Documente Academic
Documente Profesional
Documente Cultură
EOP/124 23-02-2010
What is a circuit-breaker?
It is a switching device for making and interrupting current. This function applies to any devices from the largest circuit-breaker down to the smallest relay.
General
The flow of electric current in a circuit is a form of kinetic energy, and it cannot be stopped instantaneously. The energy must be taken out of the system for all current to cease, and this takes a finite time, no matter how small it may be.
Another example
Back
When the contacts of a switch separate while carrying current, that current cannot be stopped there , but will continue to flow between the opening contacts in the form of an arc
The arc is a column of white-hot gas which is ionized by its heat and provides a conducting path for the current
This path has appreciable resistance which increases as the contacts continue to separate and the arc lengthens Eventually the resistance becomes so high that the current falls to the point where it can no longer maintain the arc temperature, ionization ceases, the air ceases to conduct and the arc goes out, finally stopping the current.
V
I 90 90
V I 90
90
When short circuit occurs with an inductive resistive circuit, the fault current is 100% asymmetrical if the fault occurs at the instant of voltage zero. The figure below shows where the asymmetrical is partial between 0% and 100%.
Back
DC interruption
Generator and cable resistance
DC generator
Load
Load
V When breaker contacts separate, the current cannot stopped there and will continue to flow in the form of an arc.
After the contacts separate far enough, the arc does not restrike and finally extinguished
DC generator Circuit breaker contacts
Load
Load
AC interruption
Assume that the circuit is purely resistive
AC generator
Load
Load
Type of faults:
to fault to to earth fault to earth fault 3 fault
Ohms law
I = V/R R=? R = 0.01 V = 254 volts I = 25,400A
Curve
Load
Protection relay will detect the fault. And activate the circuit breaker Contacts open, and the current will flow in the form of an arc
Load
V
-When contacts of circuit-breaker separate while carrying current at certain instantaneous values, the current flow between the opening contacts will be in form of arc I
Load
Continues
V
When instantaneous current goes to natural zero, the arc is extinguished momentarily. I v
When voltage high enough
But when the instantaneous voltage goes high enough to restrike the arc again.
This action will continue for few cycles until the circuitbreaker contacts separated far enough so that the voltage cannot break it down. The current finally interrupted
Load
V
I
Example: AC current breaking G The gap becomes too great for the voltage to break it down Load
Load
V I
Assume that the breaker is open at certain instantaneous current as shown in the figure
90
Load Continue
Restriking voltage
The arc restriking after current zero is the voltage which immediately reappears across the gap
90 V
Load
V
I
V V
With inductive circuit, the arc restriking immediately after current at the natural zero, because the voltage is high when current at zero
Load
The arc would take some Main moving contact time to extinguish.
Contacts will be pitted after operating many times especially high load current
-To avoid the main contacts damage, the arcing contacts are built
Arcing contacts With arcing contacts, the arc also take some time to extinguish
The arcing contacts will open after the main contacts opening
During breaker closing, the arcing contacts will close first before the main contacts
Example
Close
Circuit-breaker arcing contacts closed first, then follow by main contacts. So that the main contacts more lasting and less carbon deposit on the contacts surfaces
With arc chute, the arc extinguished before the breaker fully open.
When the arc, driven upwards by the electromagnetic forces, enters the bottom of the chute, it is split into many sections by the barriers, but the metal pieces ensure electrical continuity between the arcs in each section; the several arcs are thus in series. The electromagnetic forces within each section of the chute cause the arc in that section to take up the form of a helix
Close
But when breaking with the small load current, the electromagnetic force due to current loop is not strong, so that the arc driven by the electromagnetic force is weak, Because of this, it would also take some time to extinguish
Air is compressed in a cylinder operated by the tripping mechanism and blows any reluctant arc upwards into the chute
Air Puffer
Tripping Coil
Charge
Charging motor
M M M M
Tripping Coil
Tripping coil
Close
Charging motor
Tripping coil
Charging motor
Tripping Coil
Repeat
Charging motor
The END