9) 0.437 x 0.688 Slot 0.75 (19.1) 1.50 (38.1) 0.25 (6.4)
7 8 9
K2 WINDOW K1
K3
K4
WINDOW
Inverter
1 2 4 5
1.85 (47.0)
Main Bus End 1200A 0.25 x 4.00 1/ph 0.75 (19.1) 4.00 (101.6) 0.437 x 0.688 Slot 0.75 (19.1) 2.50 (63.5) 0.25 (6.4)
K1 K2 K3 K4 CTB1
80.00 (2032.0)
CTB
Unit 2D
Converter
Unit 3D
10 11
1 Shipping Section 1 36.00 (914.4) Approx. Weight 1550 lbs (704 kg)
1 Shipping Section 2 65.00 (1651.0) Approx. Weight 9800 lbs (4449 kg)
2 Shipping Section 3 30.00 (762.0) Optional 36.00 (914.4) Approx. Weight 900 lbs (409 kg)
Ground Bus
22.49 (571.2) 50.00 (1270.0) Right Side View 2.50 (63.5) Note A 43.00 (1092.2) 6.00 (152.4) Front 3.00 (76.2) 25.00 (635.0) 30.00 (762.0) Optional 36.00 (914.4) E 2.80 (71.1) 12.00 (304.8)
Main Bus End 2000A 0.25 x 4.00 2/ph 0.75 (19.1) 4.00 (101.6) 0.437 x 0.688 Slot 0.75 (19.1) 2.50 (63.5)
12 13 14 15 16 17 18 19 20 21
3.50 (88.9) 2.75 (69.9) 16.00 (406.4) 29.25 (743.0) 16.00 (406.4) Note A F 7.00 (177.8) E 29.00 (736.6) Front 36.00 (914.4) 4.00 (101.6) 43.00 (1092.2) 35.00 (889.0)
3.50 (88.9) Note A 59.00 (1498.6) 3.00 (76.2) 2.50 (63.5) 5.00 (127.0) Front 8.00 32.50 (203.2) (825.5) G 32.50 9.50 (825.5) (241.3)
Ground Bus End 600A 0.25 x 2.00 3.63 Inches from Each Side of the Structure 0.50 (12.7) 0.562 Dia. Hole C
L
5.75 (146.1)
2.00 (50.8)
0.25 (6.4)
60.00 Floor Plan (1524.0) Note D 60.00 Inches Detail Notes: (1524.0 mm) A - 0.875 dia. typ. 4 holes. mounting studs to extend Clear in a maximum of 2.00 inches: (50.8 mm) above grade. Front of Unit D - 90 door swing requires: 12.00 inches (304.8 mm) for 12.00 inch (304.8 mm) wide structure, for Removal 18.00 inches (457.2 mm) for 18.00 inch (457.2 mm) wide structure, of Inverter 24.00 inches (609.6 mm) for 24.00 inch (609.6 mm) structure, 30.00 inches (762.0 mm) for 30.00 inch (762.0 mm) wide drive structure, 36.00 inches (914.4 mm) for 36.00 inch (914.4 mm) wide structure, 40.00 inches (1016.0 mm) for 40.00 inch (1016.0 mm) wide structure. 32.50 inches (825.5 mm) for 65.00 inch (1651.0 mm) wide drive structure. E - HV conduit space, load. F - HV conduit space, line only. G - LV conduit space only. J - Load terminals located on right side of inverter. Optionload terminals located on left side of converter. Y - Tolerances: 0.0 inches (0.0 mm) +0.25 inches (6.35 mm) per structure. Z - Conduits to extend a maximum of 2.00 inches (50.8 mm) into structure.
Figure 10.2-3. AMPGARD SC 9000 AFD Frame C Maximum Dimensions and Incoming Line LayoutsDimensions in Inches (mm)
CA08104001E For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
CHS Controls AB
September 2011
Sheet 10 050
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
AMPGARD SC 9000 Fully Integrated Frame D AFD (Single Inverter) (20002500 hp at 2400V)
Top Entry Control Conduit Area Top Entry HV Conduit Area Mechanical Non-Loadbreak Isolating Switch DC Link Pre-charge Circuit
CA08104001E
CHS Controls AB
September 2011
Sheet 10 051
10.2-9
i
2.00 (50.8) Main Bus 12.32 50.00 (312.9) (1270.0) 5.50 (139.7) 40.75 1.38 (1035.1) (35.1) 2.00 (50.8) 2.00 (50.8) 12.32 (312.9) 5.50 (139.7) 12.00 (304.8) 36.00 (914.4) Main Bus End 1000A 0.25 x 3.00 1/ph 0.75 (19.1)
E
ii
31.88 (809.8) 50.00 (1270.0)
2.00 (50.8)
1 2 3 4
3.00 (76.2)
6.00 (152.4)
36.00 (914.4)
3.00 (76.2)
1.50 (38.1)
0.25 (6.4)
5 6 7
Main Bus End 1200A 0.25 x 4.00 1/ph 0.75 (19.1) 4.00 (101.6) 0.437 x 0.688 Slot 0.75 (19.1) 2.50 (63.5) 0.25 (6.4)
WINDOW
1.85 (47.0)
7
1
K11 K12 K13 K14 K44
2 4 8
Inverter
K12
K13
K14
CTB2
CTB
K11
CTB1
0.90 (22.9)
UNIT 3D
80.00 (2032.0)
Main Disconnect Unit 1D 1 36.00 (914.4) Shipping Section 1 40.00 (1016.0) Approx. Wt. 2560 lbs (1162 kg) 2 76.00 (1930.4) Shipping Section 2 76.00 (1930.4) Approx. Wt. 16,500 lbs (7491 kg) 3 36.00 (914.4) Shipping Section 3 36.00 (914.4) Approx. Wt. 3775 lbs (1714 kg)
Ground Bus 2.86 (72.6) 38.25 (971.6) 49.00 (1244.6) 50.00 (1270.0) Right Side View
Main Bus End 2000A 0.25 x 4.00 2/ph 0.75 (19.1) 4.00 (101.6) 0.437 x 0.688 Slot 0.75 (19.1) 2.50 (63.5) 0.25 (6.4) 0.50 (12.7)
