1600AF MCCB
For power distribution
- The highest breaking capacity - Optimum coordination technique (Cascading & discrimination) - Powerful engineering tools
For protection of motor & its control device
MCCB
OCR
Accessory
Ics: 100(75)%Icu
Icw: 25kA/1s
TS1600 Rating
Type Ampere frame Pole Rated current,(A) In -5~40C 50C 65C Rated insulation voltage, (V) Rated impulse withstand voltage, (kV) Rated operational voltage, (V) Rated short-circuit breaking capacity IEC60947-2 Rated ultimate short-circuit (sym) breaking capacity, (kA) (Icu) AC50/60Hz 220/240V 380/415V 440V/460V 480/500V 660/690V DC 250V 2P 500V 2P 750V 3P Rated service breaking capacity, (Ics) Rated short-circuit making capacity, (kA) (Icw) Overriding instantaneous protection Isolation Category Mechanical life (operations) (Life cycle) Electrical life (operations) 440V 690V Pollution degree Dimension (mm)
a d c2 c1
TS1000 1000 3, 4 800, 1000 800, 1000 800, 1000 1000 8 AC50/60Hz DC N 55 50 50 40 35 100% 1s 3s kA peak 25 50 B In/2 In In/2 In a (3p/4p) b c1
b
TS1250 1250 3, 4 1250 1250 1240 1000 8 690 L 200 150 130 100 50 100% 12 A 4000 3000 3000 2000 N 55 50 50 40 35 100% 25 50 B 10000 5000 4000 3000 2000 3 210/280 327 155.5 162.7 185.3 13 16.8 5000 4000 3000 2000 B B H 75 70 65 50 45 75% 25 50 N 55 50 50 40 35 -
TS1600 1600 3, 4 1600 1560 1420 1000 8 690 H 75 70 65 50 45 75% 25 50 B 10000 5000 2000 2000 1000 3 5000 2000 2000 1000
Ui Uimp Ue
690 H 75 70 65 50 45 75% 25 50 B 10000 6000 5000 4000 2000 6000 5000 4000 2000 3
%Icu AC50/60Hz
100% 25 50
c2 d Weight (kg) 3P 4P
Ordering
MCCB
TS1600
Ampere frame TS 1000 1250 1600 N H L NA
N
Type Normal High Current Limiting Switchdisconnector
1600A
Rated current 800A 1000A 1250A 1600A
3P
L R
Externals
Current protection
L / S / I / G / Thermal
Other protection
Current (R / S / T / N)
Measurement function
L / S / I / G / Thermal(Continuous) ZSI(Protective coordination) Earth leakage(Option) Over/Under current Over/Under frequency Unbalance(Voltage/Current) Reverse power 3 Phase Voltage/Current RMS/Vector Power(P, Q, S), PF(3-Phase) Energy(Positive/Negative) Frequency, Demand
P type P type
Fine adjustment
Power supply
Fine adjustment for long/short time delay/instantaneous/ ground Overload protection relays P type : DO (Alarm) (Ground fault is not available when using Pre trip alarm) 3DO (Fixed) 3DO (Programmable) P type L, S/I, G Alarm Trip, Alarm, General Compliance with IEC60255-3 P type SIT, VIT, EIT, DT Modbus/RS-485 Modbus / RS-485 Modbus / RS-485 Profibus-DP Profibus-DP Profibus-DP Self Power Self Power AC/DC 100~250V AC/DC 100~250V - Power source works over 30% - Power source works over 30% DC 24~60V DC 24~60V current of In (one pole) current of In (one pole) Basic protection function(L / S / I / G) - External power source are is still under normal operation required for comm. without control power. AC/DC 100~250V DC 24~60V Available Available Available Available Long time delay N type N type N type Short time delay/ Instantaneous Ground fault 10 records 256 records 256 records (Fault/Current/Date and Time) (Fault/Current/Date and Time) Last fault wave recording (3 Phase) 256 records(Content, Status, Date) P type Reset button Reset, Menu A type A type
3 Phase Voltage/Current RMS/Vector Power(P, Q, S), PF(3-Phase) Energy(Positive/Negative) Frequency, Demand Voltage/Current harmonics (1st~63th) 3 Phase Waveforms THD, TDD, K-Factor P type
Trip relay
G
Ground fault + L/S/I/G
* L/S/I/G configuration as standard -with LED indicators -without output contacts * Ground fault system by vector sum
A A Ammeter G Z E C K X
Ground fault
G 0 1 2 5 6 7 Without comm. + Earth leakage (<30A) Without comm. + Earth leakage (>30A) Comm. Comm. + Earth leakage (<30A) Comm. + Earth leakage (>30A)
0 Self-Power, 60Hz AC/DC 100V~250V, 60Hz DC 24V~60V, 60Hz Self-Power, 50Hz AC/DC 100V~250V, 50Hz DC 24V~60V, 50Hz
* L/S/I/G configuration as standard * Ground fault system by vector sum(G,C) * Earth leakage system - Z,K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF) - E,X: External CT - Private ZCT applied(faullt current >30A) * Comm. and output contacts DO NOT work under self-power condition.
