Class 6055
Product Description
RATINGS
16.5 to 27 kV 1200-2000 Amperes Continuous Ratings 16, 25 and 40 kA Symmetrical Interrupting Capacity 125 kV BIL, peak (impulse) dielectric withstand 60 kV, rms 1 minute 60 Hz dielectric withstand NEMA Type 1 Indoor enclosure
STANDARD FEATURES
Metal-Clad Switchgear as dened by ANSI C37.20.2 includes: Removable (Drawout) Circuit Breaker Fully Compartmented Construction Grounded Metal Barriers enclose all live parts Automatic Shutters over primary contacts Fluidized-Bed Epoxy Insulated Bus Mechanical Interlocks Disconnect Type Voltage Transformers Fixed Control Power Transformer with Drawout Primary Fuses Grounded Breaker Truck in and between Test-Disconnected and Connected Positions Low Voltage Instrument/Control Compartment isolated from primary voltage areas
2
2000 Schneider Electric All Rights Reserved 1/00
Dimensions
27 kV LAYOUT DIMENSIONS/CONFIGURATION GUIDE
Vertical sections are 36 wide
95.12
(242)
1.75
(44)
95.12
(242)
1.75
(44)
36.35
(923)
36.35
(923)
1.00
(25)
58.25
(1480)
16.06
(408)
1.00
(25)
58.25
(1480)
16.06
(408)
110.50
(2807)
110.50
(2807)
95.12
(242)
1.75
(44)
95.12
(242) Bus to Incoming Line
36.35
(923)
1.00
(25)
58.25
(1480)
16.06
(408)
(20)
.80
58.25
(1480)
110.50
(2807)
110.50
(2807)
95.12
(242)
95.12
(242) Bus to Incoming Line
1.00
(25)
58.25
(1480)
110.50
(2807)
110.50
(2807)
Blank/AUX Section
3
1/00 2000 Schneider Electric All Rights Reserved
Ratings
VR 27 kV Vacuum Circuit Breakers Rating Table on Symmetrical Current Rating Basis
Description Preferred Ratings per ANSI C37.06-1997 q Insulation Level Rated Withstand Rated PermisRated VoltInterImpulse sible Max. age rupting Low 1.2 x Tripping Voltage Range Time Freq. 50 s Delay kV rms Factor k Cycles kV kV Y rms Crest Sec. a
27 27 27 27 27 27 1.0 1.0 1.0 1.0 1.0 1.0 3 3 3 3 3 3 60 60 60 60 60 60 125 125 125 125 125 125 2 2 2 2 2 2
Rated Rated Short (Ref.) Cont. Circuit Three Current Current Phase 60 Hz (at rated MVA A rms Max. kV) kA rms
Rated Transient Current Values Recovery Voltage Rated Crest Voltage E2 kV Crest
51 51 51 51 51 51
16 16 25 25 40 40
q a f
Also tested per IEC 56 These values apply with circuit breaker in or out of enclosure. Close and Latch Rating (Momentary) Amperes rms = 2.7 k (Rated Short Circuit Current)
Breaker Identication
36.00
(914) Rear Aisle (114) (203)
4.50
27.00
(686) (508)
(114) (203)
4.50
8.00
20.00
8.00
VR
Top Breaker Below Bottom Circuit Breaker Above (Conduit Area)
27
025
12
Continuous Current Rating kA Rating Voltage Rating Circuit Breaker Type
3.50
(89)
(229)
9.00
53.30
11.00
(279)
4.00
28.00
(711)
(102)
4.00
Weight (Approximate)
Section (less circuit breaker) 2600 lbs. (1179 kgs.) 600 lbs. (272 kgs.) 630 lbs. (286 kgs.)
110.50
(2807) (6) .75 Dia. Mounting Holes Recommended 4.00 Mounting Channels (3) Places (By Customer)
54.70
(1389) (203)
8.00
1.00 2.00
(51) (25) Door
1.75
(203)
8.00
(44)
72.00 (38)
1.50 2.50
(64)
34.20
(869) (914)
(23)
.90
(561)
2.00
64.00
(23)
.90
36.00
NOT FOR CONSTRUCTION (64) Control Conduit Area (Top)
2.50
Square D Company 330 Weakley Road Smyrna, TN 37167 615-459-5026 1-888 Square D (1-888-778-2733) www.squared.com