No.

ID Name / Function Note


27.74 1243 Flag 4 LS5 device 63
27.75 1244 Flag 5 LS5 device 63
27.76 1245 Flag 1 LS5 device 64
27.77 1246 Flag 2 LS5 device 64
27.78 1247 Flag 3 LS5 device 64
27.79 1248 Flag 4 LS5 device 64
27.80 1249 Flag 5 LS5 device 64
9.4.5 Factory Settings
SimpIe (function) Extended (configuration) ResuIt
[00.0x] FIag {x}; {x} = 1 to 7
f TRUE, flag {x} becomes TRUE.
Deactivated by default.
FALSE
[00.08] FIag 8 - pre-configured to engine start via timer
f TRUE, flag 8 becomes TRUE.
TRUE once the configured time 1 has been
reached [11.01], and the configured time 2
[11.02] has not been reached as well if the cur-
rent day is the configured day [11.03]
( Chapter 4.7 'Configure LogicsManager'
on page 319)
Not available in operating modes "STOP" and
"MAN"
dependent on
timer
[00.09] Start request in Auto
f TRUE, the engine is started in AUTOMATC
operating mode.
TRUE once discrete input [D 2] is energized.
Note: This function is pre-configured and may be
activated by passing through the command vari-
ables [00.08] LM: Flag 8 or [04.03] Remote
request ('' instead of '0').
Not available in operating modes "STOP" and
"MAN".
dependent on
[D 2]
[00.10] Stop request in Auto
Functions
Appendix
LogicsManager Reference > Factory Settings
37528 easYgen-3400/3500 | Genset Control 676
SimpIe (function) Extended (configuration) ResuIt
f TRUE, the engine is either stopped in AUTO-
MATC operating mode or a start of the engine is
suppressed (also an emergency operation).
Deactivated by default.
Not available in operating modes "STOP" and
"MAN".
FALSE
[00.11] Inhibit emergency run
f TRUE, an emergency operation is inhibited or
interrupted.
Deactivated by default.
Not available in operating modes "STOP" and
"MAN". Only available in application mode ,
, , and .
FALSE
[00.12] UndeIay cIose GCB
f TRUE, the GCB will be closed in an emer-
gency operation without waiting for expiration of
the delayed engine monitoring.
TRUE once emergency mode is enabled.
Only available in application mode to
and operating modes "AUTO" and "MAN".
dependent on
emergency
operation
[00.14] Constant IdIe run
f TRUE, the control outputs an "Constant idle
run" if a start request for the generator is present
Deactivated by default.
FALSE
[00.15] ExternaI acknowIedgment
f TRUE, all alarms are acknowledged from an
external source.
TRUE once discrete input [D 5] is energized.
dependent on
discrete input
[D 5]
[00.16] Operation mode AUTOMATIC
Appendix
LogicsManager Reference > Factory Settings
37528 easYgen-3400/3500 | Genset Control 677
SimpIe (function) Extended (configuration) ResuIt
f TRUE the unit changes into AUTOMATC
operating mode.
Deactivated by default.
FALSE
[00.17] Operation mode MANUAL
f TRUE the unit changes into MANUAL oper-
ating mode.
Deactivated by default.
FALSE
[00.18] Operation mode STOP
f TRUE the unit changes into STOP operating
mode.
Deactivated by default.
FALSE
[00.19] Start without Ioad
f TRUE, the engine is started without load
transfer to the generator (closing the GCB is
blocked).
Deactivated by default.
FALSE
[00.20] Automatic IdIe mode
f TRUE, the control performs an idle run for a
configured time at start-up.
Deactivated by default.
Note
This function is pre-configured and may be acti-
vated by passing through the command variable
[00.09] Start req. in Auto ('' instead of '0').
FALSE
[00.21] Raise frequency/Ioad setpoint
Appendix
LogicsManager Reference > Factory Settings
37528 easYgen-3400/3500 | Genset Control 678
SimpIe (function) Extended (configuration) ResuIt
f TRUE, the frequency/load setpoint will be
raised.
Deactivated by default.
FALSE
[00.22] Lower frequency/Ioad setpoint
f TRUE, the frequency/load setpoint will be low-
ered.
Deactivated by default.
FALSE
[00.23] Raise voItage/power factor setpoint
f TRUE, the voltage/power factor setpoint will be
raised.
Deactivated by default.
FALSE
[00.24] Lower voItage/power factor setpoint
f TRUE, the voltage/power factor setpoint will be
lowered.
Deactivated by default.
FALSE
[00.25] Frequency droop active
f TRUE, the frequency droop is enabled.
TRUE once missing members are detected on
the load share bus.
Not available in operating mode "STOP".
dependent on
missing mem-
bers
[00.26] VoItage droop active
Appendix
LogicsManager Reference > Factory Settings
37528 easYgen-3400/3500 | Genset Control 679
SimpIe (function) Extended (configuration) ResuIt
f TRUE, the voltage droop is enabled.
TRUE once missing members are detected on
the load share bus.
