8 MGD Seawater Desalination Project Tender Enquiry Document for 110 kV Switchyard

ANNEX II SCADA I/O LIST The following are the minimum requirement of DCS Digital & Analog input / output per equipment / feeder. 1.0 1.1 Digital Inputs 110 kV CB (Typical for lines, transformers & B/C feeders) CB status Open & close CB operating mechanism trouble CB SF6 Gas pressure low (alarm) CB SF6 gas pressure very low (lock-out) CB L/R selector switch on Local 1.2 110 kV Isolators / Earth switches (Typical for lines, transformers, B/C & Bus PT feeders) Isolator status Open & close Isolator operating mechanism fail (Grouped alarm per feeder) Isolator L/R selector switch on Local (Grouped alarm per feeder) Earth switch status Open & Close 1.3 Line relay panel (Typical) IDMT over current protection operated IDMT earth fault protection operated Local breaker back-up (50 LBB) operated Over voltage protection operated Under voltage relay operated Line VT fuse failure relay operated Line relay panel DC fail Line protection relay fail Line lockout relay operated Line lockout relay supervision operated Line CB trip circuit-1 supervision operated Line CB trip circuit-2 supervision operated 1.4 Transformer Relay Panel (Typical) Transformer differential protection operated Transformer instantaneous over current protection operated Transformer IDMT overcurrent protection operated Transformer instantaneous earth fault protection operated Local breaker back-up (50 LBB) operated Transformer LV REF (64R) operated Transformer overfluxing relay (61) operated Transformer neutral over current (51N) operated Transformer buchholz alarm operated Transformer winding temperature high alarm Transformer oil temperature high alarm Transformer OLTC surge relay alarm
P2Sec B1-Swyd

FICHTNER India

Doc. No.6104-EL-SPC-610-001 Rev. : R0 Page : B1 : 26

5.8 MGD Seawater Desalination Project Tender Enquiry Document for 110 kV Switchyard

Transformer buchholz trip operated Transformer winding temperature trip operated Transformer oil temperature trip operated Transformer PRD trip operated Transformer OLTC surge relay trip operated Transformer relay panel DC-1 fail Transformer relay panel DC-2 fail Transformer main-1 protection relay fail Transformer main-2 protection relay fail Transformer main-1 lockout relay operated Transformer main-2 lockout relay operated Transformer main-1 lockout relay supervision operated Transformer main-2 lockout relay supervision operated Transformer CB trip circuit-1 supervision operated Transformer CB trip circuit-2 supervision operated 1.5 Bus- Tie Relay Panel (Typical) Local breaker back-up (50 LBB) operated Bus tie relay panel DC fail Bus tie lockout relay operated Bus tie lock-out relay supervision operated Bus tie CB trip circuit-1 supervision operated Bus tie CB trip circuit-2 supervision operated Bus PT fuse failure relay operated Bus under voltage relay operated 1.6 Busbar Protection Relay Panel (Typical) Bus zone-1 (Main bus) busbar protection operated Bus zone-2 (Transformer bus) busbar protection operated Bus check zone busbar protection operated Busbar protection lockout relay operated (for each feeder) Busbar protection lockout relay supervision operated (for each feeder) Busbar protection CTs supervision operated Busbar protection relay panel DC-1 fail Busbar protection relay panel DC-2 fail 1.7 Control panel (Typical for Lines, Transformer, Bus tie & Bus PT / ES) Control panel DC-1 fail Control panel DC-2 fail DCS / control panel selector switch on Control panel Synchronising selector switch ON Annunciator DC supply fail Annunciator AC supply fail Synchronising permissive ON RTCC Panel (Typical) By others OLTC L/R selector switch on Local RTCC panel DC fail Tap position upper limit reached Tap position lower limit reached
FICHTNER India
Doc. No.6104-EL-SPC-610-001 Rev. : R0 Page : B1 : 27

1.8

P2Sec B1-Swyd

5.8 MGD Seawater Desalination Project Tender Enquiry Document for 110 kV Switchyard

1.9

110V DC system 110V DC battery charger-1 fail 110V DC battery charger-2 fail Charger-1 on boost mode Charger-2 on boost mode DC system on back-up power supply Battery voltage low Charger input power supply fail Tariff metering panel (Main & Check) Tariff metering panel DC fail TVM fail Fuse failure relay operated

1.10

2.0

Digital outputs / Control outputs Close / Open operation of all 110 kV CBs Close / Open operation of all 110 kV Isolators Tap position Raise / Lower (By others)

3.0 3.1

Analog Inputs Lines (Typical) Voltage Current kW kVAr kWH kVArH Transformer (Typical) Current kW kVAr kWH kVArH Tap position (by others) Bus Tie / Bus PT Bus-1 voltage Bus-1 frequency Bus-2 voltage Bus-2 frequency

3.2

3.3

P2Sec B1-Swyd

FICHTNER India

Doc. No.6104-EL-SPC-610-001 Rev. : R0 Page : B1 : 28