Exsym Corporation
ATS-TS-060151
05-4 00 SIE 17 0005 05-4 00 SIE 17 0006 05-4 00 SIE 17 0007 05-4 00 SIE 17 0009 05-4 00 SIE 17 0010 05-4 00 SIE 17 0011 05-4 00 SIE 17 0012 05-4 00 SIE 17 0013
132kV XLPE cable SF6 gas immersed sealing end 132kV XLPE cable oil immersed sealing end 132kV XLPE cable pre-molded insulation joint Sheath voltage limiter 132kV, 220kV cable Cross bond link with SVL for 132kV & 220kV cable Solid bond link (6 way) for 132kV & 220kV cable Solid bond link (3 way) for 132kV & 220kV cable Solid bond link box with SVL for 132kV & 220kV cable
EXSYM CORPORATION
ATS-TS-060151
3-1-1 Termination, joi nt, link box and sheath voltage limiter Test methods Visual and dimensional aspect shall be checked. Requirements In accordance with our approved drawing
Test item
3-1-2 Sheath voltage limiter for link box an d gas immersed sealing end Test item Test methods Measuring the arrester voltage at applied D.C. 1mA Min.:6.0kV
Requirements Max.:7.0kV
1. Operating voltage
(Gapless arrester) The insulation resistance shall be measure using D.C. voltage source of about 1kV Not less than 10M
2. Insulation resistance
EXSYM CORPORATION
ATS-TS-060151
3-1-3 Joints Test item Test methods The test voltage shall be raised gradually to 190kV value and held for 30 minutes. Testing temperature The test voltage shall be raised gradually to and held at 2.0U0 for 10s . There shall be no detectable discharge from the test object at 2.0 U0 Testing temperature ambient temperature ambient temperature Requirements
Pr e- m ol de d u ni t of i ns u l at i o n j oi n t
Max. 10pC at 152kV(2.0U0) with background noise level not more than 2pC.
Pr e- m ol de d u ni t of i ns u l at i o n j oi n t
3. Test of the main insulation of the joints Integrity of insulated gap 25kV DC for 15min.
Less than 20k. No breakdown of the insulation shall occur. No observation of separation between semi-conducting rubber and insulation rubber by visual. No observation of crack by visual.
Pr e- m ol de d u ni t of i ns u l at i o n j oi n t
Mechanical stretch of each rubber component over a mandrel equal in diameter to the contractors site assembly mandrel. (Expanding ratio of inner diameter of rubber unit: after expansion/before expansion = more than 2.5.)
EXSYM CORPORATION
ATS-TS-060151
4. Additional test for main insulation of Following test shall be carried out for the insulation polymer in each manufacturing batch. joints FTIR analysis for characterizing the insulation polymer. Cleanliness measurement on insulation materials. Dielectric loss angles measurement for the insulation polymer at 90. Following test shall be carried out for the conducting polymer in each manufacturing batch. Polymer shall be same as used for the type test. TGA analysis for characterizing the carbon black content.
Pr e - m old e d un i t of i ns u l at i on j oi n t
Polymer shall be same as used for the type test. No observation of conductive contamination more than 500m. Less than 1%.
EXSYM CORPORATION
ATS-TS-060151
3-1-4 Terminations Test item Test methods The test voltage shall be raised gradually to 190kV value and held for 30 minutes. Testing temperature The test voltage shall be raised gradually to and held at 2.0U0 for 10s . There shall be no detectable discharge from the test object at 2.0 U0 Testing temperature ambient temperature ambient temperature Requirements
Max. 10pC at 152kV(2.0U0) with background noise level not more than 2pC.
EXSYM CORPORATION