CABLE LIST OF GENSET INSTALLATION

Equipment:

DETAILED ENGINEERING
Order: VEC001101

Customer:ROYAL GK PTE LTD

DATE

DOCUMENT

ORDER

Nov-2012 INDEX

Measure Electrical Installations


CUSTOMER

VEC001101

ROYAL GK PTE LTD

- CONTENIDO 1 MEASUREMENT TABLES ................................................................................ 1

CONSISTENTS WITH OUR CONTINUAL PRODUCT IMPROVEMENT POLICY, GUASCOR POWER RESERVES THE RIGHT TO CHANGE ANY SPECIFICATION WITHOUT PRIOR NOTICE.

DATE

DOCUMENT

ORDER

Nov-2012 INDEX

Measure Electrical Installations


CUSTOMER

VEC001101

ROYAL GK PTE LTD

1 1.1

MEASUREMENT TABLES GENSET INSTALLATION, LH

Following items are the measurement of a single genset, LH Type. Total amount of needed material should be multiplied by 13.

POS

DESCRIPTION

Uty

AMOUNT

GENSET CONTROL & POWER PANEL Supply and installation of thegenset control and power electric switchboard, formed by metallic cabinets of Schneider, IP43, full cover door with lock and sealing gasket according technical specifications, including inside the protection and control elements such is shown in single-line diagrams, including connection terminals, grounding connectors, channels, tags, etc. Connected and assembled following IEC 61439 standards. Measurement of unit finished. GENSET CONTROL WIRING Supply and installation of control wiring between Control panel and genset 24Vdc terminal box. It comprises following sub-items -1 x (20x1,5MM2) VV-K 0,6-1kV copper cable with PVC insulation. - 1 x (4x1,5MM2) VV-K 0,6-1kV copper cable with PVC insulation - 2 x (2x2,5 MM2) RV-K 0,6-1kV copper cable with XLPE Grating Polyethylene. - 1 x (3x6 MM2) RV-K 0,6-1kV copper cable with XLPE Grating Polyethylene. - 9 x (2x1,5MM2) 0,6-1kV shielded copper cable with PVC insulation. - 2 x (3x1,5MM2) 0,6-1kV shielded copper cable with PVC insulation. Measurement of executed length. GENSET RPM MEASUREMENT PICK UP WIRING Supply and installation of pick up wiring between Control panel and genset. Pick

QTY

1,00

14,00

13,00

CONSISTENTS WITH OUR CONTINUAL PRODUCT IMPROVEMENT POLICY, GUASCOR POWER RESERVES THE RIGHT TO CHANGE ANY SPECIFICATION WITHOUT PRIOR NOTICE.

DATE

DOCUMENT

ORDER

Nov-2012 INDEX

Measure Electrical Installations


CUSTOMER

VEC001101

ROYAL GK PTE LTD

POS

DESCRIPTION

Uty

AMOUNT

Up terminal to be welded to the cable. The pick-up is supplied with the genset. - 1 x (2x1,5MM2) 0,6-1kV shielded copper cable with PVC insulation. Measurement of executed length. GENSET CPU95 IGNITION UNIT WIRING Supply and installation of CPU95 ignition unit wiring between Control panel and CPU95 unit installed in genset. - 1 x (2x1,5MM2) 0,6-1kV shielded copper cable with PVC insulation. - 1 x (2x0,34MM2) 0,6-1kV shielded twisted-pair communication cable Measurement of executed length. REMOTE COOLER FANS POWER SUPPLY WIRING Supply and installation of remote cooler fans power supply wiring between genset control panel and remote cooler terminal box. - 6 x (3x2,5MM2 + 1G) 0,6-1kV RV-K 0,6-1kV copper cable with XLPE Grating Polyethylene. Measurement of executed length. COOLING PUMPS POWER SUPPLY WIRING Supply and installation of cooling pumps power supply wiring between genset control panel and cooling pumps. - 2 x (3x2,5MM2 + 1G) 0,6-1kV RV-K 0,6-1kV copper cable with XLPE Grating Polyethylene. Measurement of executed length. ROOM VENTILATION FAN POWER SUPPLY WIRING Supply and installation of cooling pumps power supply wiring between control panel and room ventilation fan. - 1 x (3x2,5MM2 + 1G) 0,6-1kV RV-K 0,6-1kV copper cable with XLPE Grating Polyethylene. Measurement of executed length. GENSET PREHEATING POWER SUPPLY WIRING Supply and installation of genset preheating power supply between control panel andgenset AC power terminal box. - 1 x (13x2,5MM2 + 1G) 0,6-1kV RV-K

12,00

40,00

17,00

10

13,00

CONSISTENTS WITH OUR CONTINUAL PRODUCT IMPROVEMENT POLICY, GUASCOR POWER RESERVES THE RIGHT TO CHANGE ANY SPECIFICATION WITHOUT PRIOR NOTICE.