Not available in operating mode "STOP".
dependent on
missing mem-
bers
[00.27] ExternaI mains decoupIing
f TRUE, a mains failure is requested by an
external device.
Deactivated by default
Not available in operation modes "STOP" and
"MAN".
FALSE
[00.28] CriticaI mode
f TRUE, the control performs a critical mode
operation.
Deactivated by default.
TRUE, if no start failure is present and/or dis-
crete input [D 1] is not energized.
Not available in operation modes "STOP" and
"MAN".
dependent on
start failure
and [D 1]
[00.29] Firing speed reached
f TRUE, the unit recognizes that the ignition
speed has been reached.
Deactivated by default.
FALSE
[00.3x] FIag {y}; {x} = 0 to 5, {y} = 9 to 14
f TRUE, flag {y} becomes TRUE.
Deactivated by default
Not available in operation modes "STOP" and
"MAN".
FALSE
[00.36] FIag 15
Appendix
LogicsManager Reference > Factory Settings
37528 easYgen-3400/3500 | Genset Control 680
SimpIe (function) Extended (configuration) ResuIt
f TRUE, flag 15 becomes TRUE.
Prepared for GCB fail to close or Synchroniza-
tion time GCB.
Not available in operating modes "STOP" and
"MAN".
dependent on
GCB fail to
close and
Synchroniza-
tion time GCB
[00.37] FIag 16
f TRUE, flag 16 becomes TRUE.
Prepared for Critical mode or Start without load.
Not available in operating modes "STOP" and
"MAN".
dependent on
Critical mode
and Start
without load
[00.38] Synchronization mode CHECK
f TRUE, the CHECK synchronization mode is
enabled.
Deactivated by default.
Only available in operating mode "AUTO" and
application mode to .
FALSE
[00.39] Synchronization mode PERMISSIVE
f TRUE, the PERMSSVE synchronization
mode is enabled.
Deactivated by default.
Only available in operating mode "AUTO" and
application mode to .
FALSE
[00.40] Synchronization mode RUN
f TRUE, the RUN synchronization mode is ena-
bled.
Deactivated by default.
Only available in operating mode "AUTO" and
application mode to .
FALSE
[00.81] Setpoint 2 frequency enabIed
Appendix
LogicsManager Reference > Factory Settings
37528 easYgen-3400/3500 | Genset Control 681
SimpIe (function) Extended (configuration) ResuIt
f TRUE, the frequency setpoint 2 is enabled.
Deactivated by default.
Not available in operating modes "STOP" and
"MAN".
FALSE
[00.82] Setpoint 2 Ioad enabIed
f TRUE, the load setpoint 2 is enabled.
Deactivated by default.
Not available in operating modes "STOP" and
"MAN".
FALSE
[00.83] Setpoint 2 voItage enabIed
f TRUE, the voltage setpoint 2 is enabled.
Deactivated by default.
Not available in operating modes "STOP" and
"MAN".
FALSE
[00.84] Setpoint 2 power factor enabIed
f TRUE, the power factor setpoint 2 is enabled.
Deactivated by default.
Not available in operating modes "STOP" and
"MAN".
FALSE
[00.85] EnabIe MCB
f TRUE, the MCB is enabled.
TRUE, if discrete input [D 6] is energized and/or
MCB did not fail to close and/or no mains phase
rotation mismatch is detected.
Only available in operating mode "AUTO" and
application mode , , , , ,
and .
dependent on
[D 6] and
MCB closure
and mains
phase rotation
[00.86] Load-dependent start/stop
Appendix
LogicsManager Reference > Factory Settings
37528 easYgen-3400/3500 | Genset Control 682
SimpIe (function) Extended (configuration) ResuIt
f TRUE, load-dependent start/stop is enabled.
Deactivated by default.
Prepared for start request in AUTO and neither
Flag 15 nor Flag 16 are enabled.
Only available in operating mode "AUTO" and
application mode to .
FALSE
[00.8x] Segment no. {y} active; {x} = 7 to 9; {y} = 2 to 4
f TRUE, load-dependent start/stop segment no.
{y} is enabled.
Deactivated by default.
Only available in operating mode "AUTO" and
application mode to .
FALSE
[00.9x] LDSS Priority {y}; {x} = 0 to 2; {y} = 2 to 4
f TRUE, load-dependent start/stop priority {y} is
enabled.
Deactivated by default.
Only available in operating mode "AUTO" and
application mode to .
FALSE
[00.9x] Transition mode {y}; {x} = 3 to 4; {y} = 1 to 2
f TRUE, transition mode {x} is enabled.
Deactivated by default.
Only available in operating mode "AUTO" and
application mode , , , and .
FALSE
[24.1x] PID{y} ctrI. reIease; {x} = 7 to 9; {y} = 1 to 3
f TRUE, PD 1 control is released.
Deactivated by default.
Not available in operating modes "STOP" and
"MAN".
FALSE
Appendix
LogicsManager Reference > Factory Settings
37528 easYgen-3400/3500 | Genset Control 683
SimpIe (function) Extended (configuration) ResuIt
[00.41] ReIay 1 [R01] - Ready for operation OFF
Relay will be de-energized if unit is not ready for
operation or the logics manager output is TRUE.
