Sunteți pe pagina 1din 10

Data sheet

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

For the monitoring of currents in single-phase AC/DC systems, ABBs CM range comprises a wide selection of powerful and compact devices, all featuring only 22.5mm(0.89in) width. This range includes current monitoring relays for over- and undercurrent protection from 3 mA to 15A.
2CDC 251 245 F0005

Incorporating ABBs long-term experience, the CM range provides your electric installation with the highest safety and reliability.

Characteristics Monitoring of DC and AC currents from 3 mA to 15 A TRMS measuring principle One device includes 3 measuring ranges Over- or undercurrent monitoring congurable Hysteresis adjustable from 3-30% Tripping delay TV adjustable 0; 0.1-30 s 3 supply voltage versions 2 c/o contacts 22.5 mm (0.89 in) width 3 LEDs for indication of operational states Order data Current monitoring relays
Type CM-SRS.21 Control supply voltage 24-240 V AC/DC 110-130 V AC 220-240 V AC CM-SRS.22 24-240 V AC/DC 110-130 V AC 220-240 V AC

Approvals

A C D K E L

UL 508, CAN/CSA C22.2 No.14 GL GOST CB Scheme CCC RMRS (pending)

Marks

a b

CE C-Tick

Measuring ranges 3-30 mA, 10-100 mA, 0.1-1 A

Order code 1SVR 430 840 R0400 1SVR 430 841 R0400 1SVR 430 841 R1400

0.3-1.5 A, 1-5 A, 3-15 A

1SVR 430 840 R0500 1SVR 430 841 R0500 1SVR 430 841 R1500

Accessories
Type ADP.01 MAR.02 COV.01 Description Adapter for screw mounting Marker label for devices with DIP switches Sealable transparent cover Order code 1SVR 430 029 R0100 1SVR 430 043 R0000 1SVR 430 005 R0100

Functions Operating controls


1 Adjustment of the threshold value (MIN = Default) 2 Adjustment of the hysteresis (MIN = Default) 3 Indication of operational states U/T: green LED control supply voltage, timing R: yellow LED relay status U: red LED over- / undercurrent
2CDC 251 245 F0005

1 2 3 4

4 Adjustment of the tripping delay TV 5 DIP switches (see DIP switch functions)

Application Depending on the configuration, the current monitoring relays CM-SRS.2 can be used for over- b or undercurrent monitoring a in single-phase AC and/or DC systems. The devices work according to the open-circuit principle. Operating mode The CM-SRS.2 has 2 c/o contacts. There are 2 versions available, CM-SRS.21 with 3 measuring ranges: 3-30 mA, 10100mA, 0,1-1 A and CM-SRS.22 with ranges: 0.3-1.5 A, 1-5 A, 3-15 A. The measuring range is selected by connecting the monitored wire to the corresponding terminal B1/B2/B3-C. The unit is adjusted with potentiometers and switches on the top of the unit. The selection of over- b or undercurrent monitoring a is made with a DIP switch . Potentiometers, with direct reading scale, allow the adjustment of the threshold value I, of the hysteresis % and of the tripping delay TV. The hysteresis % is adjustable within a range of 3 to 30% of the threshold value, and the tripping delay TV over a range of instantaneous to a 30 s delay.

2 - Current monitoring relays CM-SRS.2 | Data sheet

Function diagram: overcurrent monitoring

The current to be monitored (measured value) is applied to terminals B1/B2/B3-C. The supply voltage applied to terminals A1-A2 is displayed by the glowing green LED. If the measured value exceeds the adjusted threshold value, the tripping delay TV starts and the red LED (overcurrent) glows. Timing of TV is displayed by the flashing W green LED. When TV is complete and the measured value still exceeds the threshold value minus the adjusted hysteresis, the output relays energize and the yellow LED (relay energized) glows. If the measured value decreases below the threshold value minus the adjusted hysteresis, the output relays de-energize and the red and yellow LEDs turn off.
A1-A2 Threshold Hysteresis Measured value 11-14 (15-18) 11-12 (15-16) 21-24 (25-28) 21-22 (25-26) green LED red LED yellow LED TV < TV

Function diagram: undercurrent monitoring

The current to be monitored (measured value) is applied to terminals B1/B2/B3-C. The supply voltage applied to terminals A1-A2 is displayed by the glowing green LED. If the measured value decreases below the adjusted threshold value, the tripping delay TV starts and the red LED (undercurrent) flashes W . Timing of TV is displayed by the flashing W green LED. When TV is complete and the measured value is still below the threshold value plus the adjusted hysteresis, the output relays energize and the yellow LED (relay energized) glows. If the measured value exceeds the threshold value plus the adjusted hysteresis, the output relays de-energize and the red and yellow LEDs turn off.
A1-A2 Measured value Hysteresis Threshold 11-14 (15-18) 11-12 (15-16) 21-24 (25-28) 21-22 (25-26) green LED red LED yellow LED TV < TV

Data sheet | Current monitoring relays CM-SRS.2 - 3

2CDC 252 211 F0205

2CDC 252 210 F0205

Connection diagram
A1 B1 1115 B2 2125 B3 2125
A1-A2 B1-C Control supply voltage Measuring range 1: CM-SRS.21: 3-30 mA

