Sunteți pe pagina 1din 81

SITRANS F

Electromagnetic Flowmeters
Communication Modules
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions 08/2011
1

Introduction


2
Safety notes

3
Hardware Installation
SITRANS F

4
Connecting
Communication Modules
SITRANS F M MAG 8000
Modbus RTU

5
System integration

6
Function codes

Operating Instructions
7
Technical data

A
Modbus holding registers

B
Appendix
Add-on module for use with flowmeter types
SITRANS F M MAG 8000

08/2011
A5E03409989-01



Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
NOTICE
indicates that an unintended result or situation can occur if the relevant information is not taken into account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.

Siemens AG Order number: A5E03409989 Copyright Siemens AG 2011.
Industry Sector 08/2011 Technical data subject to change
Postfach 48 48
90026 NRNBERG
GERMANY

SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 3
Table of contents

1 Introduction................................................................................................................................................ 5
1.1 Document history...........................................................................................................................5
1.2 Modbus RTU technology ...............................................................................................................6
1.3 Further Information ........................................................................................................................8
2 Safety notes............................................................................................................................................... 9
2.1 Installation in hazardous area........................................................................................................9
3 Hardware Installation............................................................................................................................... 11
4 Connecting .............................................................................................................................................. 13
4.1 Wiring...........................................................................................................................................13
4.2 Closing the device........................................................................................................................15
5 System integration................................................................................................................................... 17
5.1 System integration instructions....................................................................................................17
5.2 Function check.............................................................................................................................17
5.3 Communication parameter settings .............................................................................................18
5.4 Parameter access ........................................................................................................................18
5.5 Commissioning with PDM............................................................................................................19
5.5.1 General instructions .....................................................................................................................19
5.5.2 Commissioning steps...................................................................................................................19
5.5.3 Installing EDD files.......................................................................................................................20
5.5.4 Adding device to network.............................................................................................................21
5.5.5 Configuring the device .................................................................................................................22
5.5.6 Operation .....................................................................................................................................24
6 Function codes ........................................................................................................................................ 25
6.1 Modbus Commands.....................................................................................................................25
6.2 Read coils ....................................................................................................................................26
6.3 Read multiple registers ................................................................................................................28
6.4 Write single coil ............................................................................................................................30
6.5 Write multiple registers ................................................................................................................31
6.6 Report slave ID command ...........................................................................................................34
6.7 Exception handling.......................................................................................................................35
7 Technical data ......................................................................................................................................... 37
Table of contents

SITRANS F M MAG 8000 Modbus RTU
4 Operating Instructions, 08/2011, A5E03409989-01
A Modbus holding registers......................................................................................................................... 39
A.1 Introduction to holding registers.................................................................................................. 39
A.2 MODBUS application settings..................................................................................................... 40
A.3 MODBUS driver settings............................................................................................................. 41
A.4 Menu control ............................................................................................................................... 42
A.5 Sensor characteristics................................................................................................................. 43
A.6 Totalization.................................................................................................................................. 45
A.7 Pulse output ................................................................................................................................ 45
A.8 Service control ............................................................................................................................ 47
A.9 Error messages........................................................................................................................... 47
A.10 Power control .............................................................................................................................. 53
A.11 Consumption statistic.................................................................................................................. 55
A.12 Consumption profile .................................................................................................................... 56
A.13 Leakage statistic ......................................................................................................................... 57
A.14 Datalog........................................................................................................................................ 59
A.15 Consumption readings ................................................................................................................ 68
B Appendix.................................................................................................................................................. 69
B.1 Data type mapping...................................................................................................................... 69
B.2 CRC calculation .......................................................................................................................... 70
Glossary .................................................................................................................................................. 75
Index........................................................................................................................................................ 77

SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 5
Introduction 1

Purpose
The Operating Instructions provide all information necessary for the installation and use of
the Modbus RTU add-on module (FDK:087L4212 or FDK:087L4213), intended for use with
the electromagnetic transmitter type SITRANS F M MAG 8000.

NOTICE
Reduced battery lifetime
The Modbus RTU communication module is designed for use with mains powered device
versions only.
Use of the Modbus RTU communication module with battery-powered device versions will
reduce the expected battery lifetime significantly.

Basic knowledge required
The instructions are not intended to be a complete tutorial on the Modbus RTU protocol, and
it is assumed the end user already has a general working knowledge of Modbus RTU
communication, especially in respect of master station configuration and operation. However
an overview is included in the following section to explain some fundamental aspects of the
protocol.
See also
For more information about SITRANS F M transmitters and sensors, please refer to the
appropriate Operating Instructions available on the flowdocumentation homepage
(http://www.siemens.com/flowdocumentation) or on the SITRANS F literature CD-ROM.
1.1 Document history
The contents of these instructions are regularly reviewed and corrections are included in
subsequent editions. We welcome all suggestions for improvement.
The following table shows the most important changes in the documentation compared to
each previous edition.

Edition Remarks
12/2010 1. edition
Introduction
1.2 Modbus RTU technology
SITRANS F M MAG 8000 Modbus RTU
6 Operating Instructions, 08/2011, A5E03409989-01
1.2 Modbus RTU technology
Modbus RTU is an open, serial (RS-232 or RS-485) protocol based on master/slave or
client/server architecture. The protocol interconnects field equipment such as sensors,
actuators, and controllers and is widely used in both process and manufacturing automation.
The fieldbus environment is the base level group of digital networks in the hierarchy of plant
networks.
Features
The SITRANS F Modbus RTU Communication modules comply with the Modbus Serial Line
Protocol. Among other things this implies a Master-Slave protocol at level 2 of the OSI
model. A node (the master) issues explicit commands to one of the slave nodes and
processes responses. Slave nodes will not transmit data without a request from the master
node, and do not communicate with other slaves.
Modbus is a mono Master system, which means that only one Master can be connected at
the time.
Introduction
1.2 Modbus RTU technology
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 7
Communication modes
Two modes of communication are possible, Unicast and Broadcast.
In unicast mode the Master sends a request to a specific Slave device, and waits a
specified time for a response.

8
5
U
4
2
Slave Slave Slave
Master
re
s
p
o
n
s
e
re
q
u
e
s
t

Figure 1-1 Unicast Mode
In Broadcast mode the master sends out a request to address "0", which means that the
information is for all Slave devices on the network. In Broadcast mode there is no
response from the Slave devices.
8
5
U
4
3
Slave Slave Slave
Master
re
q
u
e
s
t

Figure 1-2 Broadcast Mode
Modbus Frame
The Modbus frame is shown below, and is valid for both requests and responses.
Table 1- 1 Modbus Frame
SLAVE ADDRESS FUNCTION MODE DATA CRC
1 Byte 1 Byte 0 ... 252 Bytes 2 Bytes
Introduction
1.3 Further Information
SITRANS F M MAG 8000 Modbus RTU
8 Operating Instructions, 08/2011, A5E03409989-01
References
For further information, please refer to the following specification and guidelines available at
the Modbus Organisation (http://www.modbus.org/) Website
1. Serial Line Specification & Implementation guide v. 1.0
2. Application Protocol Specification v. 1.1
1.3 Further Information
The contents of these operating instructions shall not become part of or modify any prior or
existing agreement, commitment or legal relationship. All obligations on the part of Siemens
AG are contained in the respective sales contract which also contains the complete and
solely applicable warranty conditions. Any statements contained herein do not create new
warranties or modify the existing warranty.
Product information on the Internet
The Operating Instructions are available on the CD-ROM shipped with the device, and on
the Internet on the Siemens homepage, where further information on the range of SITRANS
F flowmeters may also be found:
Product information on the internet (http://www.siemens.com/flow)
Worldwide contact person
If you need more information or have particular problems not covered sufficiently by the
operating instructions, please get in touch with your contact person. You can find contact
information for your local contact person on the Internet:
Local contact person (http://www.automation.siemens.com/partner)


SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 9
Safety notes 2


CAUTION
Correct, reliable operation of the product requires proper transport, storage, positioning and
assembly as well as careful operation and maintenance. Only qualified personnel should
install or operate this instrument.

Note
Alterations to the product, including opening or improper repairs of the product, are not
permitted.
If this requirement is not observed, the CE mark and the manufacturer's warranty will expire.

2.1 Installation in hazardous area

WARNING
NOT allowed for use in hazardous areas!
Equipment used in hazardous areas must be Ex-approved and marked accordingly!
This device is NOT approved for use in hazardous areas!


Safety notes
2.1 Installation in hazardous area
SITRANS F M MAG 8000 Modbus RTU
10 Operating Instructions, 08/2011, A5E03409989-01

SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 11
3 Hardware Installation

The installation procedure for an add-on module to a MAG 8000 transmitter is as follows:
1. Loosen screws on transmitter top.
2. Remove transmitter top using a screwdriver.
3. Dispose of silica gel bag.
4. Mount the modules on the backside of the MAG 8000 electronics.


Figure 3-1 Hardware installation
5. Use the two supplied 3mm screws and washers to fix the module to the MAG 8000
electronics.
Hardware Installation

SITRANS F M MAG 8000 Modbus RTU
12 Operating Instructions, 08/2011, A5E03409989-01

SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 13
4 Connecting


Note
Shielding
Always shield a Modbus over Serial Line Cable. At one end of each cable its shield must be
connected to protective ground. If a connector is used at this end, the shell of the connector
is connected to the shield of the cable.

Note
Cable specifications
A RS485-Modbus must use a balanced pair (for D0-D1) and a third wire (for the Common).
For the balanced pairs used in an RS485-system, a Characteristic Impedance with a value
between 100 and 120 Ohms must be used.

4.1 Wiring
Connect shield to MAG 8000 enclosure using the cable clamp


Figure 4-1 Cable shield connection
Connecting
4.1 Wiring
SITRANS F M MAG 8000 Modbus RTU
14 Operating Instructions, 08/2011, A5E03409989-01
RS232 connection diagram

Common
Connect shield to enclosure
Shield connected to protective ground

Common
RS485 connection diagram

Common
Connect shield to enclosure
Shield connected to protective ground
Connecting
4.2 Closing the device
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 15

Common
Termination
Bus termination
All RS485-based networks must be terminated correctly to function properly. A termination
must be placed at each end of segment.
The Modbus RTU module can add a 120 ohm termination if a jumper is placed beside
terminals in position "ON".
Termination is set to "ON" from factory.
4.2 Closing the device
1. Replace O-ring to ensure continued IP68 enclosure rating.
Check O-ring for damage or deformity.
Smear O-ring with acid-free lubricating gel.
2. Add new Silica gel bag
Remove plastic bag from new silica gel bag.
Place new silica gel bag on top of battery pack to prevent condensation within meter.
To maintain IP68 enclosure the silica gel bag may not be in contact with the Sylgard.
3. Mount top lid.
4. Fasten screws to reassemble meter completely.
Note
All sealed MAG 8000 CT meters have to be re-verified when sealings (marked "A") have
been broken.


Connecting
4.2 Closing the device
SITRANS F M MAG 8000 Modbus RTU
16 Operating Instructions, 08/2011, A5E03409989-01

NOTICE
Loss of degree of protection
Damage to device if the enclosure is open or not properly closed. The degree of protection
specified on the nameplate or in "Technical data" is no longer guaranteed.
Make sure that the device is securely closed.

See also
Technical data (Page 37)

SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 17
System integration 5
5.1 System integration instructions
This chapter provides information on how to integrate the flowmeter in a Modbus RTU
automation and control system.
The chapter shows the necessary steps in order to put the system into operation. After
finishing the steps, the system is ready to go into normal operation in the Modbus RTU
automation control system.

Note
Storage location
All Modbus settings of the transmitter are stored in the transmitter in a non-volatile memory.

Device name and address
The transmitter is shipped with a default device name and serial number.
All devices are shipped with a temporary address that allows the host to automatically
commission the transmitter. The network address is the current device address used by the
fieldbus.

Note
It is recommended NOT to use the default address in a multi-slave network. It is of great
importance to ensure that no devices have the same address. Otherwise an abnormal
behaviour of the whole serial bus can occur, the master being unable to communicate with
all present slaves on the bus.