P P Power meter C K X A
Ground fault + Com
C 1 2 6 7 Comm. + Earth leakage (<30A) Comm. + Earth leakage (>30A) Comm. + Pre-trip alarm
1 AC/DC 100V~250V, 60Hz DC 24V~60V, 60Hz AC/DC 100V~250V, 50Hz DC 24V~60V, 50Hz
* L/S/I/G configuration as standard * Ground fault system by vector sum * Earth leakage system - K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF) - X: External CT - Private ZCT applied(faullt current >30A) * Applicable to generator protection purpose
S S Supreme meter C K X A
Ground fault + Com
C 1 2 6 7 Comm. + Earth leakage (<30A) Comm. + Earth leakage (>30A) Comm. + Pre-trip alarm
1 AC/DC 100V~250V, 60Hz DC 24V~60V, 60Hz AC/DC 100V~250V, 50Hz DC 24V~60V, 50Hz
* L/S/I/G configuration as standard * Ground fault system by vector sum * Earth leakage system - K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF) - X: External CT - Private ZCT applied(faullt current >30A) * Applicable to generator protection purpose
Note) 1. L/S/I/G configuration as standard 2. Ground fault, earth leakage and pre-trip alarm functions are alternative. 3. The functions like Metering, Communication, ZSI, Remote reset and Digital output are NOT available only under Self-power condition. 4. Voltage module should be required for P and S types(supplied seperately)
Characteristic curves
500
Isd = 1.5...10 Ir
200
200 100 50 40 30 20 12 10
100 50 40 30 20 20 10
tr = 0.5...20s
8 4 2 1
t(s)
5 4 3 2 1
t(s)
5 4 3 2 1
0.5 0.4 0.3 0.2 0.4 0.3 0.2 0.1 0.4 0.3 0.2 I2t OFF 0.1 0.1 0.05 I2t ON 0.4 0.3 0.2
0.1 0.05
0.05
0.02 0.01
0.02 0.01
0.5
0.7
10
0.5
0.7
10
20
Ir
Ir
IDMTL
50 40 30 20 Ig = 0.2...1 In 10
t(s)
1 I2t ON
t(s)
50
SIT
0.1
0.1
0.05
0.05 2 Ii = 2...15 In
0.02
0.5
0.7
10
0.1
0.2
0.3
0.4 0.5
0.7
0.05
0.07
10
In
Ir
20
4 5
0.01
0.05
20
Dimensions
Front Type
Insulation barrier 250 25 Plate protection Mounting hole 320 115.7
11
25
5.5
5.5
C L
C L
C L
37.2
C L
C L
C L
37.2
70 199 210
70 Trip button
70
70 269 280
47.5 70 199 210 70 Trip button 47.5 115.7 149.8 152.5 155.5 162.7 190.6
16.5
Rear Type
210 199 280 269 114.7 84 43.5 14
16.5
Panel drilling
3P 4P
4- 5.5 or M5
4- 5.5 or M5
283.5
15
283.5
5.5
283.5
Mounting hole
5.5
11
11
C L
C L
C L
37.2
42 135 372
212 258
212 258
212
199
269
31
31
25 44 70 70
25 44 Insulation barrier 70 70 70
95
15
15
199
95
119
119
67
67
200
200
LS constantly endeavor to improve our products so that information in this catalog is subject to change without notice.
HEAD OFFICE LS Tower, 1026-6 Hokyeh 1dong, Dongan-gu, Anyang, Kyonggi-Do, 431-848, Korea Tel. (82-2)2034-4887, 4873, 4918, 4148 Fax. (82-2)2034-4648
Susol 1600AF MCCB / October.2010 Printed in korea STAFF