Electrical distribution systems

CAS 36
Ring Main Unit

2011 Catalogue

Table of Contents

Overview General description Scope of application 36 kV distribution market leaders Top-level after sales service Environment and certification Quality Switchboard range Content of the standard unit Main characteristics Description Functional units Components Accessories Locking systems Connections Installation Civil engineering Decision diagram CAS 36 range. Standard unit and options

3 4 5 6 7 8 9 10 11 12 13 15 18 19 20 22

Overview

General description

2I + 1Q
PD0201

Schneider Electric CAS 36 type switchboards are devices with built-in SF6 breaking and insulation, of compact architecture and small size. All the switchgear and the busbar are housed in a single sealed stainless steel wraparound tank, filled with SF6 and sealed for life. Each CAS 36 switchboard includes several line and/or protection functions in a single steel case filled with SF6. Benefits of a tried and tested design: bb CAS 36 switchboard: vv Maximum safety for the operator: -- Internal arc test in accordance with the IEC 62271-200 standard -- Three-position switch for safe switching operations -- Ensures effective circuit breaking in accordance with the IEC 62271-102 standard -- There is no possibility of accessing live parts bb Insensitive to environmental conditions: vv Stainless steel tank sealed for life vv Completely enclosed fuse compartment vv Switchboard withstands temporary flooding bb Manufactured in accordance with best standards and quality approaches: vv Certified by various electricity utilities of several countries vv Design and production are ISO 9001 certified vv Applying best international quality practices vv Benefits of more than 60 years' accumulated experience in the manufacture of medium-voltage switchboards bb Environmentally friendly: vv Manufacturing accredited in accordance with the ISO 14001 standard bb Plug & Play installation vv Its compact design reduces work in the field to a minimum vv Levelling and coupling of different switchboards are avoided vv Easy mounting with four anchoring points vv Ease of connector installation vv Fast commissioning.

PE0202

Fonctions

They can be line input/output (I) or transformer protection (Q) functions, all incorporated in the same steel tank: bb Line (I) functions of In = 400 or 630 A, with switch-disconnector, to switch line inputs and outputs. bb Protection (Q) functions of In = 200 A, with combined fuse switches, for transformer protection. Both the line functions and the protection functions in all cases incorporate earthing switches with making capacity (up to 50 kA peak).
DE0203

Human safety

The CAS 36 switchboard ensures human safety through: bb Locking systems to prevent faulty operations bb Locking systems to prevent access to cable and fuse compartments bb AFL and AFLR internal arc option bb Clearly defined mimic panel display bb Effective breaking bb Prevention of busbar access bb Voltage presence indicating systems.

Overview

Scope of application

CAS 36 switchboards bring together in a single steel case all the medium voltage functions that allow network switching, as well as the connection, power supply and protection of distribution transformers. Each CAS 36 type compact unit, with SF6 insulation (busbars) is the basic device for MV switching and protection, within MV/LV transformer centres and MV distribution centres, for applications requiring high availability and minimal maintenance. This is confirmed by more than 12,000 units installed and in operation worldwide.

Substation
DD0202T

Overview

36 kV distribution market leaders


World leaders... and growing
The experience built up during more than 60 years in the design and manufacture of medium- and high-voltage switchgear and controlgear has been put to good use for the design and manufacture of the CAS 36 switchboards. Schneider Electric has supplied medium-voltage switchboards for more than 60,000 disconnection and protection functions both for electricity utility applications and for wind power applications. Our leading customers in the 36 kV distribution market include: bb Electrical utilities: IBERDROLA, ENDESA (Spain), bb EDP (Portugal), SENELEC (Senegal), STEG (Tunisia), EVN (Vietnam), EDCO (Jordan), NEC (Sudan), Australia. bb Wind power applications: GAMESA, VESTAS, ACCIONA, NORDEX, SUZLON, GENERAL ELECTRIC, etc. Benefits of the CAS 36 range bb Maximum availability: continuity of service bb Small size bb Maximum safety for personnel bb Insensitivity to the environment: SF6 insulation bb Certification: IEC bb Tried and tested quality: ISO 9001:2000 bb Environmental protection: ISO 14001:2004 bb Ease of installation bb Economy. The choice of CAS 36 switchboards guarantees installation security, endorsed by the experience of the world leader in the wind-power sector..
P106936 P106937

PE0501

UK Spain

Turkey Vietnam

PE0507

PE0502

Tunisia

PE0503

PE0504

Senegal Australia Sudan Thailand 5

PE0505

PE0506

DE57036

Overview

Top-level after sales service

bb Assistance for your projects bb Certified high-quality labour force bb Assistance for installation and commissioning bb Training bb Equipment replacement.