Deactivated by default
Note: This function is pre-configured and may be
activated by passing through the command vari-
ables [01.09] Shutdown alarm or [04.01] Oper-
ating mode AUTO or [00.01] LM: Flag 1 (''
instead of '0').
The unit is only ready for operation after an start-
up delay following the power supply connection.
FALSE
[00.42] ReIay 2 [R02] - CentraIized aIarm (horn) / freeIy configurabIe
Relay energizes if the internal condition "Horn" is
TRUE
dependent on
Logics Com-
mand Variable
[03.05]
[00.43] ReIay 3 [R03] - Starter / freeIy configurabIe
Relay energizes if the internal condition "Starter"
is TRUE
dependent on
Logics Com-
mand Variable
[03.02]
[00.44] ReIay 4 [R04] - Start/Gas / freeIy configurabIe
Relay energizes if the internal condition "Start/
Gas" is TRUE to energize the start (Diesel) or
gas (Gas) solenoid
dependent on
Logics Com-
mand Variable
[03.28]
[00.45] ReIay 5 [R05] - PregIow / Ignition / freeIy configurabIe
Relay energizes if the internal condition "Pre-
glow / gnition" is TRUE to preglow the Diesel
engine or enabling the ignition of the gas engine
dependent on
Logics Com-
mand Variable
[03.04]
[00.46] ReIay 6 [R06] - Free / Command: cIose GCB
ReIay outputs
Appendix
LogicsManager Reference > Factory Settings
37528 easYgen-3400/3500 | Genset Control 684
SimpIe (function) Extended (configuration) ResuIt
n application mode
and = freely configurable relay (unas-
signed)
n application mode to "Command:
close GCB"
Deactivated by default
FALSE
[00.47] ReIay 7 [R07] - Mains decoupIing / freeIy configurabIe / Command: open GCB
n application mode pre-configured to mains
decoupling. Relay energizes if the internal condi-
tion "Mains decoupling" is TRUE to decouple the
genset from the mains.
n application mode to "Command:
open GCB"
Deactivated by default
dependent on
application
mode and
Logics Com-
mand Variable
[07.25]
[00.48] ReIay 8 [R08] - Free / Command: cIose MCB
n application mode , , , , ,
, , and = freely configurable
relay (unassigned)
n application mode and "Command:
close MCB"
Deactivated by default
FALSE
[00.49] ReIay 9 [R09] - Mains decoupIing / freeIy configurabIe / Command: open MCB
n application mode , , , , ,
, , and pre-configured to mains
decoupling. Relay energizes if the internal condi-
tion "Mains decoupling" is TRUE to decouple the
genset from the mains.
n application mode and "Command:
open MCB"
Deactivated by default
dependent on
application
mode and
Logics Com-
mand Variable
[07.25]
[00.50] ReIay 10 [R10] - AuxiIiary services / freeIy configurabIe
n application mode , , , , ,
, and pre-configured to auxilary
services. Relay energizes if the internal condi-
tion "Aux. services" is TRUE to activate the aux-
iliary services (it energizes prior to an engine
start and de-energizes with the engine stop)
n application mode , and "Com-
mand: close GGB"
dependent on
Logics Com-
mand Variable
[03.01]
[00.51] ReIay 11 [R11] - Warning aIarm cIass active / freeIy configurabIe
Appendix
LogicsManager Reference > Factory Settings
37528 easYgen-3400/3500 | Genset Control 685
SimpIe (function) Extended (configuration) ResuIt
n application mode , , , , ,
, and pre-configured to alarm
classe A or B. Relay energizes if one of the
alarm classes A or B is active
n application mode , and "Com-
mand: open GGB"
dependent on
Logics Com-
mand Variable
[01.08]
[00.52] ReIay 12 [R12] - Shutdown aIarm cIass active / freeIy configurabIe
Relay energizes if one of the alarm classes C, D,
E or F is active
dependent on
Logics Com-
mand Variable
[01.09]
[00.xx] ExternaI digitaI output {y} - Free (externaI expansion card, if connected; {xx} = 63 to 78 ; {y} = 1 to 16)
Control of the external relay {y}, if this is con-
nected
Prepared for:
Deactivated by default
FALSE
[24.xx] ExternaI digitaI output {y} - Free (externaI expansion card, if connected; {xx} = 01 to 16 ; {y} = 17 to 32)
Control of the external relay {y}, if this is con-
nected
Prepared for:
Deactivated by default
FALSE
DI AIarm cIass Pre-assigned to
1 F freely configurable EMERGENCY STOP
2 CONTROL freely configurable LogicsManager Start in
AUTO
3 B freely configurable Low oil pressure
4 B freely configurable Coolant temperature
5 CONTROL freely configurable LogicsManager External
acknowledgement
6 CONTROL freely configurable LogicsManager Enable
MCB
7 fixed Reply MCB
Discrete inputs
Appendix
LogicsManager Reference > Factory Settings
37528 easYgen-3400/3500 | Genset Control 686