B1 B2 B3 1115 C

CM-SRS.22: 0.3-1.5 A B2-C Measuring range 2: CM-SRS.21: 10-100 mA

A1 A2 1216 1418 2226 2428 1418 2428 1216 2226 C A2

2CDC 252 205 F0005

CM-SRS.22: 1-5 A B3-C Measuring range 3: CM-SRS.21: 0.1-1 A

CM-SRS.22: 3-15 A 1115-1216/1418 Output contact - open-circuit principle

DIP switch functions


1
2CDC 252 272 F0005

ON OFF

Undercurrent monitoring Overcurrent monitoring


OFF = Default

4 - Current monitoring relays CM-SRS.2 | Data sheet

Technical data Data at Ta = 25 C and rated values, unless otherwise indicated Input circuit
Supply circuit Rated control supply voltage US Rated control supply voltage tolerance Rated frequency Current / power consumption 24 V DC 115 V AC 230 V AC On-period Power failure buffering time Transient overvoltage protection Measuring circuit Monitoring function Measuring method Measuring inputs terminal connection measuring range input resistance pulse overload capacity t < 1 s continuous capacity Threshold value Tolerance of the adjusted threshold value Hysteresis related to the threshold value Measuring signal frequency range Rated measuring signal frequency range Maximum response time AC DC Accuracy within the control supply voltage tolerance Accuracy within the temperature range Timing circuit Delay time TV Repeat accuracy (constant parameters) Tolerance of the adjusted delay time Accuracy within control supply voltage tolerance Accuracy within temperature range 0 or 0.1-30 s adjustable 0.07% of full scale t 0.5% t 0.06% / C 24 mA / 2.6 VA 100% 20 ms varistors B1/B2/B3-C-C over- or undercurrent monitoring configurable TRMS measuring principle CM-SRS.21 B1-C 3.3 B2-C 1 B3-C 0.1 10 A CM-SRS.22 B1-C 0.05 1A 2A B2-C 0.01 50 A 7A B3-C 3-15 A 0.0025 100 A 17 A A1-A2 110-130 V AC -15...+10% 50/60 Hz 12 mA / 2.6 VA 50/60 Hz or DC 30 mA / 0.75 W 17 mA / 1.9 VA 11 mA / 2.6 VA 220-240 V AC 24-240 V AC/DC

3-20 mA 10-100 mA 0.1-1 A

0.3-1.5 A 1-5 A

500 mA 1 A 50 mA

150 mA 1.5 A

adjustable within the indicated measuring range 10% of the range end value 3-30% adjustable DC / 15 Hz - 2 kHz DC / 50-60 Hz 80 ms 120 ms U 0.5% U 0.06% / C

Indication of operational states


Control supply voltage U/T: green LED

Measured value

U: red LED

Relay status

R: yellow LED

V: control supply voltage applied W: tripping delay TV active V: overcurrent W: undercurrent V: relay energized

Data sheet | Current monitoring relays CM-SRS.2 - 5

Output circuits
Kind of output 1115-1216/1418 2125-2226/2428 Operating principle relay, 1st c/o contact relay, 2nd c/o contact open-circuit principle (output relay energizes if the measured value exceeds adjusted threshold value) Contact material Rated operational voltage Ue (VDE 0110, IEC/EN 60947-1) Minimum switching voltage / minimum switching current Maximum switching voltage / maximum switching current Rated operational current Ie (IEC/EN 60947-5-1) AC12 (resistive) at 230 V AC15 (inductive) at 230 V DC12 (resistive) at 24 V DC13 (inductive) at 24 V AC rating (UL 508) utilization category (Control Circuit Rating Code) max. rated operational voltage max. continuous thermal current at B 300 max. making/breaking apparent power (Make/Break) at B 300 Mechanical lifetime Electrical lifetime (AC12, 230 V, 4 A) Maximum fuse rating to achieve short-circuit protection n/c contact n/o contact 30 x 106 switching cycles 0.1 x 106 switching cycles 10 A fast-acting 10 A fast-acting AgNi 250 V 24 V / 10 mA 250 V AC / 4 A AC 4A 3A 4A 2A B 300 300 V AC 5A 3600/360 VA

d / falls below c the

General data
MTBF Dimensions (W x H x D) product dimensions packaging dimensions Weight net weight available on request 22.5 x 78 x 100 mm (0.89 x 3.07 x 3.94 in) 81 x 106 x 26 mm (3.19 x 4.17 x 1.02 in) CM-SRS.22 version 24-240 V AC/DC: 0.140 kg (0.309 lb) version 110-130 V AC: 0.168 kg (0.370 lb) version 220-240 V AC: 0.169 kg (0.373 lb) CM-SRS.22 version 24-240 V AC/DC: 0.145 kg (0.320 lb) version 110-130 V AC: 0.170 kg (0.375 lb) version 220-240 V AC: 0.171 kg (0.377 lb) gross weight CM-SRS.22 version 24-240 V AC/DC: 0.163 kg (0.359 lb) version 110-130 V AC: 0.190 kg (0.419 lb) version 220-240 V AC: 0.191 kg (0.421 lb) CM-SRS.22 version 24-240 V AC/DC: 0.167 kg (0.368 lb) version 110-130 V AC: 0.193 kg (0.425 lb) version 220-240 V AC: 0.194 kg (0.428 lb) Material of enclosure Mounting Mounting position Degree of protection enclosure terminals PA 6 DIN rail (IEC/EN 60715) any IP50 IP20