PE0601

Virtual instruction manual

To facilitate installation and mounting, we have created a virtual instruction manual so that our customers may train their work teams.

Courses in factory or in the transformer centre

PE60312

PE0602

Get to know the CAS 36 from its design, manufacture, handling and installation through to its maintenance where you want: bb In the factory bb In your offices bb At the switchboard installation location.

Overview

Environment and certication

Environment A strict system of materials management, established on the whole production process, ensures product traceability and no polluting element emissions.

Emission-free
Schneider Electric is a company deeply committed to environmental protection. As part of this commitment, the CAS 36 switchboards have been designed to be environmentally friendly. The tanks' sealing properties enable the CAS 36 switchboards to be classified as "pressure-sealed systems" in accordance with the established definition in recommendations. All the materials used, both conductors and insulants, can be identified and separated easily. At end of life, the CAS 36 switchboards can be treated and recycled and their materials can be recovered in accordance with the requirements of European legislation on the end of life of electrical and electronic products. The environmental management system put in place by Schneider Electric has been certified in compliance with the requirements of the ISO 14001:2004 standard.

Quality
PE57356

PE57354

International regulations
Design: Certification in accordance with IEC regulations CAS 36 switchboards have been designed and certified in compliance with the following standards, some of which are in the process of being updated: bb Operating conditions and general information IEC 62271-1, IEC 62271-200 bb Disconnectors and earthing switches IEC 62271-102. Manufacture: Rigorous, systematic checks The quality system for the production and design of CAS 36 switchboards has been certified in compliance with the requirements of the ISO 9001:2000 standard.
PE57357

During the manufacturing process, in order to check quality, each CAS 36 switchboard is subjected to systematic routine checks. The results of all these checks are recorded and form part of the test certificate available for each switchboard.

DE56817

Stainless steel

83.73%

Epoxy resin Wood Copper Iron SF6 Aluminium Other

4.39% 4.24% 3.40% 2.29% 1.58% 0.20% 0.17%

Overview

Quality

PE0801

Altitude
bb Below 1000 m bb Above 1000 m and up to 1700 m, please consult us. IEC 62271-200 (AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV). bb Switch classification: PM class (metallic partition). bb Loss of service continuity: class LSC2B for switches and disconnectors. bb Internal arc classification: AFL and AFLR class, up to 20 kA 1 s (optional on request).

Switch-disconnector

IEC 60265-1 (High-voltage switches for rated voltages above 1 kV and less than 52 kV) bb Class E3/M1 vv 100 opening/closing cycles under load and 0.7 p.f. vv 1000 mechanical opening/closing cycles.

Other applications
bb Switches combined with fuses: IEC 62271-105: Alternating current switch-fuse combinations. bb Earthing switches: IEC 62271-102: Alternating current disconnectors and earthing switches.

Overview

Switchboard range

36 kV utility type compact layouts


CAS 36 (1I+1Q)
DE60644

CAS 36 (2I+1Q)

CAS 36 (2I+2Q)

CAS 36 (3I+1Q)

CAS 36 (3I)

CAS 36 (4I)

36 kV extendable type compact layouts


CAS 36 (2I+1Q-EXT) CAS 36 (1I+1Q-EXT) CAS 36 (3I+2Q) CAS 36 (1I-EXT) CAS 36 (1Q+EXT)

36 kV wind power type standardized compact layouts


CAS 36 (0I+1I+1Q) CAS 36 (0I+1Q) CAS 36 (0I+2I+1Q) CAS 36 (0IT+1Q) CAS 36 (0IDB+1Q)

