POWER CABLE AMPACITY

(132 kV)

132 kV, 1200 mm2


In trench section
In HDD crossing section
In Duct bank for crossing section

Final Ampacity calculation N7144.xmcd

22.03.2013

CONTENTS
Variable Data (General)

Power Cable Ampacity Calculations


1.

AC Resistance of Conductor

13

2.

Dielectric Loss per Unit Length for the Insulation

15

3.

Loss Factor for Metallic Screen and Sheath

15

4.

Calculation of Thermal Resistance

21

5.

Conductor Temperature Rise above the Ambient

26

6.

Continuous Current Carrying Capacity of one 132 kV circuit

26

7.

Reduction factor of one 132 kV Circuit

29

8.

Super position method to calculate interaction of Brugg 132 kV cable


circuit and two existing 400 kV cable circuits

39

Reduction factor of interaction of Brugg 132 kV cable circuits with the


two existing 400 kV cable circuits

51

9.

Power Cable Impedance Calculations


1.

Positive/Negative Sequence Impedance

76

2.

Zero Impedance

76

Final Ampacity calculation N7144.xmcd

22.03.2013

POWER CABLE AMPACITY


CALCULATIONS
IEC 60287 & CIGRE WG B1-03

Final Ampacity calculation N7144.xmcd

22.03.2013

CABLE TYPE: 132 kV XLPE cable, 12sqmm, copper conductor, lead & HDPE sheathed (BRUGG)
INSTALLATION PLACE: ABU DHABI - U.A.E.
PROJECT: ABU DHABI 26 / ETA, TRANSCO N7144

VARIABLE DATA
A. Electrical System Data:

U p_400 := 400000

(Phase to phase voltage, V)

U p_132 := 132000

(Phase to phase voltage, V)

fc := 50

(Frequency, Hz)

:= 2. fc

(Angular frequency, Hz)

Iccs_400 := 63000

(Max. earth-fault current in cable sheath, A)

Iccs_132 := 31500

(Max. earth-fault current in cable sheath, A)

tcc := 0.5

(Short-circuit time in the metallic sheath, sec)

P 400tr := 1102.3

(Transmission capacity for induced voltage calculation, MVA)

P 400hdd := 568

(Transmission capacity for induced voltage calculation, MVA)

P 400rc := 800

(Transmission capacity for induced voltage calculation, MVA)


P 400tr

Inom_400tr :=

U p_400 10

Inom_400hdd :=

P 400hdd

Up_400 10

Inom_400rc :=

(Nominal transmission current in trench, A)

Inom_400tr = 1591

(Nominal transmission current in HDD crossing, A)

Inom_400hdd = 820

P 400rc

6
Up_400 ( 10 )

= 314.2

(Nominal transmission current in road crossing, A)

Inom_400rc = 1155

Final Ampacity calculation N7144.xmcd

22.03.2013

B. Cable Construction Data:


n := 1

(Number of load-carrying in the cable)

np := 1

(Number oc conductors in parallel)

dc := 45

(Diamenter of conductor, mm)

Acc := 1200

(Cross-section of copper condutor, mm 2 )

tc1 := 0.9

(Thickness of conductor binder/swelling tape, mm)

dc0 := dc + 2 tc1

(Diamenter of conductor, including binder tape, mm)

tc2 := 1.5

(Avarage thickness of conductor screen, mm)

tcs := tc1 + tc2

(Total thickness of conductor screen, mm)

tcs = 2.4

dc1 := dc + 2 tcs

( Diameter of conductor, including screen, mm)

dc1 = 49.8

ti := 16

(Min. avarage thickness of insulation, mm)

din := dc + 2 tcs + 2 ti

(External diamenter of insulation, excluding screen, mm)

tinss := 1.8

(Min. avg. thickness of insulation screen, mm)

dbst := din + 2 tinss

(Diameter over insulation screen, mm)

tst1 := 0.9

(Thickness of swelling tape/bedding, mm)

dbcs := dbst + 2 tst1

(Diameter over swelling tape/bedding, mm)

tcms :=

dbcs dc

(Thickness between condcutor and metal sheath, mm)

dc0 = 46.8

din = 81.8

dbst = 85.4

dbcs = 87.2

tcms = 21.1

tls := 3.6

(Avg. thickness of lead sheath, mm)

dals := dbcs + 2 tls

(Diameter over lead sheath, mm)

dlead := dals tls

(Mean diameter of lead sheath, mm)

dmm := dals tls

(Mean geometric diameter of lead sheath, mm)

dmm = 90.8

(Cross-section of lead sheath, m2)

Alead = 1.027 10

Alead := tls dbcs + tls 10

tos := 4.7

(Avg. thickness of outer covering, including SC skin, mm)

do := dals + 2 tos

(External diameter of the cable, mm)

Final Ampacity calculation N7144.xmcd

dals = 94.4
dlead = 90.8

do = 103.8
22.03.2013

C. Electrical Characteristics:
Ro := 15.1 10

copper := 1.7241 10
lead := 21.4 10

(D.C. resistance of the conductor at 20C, Ohm/m)


8

(Electrical resistivity of Copper, Ohm/m) - IEC 60287-1-1, Table 1

(Electrical resistivity of Lead, Ohm/mm) - IEC 60287-1-1, Table 1

D. Electrical Coefficients:

kp := 0.37

(Proximity effect coefficient acc. to Cigre technical paper n272,


Working Group B1.03)

ks := 0.44

(Proximity effect coefficient acc. to Cigre technical paper n272,


Working Group B1.03)

E. Insulation Characteristics:
p := 2.4

(Relative permittivity of insulation)

tan ( ) := 0.001

(Loss factor of the insulation)

F. Thermal Resistivities:
xlpe := 3.5

(Themal resistivity of XLPE, K.m/W acc to IEC 60287-2-1)

pe := 3.5

(Themal resistivity of PE, K.m/W acc to IEC 60287-2-1)

b := 6

(Themal resistivity of swelling tapes, K.m/W)

sc := 2.5

(Themal resistivity of S/C, K.m/W)

pvc := 6

(Themal resistivity of PVC, K.m/W acc to IEC 60287-2-1)

sr := 1.2

(Themal soil resistivity at road crossing , K.m/W)

st := 1.2

(Themal soil resistivity in trech (Stabilised sourrounding , K.m/W)

bentonite := 1.0

(Themal resistivity of bentonite , K.m/W)

concrete := 1.0

(Themal soil resistivity of concrete of the duct bank , K.m/W)

hdd := 1.0

(Themal soil resistivity of HDD section , K.m/W)

Final Ampacity calculation N7144.xmcd

22.03.2013

G. Temperatures and Temperature Coefficients:

max := 90

(Max. operating temperature of conductor. C)

c1 := 250

(Max. short-circuit temperature of conductor, C)

ms := 80

(Max. working temperature of the lead sheath, C)

cs1 := 250

(Final earth-fault temperature of copper wire screen, C)

cs2 := ms

(Initial earth-fault temperature of copper wire screen, C)

l1 := 180

(Final earth-fault temepratre of lead sheath, C)

cground := 40

(Max. ground temperature, C)

bentonite := 70

(Mean temperature of the medium filling between cable and duct, C)

ap := 77.3

(Mean temperature of air inside the road crossing pipe, C)

c20 := 3.93 10

(Constant copper temperature coefficient, 1/C)

lead := 4 10

(Temperature coefficient of lead sheath resistance. 1/C)

c := 234.5

(Reciprocal of temperature coefficient of resistance copper)

Kc := 226

(Constant of copper)

s := 230

(Reciprocal of temperature coefficient of resistance lead)

Ks := 41

(Constant of lead)

Final Ampacity calculation N7144.xmcd

22.03.2013

H. Typical Trough cross-sction:


132 kV Circuit

hgcb_tr := 1150

(Distance from ground surface to cable bottom, mm)

do
hg1ca_tr := hgcb_tr
2

(Distance from ground surface to cable axis, mm)

s tr := 200

(Axial spacing of conductor R,Y,B in trench, mm)

s ctr := 2100

(Center to Center distance of cable circuits in trench, mm)

m_tr := 81.5

(Working temperature of the lead sheath in trough, C)

Final Ampacity calculation N7144.xmcd

hg1ca_tr = 1098

22.03.2013

I. HDD Crossing
132 kV Circuit

tpipe_hdd := 15

(Thickness of HDPE duct wall, mm)

dipipe_hdd := 195

(Inside diameter of HDPE duct, mm)

dopipe_hdd := dipipe_hdd + 2 tpipe_hdd

(Outdise diamenter of HDPE, mm)

tbt := 50

(Thickness of bentonite layer around the cable, mm)

s hdd := dopipe_hdd

(Axial spacing of the conductors in HDD section, mm)

dopipe_hdd = 225

Lhdd := 7000 + +
2 3

dopipe_hdd (Distance from road level to the trefoil center, mm)

m_hdd := 80

Final Ampacity calculation N7144.xmcd

Lhdd = 7242

(Working temperature of the lead sheath in trough, C)

22.03.2013

J. Typical Road Crossing:


132 kV Circuit

tpipe_rc := 10

(Thickness of HDPE duct wall, mm)

dipipe_rc := 180

(Inside diameter of HDPE duct, mm)

dopipe_rc := dipipe_rc + 2 tpipe_rc

(Outdise diamenter of HDPE, mm)

tbt := 50

(Thickness of bentonite layer around the cable, mm)

WDB := 1800

(Width of the Duct bank, mm)

H DB := 550

(Height of the Duct bank, mm)

hgDB := 1225

(Depth of the Duct bank centre, mm)

N := 3

(Number of cables of half duct banks)

s rc := 300

(Axial spacing of the conductors in road crossing, mm)

Final Ampacity calculation N7144.xmcd

10

dopipe_rc = 200

22.03.2013

s crc := 2100

(Center to Center distance of cable circuits in trench, mm)

hgcb_rc := 1325

(Distance from ground surface to cable bottom, mm)

hgdb_rc := hgcb_rc +

tpipe_rc

do

hg1ca_rc := hgcb_rc

hgda_rc := hgdb_rc

(Distance from ground surface to duct bottom, mm)

2
(Distance from ground surface to cable axis, mm)

2
dipipe_rc

(Distance from ground surface to duct axis, mm)

m_rc := 80.5

hgdb_rc = 1330

hg1ca_rc = 1273

hgda_rc = 1240

(Working temperature of the lead sheath in trough, C)

K. Details of parallel running 400 kV Cables in Trough Section:


hg400_tr := 1100

(Burial depth from ground surface to cable bottom, mm)

D 400a_400b_tr := 2800

(Axial distance between 400 kV and 400 kV Circuits, mm)

D 400a_132_tr := 2100

(Axial distance between 400 kV closest and 132 kV Circuits, mm)

D 400b_132_tr := 4900

(Axial distance between 400 kV furthest and 132 kV Circuits, mm)

S 400_tr := 600

(Axial distance between of the 400 kV circuits, mm)

A400 := 2500

(Cross section of copper conductor, mm 2)

RAC_400_tr := 9.7232 10

(AC resistance of the conductor, Ohm/m)

1a_tr_400 := 0.0901

(Loss factor for screen and sheath of phase 1)

1b_tr_400 := 0.0605

(Loss factor for screen and sheath of phase 2)

1c_tr_400 := 0.0601

(Loss factor for screen and sheath of phase 3)

Wd400 := 1.08

(Dielectric Losses, W/m)

Final Ampacity calculation N7144.xmcd

11

22.03.2013

I. Details of parallel running 400 kV Cables in HDD Section:


hg400_hdd := 7500

(Burial depth from ground surface to cable bottom, mm)

do400pipe := 280

(Thickness of HDPE pipe,mm)

S 400_hdd := do400pipe = 280

(Axial distance between of the 400 kV circuits, mm)

L400hdd := 7000 + +
2 3

do400pipe (Distance from road level to trefoil center,mm)

Hhl400 := L400hdd S400_hdd


3

(Burial depth of the upmost cables,mm)

Hhl400 = 7140

Hbl400 := L400hdd + S400_hdd


3

(Burial depth of the deepes cables,mm)

Hbl400 = 7463

D 400a_400b_hdd := 3000

(Axial distance between 400 kV and 400 kV Circuits, mm)

D 400a_132_hdd := 3000

(Axial distance between 400 kV closest and 132 kV Circuits, mm)

D 400b_132_hdd := 6000

(Axial distance between 400 kV furthest and 132 kV Circuits, mm)

RAC_400_hdd := 9.754 10

1_hdd_400 := 0.1

(AC resistance of the conductor, Ohm/m)


(Loss factor for screen and sheath )

J. Details of parallel running 400 kV Cables in Road Crossing Section:


hg400_rc := 1350

(Burial depth from ground surface to cable bottom, mm)

D 400a_400b_rc := 2800

(Axial distance between 400 kV and 400 kV Circuits, mm)

D 400a_132_rc := 2100

(Axial distance between 400 kV closest and 132 kV Circuits, mm)

D 400b_132_rc := 4900

(Axial distance between 400 kV furthest and 132 kV Circuits, mm)

S 400_rc := 300

(Axial distance between of the 400 kV circuits, mm)

RAC_400_rc := 9.723 10

1a_rc_400 := 0.0899

Final Ampacity calculation N7144.xmcd

(AC resistance of the conductor, Ohm/m)


(Loss factor for screen and sheath of phase 1)

12

22.03.2013

1b_rc_400 := 0.0604

(Loss factor for screen and sheath of phase 2)

1c_rc_400 := 0.0600

(Loss factor for screen and sheath of phase 3)

1. AC Resistance of Conductor
DC Resistance of Conductor
kcopper( ) := 1 + c20( 20)

R := Ro kcopper max

(Factor)

kcopper max = 1.3

(D.C. resistance of conductor at max. operating temperature, Ohm/m)


R = 1.925 10

R20 := Ro

(D.C. Resistance of condcutor at 20C, Ohm/m)

R20 = 1.51 10

1.1. Cables in trough


1.1.1 Skin Effect Factor
xs :=

ys :=

8 fc
R
xs

( 10 7) ks

(Factor)

xs = 1.695

(Skin effect factor)

192 + 0.8xs

ys = 0.0415

1.1.2 Proximity effect factor


xp :=

8 fc
R

10

(Factor for conduits)

kp

xp = 1.554

4
2

d 2
192 + 0.8 x 4
xp

c
dc
( p)

yp( s) :=
0.312 + 1.18

4
4
s
192 + 0.8xp4 s
xp) + 0.27192 + 0.8 ( xp)
(

( )

yp str = 0.006

1.1.3 AC Resistance of the Conductor

( ))

Rcac_tr := R 1 + ys + yp s tr

(A.C. resistance of conductor at max. operating temperature , Ohm/m)