8 9 10 11 12 13
Ground Bus End 600A 0.25 x 2.00 3.63 Inches (92.2 mm) from Each Side of the structure 0.562 Dia. Hole 0.63 (16.0) 30.00 (762.0) 0.50 (12.7)
C L
5.00 29.00 (127.0) (736.6) Note A 12.00 (304.8) 18.00 (457.2) 23.00 F 41.33 (584.2) 14.00 7.00 (1049.8) (355.6) 41.38 (177.8) (1051.1) 3.00 19.63 (76.2) (498.6) 3.50 (88.9) Front 6.00 1.50 (152.4) (38.1) 8.88 (225.6) 36.00 (914.4)
13.00 (330.2)
3.50 (88.9) 6.00 (152.4) 43.00 (1092.2) 2.80 (71.1) Front 31.00 (787.4) 36.00 (914.4) 60.00 Inches (1524.0 mm) Clear in Front of Unit for Removal of Inverter
E
2.00 (50.8)
0.25 (6.4)
44.00 (1117.6)
14 15 16 17 18 19 20 21
50.00 (1270.0)
3.00 (76.2)
12.00 (304.8)
38.00 (965.2)
38.00 (965.2)
1.85 (47.0)
Detail Notes: A - 0.875 dia. typ. 4 holes. mounting studs to extend a maximum of 2.00 inches (50.8 mm) above grade. D - 90 door swing requires: 12.00 inches (304.8 mm) for 12.00 inch (304.8 mm) wide structure, 18.00 inches (457.2 mm) for 18.00 inch (457.2 mm) wide structure, 24.00 inches (609.6 mm) for 24.00 inch (609.6 mm) structure, 36.00 inches (914.4 mm) for 36.00 inch (914.4 mm) wide structure, 40.00 inches (1016.0 mm) for 40.00 inch (1016.0 mm) wide structure, 32.50 inches (825.5 mm) for 65.00 inch (1651.0 mm) wide drive structure. E - HV conduit space, load. F - HV conduit space, line only. G - LV conduit space only. J - Load terminals located on right-hand side of enclosure. Y - Tolerances: 0.00 inches (0.0 mm) +0.25 inches (6.35 mm) per structure. Z - Conduits to extend a maximum of 2.00 inches (50.8 mm) into structure.
Figure 10.2-4. AMPGARD SC 9000 AFD Frame D (Single Inverter) Maximum Dimensions and Incoming Line LayoutsDimensions in Inches (mm)
CA08104001E For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
CHS Controls AB
September 2011
Sheet 10 052
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
AMPGARD SC 9000 Fully Integrated Frame D AFD (Parallel Inverters) (32504500 hp at 4160V) (22503000 hp at 3300V)
Top Entry Control Conduit Area Secondary Blower DC Link Pre-Charge Circuit Balancing Reactor Top Load Conduit Area
Load Cable Termination Type HLE Current Limiting Fuses Type SL Vacuum Contactor Assembly
CA08104001E
CHS Controls AB
September 2011
Sheet 10 053
10.2-11
i ii
2.00 (50.8) 12.32 (312.9) 50.00 (1270.0) 2.00 (50.8) 12.32 (312.9) 30.88 5.50 (784.4) (139.7)
E
2.00 (50.8)
2.00 (50.8)
1 2 3 4
3.00 (76.2)
5.50 (139.7) 40.75 1.38 (1035.1) (35.1) 3.00 (76.2) 86.00 (2184.4)
Recommend 24.00 Inch (609.6 mm) Clearance 24.00 for Blower Removal (609.6)
PH PH PH MAIN A B C BUS
K12 K13 K14 K15 K44 K15 K16 K17
7
5 6 7 8 9 10 11 12 13 14 15
WINDOW
1.85 (47.0)
3.50 (88.9)
30.36 (771.1)
2 4 8
CTB2
CTB
K11
CTB1
Main Disconnect
Inverter-1 Unit 3D
Inverter-2
0.90 (22.9)
4.38 (111.3) Load Term Note J 68.00 (1727.2) Ground 3.26 (82.8) Bus 22.75 (577.9) 49.00 (1244.6) 50.00 (1270.0)
80.00 (2032.0)
Unit 1D 1 36.00 (914.4) Shipping Section 1 40.00 (1016.0) Approx. Weight 2560 lbs (1162 kg) 3.50 (88.9)
Ground Bus 5.00 (127.0) 38.25 (971.6) 49.00 (1244.6) 50.00 (1270.0) Right Side View
2 76.00 (1930.4) Shipping Section 2 76.00 (1930.4) Approx. Weight 16,500 lbs (7491 kg)
3 86.00 (2184.4) Shipping Section 3 86.00 (2184.4) Approx. Weight 6800 lbs (3087 kg) 13.00 (330.2)
29.00 (736.6)
25.00 (635.0)
25.00 (635.0)
31.13 (790.7)
48.12 (1222.2)
15.50 (393.7)
5.00 (127.0)
41.38 (1051.1)
Note A 18.00 23.00 (457.2) F (584.2) 19.63 (498.6) Front 36.00 (914.4)
41.33 (1049.8)
7.00 (177.8)
43.25 5.00 Note A 4.15 (1098.6) (127.0) 44.00 (105.4) 39.00 Front (1117.6) 50.00 (990.6) 2.75 (1270.0) (69.9) 3.00 (76.2)
G
Note A
3.00 31.00 39.00 (76.2) (787.4) (990.6) 2.63 (66.8) 2.00 14.00 (50.8) E (355.6) 42.50 6.75 (1079.5) (171.5)
38.00 (965.2)
38.00 (965.2)
1.85 (47.0)
Main Bus End 1000A 0.25 x 3.00 1/ph 0.75 (19.1) 3.00 (76.2) 0.437 x 0.688 Slot 0.75 (19.1) 1.50 (38.1) 0.25 (6.4)
Main Bus End 1200A 0.25 x 4.00 1/ph 0.75 (19.1) 4.00 (101.6) 0.437 x 0.688 Slot 0.75 (19.1) 2.50 (63.5) 0.25 (6.4)