Overview

Content of the standard unit

PE55611

Cladding

The hardness of the galvanized steel makes the compartment a nondeformable corrosion-resistant component. Tank The SF6 in the tank is at a pressure of 0.3 bar. It is sealed for life after filling. Routine checks are performed throughout the production process to ensure closing, and this gives it a service life of 30 years. Therefore, the CAS 36 requires no maintenance on live parts. The tank contains all the live parts. All the switchgear and controlgear is located inside, together with the busbars of the switchboard and the fuse compartment. The efficiency levels of the CAS 36 are consistent with the definition of "pressurized and sealed for life" in accordance with IEC recommendations. The strength and reliability of the CAS 36 design mean that the occurrence of failures in the switching equipment is unlikely. However, in order to ensure human safety, the CAS 36 is manufactured to withstand an internal arc having the power of a 16 kA short circuit during 1 second or 20 kA during 1 second without putting the operator in danger. The overpressure caused by an internal arc is limited by the opening of a safety valve in the lower part of the tank, without any consequence for the front part of the tank. After type tests carried out for 16 kA /1 s and 20 kA /1 s, the device is in conformance with the six criteria defined in Appendix AA of the IEC 60295 standard (IEC 62271-200).

Sealed compartment of a CAS 36 2I + 2Q switchboard

DD0403

The air-blast circuit breaker uses a blast of SF6 gas toward the region of contact union as breaking technique. This air blast occurs only as a result of the very high-speed movement of the switch inside the gas tank, without supplying additional SF6.

10

Overview

Main characteristics

DD0301

Electrical characteristics
CAS 36 kV Rated voltage Test voltage of short duration (1 min.) at 50 Hz Rated lightning impulse withstand voltage (1.2/50 s) Height (A) Rated current of busbars Rated line output current (I) Rated protection output current (Q) Permissible current of short duration (1 s rms value) Breaking capacity of switch-disconnectors (I or Q) Rated making capacity in short circuit Mechanical endurance of switch-disconnectors Width (B) Depth (C) Temperature of working environment Insulation medium Nominal relative gas pressure General degree of protection Gas tank degree of protection General degree of protection against impacts 36 kV 70 kV rms 170 kV peak 400 A / 630 A 400 A / 630 A 200 A (1) 16/20 kA rated 400 A / 630 A 40/50 kA peak 1000 switching operations -15 C / +40 C SF6 0.3 bar IP-3X (as per UNE-EN 60529) IP-67 (as per UNE-EN 60529) IK-08 International IEC 60298 (62271-200) IEC 60129 (62271-102) IEC 60265-1 IEC 60694 (62271-1) IEC 60420 (62271-105) Height A (mm) 1705 1705 1850 2100 1850 1705 1705 1705 1705 1705 1705 1705 1705 1705 1705 1705 Width B (mm) 1050 1200 1050 1200 1200 1700 600 925 1600 600 600 1100 1100 650 650 650 Depth C (mm) 1050 1050 1025 1050 1025 1050 1050 1050 1050 1050 1285 1050 1050 1050 1050 1050 Weight (kg) 500 600 450 600 500 850 400 400 800 400 400 500 400 400 400 400

Regulations
Standard MV cubicles Disconnectors Switches Stipulations Switch-fuse combination

Dimensions and weight


400/630 type cubicle CAS 36 2I+1Q CAS 36 2I+2Q CAS 36 3I CAS 36 3I+1Q CAS 36 4I CAS 36 3I+2Q CAS 36 0I+1T+1Q CAS 36 0IT+1Q CAS 36 0I+2I+1Q CAS 36 1I+1Q CAS 36 0IDB+1Q CAS 36 0I+1Q CAS 36 2I+1Q EXT CAS 36 1I+1Q EXT CAS 36 1I EXT CAS 36 1Q EXT

(1) The permissible protective device output current will always be limited by the rating of the fuse installed on the cubicle.

11

Overview

Description

2I + 1Q
PD0201

Compact architecture
14

4 11 12 6 5

CAS 36 switchboards are small devices manufactured in quantities from 1 unit up to 4 functional units. This single-piece unit with integral insulation comprises: bb All the switchgear and the busbar housed in a single sealed stainless steel wrap-around tank, filled with SF6 and sealed for life. bb From one to four line compartments with connection interfaces for both the network and the transformer. bb One or two fuse compartments. The efficiency levels of the CAS 36 are consistent with the definition of "pressurized and sealed for life" in accordance with IEC recommendations. Switch-disconnector The electric arc is turned off using the SF6 air blast technique. The picture shows a cross section of the CAS 36 2I+Q in which several compartments and functions can be seen: bb Function (I) located in the lower part of the CAS 36. For functions for more than 2 lines, the third and fourth (3I & 4I) will be located at the top. bb Function (Q) located in the upper part of the CAS 36. Each I or Q function is equipped with a moving contact and two fixed contacts, one for closing the switch and the other for earthing.