5

Rcac_tr = 2.017 10

Final Ampacity calculation N7144.xmcd

13

22.03.2013

( ))

Rcac_tr20 := R20 1 + ys + yp s tr

(A.C. resitance of condcutor at 20C temperature, Ohm/m)


Rcac_tr20 = 1.6 10

1.2 Cables in HDD


1.2.1 Skin effect factor
ys = 0.0415

1.2.2 Proximity effect factor

yp shdd = 0.00469

1.2.3 AC Resistance of the Conductor

Rcac_hdd := R 1 + ys + yp shdd

))

(A.C. resistance of conductor at max. operating temperature,


Ohm/m)
Rcac_hdd = 2.014 10

Rcac_hdd20 := R20 1 + ys + yp shdd

))

(A.C. resistance of conductor at 20C temperature, Ohm/m)


5

Rcac_hdd20 = 1.6 10

1.3 Cables in Duct Bank at Road crossing


1.3.1 Skin effect factor
ys = 0.0415

1.3.2 Proximity effect factor

( )

yp src = 0.00263

1.3.3 AC Resistance of the conductor

( ))

Rcac_rc := R 1 + ys + yp src

(A.C. resistance of conductor at max. operating temperature, Ohm/mm)


5

Rcac_rc = 2.01 10

Final Ampacity calculation N7144.xmcd

14

22.03.2013

( ))

Rcac_rc20 := R20 1 + ys + yp src

(A.C. resistance of conductor at 20C temperature, Ohm/m)


5

Rcac_rc20 = 1.6 10

2. Dielectric Loss per Unit Length for the Insulation


C :=

din
18. ln
dc1

U o :=

10

(Capacitance of each pahse against the screen surrounding, F/m/phase)


C = 268.7 10

Up_132

(Phase to neutral voltage, V)

3
Ic := Uo C 10

(Charging current per conductor, A/km)

2
Wd := C Uo tan ( )

(Dielectric losses per unit length per phase, W/m)

12

3
U o = 76.2 10

Ic = 6.43

Wd = 0.49

3. Loss Factor for the Metallic Screen and Sheath


(1) Equivalent Resistance of Lead Sheath

( )

klead m := 1 + m 20 lead

(Factor)

klead20 := 1.05

( )

Rs lead m :=

lead
k

Alead lead( m)

lead
k
( 20)
Alead lead

= 208.39 10

(D.C. resistance of the lead sheath at theta C, Ohm/m)

(Max. D.C. metallic sheath resistance at 20C, Ohm/m)

(2) General

( )

m m :=

10 7
Rs

lead( m)

( )

( )

s m := lead klead m

( )

1 m :=

(Electrical resistivity of the lead sheath at screen temperature)

( 107) s( m)

Final Ampacity calculation N7144.xmcd

15

22.03.2013

( )

gs m := 1

(Note - For lead sheath cables gs can be take as unity and

( 1 ts) 4
12 10

can be neglected - IEC 60287-1-1)

12

3.1 Circulation Loss Factor (Cl.2.3.6.2 of IEC 60287-1-1)


(1) Circulating loss calculation for three single-core cables in flat formation, without transposition, sheathes
bonded at both ends (Clause 2.3.2)
7.

X flat( s) := 2. 10

X m_flat := 2 10

dlead

2s

ln

(Reactance of Sheath per unit length, Ohm/m)

ln( 2 )

(Mutual reactance per unit length of cable between the sheath of an outer cable and
conductor, Ohm/m)
6
X m_flat = 43.552 10

P ( s ) := Xflat( s) + X m_flat

Q ( s) := Xflat( s)

X m_flat

(a) Centre Cable

'1flat_a m , s , Rac :=

( )

Rslead m

Q ( s)

Rac

2
2
Rs
lead( m) + Q( s)

'1flat_cba m , s , Rac := '1flat_a m , s , Rac 0.004

(Where lenghts of minor sections are unknow, multiply by factor of 0.004)

(b)Outer cable Leading phase

'1flat_b m , s , Rac :=

( )

Rslead m

0.75 P( s )

Rac

2
2
Rs
lead( m) + P( s)

'1flat_cbb m , s , Rac := '1flat_b m , s , Rac 0.004

0.25 Q( s)

( )

Rs lead m

2
+

+ Q( s)

( )

2
2
2
2
3 + Rs lead( m) + P( s) Rslead( m) + Q( s )

2 Rslead m P( s) Q( s) Xm_flat

(Where lenghts of minor sections are unknow, multiply by factor of 0.004)

(b)Outer cable Lagging phase

'1flat_c m , s , Rac :=

( )

Rslead m

0.75 P( s)

Rac

2
2
Rs
lead( m) + P( s)

Final Ampacity calculation N7144.xmcd

0.25 Q ( s)

( )

Rslead m

16

+ Q ( s)

+
2

( )

2
2
2
2
3 + Rslead( m) + P( s ) Rs lead( m) + Q( s)

2 Rs lead m P( s) Q ( s) X m_flat

22.03.2013

'1flat_cbc m , s , Rac := '1flat_c m , s , Rac 0.004

(Where lenghts of minor sections are unknow, multiply by factor of 0.004)

(2) Circulating loss calculation for three single-core cables in trefoil formation bonded at both ends (Clause 2.3.1)

X tref( s) := 2. 10

2.s

dlead

7.

ln

(Reactance of Sheath per unit length, Ohm/m)

X tref shdd = 1.006 10

'1_tref m , s , Rac :=

( )

Rslead m

Rac

Rslead( m)
1+
Xtref( s )

'1_tref_cb m , s , Rac := '1_tref m , s , Rac 0.004

(Where lenghts of minor sections are unknow, multiply by factor of 0.004)

3.2 Eddy Current Loss Factor (Cl.2.3.6.1 of IEC 60287-1-1)


(1) Eddy Current loss calculation formula for the three single-core cables in trefoil formation
2
m 2 d
( m) lead
0_t ( m , s) := 3

2 2s
1 + m( m)

d
2.45

lead
1_t ( m , s ) := 1.14 m( m)
+ 0.33

2s

0.92 m( m) + 1.66

2_t m , s := 0

"1_t m , s , Rac :=

Rslead( m)
g
, s 1 + 1_t ( m , s) + 2_t ( m , s ) )

s( m) 0_t ( m ) (
Rac

(2) Eddy Current loss calculation formula for three single-core cables in flat formation
a) Centre cable:
2
m 2 d
( m) lead
0a( m , s ) := 6

1 + m( m) 2 2s

Final Ampacity calculation N7144.xmcd

( Eddy current loss factor for cables in trough)

17

22.03.2013

d
3.08 lead
1a m , s := 0.86 m m

2s

1.4 m( m) + 0.7

( )

2a m , s := 0

Rslead( m)
g , s 1 + 1a( m , s) + 2a( m , s ) )

s( m) 0a( m ) (
Rac

"1a m , s , Rac :=

b) Outer cable leading phase:


2
m 2 d
( m) lead (Eddy current loss factor for cables in trough)
0b( m , s) := 1.5

1 + m( m) 2 2 s

d
0.7 lead
1b( m , s ) := 4.7 m( m)

2s

d
3.3 lead
2b( m , s ) := 21 m( m)

2s

"1b m , s , Rac :=

0.16 m( m) + 2

1.47 m( m) + 5.06

Rslead( m)
g , s 1 + 1b( m , s) + 2b( m , s ) )

s( m) 0b( m ) (
Rac

C) Outer cable lagging phase:


2
m 2 d
( m) lead
0c( m , s ) := 1.5

1 + m( m) 2 2 s

1c m , s :=

( ( ) ) ( )
2
2 + ( m( m) 0.3)

0.74 m m + 2 m m

0.5

d
3.7 lead

2c( m , s) := 0.92 m( m)

2 s

"1c m , s , Rac :=

(Eddy current loss factor for cables in trough)

dlead

2s

( )

m m + 1

( )

m m + 2

Rslead( m)
g , s 1 + 1c( m , s) + 2c( m , s ) )

s( m) 0c( m ) (
Rac

Final Ampacity calculation N7144.xmcd

18

22.03.2013

3.3 Loss Factor for Sheath and screen


3.3.1 Loss Factor for Sheath in trough

Rs lead ms = 258.403 10

(D.C. resistance of the lead sheath at theta C, Ohm/m)

'1flat_cba ms , str , Rcac_tr = 0.0043 (Circulating current loss factor on lead sheath of centre cable)

'1flat_cbb ms , str , Rcac_tr = 0.0095 (Circulating current loss factor on lead sheath of outer leading cable)

'1flat_cbc ms , str , Rcac_tr = 0.0095 (Circulating current loss factor on lead sheath of outer lagging cable)

"1a ms , str , Rcac_tr = 0.0577

(Eddy current loss factor on lead sheath of centre cable)

"1b ms , str , Rcac_tr = 0.0152


"1c ms , str , Rcac_tr = 0.0152

(Eddy current loss factor on lead sheath of outer cable leading phase)

(Eddy current loss factor on lead sheath of outer cable lagging phase)

1a_tr m , s , Rac := '1flat_cba m , s , Rac + "1a m , s , Rac

(Loss factor for metallic screens/sheath for cables in trough, phase 1)

1a_tr ms , str , Rcac_tr = 0.0621

1b_tr m , s , Rac := '1flat_cbb m , s , Rac + "1b m , s , Rac

(Loss factor for metallic screens/sheath for cables in trough, phase 2)

1b_tr ms , s tr , Rcac_tr = 0.0247

1c_tr m , s , Rac := '1flat_cbc m , s , Rac + "1c m , s , Rac

(Loss factor for metallic screens/sheath for cables in trough, phase 3)

1c_tr ms , str , Rcac_tr = 0.0247

1_tr := 1a_tr ms , str , Rcac_tr = 0.0621

Final Ampacity calculation N7144.xmcd

(Loss factor used for current rating calculation)

19

22.03.2013

3.3.2 Loss Factor for Sheath and Screen in HDD

Rs lead ms = 258.4 10

(D.C. resistance of the lead sheath at theta C, Ohm/m)

'1_tref_cb ms , shdd , Rcac_hdd = 0.0067

(Circulating current loss factor)

"1_t ms , shdd , Rcac_hdd = 0.0233 (Eddy current loss factor on lead sheath of centre cable)

1_hddf m , s , Rac := '1_tref_cb m , s , Rac + "1_t m , s , Rac

(Loss factor for metallic screen/sheath for trefoil formation)

1_hddf ms , shdd , Rcac_hdd = 0.03

1_hdd := 1_hddf ms , shdd , Rcac_hdd = 0.03

(Loss factor used for current rating calculation)

3.3.3 Loss Factor for Sheath and Screen in Road crossing

Rs lead ms = 258.403 10

(D.C. resistance of the lead sheath at theta C, Ohm/m)

'1flat_cba ms , src , Rcac_rc = 0.0072 (Circulating current loss factor on lead sheath of centre cable)

'1flat_cbb ms , src , Rcac_rc = 0.0127 (Circulating current loss factor on lead sheath of outer leading cable)

'1flat_cbc ms , src , Rcac_rc = 0.0127 (Circulating current loss factor on lead sheath of outer lagging cable)

"1a ms , src , Rcac_rc = 0.0257

(Eddy current loss factor on lead sheath of centre cable)

"1b ms , src , Rcac_rc = 6.584 10


"1c ms , src , Rcac_rc = 0.0066

(Eddy current loss factor on lead sheath of outer cable leading phase)

(Eddy current loss factor on lead sheath of outer cable lagging phase)

1a_rc m , s , Rac := '1flat_cba m , s , Rac + "1a m , s , Rac

(Loss factor for metallic screens/sheath for cables in trough, phase 1)

1a_rc ms , src , Rcac_rc = 0.0329

Final Ampacity calculation N7144.xmcd

20

22.03.2013

1b_rc m , s , Rac := '1flat_cbb m , s , Rac + "1b m , s , Rac

(Loss factor for metallic screens/sheath for cables in trough, phase 2)

1b_rc ms , src , Rcac_rc = 0.0193

1c_rc m , s , Rac := '1flat_cbc m , s , Rac + "1c m , s , Rac

(Loss factor for metallic screens/sheath for cables in trough, phase 3)

1c_rc ms , src , Rcac_rc = 0.0193

1_rc := 1a_rc ms , src , Rcac_rc = 0.0329 (Loss factor used for current rating calculation)

4. Calculation of Thermal Resistance


4.1 Thermal Resistance between on conductor and sheath, T1
(Cl.2.1.1.1 of IEC 60271-2-1)
4.1.1 Thermal Resistance of binder tape over conductor
b dc0

T10 :=
ln
2 dc

(Thermal resistance between one conductor and S/C, K.m/W)

T10 = 0.0375

4.1.2 Thermal Resistance of S/C screen over binder tape


sc dc1

T11 :=
ln
2 dc0

(Thermal resistance between one conductor and insulation sheath,


K.m/W)
T11 = 0.0247

4.1.3 Thermal Resistance of XLPE insulation


T12 :=

xlpe

din
dc1

ln

(Thermal resistance between one conductor and S/C, K.m/W)


T12 = 0.2764

4.1.4 Thermal Resistance of S/C screen over insulation


sc dbst

T13 :=
ln
2 din

Final Ampacity calculation N7144.xmcd

(Thermal resistance between one conductor and metallic sheath,


K.m/W)
T13 = 0.0171
21

22.03.2013

4.1.5 Thermal Resistance of S/C Bedding below Lead Sheath


b

T14 :=

dbcs
dbst

ln

(Thermal resistance between Swelling tape, K.m/W)


T14 = 0.0199

4.1.6 Thermal Resistance one conductor and sheath, T1


T1 := T10 + T11 + T12 + T13 + T14

T1 = 0.3757

4.2 Thermal Resistance between Sheath and Armour, T2


(Cl. 2.1.2 of IEC 60287-2-1)
T2 := 0

(No armouring)

T2 = 0

4.3 Thermal Resistanceof outer covering, T3 (Cl. 2.1.3 of IEC 60287-2-1)

T3 :=

pe

ln1 +

2.tos
dals

(Thermal resistance of outer cover, K.m/W)


T3 = 0.0529

4.4 Thermal Resistanceof cable surrounding, T4 (Cl. 2.2 of IEC 60287-2-1)


4.4.1 Cables in trough
For 3 cables having unequal sheath losses, laid in flat formation and equally spaced apart

u :=

( 2.hg1ca_tr)

u = 21.158

do

u1 := lnu +

2
u 1

soil
2 hg1ca_tr
T4trn( soil) :=
u1 + ln1 +


2
str

u1 = 3.745

External Thermal Resistance for current rating calculation in


trough (to used at numerator of the final formula), K.m/W

( )