Ground Bus End 600A 0.25 x 2.00 3.63 Inches from Each Side of the Structure 0.562 Dia. Hole 0.63 (16.0) 0.50 (12.7)
C L
0.75 (19.1) 4.00 (101.6) 0.437 x 0.688 Slot 0.75 (19.1) 2.50 (63.5)
Detail Notes: A - 0.875 dia. typ. 4 holes. Mounting studs to extend a maximum of 2.00 inches (50.8 mm) above grade. D - 90 door swing requires: 12.00 inches (304.8 mm) for 12.00 inch (304.8 mm) wide structure, 18.00 inches (457.2 mm) for 18.00 inch (457.2 mm) wide structure, 24.00 inches (609.6 mm) for 24.00 inch (609.6 mm) structure, 36.00 inches (914.4 mm) for 36.00 inch (914.4 mm) wide structure, 40.00 inches (1016.0 mm) for 40.00 inch (1016.0 mm) wide structure, 32.50 inches (825.5 mm) for 65.00 inch (1651.0 mm) wide drive structure. E - HV conduit space, load. F - HV conduit space, line only. G - LV conduit space only. J - Load terminals located on right-hand side of enclosure. Y - Tolerances: 0.00 inches (0.0 mm) +0.25 inches (6.35 mm) per structure. Z - Conduits to extend a maximum of 2.00 inches (50.8 mm) into structure.
16 17 18 19 20 21
2.00 (50.8)
0.25 (6.4)
Figure 10.2-5. AMPGARD SC 9000 AFD Frame D (Parallel Inverters) Maximum Dimensions and Incoming Line LayoutsDimensions in Inches (mm)
CA08104001E
CHS Controls AB
September 2011
Sheet 10 054
i ii 1 2 3 4
K2
K3
K4
K5
K33 K4 K6
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
CTB1
1
Window
2 4 8
K1 K3
K1 CTB2
CTB
Inverter-1
Inverter-2
Main Disconnect Unit 1D 1 36.00 (914.4) Shipping Section 1 Approx. Weight (2560 lbs) 2 100.00 (2540.0) Shipping Section 2 Approx. Weight (19,500 lbs) 3 86.00 (2184.4) Shipping Section 3 Approx. Weight (6800 lbs)
Figure 10.2-6. AMPGARD Frame EDimensions in Inches (mm) Table 10.2-1. AMPGARD Frame EDimensions in Inches (mm)
Output Voltage 3300 4160
Cabinet Size Width 222.00 (5638.8) 222.00 (5638.8) Height 92.00 (2336.8) 92.00 (2336.8) Depth 50.00 (1270.0) 50.00 (1270.0)
3300V, 50 Hz.
CA08104001E
CHS Controls AB
September 2011
Sheet 10 055
Motor Control (AMPGARD)Medium Voltage 10.2-13 Adjustable Frequency Drives Synchronous Transfer Systems
General Description
If the PLC receives a command to sync down, the PLC will start the AFD and close the motor select contactor; however, the AFD output contactor does not close initially. See Figure 10.2-11.
4160V, 60 Hz, Line
i ii 1 2
AFD Bus
3 4 5 6 7 8 9
General Description
The sequence of operation outlined is of an Adjustable Frequency Drive/Programmable Logic Controller (AFD/PLC) synchronous transfer control system. Included in this system is an AFD per system, a PLC per system, a bypass contactor and a motor select contactor per motor. The AFD output contactor feeding the AFD bus is an option and is illustrated for this example.
The AFD output will adjust to match the utility voltage, frequency and phase. Once these parameters are locked in, the AFD output contactor will close and the bypass contactor will open such that paralleling is minimized. The output reactor will dampen transient currents. See Figure 10.2-12.
4160V, 60 Hz, Line
AFD Bus
Figure 10.2-8. Synchronous Transfer Process When the motor is required to transfer to the utility line, the PLC will send the Sync Up command to the AFD. The AFD will adjust the output to match the line voltage, frequency and phase angle. Once synchronization is locked, the bypass and motor select contactor are closed and opened such that paralleling is minimized. The output reactor dampens transient currents. See Figure 10.2-9.
4160V, 60 Hz, Line
Application Description
The basic principle is to adjust the AFD output voltage, frequency and phase to match the utility. By matching these parameters, the system can transfer the motor to the utility in a bump-less manner. The AFD and PLC system is programmed to follow these general commands.
AFD Bus
10 11 12 13 14
Figure 10.2-12. AFD Adjusts to Match the Utility Voltage, Frequency and Phase The AFD will operate at a set speed point or follow a reference speed. See Figure 10.2-13.
