Excitation
Ready to start/no fault Emergency OFF Common Trip &
DB3.DBX4.2 DB3.DBX4.3
PROFIBUS DP PROFIBUS DP
(50) (51)
Drive OFF
Start command from customer or OP177B OP177B: Drive ON Life-bit & Netcontrol Main contactors ON 415V for converter ON 30s Command MBC ON Feedback MBC ON
Life-bit
-X20:101,102
hardwired
MCC
+1.CC-X4:1-5
MBC
(48)
Internal routines
-X20:31, 32 -X20:25, 26
MBM
(63) (59)
2s
Remote fault reset VFD output contactor acknowledge Field current reference value for MASTERDRIVE Field current actual 4...20mA Enable MASTERDRIVE set Run request Start
DB3.DBX141.7 DB3.DBX141.3
PROFIBUS DP PROFIBUS DP
Internal settings (field current setpoint has to be true) VFD control the motor field current Field current reference 4...20mA
-X10:1, 2 -X10:3, 4
+1.CC-X3:4, 5 +1.CC-X3:13, 14
DB3.DBX140.0 DB3.DBX140.2
PROFIBUS DP PROFIBUS DP
(48) (50)
VFD speeds up the drive and matches frequency, voltage and phase angle After the synchronism is achived
DB3.DBX5.3
The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved.
(59)
MBL
+1.CC-X100:1, 2
+1.CC-X2:19, 80
DB3.DBX140.0 DB3.DBX140.3
PROFIBUS DP PROFIBUS DP
(48) (51)
-X20:33, 34 -X20:27, 28
hardwired hardwired
MBM
reset Up-transfer request O& 5M Command MBC OFF Feedback MBC OFF 1M 415V for converter OFF Emergency OFF
DB3.DBX141.5 DB3.DBX5.4
PROFIBUS DP PROFIBUS DP
(61) (60)
+1.CC-X2:61, 59, 62
MBC
-X20:101,102
hardwired
MCC
+1.CC-X4:1-5
-X20:75, 76
hardwired
+1.CC-X2:1, 2
Borl
Orig./Repl. f./Repl. by
SIEMENS AG
I IS IN E&C PPC
Start-up sequence
(3) E10542-H1478-S101-A
A Emergency OFF Common Trip 22.08.08 Ka Date Drawn Main contactors OFF Emergency OFF Disable MASTERDRIVE Motor is ON Command MBL OFF Feedback MBL OFF 08.08.2008 Kartes Kraus Drive OFF Stop command from customer or OP177B OP177B: Drive OFF
The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved. Confi a titre de sescret dentreprise. Tous droits rserves Confiado como secreto industrial. Nos reservamos todos los derechos Comunicado como segredo empresarial. Reservados todos os direitos
Weitergabe sowie Vervielfltigung dieser Unterlage, Verwertung und Mitteilung ihres Inhalts nicht gestattet, soweit nicht ausdrcklich zugestanden. Zuwiderhandlungen verpflichten zu Schadenersatz. Alle Rechte vorbehalten, insbesondere fr den Fall der Patenterteilung oder GM-Eintragung.
Excitation
Borl
-X20:49, 50 hardwired
Orig./Repl. f./Repl. by
-X20:39, 40 hardwired
-X20:45, 46 hardwired
SIEMENS AG
MBL MBL Stop sequence Perfect Harmony VFD
=
I IS IN E&C PPC
+ Blatt 2 2 Bl.
(3) E10542-H1478-S101-A