5.2 Function check
Before proceeding further, make sure that installation and connection have been performed
successfully.
See chapter "Hardware installation (Page 11)" for installation verification.
See chapter "Connecting (Page 13)" for connection verification.
When the function check has been successfully carried out, the device can be switched on.
System integration
5.3 Communication parameter settings
SITRANS F M MAG 8000 Modbus RTU
18 Operating Instructions, 08/2011, A5E03409989-01
5.3 Communication parameter settings
Effect of changing baudrate or framing
Changing baudrate or framing has effect on the communication as follows:
When changed from the Modbus master, the new settings only have effect after a reset
(PowerUp) of the device or after writing to the "ResetCommunication" coil.
Table 5- 1 Communication parameters
Item Value Description
Device Communication Address 1-247 Device address [Factory setting: 1]
Baud rate 1200, 2400, 4800, 9600, 19200, 38400 Communication speed
[Factory setting: 19200]
Parity
Even, 1 stop bit
Odd, 1 stop bit
None, 2 stop bit
None, 1 stop bit
Communication parameters
[Factory setting: Even, 1 stopbit ]
Interframe Space 35-255 chars The minimum interframe space
between two Modbus RTU messages
in sequence (specified as 3.5
characters) is configurable. Range: 3.5
25 character times. Specified in bytes
times ten.
[Factory setting: 35 ]
Response Delay 0-255 msec. The minimum time from when a slave
receives a request and until it returns a
response. This makes it possible to
send data to slow masters.
[Factory setting: 5 ]
5.4 Parameter access
Write protection
Writable parameters in the MAG 8000 are protected by a software password. Some
parameters with influence on the accuracy or identity of the flowmeter are furthermore
protected by a hardware lock.
For information on how to unlock parameters protected by a hardware lock, refer to the MAG
8000 Operating Instructions.
System integration
5.5 Commissioning with PDM
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 19
Parameter access
When attempting to write a parameter without a password, MAG 8000 will return "Illegal data
address" exception code.
To successfully change a parameter, use the following routine:
1. Write the password to parameter "Meter Access Code" at address 2007. Default
password is "1000"
2. Change the parameter.
When the correct password has been entered, the flowmeter remains "unlocked" for 10
minutes after last communication.
If a parameter is write-protected by a hardware lock, the MAG 8000 will return "Illegal data
address".
5.5 Commissioning with PDM
5.5.1 General instructions
SIMATIC PDM (Process Device Manager) is a software package for configuring,
parameterizing, commissioning and maintaining devices (e.g. transducers) and for
configuring networks and PCs.
Among other features, SIMATIC PDM contains a simple process monitoring of process
values, interrupts and status/diagnosis signals of device.

Note
For instructions on installation and operation of SIMATIC PDM, please refer to the SIMATIC
PDM Getting Started


NOTICE
Infrared communication
Activated infrared communication blocks all communication with a wired Modbus master.
Ensure that no infrared communication is activated before communicating with the wired
Modbus master.

5.5.2 Commissioning steps
In the following it is described how to commission the device with SIMATIC PDM.
The steps are divided into the following sections:
System integration
5.5 Commissioning with PDM
SITRANS F M MAG 8000 Modbus RTU
20 Operating Instructions, 08/2011, A5E03409989-01
1. Install the EDD files (Page 20)
2. Add the device to the communication network (Page 21)
3. Configure the device (Page 22).
Describes the setup of the basic parameters of the flowmeter.
4. Operation (Page 24).
Describes how to view all available process values.
5.5.3 Installing EDD files
Installing EDD files
Procedure for installing PDM device driver consists of the following steps:
Download update from the Internet on MAG 8000 Downloads
(http://support.automation.siemens.com/WW/view/en/19701862/133100) , or copy it from
supplied CD into envisaged folder and unzip file. It is recommended to check that the
EDD is the version valid for the device.
Open "Manage Device Catalog" from Start > SIMATIC > SIMATIC PDM.
Navigate to PDM device driver, select device and click "OK" and driver is installed on PC.
System integration
5.5 Commissioning with PDM
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 21
5.5.4 Adding device to network
Before setting the parameters, it is necessary to configure the MAG 8000 project in PDM.
1. Add the device to SIMATIC Modbus network:
Select "File"->"New"
Type in a project name, e.g. MAG 8000
Right click on "Net" and select "Insert New Object"->"Modbus Net".
Your PC is now added to the Modbus Net, e.g. NOG0482D
Right click on "Modbus Net" and select "Insert New Object"->"Modbus Device".
Click on "Assign" and assign the Modbus device to MAG8000 Advanced or Basic
(Sensors->Flow->Electromagnetic->SIEMENS AG->MAG8000) and click "ok".


Figure 5-1 Assigning Modbus device to network
Rename the device according to the application requirements (max. 32 characters).
2. Set up the communication parameters for SIMATIC Modbus network.
Select "Net"->"Modbus net", right click on "Modbus net" and select "Object Properties"
Select "Connection" and set "data transmission rate" to "19200 Baud" and "Vertical
parity position" to "0 - even"

System integration
5.5 Commissioning with PDM
SITRANS F M MAG 8000 Modbus RTU
22 Operating Instructions, 08/2011, A5E03409989-01

Figure 5-2 MODBUS net Object properties
5.5.5 Configuring the device
Read all parameters
Before any parameterization is done it is necessary to read all parameters from the device
into the offline table of SIMATIC PDM. The offline table merely contains default data.
1. Open the PDM device driver.
2. Select "Device->Upload to PC/PG .." Select "Execute even if the device TAG does not
match the project data TAG." and click "OK" to read all parameters to the offline table.
After closing the dialog all loaded parameters should show "Loaded" in the status of the
PDM table.
System integration
5.5 Commissioning with PDM
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 23
Setting basic parameters
In the following it is shown by example how to set the following basic flow parameters:
Low flow cut-off
Filter time constant


NOTICE

Change of other parameters
All parameters are described in chapter "holding registers (Page 39)".
Change of parameters is always carried out as described in the following example
Download settings to device
1. Select: "Device->Download to device...".
2. Enter password (Default factory password is "1000").
System integration
5.5 Commissioning with PDM
SITRANS F M MAG 8000 Modbus RTU
24 Operating Instructions, 08/2011, A5E03409989-01
5.5.6 Operation
The system is now ready for normal operation.
1. Select "View->Display" to see all process values.
2. Verify that the process values show the expected values.