DATE

DOCUMENT

ORDER

Nov-2012 INDEX

Measure Electrical Installations


CUSTOMER

VEC001101

ROYAL GK PTE LTD

POS

DESCRIPTION

Uty

AMOUNT

10

11

12

13

0,6-1kV copper cable with XLPE Grating Polyethylene This cable can be splitted, for example in 2x (7x2,5MM2 +1G) Measurement of executed length. KNOCKING DETECTION UNIT Knocking Detection unit, with ISU unit and power supply converter. Installed in a IP45 box. This item is supplied as a loose item with the genset and has to be installed not further than 6m of the genset.. KNOCKING DETECTION UNIT WIRING Supply and installation of wiring between knocking detection unit and control panel. - 1 x CAN Open cable (without connectors) - 1 x (2x1,5MM2) 0,6-1kV shielded copper cable with PVC insulation - 1 x (2x1,5MM2) VV-K 0,6-1kV copper cable with PVC insulation Measurement of executed length. ALTERNATOR CONTROL WIRING Supply and installation of wiring of control signals of the alternator between alternator wiring boxes and control panel and also for the alternator preheating resistor: - 1 x (2x1,5MM2) 0,6-1kV shielded copper cable with PVC insulation. (Faston terminals to be provided at alternator side) - 1 x (2x1,5MM2) VV-K 0,6-1kV copper cable with PVC insulation Measurement of executed length. GAS TRAIN WIRING Supply and installation of wiring of control signals of the gas train between gas train and control panel: - 4 x (2x1,5MM2) VV-K 0,6-1kV copper cable with PVC insulation - 1 x (3x1,5MM2+G) RV-K 0,6-1kV copper cable with XLPE Grating Polyethyleneinsulation Measurement of executed length. OIL TANK WIRING Supply and installation of wiring of prelube pump and oil tank between

QTY

20,00

13,00

17,00

18,00

CONSISTENTS WITH OUR CONTINUAL PRODUCT IMPROVEMENT POLICY, GUASCOR POWER RESERVES THE RIGHT TO CHANGE ANY SPECIFICATION WITHOUT PRIOR NOTICE.

DATE

DOCUMENT

ORDER

Nov-2012 INDEX

Measure Electrical Installations


CUSTOMER

VEC001101

ROYAL GK PTE LTD

POS

DESCRIPTION

Uty

AMOUNT

oiltank and control panel: - 2 x (2x1,5MM2) VV-K 0,6-1kV copper cable with PVC insulation - 1 x (2x2,5MM2+G) RV-K 0,6-1kV copper cable with XLPE Grating Polyethylene insulation. Measurement of executed length.

1.2

GENSET INSTALLATION, RH

Following items are the measurement of a single genset, RH Type. Total amount of needed material should be multiplied by 13.

POS

DESCRIPTION

Uty

AMOUNT

GENSET CONTROL & POWER PANEL Supply and installation of thegenset control and power electric switchboard, formed by metallic cabinets of Schneider, IP43, full cover door with lock and sealing gasket according technical specifications, including inside the protection and control elements such is shown in single-line diagrams, including connection terminals, grounding connectors, channels, tags, etc. Connected and assembled following IEC 61439 standards. Measurement of unit finished. GENSET CONTROL WIRING Supply and installation of control wiring between Control panel and genset 24Vdc terminal box. It comprises following sub-items -1 x (20x1,5MM2) VV-K 0,6-1kV copper cable with PVC insulation. - 1 x (4x1,5MM2) VV-K 0,6-1kV copper cable with PVC insulation - 2 x (2x2,5 MM2) RV-K 0,6-1kV copper cable with XLPE Grating Polyethylene. - 1 x (3x6 MM2) RV-K 0,6-1kV copper cable with XLPE Grating Polyethylene. - 9 x (2x1,5MM2) 0,6-1kV shielded copper cable with PVC insulation. - 2 x (3x1,5MM2) 0,6-1kV shielded

QTY

1,00

12,00

CONSISTENTS WITH OUR CONTINUAL PRODUCT IMPROVEMENT POLICY, GUASCOR POWER RESERVES THE RIGHT TO CHANGE ANY SPECIFICATION WITHOUT PRIOR NOTICE.

