Fundamentos de Arranque Motor

Ing. Guillermo Surez Mayo 2009

Schneider Electric - Ahorro de Energa Mayo 2009

65

Schneider Electric - Ahorro de Energa Mayo 2009

66

Schneider Electric - Ahorro de Energa Mayo 2009

67

Schneider Electric - Ahorro de Energa Mayo 2009

68

Schneider Electric - Ahorro de Energa Mayo 2009

69

80 aos de innovacin
TeSys D TeSys U

TeSys T Busbar Contactor

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

Una historia de innovacin que no termina.


Motor Circuit Breaker GV3P EveLink power terminal Modularity concept with the new TeSys range 2000

2004

* 2006 *

D2 : new raw material, more modularity & accessories 1990 First monobloc contactor 1935 The very first contactor ... * * First motor starter enclosure 1924 1973 * 1960

* Motor Management System Tesys T Give your motor starter a sixth sense ! Tesys Mod. U All in 1 product Disconnection , Electronic protection , Switching ,

1993 * GV2: a really impulsion to 2 * First modular component contactor solution *

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

Campo de actividad
Utilities Distribution
source switching

Terminal loads
M

Circuit switching

Process
Machine

Terminal loads
M

Terminal loads
M M M

Lighting

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

Funciones asociadas al arranque motor


Distribucin baja tensin Aislamiento Seccionamiento Proteccin corto-circuito Proteccin sobrecarga Maniobra

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

Seccionamiento

Este dispositivo tiene la habilidad de aislar y desconectar. Puede ser usado con seguridad con carga. No incluye ningn mecanismo de proteccin. Puede ser usado como un botn de parada de emergencia (Con la cubierta amarilla y la manija roja).

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

Interruptor

Estos equipos pueden ser manejados con carga. Incluyen fusibles para la proteccin de corto circuito. La operacin se realiza por la manija del lado.

GS1

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

Proteccin contra corto circuito disyuntor magntico


Este equipo proporciona la proteccin contra los corto circuitos. El detecta y despeja los altos niveles de corriente de corto circuito hasta el limite de su capacidad de ruptura. Tiene la capacidad de desconexin El reset despus de la falla puede ser realizado manualmente con el mando rotatorio del equipo o remotamente usando mdulos especficos para esta accin. Para fallas de baja corriente, la operacin de un disyuntor, es mas rpida que la de los fusibles.

GV2-L

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

Proteccin Magntica.

Este disyuntor incluye tanto la proteccin magntica contra cortocircuitos, como la proteccin trmica ( sobrecarga de motor). Ya que estos equipos incluyen todos los tipos de proteccin y tiene la capacidad de desconexin, pueden ser usados como un arrancador de motor para mquinas simples.

GV2-ME
Bloques adicionales pueden ser aadidos para permitir el reset remoto y el control del disyuntor.

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

El Contactor
Apertura y cierre bajo carga- capacidad de switcheo. Manejo remoto utilizando un electroimn con un circuito de control separado . Cuando la bobina del contactor es energizada, La parte mvil del contactor se mueve y la corriente puede pasar de la red de suministro a la carga. Estos equipos tienen contactos auxiliares incluidos que se mueven simultneamente con la parte mvil del contactor .

LC1-D contactor

Bar contactor

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

10

El Rel Trmico
La sobrecarga es la falla mas comn en las mquinas. La sobrecarga crea un aumento de la corriente que pasa a la carga y produce un calentamiento peligroso de la misma. La sobrecarga puede afectar los materiales de aislamiento y as mismo el tiempo de vida del motor.

LRD Relay
El rel esta compuesto de 3 elementos bimetalicos, cada uno rodeado de una bobina que lleva su corriente de fase. Cuando la corriente se incrementa o disminuye , estos materiales tendrn una deformacin, equivalente a la corriente que esta pasando por ellos hacia la carga.
Schneider Electric - Fundamentos de Arranque Motor Mayo 2009 11

Arranque Motor Combinado


En 1983, Telemecanique lanzo el primer equipo capaz de interrumpir , maniobrar y proteger trmica y magnticamente: EL INTEGRAL Este tipo de producto ofrece todas las protecciones del motor en un solo producto. Ofrece COORDINACION TOTAL: No hay soldadura de los contactos despus de una falla por cortocircuito, reduciendo el tiempo de parada y por ende el de mantenimiento. El arrancador TeSys U ofrece la capacidad de comunicacin integrada con buses de campo y mucha modularidad.
Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