T4trn st = 1.632

Final Ampacity calculation N7144.xmcd

22

22.03.2013

soil
1 + 0.5 ( 1a_tr ( ms , s tr , Rcac_tr) + 1c_tr ( ms , s tr , Rcac_tr) ) 2 hg1ca_tr
T4trd( soil) :=
( u1) +
ln 1 +

str
2
( 1 + 1b_tr ( ms , str , Rcac_tr) )

External Thermal Resistance for current rating calculation in trough (to used at
denominator of the final formula), K.m/W

( )

T4trd st = 1.649

4.4.2 Cables in HDD


For 3 cables having equal sheath losses, laid in trefoil formation and equally spaced apart

4.4.2.1 Thermal resistance of bentonite between cable and pipe

T41hdd :=

bentonite dipipe_hdd
(Thermal resistance of bentonite between cable and pipe, K.m/W)

ln

do
2

T41hdd = 0.1004

4.4.2.2 Thermal resistance of pipe material

T42hdd :=

pe dopipe_hdd
ln
2 dipipe_hdd

(Thermal resistance of pipe material, K.m/W)

T42hdd = 0.0797

4.4.2.3 Thermal resistance of soil


Hhl := Lhdd shdd
Hbl := Lhdd + shdd
uland :=

Hhl = 7113

(Burial depth of the deepst cable, mm)

Hbl = 7307

(u is calculated with reference to the centre line of the deepest ducts(non-touching


ducts)
uland = 64.954

dopipe_hdd

u 2 1
land

soil

u1
+ ln
land
2

T4land soil :=

(Burial depth of the upmost cable, mm)

2.Hbl

u1land := lnuland +

Final Ampacity calculation N7144.xmcd

u1land = 4.867

2
2

( 2 Hbl) + ( shdd)

+ ln

s hdd

( 2 Hhl)

2
2 shdd
( Hbl Hhl) +

2
2

23

shdd
+

T4land hdd = 2.099

22.03.2013

4.4.2.4 Total Thermal resistance of cable surrounding T4

T4hdd soil := T41hdd + T42hdd + T4land soil

External Thermal Resistance for current rating calculation in HDD, K.m/W:

T4hdd hdd = 2.3

4.4.3 Cable in duct at road crossing (reference to hottest cable: n3)


For 3 cables having unequal sheath losses, laid in flat formation and equally spaced apart

4.4.3.1 Thermal resistance of bentonite between cable and pipe

T41rc :=

bentonite dipipe_rc

ln
2 do

(Thermal resistance of bentonite between cable and pipe, K.m/W)


T41rc = 0.0876

4.4.3.2 Thermal resistance of pipe material

T42rc :=

pvc dopipe_rc

ln
2 dipipe_rc

(Thermal resistance of bentonite between cable and pipe, K.m/W)


T42rc = 0.1006

4.4.3.3 External thermal resistance of pipe material

x :=

1 H DB 4
W
2
DB

2

2
W
DB

HDB
H
ln1 + 2 + ln DB
WDB
2
H 2

DB
2

rb := e

uDB :=

(Equivalent radius of the duct bank, mm)

rb = 357.897

hgDB
uDB = 3.423

rb

T43_corr soil :=

2
N

( soil concrete ) lnuDB + uDB 1


2

Final Ampacity calculation N7144.xmcd

24

( )

T43_corr sr = 0.182

22.03.2013

4.4.3.4 Thermal resistance of cable sorrounding T4

ur :=

2 hg1ca_rc

ur = 12.731

dopipe_rc

u1r := lnur +

u 2 1
r

u1r = 3.236

concrete
2 hg1ca_rc
T43m( soil) :=
u1r + ln1 +
+ T43_corr ( soil)
src
2

External Thermal Resistance for current rating calculation in


duct bank (to used at numerator of the final formula), K.m/W

( )

T43m sr = 1.379
2

concrete
1 + 0.5 ( 1a_rc( ms , src , Rcac_rc) + 1c_rc( ms , src , Rcac_rc) ) 2 hg1ca_rc
T43rd( soil) :=
u1r +
ln 1 +
+ T43_corr ( soil)

src
1 + 1b_rc ( ms , src , Rcac_rc) )
2
(

External Thermal Resistance for current rating calculation in


duct bank (to used at denominator of the final formula), K.m/W

( )

T43rd sr = 1.384

4.4.3.5 Total Thermal resistance of cable surrounding T4

T4m soil := T41rc + T42rc + T43m soil

External thermal resistance for current rating calculation in duct


bank to be used at numerator of the final formula, K.m/W)

( )

T4m sr = 1.5677

T4rc soil := T41rc + T42rc + T43rd soil

External thermal resistance for current rating calculation in duct


bank to be used at the denominator of the final formula, K.m/W)

( )

T4rc sr = 1.5723

Final Ampacity calculation N7144.xmcd

25

22.03.2013

5. Conductor Temperature Rise above the Ambient Temperature


tr := max cground

(Temperature rise of the conductor with respect to the surroundings of trough, C)


tr = 50

hdd := max cground

(Temperature rise of the conductor with respect to the surroundings of HDD, C)


hdd = 50

rc := max cground

(Temperature rise of the conductor with respect to the surroundings of road crossing, C)
rc = 50

6. Continuous Current Carrying Capacity (A)


6.1 Cables in trough (Current as a function of soil thermal resistivity)
soil := 0.8 , 0.9 .. 2.3

I1tr soil :=

(Variable thermal resistivity of soil, K.m/W)

) )

Rcac_tr T1 + n Rcac_tr ( 1 + 1_tr ) T2 + n Rcac_tr ( 1 + 1_tr ) ( T3 + T4trd( soil) )

P1 tr soil := I1tr soil U p_132 10

I1tr soil =

tr Wd 0.5T1 + n T2 + T3 + T4trn soil

soil =

(Transmission Power in MVA)

P1 tr soil =

1237

0.8

282.8

1183.3

0.9

270.5

1136

259.7

1093.8

1.1

250.1

1055.9

1.2

241.4

1021.6

1.3

233.6

990.3

1.4

226.4

961.7

1.5

219.9

935.4

1.6

213.9

911

1.7

208.3

888.4

1.8

203.1

867.3

1.9

198.3

847.7

193.8

829.2

2.1

189.6

811.9

2.2

185.6

795.5

2.3

181.9

Final Ampacity calculation N7144.xmcd

( )

(A)

( )

(MVA)

I1tr st = 1055.9
P1 tr st = 241.4

26

2
Wc_tr := I1tr st Rcac_tr = 22.485

( )

(kW/km)

Ws_tr := 1_tr Wc_tr = 1.396

(kW/km)

Wd_tr := Wd = 0.49

(kW/km)

Wtotal_tr := Wc_tr + Ws_tr + Wd_tr = 24.37

(kW/km)

22.03.2013

Final verification of the screen/sheath temperature

fin_tr soil := max T1 Rcac_tr I1tr soil

) +
2

Wd

( )

fin_tr st = 81.5
m_tr = 81.5

6.2 Cables in HDD (Current as a function of soil thermal resistivity)

soil := 0.8 , 0.9 .. 2.3

I1hdd soil :=

(Variable thermal resistivity of soil, K.m/W)

) )

Rcac_hdd T1 + n Rcac_hdd ( 1 + 1_hdd) T2 + n Rcac_hdd ( 1 + 1_hdd) ( T3 + T4hdd( soil) )

P1 hdd soil := I1hdd soil Up_132 10


I1hdd soil =

hdd Wd 0.5T1 + n T2 + T3 + T4hdd soil

soil =

(Transmission Power in MVA)

1018

0.8

232.8

973

0.9

222.5

934

213.4

898

1.1

205.4

867

1.2

198.1

838

1.3

191.6

812

1.4

185.6

788

1.5

180.1

766

1.6

175.1

746

1.7

170.5

727

1.8

166.1

709

1.9

162.1

693

158.4

677

2.1

154.8

663

2.2

151.5

649

2.3

148.4

Final Ampacity calculation N7144.xmcd

P1 hdd soil =

(A)

(MVA)

I1hdd hdd = 933.6


P1 hdd hdd = 213.4

2
Wc_hdd := I1hdd hdd Rcac_hdd = 17.558

(kW/km)

Ws_hdd := 1_hdd Wc_hdd = 0.527

(kW/km)

Wd_hdd := Wd = 0.49

(kW/km)

Wtotal_hdd := Wc_hdd + Ws_hdd + Wd_hdd = 18.57 (kW/km)

27

22.03.2013

Final verification of the screen/sheath temperature

fin_hdd soil := max T1 Rcac_hdd I1hdd soil

) +

Wd

fin_tr hdd = 80.1


m_hdd = 80

6.3 Cables in ducts at road crossing (Current as a function of soil thermal resistivity)

soil := 0.8 , 0.9 .. 2.3

I1rc soil :=

(Variable thermal resistivity of soil, K.m/W)

) )

Rcac_rc T1 + n Rcac_rc ( 1 + 1_rc) T2 + n Rcac_rc ( 1 + 1_rc) ( T3 + T4rc( soil) )

P1 rc soil := I1rc soil U p_132 10

I1rc soil =

rc Wd 0.5T1 + n T2 + T3 + T4m soil

soil =

(Transmission Power in MVA)

P1 rc soil =

1208

0.8

276.3

1175

0.9

268.7

1145

261.8

1117

1.1

255.3

1090

1.2

249.3

1066

1.3

243.7

1043

1.4

238.4

1021

1.5

233.5

1001

1.6

228.8

982

1.7

224.5

964

1.8

220.3

946

1.9

216.4

930

212.6

914

2.1

209

899

2.2

205.6

885

2.3

202.4

Final Ampacity calculation N7144.xmcd

( )

(A)

( )

(MVA)

I1rc sr = 1090
P1 rc sr = 249.3

( )

2
Wc_rc := I1hdd sr Rcac_rc = 15.099
Ws_rc := 1_rc Wc_rc = 0.497
Wd_rc := Wd = 0.49
Wtotal_rc := Wc_rc + Ws_rc + Wd_rc = 16.09

28

22.03.2013

Final verification of the screen/sheath temperature

Wd

) 2 +

fin_rc soil := max T1 Rcac_rc I1rc soil

( )

fin_rc sr = 80.9
m_rc = 80.5

7. Reduction Factors
7.1 RF1= Cables in trough for various Depths and Laying - distance from ground surface to cable axis
hgca := 600 , 700 .. 2000

(Variable Distances of Cables from ground surface, mm)

( 2.hr)

ut_RF1( hr) :=

do

u1t_RF1( hr) := lnut_RF1( hr) +

soil
2 hr

u1t_RF1( hr) + ln1 +


2
str

soil
1 + 0.5 ( 1a_tr( ms , str , Rcac_tr) + 1c_tr( ms , str , Rcac_tr) ) 2 hr 2

u1t_RF1( hr) +
ln 1 +

str
1 + 1b_tr ( ms , str , Rcac_tr) )
2
(

T4trn_RF1 soil , hr :=

2
ut_RF1( hr) 1

T4trd_RF1 soil , hr :=

External Thermal Resistance for current rating calculation in


trough (to used at numerator of the final formula), K.m/W

External Thermal Resistance for current rating calculation in trough (to used at
denominator of the final formula), K.m/W

I1tr_RF1 soil , hr :=

(
) )

Rcac_tr T1 + n Rcac_tr ( 1 + 1_tr ) T2 + n Rcac_tr ( 1 + 1_tr ) ( T3 + T4trd_RF1( soil , hr) )

tr Wd 0.5T1 + n T2 + T3 + T4trn_RF1 soil , hr

P1 tr_RF1 soil , hr := I1tr_RF1 soil , hr Up_132 10

RF1 t soil , hr :=

(Transmission Power in MVA)

I1tr_RF1( soil , hr)

I1tr( st)

Final Ampacity calculation N7144.xmcd

29

22.03.2013

hgca =

RF1 t st , hgca =

I1tr_RF1 st , hgca =

1600

1800

P1 tr_RF1 st , hgca =

600

1.099

1160

265

700

1.071

1131

259

800

1.048

1107

253

900

1.03

1087

249

1000

1.014

1070

245

1100

1056

241

1200

0.988

1043

238

1300

0.977

1031

236

1400

0.967

1021

233

1500

0.958

1012

231

1600

0.95

1003

229

1700

0.943

995

228

1800

0.936

988

226

1900

0.929

981

224

2000

0.923

975

223

Transmission Power, MVA

270

257.5

P1 tr_RF1 st , hgca

245

232.5

220
600

800

1000

1200

1400

2000

hgca

Cable Laying depth, mm

Final Ampacity calculation N7144.xmcd

30

22.03.2013

7.2 RF2= Cables in HDD crossing for various Depths and Laying - distance from ground surface to cable axis
hgca := 3500 , 4000 .. 15000

Hhl_RF2 ( hr) := hr shdd


Hbl_RF2 ( hr) := hr + shdd
uRF2( hr) :=

(Variable Distances of Cables from ground surface, mm)

(Burial depth of the upmost cable, mm)

3
3

(Burial depth of the deepst cable, mm)

2. Hbl_RF2( hr)

(u RF2 is calculated with reference to the centre line of the deepest

dopipe_hdd

ducts(non-touching ducts)

u1c_RF2( hr) := lnuRF2( hr) +

T43c_RF2 soil , hr :=

u ( hr) 2 1
RF2

soil

u
( hr) + ln
1c_RF2

2
2

( 2 Hbl_RF2 ( hr) ) + ( shdd)

+ ln
s hdd

( 2 Hhl_RF2( hr) )

2
s
2 hdd
( Hbl_RF2( hr) Hhl_RF2( hr) ) +

2
2

shdd
+

T4c_RF2 soil , hr := T41hdd + T42hdd + T43c_RF2 soil , hr

External Thermal Resistance for current rating calculation in HDD, K.m/W:

T4hdd hdd = 2.3

I1hdd_RF2 soil , hr :=

) )

Rcac_hdd T1 + n Rcac_hdd ( 1 + 1_hdd) T2 + n Rcac_hdd ( 1 + 1_hdd) ( T3 + T4c_RF2( soil , hr) )

P1 hdd_RF2 soil , hr := I1hdd_RF2 soil , hr U p_132 10

RF2 t soil , hr :=

hdd Wd 0.5T1 + n T2 + T3 + T4c_RF2 soil , hr

(Transmission Power in MVA)

I1hdd_RF2( soil , hr)

I1hdd( hdd)

Final Ampacity calculation N7144.xmcd

31

22.03.2013

hgca =

RF2 t hdd , hgca =

I1hdd_RF2 hdd , hgca = P1 hdd_RF2 hdd , hgca =

3500

1.073

1002

229

4000

1.059

988

226

4500

1.046

977

223

5000

1.035

967

221

5500

1.026

958

219

6000

1.018

950

217

6500

1.01

943

216

7000

1.003

937

214

7500

0.997

931

213

8000

0.991

925

212

8500

0.986

920

210

9000

0.981

916

209

9500

0.976

911

208

10000

0.972

907

207

10500

0.968

904

207

11000

0.964

900

206

11500

0.96

897

205

12000

0.957

893

204

12500

0.954

890

204

13000

0.951

887

203

13500

0.948

885

202

14000

0.945

882

202

14500

0.942

880

201

15000

0.94

877

201

Transmission Power, MVA

230

222.5

P1 hdd_RF2 hdd , hgca

215

207.5

200
3500

5142.9

6785.7

8428.6

10071.4

11714.3

13357.1

15000

hgca

Cable Laying depth, mm


Final Ampacity calculation N7144.xmcd

32

22.03.2013

7.3 RF3= Cables in ductbank for road crossing for various Depths and Laying - distance from ground
surface to cable axis
hgca := 600 , 700 .. 2000

do

hgDB( hr) := hr +

uDB_RF3 ( hr) :=

(Variable Distances of Cables from ground surface, mm)


H DB

hgDB( hr)
rb

T4r_corr_RF3 soil , hr :=

urc_RF3( hr) :=

+ tpipe_rc dopipe_rc 200 +

2
N

( soil concrete ) lnuDB_RF3 ( hr) + uDB_RF3 ( hr) 1


2

2 hr
dopipe_rc

u1rc_RF3( hr) := lnurc_RF3( hr) +

T43rn_RF3 soil , hr :=

2
urc_RF3( hr) 1

concrete
2 hr

u1rc_RF3( hr) + ln1 +


+ T4r_corr_RF3( soil , hr)

str
2

External Thermal Resistance for current rating calculation in


duct bank (to used at numerator of the final formula), K.m/W

T43rd_RF3 soil , hr :=

concrete
1 + 0.5 ( 1a_rc( ms , src , Rcac_rc) + 1c_rc( ms , s rc , Rcac_rc) ) 2 hr 2

u1rc_RF3( hr) +
ln 1 +

str
1 + 1b_rc ( ms , src , Rcac_rc) )
2
(

...

