Complete structural design calculations and drawings which are fully coordinated with
architectural drawings/requirements and fully conform to applicable codes and
geotechnical parameters.
Complete Architectural Drawings indicating plans, elevations, sections, perspective view
and details including location, thickness and height of masonary walls, thickness of floor
finishes and other pertinent details are required.
Besides comments/observations on geotechnical investigation report, submitted by Soil
Cone Foundation Masters, are as follows:
Geotechnical Investigations are not site specific.
Exact location, coordinates and elevation of each borehole and nearest road level are not
given, for any interpretation.
Location plan of drilled boreholes is not attached.
The method of drilling is primitive and does not afford reliable results.
Exact location of undisturbed samples extracted from cohesive soil was not mentioned in
Borehole logs. Method used for extraction of undisturbed soil samples is not mentioned in
the report.
The procedure or testing backup for the determination of Bulk Density/ Dry density,
Natural Moisture Content, unconfined compressive strength, cohesion and angle of
internal friction is not mentioned despite giving values in the report.
Details of Laboratory test results were not provided in the report.
The bearing capacity of 1.57 Tsf is adopted in the report without using any laboratory test
results. Require justification?
In the design report the method of calculating the immediate settlement is incorrect.
Approach and basic formula is wrong.
Change/ variation from attached boreholes logs was observed during excavation
It is suggested that site specific geotechnical investigations should be conducted under full
time supervision of geotechnical engineer for confirmation and further evaluation/ analysis
Regards
Khalid Ejaz
General Manager Structures