4160V, 60 Hz, Line
Once the system bus is energized, the AFD and Feeder Bus are energized. See Figure 10.2-7.
4160V, 60 Hz, Line AFD Bus AFD Bus
15 16 17 18 19 20
Figure 10.2-9. Voltage, Frequency and Phase Angle Synchronization The AFD is shut down and waits for another Start command for the next motor. The rst motor is running on bypass. See Figure 10.2-10.
4160V, 60 Hz, Line
Figure 10.2-13. AFD Operating Speed These sequences can be commanded for any of the motors (15) illustrated and are not limited to just ve motors in a system; however, only one motor at a time can be on the AFD. Each system can be congured to start any number of motors, keeping in mind equipment size and layout.
AFD Bus
Figure 10.2-7. AFD and Feeder Bus Energized The Start command will start the synchronous transfer process. First the PLC will close the appropriate motor select contactor and then start the AFD. The AFD will operate at a preset speed or a reference speed. See Figure 10.2-8.
AFD Bus
21
CHS Controls AB
10.2-14 Motor Control (AMPGARD)Medium Voltage Adjustable Frequency Drives Synchronous Transfer Systems
Layout Dimensions
September 2011
Sheet 10 056
i ii 1
K2
K3
K4
2 3
SC 9000
CTB
Inverter
Unit 7B
Door
Unit 10B
Door
4 5 6 7 8 9
Converter Inverter 1
Unit 2D
Unit 3D
K5
Drive Output 2 3 4 5 6
Trip PB Mech Unlatch
A4 Motor Select 9
Mech Unlatch
Mech Unlatch
10
4.00 (101.6) 65.00 (1651.0) 65.00 (1651.0) Shipping Section 1 Approx. Weight (9325 lbs) 36.00 (914.4) 76.00 (1930.4) Shipping Section 2 Approx. Weight (4725 lbs) 36.00 (914.4) 36.00 (914.4) 72.00 (1828.8) Shipping Section 3 Approx. Weight (3600 lbs) 36.00 (914.4) 36.00 (914.4) 72.00 (1828.8) Shipping Section 4 Approx. Weight (4700 lbs) 36.00 (914.4) 36.00 (914.4) 72.00 (1828.8) Shipping Section 5 Approx. Weight (4700 lbs) 36.00 (914.4)
10
24 Pulse XFMR
11
D Unit 1D Unit 2D Unit 3D Unit 5D Unit 6D MS Unit 7D MS Unit 8D MS Unit 9D MS Unit 10D MS
12 13 14 15 16 17 18 19 20 21
Figure 10.2-14. AMPGARD SC 9000 Synchronous Transfer System with Five MV Starters (For Reference Only)
CA08104001E
CHS Controls AB
September 2011
Sheet 10 057
10.2-15
i ii 1 2
K2 K3 K5 K6
MP4000
K1
1 2
Window
K4 K5 K6
3 4 5
1 3
2 4 8
K1 K2 K3 K4
Contactor Unit 2D
6 7
1 36.00 (914.4)
2 36.00 (914.4)
4 86.00 (2184.4) Shipping Section 3 Approx. Weight (6800 lbs) Detail Notes: A - 0.875 dia. typ. 4 holes. Mounting studs to extend a maximum of 2.00 inches (50.8 mm) above grade. D - 90 door swing requires: 12.00 inches (304.8 mm) for 12.00 inch (304.8 mm) wide structure, 18.00 inches (457.2 mm) for 18.00 inch (457.2 mm) wide structure, 24.00 inches (609.6 mm) for 24.00 inch (609.6 mm) structure, 30.00 inches (762.0 mm) for 30.00 inch (762.0 mm) wide drive structure, 36.00 inches (914.4 mm) for 36.00 inch (914.4 mm) wide structure, 40.00 inches (1016.0 mm) for 40.00 inch (1016.0 mm) wide structure. 32.50 inches (82.6 mm) for 65.00 inch (1651.0 mm) wide drive structure. E - HV conduit space, load. F - HV conduit space, line only. G - LV conduit space only. J - Load terminals located on right side of inverter. Optionload terminals located on left side of converter. Y - Tolerances: 0.0 inches (0.0 mm) +0.25 inches (6.4 mm) per structure. Z - Conduits to extend a maximum of 2.00 inches (50.8 mm) into structure.
8 9 10 11 12 13 14 15 16 17 18
72.00 (1828.8) Shipping Section 1 Approx. Weight (4500 lbs) Main Bus End 1000A 0.25 x 3.00 1/ph 0.75 (19.1) 1.50 (38.1) 3.00 (76.2) 0.437 x 0.688 Slot 0.75 (19.1) 0.25 (6.4) 0.437 x 0.688 Slot 0.75 (19.1)
Main Bus End 2000A 0.25 x 4.00 2/ph 0.75 (19.1) 2.50 (63.5) 4.00 (101.6) 0.25 (6.4) 0.50 (12.7)
Main Bus End 1200A 0.25 x 4.00 1/ph 0.75 (19.1) 2.50 (63.5) 4.00 (101.6) 0.437 x 0.688 Slot 0.75 (19.1) 0.25 (6.4)
Ground Bus End 600A 0.25 x 2.00 3.63 Inches (92.2 mm) from Each Side of the Structure 0.50 (12.7)
0.63 (16.0)
2.00 (50.8)
0.25 (6.4)
K2, K3 K4 K5, K6
Figure 10.2-15. AMPGARD SC 9000 Frame D 4160V with High Voltage Input
19 20 21
additional 72-inch (1828.8 mm) wide structure to accommodate a 95 kV BIL incoming line and a 15 kV input contactor. Please consult the factory for drive dimensions and incoming line section requirements.