+ T4r_corr_RF3 soil , hr

External Thermal Resistance for current rating calculation in duct bank (to used at
denominator of the final formula), K.m/W

T4rn_RF3 soil , hr := T41rc + T42rc + T43rn_RF3 soil , hr

External Thermal Resistance for current rating calculation in


duct bank (to used at numerator of the final formula), K.m/W

T4rd_RF3 soil , hr := T41rc + T42rc + T43rd_RF3 soil , hr

I1rc_RF3 soil , hr :=

External Thermal Resistance for current rating calculation in


duct bank (to used at denominator of the final formula), K.m/W

) )

Rcac_rc T1 + n Rcac_rc ( 1 + 1_rc) T2 + n Rcac_rc ( 1 + 1_rc) ( T3 + T4rd_RF3 ( soil , hr) )

Final Ampacity calculation N7144.xmcd

rc Wd 0.5T1 + n T2 + T3 + T4rn_RF3 soil , hr

33

22.03.2013

P1 rc_RF3 soil , hr := I1rc_RF3 soil , hr Up_132 10

RF3 t soil , hr :=

(Transmission Power in MVA)

I1rc_RF3( soil , hr)

I1rc( sr)

hgca =

RF3 t sr , hgca =

I1rc_RF3 sr , hgca =

1600

1800

P1 rc_RF3 sr , hgca =

600

1.093

1192

273

700

1.063

1159

265

800

1.04

1134

259

900

1.02

1112

254

1000

1.004

1094

250

1100

0.989

1079

247

1200

0.977

1065

244

1300

0.966

1053

241

1400

0.956

1043

238

1500

0.947

1033

236

1600

0.939

1024

234

1700

0.932

1016

232

1800

0.925

1009

231

1900

0.918

1002

229

2000

0.913

995

228

Transmission Power, MVA

275

263

P1 rc_RF3 sr , hgca

) 251

239

227
600

800

1000

1200

1400

2000

hgca

Cable Laying depth, mm


Final Ampacity calculation N7144.xmcd

34

22.03.2013

7.4 RF4= Cables in trough for for various ground temperatures


ground := 30 , 31 .. 50

RF4 ground := max ground

I1c_RF4 soil , ground :=

( ) )
n
p
Rcac_tr T1 + n Rcac_tr ( 1 + 1_tr ) T2 + n Rcac_tr ( 1 + 1_tr ) ( T3 + T4trd( soil) )

RF4 ground Wd 0.5T1 + n T2 + T3 + T4trn soil

P1 c_RF4 soil , ground := I1c_RF4 soil , ground Up_132 10

RF4 c soil , ground :=

ground =

(Transmission Power in MVA)

I1c_RF4( soil , ground)

I1rc( st)

RF4 c st , ground = I1c_RF4 st , ground = P1 c_RF4 st , ground =

30

1.062

1158

265

31

1.053

1149

263

32

1.044

1139

260

33

1.035

1129

258

34

1.026

1119

256

35

1.016

1108

253

36

1.007

1098

251

37

0.997

1088

249

38

0.988

1077

246

39

0.978

1067

244

40

0.968

1056

241

41

0.958

1045

239

42

0.948

1034

236

43

0.938

1023

234

44

0.928

1012

231

45

0.918

1001

229

46

0.907

989

226

47

0.897

978

224

48

0.886

966

221

49

0.875

954

218

50

0.864

942

215

Final Ampacity calculation N7144.xmcd

35

22.03.2013

7.5 RF5= Cables in HDD crossing for for various ground temperatures
soil := 20 , 21 .. 40

RF5 soil := max soil

I1c_RF5 soil , soil :=

) )
n
p
Rcac_hdd T1 + n Rcac_hdd ( 1 + 1_hdd) T2 + n Rcac_hdd ( 1 + 1_hdd) ( T3 + T4hdd( soil) )

P1 c_RF5 soil , soil := I1c_RF5 soil , soil U p_132 10

RF5 c soil , soil :=

soil =

RF5 soil Wd 0.5T1 + n T2 + T3 + T4hdd soil

(Transmission Power in MVA)

I1c_RF5( soil , soil)

I1hdd( hdd)

RF5 c hdd , soil =

I1c_RF5 hdd , soil =

20

1.187

1109

253

21

1.179

1101

252

22

1.17

1092

250

23

1.161

1084

248

24

1.152

1076

246

25

1.144

1068

244

26

1.135

1059

242

27

1.125

1051

240

28

1.116

1042

238

29

1.107

1034

236

30

1.098

1025

234

31

1.088

1016

232

32

1.079

1007

230

33

1.069

998

228

34

1.06

989

226

35

1.05

980

224

36

1.04

971

222

37

1.03

962

220

38

1.02

953

218

39

1.01

943

216

40

934

213

Final Ampacity calculation N7144.xmcd

36

P1 c_RF5 hdd , soil =

22.03.2013

7.6 RF6= Cables in Duct bank at road crossing for for various ground temperatures
ground := 30 , 31 .. 50

RF6 ground := max ground

I1c_RF6 soil , ground :=

( ) )
n
p
Rcac_rc T1 + n Rcac_rc ( 1 + 1_rc) T2 + n Rcac_rc ( 1 + 1_rc) ( T3 + T4rc( soil) )

RF6 ground Wd 0.5T1 + n T2 + T3 + T4m soil

P1 c_RF6 soil , ground := I1c_RF6 soil , ground Up_132 10

RF6 c soil , ground :=

ground =

(Transmission Power in MVA)

I1c_RF6( soil , ground)

I1rc( sr)

RF6 c sr , ground = I1c_RF6 sr , ground = P1 c_RF6 sr , ground =

30

1.097

1196

274

31

1.088

1186

271

32

1.078

1176

269

33

1.069

1166

266

34

1.059

1155

264

35

1.05

1145

262

36

1.04

1134

259

37

1.03

1123

257

38

1.02

1112

254

39

1.01

1102

252

40

1090

249

41

0.99

1079

247

42

0.979

1068

244

43

0.969

1057

242

44

0.958

1045

239

45

0.948

1033

236

46

0.937

1022

234

47

0.926

1010

231

48

0.915

998

228

49

0.904

986

225

50

0.892

973

222

Final Ampacity calculation N7144.xmcd

37

22.03.2013

7.7 RF7= Cables in trough for for various cable separation


s ca := 200 , 250 .. 600
ut_RF7 :=

( 2.hg1ca_tr)
do

u1t_RF7 := lnut_RF7 +

2
ut_RF7 1

soil
2 hg1ca_tr External Thermal Resistance for current rating calculation in
T4trn_RF7( soil , s ) :=
u1t_RF7 + ln1 +
trough (to used at numerator of the final formula), K.m/W
s
2


2

soil
1 + 0.5 ( 1a_tr ( ms , s tr , Rcac_tr) + 1c_tr ( ms , s tr , Rcac_tr) ) 2 hg1ca_tr
T4trd_RF7( soil , s ) :=
( u1t_RF7) +
ln 1 +


1 + 1b_tr ( ms , s tr , Rcac_tr) )
s
2

(

External Thermal Resistance for current rating calculation in trough (to used at
denominator of the final formula), K.m/W

I1c_RF7 soil , s :=

(
) )

Rcac_tr T1 + n Rcac_tr ( 1 + 1_tr ) T2 + n Rcac_tr ( 1 + 1_tr ) ( T3 + T4trd_RF7( soil , s) )

tr Wd 0.5T1 + n T2 + T3 + T4trn_RF7 soil , s

P1 c_RF7 soil , s := I1c_RF7 soil , s U p_132 10

RF7 c soil , s :=

s ca =

(Transmission Power in MVA)

I1c_RF7( soil , s)

I1tr( st)

RF7 c st , s ca =

I1c_RF7 st , s ca =

200

1056

241

250

1.022

1079

247

300

1.041

1099

251

350

1.058

1117

255

400

1.073

1133

259

450

1.087

1147

262

500

1.099

1161

265

550

1.111

1173

268

600

1.122

1184

271

Final Ampacity calculation N7144.xmcd

P1 c_RF7 st , sca =

38

22.03.2013

8. Mirror principle applied for parallel unequally loaded cable circuits (Super position)
8.1 Cables in trough between 132 kV Brugg Circuit and 2 Circuits 400 kV Viscas

P a_400 := 100 , 200 .. 1200


D x02_x1 :=

(Variable loading of parallel running 400 kV cable, MVA)

( D400b_132_tr + S400_tr ) 2 + ( hg1ca_tr hg400_tr ) 2

(distance between X02 and X1, mm)


3
D x02_x1 = 5.500 10

D x02_x1m :=

( D400b_132_tr + S400_tr ) 2 + ( hg1ca_tr + hg400_tr ) 2

(distance between X02 and mirror image X1, mm)


3
D x02_x1m = 5.923 10

D x02_x2 :=

( D400b_132_tr) 2 + ( hg1ca_tr hg400_tr ) 2

(distance between X02 and X2, mm)


3
D x02_x2 = 4.900 10

D x02_x2m :=

( D400b_132_tr ) 2 + ( hg1ca_tr + hg400_tr ) 2

(distance between X02 and mirror image X2, mm)


3
D x02_x2m = 5.370 10

Final Ampacity calculation N7144.xmcd

39

22.03.2013

( D400b_132_tr S400_tr ) + ( hg1ca_tr hg400_tr )


2

D x02_x3 :=

(distance between X02 and X3, mm)


3
D x02_x3 = 4.300 10

( D400b_132_tr S400_tr ) + ( hg1ca_tr + hg400_tr )


2

D x02_x3m :=

(distance between X02 and mirror image X3, mm)


3
D x02_x3m = 4.829 10

( D400a_132_tr + S400_tr ) + ( hg1ca_tr hg400_tr )


2

D x02_x4 :=

(distance between X02 and X4, mm)


3
D x02_x4 = 2.700 10

( D400a_132_tr + S400_tr ) + ( hg1ca_tr + hg400_tr )


2

D x02_x4m :=

(distance between X02 and mirror image X4, mm)


3
D x02_x4m = 3.482 10

( D400a_132_tr) + ( hg1ca_tr hg400_tr )


2

D x02_x5 :=

(distance between X02 and X5, mm)


3
D x02_x5 = 2.100 10

( D400a_132_tr) + ( hg1ca_tr + hg400_tr )


2

D x02_x5m :=

(distance between X02 and mirror image X5, mm)


3
D x02_x5m = 3.040 10

( D400a_132_tr S400_tr ) + ( hg1ca_tr hg400_tr )


2

D x02_x6 :=

( D400a_132_tr S400_tr ) + ( hg1ca_tr + hg400_tr )


2

D x02_x6m :=

(distance between X02 and X6, mm)


3
D x02_x6 = 1.500 10
2

(distance between X02 and X6, mm)


3
D x02_x6m = 2.661 10

I400tr ( P ) :=

( P 1000)

(Current in the 400 kV circuit as a function of the transmitted power, A)

3 400 )

I400tr P 400tr = 1591

W400_atr( P) := RAC_400_tr 1 + 1a_tr_400 I400tr ( P )

+ Wd400

(Estimated losses in the 400 kV phase a circuit as a function of


the transmitted power P at 400 kV, W/m)

W400_atr P400tr = 27.911

W400_btr ( P ) := RAC_400_tr 1 + 1b_tr_400 I400tr ( P)

+ Wd400

(Estimated losses in the 400 kV phase b circuit as a function of


the transmitted power P at 400 kV, W/m)

W400_btr P 400tr = 27.182

W400_ctr( P) := RAC_400_tr 1 + 1c_tr_400 I400tr ( P )

+ Wd400

(Estimated losses in the 400 kV phase c circuit as a function of


the transmitted power P at 400 kV, W/m)

W400_ctr P400tr = 27.172

Final Ampacity calculation N7144.xmcd

40

22.03.2013

x02_x1 soil , P :=

x02_x2 soil , P :=

x02_x3 soil , P :=

x02_x4 soil , P :=

x02_x5 soil , P :=

x02_x6 soil , P :=

1
2
1
2
1
2
1
2
1
2
1
2

Dx02_x1m
Dx02_x1

(Temperature rise at the surface of cable produced by the power


of furthest 400 kV circuit and disspated in cable X02)

Dx02_x2m
Dx02_x2

(Temperature rise at the surface of cable produced by the power


of furthest 400 kV circuit and disspated in cable X02)

Dx02_x3m
Dx02_x3

(Temperature rise at the surface of cable produced by the power


of furthest 400 kV circuit and disspated in cable X02)

Dx02_x4m
Dx02_x4

(Temperature rise at the surface of cable produced by the power


of closest 400 kV circuit and disspated in cable X02)

Dx02_x5m
Dx02_x5

(Temperature rise at the surface of cable produced by the power


of closest 400 kV circuit and disspated in cable X02)