Figure 5-3 View all process values

SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 25
Function codes 6
6.1 Modbus Commands
Modbus addressing model
The module allows R/W access to the following standard Modbus data register blocks:
Coils (ref. 0x address range)
Holding Registers (ref. 4x address range)
I.e. the module will not support the other standard data register blocks:
"Discrete Input" (ref. 1x address range)
"Input Registers"(ref. 3x address range)
Commands
Broadcast communication from master to slave(s) through device address 0 is supported. No
response from the slave is generated in that case. Broadcast communication is not secured
by the normal check mechanisms and shall be limited to very few uses.
A SITRANS F Modbus slave only recognizes (and accepts) few Modbus RTU
commands/function codes.
Supported function codes are listed in the table below.
Table 6- 1 Function codes
Function code Command text Description
01 hex Read coils Reads the status of single bit(s) in a slave
03 hex Read multiple registers Reads the binary content of multiple 16-bit registers in the slave.
The maximum number of registers is 26
05 hex Write single coil Writes a single on/off bit
10 hex Write multiple registers Preset values into a sequence of 16-bit registers. The maximum
number of registers is 25
11 hex Report Slave ID The SITRANS F slave will respond to a Report Slave ID command
(Command 17) request from the master by giving information
about device type, vendor, revision level etc. in a format as shown
Function codes
6.2 Read coils
SITRANS F M MAG 8000 Modbus RTU
26 Operating Instructions, 08/2011, A5E03409989-01
6.2 Read coils
Command messages
The read coils functions (01 hex) allow the master to request information from the slave. The
command message of a coil read is structured as shown below. Each row in the table
compares to a byte in the message top byte (Slave address) is transmitted first.
The initial slave address is 1. Address 0 (broadcast) and other values between 1 and 255
can be used.
The function code of this message is 01 hex (read coil) .
The starting coil is the first binary data to be read.
The quantity indicates how many consecutive bits are to be read. The quantity may range
from 1 to 432 bits.
A CRC value is generated from a calculation using the values of the slave address, function
code, and data sections of the message. When the slave receives the command message it
calculates a CRC-16 value and compares it to the one in the CRC-16 field of the command
message. If these two CRC-16 values are the same the slave has received the proper
command message. If the two CRC-16 values are not the same the slave will not respond.
Table 6- 2 Read coil command messages
Message byte Example
Slave address xx hex
Function code 01 hex
Starting coil Upper 00 hex
Lower 00 hex
Quantity Upper 00 hex
Lower xx hex
CRC-16 Lower xx hex
Upper xx hex
Normal response
If the command message has a valid slave address, function code, starting coil and quantity
value, the slave will respond with a normal response message. If the command message
has an invalid slave address, function code, starting coil and/or quantity, the slave will
respond with an exception response message.
The normal response message contains the same slave address and function code as the
command message.
The Bit count is the number of status bits returned in the response message. The number
equals the quantity in the command message.
The data section of the response message contains a number of bits representing the status
of the coils(s) that has been read from the device. The LSB of the coil status byte indicates
the status of the coil.
Function codes
6.2 Read coils
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 27
Table 6- 3 Read coil normal response messages
Message byte Example
Slave address xx hex
Function code 01 hex
Bit count xx hex
Coil status byte(s) xx hex
xx hex
Next coil status byte(s) xx hex
xx hex
Last coil status byte(s) xx hex
xx hex
CRC-16 Lower xx hex
Upper xx hex
Exception response
The exception response message contains the same slave address as the command
message.
The function code of the exception message is actually a value of 80 hex plus the original
function code of 01 hex.
The exception code indicates where the error occurred in the command message. A
complete listing of exception codes is shown in a later chapter.
Table 6- 4 Read coil exception response messages
Message byte Example
Slave address xx hex
Function code 81 hex
Exception code 02 hex
CRC-16 Lower xx hex
Upper xx hex
Example
Read Coil Customer Totalizer (0:00018):
Query: 1,1,0,18,0,1,93,207 (Hex 01,01,00,12,00,01,5D,CF)
Response: 1,1,1,0,81,136 (Hex 01,01,01,00,51,88)
Function codes
6.3 Read multiple registers
SITRANS F M MAG 8000 Modbus RTU
28 Operating Instructions, 08/2011, A5E03409989-01
6.3 Read multiple registers
Command messages
The multiple register read functions (03 hex) allows the master to request information from
the slave. The command message of a multiple register read is structured as shown below.
Each row in the table compares to byte in the message top byte (Slave address) is
transmitted first.
The initial slave address is 1. Address 0 (broadcast) and other values between 1 and 255
can be used.
The function code of this message is 03 hex (read multiple registers)
The starting register is the first register to be read.
The quantity indicates how many consecutive 16-bit registers are to be read. The quantity
may range from 1 to 26 registers. If the quantity is greater than 26 an error code of 03 hex is
returned in the exception response message.
A CRC value is generated from a calculation using the values of the slave address, function
code, and data sections of the message. When the slave receives the command message it
calculates a CRC-16 value and compares it to the one in the CRC-16 field of the command
message. If these two CRC-16 values are the same the slave has received the proper
command message. If the two CRC-16 values are not the same the slave will not respond.
If the command message has a valid slave address, function code, starting register and
quantity value, the slave will respond with a normal response message. If the command
message has an invalid function code, starting register and/or quantity, the slave will
respond with an exception response message.
Table 6- 5 Read multiple registers command messages
Message byte Example
Slave address xx hex
Function code 03 hex
Starting register Upper 00 hex
Lower 20 hex
Quantity Upper 00 hex
Lower 04 hex
CRC-16 Lower xx hex
Upper xx hex
Normal response
The normal response message contains the same slave address and function code as the
command message.
The Byte count is the number of data bytes returned in the response message. The number
is actually the quantity (in the command message) times 2, since there are two bytes of data
in each register.
Function codes
6.3 Read multiple registers
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 29
The data section of the response message contains 8 upper and 8 lower bits of data for each
register that has been read from the device.
Table 6- 6 Read multiple registers normal response messages
Message byte Example
Slave address xx hex
Function code 03 hex
Byte count xx hex
Starting register Upper xx hex
Lower xx hex
Next register Upper xx hex
Lower xx hex
Last register Upper xx hex
Lower xx hex
CRC-16 Lower xx hex
Upper xx hex
Exception response
The exception response message contains the same slave address as the command
message.
The function code of the exception message is actually a value of 80 hex plus the original
function code of 03 hex. The exception code indicates where the error occurred in the
command message. A complete listing of exception codes is shown in chapter "exception
handling (Page 35)".
Table 6- 7 Read multiple registers exception response messages
Message byte Example
Slave address xx hex
Function code 83 hex
Exception code 01 hex to 06 hex
CRC-16 Lower xx hex
Upper xx hex
Example
Read actual velocity (4:03001)
Query: 1,3,11,184,0,2,70,10 (Hex 01,03,0B,B8,00,02,46,0A)
Response: 1,3,4,64,195,82,139,98,200 (Hex 01,03,04,40,C3,52,8B,62,C8)
Actual velocity = 6.10383 mm/s.
Function codes
6.4 Write single coil
SITRANS F M MAG 8000 Modbus RTU
30 Operating Instructions, 08/2011, A5E03409989-01
6.4 Write single coil
Command messages
The write coil functions (05 hex) allow the master to control single bits in the slave. The
command message of a coil write is structured as shown below.
The initial slave address is 1. Address 0 (broadcast) and other values between 1 and 255
can be used.
The function code of this message is 05 hex (write coil).
The coil address is the coil to be written to.
The requested coil status is specified by a constant in the query data field. A value of FF hex
, 00 hex (upper, lower) requests the coil/bit to be set. A value of 00 hex , 00 hex requests it
to be reset. All other values are illegal and will not affect the coil.
CRC check and exception handling is performed as described for command Read multiple
registers.
Table 6- 8 Write coil command messages
Message byte Example
Slave address xx hex
Function code 05 hex
Coil address Upper xx hex
Lower xx hex
New coil value Upper FF hex or 00 hex
Lower 00 hex
CRC-16 Lower xx hex
Upper xx hex
Normal response
The normal response message contains the same slave address and function code as the
command message.
The coil address is the coil that was written to.
The new coil value is the value written to the coil.
Table 6- 9 Write coil normal response messages
Message byte Example
Slave address xx hex
Function code 05 hex
Coil address Upper xx hex
Lower xx hex
New coil value Upper FF hex or 00 hex
Function codes
6.5 Write multiple registers
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 31
Message byte Example
Lower 00 hex
CRC-16 Lower xx hex
Upper xx hex
Exception response
The exception response message contains the same slave address as the command
message.
The function code of the exception message is actually a value of 80 hex plus the original
function code of 05 hex. The exception code indicates where the error occurred in the
command message. A complete listing of exception codes is shown in chapter "Exception
handling (Page 35)".
Table 6- 10 Write coil exception response messages
Message byte Example
Slave address xx hex
Function code 85 hex
Exception code 01 hex to 06 hex
CRC-16 Lower xx hex
Upper xx hex
Examples
Coil 0 (Restart Modbus communication)
To activate a new baudrate and parity/framing the coil 0 (restart Modbus communication)
must be sent. Otherwise a power down/up initiate a new baudrate and parity/framing:
Query: 1,5,0,0,255,0,140,58 (Hex 01,05,00,00,FF,00,8C,3A) (Set coil 0 to 0xFF00)
Receive: 1,5,0,0,255,0,140,58 (Hex 01,05,00,00,FF,00,8C,3A) (Restart Modbus
communication)
6.5 Write multiple registers
Command messages
The multiple register write functions (10 hex) allow the master to write data to the slaves
registers. The command message of a multiple register write is structured as shown below.
The initial slave address is 1. Address 0 (broadcast) and other values between 1 and 255
can be used.
The function code of this message is 10 hex (write multiple registers).
The starting register is the first register to be written to.
Function codes
6.5 Write multiple registers
SITRANS F M MAG 8000 Modbus RTU
32 Operating Instructions, 08/2011, A5E03409989-01
The quantity indicates how many consecutive 16-bit registers are to be written to. The
quantity may range from 1 to 25 registers. If the quantity is greater than 25, an error code of
03 hex is returned in the exception response message.
The Byte count is the number of bytes of data to be written to the device. The number of
bytes is actually the quantity times 2, since there are two bytes of data in each register.
The data section of the command message contains 8 upper and 8 lower bits of data for
each register that is being written to.
CRC check and exception handling is performed as described for command Read multiple
registers.
Table 6- 11 Write multiple coil command messages
Message byte Example
Slave address xx hex
Function code 10 hex
Starting register Upper 00 hex
Lower 20 hex
Quantity Upper 00 hex
Lower 04 hex
Byte count xx hex
Starting register value Upper xx hex
Lower xx hex
Next register value Upper xx hex
Lower xx hex
Last register value Upper xx hex
Lower xx hex
CRC-16 Lower xx hex
Upper xx hex
Normal response
The normal response message contains the same slave address and function code as the
command message.
The starting register is the first register that was written to.
The quantity value indicates how many consecutive registers were written to.
Table 6- 12 Write multiple coil normal response messages
Message byte Example
Slave address xx hex
Function code 10 hex
Starting register Upper xx hex
Lower xx hex
Quantity Upper xx hex
Function codes
6.5 Write multiple registers
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 33
Message byte Example
Lower xx hex
CRC-16 Lower xx hex
Upper xx hex
Exception responses
The exception response message contains the same slave address as the command
message.
The function code of the exception message is actually a value of 80 hex plus the original
function code of 10 hex.
The exception code indicates where the error occurred in the command message. A
complete listing of exception codes is shown in chapter "Exception handling (Page 35)".
Table 6- 13 Write multiple coil exception response messages
Message byte Example
Slave address xx hex
Function code 90 hex
Exception code 01 hex to 06 hex
CRC-16 Lower xx hex
Upper xx hex
Example
Set baud rate to 38400 baud
Query: 1,16,2,17,0,1,2,0,5,70,210 (38400 = value 5) (Hex
01,10,02,11,00,01,02,00,05,46,D2)
Receive: 1,16,2,17,0,1,80,116 (Hex 01,10,02,11,00,01,50,74)
To activate a new baudrate and parity/framing the coil 0 (Restart Modbus communication)
must be sent.
Otherwise a power down/up initiate a new baudrate and parity/framing:
Query: 1,5,0,0,255,0,140,58 (Hex 01,05,00,00,FF,00,8C,3A) (Set coil 0 to 0xFF00)
Receive: 1,5,0,0,255,0,140,58 (Hex 01,05,00,00,FF,00,8C,3A) (Restart Modbus
communication)
Function codes
6.6 Report slave ID command
SITRANS F M MAG 8000 Modbus RTU
34 Operating Instructions, 08/2011, A5E03409989-01
6.6 Report slave ID command
All MAG 8000 will respond to a Report Slave ID command (Command 17) request from the
master by giving information about device type, vendor, revision level etc. in a format as
shown:
Table 6- 14 Report slave ID command messages
Message byte Example
Slave address xxhex
Function code 11hex
Lower xxhex CRC-16
Upper xxhex

Table 6- 15 Report slave ID messages
Message byte Description Length
Slave address 1 byte
Function code 1 byte
Byte count 1 byte
Slave ID 1 byte
Run Indicator 0=Off; FF=Running 1 byte
Product code 0x1B = MAG8000 1 byte
Software code no

"087C4054" for MAG8000
Null terminator included
9 bytes
Capability bits Bits describing the capabilities of this
module.
1.2, 2.4, 4.8, 9.6, 19.2, 38.4 kB/s
3 bytes
Manufacturer name "Siemens" (Read from EEPROM) Null
terminator included
12 bytes
Product name "MAG 8000"
Null terminator included
12 bytes
Product major revision 1 byte
Product minor revision 1 byte
Comm option name Not used in MAG 8000 11 bytes
Comm option code Not used in MAG 8000 1 byte
Comm option Major revision Not used in MAG 8000 1 byte
CRC-16 2 bytes

Function codes
6.7 Exception handling
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 35
6.7 Exception handling
There is a defined set of exception codes to be returned by slaves in the event of problems.
All exceptions are signalled in the response from the slave by adding 80 hex to the function
code of the request and following this byte by an exception code.
Table 6- 16 Exception codes
Exception code
(dec)
Exception text Description
01 Illegal function The function code received in the query is not an allowable action for
the slave
02 Illegal data address The data address received in the query is not an allowable address for
the slave.
03 Illegal data value A value contained in the query data field is not an allowable value for
the addressed location. This may indicate a fault in the structure of the
remainder of a complex request, such that the implied length is
incorrect.
04 Slave device failure The request is by some other reason not acceptable. It may e.g.
indicate that the data value to write is evaluated to be beyond limits.
06 BUSY-acknowledge The slave is processing a long-duration command. The master should
retransmit the message later when the slave is free.
If an exception code 04 is received, further requests have to be done to narrow down the
exact problem.
If any doubts about the address that failed, "Last Coil/HoldReg ErrorAddr" can be read. This
will return the faulty address.
Table 6- 17 Last Coil/HoldReg ErrorAddr
MODBUS
register
MODBUS
address
No. of
bytes
Data type Description Read/
write
4:00681 680 2 Word Last Coil ErrorAddr (MODBUS cmd: 1 or 5) R
4:00682 681 2 Word Last Coil ErrorNo (127 = No error) R
4:00683 682 2 Word Last HoldReg ErrorAddr (MODBUS cmd: 3 or 16) R
4:00684 683 2 Word Last HoldReg ErrorNo (127 = No error) R
Reading "Last Coil/HoldReg ErrorNo" will return a detailed error reason. A list of error
numbers can be seen below.
Table 6- 18 Error numbers
Error Number
(Dec)
Error Number
(Hex)
Error name Reason
3 3 Write access
denied
This parameter is in a state where it is not
writable
4 4 Max. limit The value was greater than the allowed
maximum value
Function codes
6.7 Exception handling
SITRANS F M MAG 8000 Modbus RTU
36 Operating Instructions, 08/2011, A5E03409989-01
Error Number
(Dec)
Error Number
(Hex)
Error name Reason
5 5 Min. limit The value was less than the allowed
minimum value
127 7F No error No problem


SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 37
Technical data 7

Table 7- 1 Technical data
Device type Slave
Baud rates 1200, 2400, 4800, 9600, 19200, 38400 bits/sec
Number of stations Recommended: max. 31 per segment without
repeaters
Device address range 1-247
Protocol RTU (Other Modbus protocols like ASCII, Plus or
TCP/IP are not supported.)
Electrical interface
RS485, 3-wire
RS232, 3-wire
Connecter type Screw terminals
Supported function codes
1 Read coils
3 Read holding registers
5 Write single coil
16 Write multiple registers
17 Report slave ID
Broadcast Yes
Maximum cable length 1200 meters (@ 38400 bits/sec)
Standard Modbus over serial line v1.0*
Certified No
Device Profile None
According to the Specification & Implementation guide v. 1.0 available at the Modbus Organisation
website.

Technical data

SITRANS F M MAG 8000 Modbus RTU
38 Operating Instructions, 08/2011, A5E03409989-01

SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 39
Modbus holding registers A
A.1 Introduction to holding registers
In the following the holding registers for the MAG 8000 Modbus RTU module are described.
Comm. settings
lnfo/status
Application settings
Min. values
Max. values
0
500
600
700
2000
3300
10000
20000
30000
65535
8
5
U
4
0

Figure A-1 Modbus Holding Registers Memory Map
The minimum value of a writable "holding register" value can be read by adding 10000 to
the address of the value.
The maximum value of a writable "holding register" value can be read by adding 20000 to
the address of the value.
If the value is not directly applicable, the min./max. limit shown will be based on the data type
- e.g. a "WORD-type" value will show the limits 0-65535 - even though some of these values
are not allowed.