Integral

TeSys U
12

Distribucin de bajo voltaje


Asla el equipo del suministro elctrico Interrumpe la corriente por el equipo Protege la vida humana y los daos Materiales causados por los C.C Protege al motor de las corrientes de sobrecarga ON / OFF Cargas

Isolation Disconnection Short circuit protection Overload protection Switching


Motor

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

13

Distribucin de bajo voltaje


Switch Disconnector TeSys VARIO

Isolation Disconnection Short circuit protection Overload protection Switching


Motor

IEC 60 947-3

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

14

Distribucin de bajo voltaje


Motor Circuit Breakers TeSys GV

Isolation Disconnection Short circuit protection Overload protection Switching


Motor

IEC 60 947- 2

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

15

Distribucin de bajo voltaje

Isolation Disconnection Short circuit protection Overload protection Switching


Motor

Contactors TeSys K TeSys D TeSys F Bar Contactors

IEC 60 947- 4 -1
Schneider Electric - Fundamentos de Arranque Motor Mayo 2009 16

Distribucin de bajo voltaje


Motor Starters TeSys U Isolation Disconnection Short circuit protection Overload protection Switching
Motor

Power

Control

IEC 60 947- 6
Schneider Electric - Fundamentos de Arranque Motor Mayo 2009 17

Arranque Motor
Fuse Switch On-load switch switch disconnector Contactor Thermal relay Magnetic circ. brkr. Therm. magnetic circ. brkr. Starter controller

Vario Isolation On-load switch Short-circuit protection Overload protection Control

GS1

LC1D

LRD

GV2P

GV2ME

TeSys U

Manual control

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

18

Teoria arranque motor


Voltaje de arranque
FULL LOAD TORQUE (%)

200 150 100 50 0

500 400 300 200 100 0

La corriente gradualmente baja como consecuencia del aumento de la velocidad del motor. La carga del motor afecta slo el tiempo tomado para la aceleracin.
Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

100 90 80 70 60 50 40 30 20 10

SLIP (%)

19

CURRENT (%)

La corriente se eleva al instante a niveles de LRC (la corriente de Rotor Cerrada) . Esto causa una corriente transitoria, que puede tener efectos indeseables sobre el suministro.

300 250

700 600

Arranque D.O.L*
Corriente disponible Arranque = 100% Pico de corriente arranque = 4 to 8 In Pico de torque en arranque = 0.6 to 1.5Tn Ventajas:
Arranque simple Bajo costo Alto torque en el arranque

Aplicaciones Tpicas: Pequeas Mquinas.

Desventajas :
Alta corriente de arranque y torque El suministro de energa debe aguantar el pico de corriente. Duro arranque mecnico.
Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

* Direct On Line
20

Arranque Motor Asincrono D.O.L.*


La solucin mas frecuentemente usada. La solucin mas econmica y simple. No es plano el arranque (no elevadores, escaleras..) Alta corriente de Arranque (5 to 8x In). El nico mtodo de arranque que no reduce el torque. (excepto con variador de velocidad.

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

21

Arranque Motor Asincrono D.O.L.*

Control and Protection during starting phase

Rated Torque Load torque maximum zone during starting phase

Load torque maximum zone during running phase

Control and Protection during running phase

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

22

Estrella-Triangulo - Arranque
Corriente disponible arranque = 33% Pico de corriente arranque = 1.3 to 2.6 In Pico torque arranque: = 0.2 to 0.5 Tn

Ventajas :
Arranque Simple y econmico. Buen torque de arranque y corriente.

Aplicaciones Tpicas:
Mquina que arrancan sin carga (pequeas bombas centrfugas, ventiladores etc.)

Desventajas :
Bajo torque de arranque. No se pueden ajustar parmetros en el arranque. La perdida de suministro en el motor produce una corriente transitoria mxima severa.
Schneider Electric - Fundamentos de Arranque Motor Mayo 2009 23

Teoria Arranque Motor


Es necesario cambiar esta transicin y tambin proteger el motor y la instalacin

Star-Delta
insuficiente para acelerar esta carga en configuracin de estrella
FULL LOAD TORQUE (%)

Momento de rotacin

300 250 200 150

700 600 500 400 300

Desventajas: - No ajuste en arranque. El cambio de estrella a


triangulo causa corrientes dainas y trasientes de torque.

100 50 0

200 100 0

100 90

80

70

60

50

40

30

20

10

SLIP (%)

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

24

CURRENT (%)

Teoria arranque motor


El motor al principio es conectado en la configuracin de estrella y luego, despus de un tiempo predeterminado, el motor es desconectado del suministro y conectado de nuevo en la configuracin delta. La corriente y el momento de rotacin en la configuracin de estrella son un tercio de la corriente de voltaje y el torque cuando el motor es conectado en la configuracin delta.

