Substation Automation and Protection Training

PCM 600 Application Configuration CAP 531

ABB Power Technologies AB, 2007 2007-09-07 1

Substation Automation and Protection Training

Application Configuration CAP 531


CAP 531 IS THE MASTER TOOL!
You MUST start the engineering from CAP 531. After COMPILING the graphic configuration, CAP 531 passes IMPORTANT INFORMATION to other subtools:
PCM 600 receives the list of used functions SMT receives the list of hardware cards and used virtual I/O GDE receives the used control and measurement blocks

ABB Power Technologies AB, 2007 2007-09-07 3

Substation Automation and Protection Training

Application Configuration CAP 531


In CAP 531 the application configuration is drawn without considering the hardware set-up of the IED.

ABB Power Technologies AB, 2007

The association VIRTUAL I/O PHISICAL I/O is done in SIGNAL MATRIX

2007-09-07 4

Substation Automation and Protection Training

Application Configuration CAP 531

ABB Power Technologies AB, 2007 2007-09-07 5

Substation Automation and Protection Training

CAP 531 On Line Software Library Synchronization


ONLINE / UPLOAD OPTIONS
IF YOU HAVE THE IED connected to the PC, the fastest way to get the PC function library synchronized with the IED library is to run Upload Options:

BEFORE UPLOAD OPTIONS: PC contains more functions than IED


ABB Power Technologies AB, 2007

AFTER UPLOAD OPTIONS: PC contains the same functions than IED

2007-09-07 6

Substation Automation and Protection Training

CAP 531 On Line Software Library Synchronization


EDIT / FUNCTION SELECTOR

ABB Power Technologies AB, 2007 2007-09-07 7

Substation Automation and Protection Training

CAP 531 Draw the Configuration

ABB Power Technologies AB, 2007 2007-09-07 8

Substation Automation and Protection Training

CAP 531 Insert a Work Sheet


Select the terminal and choose the menu Edit / Insert:

Enter the name of the work sheet

ABB Power Technologies AB, 2007 2007-09-07 9

Substation Automation and Protection Training

CAP 531 Insert Function Blocks


Choose the menu Object / Function Block:

ABB Power Technologies AB, 2007 2007-09-07 10

Substation Automation and Protection Training

CAP 531 Insert Function blocks


In the window choose the correct function block and click on Ok.

ABB Power Technologies AB, 2007

The function block will appear on your work sheet.

2007-09-07 11

Substation Automation and Protection Training

CAP 531 Connect Function Blocks


Click on the button and start connecting the signals

ABB Power Technologies AB, 2007 2007-09-07 12

Substation Automation and Protection Training

CAP 531 Variables


This configuration: Is equivalent to this one:

ABB Power Technologies AB, 2007 2007-09-07 13

Substation Automation and Protection Training

CAP 531 Cross Referenced vs Not Cross Referenced


CROSS REFERENCES
If you want a variable to be cross-referenced in CAP print-out, just drag the variable to cross the red dashed line shown by CAP 531 when you choose the menu Layout / Page Borders.

ABB Power Technologies AB, 2007

Cross Referenced Variables

NOT Cross Referenced Variables

2007-09-07 14

Substation Automation and Protection Training

CAP 531 Graphic Buttons

Zoom Out Zoom In Select Zoom Area Select Mark Mode


ABB Power Technologies AB, 2007

Create Variable Insert Function Block Free Text

Select Drawing Mode

2007-09-07 15

Substation Automation and Protection Training

CAP 531 CAD Features

ABB Power Technologies AB, 2007 2007-09-07 16

Substation Automation and Protection Training

CAP 531 Insert a Template

ABB Power Technologies AB, 2007 2007-09-07 17

Substation Automation and Protection Training

CAP 531 Page Layout


With CAP 531 you have the possibility to associate a page layout to your drawing with all the important data: - customer name - issue date - drawing number - etc. It is also possible to customize the page layout according to your customer needs.

ABB Power Technologies AB, 2007 2007-09-07 18

Substation Automation and Protection Training

CAP 531 Page Layout


From Page Preview you can see how the drawing will be printed out:

ABB Power Technologies AB, 2007 2007-09-07 19

Substation Automation and Protection Training

CAP 531 Compiling the Configuration


When the Application Configuration is ready you have to compile it Note: The Graphic Application Configuration does not contain any Input/Output information. It only contains VIRTUAL I/O information!

ABB Power Technologies AB, 2007 2007-09-07 20

Substation Automation and Protection Training

CAP 531 Downloading the Configuration


The successfully compiled configuration can be downloaded into the IED:

ABB Power Technologies AB, 2007 2007-09-07 21

Substation Automation and Protection Training

CAP 531 Downloading Phase


1) Secret Upload Options (reading)

2) Download of operative configuration

(writing)

ABB Power Technologies AB, 2007 2007-09-07 22

Substation Automation and Protection Training

CAP 531 Downloading Phase


3) Uploading of configuration (reading)

4) Comparing PC configuration against uploaded one

ABB Power Technologies AB, 2007 2007-09-07 23

Substation Automation and Protection Training

CAP 531 Downloading Phase


5) If Compare is not Ok you are requested to download again

6) If Compare is Ok : Download of graphic information of configuration (the so called zip file) (writing)

ABB Power Technologies AB, 2007 2007-09-07 24

Substation Automation and Protection Training

CAP 531 Exit CAP531 and go back to PCM 600


When you exit CAP 531 containing a successfully compiled configuration, the list of used functions is associated to your IED in PCM 600 structure.

ABB Power Technologies AB, 2007 2007-09-07 25

Substation Automation and Protection Training

CAP 531 Uploading application configuration from IED

UPLOAD THE CONFIGURATION

ABB Power Technologies AB, 2007

You can upload the graphic configuration from the terminal into the PC.

2007-09-07 26

Substation Automation and Protection Training

CAP 531 Uploading application configuration from IED

ABB Power Technologies AB, 2007

COMPILE and EXIT CAP531!


2007-09-07 27 Substation Automation and Protection Training

CAP 531 Uploading application configuration from IED This happens while you exit CAP531:

ABB Power Technologies AB, 2007 2007-09-07 28

Substation Automation and Protection Training

CAP 531 Compare Configurations


CAP 531 has the possibility to compare the configuration located into the PC with the configuration stored into the terminal. This process is very useful to check if the configuration stored in the terminal is the same configuration which was downloaded during the commissioning or during the last download.

ABB Power Technologies AB, 2007 2007-09-07 29

Substation Automation and Protection Training

CAP 531 Compare Configurations

If these two different configurations will be compared, a window with the list of differences will be produced:

ABB Power Technologies AB, 2007 2007-09-07 30

Substation Automation and Protection Training

CAP531 On-line/Debug

ABB Power Technologies AB, 2007 2007-09-07 31

Substation Automation and Protection Training