Note
Reading min./max. values
Min./max. values do not apply to all datatypes (e.g. strings). Reading min./max. value for
such "holding registers" will return zero-values.

Note
Firmware version 3.00
Registers and addresses are valid for MAG 8000 firmware 3.00 or newer.


Modbus holding registers
A.2 MODBUS application settings
SITRANS F M MAG 8000 Modbus RTU
40 Operating Instructions, 08/2011, A5E03409989-01
A.2 MODBUS application settings
Table A- 1 Customer profile
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:02008 2007 6 string Meter access
code
Password to change parameters in the
water meter
W
4:00009 8 6 string New access
code
Downloaded password is protected and
can not be read.
New password can be changed when old
password is entered or if hardware key is
mounted.
W
4:00656 655 16 string Application
identifier
Customer application identification
information (max 15 characters)
R/W
4:00664 663 16 string Application
location
Customer application location information
(max 15 characters)
R/W

Table A- 2 Measurement
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:03000 2999 4 float32 Actual velocity Actual velocity in mm/s R
4:03002 3001 4 float32 Flow rate Actual flow value R
4:03004 3003 4 float32 Insulation
value
Insulation value from last insulation test R
4:03006 3005 4 uint32 Insulation tests
fulfilled
Number of insulation tests since last power
up
R
4:03047 3046 6 date Insulation test
date
Date of last insulation test R
4:03008 3007 4 sint32 Electrode
impedance A
Electrode impedance A for empty pipe
detection
R
4:03010 3009 4 sint32 Electrode
impedance B
Electrode impedance B for empty pipe
detection
R
4:03012 3011 4 float32 Flowrate
percent value
Flowrate as percent of Qn R

Table A- 3 Totalization
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:03017 3016 8 totaltype Totalizer 1 Volume for totalization register 1 R/W
4:03021 3020 8 totaltype Totalizer 2 Volume for totalization register 2 R/W
4:03025 3024 8 totaltype Customer
totalizer 3
Customer totalizer 3 based on totalizer 1
set up
R
Modbus holding registers
A.3 MODBUS driver settings
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 41
A.3 MODBUS driver settings
Table A- 4 MODBUS driver settings
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00528 527 2 uint16 Device
Communica
tion
Address
Meter has default address value "1" with
selectable address up to 247
R
4:00529 528 2 uint16 Baudrate Communication port speed
0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19200
5 = 38400
R
4:00530 529 2 uint16 Parity Communication port parity
0 = Even 1 stop
1 = Odd 1 stop
2 = None 2 stop
3 = None 1 stop
R
4:00079 78 2 uint16 Device
Product ID
Siemens MAG 8000 product ID 10779 R
4:00531 530 2 uint16 Interframe
space
Minimum space between two messages given in
tenth bytes
R
4:00372 371 2 uint16 Response
delay
Minimum time from receiving a request to its
response
R
0:00000 0 1 coil Reset
communica
tion driver
Warning! Check settings before reset and
accept new communications settings - otherwise
communication will be interrupted!
0 =No
1 = Yes
R

Modbus holding registers
A.4 Menu control
SITRANS F M MAG 8000 Modbus RTU
42 Operating Instructions, 08/2011, A5E03409989-01
A.4 Menu control
Table A- 5 Menu control
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00234 233 1 uint8 Menu active 1 byte describing which menus are enabled
Bit 1: Operator menu,
Bit 2: Meter info menu,
Bit 3: Service menu,
Bit 4: Log menu,
Bit 5: Statistic menu,
Bit 6: Revenue menu,
Bit 7: Not Used
Bit 8: Not Used
Example
Menu active = 15 :
Operator; Meter info and Service menu
enabled
R
4:00402 401 1 uint8 Default
operator
menu index
Default menu index. Automatically selected
after 10 minutes of no operation of display
key.
0 =Totalizer 1
1 =Totalizer 2
2 = Actual Flow rate
3 = Fault codes
4 = Customer Totalizer
R
4:00406 405 1 uint8 Decimal point Decimal point for displayed totalized value
0 = No point
1 = One digit after point
2 = Two digits after point
3 = Three digits after point
4 = Automatic point adjust
R/W
4:00222 221 1 uint8 Displayed
unit
Displayed m3 unit or an arrow indication for a
unit label
0 = m3 unit not displayed
1 = Use m3 unit
R

Modbus holding registers
A.5 Sensor characteristics
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 43
A.5 Sensor characteristics
Table A- 6 Sensor characteristics
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00206 205 4 float32 Flow unit factor Flow unit correction factor from m3/s to
other flow unit
R
4:00208 207 4 float32 Totalizer volume
unit factor
Totalizer unit correction factor from m3
to other volume unit
R
4:00210 209 12 string Flowrate unit Meter unit text for flowrate R
4:00216 215 12 string Totalizer unit Meter unit text for totalized volume R
4:00223 222 2 uint16 Pipe size Pipe diameter size in mm R
4:00224 223 4 float32 Sensor offset Sensor calibration offset in mm/s R
4:00226 225 4 float32 Qn Nominal flow R
4:00793 792 4 float32 Flow alarm limit Selectable flow limit for generating a
flow alarm
R/W
4:00228 227 4 float32 Calibration factor Calibration factor R
4:00230 229 6 date Calibration date Date of calibration R
4:00233 232 1 uint8 Verification mode
enable
Select 'Yes' to enable verification mode.
High resolution for calibration or
verification. Automatically stopped after
4 hours.
0 = No
1 = Yes
R/W
4:00117 116 4 float32 Gain correction Electronic calibration factor R
4:00236 235 4 float32 Adjustment Factor Meter correction factor for customer
adjustment of the calculated flow value.
R
4:00247 246 1 uint8 Excitation
frequency sensor
limit
Maximum possible sensor excitation
frequency.
0 = 1/15Hz
1 = 1/5Hz
2 = 1.5625Hz
3 = 3.125Hz
4 = 6.25Hz
5 = 1/30Hz
6 = 1/60Hz
R
Modbus holding registers
A.5 Sensor characteristics
SITRANS F M MAG 8000 Modbus RTU
44 Operating Instructions, 08/2011, A5E03409989-01
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00048 47 1 uint8 Excitation
frequency limit
Maximum selectable excitation
frequency
0 = 1/15Hz
1 = 1/5Hz
2 = 1.5625Hz
3 = 3.125Hz
4 = 6.25Hz
5 = 1/30Hz
6 = 1/60Hz
R
4:00238 237 1 uint8 Excitation
frequency
Actual selected excitation frequency
0 = 1/15Hz
1 = 1/5Hz
2 = 1.5625Hz
3 = 3.125Hz
4 = 6.25Hz
5 = 1/30Hz
6 = 1/60Hz
R
4:00239 238 4 float32 Low flow cut-off If the flow subceeds this percentage of
Qn, then the flowvalue is set to zero.n.
R
4:00241 240 2 uint16 Filter time constant Generel filter for flow measurement.
Filter constant is the number of
excitations the filtering will take place
over. Higher number gives a slower and
more stable flow signal.
R
4:00242 241 1 uint8 Empty pipe
detection enable
Select 'Yes' to enable empty pipe
detection.
0 = No
1 = Yes
R
4:00243 242 4 sint32 Empty pipe limit Electrode impedance in ohm for active
empty pipe detection
R
4:00254 253 4 sint32 Low medium
impedance alarm
Electrode impedance in ohm for active
low impedance alarm detection
R/W
4:00245 244 1 uint8 Insulation test
enable
Select 'Yes' for enabling insulation test
0 = No
1 = Yes
R/W
4:00246 245 2 uint16 Insulation test
interval
Number of days between insulation
tests
R/W
4:00820 819 4 float32 Reverse flow
alarm limit
Selectable reverse flow limit for
generating a reverse flow alarm
R/W

Modbus holding registers
A.6 Totalization
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 45
A.6 Totalization
Table A- 7 Totalization
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00400 399 1 uint8 Flow direction totalizer 1 Calculation principle on flow
direction for forward - reverse
or net flow
0 = Forward
1 = Reverse
2 = Net
R/W
4:00073 72 6 date Totalizer 1 changes date Date and time when totalizer
1 has been changed
R
4:00401 400 1 uint8 Flow direction totalizer 2 Calculation principle on flow
direction for forward - reverse
or net flow
0 = Forward
1 = Reverse
2 = Net
R/W
4:00076 75 6 date Totalizer 2 changes date Date and time when totalizer
2 has been changed
R

A.7 Pulse output
Table A- 8 Pulse output
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00373 372 1 uint8 Output A
enable
Select 'Yes' to enable output A
0 = No
1 = Yes
R/W
4:00374 373 1 uint8 Pulse A
function
Pulse output calculation on pure forward or
reverse flow - or net flow for forward and reverse
pulse flow
0 = Forward
1 = Reverse
2 = Forward net
3 = Reverse net
R/W
4:00375 374 4 float32 Amount
per pulse
A
Volume per pulse. Output A R/W
Modbus holding registers
A.7 Pulse output
SITRANS F M MAG 8000 Modbus RTU
46 Operating Instructions, 08/2011, A5E03409989-01
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00377 376 1 uint8 Pulse
width for
pulse A
Pulse length when the pulse is active
0 = 10 ms
1 = 50 ms
2 = 100 ms
3 = 500 ms
4 = 5 ms
R/W
4:00378 377 1 uint8 Output B
enable
Select 'Yes' to enable output B
0 = No
1 = Yes
R/W
4:00379 378 1 uint8 Pulse B
function
Configuration of output B as pulse - alarm or call
up function
0 = Pulse
1 = Alarm
2 = Call up
R/W
4:00380 379 1 uint8 Pulse B
direction
Pulse output calculation on pure forward or
reverse flow - or net flow for forward and reverse
pulse flow
0 = Forward
1 = Reverse
2 = Forward net
3 = Reverse net
R/W
4:00381 380 4 float32 Amount
per pulse
B
Volume per pulse. Output B R/W
4:00383 382 1 uint8 Pulse
width for
pulse B
Pulse length when the pulse is active
0 = 10 ms
1 = 50 ms
2 = 100 ms
3 = 500 ms
R/W

Modbus holding registers
A.8 Service control
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 47
A.8 Service control
Table A- 9 Service control
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
0:00000 15 1 coil Coil current
disable
Select 'Yes' to disable coil current for
magnetic field
0 = No
1 = Yes
R
0:00000 16 1 coil Fixed flow
mode enable
Select 'Yes' to enable fixed flow value
0 = No
1 = Yes
R
4:00361 360 4 float32 Fixed flow
value
Fixed flow value for enabled fixed flow R
4:00363 362 6 date Latest service
date
Latest service date (can also be used for
date of installation)
R/W
4:00080 79 4 uint32 Operating
hours since
power up
Total operation hours since first power up R
4:00366 365 2 uint16 Numbers of
power up
Total number of power up since first time
power up.
R
4:03033 3032 6 date Actual date
and time
Actual date and time of day-month-year and
hours:minutes:seconds
R/W