Dx02_x6m
Dx02_x6

(Temperature rise at the surface of cable produced by the power


of closest 400 kV circuit and disspated in cable X02)

soil W400_atr( P ) ln

soil W400_btr ( P) ln

soil W400_ctr( P ) ln

soil W400_atr( P ) ln

soil W400_btr ( P) ln

soil W400_ctr( P ) ln

Ptr soil , P := x02_x1 soil , P + x02_x2 soil , P + x02_x3 soil , P + x02_x4 soil , P ...
+

x02_x5 soil , P + x02_x6 soil , P

(Total rise above ambient temperature at the surface of the X02 cable, whose rating is being determined, caused by the
power disspated by the other cables in group)

I1132_400tr soil , P :=

P1 132_400tr soil , P :=

( tr Ptr( soil , P) ) Wd 0.5T1 + n ( T2 + T3 + T4trn( soil) )

Rcac_tr T1 + n Rcac_tr ( 1 + 1_tr ) T2 + n Rcac_tr ( 1 + 1_tr ) ( T3 + T4trd( soil) )

I1132_400tr ( soil , P) ( 3 132 )

1000

RF4 tr soil , P := RF4 c soil , cground + Ptr soil , P

Final Ampacity calculation N7144.xmcd

))

(Reduction Factor due to 400 kV circuit)

41

22.03.2013

P a_400 =

I400tr P a_400 =

Ptr st , P a_400 =

RF4 tr st , P a_400 =

I1132_400tr st , P a_400 =

100

144

0.37

0.965

1052

200

289

0.55

0.963

1050

300

433

0.85

0.96

1047

400

577

1.28

0.956

1042

500

722

1.83

0.95

1036

600

866

2.5

0.943

1029

700

1010

3.3

0.935

1020

800

1155

4.21

0.926

1010

900

1299

5.25

0.915

998

1000

1443

6.41

0.903

985

1100

1588

7.69

0.889

970

1200

1732

9.1

0.874

953

0.97

Reduction Factor, RF4tr

0.95

I1132_400tr st , P 400tr = 969


0.93

RF4tr st , P a_400

(A)

P1 132_400tr sr , P 400tr = 222 (MVA)

)
0.92

0.9

0.88
100

283.3

466.7

650

833.3

1016.7

1200

P a_400

Transmission Power, MVA

2
Wc_tr_final := I1132_400tr st , P400tr Rcac_tr = 18.947
Ws_tr_final := 1_tr Wc_tr_final = 1.176
Wd_tr_final := Wd = 0.49
Wtotal_tr_final := Wc_tr_final + Ws_tr_final + Wd_tr_final = 20.61 (Total Losses disspated by one phase of the 132 kV circuit, W/m)

Final Ampacity calculation N7144.xmcd

42

22.03.2013

8.2 Cables in HDD between 132 kV Brugg Circuit and 400 kV Viscas Circuit

Hhl = 7113

(Burial depth of the upmost 132 kV cable, mm)

Hbl = 7307

(Burial depth of the deepst 132 kV cable, mm)

P b_400 := 50 , 100 .. 600

(Variable loading of parallel running 400 kV cable, MVA)

D y02_y1 :=

shdd

D400b_132_hdd

+ Hbl Hhl400

)2

(distance between Y02 and Y1, mm)


3
D y02_y1 = 5.890 10

D y02_y1m :=

s hdd

D400b_132_hdd

Final Ampacity calculation N7144.xmcd

+ Hbl + Hbl400

)2

(distance between Y02 and mirror image Y1, mm)


3
D y02_y1m = 15.901 10

43

22.03.2013

D y02_y2 :=

D y02_y2m :=

D y02_y3 :=

D y02_y3m :=

D y02_y4 :=

D y02_y4m :=

D y02_y5 :=

shdd

D400b_132_hdd
2

S 400_hdd

shdd

D400b_132_hdd
2

s hdd

D400b_132_hdd
2

shdd

D400a_132_hdd

+ Hbl + Hbl400

(distance between Y02 and mirror image Y2, mm)


3
D y02_y2m = 15.953 10

(distance between Y02 and Y3, mm)


3
D y02_y3 = 5.750 10

+ Hbl + Hbl400

(distance between Y02 and mirror image Y3, mm)


3
D y02_y3m = 15.849 10

+ Hbl Hhl400

(distance between Y02 and Y4, mm)


3
D y02_y4 = 2.892 10

shdd

D400a_132_hdd

shdd

D400a_132_hdd
2

+ Hbl400 Hbl

S 400_hdd

(distance between Y02 and Y2, mm)

2
3
D y02_y2 = 6.030 10

+ Hbl400 Hbl

S 400_hdd

S 400_hdd

s hdd

D400b_132_hdd
2

+ Hbl + Hbl400

(distance between Y02 and mirror image Y4, mm)


3
D y02_y4m = 15.050 10

S 400_hdd

+ Hhl400 Hbl

(distance between Y02 and Y5, mm)


3
D y02_y5 = 3.032 10

D y02_y5m :=

shdd

D400a_132_hdd
2

S 400_hdd

+ Hbl + Hhl400

(distance between Y02 and mirror image Y5, mm)


3
D y02_y5m = 14.761 10

D y02_y6 :=

D y02_y6m :=

shdd

D400a_132_hdd
2

shdd

D400a_132_hdd
2

S 400_hdd

2
2

(distance between Y02 and Y6, mm)


3
D y02_y6 = 2.752 10

S 400_hdd

+ Hbl400 Hbl

+ Hbl + Hbl400

(distance between X02 and X6, mm)


3
D y02_y6m = 15.024 10

Final Ampacity calculation N7144.xmcd

44

22.03.2013

I400hdd( P) :=

( P 1000)

(Current in the 400 kV circuit as a function of the transmitted power, A)

3 400 )

I400tr P 400hdd = 820

W400_hdd ( P ) := RAC_400_hdd 1 + 1_hdd_400 I400hdd( P )

+ Wd400
(Estimated losses in the 400 kV phase a circuit as a function of
the transmitted power P at 400 kV, W/m)

W400_hdd P 400hdd = 8.292

y02_y1 soil , P :=

2
1

y02_y2 soil , P :=

2
1

y02_y3 soil , P :=

2
1

y02_y4 soil , P :=

2
1

y02_y5 soil , P :=

2
1

y02_y6 soil , P :=

Dy02_y1m
Dy02_y1

(Temperature rise at the surface of cable produced by the power


of furthest 400 kV circuit and disspated in cable Y02)

Dy02_y2m
Dy02_y2

(Temperature rise at the surface of cable produced by the power


of furthest 400 kV circuit and disspated in cable Y02)

Dy02_y3m
Dy02_y3

(Temperature rise at the surface of cable produced by the power


of furthest 400 kV circuit and disspated in cable Y02)

Dy02_y4m
Dy02_y4

(Temperature rise at the surface of cable produced by the power


of closest 400 kV circuit and disspated in cable Y02)

Dy02_y5m
Dy02_y5

(Temperature rise at the surface of cable produced by the power


of closest 400 kV circuit and disspated in cable y02)

Dy02_y6m
Dy02_y6

(Temperature rise at the surface of cable produced by the power


of closest 400 kV circuit and disspated in cable Y02)

soil W400_hdd ( P ) ln

soil W400_hdd ( P ) ln

soil W400_hdd ( P ) ln

soil W400_hdd ( P ) ln

soil W400_hdd ( P ) ln

soil W400_hdd ( P ) ln

Phdd soil , P := y02_y1 soil , P + y02_y2 soil , P + y02_y3 soil , P + y02_y4 soil , P ...
+

y02_y5 soil , P + y02_y6 soil , P

(Total rise above ambient temperature at the surface of the Y02 cable, whose rating is being determined, caused by the
power disspated by the other cables in group)
ground := 30 , 31 .. 50
I1132_400hdd soil , P :=

P1 132_400hdd soil , P :=

( hdd Phdd( soil , P) ) Wd 0.5T1 + n ( T2 + T3 + T4hdd( soil) )

Rcac_hdd T1 + n Rcac_hdd ( 1 + 1_hdd) T2 + n Rcac_hdd ( 1 + 1_hdd) ( T3 + T4hdd( soil) )

I1132_400hdd ( soil , P) ( 3 132 )

1000

RF5 hdd soil , P := RF5c soil , cground + Phdd soil , P


Final Ampacity calculation N7144.xmcd

))

(Reduction Factor due to 400 kV circuit)

45

22.03.2013

P b_400 =

I400hdd Pb_400 =

Phdd hdd , Pb_400 =

RF5 hdd hdd , P b_400 =

I1132_400hdd hdd , P b_400 =

50

72

1.43

0.985

920

100

144

1.64

0.983

918

150

217

1.99

0.979

914

200

289

2.49

0.974

910

250

361

3.12

0.967

903

300

433

3.89

0.959

896

350

505

4.81

0.949

886

400

577

5.86

0.938

876

450

650

7.06

0.925

863

500

722

8.39

0.91

849

550

794

9.87

0.893

834

600

866

11.49

0.874

816

0.99

Reduction Factor, RF5hdd

0.97

I1132_400hdd hdd , P 400hdd = 828 (A)


P1 132_400hdd hdd , P 400hdd = 189 (MVA)

0.94

RF5hdd hdd , P b_400

)
0.92

0.89

0.87
50

141.7

233.3

325

416.7

508.3

600

P b_400

Transmission Power, MVA

2
Wc_hdd_final := I1132_400hdd hdd , P400hdd Rcac_hdd = 13.799
Ws_hdd_final := 1_hdd Wc_hdd_final = 0.414
Wd_hdd_final := Wd = 0.49
Wtotal_hdd_final := Wc_hdd_final + Ws_hdd_final + Wd_hdd_final = 14.7
Final Ampacity calculation N7144.xmcd

46

(Total Losses disspated by the 132 kV circuit, W/m)

22.03.2013

8.3 Road crossing ductbanks between 132 kV Brugg Circuit and 2 Circuits 400 kV Viscas

P c_400 := 100 , 150 .. 800


D k02_k1 :=

(Variable loading of parallel running 400 kV cable, MVA)

( D400b_132_rc + S400_rc) 2 + ( hg1ca_rc hg400_rc) 2

(distance between K02 and K1, mm)


3
D k02_k1 = 5.201 10

D k02_k1m :=

( D400b_132_rc + S400_rc ) 2 + ( hg1ca_rc + hg400_rc ) 2

(distance between K02 and mirror image K1, mm)


3
D k02_k1m = 5.824 10

D k02_k2 :=

( D400b_132_rc ) 2 + ( hg1ca_rc hg400_rc ) 2

(distance between K02 and K2, mm)


3
D k02_k2 = 4.901 10

D k02_k2m :=

( D400b_132_rc ) 2 + ( hg1ca_rc + hg400_rc) 2

(distance between K02 and mirror image K2, mm)


3
D k02_k2m = 5.558 10

D k02_k3 :=

( D400b_132_rc S400_rc) 2 + ( hg1ca_rc hg400_rc) 2

(distance between K02 and K3, mm)


3
D k02_k3 = 4.601 10

Final Ampacity calculation N7144.xmcd

47

22.03.2013

( D400b_132_rc S400_rc ) + ( hg1ca_rc + hg400_rc )


2

D k02_k3m :=

(distance between K02 and mirror image K3, mm)


3
D k02_k3m = 5.295 10

( D400a_132_rc + S400_rc) + ( hg1ca_rc hg400_rc)


2

D k02_k4 :=

(distance between K02 and K4, mm)


3
D k02_k4 = 2.401 10

( D400a_132_rc + S400_rc) + ( hg1ca_rc + hg400_rc)


2

D k02_k4m :=

(distance between K02 and mirror image K4, mm)


3
D k02_k4m = 3.555 10

( D400a_132_rc) + ( hg1ca_rc hg400_rc )


2

D k02_k5 :=

(distance between K02 and K5, mm)


3
D k02_k5 = 2.101 10

( D400a_132_rc) + ( hg1ca_rc + hg400_rc )


2

D k02_k5m :=

(distance between K02 and mirror image K5, mm)


3
D k02_k5m = 3.360 10

( D400a_132_rc S400_rc) + ( hg1ca_rc hg400_rc)


2

D k02_k6 :=

(distance between K02 and K6, mm)


3
D k02_k6 = 1.802 10

( D400a_132_rc S400_rc) + ( hg1ca_rc + hg400_rc)


2

D k02_k6m :=

(distance between K02 and K6, mm)


3
D k02_k6m = 3.181 10

I400rc ( P) :=

( P 1000)

(Current in the 400 kV circuit as a function of the transmitted power, A)

3 400 )

I400rc P400rc = 1155

W400_arc ( P ) := RAC_400_rc 1 + 1a_rc_400 I400rc ( P )

+ Wd400

(Estimated losses in the 400 kV phase a circuit as a function of


the transmitted power P at 400 kV, W/m)

W400_arc P 400rc = 15.209

W400_brc ( P ) := RAC_400_rc 1 + 1b_rc_400 I400rc ( P)

+ Wd400

(Estimated losses in the 400 kV phase b circuit as a function of


the transmitted power P at 400 kV, W/m)

W400_brc P 400rc = 14.827

W400_crc ( P ) := RAC_400_rc 1 + 1c_rc_400 I400rc ( P )

+ Wd400

(Estimated losses in the 400 kV phase c circuit as a function of


the transmitted power P at 400 kV, W/m)

W400_crc P 400rc = 14.822

Final Ampacity calculation N7144.xmcd

48

22.03.2013

k02_k1 soil , P :=

k02_k2 soil , P :=

k02_k3 soil , P :=

k02_k4 soil , P :=

k02_k5 soil , P :=

k02_k6 soil , P :=

1
2

1
2

1
2

1
2

1
2

1
2

Dk02_k1m (Temperature rise at the surface of cable produced by the power


Dk02_k1 of furthest 400 kV circuit and disspated in cable K02)

soil W400_arc ( P ) ln

D k02_k2m (Temperature rise at the surface of cable produced by the power


D k02_k2 of furthest 400 kV circuit and disspated in cable K02)

soil W400_brc ( P ) ln

Dk02_k3m (Temperature rise at the surface of cable produced by the power


Dk02_k3 of furthest 400 kV circuit and disspated in cable K02)

soil W400_crc ( P ) ln

Dk02_k4m (Temperature rise at the surface of cable produced by the power


Dk02_k4 of closest 400 kV circuit and disspated in cable K02)

soil W400_arc ( P ) ln

D k02_k5m (Temperature rise at the surface of cable produced by the power


D k02_k5 of closest 400 kV circuit and disspated in cable K02)

soil W400_brc ( P ) ln

Dk02_k6m (Temperature rise at the surface of cable produced by the power


Dk02_k6 of closest 400 kV circuit and disspated in cable K02)

soil W400_crc ( P ) ln

Prc soil , P := k02_k1 soil , P + k02_k2 soil , P + k02_k3 soil , P + k02_k4 soil , P ...
+

k02_k5 soil , P + k02_k6 soil , P

(Total rise above ambient temperature at the surface of the K02 cable, whose rating is being determined, caused by the
power disspated by the other cables in group)