For more information, visit: www.eaton.com/consultants
Tel +46 42 38 61 00, Fax +46 42 38 61 29 chs@chscontrols.se www.chscontrols.se
CHS Controls AB
10.2-16 Motor Control (AMPGARD)Medium Voltage Adjustable Frequency Drives Integrated VCPW Main Breaker
Layout Dimensions
September 2011
Sheet 10 058
i ii 1 2 3 4
61.12 (1552.4)
Frame B SC 9000 Medium Voltage Drive Main Breaker, Output Contactor with Bypass Elevation View
5
1 2
Cs Sw Fp4000
6
Unit 1B
MP3000
1
Start Stop
2 4
7
Unit 1C
Loc/rem
Enter
3 5
Unit 2C
Converter
1 3
2 4 8
Inverter
Unit 7D
8 9
Spacer Unit 4D
Ctb Unit 5D
1
10 11 12 13 14 15 16 17 18 19 20 21
60.00 (1524.0) Floor Plan
Main Breaker
Unit 1F
1
Spacer
4
Unit 2F
2
Unit 7D
7
26.00 (660.4)
4.00 (101.6) 65.00 (1651.0) Shipping Section 2 65.00 (1651.0) Approx. Weight 8025 lbs (3643 kg) 30.00 (762.0) Shipping Section 3 30.00 (762.0) Approx. Weight 900 lbs (409 kg)
4.00 (101.6) 36.00 (914.4) Shipping Section 3 40.00 (1016.0) Approx. Weight 1800 lbs (817 kg)
30.00 (762.0)
50.00 (1270.0)
Figure 10.2-16. AMPGARD Integrated Control-Gear with Main Breaker Dimensions(See Page 10.0-4 for Information on Main Bus. Refer to Eaton for Larger hp Layouts and Detailed Assembly Dimensions.)
Note: For exact conduit locations and descriptions, please see Page 10.2-24.
CA08104001E
CHS Controls AB
Sheet 10 059
H1
1LA
2LA
3LA
GND
VA
H1 H2
MP2
VB VA VB
H2 H2 H3 H1 H3
CONTROL
TRANSFORMER
L1 A 2L1 NEG
CONVERTER
1L1
M 2L1 R
INVERTER
CA08104001E
September 2011
Typical Schematic
ISOLATION SWITCH
ISW
MAIN FUSE
T1
S NEUT
24PR
INV
L2 B
1L2
MP3
VC
T2
H1
A9
X1 X0 X2 X3 X0 X0
11 X0 X1 X1
X11 3
X1 X2
5KVA
X2 X2
H11
SLOT A
REFERENCE OUTPUT (0-10 VDC) ANALOG INPUT I/O GROUND
X2
X1
A B C D
ISW GND
-1 1 2 -2
IO18
X11 X21 X31
ISO
IS4 11 PHASE 13
X21 4 5
IS6
H22 H33
13
GND IO17
3X
4 5 6
Technical Data
4X
1
SUPP
ISWX
2X IS1 X2 IS2 A1
A B C D
X3
CONTROL VOLTAGE OUTPUT I/O GROUND FORWARD START/STOP
CHS Controls AB
PX
6
3X
5X
5X
PX
MS1
1H11
MAIN BLOWERS
P9/J9 BRN BLU BLK GRN
1H2
3 4
5X
FB-2
9 10
DIN2 DIN3
1H21 1H31
FB-3
1H3
6
MB1
11 12 13 CMA 24Vout GND
ISWX
SF4
1B
1X
21
22
31
32
GND
X6 14 15 DIN4 DIN5
A B C D
16
DIN6 17 CMB
GND MAX
IO8
IO8
MAX
11
14
23
24
AUX3
54 ## ##
18 19
Lout+ Lout-
31
32
33
37
38
39
51
52
53
IO9 MAX
IO9
MAX
11
14
12
14
AUX5
AUX6
*
56
31
32
33
40
41 42
49
50
55
= REMOTE DEVICE = INTERNALTERM. BLK(S) = TERM. BLK. FOR CUSTOMER CONN. TX = TX TYPE LIGHT
10.2-17
ii
21
20
19
18
17
16
15
14
13
12
11
10
ii
D1
D2
F2 1S1
D3
D4
D5
D6
BLACK
WHITE
RED
BLACK
WHITE
D7
D8
D9
14
R6 R2
RED
21
SP1
20
Technical Data
URTD VRTD
INVERTER
GND
19
1 2 1 2 1 2
BLK RED BLK RED BLK RED
18
INV
WRTD
J6
1 2
17
24 PULSE RECTIFIER 24 PULSE RECTIFIER POS (POS)
16
24PR DC LINK
URTD WRTD VRTD
J4
1 2
15
1 2 7 8 DMCR 5 SLAVE 6 INTERFACE 3 CARD 4 9 10
PHASE PHASE
14
J8
1 2
13
PHASE
12
11
10
IO12[A]
V
IGBT
5 79
WPU C G E
11
T1
450 AMP TYPICAL F1
RTDI
RTD
12
14
+22.5
1R1 C1 UPU VPU
5 79
C G E
5 79
C G E
R4
Q1 Q5
4 68 4 68
Q9
4 68
IO13[A]
T4
F3 1T1
11
RTDT
RTD
13
14
U1CT
5 79
UPL VPL WPL R3
-7.5
F4 F5 F6 2T1 R5 R1 (NEUT) NEUT GND F7 3R1 3S1 3T1 UNU D7-12 DD2 F8 F9 N R4 2S1 2R1
5 79
C G E
5 79
C G E
R3
H3
C G E
Q2
4 68 4 68
Q6
Q10
+
M
2L3
IO13[B]
S3
4 68
21
RTD5
RTD
T3
U
V1CT
V
23
24
2L2
H2
V
+
M
IO14[A]
11
RTD6
RTD
12
+7.5
R2
S2
10.2-18 Motor Control (AMPGARD)Medium Voltage Adjustable Frequency Drives Technical Data
Figure 10.2-18. Typical Schematic for 24-Pulse Transformer, Rectier and Inverter
5 79 5 79 5 79
BLACK
WHITE
D10
D11
F11 4S1
D12
H0
R1
F10 4R1
IO12[B]
5 79
UNL NEG (-) C2
5 79
C G E
5 79
BLK
RED
BLK
RED BLK
GRN
AF1M
DMCR
0V -Vc M +15
EPC VTN
-HT +HT
TS B B W R (-)
NEGATIVE
GND
NEG POS
DMCR
1 2 3 4 5 6 7 8 9 U V W
BRN
BLK
BLU
P-J
MP1
4 2
0v 0v
WHT
BLK
RED
7 8
LEM VOLTAGE SENSORS N TS
WHT
BLK
14 11 12
IO11
RED
MP2
VTP
-HT
6 5 4 3 2 1
B B W R
0V -Vc M +15
POSITIVE
+HT
(+)
GND
= REMOTE DEVICE = INTERNALTERM. BLK(S) = TERM. BLK. FOR CUSTOMER CONN. TX = TX TYPE LIGHT
GRN
GRN
RED
21
T1
RDTO 23
RTD
Q4
4 68
VNL
C G E
Q8
4 68
WNL
C G E
Q12
4 68
GND
24
GND
RED
CHS Controls AB
2L1
H1
T2
W1CT Q7
4 68
WNU
W
Q11
4 68
+
M
IO14[B]
C G E
21
RTD7
RTD
23
24
-22.5
September 2011
CA08104001E
Sheet 10 060
September 2011