A.9 Error messages
Table A- 10 Error messages
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
0:00000 2 - coil Insulation alarm
output enable
Select 'Yes' to enable current alarm on
alarm output / call-up
0 = No
1 = Yes
R/W
4:00272 271 2 uint16 Insulation fault
hours
Total hours fault active R
4:00273 272 1 uint8 Insulation fault
counter
Total number of faults R
4:00274 273 6 date Insulation fault
appears
First time the fault appeared R
4:00277 276 6 date Insulation fault
disappears
Last time the fault disappeared R
Modbus holding registers
A.9 Error messages
SITRANS F M MAG 8000 Modbus RTU
48 Operating Instructions, 08/2011, A5E03409989-01
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
0:00000 3 - coil Coil current
alarm output
enable
Select 'Yes' to enable active alarm on
alarm output / call-up
0 = No
1 = Yes
R/W
4:00281 280 1 uint8 Coil current fault
counter
Total number of faults R
4:00282 281 6 date Coil current fault
appears
First time the fault appeared R
0:00000 2 - coil Insulation alarm
output enable
Select 'Yes' to enable current alarm on
alarm output / call-up
0 = No
1 = Yes
R
4:00285 284 6 date Coil current fault
disappears
Last time the fault disappeared R
0:00000 4 - coil Amplifier alarm
output enable
Select 'Yes' to enable active alarm on
alarm output / call-up
0 = No
1 = Yes
R/W
4:00288 287 2 uint16 Amplifier fault
hours
Total hours fault active R
4:00289 288 1 uint8 Amplifier fault
counter
Total number of faults R
4:00290 289 6 date Amplifier fault
appears
First time the fault appeared R
4:00293 292 6 date Amplifier fault
disappears
Last time the fault disappeared R
0:00000 5 - coil Parameter
checksum alarm
output enable
Select 'Yes' to enable active alarm on
alarm output / call-up
0 = No
1 = Yes
R/W
4:00296 295 2 uint16 Parameter
checksum fault
hours
Total hours fault active R
4:00297 296 1 uint8 Parameter
checksum fault
counter
Total number of faults R
4:00298 297 6 date Parameter
checksum fault
appears
First time the fault appeared R
4:00301 300 6 date Parameter
checksum fault
disappears
Password to change parameters in the
water meter
R
Modbus holding registers
A.9 Error messages
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 49
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
0:00000 6 - coil Low power alarm
output enable
Select 'Yes' to enable active alarm on
alarm output / call-up
0 = No
1 = Yes
R/W
4:00304 303 2 uint16 Low power fault
hours
Total hours fault active R
4:00305 304 1 uint8 Low power fault
counter
Total number of faults R
4:00306 305 6 date Low power fault
appears
First time the fault appeared R
4:00309 308 6 date Low power fault
disappears
Last time the fault disappeared R
0:00000 7 - coil Flow overflow
alarm output
enable
Select 'Yes' to enable active alarm on
alarm output / call-up
0 = No
1 = Yes
R/W
4:00312 311 2 uint16 Overflow fault
hours
Total hours fault active R
4:00313 312 1 uint8 Overflow fault
counter
Total number of faults R
4:00314 313 6 date Overflow fault
appears
First time the fault appeared R
4:00317 316 6 date Overflow fault
disappears
Last time the fault disappeared R
0:00000 8 - coil Pulse A overload
alarm output
enable
Select 'Yes' to enable active alarm on
alarm output / call-up
0= no
1 = Yes
R/W
4:00320 319 2 uint16 Pulse A overload
fault hours
Total hours fault active R
4:00321 320 1 uint8 Pulse A overload
fault counter
Total number of faults R
4:00322 321 6 date Pulse A overload
fault appears
First time the fault appeared R
4:00325 324 6 date Pulse A overload
fault disappears
Last time the fault disappeared R
0:00000 9 - coil Pulse B overload
alarm output
enable
Select 'Yes' to enable active alarm on
alarm output / call-up
0 = No
1 = Yes
R/W
4:00328 327 2 uint16 Pulse B overload
fault hours
Total hours fault active R
4:00329 328 1 uint8 Pulse B overload
fault counter
Total number of faults R
Modbus holding registers
A.9 Error messages
SITRANS F M MAG 8000 Modbus RTU
50 Operating Instructions, 08/2011, A5E03409989-01
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00330 329 6 date Pulse B overload
fault appears
First time the fault appeared R
4:00333 332 6 date Pulse B overload
fault disappears
Last time the fault disappeared R
0:00000 10 - coil Consumption
alarm output
enable
Select 'Yes' to enable active alarm on
alarm output / call-up
0 = No
1 = Yes
R/W
4:00336 335 2 uint16 Consumption
fault hours
Total hours fault active R
4:00337 336 1 uint8 Consumption
fault counter
Total number of faults R
4:00338 337 6 date Consumption
fault appears
First time the fault appeared R
4:00341 340 6 date Consumption
fault disappears
Last time the fault disappeared R
0:00000 11 - coil Leakage alarm
output enable
Select 'Yes' to enable active alarm on
alarm output / call-up
0 = No
1 = Yes
R/W
4:00344 343 2 uint16 Leakage fault
hours
Total hours fault active R
4:00345 344 1 uint8 Leakage fault
counter
Total number of faults R
4:00346 345 6 date Leakage fault
appears
First time the fault appeared R
4:00349 348 6 date Leakage fault
disappears
Last time the fault disappeared R
0:00000 12 - coil Empty pipe
alarm output
enable
Select 'Yes' to enable active alarm on
alarm output / call-up
0 = No
1 = Yes
R/W
4:00352 351 2 uint16 Empty pipe fault
timer
Total hours fault active R
4:00353 352 1 uint8 Empty pipe fault
counter
Total number of faults R
4:00354 353 6 date Empty pipe fault
appears
First time the fault appeared R
4:00357 356 6 date Empty pipe fault
disappears
Last time the fault disappeared R
0:00000 26 - coil Low impedance
alarm output
enable
Select 'Yes' to enable active alarm on
alarm output / call-up
0 = No
1 = Yes
R/W
Modbus holding registers
A.9 Error messages
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 51
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00795 794 2 uint16 Low impedance
fault timer
Total hours fault active R
4:00796 795 1 uint8 Low impedance
fault counter
Total number of faults R
4:00797 796 6 date Low impedance
fault appears
First time the fault appeared R
4:00800 799 6 date Low impedance
fault disappears
Last time the fault disappeared R
0:00000 27 - coil Flow alarm
output enable
Select 'Yes' to enable active alarm on
alarm output / call-up
0 = No
1 = Yes
R/W
4:00803 802 2 uint16 Flow alarm fault
timer
Total hours fault active R
4:00804 803 1 uint8 Flow alarm fault
counter
Total number of faults R
4:00805 804 6 date Flow alarm fault
appears
First time the fault appeared R
4:00808 807 6 date Flow alarm fault
disappears
Last time the fault disappeared R
0:00000 28 - coil Reverse flow
alarm output
enable
Select 'Yes' to enable active alarm on
alarm output / call-up
0 = No
1 = Yes
R/W
4:00811 810 2 uint16 Reverse flow
fault timer
Total hours fault active R
4:00812 811 1 uint8 Reverse flow
fault counter
Total number of faults R
4:00813 812 6 date Reverse flow
fault appears
First time the fault appeared R
4:00816 815 6 date Reverse flow
fault disappears
Last time the fault disappeared R
Modbus holding registers
A.9 Error messages
SITRANS F M MAG 8000 Modbus RTU
52 Operating Instructions, 08/2011, A5E03409989-01
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00360 359 2 uint16 Alarm
configuration list
2 bytes describing which errors/warning
should generate an alarm or call up on
output B
Bit 1: Insulation error
Bit 2: Coil current error
Bit 3: Preamplifier overload
Bit 4: Database checksum error
Bit 5: Low power warning
Bit 6: Flow overload warning
Bit 7: Pulse A overload warning
Bit 8: Pulse B overload warning
Bit 9: Consumption interval warning
Bit 10/L: Leakage warning
Bit 11/E: Empty pipe warning
Bit 12/C: Low impedance warning
Bit 13/d: Flow limit warning
Bit 14/A: Reverse flow warning
Bit 15: Not used
Bit 16: Not used
R/W
4:00052 51 2 uint16 Non optimal
measure time
Total hours of non optimal measurement
conditions
R
4:03016 3015 2 uint16 Fault status 2 bytes describing which errors/warnings
are active
Bit 1: Insulation error
Bit 2: Coil current error
Bit 3: Preamplifier overload
Bit 4: Database checksum error
Bit 5: Low power warning
Bit 6: Flow overload warning
Bit 7: Pulse A overload warning
Bit 8: Pulse B overload warning
Bit 9: Consumption interval warning
Bit 10/L: Leakage warning
Bit 11/E: Empty pipe warning
Bit 12/C: Low impedance warning
Bit 13/d: Flow limit warning
Bit 14/A: Reverse flow warning
Bit 15: Not used
Bit 16: Not used
R
Modbus holding registers
A.10 Power control
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 53
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
0:00000 14 - coil Call up
acknowledge
Select 'Yes' to reset active call-up
0 = No
1 = Yes
R/W
4:00049 48 6 date Date of fault log
reset
Date of fault log reset R
0:00000 13 - coil Reset the fault
log and faults
Reset the fault log and faults
0 = No
1 = Reset
R/W
A.10 Power control
Table A- 11 Power control
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00367 366 1 uint8 Mains frequency Country related mains power frequency
for enabling correct noise filtering
0 = 50 Hz
1 = 60 Hz
R
4:03029 3028 1 uint8 Power supply Meter power supply source
0 = Battery
1 = Mains supply
R
4:00368 367 1 uint8 Battery power Number of installed batteries (Internal
batterypack has 2 batteries and external
batterypack has 4 batteries)
R
4:03014 3013 4 uint32 Excitations no. Numbers of excitations since last battery
reset
R
4:03030 3029 1 uint8 Actual battery
capacity
Actual remaining battery power capacity
as a percentage of max capacity
R
4:00089 88 4 uint32 Battery operating
time
Operating time since installation of
batteries (last battery reset)
R
Modbus holding registers
A.10 Power control
SITRANS F M MAG 8000 Modbus RTU
54 Operating Instructions, 08/2011, A5E03409989-01
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:03031 3030 1 uint8 Power status
0 = Normal operation
1 = Battery alarm. Actual battery
capacity is below battery alarm level
(% of max capacity)
2 = Too low power (enters stand by
mode)
3 = As value 1 and 2 together
4 = External power gone
5 = As value 1 and 4 together
6 = As value 2 and 4 together
7 = As value 1 and 2 and 4 together
R
4:00369 368 1 uint8 Battery alarm
limit
Battery capacity level (%) where low
power alarm will be activated.
R/W
4:03042 3041 4 float32 Transmitter
temperature
Temperature inside the transmitter (C) R
4:00091 90 6 date Battery
installation date
Latest installation date of batteries R
0:00000 17 - coil Battery change
enable
Select 'Yes' to set battery installation date
to current date and reset remaining
battery operation capacity to maximum.
0 = No
1 = Yes
R/W
4:00822 821 1 uint8 Communication
module type
Communication module type - for
calculating correct power use.
0 = No module
1 = RS485
2 = RS232
3 = RS232 always connected
R

Modbus holding registers
A.11 Consumption statistic
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 55
A.11 Consumption statistic
Table A- 12 Consumption statistic
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
0:00000 18 - coil Reset customer
totalizer 3
Reset of customer totalizer
0 = No
1 = Yes
R/W
4:00098 97 6 date Customer
totalizer 3 reset
date
Date when customer totalizer has been
reset
R
4:00407 406 4 float32 Highest flowrate Value of highest measured flow rate R
4:00409 408 6 date Date of highest
flowrate
Date where highest flow rate occured R
4:00412 411 4 float32 Lowest flowrate Value of lowest measured flow rate R
4:00414 413 6 date Date of lowest
flowrate
Date where lowest flow rate occured R
4:00417 416 4 float32 Highest day
consumption
Value of highest measured daily
consumption. Calculation based on
totalizer 1
R
4:00419 418 6 date Date of highest
day consumption
Date when highest measured daily
consumption occured
R
4:00422 421 4 float32 Lowest day
consumption
Value of lowest measured daily
consumption. Calculation based on
totalizer 1
R
4:00424 423 6 date Date of lowest
day consumption
Date when lowest measured daily
consumption occured
R
4:00164 163 4 float32 Latest week
consumption
Latest week consumption (based on
totalizer 1 for the last 7 days)
R
4:00162 161 4 float32 Day 1
(yesterday) of
last week
consumption
Latest day consumption (based on
totalizer 1)
R
4:00101 100 4 float32 Day 2 of last
week
consumption
Latest day-1 consumption (based on
totalizer 1)
R
4:00033 32 4 float32 Day 3 of last
week
consumption
Latest day-2 consumption (based on
totalizer 1)
R
4:00035 34 4 float32 Day 4 of last
week
consumption
Latest day-3 consumption (based on
totalizer 1)
R
4:00037 36 4 float32 Day 5 of last
week
consumption
Latest day-4 consumption (based on
totalizer 1)
R
4:00039 38 4 float32 Day 6 of last
week
consumption
Latest day-5 consumption (based on
totalizer 1)
R
Modbus holding registers
A.12 Consumption profile
SITRANS F M MAG 8000 Modbus RTU
56 Operating Instructions, 08/2011, A5E03409989-01
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00041 40 4 float32 Day 7 (7 days
ago) of last week
consumption
Latest day-6 consumption (based on
totalizer 1)
R
4:03044 3043 4 float32 Actual month
consumption
Actual month consumption (based on
totalizer 1 from the first in the month)
R
4:00166 165 4 float32 Latest month
consumption
Latest month consumption (based on
totalizer 1 from the first in the month)
R
4:00427 426 6 date Reset date of
statistic inf.
Date of log reset of statistic information R
0:00000 19 - coil Reset statistic
information
Reset the statistic information log
0 = No
1 = Yes
R/W