Main Contactor Thermal Overload Motor 3~

Delta Contactor

Star Contactor

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

25

Arranque motor asncrono Star - Delta


Is: DOL start current Is/3: start current under star connection Ts: DOL start torque Ts/3: start torque under star connection Tr: resistive torque (load)
Star

I(A) T (Nm)

Is

Is/3 Ts/3

Ts

Tr
Delta

n (rpm)

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

26

Arranque Motor asncrono Star - Delta


Corriente pico limitada a (1.3 to 1.6x In) Motor especifico para la aplicacin. Maquinas que presenten bajo torque en el arranque.
Ventiladores, compresores, maquinas herramientas.

Corrientes transitorias en el cambio de estrella a triangulo.


Si la temporizacin en estrella es muy corta, se vuelve un arranque directo. Si el torque resistente es mas alto en el cambio de estrella el motor se parara.
Schneider Electric - Fundamentos de Arranque Motor Mayo 2009 27

Tcnica
La coordinacin de protecciones para las soluciones arranque motor

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

28

Tcnica: Coordinacin de Protecciones


Efectos de un Corto-Circuito
Efectos electrodinmicos de corriente cresta : repulsin de los contactos. propagacin de arcos elctricos ruptura de los materiales aislantes, deformacin de piezas Efectos trmicos l2t : fusin de los contactos generacin de arcos elctricos calcinacin de los materiales aislantes

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

29

Repulsin de contactos:
Comportamiento del contactor bajo el efecto de corrientes de cortocircuito no limitadas

Tiempo

Tiempo

Tiempo

Repulsin de los contactos provocada por la energa generada por el corto-circuito

La energa debida al cortocircuito aumenta, el arco se vuelve importante

Los contactos en plata entran en fusin y se sueldan

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

30

Repulsin de contactos:
Comportamiento del contactor bajo el efecto de corrientes de cortocircuito limitadas
Courant Icc

Tiempo

Tiempo

Tiempo

Inicio de la repulsin de los contactos bajo el efecto del cortocircuito


Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

La energa debida al cortocircuito es limitada, la repulsin es anulada

Los contactos quedan operacionales


31

Definicin
Pruebas de la aparamenta elctrica en condiciones extremas. La coordinacin es definida segn el estado de los productos despus de la prueba.

Ausencia de coordinacin
Los riesgos son importantes para el operador, los daos fsicos y materiales pueden serlo igualmente.

Coordinacin tipo 1
Ningn riesgo para el operario. Es la solucin estndar ms utilizada. Antes de rearrancar, la revisin del arranque puede hacerse necesaria.

Coordinacin tipo 2
Es una solucin de alto desempeo. Se admite una ligera soldadura de los polos del contactor si son fcilmente separables.

Coordinacin total Continuidad de servicio


Es la solucin de ms alto desempeo. Rearranque inmediato sin precauciones particulares.
Schneider Electric - Fundamentos de Arranque Motor Mayo 2009 32

Coordinacin total, continuidad de servicio


Aparatos que responden a todas las funciones del Arrancador Motor segn la norma IEC947-6-2 (TeSys U)
Seguridad de las personas y de las instalaciones Ningn dao, ningn riesgo de soldadura El aislamiento elctrico se debe mantener Despus del despeje de la falla, el arrancador-motor debe estar en capacidad de rearrancar inmediatamente.

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

33

El contactor y el arranque motor


Coordinacin con dispositivo de proteccin contra los corto circuitos (DPCC)
Temps

Capacidad de cierre del contactor Pc selon IEC 947-4 DPCC

Lmite trmico del rel de sobrecarga sin dao Arranque


Icc presumido (kA)

Courant

Sobrecarga normal

Somme des Idt 10

Rel de sobrecarga

Arranque motor correctamente combinado

TeSys U
1 Base potencia 32A 2 Base potencia 12A

Rotor bloqueado

Corto-circuito
34

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

Tcnica: Las clases de disparo


Definicin
La clase de disparo define la duracin del disparo a 7,2 Ir. La seleccin se efecta en funcin de la aplicacin instalada.

Clase 10A 2 < Tp <= 10s Clase 10 Clase 20 Clase 30 4 < Tp <= 10s 6 < Tp <= 20s 2 < Tp <= 30s

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

35

Principales fallas de motor

10% 5%

12% Over Load

18%

10%

Moisture Contamination Aging Single Phasing Bearing

10% 35%

Miscellaneous

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

36

Make the most of your energy

Schneider Electric - Fundamentos de Arranque Motor Mayo 2009

42