Documente Academic
Documente Profesional
Documente Cultură
General Specications
GS 33K15P10-50E
GENERAL
For off-site oil facility operation system (arrival of goods, transport, mixing, delivery), the function blocks are available for ow rate control, batch control, and mixing control.
FUNCTION SPECIFICATIONS
This document describes about LFS8620 Off-site Block Package which provides off-site block with CENTUM VP. Flow rate control block (FSBSET) Blend master control block (BLEND) The combined off-site block, motor operation block (MC-2, MC-3) and switch instrument block (S10) implements offsite batch delivery control and blend delivery control. FlowRate Control Block The control block is used for batch delivery control and component owrate control on mixing control. Input Processing Functions: Compensating computations and totalizing processing are applied to the pulse train input or analog input, and then the instantaneous ow rate (PV) is calculated. Control Functions: Required types of control are conducted according to the control steps. Output Processing Functions: The output is sent to the control valve (process output), or to another control block.
Compensation after temperature compensation Compensation before temperature compensation Control calculations Accumulated-deviation PI control algorithm Instantaneous-deviation PI control algorithm
COX
DENS
VCF
CCY
SIMM
Simulation
PV value conversion digital filtering Output processing
Temperature compensation
PV
MV
O U T
DSM
SV
Analog
SUM1
SUM
B-MODE V-MODE
C-MODE
BSET
ZONE CMND
SUM2
TMI
BLEND
F01E.ai
Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel.: 81-422-52-5634 Fax.: 81-422-52-9802
GS 33K15P10-50E Copyright Aug. 2011 (YK) 1st Edition Aug. 19, 2011 (YK)
<<Contents>> <<Index>> Brend Master Control Block The control block sends output of each components ow set value, and is used to manage multiple port on mixing control. Input Processing Functions: The BLEND master acquires instantaneous-ow data from component FSBSET or BLEND to summarize and totalize them, and reads ow rate setpoints from port FSBSET or BLEND to obtain the totalized current ow rate setpoint. Component Management Functions: The BLEND master manages the component conguration and monitors for component ow alarms. Port Management Functions: The BLEND master can also provide port batch functions. Control Functions: The BLEND master manages control according to the control step.
DV1 DV2 IOP NPLS OOP EMST
AOF
Release end
ZONE No. 14 data status Control step CMND Operation command PV Control functions
No.1 PV (SUM) No.2 PV (SUM) Release end Instantaneous flow calc. (SUM)
(SUM)
SV
No.1 SV
No.2 SV
No.6 SV
Port FSBSET/BLEND
F02.ai
<<Contents>> <<Index>>
APPLICATION CAPACITY
OPERATING ENVIRONMENT
Hardware Requirements PFCS-H, PFCD-H, AFS10S, AFS10D, AFS20S, AFS20D, AFS30S, AFS30D, AFS40S, AFS40D, AFG10S, AFG10D, AFG20S, AFG20D, AFG30S, AFG30D, AFG40S, AFG40D, AFG81S, AFG81D, AFG82S, AFG82D, AFG83S, AFG83D, AFG84S, AFG84D, AFF50S, AFF50D, AFV30S, AFV30D, AFV40S, AFV40D, AFV10S, AFV10D Software Requirements LFS1100 Control Function for Standard Field Control Station (for RIO), LFS1130 Control Function for Enhanced Field Control Station (for RIO), LFS1300 Control Function for Standard Field Control Station (for FIO), LFS1330 Control Function for Enhanced Field Control Station (for FIO), LFS1350 Control Function for Compact Field Control Station (for FIO), LFS1120 Control Function for Compact Field Control Station, LFS1700 Control Function for Field Control Station (for AFV30/AFV40, Vnet/IP and FIO) or LFS1500 Control Function for Field Control Station (for AFV10, Vnet/IP and FIO). Engineering Requirements LHS5100 or LHM5100 Standard Builder Function
ORDERING INFORMATION
Specify model and sufx codes.
TRADEMARK
CENTUM is a registered trademark of Yokogawa Electric Corporation. Other product and company names appearing in this document are trademarks or registered trademarks of their respective holders.
All Rights Reserved. Copyright 2011, Yokogawa Electric Corporation Subject to change without notice.