I1132_400rc soil , P :=

P1 132_400rc soil , P :=

( rc Prc( soil , P) ) Wd 0.5T1 + n ( T2 + T3 + T4m( soil) )

Rcac_rc T1 + n Rcac_rc ( 1 + 1_rc) T2 + n Rcac_rc ( 1 + 1_rc) ( T3 + T4rc( soil) )

I1132_400rc ( soil , P) ( 3 132 )

1000

RF6 rc soil , P := RF6c soil , cground + Prc soil , P

Final Ampacity calculation N7144.xmcd

))

(Reduction Factor due to 400 kV circuit)

49

22.03.2013

P c_400 =

I400rc Pc_400 =

Prc sr , P c_400 =

RF6 rc sr , Pc_400 =

I1132_400rc sr , Pc_400 =

100

144

0.45

0.995

1086

150

217

0.54

0.994

1084

200

289

0.67

0.993

1083

250

361

0.84

0.991

1081

300

433

1.05

0.989

1079

350

505

1.29

0.987

1076

400

577

1.57

0.984

1073

450

650

1.89

0.981

1069

500

722

2.24

0.977

1065

550

794

2.64

0.973

1061

600

866

3.07

0.968

1056

650

938

3.53

0.963

1051

700

1010

4.04

0.958

1045

750

1083

4.58

0.952

1038

800

1155

5.16

0.946

1032

Reduction Factor, RF6rc

0.99

I1132_400rc sr , P400rc = 1032 (A)


P1 132_400rc sr , P 400rc = 236 (MVA)

0.98

RF6rc sr , P c_400

)
0.96

0.95

0.94
100

216.7

333.3

450

566.7

683.3

800

P c_400

Transmission Power, MVA

2
Wc_rc_final := I1132_400rc sr , P 400rc Rcac_rc = 21.394
Ws_rc_final := 1_rc Wc_rc_final = 0.704
Wd_rc_final := Wd = 0.49
Wtotal_rc_final := Wc_rc_final + Ws_rc_final + Wd_rc_final = 22.59
(Total Losses disspated by the 132 kV circuit, W/m)

Final Ampacity calculation N7144.xmcd

50

22.03.2013

9. Reduction Factors
9.1 RFX1= Cables in trough for various Depths and Laying with interacion of 400 kV circuits
hgca := 600 , 700 .. 2000
D x02_x1a( hr) :=

D x02_x1ma( hr) :=

D x02_x2a( hr) :=

D x02_x2ma( hr) :=

D x02_x3a( hr) :=

D x02_x3ma( hr) :=

D x02_x4a( hr) :=

D x02_x4ma( hr) :=

D x02_x5a( hr) :=

D x02_x5ma( hr) :=

D x02_x6a( hr) :=

D x02_x6ma( hr) :=

(Variable Distances of Cables axis from ground surface of 132 kV circuit, mm)

( D400b_132_tr + S400_tr ) 2 + ( hr hg400_tr ) 2

(distance between X02 and X1, mm)

( D400b_132_tr + S400_tr ) 2 + ( hr + hg400_tr ) 2

(distance between X02 and mirror image X1, mm)

( D400b_132_tr ) 2 + ( hr hg400_tr ) 2

(distance between X02 and X2, mm)

( D400b_132_tr) 2 + ( hr + hg400_tr ) 2

(distance between X02 and mirror image X2, mm)

( D400b_132_tr S400_tr ) 2 + ( hr hg400_tr ) 2

(distance between X02 and X3, mm)

( D400b_132_tr S400_tr ) 2 + ( hr + hg400_tr ) 2

(distance between X02 and mirror image X3, mm)

( D400a_132_tr + S400_tr ) 2 + ( hr hg400_tr ) 2

(distance between X02 and X4, mm)

( D400a_132_tr + S400_tr ) 2 + ( hr + hg400_tr ) 2

(distance between X02 and mirror image X4, mm)

( D400a_132_tr) 2 + ( hr hg400_tr ) 2

(distance between X02 and X5, mm)

( D400a_132_tr) 2 + ( hr + hg400_tr ) 2

(distance between X02 and mirror image X5, mm)

( D400a_132_tr S400_tr ) 2 + ( hr hg400_tr ) 2

(distance between X02 and X6, mm)

( D400a_132_tr S400_tr ) 2 + ( hr + hg400_tr ) 2

Final Ampacity calculation N7144.xmcd

(distance between X02 and X6, mm)

51

22.03.2013

I400tra :=

( P400tr 1000)
(

(Current in the 400 kV circuit as a function of the transmitted power, A)

3 400 )

I400tra = 1591

W400_atra := RAC_400_tr 1 + 1a_tr_400 I400tra

+ Wd400

W400_btra := RAC_400_tr 1 + 1b_tr_400 I400tra

W400_ctra := RAC_400_tr 1 + 1c_tr_400 I400tra

x02_x1a soil , hr :=

x02_x2a soil , hr :=

x02_x3a soil , hr :=

x02_x4a soil , hr :=

x02_x5a soil , hr :=

x02_x6a soil , hr :=

1
2
1
2
1
2
1
2
1
2
1
2

+ Wd400

+ Wd400

(Estimated losses in the 400 kV phase a circuit as a function of


the transmitted power P at 400 kV, W/m)
W400_atra = 27.911
(Estimated losses in the 400 kV phase b circuit as a function of
the transmitted power P at 400 kV, W/m)
W400_btra = 27.182
(Estimated losses in the 400 kV phase c circuit as a function of
the transmitted power P at 400 kV, W/m)
W400_ctra = 27.172

Dx02_x1ma( hr) (Temperature rise at the surface of cable produced by the power
Dx02_x1a( hr) of furthest 400 kV circuit and disspated in cable X02)

soil W400_atra ln

Dx02_x2ma( hr) (Temperature rise at the surface of cable produced by the power
Dx02_x2a( hr) of furthest 400 kV circuit and disspated in cable X02)

soil W400_btra ln

Dx02_x3ma( hr) (Temperature rise at the surface of cable produced by the power
Dx02_x3a( hr) of furthest 400 kV circuit and disspated in cable X02)

soil W400_ctra ln

Dx02_x4ma( hr) (Temperature rise at the surface of cable produced by the power
Dx02_x4a( hr) of closest 400 kV circuit and disspated in cable X02)

soil W400_atra ln

Dx02_x5ma( hr) (Temperature rise at the surface of cable produced by the power
Dx02_x5a( hr) of closest 400 kV circuit and disspated in cable X02)

soil W400_btra ln

Dx02_x6ma( hr) (Temperature rise at the surface of cable produced by the power
Dx02_x6a( hr) of closest 400 kV circuit and disspated in cable X02)

soil W400_ctra ln

Ptra soil , hr := x02_x1a soil , hr + x02_x2a soil , hr + x02_x3a soil , hr + x02_x4a soil , hr ...
+

x02_x5a soil , hr + x02_x6a soil , hr

(Total rise above ambient temperature at the surface of the X02 cable, whose rating is being determined, caused by the
power disspated by the other cables in group)

ut_RFX1 ( hr) :=

( 2.hr)
do

Final Ampacity calculation N7144.xmcd

52

22.03.2013

u1t_RFX1( hr) := lnut_RFX1( hr) +

2
ut_RFX1( hr) 1

soil
2 hr

T4trn_RFX1( soil , hr) :=


u1t_RFX1 ( hr) + ln 1 +

2
s tr

T4trd_RFX1 soil , hr :=

External Thermal Resistance for current rating calculation in


trough (to used at numerator of the final formula), K.m/W

soil
1 + 0.5 ( 1a_tr( ms , str , Rcac_tr) + 1c_tr( ms , str , Rcac_tr) ) 2 hr 2

u1t_RFX1 ( hr) +
ln 1 +

str
2
( 1 + 1b_tr ( ms , str , Rcac_tr) )



External Thermal Resistance for current rating calculation in trough (to used at
denominator of the final formula), K.m/W

I1tr_RFX1 soil , hr :=

( tr Ptra ( soil, hr) ) Wd 0.5T1 + n ( T2 + T3 + T4trn_RF1( soil, hr) )

Rcac_tr T1 + n Rcac_tr ( 1 + 1_tr ) T2 + n Rcac_tr ( 1 + 1_tr ) ( T3 + T4trd_RFX1( soil , hr) )

P1 tr_RFX1 soil , hr := I1tr_RFX1 soil , hr U p_132 10

RFX1 t soil , hr :=

hgca =

(Transmission Power in MVA)

I1tr_RFX1( soil , hr)


I1132_400tr ( soil , P400tr )

Ptra st , hgca =

RFX1 t st , hgca =

I1tr_RFX1 st , hgca =

600

4.7

1.139

1104

252

700

5.4

1.101

1067

244

800

1.07

1037

237

900

6.6

1.043

1011

231

1000

7.2

1.02

989

226

1100

7.7

969

222

1200

8.2

0.982

951

218

1300

8.6

0.966

936

214

1400

0.951

922

211

1500

9.4

0.939

910

208

1600

9.7

0.927

899

205

1700

9.9

0.917

889

203

1800

10.1

0.908

880

201

1900

10.3

0.899

872

199

2000

10.5

0.892

864

198

Final Ampacity calculation N7144.xmcd

53

P1 tr_RFX1 st , hgca =

22.03.2013

Reduction Factor, RFX1tr

1.14

1.09

1.04

RFX1t st , hgca

)
0.99

0.94

0.89
600

833.3

1066.7

1300

1533.3

1766.7

2000

hgca

Depth of cable circuit, mm

Final Ampacity calculation N7144.xmcd

54

22.03.2013

9.2 RFY1= Cables in HDD crossing for various Depths & Laying with interaction of 400 kV circuits
hgca := 3500 , 4000 .. 15000

D y02_y1a( hr) :=

D y02_y1ma( hr) :=

D y02_y2a( hr) :=

D y02_y2ma( hr) :=

D y02_y3a( hr) :=

D y02_y3ma( hr) :=

D y02_y4a( hr) :=

D y02_y4ma( hr) :=

D y02_y5a( hr) :=

D y02_y5ma( hr) :=

(Variable Distances of Cables from ground surface, mm)

s hdd

D400b_132_hdd

+ hr Hhl400

shdd

D 400b_132_hdd

s hdd

D400b_132_hdd
2

s hdd

D400b_132_hdd
2

(distance between Y02 and Y2, mm)

+ hr + Hbl400

)2

(distance between Y02 and mirror image Y2, mm)

+ Hbl400 hr

S400_hdd

)2

(distance between Y02 and Y3, mm)

)2

+ hr + Hbl400

)2

(distance between Y02 and mirror image Y3, mm)

+ hr Hhl400

s hdd

D 400a_132_hdd

s hdd

D 400a_132_hdd
2

Final Ampacity calculation N7144.xmcd

+ Hbl400 hr

S400_hdd

(distance between Y02 and mirror image Y1, mm)

shdd

D 400b_132_hdd
2

shdd

D400a_132_hdd
2

)2

S 400_hdd

shdd

D400a_132_hdd

+ hr + Hbl400

shdd

D 400b_132_hdd
2

(distance between Y02 and Y1, mm)

S 400_hdd

)2

)2

(distance between Y02 and Y4, mm)

+ hr + Hbl400

S 400_hdd

)2

+ Hhl400 hr

S 400_hdd

(distance between Y02 and mirror image Y4, mm)

)2

(distance between Y02 and Y5, mm)

+ hr + Hhl400

55

)2

(distance between Y02 and mirror image Y5, mm)

22.03.2013

D y02_y6a( hr) :=

shdd

D400a_132_hdd
2

s hdd

D 400a_132_hdd
2

D y02_y6ma( hr) :=

I400hdda :=

( P400hdd 1000)
(

S 400_hdd

S 400_hdd

(distance between Y02 and Y6, mm)

+ Hbl400 hr

+ hr + Hbl400

(distance between X02 and X6, mm)

(Current in the 400 kV circuit as a function of the transmitted power, A)

3 400 )

I400hdda = 820

W400_hdda := RAC_400_hdd 1 + 1_hdd_400 I400hdda

+ Wd400
(Estimated losses in the 400 kV phase a circuit as a function of
the transmitted power P at 400 kV, W/m)
W400_hdda = 8.292

y02_y1a soil , hr :=

y02_y2a soil , hr :=

y02_y3a soil , hr :=

y02_y4a soil , hr :=

y02_y5a soil , hr :=

y02_y6a soil , hr :=

1
2
1
2
1
2
1
2
1
2
1
2

Dy02_y1ma( hr) (Temperature rise at the surface of cable produced by the power
Dy02_y1a( hr) of furthest 400 kV circuit and disspated in cable Y02)

soil W400_hdda ln

Dy02_y2ma( hr) (Temperature rise at the surface of cable produced by the power
Dy02_y2a( hr) of furthest 400 kV circuit and disspated in cable Y02)

soil W400_hdda ln

Dy02_y3ma( hr) (Temperature rise at the surface of cable produced by the power
Dy02_y3a( hr) of furthest 400 kV circuit and disspated in cable Y02)

soil W400_hdda ln

Dy02_y4ma( hr) (Temperature rise at the surface of cable produced by the power
Dy02_y4a( hr) of closest 400 kV circuit and disspated in cable Y02)

soil W400_hdda ln

Dy02_y5ma( hr) (Temperature rise at the surface of cable produced by the power
Dy02_y5a( hr) of closest 400 kV circuit and disspated in cable y02)

soil W400_hdda ln

Dy02_y6ma( hr) (Temperature rise at the surface of cable produced by the power
Dy02_y6a( hr) of closest 400 kV circuit and disspated in cable Y02)

soil W400_hdda ln

Phdda soil , hr := y02_y1a soil , hr + y02_y2a soil , hr + y02_y3a soil , hr + y02_y4a soil , hr ...
+

y02_y5a soil , hr + y02_y6a soil , hr

(Total rise above ambient temperature at the surface of the Y02 cable, whose rating is being determined, caused by the
power disspated by the other cables in group)

Final Ampacity calculation N7144.xmcd

56

22.03.2013

Hhl_RFY1 ( hr) := hr shdd


Hbl_RFY1 ( hr) := hr + shdd

uRFY1( hr) :=

(Burial depth of the upmost cable, mm)

3
3

(Burial depth of the deepst cable, mm)

