TENDER DOCUMENT FOR Diagnostic Testing of Transformers at NRL Site (NRL/C17/00344).

Tender No. OC17000051

PART - I :

UNPRICED BID

PREPARED & ISSUED BY

NUMALIGARH REFINERY LIMITED


( A Govt. of India Enterprise )

NUMALIGARH REFINERY LIMITED (A GOVERNMENT OF INDIA ENTERPRISE) NRL COMPLEX, NUMALIGARH, Dist : GOLAGHAT, ASSAM 785699 Tel.: 03776-265413 Fax : 03776-265514

Schedule of Rate
TENDER DOCUMENT FOR Diagnostic Testing of Transformers at NRL Site (NRL/C17/00344).

Tender No. OC17000051

PART - II : PRICED BID

PREPARED & ISSUED BY

NUMALIGARH REFINERY LIMITED


( A Govt. of India Enterprise )

Page No: ____________________________________________________________________________________________________ Item Ref. Description Unit Qty Figures Rate in Words Amount

NUMALIGARH REFINERY LTD. Numaligarh

00010

Diagnostic testing of transformer

The item covers the following services: 10 IR & PI test Numbers 16.000

Insulation Resistance and polarization index: These are to be measured at 2.5 KV.

20

Numbers

16.000

DC winding resistance: Winding resistance measurement will indicate change due to shorted turns, loose connections, or deteriorating contacts in tap changers.The transformer inductive circuit must be charged and stabilized in order to allow an accurate reading to be made.

30

Numbers

16.000

____________________________________________________________________________________________________
Tender No. : OC17000051 Sheet 3 of 8

TTR test: The TTR is performed to ensure that the turns ratio of the transformer is correct, that is, none of the transformer windings are shorted out. Basically it compares the number of

Page No: ____________________________________________________________________________________________________ Item Ref. Description Unit Qty Figures turns in winding 1 with the number of turns in winding 2. The test should be performed for each tap position for transformers equipped with tap changers.The TTR test can also verify the polarity of the transformer. The TTR test value for acceptance should not be greater than 0.5% as compared to calculated values.The TTR test shall be performed at higher voltages using a capacitor in combination with the PF test set.The benefits of the HV TTR tests are that it identifies problems and anomalies in the electric and magnetic circuit (i.e., core and coils) of the transformer that are not revealed with the low-voltage TTR tests. Rate in Words Amount

NUMALIGARH REFINERY LTD. Numaligarh

40

Numbers

16.000

This test shall be carried out to assess winding shorts, degradation and winding contamination. 50 Numbers 16.000

Capacitance and TanDelta Test ( Winding and the bushings): Test should cover entire mass of Insulation: HV v/s LV grounded LV v/s H/V grounded HV v/s LV Bushing insulation To assess presence of voids in insulation,contamination due to moisture,occurrence of partial discharge in the voids.

____________________________________________________________________________________________________
Tender No. : OC17000051 Sheet 4 of 8

Page No: ____________________________________________________________________________________________________ Item Ref. Description Unit Qty Figures Rate in Words Amount

NUMALIGARH REFINERY LTD. Numaligarh

60 SFRA ( Sweep Frequency Response Analysis): Sweep frequency response method measures the response over a band of frequencies from 20 Hz to 2 MHz.SFRA is the ratio of a steady sinusoidal output from a test object subjected to a steady sinusoidal input can be identified by its frequency-dependent transfer function.It detect mechanical failure or movement of windings due to short circuits,mechanical stresses, or transportation.Typical internal mechanical problems identifi ed in transformers with SFRA are: -Core movement -Winding deformation and displacement -Faulty core grounds -Partial winding collapse -Hoop buckling -Broken or loosened clamping structures -Shorted turns and open windings

Numbers

10.000

SFRA ( Sweep Frequency Response Analysis): Sweep frequency response method measures the response over a band of frequencies from 20 Hz to 2 MHz.SFRA is the ratio of a steady sinusoidal output from a test object subjected to a steady sinusoidal input can be identified by its frequency-dependent transfer function.It detect mechanical failure or movement of windings due to short circuits,mechanical stresses, or transportation.Typical internal mechanical problems identifi ed in transformers with SFRA : OC17000051

____________________________________________________________________________________________________
Tender No. Sheet 5 of 8

Page No: ____________________________________________________________________________________________________ Item Ref. Description Unit Qty Figures are: -Core movement -Winding deformation and displacement -Faulty core grounds -Partial winding collapse -Hoop buckling -Broken or loosened clamping structures -Shorted turns and open windings Rate in Words Amount

NUMALIGARH REFINERY LTD. Numaligarh

70

Numbers

16.000

Excitation Current Test: In this test, voltage is applied to the primary windings one at time with all other windings left open.It provides means of detection for winding problems, such as short-circuited or open turns, poor joints or contacts,core problems, etc.

80

Numbers

16.000

Polarization recovery voltage test: The transformer insulation systems are composites of two insulating materials: cellulose fi ber (paper) and insulating oil. This structure shows space-charge polarization effects which are strongly infl uenced by the moisture content and aging products.

90 Activity unit 3.000 ____________________________________________________________________________________________________ Tender No. : OC17000051 Sheet 6 of 8

Page No: ____________________________________________________________________________________________________ Item Ref. Description Unit Qty Figures Rate in Words Amount

NUMALIGARH REFINERY LTD. Numaligarh

MOBILISATION & DEMOBILISATION CHARGES FOR ELECTRICAL ANALYST: Includes to & fro transportation expenses to NRL & back as per actual.

MOBILISATION & DEMOBILISATION CHARGES FOR ELECTRICAL ANALYST: Includes to & fro transportation expenses to NRL & back as per actual.

100

Activity unit

3.000

MOBILISATION & DEMOBILISATION CHARGES FOR ENGINEER: Mobilising & demobilisation charges as required for conducting the test at NRL site.This includes to & fro transportation expenses to NRL & back as per actual.

110

Activity unit

3.000

MOBILISATION & DEMOBILISATION CHARGES FOR EQUIPMENT: Mobilising charges as required for conducting the test at NRL ____________________________________________________________________________________________________ Tender No. : OC17000051 Sheet 7 of 8

Page No: ____________________________________________________________________________________________________ Item Ref. Description Unit Qty Figures site.This includes the transportation expenses,mobilising the equipments at site & demobilising after all the relevant tests are conducted. Rate in Words Amount

NUMALIGARH REFINERY LTD. Numaligarh

____________________________________________________________________________________________________
Total : ____________________________________________________________________________________________________ Percentage rebate(if any) in words : Grand Total in Words : Signature : Percentage : Less Rebate : Grand Total :

Name Address of the Contractor Place : Date :

: : :

____________________________________________________________________________________________________
Tender No. : OC17000051 Sheet 8 of 8