A.12 Consumption profile
Table A- 13 Consumption profile
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00430 429 1 uint8 Upper limit in CP
range 1
Consumption flow range 1 - from 0 to
upper limit 1 as a percent of Qn
R/W
4:00431 430 4 float32 Total time in CP
range 1
Total hours of flow rate in flow range 1 R
4:00433 432 1 uint8 Upper limit in CP
range 2
Consumption flow range 2 - from previous
flow range to upper limit 2 as a percent of
Qn
R/W
4:00434 433 4 float32 Total time in CP
range 2
Total hours of flow rate in flow range 2 R
4:00436 435 1 uint8 Upper limit in CP
range 3
Consumption flow range 3 - from previous
flow range to upper limit 3 as a percent of
Qn
R/W
4:00437 436 4 float32 Total time in CP
range 3
Total hours of flow rate in flow range 3 R
4:00439 438 1 uint8 Upper limit in CP
range 4
Consumption flow range 4 - from previous
flow range to upper limit 4 as a percent of
Qn
R/W
4:00440 439 4 float32 Total time in CP
range 4
Total hours of flow rate in flow range 4 R
4:00442 441 1 uint8 Upper limit in CP
range 5
Consumption flow range 5 - from previous
flow range to upper limit 5 as a percent of
Qn
R/W
4:00443 442 4 float32 Total time in CP
range 5
Total hours of flow rate in flow range 5 R
Modbus holding registers
A.13 Leakage statistic
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 57
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00445 444 4 float32 Total time in CP
range 6
Total hours of flow rate in the last flow
range 6 (from previous flow range up to
Qn)
R
4:00447 446 6 date Reset date of
consumptionprofi
le
Date of log reset of consumption profile
information
R
0:00000 20 - coil Reset
consumption
profile
Reset the consumption profile information
log
0 = No
1 = Yes
R/W

A.13 Leakage statistic
Table A- 14 Leakage statistic
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00450 449 1 uint8 Leakage
detection mode
Leakage detection can be controlled by a
fixed leakage limit or the lowest measured
value added the leakage limit
0 = Off
1 = Fixed limit
2 = Lowest added fixed limit
R/W
4:00451 450 1 uint8 Leakage
excitation
frequency
Selected excitation frequency in leakage
detection period
0 = 1/15Hz
1 = 1/5Hz
2 = 1.5625Hz
3 = 3.125Hz
4 = 6.25Hz
5 = 1/30Hz
6 = 1/60Hz
R/W
4:00452 451 4 float32 Leakage limit If measured leakage value is above this
limit, a possible leakage is detected
R/W
4:03036 3035 12 string Leakage value
unit
The actual text of unit choice (flowrate or
volume)
R
4:00454 453 1 uint8 Leakage source The source value for leakage can be
flowrate or volume
0 = Flowrate
1 = Volume
R/W
Modbus holding registers
A.13 Leakage statistic
SITRANS F M MAG 8000 Modbus RTU
58 Operating Instructions, 08/2011, A5E03409989-01
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00455 454 2 uint16 Start period for
leakage
detection
Time of day to start the leakage detection
period
R/W
4:00456 455 1 uint8 Duration leakage
detection
Leakage detection duration in 10 minutes
resolution
R/W
4:00457 456 1 uint8 Periods with
possible leakage
Actual days/periods where measured
leakage value is above leakage limit
R
4:00458 457 1 uint8 Leakage periods
before alarm
Number of days / periods before leakage
fault/alarm appears
R/W
4:00459 458 4 float32 Lowest
measured
leakage value
Lowest measured value in leakage period R
4:00461 460 6 date Date of lowest
leakage value
Date of lowest measured value R
4:00464 463 4 float32 Highest
measured
leakage value
Highest measured value in leakage
period
R
4:00466 465 6 date Date of highest
leakage value
Date of highest measured value R
4:00469 468 4 float32 Latest leakage
period flowrate
Last period lowest flow value R
4:00370 369 4 float32 Latest leakage
period volume
Latest leakage period totalized R
0:00000 22 - coil Reset leakage
fault
Reset the leakage fault.
0 = No
1 =Yes
R/W
Modbus holding registers
A.14 Datalog
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 59
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
0:00000 21 - coil Reset leakage
period
information
Reset the leakage indication information
0 = No
1 = Yes
R/W
4:00403 402 1 uint8 Leakage status One byte describing status of leakage
detection
Bit 1: Finished successfully
Bit 2: Leakage detection running
Bit 3: Leakage detection failed
(SystemStatus have fatal error)
Bit 4: Leakage detection failed
(Empty-pipe detection disabled)
Bit 5: Leakage detection failed (Coil
current off)
Bit 6: Leakage detection failed
(Insulation test was active during
detection)
Bit 7 : Leakage detection stopped
because leakage parameter was
changed.
R/W