DATE

DOCUMENT

ORDER

Nov-2012 INDEX

Measure Electrical Installations


CUSTOMER

VEC001101

ROYAL GK PTE LTD

POS

DESCRIPTION

Uty

AMOUNT

copper cable with PVC insulation. Measurement of executed length. GENSET RPM MEASUREMENT PICK UP WIRING Supply and installation of pick up wiring between Control panel and genset. Pick Up terminal to be welded to the cable. The pick-up is supplied with the genset. - 1 x (2x1,5MM2) 0,6-1kV shielded copper cable with PVC insulation. Measurement of executed length. GENSET CPU95 IGNITION UNIT WIRING Supply and installation of CPU95 ignition unit wiring between Control panel and CPU95 unit installed in genset. - 1 x (2x1,5MM2) 0,6-1kV shielded copper cable with PVC insulation. - 1 x (2x0,34MM2) 0,6-1kV shielded twisted-pair communication cable Measurement of executed length.. REMOTE COOLER FANS POWER SUPPLY WIRING Supply and installation of remote cooler fans power supply wiring between genset control panel and remote cooler terminal box. - 6 x (3x2,5MM2 + 1G) 0,6-1kV RV-K 0,6-1kV copper cable with XLPE Grating Polyethylene. Measurement of executed length. COOLING PUMPS POWER SUPPLY WIRING Supply and installation of cooling pumps power supply wiring between genset control panel and cooling pumps. - 2 x (3x2,5MM2 + 1G) 0,6-1kV RV-K 0,6-1kV copper cable with XLPE Grating Polyethylene. Measurement of executed length. ROOM VENTILATION FAN POWER SUPPLY WIRING Supply and installation of cooling pumps power supply wiring between control panel and room ventilation fan. - 1 x (3x2,5MM2 + 1G) 0,6-1kV RV-K 0,6-1kV copper cable with XLPE Grating Polyethylene. Measurement of executed length. GENSET PREHEATING POWER

13,00

15,00

40,00

18,00

10,00

15,00

CONSISTENTS WITH OUR CONTINUAL PRODUCT IMPROVEMENT POLICY, GUASCOR POWER RESERVES THE RIGHT TO CHANGE ANY SPECIFICATION WITHOUT PRIOR NOTICE.

DATE

DOCUMENT

ORDER

Nov-2012 INDEX

Measure Electrical Installations


CUSTOMER

VEC001101

ROYAL GK PTE LTD

POS

DESCRIPTION

Uty

AMOUNT

10

11

SUPPLY WIRING Supply and installation of genset preheating power supply between control panel andgenset AC power terminal box. - 1 x (13x2,5MM2 + 1G) 0,6-1kV RV-K 0,6-1kV copper cable with XLPE Grating Polyethylene This cable can be splitted, for example in 2x (7x2,5MM2 +1G) Measurement of executed length. KNOCKING DETECTION UNIT Knocking Detection unit, with ISU unit and power supply converter. Installed in a IP45 box. This item is supplied as a loose item with the genset and has to be installed not further than 6m of the genset.. KNOCKING DETECTION UNIT WIRING Supply and installation of wiring between knocking detection unit and control panel. - 1 x CAN Open cable (without connectors) - 1 x (2x1,5MM2) 0,6-1kV shielded copper cable with PVC insulation - 1 x (2x1,5MM2) VV-K 0,6-1kV copper cable with PVC insulation Measurement of executed length. ALTERNATOR CONTROL WIRING Supply and installation of wiring of control signals of the alternator between alternator wiring boxes and control panel and also for the alternator preheating resistor: - 1 x (2x1,5MM2) 0,6-1kV shielded copper cable with PVC insulation (Faston terminals to be provided at alternator side) - 1 x (2x1,5MM2) VV-K 0,6-1kV copper cable with PVC insulation Measurement of executed length. GAS TRAIN WIRING Supply and installation of wiring of control signals of the gas train between gas train and control panel: - 4 x (2x1,5MM2) VV-K 0,6-1kV copper cable with PVC insulation - 1 x (3x1,5MM2+G) RV-K 0,6-1kV

QTY

20,00

13,00

12

15,00

CONSISTENTS WITH OUR CONTINUAL PRODUCT IMPROVEMENT POLICY, GUASCOR POWER RESERVES THE RIGHT TO CHANGE ANY SPECIFICATION WITHOUT PRIOR NOTICE.

DATE

DOCUMENT

ORDER

Nov-2012 INDEX

Measure Electrical Installations


CUSTOMER

VEC001101

ROYAL GK PTE LTD

POS

DESCRIPTION

Uty

AMOUNT

copper cable with XLPE Grating Polyethylene insulation Measurement of executed length. 13 OIL TANK WIRING Supply and installation of wiring of prelube pump and oil tank between oil tank and control panel: - 2 x (2x1,5MM2) VV-K 0,6-1kV copper cable with PVC insulation - 1 x (2x2,5MM2+G) RV-K 0,6-1kV copper cable with XLPE Grating Polyethylene insulation. Measurement of executed length. M 20,00