2. Hbl_RFY1 ( hr)

(u RF2 is calculated with reference to the centre line of the deepest

dopipe_hdd

ducts(non-touching ducts)

u1c_RFY1 ( hr) := lnuRFY1( hr) +

T43c_RFY1 soil , hr :=

2
u

RFY1( hr) 1

soil

u
1c_RF2( hr) + ln

2
2

( 2 Hbl_RFY1 ( hr) ) + ( s hdd)

+ ln

shdd

T4c_RFY1 soil , hr := T41hdd + T42hdd + T43c_RFY1 soil , hr

( 2 Hhl_RFY1 ( hr) )

2
2 shdd
( Hbl_RFY1 ( hr) Hhl_RFY1 ( hr) ) +

2
2

shdd
+

External Thermal Resistance for current rating calculation in HDD, K.m/W

I1hdd_RFY1 soil , hr :=

( hdd Phdda( soil, hr) ) Wd 0.5T1 + n ( T2 + T3 + T4c_RFY1( soil, hr) )

Rcac_hdd T1 + n Rcac_hdd ( 1 + 1_hdd) T2 + n Rcac_hdd ( 1 + 1_hdd) ( T3 + T4c_RFY1( soil , hr) )

P1 hdd_RFY1 soil , hr := I1hdd_RFY1 soil , hr Up_132 10

RFY1t soil , hr :=

(Transmission Power in MVA)

I1hdd_RFY1 ( soil , hr)


I1132_400hdd ( soil , P400hdd)

Final Ampacity calculation N7144.xmcd

57

22.03.2013

hgca =

Phdda hdd , hgca =

I1hdd_RFY1 hdd , hgca =

3500

5.7

942

4000

6.5

921

4500

7.2

901

5000

884

5500

8.7

868

6000

9.3

854

6500

9.9

842

7000

10.3

832

7500

10.5

824

8000

10.6

818

8500

10.6

814

9000

10.5

811

9500

10.3

810

10000

10

808

10500

9.8

808

11000

9.5

807

11500

9.2

807

12000

8.9

807

12500

8.7

807

13000

8.4

807

13500

8.1

807

14000

7.9

807

14500

7.7

807

15000

7.4

807

RFY1t hdd , hgca =

1.138

P1 hdd_RFY1 hdd , hgca =

215
210

1.112

206

1.089

202

1.068

199

1.049

195

1.032

193

1.018

190

1.005

188

0.996

187

0.989

186

0.984

185

0.98

185

0.978

185

0.977

185

0.976

185

0.976

185

0.975

185

0.975

185

0.975

185

0.975

185

0.975

185

0.975

185

0.975

185

0.975

Reduction Factor, RFY1hdd

1.14

1.11

1.07

RFY1t hdd , hgca

)
1.04

0.97
3500

5416.7

7333.3

9250

11166.7

13083.3

15000

hgca

Depth of cable circuit, mm

Final Ampacity calculation N7144.xmcd

58

22.03.2013

9.3 RFK1= Cables in ductbank for road crossing for various Depths and Laying with interaction of
400 kV circuits
hgca := 750 , 1000 .. 3000
D k02_k1a( hr) :=

D k02_k1ma( hr) :=

D k02_k2a( hr) :=

D k02_k2ma( hr) :=

D k02_k3a( hr) :=

D k02_k3ma( hr) :=

D k02_k4a( hr) :=

D k02_k4ma( hr) :=

D k02_k5a( hr) :=

D k02_k5ma( hr) :=

D k02_k6a( hr) :=

D k02_k6ma( hr) :=

(Variable Distances of Cables axis from ground surface, mm)

( D400b_132_rc + S400_rc ) 2 + ( hr hg400_rc) 2

(distance between K02 and K1, mm)

( D400b_132_rc + S400_rc) 2 + ( hr + hg400_rc ) 2


( D400b_132_rc ) 2 + ( hr hg400_rc ) 2

(distance between K02 and K2, mm)

( D400b_132_rc ) 2 + ( hr + hg400_rc) 2

(distance between K02 and mirror image K2, mm)

( D400b_132_rc S400_rc ) 2 + ( hr hg400_rc) 2

(distance between K02 and K3, mm)

( D400b_132_rc S400_rc) 2 + ( hr + hg400_rc ) 2


( D400a_132_rc + S400_rc) 2 + ( hr hg400_rc ) 2

(distance between K02 and mirror image K3, mm)

(distance between K02 and K4, mm)

( D400a_132_rc + S400_rc ) 2 + ( hr + hg400_rc) 2


( D400a_132_rc) 2 + ( hr hg400_rc) 2

(distance between K02 and mirror image K4, mm)

(distance between K02 and K5, mm)

( D400a_132_rc) 2 + ( hr + hg400_rc ) 2

(distance between K02 and mirror image K5, mm)

( D400a_132_rc S400_rc) 2 + ( hr hg400_rc ) 2

(distance between K02 and K6, mm)

( D400a_132_rc S400_rc ) 2 + ( hr + hg400_rc) 2

Final Ampacity calculation N7144.xmcd

(distance between K02 and mirror image K1, mm)

59

(distance between K02 and K6, mm)

22.03.2013

I400rca :=

( P400rc 1000)
(

(Current in the 400 kV circuit as a function of the transmitted power, A)

3 400 )

I400rca = 1155

W400_arca := RAC_400_rc 1 + 1a_rc_400 I400rca

+ Wd400

W400_brca := RAC_400_rc 1 + 1b_rc_400 I400rca

W400_crca := RAC_400_rc 1 + 1c_rc_400 I400rca

k02_k1a soil , hr :=

k02_k2a soil , hr :=

k02_k3a soil , hr :=

k02_k4a soil , hr :=

k02_k5a soil , hr :=

k02_k6a soil , hr :=

1
2
1
2
1
2
1
2
1
2
1
2

(Estimated losses in the 400 kV phase a circuit as a function of


the transmitted power P at 400 kV, W/m)
W400_arca = 15.209

+ Wd400

(Estimated losses in the 400 kV phase b circuit as a function of


the transmitted power P at 400 kV, W/m)
W400_brca = 14.827

+ Wd400

(Estimated losses in the 400 kV phase c circuit as a function of


the transmitted power P at 400 kV, W/m)
W400_crca = 14.822

Dk02_k1ma( hr) (Temperature rise at the surface of cable produced by the power
D k02_k1a( hr) of furthest 400 kV circuit and disspated in cable K02)

soil W400_arca ln

D k02_k2ma( hr) (Temperature rise at the surface of cable produced by the power
Dk02_k2a( hr) of furthest 400 kV circuit and disspated in cable K02)

soil W400_brca ln

Dk02_k3ma( hr) (Temperature rise at the surface of cable produced by the power
D k02_k3a( hr) of furthest 400 kV circuit and disspated in cable K02)

soil W400_crca ln

Dk02_k4ma( hr) (Temperature rise at the surface of cable produced by the power
D k02_k4a( hr) of closest 400 kV circuit and disspated in cable K02)

soil W400_arca ln

D k02_k5ma( hr) (Temperature rise at the surface of cable produced by the power
Dk02_k5a( hr) of closest 400 kV circuit and disspated in cable K02)

soil W400_brca ln

Dk02_k6ma( hr) (Temperature rise at the surface of cable produced by the power
D k02_k6a( hr) of closest 400 kV circuit and disspated in cable K02)

soil W400_crca ln

Prca soil , hr := k02_k1a soil , hr + k02_k2a soil , hr + k02_k3a soil , hr + k02_k4a soil , hr ...
+

k02_k5a soil , hr + k02_k6a soil , hr

(Total rise above ambient temperature at the surface of the K02 cable, whose rating is being determined, caused by the
power disspated by the other cables in group)

do

hgDB_RFK1( hr) := hr +

+ tpipe_rc dopipe_rc 200 + HDB

Final Ampacity calculation N7144.xmcd

60

22.03.2013

hgDB_RFK1( hr)

uDB_RFK1( hr) :=

rb

T4r_corr_RFK1 soil , hr :=

urc_RFK1( hr) :=

2
N

( soil concrete) lnuDB_RFK1( hr) + uDB_RFK1( hr) 1


2

2hr
dopipe_rc

u1rc_RFK1 ( hr) := lnurc_RFK1( hr) +

T43rn_RFK1 soil , hr :=

2
urc_RFK1( hr) 1

concrete
2 hr

u1rc_RFK1( hr) + ln1 +


+ T4r_corr_RFK1 ( soil , hr)

2
str

External Thermal Resistance for current rating calculation in


duct bank (to used at numerator of the final formula), K.m/W

T43rd_RFK1 soil , hr :=

concrete
1 + 0.5 ( 1a_rc( ms , s rc , Rcac_rc) + 1c_rc( ms , src , Rcac_rc) ) 2 hr 2

u1rc_RFK1( hr) +
ln 1 +

s tr
2
( 1 + 1b_rc ( ms , src , Rcac_rc) )

+ T4r_corr_RFK1 soil , hr

...

External Thermal Resistance for current rating calculation in duct bank (to used at
denominator of the final formula), K.m/W

T4rn_RFK1 soil , hr := T41rc + T42rc + T43rn_RFK1 soil , hr

T4rd_RFK1 soil , hr := T41rc + T42rc + T43rd_RFK1 soil , hr

I1rc_RFK1 soil , hr :=

External Thermal Resistance for current rating calculation in


duct bank (to used at denominator of the final formula), K.m/W

( rc Prca( soil, hr) ) Wd 0.5T1 + n ( T2 + T3 + T4rn_RFK1( soil , hr) )

Rcac_rc T1 + n Rcac_rc ( 1 + 1_rc) T2 + n Rcac_rc ( 1 + 1_rc) ( T3 + T4rd_RFK1 ( soil , hr) )

P1 rc_RFK1 soil , hr := I1rc_RFK1 soil , hr U p_132 10

RFK1t soil , hr :=

External Thermal Resistance for current rating calculation in


duct bank (to used at numerator of the final formula), K.m/W

(Transmission Power in MVA)

I1rc_RFK1( soil , hr)


I1132_400rc ( soil , P400rc )

Final Ampacity calculation N7144.xmcd

61

22.03.2013

hgca =

Prca sr , hgca =

RFK1t sr , hgca =

I1rc_RFK1 sr , hgca =

P1 rc_RFK1 sr , hgca =

750

3.337

1.062

1095

250

1000

4.282

1.007

1039

237

1250

5.094

0.967

998

228

1500

5.76

0.937

966

221

1750

6.274

0.913

942

215

2000

6.648

0.894

923

211

2250

6.898

0.879

907

207

2500

7.047

0.867

894

204

2750

7.115

0.857

884

202

3000

7.122

0.848

875

200

Reduction Factor, RFK1rc

1.1

1.05

RFK1t sr , hgca

)
0.94

0.89

0.84
750

1125

1500

1875

2250

2625

3000

hgca

Depth of cable circuit, mm

Final Ampacity calculation N7144.xmcd

62

22.03.2013

9.4 RFX2= Cables in trough for various soil resistivitiy with interacion of 400 kV circuits

soil := 0.8 , 0.9 .. 2.3

I1tr_RFX2 soil , P :=

P1 tr_RFX2 soil , P :=

(Variable thermal resistivity of soil, K.m/W)

( tr Ptr( soil, P) ) Wd 0.5T1 + n ( T2 + T3 + T4trn( soil) )

Rcac_tr T1 + n Rcac_tr ( 1 + 1_tr ) T2 + n Rcac_tr ( 1 + 1_tr ) ( T3 + T4trd( soil) )

I1tr_RFX2( soil , P) ( 3 132 )

1000

)
)

I1tr_RFX2 soil , P
RFX2 t soil , P :=
I1132_400tr st , P

soil =

(Reduction Factor due to 400 kV circuit)

RFX2 t soil , P 400tr =

I1tr_RFX2 soil , P 400tr =

P1 tr_RFX2 soil , P 400tr =

0.8

1.208

1171

268

0.9

1.147

1112

254

1.093

1059

242

1.1

1.044

1012

231

1.2

969

222

1.3

0.96

930

213

1.4

0.923

895

205

1.5

0.889

862

197

1.6

0.857

831

190

1.7

0.828

802

183

1.8

0.8

776

177

1.9

0.774

750

172

0.75

727

166

2.1

0.727

704

161

2.2

0.705

683

156

2.3

0.684

663

151

Final Ampacity calculation N7144.xmcd

63

22.03.2013

1.2

Reduction Factor, RFX2tr

1.1

RFX2t soil , P 400tr

)
0.8

0.7

0.6
0.8

1.1

1.3

1.6

1.8

2.1

2.3

soil

Soil thermal resistivity, C.m/W

9.5 RFY2= Cables in HDD crossing for various soil resistivity with interacion of 400 kV circuits

soil := 0.8 , 0.9 .. 2.3

(Variable thermal resistivity of soil, K.m/W)

I1hdd_RFY2 soil , P :=

P1 hdd_RFY2 soil , P :=

RFY2t soil , P :=

( hdd Phdd( soil, P) ) Wd 0.5T1 + n ( T2 + T3 + T4hdd( soil) )

Rcac_hdd T1 + n Rcac_hdd ( 1 + 1_hdd) T2 + n Rcac_hdd ( 1 + 1_hdd) ( T3 + T4hdd( soil) )

I1132_400hdd ( soil , P) ( 3 132 )

1000

(
)
I1132_400hdd ( hdd , P)
I1hdd_RFY2 soil , P

Final Ampacity calculation N7144.xmcd

(Reduction Factor due to 400 kV circuit)

64

22.03.2013

soil =

RFY2t soil , P 400hdd =

I1hdd_RFY2 soil , P 400hdd =

P1 hdd_RFY2 soil , P 400hdd =

0.8

1.12

927

212

0.9

1.057

875

200

828

189

1.1

0.949

785

180

1.2

0.902

747

171

1.3

0.859

711

163

1.4

0.819

678

155

1.5

0.782

648

148

1.6

0.748

619

142

1.7

0.715

592

135

1.8

0.685

567

130

1.9

0.656

543

124

0.628

520

119

2.1

0.601

498

114

2.2

0.576

476

109

2.3

0.551

456

104

Reduction Factor, RFY2hdd

1.1

0.9

RFY2t soil , P 400hdd

)
0.8

0.7

0.6
0.8

1.1

1.3

1.6

1.8

2.1

2.3

soil

Soil thermal resistivity, C.m/W

Final Ampacity calculation N7144.xmcd

65

22.03.2013

9.6 RFK2= Cables in Duct bank for crossing for various soil resistivity with interacion of 400 kV
circuits
soil := 0.8 , 0.9 .. 2.3

I1rc_RFK2 soil , P :=

P1 rc_RFK2 soil , P :=

(Variable thermal resistivity of soil, K.m/W)

( rc Prc( soil, P) ) Wd 0.5T1 + n ( T2 + T3 + T4m( soil) )