6 - Current monitoring relays CM-SRS.2 | Data sheet

Electrical connection
Wire size fine-strand with(out) wire end ferrule rigid Stripping length Tightening torque 2 x 0.75-2.5 mm (2 x 18-14 AWG) 2 x 0.5-4 mm (2 x 20-12 AWG) 7 mm (0.28 in) 0.6-0.8 Nm (5.31-7.08 lb.in)

Environmental data
Ambient temperature operation storage Damp heat (IEC 60068-2-30) Vibration (sinusoidal) (IEC/EN 60255-21-1) Shock (IEC/EN 60255-21-2) -20...+60 C -40...+85 C 55 C, 6 cycle class 2 class 2

Isolation data
Rated insulation voltage (VDE 0110, IEC/EN 60947-1, IEC/EN 60255-5) Rated impulse withstand voltage Uimp (IEC/EN 60947-1, IEC/EN 60255-5) Test voltage between all isolated circuits (type test) Pollution degree (VDE 0110, IEC 664, IEC/EN 60255-5) Overvoltage category (VDE 0110, IEC 664, IEC/EN 60255-5) supply / measuring circuit / output supply / output 1 / output 2 supply / measuring circuit / output supply / output 1 / output 2 rated insulation voltage 250 V rated insulation voltage 600 V 600 V 250 V 6 kV 1.2/50 s 4 kV 1.2/50 s 2.0 kV, 50 Hz 2.5 kV, 50 Hz 3 III

Standards
Product standard Low Voltage Directive EMC Directive RoHS Directive IEC/EN 60255-6 2006/95/EC 2004/108/EC 2002/95/EC

Electromagnetic compatibility
Interference immunity to electrostatic discharge radiated, radio-frequency, electromagnetic field electrical fast transient / burst surge conducted disturbances, induced by radio-frequency fields Interference emission high-frequency radiated high-frequency conducted IEC/CISPR 22, EN 55022 IEC/CISPR 22, EN 55022 IEC/EN 61000-6-3 Class B Class B IEC/EN 61000-4-2 IEC/EN 61000-4-3 IEC/EN 61000-4-4 IEC/EN 61000-4-5 IEC/EN 61000-4-6 IEC/EN 61000-6-2 Level 3 Level 3 Level 3 Level 3 Level 3

Data sheet | Current monitoring relays CM-SRS.2 - 7

Technical diagrams Load limit curves


V 300 V 200 100 80 60 50 40 30 20 10 0.1
V 300 V 200 100 80 60 50 40 30 20 10 0.1

2CDC 252 194 F0205

0.2

0.5

2 I

10 A

0.2

0.5

2 I

10 A

AC load (resistive)

DC load (resistive)

0.9 0.8 F 0.7


2CDC 252 192 F0205

Switching cycles

1.0

250 V resistive load

0.5 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 cos

Switching current [A]

Derating factor F for inductive AC load

Contact lifetime

8 - Current monitoring relays CM-SRS.2 | Data sheet

2CDC 252 148 F0206

0.6

2CDC 252 193 F0205

Dimensions in mm and inches


109.5 4.31 102 4.02 22.5 0.886

78 3.07

1 0.155

100 3.94

5.5 0.216

CM-SRS.2

6.5 0.256

62.5 2.461 10 0.394 20 0.787

11.5 0.453

60 2.362 70 2.756
ADP.01 - Adapter for screw mounting

4T22
18 0.709 21 0.827

MAR.02 - Marker label for devices with DIP switches

22.5 0.886

7 0.275 3.5 0.138

68.5 2.70

front-to-back size 107

COV.01 - Sealable transparent cover

Further documentation
Document title Electronic products and relays Document type Technical catalogue Document number 2CDC 110 004 C020x

You can find the documentation on the internet at www.abb.com/lowvoltage -> Control Products -> Electronic Relays and Controls -> Single Phase Monitors

2CDC 252 185 F0005

2CDC 252 010 F0010

8 0.314

2CDC 252 008 F0010

2CDC 252 031 F0003

Data sheet | Current monitoring relays CM-SRS.2 - 9

Contact us

You can find the address of your local sales organisation on the ABB home page http://www.abb.com/contacts -> Low Voltage Products and Systems

Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2011 ABB All rights reserved

Document number 2CDC 112 098 D0202 (09.2011)

ABB STOTZ-KONTAKT GmbH P. O. Box 10 16 80 69006 Heidelberg, Germany Phone: +49 (0) 6221 7 01-0 Fax: +49 (0) 6221 7 01-13 25 E-mail: info.desto@de.abb.com

S-ar putea să vă placă și