A.14 Datalog
Table A- 15 Datalog
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00471 470 1 uint8 Log interval Log interval
0 = Daily
1 = Weekly (7 days)
2 = Monthly
R/W
4:00235 234 1 uint8 Delay weekly log
interval
Delay of weekly data logging from current
day to first day logging at 00:00:00.
Thereafter a fixed interval of 7 days.
R/W
4:00472 471 4 float32 Limit for too high
consumption
Limit for too high consumption during
current log interval. Based on totalizer 1
R/W
4:00474 473 4 float32 Limit for too low
consumption
Limit for too low consumption during
current log interval. Based on totalizer 1
R/W
Modbus holding registers
A.14 Datalog
SITRANS F M MAG 8000 Modbus RTU
60 Operating Instructions, 08/2011, A5E03409989-01
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
0:00000 23 - coil Reset
consumption log
fault
Reset the consumption fault. Caused by
too low or too high consumption in the log
interval
0 = No
1 = Yes
R/W
4:00476 475 6 date Date of latest log
period
Date of latest stored value for log 1 R
4:00479 478 4 float32 Latest Log
period totalized
(1)
Latest logged value of consumption
based on totalizer 1
R
4:00481 480 4 float32 Latest Log
period totalized
(2)
Latest logged value of consumption
based on totalizer 2
R
4:00483 482 2 uint16 Latest Log
period fault
status
Two bytes describing fault status in log
period
Bit 1: Insulation error
Bit 2: Coil current error
Bit 3: Preamplifier overload
Bit 4: Database checksum error
Bit 5: Low power warning
Bit 6: Flow overload warning
Bit 7: Pulse A overload warning
Bit 8: Pulse B overload warning
Bit 9: Consumption interval warning
Bit 10/L: Leakage warning
Bit 11/E: Empty pipe warning
Bit 12/C: Low impedance warning
Bit 13/d: Flow limit warning
Bit 14: Not used
Bit 15: Not used
Bit 16: Not used
R
4:00484 483 1 uint8 Latest Log
period status
information
One byte describing status information in
log period
Bit 1: Totalizer 1 or 2 changed or reset
Bit 2: Tariff setting changed or reset
Bit 3: Tariff register changed or reset
Bit 4: Date - time changed
Bit 5: Alarm active in logged period
(See alarm fault log)
Bit 6: Fault log has been reset
Bit 7: HW lock broken
Bit 8: Power Up
R
Modbus holding registers
A.14 Datalog
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 61
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00485 484 6 date Date of log
period 2
Date where value for log 2 is stored R
4:00488 487 4 float32 Log period 2
totalized (1)
Previous logged value of consumption
based on totalizer 1
R
4:00490 489 4 float32 Log period 2
totalized (2)
Previous logged value of consumption
based on totalizer 2
R
4:00492 491 2 uint16 Log period 2
fault status
Two bytes describing fault status in log
period
Bit 1: Insulation error
Bit 2: Coil current error
Bit 3: Preamplifier overload
Bit 4: Database checksum error
Bit 5: Low power warning
Bit 6: Flow overload warning
Bit 7: Pulse A overload warning
Bit 8: Pulse B overload warning
Bit 9: Consumption interval warning
Bit 10/L: Leakage warning
Bit 11/E: Empty pipe warning
Bit 12/C: Low impedance warning
Bit 13/d: Flow limit warning
Bit 14: Not used
Bit 15: Not used
Bit 16: Not used
R
4:00493 492 1 uint8 Log period 2
status
information
One byte describing status information in
log period
Bit 1: Totalizer 1 or 2 changed or reset
Bit 2: Tariff setting changed or reset
Bit 3: Tariff register changed or reset
Bit 4: Date - time changed
Bit 5: Alarm active in logged period
(See alarm fault log)
Bit 6: Fault log has been reset
Bit 7: HW lock broken
Bit 8: Power Up
R
4:00494 493 6 date Date of log
period 3
Date where value for log 3 is stored R
4:00497 496 4 float32 Log period 3
totalized (1)
Log period 3 logged value of consumption
based on totalizer 1
R
4:00499 498 4 float32 Log period 3
totalized (2)
Log period 3 logged value of consumption
based on totalizer 2
R
Modbus holding registers
A.14 Datalog
SITRANS F M MAG 8000 Modbus RTU
62 Operating Instructions, 08/2011, A5E03409989-01
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00501 500 2 uint16 Log period 3
fault status
See log period 2 R
4:00502 501 1 uint8 Log period 3
status
information
See log period 2 R
4:00503 502 6 date Date of log
period 4
Date where value for log 4 is stored R
4:00506 505 4 float32 Log period 4
totalized (1)
Log period 4 logged value of consumption
based on totalizer 1
R
4:00508 507 4 float32 Log period 4
totalized (2)
Log period 4 logged value of consumption
based on totalizer 2
R
4:00510 509 2 uint16 Log period 4
fault status
See log period 2 R
4:00511 510 1 uint8 Log period 4
status
information
See log period 2 R
4:00532 531 6 date Date of log
period 5
Date where value for log 5 is stored R
4:00535 534 4 float32 Log period 5
totalized (1)
Log period 5 logged value of consumption
based on totalizer 1
R
4:00537 536 4 float32 Log period 5
totalized (2)
Log period 5 logged value of consumption
based on totalizer 2
R
4:00539 538 2 uint16 Log period 5
fault status
See log period 2 R
4:00540 539 1 uint8 Log period 5
status
information
See log period 2 R
4:00541 540 6 date Date of log
period 6
Date where value for log 6 is stored R
4:00544 543 4 float32 Log period 6
totalized (1)
Log period 6 logged value of consumption
based on totalizer 1
R
4:00546 545 4 float32 Log period 6
totalized (2)
Log period 6 logged value of consumption
based on totalizer 2
R
4:00548 547 2 uint16 Log period 6
fault status
See log period 2 R
4:00549 548 1 uint8 Log period 6
status
information
See log period 2 R
4:00550 549 6 date Date of log
period 7
Date where value for log 7 is stored R
4:00553 552 4 float32 Log period 7
totalized (1)
Log period 7 logged value of consumption
based on totalizer 1
R
4:00555 554 4 float32 Log period 7
totalized (2)
Log period 7 logged value of consumption
based on totalizer 2
R
4:00557 556 2 uint16 Log period 7
fault status
See log period 2 R
Modbus holding registers
A.14 Datalog
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 63
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00558 557 1 uint8 Log period 7
status
information
See log period 2 R
4:00559 558 6 date Date of log
period 8
Date where value for log 8 is stored R
4:00562 561 4 float32 Log period 8
totalized (1)
Log period 8 logged value of consumption
based on totalizer 1
R
4:00564 563 4 float32 Log period 8
totalized (2)
Log period 8 logged value of consumption
based on totalizer 2
R
4:00566 565 2 uint16 Log period 8
fault status
See log period 2 R
4:00567 566 1 uint8 Log period 8
status
information
See log period 2 R
4:00568 567 6 date Date of log
period 9
Date where value for log 9 is stored R
4:00571 570 4 float32 Log period 9
totalized (1)
Log period 9 logged value of consumption
based on totalizer 1
R
4:00573 572 4 float32 Log period 9
totalized (2)
Log period 9 logged value of consumption
based on totalizer 2
R
4:00575 574 2 uint16 Log period 9
fault status
See log period 2 R
4:00576 575 1 uint8 Log period 9
status
information
See log period 2 R
4:00577 576 6 date Date of log
period 10
Date where value for log 10 is stored R
4:00580 579 4 float32 Log period 10
totalized (1)
Log period 10 logged value of
consumption based on totalizer 1
R
4:00582 581 4 float32 Log period 10
totalized (2)
Log period 10 logged value of
consumption based on totalizer 2
R
4:00584 583 2 uint16 Log period 10
fault status
See log period 2 R
4:00585 584 1 uint8 Log period 10
status
information
See log period 2 R
4:00586 585 6 date Date of log
period 11
Date where value for log 11 is stored R
4:00589 588 4 float32 Log period 11
totalized (1)
Log period 11 logged value of
consumption based on totalizer 1
R
4:00591 590 4 float32 Log period 11
totalized (2)
Log period 11 logged value of
consumption based on totalizer 2
R
4:00593 592 2 uint16 Log period 11
fault status
See log period 2 R
4:00594 593 1 uint8 Log period 11
status
information
See log period 2 R
Modbus holding registers
A.14 Datalog
SITRANS F M MAG 8000 Modbus RTU
64 Operating Instructions, 08/2011, A5E03409989-01
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00595 594 6 date Date of log
period 12
Date where value for log 1 2 is stored R
4:00598 597 4 float32 Log period 12
totalized (1)
Log period 12 logged value of
consumption based on totalizer 1
R
4:00600 599 4 float32 Log period 12
totalized (2)
Log period 12 logged value of
consumption based on totalizer 2
R
4:00602 601 2 uint16 Log period 12
fault status
See log period 2 R
4:00603 602 1 uint8 Log period 12
status
information
See log period 2 R
4:00604 603 6 date Date of log
period 13
Date where value for log 13 is stored R
4:00607 606 4 float32 Log period 13
totalized (1)
Log period 13 logged value of
consumption based on totalizer 1
R
4:00609 608 4 float32 Log period 13
totalized (2)
Log period 13 logged value of
consumption based on totalizer 2
R
4:00611 610 2 uint16 Log period 13
fault status
See log period 2 R
4:00612 611 1 uint8 Log period 13
status
information
See log period 2 R
4:00613 612 6 date Date of log
period 14
Date where value for log 14 is stored R
4:00616 615 4 float32 Log period 14
totalized (1)
Log period 14 logged value of
consumption based on totalizer 1
R
4:00618 617 4 float32 Log period 14
totalized (2)
Log period 14 logged value of
consumption based on totalizer 2
R
4:00620 619 2 uint16 Log period 14
fault status
See log period 2 R
4:00621 620 1 uint8 Log period 14
status
information
See log period 2 R
4:00622 621 6 date Date of log
period 15
Date where value for log 15 is stored R
4:00625 624 4 float32 Log period 15
totalized (1)
Log period 15 logged value of
consumption based on totalizer 1
R
4:00627 626 4 float32 Log period 15
totalized (2)
Log period 15 logged value of
consumption based on totalizer 2
R
4:00629 628 2 uint16 Log period 15
fault status
See log period 2 R
4:00630 629 1 uint8 Log period 15
status
information
See log period 2 R
4:00631 630 6 date Date of log
period 16
Date where value for log 16 is stored R
Modbus holding registers
A.14 Datalog
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 65
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00634 633 4 float32 Log period 16
totalized (1)
Log period 16 logged value of
consumption based on totalizer 1
R
4:00636 635 4 float32 Log period 16
totalized (2)
Log period 16 logged value of
consumption based on totalizer 2
R
4:00638 637 2 uint16 Log period 16
fault status
See log period 2 R
4:00639 638 1 uint8 Log period 16
status
information
See log period 2 R
4:00678 677 6 date Date of log
period 17
Date where value for log 17 is stored R
4:00681 680 4 float32 Log period 17
totalized (1)
Log period 17 logged value of
consumption based on totalizer 1
R
4:00683 682 4 float32 Log period 17
totalized (2)
Log period 17 logged value of
consumption based on totalizer 2
R
4:00685 684 2 uint16 Log period 17
fault status
See log period 2 R
4:00686 685 1 uint8 Log period 17
status
information
See log period 2 R
4:00687 686 6 date Date of log
period 18
Date where value for log 18 is stored R
4:00690 689 4 float32 Log period 18
totalized (1)
Log period 18 logged value of
consumption based on totalizer 1
R
4:00692 691 4 float32 Log period 18
totalized (2)
Log period 18 logged value of
consumption based on totalizer 2
R
4:00694 693 2 uint16 Log period 18
fault status
See log period 2 R
4:00695 694 1 uint8 Log period 18
status
information
See log period 2 R
4:00696 695 6 date Date of log
period 19
Date where value for log 19 is stored R
4:00699 698 4 float32 Log period 19
totalized (1)
Log period 19 logged value of
consumption based on totalizer 1
R
4:00701 700 4 float32 Log period 19
totalized (2)
Log period 19 logged value of
consumption based on totalizer 2
R
4:00703 702 2 uint16 Log period 19
fault status
See log period 2 R
4:00704 703 1 uint8 Log period 19
status
information
See log period 2 R
4:00705 704 6 date Date of log
period 20
Date where value for log 20 is stored R
4:00708 707 4 float32 Log period 20
totalized (1)
Log period 20 logged value of
consumption based on totalizer 1
R
Modbus holding registers
A.14 Datalog
SITRANS F M MAG 8000 Modbus RTU
66 Operating Instructions, 08/2011, A5E03409989-01
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00710 709 4 float32 Log period 20
totalized (2)
Log period 20 logged value of
consumption based on totalizer 2
R
4:00712 711 2 uint16 Log period 20
fault status
See log period 2 R
4:00713 712 1 uint8 Log period 20
status
information
See log period 2 R
4:00714 713 6 date Date of log
period 21
Date where value for log 21 is stored R
4:00717 716 4 float32 Log period 21
totalized (1)
Log period 21 logged value of
consumption based on totalizer 1
R
4:00719 718 4 float32 Log period 21
totalized (2)
Log period 21 logged value of
consumption based on totalizer 2
R
4:00721 720 2 uint16 Log period 21
fault status
See log period 2 R
4:00722 721 1 uint8 Log period 21
status
information
See log period 2 R
4:00723 722 6 date Date of log
period 22
Date where value for log 22 is stored R
4:00726 725 4 float32 Log period 22
totalized (1)
Log period 22 logged value of
consumption based on totalizer 1
R
4:00728 727 4 float32 Log period 22
totalized (2)
Log period 22 logged value of
consumption based on totalizer 2
R
4:00730 729 2 uint16 Log period 22
fault status
See log period 2 R
4:00731 730 1 uint8 Log period 22
status
information
See log period 2 R
4:00732 731 6 date Date of log
period 23
Date where value for log 23 is stored R
4:00735 734 4 float32 Log period 23
totalized (1)
Log period 23 logged value of
consumption based on totalizer 1
R
4:00737 736 4 float32 Log period 23
totalized (2)
Log period 23 logged value of
consumption based on totalizer 2
R
4:00739 738 2 uint16 Log period 23
fault status
See log period 2 R
4:00740 739 1 uint8 Log period 23
status
information
See log period 2 R
4:00741 740 6 date Date of log
period 24
Date where value for log 24 is stored R
4:00744 743 4 float32 Log period 24
totalized (1)
Log period 24 logged value of
consumption based on totalizer 1
R
4:00746 745 4 float32 Log period 24
totalized (2)
Log period 24 logged value of
consumption based on totalizer 2
R
Modbus holding registers
A.14 Datalog
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 67
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00748 747 2 uint16 Log period 24
fault status
See log period 2 R
4:00749 748 1 uint8 Log period 24
status
information
See log period 2 R
4:00750 749 6 date Date of log
period 25
Date where value for log 25 is stored R
4:00753 752 4 float32 Log period 25
totalized (1)
Log period 25 logged value of
consumption based on totalizer 1
R
4:00755 754 4 float32 Log period 25
totalized (2)
Log period 25 logged value of
consumption based on totalizer 2
R
4:00757 756 2 uint16 Log period 25
fault status
See log period 2 R
4:00758 757 1 uint8 Log period 25
status
information
See log period 2 R
4:00759 758 6 date Date of log
period 26
Date where value for log 26 is stored R
4:00762 761 4 float32 Log period 26
totalized (1)
Log period 26 logged value of
consumption based on totalizer 1
R
4:00764 763 4 float32 Log period 26
totalized (2)
Log period 26 logged value of
consumption based on totalizer 2
R
4:00766 765 2 uint16 Log period 26
fault status
See log period 2 R
4:00767 766 1 uint8 Log period 26
status
information
See log period 2 R
Modbus holding registers
A.15 Consumption readings
SITRANS F M MAG 8000 Modbus RTU
68 Operating Instructions, 08/2011, A5E03409989-01
A.15 Consumption readings
Table A- 16 Consumption readings
MODBUS
register
MODBUS
address
No. of
bytes
Data type Label Description Read /
write
4:00144 143 1 uint8 Actual flow meter
status
One byte describing actual status
Bit 1: Totalizer 1 or 2 changed or reset
Bit 2: Tariff setting changed or reset
Bit 3: Tariff register changed or reset
Bit 4: Date - time changed
Bit 5: Alarm active
Bit 6: Fault log has been reset
Bit 7: HW lock broken
Bit 8: Power Up
R
4:00145 144 6 SettlingD
ate
Next settling
date
Next automatically settling date where
actual value of totalizer 1 is stored
R/W
4:00148 147 6 date Latest settling
date
Latest settling date where value of
totalizer 1 was stored
R
4:00151 150 8 totaltype Latest totalizer 1
value
Latest stored value of totalizer 1 R
4:00155 154 6 date Previous settling
date
Previous settling date where value of
totalizer 1 was stored
R
4:00158 157 8 totaltype Previous totalizer
1 value
Previous stored value of totalizer 1 R


SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 69
Appendix B
B.1 Data type mapping
Some standard data types are defined in the MAG 8000 protocol. Most of these data types
are not present in the Modbus RTU protocol as it defines Registers and Coils for all
variables.
A register in this context is always 16 bit long.
Table B- 1 Data type mapping
Datatype Modbus RTU implementation
uint8 Data organized as 8-bit unsigned integers.
The parameters are read using function code 03 hex Read multiple registers.
The parameters are written using function code 10 hex Write multiple registers.
uint8 type of data is accessed through a single register, where the data is found in the
lower byte of the register.
Data value can be 0 255 with no sign bit.
uint16 Data organized as 16-bit unsigned integers.
The parameters are read using function code 03 hex Read multiple registers.
The parameters are written using function code 10 hex Write multiple registers.
uint16 type of data is accessed through a single register.
Data value can be 0 65536 with no sign bit.
float32 Data organized as 32-bit signed floats (IEEE format).
The parameters are read using function code 03 hex Read multiple registers.
The parameters are written using function code 10 hex Write multiple registers.
float32 type of data is accessed through two registers.
Data values are coded in IEEE floating point format.
float64 Data organized as 64-bit signed floats (IEEE format).
The parameters are read using function code 03 hex Read multiple registers.
The parameters are written using function code 10 hex Write multiple registers.
float64 type of data is accessed through four registers.
Data values are coded in IEEE floating point format.
String Consecutive pairs of 8-bit ASCII characters stored one pair per 16-bit register.
Strings are read using function code 03 hex "Read multiple registers.
Strings are written using function code 10 hex Write multiple registers.
string type of data must be read or written as a series of 1 to 25 consecutive registers,
depending on the number of characters specified for the string. The max. string length is
50 chars (incl. delimiter). Strings are terminated by a zero-delimiter.
Appendix
B.2 CRC calculation
SITRANS F M MAG 8000 Modbus RTU
70 Operating Instructions, 08/2011, A5E03409989-01
Datatype Modbus RTU implementation
TotalType Data type defined by Siemens mainly used for Totalizer values. TotalType consist of two
parts:
1. signed long Number - contains the integer part of Value
2. signed long Decimal contains the fractional part of the Value multiplied with 1.0E9
The parameters are read using function code 03 hex Read multiple registers.
The parameters are written using function code 10 hex Write multiple registers.
Date Data type defined by Siemens used for dates. Date consist of 6 parts:
1. Unsigned Char Year
2. Unsigned Char Month
3. Unsigned Char Day
4. Unsigned Char Hour
5. Unsigned Char Minute
6. Unsigned Char Second
The parameters are read using function code 03 hex Read multiple registers.
The parameters are written using function code 10 hex Write multiple registers.

