Sunteți pe pagina 1din 4

THREE-PHASE SYNCHRONOUS GENERATOR

MJB 355 MA 4
4 POLES
50 Hz-1500 min-1 / 60 Hz-1800 min -1

CONTINUOUS DUTY
AMBIENT TEMPERATURE 40C
TEMPERATURE RISE H
INSULATION CLASS H
POWER FACTOR 0,8
FREQUENCY
VOLTAGE

WINDING DATA
Winding code
Number of leads
Winding pitch
50

Hz
Star series
Star parallel

RATING

EFFICIENCY (%) @ 0,8 p.f.

EFFICIENCY (%) @ 1,0 p.f.


SHORT CIRCUIT RATIO
REACTANCES (%)
Direct axis synchronous
Quadrature axis synchronous
Direct axis transient
Direct axis subtransient
Quadrature axis subtransient
Negative sequence
Zero sequence
TIME CONSTANTS [s]
Open circuit (T'do)
Transient (T'd)

380
V
190
kVA 680
kW 544
4/4 94,4
3/4 95,2
2/4 95,5
4/4 95,6
3/4 96,2
2/4 96,4
0,32

400
200
680
544
94,7
95,3
95,4
95,8
96,3
96,4
0,35

415
208
680
544
94,8
95,3
95,4
95,9
96,3
96,4
0,38

440
220
680
544
94,8
95,2
95,4
95,9
96,2
96,3
0,42

380
190
700
560
94,3
94,8
95,0
95,5
95,9
96,1
0,26

416
208
740
592
94,6
95,1
95,2
95,7
96,1
96,2
0,29

60
440
220
775
620
94,9
95,3
95,4
96,0
96,3
96,4
0,31

460
230
805
644
95,0
95,4
95,5
96,1
96,3
96,4
0,33

480
240
825
660
95,1
95,4
95,5
96,1
96,4
96,4
0,35

xd
xq
x'd
x"d
x"q
x2
x0

290
160
24,0
12,2
14,5
13,4
3,5

270
150
22,3
11,3
13,5
12,4
3,3

240
130
19,8
10,1
12,0
11,1
2,9

395
220
32,8
16,7
19,8
18,3
4,8

350
195
29,0
14,7
17,5
16,2
4,2

330
180
27,1
13,8
16,4
15,1
4,0

310
170
25,8
13,1
15,6
14,4
3,8

295
160
24,3
12,3
14,7
13,5
3,5

320
175
26,6
13,5
16,1
14,8
3,9

1,95 Subtransient (T''d)


0,16 Armature (Ta)

MECHANICAL CHARACTERISTICS
D-end bearing/Lubrication
N-end bearing/Lubrication
Weight (IM B34) [kg]

6322
6317
1800
11,69
2250
IC 01
0,93
IP 23
B2
CW

Inertia (J) (IM B34) [kgm ]


-1
Overspeed [min ]
Method of cooling
3

Cooling air required [m /s] @ 50/60 Hz


Degree of protection
Type of construction available
Direction of rotation
OTHER DATA
Phase resistance [m] @ 20 C - Star series
Overloads
3-phase short circuit current
Voltage regulation accuracy

0,016
0,022

2RS C3 / Prelubricated
2RS C3 / Prelubricated

/ 1,12
- SAE / IM B34

4,0
10% for 1 hour
>= 300% (3 In)
+/- 0,5 % (in steady state condition,
speed from -2% to +5%, p.f. from 0,8 to 1)
EN 55011 Class B Group 1
< 2%
< 2% (at no load)

Radio interference
Wave form THF
Total harmonic content

STANDARDS
IEC 60034-1; CEI 2-3; BS 4999-5000; VDE 0530; NF 51-100,111; OVE M-10, NEMA MG 1.22.
Data and Technical Specification are subject to change in order to update or improve the products, without prior notice

SIN.DT.024.5

M0
12
2/3

1/4

THREE-PHASE SYNCHRONOUS GENERATOR

MJB 355 MA 4
Typical efficiency curves

50 Hz - 1500 min

-1

380 V

Efficiency [%]

98

96
1,0 p.f.
0,8 p.f.

94

92
0

0,25

0,5

0,75

1,25

Load [p.u.]

400 V

Efficiency [%]

98

96

1,0 p.f.
0,8 p.f.

94

92
0

0,25

0,5

0,75

1,25

Load [p.u.]

415 V

Efficiency [%]

98

96

1,0 p.f.
0,8 p.f.

94

92
0

0,25

0,5

0,75

1,25

Load [p.u.]

440 V

Efficiency [%]

98

96

1,0 p.f.
0,8 p.f.

94

92
0

0,25

0,5

0,75

Load [p.u.]

Data and Technical Specification are subject to change in order to update or improve the products, without prior notice

SIN.DT.024.5

2/4

1,25

THREE-PHASE SYNCHRONOUS GENERATOR

MJB 355 MA 4
Typical efficiency curves

60 Hz - 1800 min

-1

380 V

Efficiency [%]

98
96

1,0 p.f.

94

0,8 p.f.

92
0

0,25

0,5

0,75

1,25

Load [p.u.]

416 V

Efficiency [%]

98
96

1,0 p.f.

94

0,8 p.f.

92
0

0,25

0,5

0,75

1,25

Load [p.u.]

440 V

Efficiency [%]

98
1,0 p.f.

96

0,8 p.f.

94
92
0

0,25

0,5

0,75

1,25

Load [p.u.]

460 V

Efficiency [%]

98
1,0 p.f.

96

0,8 p.f.

94
92
0

0,25

0,5

0,75

1,25

Load [p.u.]

480 V

Efficiency [%]

98
1,0 p.f.

96

0,8 p.f.
94
92
0

0,25

0,5

0,75

Load [p.u.]

Data and Technical Specification are subject to change in order to update or improve the products, without prior notice

SIN.DT.024.5

3/4

1,25

THREE-PHASE SYNCHRONOUS GENERATOR

MJB 355 MA 4
Locked rotor motor starting curves (*)
-1

50 Hz - 1500 min
50

Voltage Dip (%)

40

380 V
400 V
415 V
440 V

30

20

10

0
0

200

400

600

800

1000

1200

1400

1600

1800

P [kVA]

-1

60 Hz - 1800 min
60

50

Voltage Dip (%)

40

380 V
416 V
440 V

30

460 V
480 V

20

10

0
0

500

1000

1500

2000

P [kVA]

P = Pn x (Is / In) / (cosn x n)


(*): A coefficient of 0,85 must be applied to the voltage dip if the load has a power factor equal or greater than 0,8.

Data and Technical Specification are subject to change in order to update or improve the products, without prior notice

SIN.DT.024.5

4/4

2500