Rcac_rc T1 + n Rcac_rc ( 1 + 1_rc) T2 + n Rcac_rc ( 1 + 1_rc) ( T3 + T4rc( soil) )

I1132_400rc ( soil , P) ( 3 132 )

1000

)
)

I1rc_RFK2 soil , P
RFK2t soil , P :=
I1132_400rc sr , P

soil =

(Reduction Factor due to 400 kV circuit)

RFK2t soil , P 400rc =

I1rc_RFK2 soil , P 400rc =

P1 rc_RFK2 soil , P400rc =

0.8

1.13

1165

266

0.9

1.094

1128

258

1.06

1094

250

1.1

1.029

1062

243

1.2

1032

236

1.3

0.973

1003

229

1.4

0.947

977

223

1.5

0.923

952

218

1.6

0.899

928

212

1.7

0.878

905

207

1.8

0.857

884

202

1.9

0.837

863

197

0.818

844

193

2.1

0.8

825

189

2.2

0.783

807

185

2.3

0.766

790

181

Final Ampacity calculation N7144.xmcd

66

22.03.2013

1.13

Reduction Factor, RFK2rc

1.06

0.98

RFK2t soil , P 400rc

)
0.91

0.83

0.76
0.8

1.1

1.3

1.6

1.8

2.1

2.3

soil

Soil thermal resistivity, C.m/W


9./ RFX3= Cables in trough for various soil temperatures with interacion of 400 kV circuits
ground := 30 , 31 .. 50

RFX3 ground := max ground

I1tr_RFX3 soil , P , ground :=

P1 tr_RFX3 soil , P , ground :=

RFX3 t soil , P , ground :=

( RFX3 ( ground) Ptr( soil, P) ) Wd 0.5T1 + n ( T2 + T3 + T4trn( soil) )


Rcac_tr T1 + n Rcac_tr ( 1 + 1_tr ) T2 + n Rcac_tr ( 1 + 1_tr ) ( T3 + T4trd( soil) )

I1tr_RFX3( soil , P , ground) ( 3 132 )

1000

I1tr_RFX3 soil , P , ground

I1132_400tr soil , P

Final Ampacity calculation N7144.xmcd

(Reduction Factor due to 400 kV circuit)

67

22.03.2013

ground =

RFX3 t st , P 400tr , ground =

I1tr_RFX3 st , P 400tr , ground = P1 tr_RFX3 st , P 400tr , ground =

30

1.114

1080

247

31

1.103

1070

245

32

1.092

1059

242

33

1.081

1048

240

34

1.07

1037

237

35

1.059

1026

235

36

1.047

1015

232

37

1.036

1004

229

38

1.024

992

227

39

1.012

981

224

40

969

222

41

0.988

957

219

42

0.976

946

216

43

0.963

933

213

44

0.95

921

211

45

0.938

909

208

46

0.925

896

205

47

0.911

883

202

48

0.898

870

199

49

0.885

857

196

50

0.871

844

193

Reduction Factor, RFX3tr

1.12

1.07

1.02

RFX3t st , P 400tr , ground

)
0.97

0.92

0.87
30

33.3

36.7

40

43.3

46.7

50

ground

Soil Temperature, C

Final Ampacity calculation N7144.xmcd

68

22.03.2013

9.8 RFY3= Cables in HDD crossing for various soil temperatures with interacion of 400 kV circuits
ground := 30 , 31 .. 50

RFY3 ground := max ground

ground := 30 , 31 .. 50
I1hdd_RFY3
soil , P , ground :=

P1 hdd_RFY3 soil , P , ground :=

RFY3t soil , P , ground :=

ground =

( RFY3( ground) Phdd( soil , P) ) Wd 0.5T1 + n ( T2 + T3 + T4hdd( soil) )


Rcac_hdd T1 + n Rcac_hdd ( 1 + 1_hdd) T2 + n Rcac_hdd ( 1 + 1_hdd) ( T3 + T4hdd( soil) )

I1hdd_RFY3 ( soil , P , ground) ( 3 132 )

1000

I1hdd_RFY3 soil , P , ground

I1132_400hdd soil , P

(Reduction Factor due to 400 kV circuit)

)
)

RFY3t hdd , P 400hdd , ground =

30

1.123

929

212

31

1.111

920

210

32

1.099

910

208

33

1.087

900

206

34

1.075

890

204

35

1.063

880

201

36

1.051

870

199

37

1.038

859

196

38

1.026

849

194

39

1.013

838

192

40

828

189

41

0.987

817

187

42

0.974

806

184

43

0.96

795

182

44

0.946

783

179

45

0.932

772

176

46

0.918

760

174

47

0.904

748

171

48

0.89

736

168

49

0.875

724

166

50

0.86

712

163

Final Ampacity calculation N7144.xmcd

I1hdd_RFY3 hdd , P 400hdd , ground =P1 hdd_RFY3 hdd , P 400hdd , ground

69

22.03.2013

Reduction Factor, RFY3hdd

1.12

1.07

1.02

RFY3t hdd , P 400hdd , ground

)
0.96

0.91

0.86
30

33.3

36.7

40

43.3

46.7

50

ground

Soil Temperature, C
9.9 RFK3= Cables in Duct bank for crossing for various soil temperatures with interacion of 400
kV circuits
ground := 30 , 31 .. 50

RFK3 ground := max ground

I1rc_RFK3 soil , P , ground :=

P1 rc_RFK3 soil , P , ground :=

RFK3t soil , P , ground :=

( RFK3( ground) Prc( soil , P) ) Wd 0.5T1 + n ( T2 + T3 + T4m( soil) )


Rcac_rc T1 + n Rcac_rc ( 1 + 1_rc) T2 + n Rcac_rc ( 1 + 1_rc) ( T3 + T4rc( soil) )

I1rc_RFK3( soil , P , ground) ( 3 132 )

1000

I1rc_RFK3 soil , P , ground

I1132_400rc soil , P

Final Ampacity calculation N7144.xmcd

(Reduction Factor due to 400 kV circuit)

70

22.03.2013

ground =

RFK3t sr , P 400rc , ground =

I1rc_RFK3 sr , P 400rc , ground =

P1 rc_RFK3 sr , P400rc , ground =

30

1.108

1143

261

31

1.098

1132

259

32

1.087

1122

256

33

1.077

1111

254

34

1.066

1100

251

35

1.055

1089

249

36

1.045

1078

246

37

1.034

1066

244

38

1.022

1055

241

39

1.011

1043

239

40

1032

236

41

0.989

1020

233

42

0.977

1008

230

43

0.965

996

228

44

0.953

984

225

45

0.941

971

222

46

0.929

959

219

47

0.917

946

216

48

0.904

933

213

49

0.892

920

210

50

0.879

907

207

Reduction Factor, RFY3hdd

1.12

1.07

1.02

RFY3t hdd , P 400hdd , ground

)
0.97

0.92

0.87
30

33.3

36.7

40

43.3

46.7

50

ground

Soil Temperature, C

Final Ampacity calculation N7144.xmcd

71

22.03.2013

9.10 RFX4= Cables in trough for various cable separation with interacion of 400 kV circuits
s ca := 200 , 250 .. 600

( )

D x02_x1b s ca :=

( )

D x02_x1mb sca :=

( )

D x02_x2b s ca :=

( )

D x02_x2mb sca :=

( )

D x02_x3b s ca :=

( )

D x02_x3mb sca :=

( )

D x02_x4b s ca :=

( )

D x02_x4mb sca :=

( )

D x02_x5b s ca :=

( )

D x02_x5mb sca :=

( )

D x02_x6b s ca :=

( )

D x02_x6mb sca :=

( D400b_132_tr + sca) + ( hg1ca_tr hg400_tr )


2

(distance between X02 and X1, mm)

( D400b_132_tr + sca) + ( hg1ca_tr + hg400_tr )


2

( D400b_132_tr) + ( hg1ca_tr hg400_tr )


2

(distance between X02 and X2, mm)

(distance between X02 and mirror image X2, mm)

( D400b_132_tr sca) + ( hg1ca_tr hg400_tr )


2

(distance between X02 and X3, mm)

( D400b_132_tr sca) + ( hg1ca_tr + hg400_tr )


2

( D400a_132_tr + sca) + ( hg1ca_tr hg400_tr )


2

(distance between X02 and mirror image X5, mm)

(distance between X02 and X6, mm)

( D400a_132_tr sca) + ( hg1ca_tr + hg400_tr )


)

Final Ampacity calculation N7144.xmcd

(distance between X02 and mirror image X4, mm)

(distance between X02 and X5, mm)

( D400a_132_tr sca) + ( hg1ca_tr hg400_tr )


2

( D400a_132_tr) + ( hg1ca_tr + hg400_tr )


2

(distance between X02 and mirror image X3, mm)

(distance between X02 and X4, mm)

( D400a_132_tr + sca) + ( hg1ca_tr + hg400_tr )


2

(distance between X02 and mirror image X1, mm)

( D400b_132_tr ) + ( hg1ca_tr + hg400_tr )

( D400a_132_tr) + ( hg1ca_tr hg400_tr )

72

(distance between X02 and X6, mm)

22.03.2013

I400trb :=

( P400tr 1000)
(

(Current in the 400 circuit as a function of the transmitted power, A)

3 400 )

I400trb = 1591

W400_atrb := RAC_400_tr 1 + 1a_tr_400 I400trb

+ Wd400

(Estimated losses in the 400 kV phase a circuit as a function of


the transmitted power P at 400 kV, W/m)
W400_atrb = 27.911

W400_btrb := RAC_400_tr 1 + 1b_tr_400 I400trb

+ Wd400

(Estimated losses in the 400 kV phase b circuit as a function of


the transmitted power P at 400 kV, W/m)
W400_btrb = 27.182

W400_ctrb := RAC_400_tr 1 + 1c_tr_400 I400trb

+ Wd400

(Estimated losses in the 400 kV phase c circuit as a function of


the transmitted power P at 400 kV, W/m)
W400_ctrb = 27.172

x02_x1b soil , sca :=

x02_x2b soil , sca :=

x02_x3b soil , sca :=

x02_x4b soil , sca :=

x02_x5b soil , sca :=

x02_x6b soil , sca :=

1
2

1
2
1
2
1
2
1
2
1
2

Dx02_x1mb( sca) (Temperature rise at the surface of cable produced by the power
Dx02_x1b( sca) of furthest 400 kV circuit and disspated in cable X02)

soil W400_atrb ln

Dx02_x2mb( sca) (Temperature rise at the surface of cable produced by the power
Dx02_x2b( sca) of furthest 400 kV circuit and disspated in cable X02)

soil W400_btrb ln

Dx02_x3mb( sca) (Temperature rise at the surface of cable produced by the power
Dx02_x3b( sca) of furthest 400 kV circuit and disspated in cable X02)

soil W400_ctrb ln

Dx02_x4mb( sca) (Temperature rise at the surface of cable produced by the power
Dx02_x4b( sca) of closest 400 kV circuit and disspated in cable X02)

soil W400_atrb ln

Dx02_x5mb( sca) (Temperature rise at the surface of cable produced by the power
Dx02_x5b( sca) of closest 400 kV circuit and disspated in cable X02)

soil W400_btrb ln

Dx02_x6mb( sca) (Temperature rise at the surface of cable produced by the power
Dx02_x6b( sca) of closest 400 kV circuit and disspated in cable X02)

soil W400_ctrb ln

Ptrb soil , sca := x02_x1b soil , s ca + x02_x2b soil , sca + x02_x3b soil , sca + x02_x4b soil , sca ...
+

x02_x5b soil , sca + x02_x6b soil , sca

(Total rise above ambient temperature at the surface of the X02 cable, whose rating is being determined, caused by the
power disspated by the other cables in group)

Final Ampacity calculation N7144.xmcd

73

22.03.2013

( 2.hg1ca_tr)

ut_RF7b :=

do

u1t_RF7b := lnut_RF7b +

2
ut_RF7b 1

2 External Thermal Resistance for current rating calculation in

soil
2 hg1ca_tr
trough (to used at numerator of the final formula), K.m/W
T4trn_RF7b( soil , sca ) :=
u1t_RF7b + ln1 +


2
sca
2

soil
1 + 0.5 ( 1a_tr( ms , str , Rcac_tr) + 1c_tr( ms , str , Rcac_tr) ) 2 hg1ca_tr
T4trd_RF7b( soil , sca ) :=
( u1t_RF7b) +
ln 1 +

sca
2
( 1 + 1b_tr( ms , str , Rcac_tr) )

External Thermal Resistance for current rating calculation in trough (to used at
denominator of the final formula), K.m/W

I1tr_RFX4 soil , s ca :=

( tr Ptrb( soil , sca) ) Wd 0.5T1 + n ( T2 + T3 + T4trn_RF7b( soil , sca) )


Rcac_tr T1 + n Rcac_tr ( 1 + 1_tr ) T2 + n Rcac_tr ( 1 + 1_tr ) ( T3 + T4trd_RF7b( soil , sca ) )

P1 tr_RFX4 soil , sca := I1tr_RFX4 soil , sca U p_132 10

RFX4 c soil , sca :=

s ca =

(Transmission Power in MVA)

I1c_RF7( soil , sca)


I1132_400tr ( soil , P400tr )

RFX4 c st , sca =

200

1.089

250
300

I1tr_RFX4 st , sca =

974

223

1.113

995

228

1.134

1014

232

350

1.152

1029

235

400

1.169

1043

239

450

1.184

1056

241

500

1.197

1068

244

550

1.21

1078

246

600

1.222

1088

249

Final Ampacity calculation N7144.xmcd

74

P1 tr_RFX4 st , sca =

22.03.2013

POWER CABLE
IMPEDANCE
CALCULATIONS

Final Ampacity calculation N7144.xmcd

75

22.03.2013

Variable Data

K := 0.05
:=

Self impedance factor

Factor for calculation conductor mean self geometric distance

K
exp

0.2

= 0.779

dc

rGMD :=

Mean geometric conductor radius, mm


rGMD = 17.523

Avarage value for liss factor (cables in trough);

t := 1a_tr ms , str , Rcac_tr

1.

t = 0.062

Positive and negative sequence impedance


1

2.
s tr

3
3 3
Zab := Rcac_tr 10 ( 1 + t) + K + 0.2 ln
2 10 i
dc

Direct/Inverse sequence Impedance, Ohm/km


Zab = 0.021 + 0.168i
Zab = 0.169

2.

Zero sequence impedance


Rs acld :=

klead ms lead

A.C. Resistances of lead sheath , Ohm/km

Alead

3
3
4
Z0 := Rcac_tr 10 + Rsacld 10 + 2 10
ln

2 rGMD
dlead

Zero Sequence Impedance, /km


Z0 = 0.279 + 0.060i
Z0 = 0.285

Final Ampacity calculation N7144.xmcd

76

22.03.2013