Sheet 10 061
Motor Control (AMPGARD)Medium Voltage 10.2-19 Adjustable Frequency Drives Personnel Safety Features
General Description
i ii 1 2 3
Isolation Switch Operating Shaft
4 5
6 7
8 9 10
11 12 13 14 15 16 17 18
Motion of Shutter
19 20 21
Shutter Mechanism and Finger Barrier Isolation of Incoming Line Bus (Shown with Removable Portion of Isolation Switch Removed)
CA08104001E
CHS Controls AB
10.2-20 Motor Control (AMPGARD)Medium Voltage Adjustable Frequency Drives Component Details
General Description
September 2011
Sheet 10 062
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
This method of heat removal from the inverter is up to 10 times more efcient than traditional air-cooling methods, resulting in less required airow for quieter and more efcient operation. The thermal management system has been subjected to temperatures of 50C to model cold weather transport without the rupture of any heat pipes. It is also important to note that thermal management performance was unaffected by the extreme cold storage.
In the event of a failure, the modular roll-in/roll-out design of the inverter will minimize downtime. In traditional medium voltage drives, only the device that fails is replaced. This can result in future downtime due to latent failures of other devices that were damaged in the original incident. The SC 9000 uses an inverter replacement system that minimizes mean-time-to-repair (MTTR) and is designed exclusively for the purposes of inverter module exchange. The system removes the existing inverter safely and effectively and then allows for the insertion of a replacement inverter that is on-site or shipped from the factory where spare inverters are stocked.
General Description
The roll-out three-phase inverter module employs a patented insulation and buswork system to obtain the highest power density rating in the market. Heat pipe technology is used to cool the active power components in the inverter.
Figure 10.2-20. Heat Pipe Construction This cooling methodology and the encapsulation of the medium voltage components result in a harsh-environment inverter that protects the active power devices and circuit boards from the environment and airborne contaminants eliminating potential causes of failures. The encapsulation system also protects other components from ying debris and collateral damage in the event of a device failure.
CA08104001E
CHS Controls AB
September 2011
Sheet 10 063
10.2-21
Type SL Vacuum Contactor Stab-in with Wheels, Fuses, and Line and Load Fingers
See Page 10.1-4 for detailed information on current limiting fuses. See Page 10.1-21 for detailed information on contactor-fuse coordination.
i ii 1 2 3 4
Roll-Out Wheels
5 6 7 8 9 10 11 12 13
1/4 Turn Door Latch Top and Bottom External Motor Protection Relay (optional) Indicating Lights and Pushbuttons
14 15 16 17 18 19 20 21
The Device Panel and optional Eaton MP Series Motor Protection Relays t in the same size low voltage door cutout. The standard SC 9000 keypad can be removed for plug-in of a laptop via a serial connection. A standard viewing window allows visual verication of the AMPGARD SC 9000 AFD status. The low voltage control panel is behind the low voltage door and is completely isolated from the medium voltage compartment. The medium voltage door is locked closed and interlocked with the isolation switch.
CA08104001E
CHS Controls AB
10.2-22 Motor Control (AMPGARD)Medium Voltage Adjustable Frequency Drives Component Details
General Description
September 2011
Sheet 10 064
i ii 1 2 3
Pre-Charge Circuit
SC 9000 Options
Integrated Control-Gear Under One Main Bus Options (see CAG Tab 10)
4 5
Patented SC 9000 Pre-Charge Circuit
6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Unlike other pre-charge methods, the innovative pre-charge circuit in the AMPGARD SC 9000 protects the transformer, rectier and DC bus components from high in-rush currents. The design uses the control power circuit for DC link capacitor charging. This feature eliminates the risk of component or transformer failure during the pre-charge cycle and lengthens the life of the affected components.