B.2 CRC calculation
The Cyclical Redundancy Checking (CRC) field is two bytes, containing a 16bit binary
value. The CRC value is first generated by the transmitting device, which appends the CRC
to the message. The receiving device recalculates a CRC during receipt of the message,
and compares the calculated value to the actual value it received in the CRC field. If the two
values are not equal an error occurs.
In the following a short text description of how the CRC is calculated is provided. This
description is then followed by a C programming example.
CRC calculation
1. Load a 16bit register with FFFF hex (all 1s). Call this the CRC register.
2. Exclusive OR the first 8bit byte of the message with the loworder byte of the 16bit
CRC register, putting the result in the CRC register.
3. Shift the CRC register one bit to the right (toward the LSB), zerofilling the MSB. Extract
and examine the LSB.
4. (If the LSB was 0): Repeat Step 3 (another shift). (If the LSB was 1): Exclusive OR the
CRC register with the polynomial value 0xA001 (1010 0000 0000 0001).
5. Repeat Steps 3 and 4 until 8 shifts have been performed. When this is done, a complete
8bit byte will have been processed.
6. Repeat Steps 2 through 5 for the next 8bit byte of the message. Continue doing this until
all bytes have been processed.
Appendix
B.2 CRC calculation
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 71
7. The final content of the CRC register is the CRC value.
8. When the CRC is placed into the message, its upper and lower bytes must be swapped
as described below.
Placing the CRC into the Message
When the 16bit CRC (two 8bit bytes) is transmitted in the message, the low-order byte will
be transmitted first, followed by the high-order byte.
For example, if the CRC value is 1241 hex (0001 0010 0100 0001):

Addr Func Data count Data n Data n+1 Data n+2 Data n+x CRC LO CRC HI
0x41 0x12
CRC programming example
/* Table of CRC values for high-order byte */
static __flash unsigned char auchCRCHi[] = {
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0, 0x80,
0x41, 0x00, 0xC1, 0x81,
0x40, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1,
0x81, 0x40, 0x01, 0xC0,
0x80, 0x41, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00,
0xC1, 0x81, 0x40, 0x01,
0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41,
0x01, 0xC0, 0x80, 0x41,
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81,
0x40, 0x00, 0xC1, 0x81,
0x40, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0,
0x80, 0x41, 0x01, 0xC0,
0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40, 0x01,
0xC0, 0x80, 0x41, 0x01,
0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41,
0x00, 0xC1, 0x81, 0x40,
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0, 0x80,
0x41, 0x00, 0xC1, 0x81,
0x40, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1,
0x81, 0x40, 0x01, 0xC0,
0x80, 0x41, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00,
0xC1, 0x81, 0x40, 0x01,
0xC0, 0x80, 0x41, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40,
0x01, 0xC0, 0x80, 0x41,
0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80,
0x41, 0x00, 0xC1, 0x81,
0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1,
0x81, 0x40, 0x01, 0xC0,
0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40, 0x01,
0xC0, 0x80, 0x41, 0x01,
0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40,
0x01, 0xC0, 0x80, 0x41,
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0, 0x80,
0x41, 0x00, 0xC1, 0x81,
0x40
Appendix
B.2 CRC calculation
SITRANS F M MAG 8000 Modbus RTU
72 Operating Instructions, 08/2011, A5E03409989-01
} ;

/* Table of CRC values for low-order byte */
static __flash char auchCRCLo[] = {
0x00, 0xC0, 0xC1, 0x01, 0xC3, 0x03, 0x02, 0xC2, 0xC6, 0x06, 0x07,
0xC7, 0x05, 0xC5, 0xC4,
0x04, 0xCC, 0x0C, 0x0D, 0xCD, 0x0F, 0xCF, 0xCE, 0x0E, 0x0A, 0xCA,
0xCB, 0x0B, 0xC9, 0x09,
0x08, 0xC8, 0xD8, 0x18, 0x19, 0xD9, 0x1B, 0xDB, 0xDA, 0x1A, 0x1E,
0xDE, 0xDF, 0x1F, 0xDD,
0x1D, 0x1C, 0xDC, 0x14, 0xD4, 0xD5, 0x15, 0xD7, 0x17, 0x16, 0xD6,
0xD2, 0x12, 0x13, 0xD3,
0x11, 0xD1, 0xD0, 0x10, 0xF0, 0x30, 0x31, 0xF1, 0x33, 0xF3, 0xF2,
0x32, 0x36, 0xF6, 0xF7,
0x37, 0xF5, 0x35, 0x34, 0xF4, 0x3C, 0xFC, 0xFD, 0x3D, 0xFF, 0x3F,
0x3E, 0xFE, 0xFA, 0x3A,
0x3B, 0xFB, 0x39, 0xF9, 0xF8, 0x38, 0x28, 0xE8, 0xE9, 0x29, 0xEB,
0x2B, 0x2A, 0xEA, 0xEE,
0x2E, 0x2F, 0xEF, 0x2D, 0xED, 0xEC, 0x2C, 0xE4, 0x24, 0x25, 0xE5,
0x27, 0xE7, 0xE6, 0x26,
0x22, 0xE2, 0xE3, 0x23, 0xE1, 0x21, 0x20, 0xE0, 0xA0, 0x60, 0x61,
0xA1, 0x63, 0xA3, 0xA2,
0x62, 0x66, 0xA6, 0xA7, 0x67, 0xA5, 0x65, 0x64, 0xA4, 0x6C, 0xAC,
0xAD, 0x6D, 0xAF, 0x6F,
0x6E, 0xAE, 0xAA, 0x6A, 0x6B, 0xAB, 0x69, 0xA9, 0xA8, 0x68, 0x78,
0xB8, 0xB9, 0x79, 0xBB,
0x7B, 0x7A, 0xBA, 0xBE, 0x7E, 0x7F, 0xBF, 0x7D, 0xBD, 0xBC, 0x7C,
0xB4, 0x74, 0x75, 0xB5,
0x77, 0xB7, 0xB6, 0x76, 0x72, 0xB2, 0xB3, 0x73, 0xB1, 0x71, 0x70,
0xB0, 0x50, 0x90, 0x91,
0x51, 0x93, 0x53, 0x52, 0x92, 0x96, 0x56, 0x57, 0x97, 0x55, 0x95,
0x94, 0x54, 0x9C, 0x5C,
0x5D, 0x9D, 0x5F, 0x9F, 0x9E, 0x5E, 0x5A, 0x9A, 0x9B, 0x5B, 0x99,
0x59, 0x58, 0x98, 0x88,
0x48, 0x49, 0x89, 0x4B, 0x8B, 0x8A, 0x4A, 0x4E, 0x8E, 0x8F, 0x4F,
0x8D, 0x4D, 0x4C, 0x8C,
0x44, 0x84, 0x85, 0x45, 0x87, 0x47, 0x46, 0x86, 0x82, 0x42, 0x43,
0x83, 0x41, 0x81, 0x80,
0x40
} ;

unsigned short int CRC16(unsigned char *puchMsg, unsigned short int
usDataLen)
{
unsigned char uchCRCHi = 0xFF; /* high byte of CRC initialized */
unsigned char uchCRCLo = 0xFF; /* low byte of CRC initialized */
unsigned uIndex ; /* will index into CRC lookup
table */
while(usDataLen--) /* pass through message buffer */
{
uIndex = uchCRCHi ^ *puchMsg++ ; /* calculate the CRC */
uchCRCHi = uchCRCLo ^ auchCRCHi[uIndex] ;
uchCRCLo = auchCRCLo[uIndex] ;
}
#ifdef INTEL_LIKE_PROCESSOR
Appendix
B.2 CRC calculation
SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 73
return (unsigned short int)((uchCRCLo << 8) | uchCRCHi);
#else
return (unsigned short int)((uchCRCHi << 8) | uchCRCLo);
#endif
}
See also
There are many ways of calculating a CRC checksum. For further information, please refer
to the Modbus Organisation Website (http://www.modbus.org/) , where detailed descriptions
and programming examples are available.
Appendix
B.2 CRC calculation
SITRANS F M MAG 8000 Modbus RTU
74 Operating Instructions, 08/2011, A5E03409989-01

SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 75
Glossary
CRC
Cyclic Redundancy Check. Used for error-checking in Modbus RTU
Modbus master
A Modbus device, which is able to access data in one or more connected Modbus slaves.
Modbus slave
A Modbus device, which is able to respond to requests from a single Modbus master.
RS232
Refers to communication standard defined by EIA/TIA-232 (Physical layer).
RS485
Refers to communication standard defined by EIA/TIA-485 (Physical layer).
Glossary

SITRANS F M MAG 8000 Modbus RTU
76 Operating Instructions, 08/2011, A5E03409989-01

SITRANS F M MAG 8000 Modbus RTU
Operating Instructions, 08/2011, A5E03409989-01 77
Index

A
Application settings, 40
B
Baudrate, 18
C
Cable specifications, 13
Commissioning
Steps, 19
with PDM, 19
Communication modes, 7
Communication parameters, 18
Setup, 21
Configuring the device, 22
Consumption profile, 56
Consumption readings, 68
Consumption statistic, 55
Contact person, 8
Customer profile, 40
D
Data type mapping, 69
Datalog, 59
Device
Address, 17
Name, 17
Document history, 5
Driver settings, 41
E
EDD files
Download, 20
Installation, 20
Electrical connection
General instructions, 13
Shielding, 13
Error messages, 47
Ex Approval, 9
Exception codes, 35
F
Function codes, 25
H
Hardware lock, 18
Hazardous areas, 9
I
Installation
Hardware, 11
Internet
Contact person, 8
Flowdocumentation, 8
Modbus Organisation, 8
L
Leakage statistic, 57
M
Measurement, 40
Menu control, 42
Modbus
Features, 6
Frame, 7
Network, 21
Organisation Website, 8
Technology, 6
Modbus addressing model, 25
O
Operation, 24
P
Parameter access, 19
Parameterization, 22
PDM
Index

SITRANS F M MAG 8000 Modbus RTU
78 Operating Instructions, 08/2011, A5E03409989-01
Commissioning, 19
Commissioning steps, 19
Power control, 53
Pulse output, 45
R
Read coils, 26
Read multiple register, 28
Report Slave ID, 34
S
Safety notes, 9
Sensor characteristics, 43
Service control, 47
System integration, 17
T
Totalization, 40, 45
W
Wiring, 14
Bus termination, 15
RS232 connection diagram, 14
RS485 connection diagram, 14
Write coil, 30
Write protection, 18

www.siemens.com/processautomation
Siemens A/S
Flow Instruments
Nordborgvej 81
DK-6430 Nordborg
Subject to change without prior notice
Order No.: A5E03409989
Lit. No.: A5E03409989-01
Siemens AG 08.2011
For more information
www.siemens.com/flow
!A5E03409989!

S-ar putea să vă placă și