AMPGARD main/feeder breaker MEF main/feeder breaker VCPW main/feeder breaker Incoming line section Load break switches Output contactor Full voltage non-reversing contactor bypass Reduced voltage solid-state bypass Reduced voltage autotransformer bypass Reduced voltage primary reactor bypass Full voltage non-reversing contactor additional starters Reduced voltage solid-state additional starters Reduced voltage auto-transformer additional starters Synchronous starters Classic AMPGARD transition
Powerware UPS control power backup (see Tab 39, Section 39.2) Eaton MP-3000 motor protection relay with RTDs (see Tab 4, Section 4.2) Eaton MP-4000 motor protection relay with RTDs (see Tab 4, Section 4.2) Eaton Power Xpert meters (see Tab 3) Eaton EMR-4000 motor protection relays with RTDs Eaton EMR-5000 motor protection relays with RTDs Redundant fans with automatic switchover
Communications Options
Enclosure Options
NEMA 1 Gasketed is standard and the only enclosure option at this time. If an outdoor installation is required, Eaton can supply the AFDs and other electrical equipment in a modular building called an Integrated Power Assembly (see CAG Tab 38).
Johnson Controls N2 Modbus TCP Modbus PROFIBUS DP DeviceNet BACnet CANopen LonWorks EtherNet/IP
Output Filters
Drive output lters are recommended for longer cable lengths between the drive and motor. Table 10.2-2. Recommended Output Filter Application
Motor Type Motor Lead Length (ft) dv/dt Filter Non-inverter duty rated Inverter duty rated Over 100 ft Over 300 ft Sine Filter Over 500 ft Over 1000 ft
Seismic Certication
SC 9000 AFDs are seismically tested per the requirements of the 2009 International Building Code (IBC). SC 9000 AFDs require the use of special keyed door latches on the medium voltage doors to ensure that the doors do not open during a seismic event.
CA08104001E
CHS Controls AB
September 2011
Sheet 10 065
Motor Control (AMPGARD)Medium Voltage 10.2-23 Adjustable Frequency Drives Optional Output Filters and Reactors
Layout Dimensions
Layout Dimensions
DVDT Filter 2.00 (50.8) 23.80 (604.5) 2.00 (50.8) 12.27 (311.7) 32.47 (824.7) 7.00 (177.8) 50.00 (1270.0) 6.00 (152.4) 36.00 (914.4) Top View 40.00 (1016.0) Top View Sine Filter 2.00 (50.8) 2.00 (50.8) Detail Notes: A - 0.875 dia. typ. 4 holes. Mounting studs to extend a maximum of 2.00 inches (50.8 mm) above grade. D - 90 door swing requires: 12.00 inches (304.8 mm) for 12.00 inch (304.8 mm) wide structure, 18.00 inches (457.2 mm) for 18.00 inch (457.2 mm) wide structure, 24.00 inches (609.6 mm) for 24.00 inch (609.6 mm) structure, 36.00 inches (914.4 mm) for 36.00 inch (914.4 mm) wide structure, 40.00 inches (1016.0 mm) for 40.00 inch (1016.0 mm) wide structure, 32.50 inches (825.5 mm) for 65.00 inch (1651.0 mm) wide drive structure. E - HV conduit space, load. F - HV conduit space, line only. G - LV conduit space only. J - Load terminals located on right-hand side of enclosure. Y - Tolerances: 0.00 inches (0.0 mm) +0.25 inches (6.35 mm) per structure. Z - Conduits to extend a maximum of 2.00 inches (50.8 mm) into structure.
i ii 1 2 3 4 5
PH A PH B PH MAIN C BUS
E
2.63 (66.8)
26.67 (677.4)
50.00 (1270.0)
K4
K16
6 7
DVDT Filter
Sine Filter
6.75 (171.5)
6
4.38 (111.3)
8
46.88 (1190.8) 80.00 (2032.0)
9 10
Ground Bus 1 36.00 (914.4) Shipping Section 1 1875 lbs (851 kg) 3.00 (76.2) 2.40 (61.0) 2 40.00 (1016.0) Shipping Section 2 2560 lbs (1162 kg)
1.45 (36.8) 22.85 (580.4) 50.00 (1270.0) Main Bus End 1200A 0.25 x 4.00 1/ph 0.75 (19.1)
11 12 13 14
0.25 (6.4)
49.00 (1244.6)
Main Bus End 1000A 0.25 x 3.00 1/ph 0.75 (19.1) Note A
Note A 21.50 (546.1) 43.00 (1092.2) 22.00 (558.8) 31.00 (787.4) 2.50 (63.5) 36.00 (914.4) Front 35.00 (889.0) 2.50 (63.5) 44.00 (1117.6)
3.00 (76.2) 1.50 (38.1) 0.25 (6.4) 0.437 x 0.688 0.75 Slot (19.1)
15 16 17
E
Front
Main Bus End 2000A 0.25 x 4.00 2/ph 0.75 (19.1) 4.00 (101.6) 0.437 x 0.688 0.75 Slot (19.1) 2.50 (63.5) 0.50 (12.7)
Ground Bus End 600A 0.25 x 2.00 3.63 Inches from Each Side of the Structure 0.562 Dia. Hole
C L
40.00 (1016.0)
0.50 (12.7)
2.00 (50.8)
0.25 (6.4)
18 19 20 21
Varies for sine (depends on option), 46.88 (1190.8) standard, dv/dt 57.88 (1470.2). 10.92 (277.4) sine. 9.00 for dv/dt.
Figure 10.2-21. AMPGARD SC 9000 AFD Output Filter Maximum Dimensions and Incoming Line LayoutsDimensions in Inches (mm)
CA08104001E
CHS Controls AB
10.2-24 Motor Control (AMPGARD)Medium Voltage Adjustable Frequency Drives Technical Data and Ratings
Technical Data
September 2011
Sheet 10 066
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Technical Data
Table 10.2-3. Design Specications
Description Power rating Motor type Input voltage rating Input voltage tolerance Power loss ride-through Input protection Input frequency Input power circuit protection Input impedance device Output voltage NEMA 3006000 hp Induction and synchronous 2400V15 kV 10% of nominal 5 cycles (Std.) Metal oxide varistor 50/60 Hz, 5% Contactor/fuses Isolation transformer 02400V 03300V 04160V PWM IGBT NEMA 1 0 to 40C 40 to 70C 95% noncondensing 03300 ft 2006 IBC UL, IEEE, CSA Air-cooling advanced heat pipe technology 25 watts/hp >0.96 IGBTs 12 12 12 PIV 3300V 6500V 6500V 24-pulse PWM Diode Non-rupture, non-arc Air-cooled Sinusoidal current/voltage 0.1% without tach feedback 1120 Hz Standard 9798% <75 dB (A) Yes IEC 1504313 kW Induction 2400/3300/4160V 10% of nominal 5 cycles (std.) Metal oxide varistor 60 Hz, 5% Contactor/fuses Isolation transformer 02400V 04160V PWM IGBT IP20 0 to 40C 40 to 70C 95% noncondensing 01000 m 2006 IBC IEC Air-cooling advanced heat pipe technology 2527 watts/hp >0.96 IGBTs 12 12 12 PIV 3300V 6500V 6500V 24-pulse PWM Diode Non-rupture, non-arc Air-cooled Sinusoidal current/voltage 0.1% without tach feedback 1120 Hz Standard 9798% <75 dB (A) Yes
Inverter design Inverter switch Enclosure Ambient temperature Storage and transport temperature Relative humidity Altitude (without derating) Seismic Standards Cooling Average watts loss Input power factor Number of inverter IGBTs 2400V 3300V 4160V IGBT PIV rating 2400V 3300V 4160V Rectier designs Rectier switch Rectier switch failure mode Rectier switch cooling Output waveform to motor Speed regulation Output frequency range Service duty rating Typical efciency Noise level Flying start capability
CA08104001E
CHS Controls AB
September 2011
Sheet 10 067
Motor Control (AMPGARD)Medium Voltage 10.2-25 Adjustable Frequency Drives Technical Data and Ratings
Technical Data
Table 10.2-7. SC 9000 Frame D See Pages 10.2-9 and 10.2-11 and Figures 10.2-4 and 10.2-5
2400/60 Hz VT FLA 448 504 561 hp 2000 2250 2500 3300/50 Hz VT FLA 360 400 440 480 hp 2250 2500 2750 3000 4160/60 Hz VT FLA 403 434 461 493 527 558 hp 3250 3500 3750 4000 4250 4500
i ii 1 2 3 4 5 6
4160/60 Hz CT FLA 279 310 341 372 403 hp 2250 2500 2750 3000 3250
2400/60 Hz CT FLA 69 80
hp 300 350
7 8 9 10 11 12 13 14 15
Table 10.2-5. SC 9000 Frame B See Page 10.2-5 and Figure 10.2-2
2400/60 Hz VT FLA 134 156 178 201 223 hp 600 700 800 900 1000 3300/50 Hz VT FLA 128 144 160 200 240 hp 800 900 1000 1250 1500 4160/60 Hz VT FLA 124 155 186 217 248 hp 1000 1250 1500 1750 2000
2400/60 Hz CT FLA hp
2400/60 Hz CT FLA 91 103 114 134 156 hp 400 450 500 600 700
3300/50 Hz CT FLA 96 112 128 144 160 hp 600 700 800 900 1000
4160/60 Hz CT FLA 89 101 114 124 155 hp 700 800 900 1000 1250
VT = Variable Torque (110% overload for 1 minute every 10 minutes) CT = Constant Torque (150% overload for 1 minute every 10 minutes)
Table 10.2-6. SC 9000 Frame C See Page 10.2-7 and Figure 10.2-3
2400/60 Hz VT FLA 279 335 390 hp 1250 1500 1750 3300/50 Hz VT FLA 280 320 hp 1750 2000 4160/60 Hz VT FLA 279 310 341 372 hp 2250 2500 2750 3000
16 17 18 19 20 21
CA08104001E
CHS Controls AB
10.2-26 Motor Control (AMPGARD)Medium Voltage Adjustable Frequency Drives Technical Data and Ratings
Technical Data
Table 10.2-9. Typical Drive Efciency, Power Factor and Harmonics
Description Load (%) 25 50 < 0.86 1.00% >5% 93.84% < 0.86 1.00% 2.30% 95.32% 0.98 1.00% 2.30% 96.33% 75 < 0.86 1.05% >5% 94.93% < 0.86 1.05% 2.40% 96.02% 0.99 1.05% 2.40% 96.74% 100.00 0.98 1.10% 5.00% 95.34% 0.98 1.10% 2.50% 96.32% 0.99 1.10% 2.50% 96.84%
September 2011
Sheet 10 068
i ii 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Speed 50%
Input PF (1) Input THD (V) Input THD (I) Efciency (%) < 0.86 0.90% >5% 90.52% < 0.86 0.90% 2.30% 93.05% < 0.86 0.90% 2.30% 94.85%
Speed: 75%
Input PF (1) Input THD (V) Input THD (I) Efciency (%)
Speed: 100%
Input PF (1) Input THD (V) Input THD (I) Efciency (%)
CA08104001E
CHS Controls AB