PE55633

13 9 1 4 12 11 6 2 5 3

8 7 10

1 Sealed stainless steel tank filled with SF6 2 Electrolytic copper bars 3 3-position air-blast circuit breakers 4 Fuse compartment 5 Controls compartment 6 Actuation panel and mimic panel 7 Line connectors compartment 8 Screw-on line connectors (I) 9 Plug-in protective connectors (Q) 10 Safety valve (internal arc) 11 SF6 pressure indicator 12 Voltage presence detector, VPIS 13 Low-voltage compartment (optional)

12

Functional units

Components

Controls compartment
PE1302

Actuation panel

It is provided with a mimic diagram on which the various positions of the moving equipment can be viewed. Here are located the various grooves in which must be inserted the operating lever to actuate the switches and earthing switches. It also contains the push buttons which act on the mechanisms operating the protective switches (Q).

Controls compartment

This is the location of the mechanisms which transmit the operations to the various switches and earthing switches. Line functions (I) bb Switch function: closing and opening by means of a lever (or optional power system independent of the operator's force). bb Earthing switch function: closing and opening by lever. Protection function (Q) bb Switch function: closing by means of a lever independent of the operator's force. During the closing operation, energy is accumulated for opening. Opening independent of the operator's force by means of a push button, a tripping coil or fuse blowing. bb Earthing switch function: closing and opening by lever. This function cannot be power-operated.

Cable connection compartments


PE1402

Cable connection compartments (line functions)

They are separate for each function (I) and receive the three cable glands to which should be connected each of the 3 set screw connectors for each line. Access to each of these compartments is locked with earthing of the corresponding line switch-disconnector (I). As an additional safety measure, each line of each function has voltage presence detectors.

bb A front closing panel bb Cable fastening clamps bb Cable earth connection bb Integral locking which prevents access to the connection compartment when the earthing switch is open. bb Integral locking which prevents access to the switch when the panel of the connection compartment is open. Options: bb Back of compartment for single-pole or three-pole cable (compulsory for non-directional field connections) bb Internal arc in line function up to 20 kA / 1 s bb IP-3X closing on cables bb Base.

Standard equipment of the cable compartment

13

Functional units

Components

Fuse replacement operation


PE1501

Fuse compartments

Each compartment contains three separate fuse holders, single-pole and plug-in, which facilitate fuse replacement in the event of fuse blowing. The separate fuse holders are completely sealed and the fuse compartments are therefore floodable. In the case of the CAS 36, this compartment is fully immersed in the SF6 compartment, also forming part of the tank in which the rest of the switchgear and busbars are housed. Opening of the access door is locked by earthing of the corresponding protective switch-disconnector (Q), which earths the two ends of each of the three fuses.

CF fuses: Basic characteristics and selection table Fusarc CF fuse range


PE60313

The fuses to be installed shall be in compliance with the UNE-EN 60282-1 recommendation. It is recommended to use CF fuses provided with a Schneider Electric thermal striker (in accordance with DIN regulations), due to the low losses through heat dissipation. The following table shows the type of Fusarc CF fuse to use for each mains voltage and for the power of the transformer to be protected. In the event of overloads of 20% and/or ambient temperatures 40C, please consult us. For the use of fuses of another type or from another manufacturer, please consult us.

Choice of Fusarc CF fuses in CAS 36 for protection of transformers


In accordance with the IEC 60076-5:2000 standard: Ucc (S 630 kVA) = 4% Ucc (S > 630 kVA and 1250 = 5% Ucc (S > 1250 kVA) = 6% Permissible overloads of 20% and ambient temperature of < 40C.
Un (kV) S (kVA)

6 6.6 10 11 13.2 13.8 15 20 22 25 30 33

25
12/6.3 12/6.3 12/6.3 12/4 24/4 24/4 24/4

50
12/16 12/16 12/10 12/10 24/6.3 24/6.3 24/6.3 24/6.3 24/4 36/4 36/4 36/4

75
12/25 12/20 12/16 12/16 24/10 24/10 24/10 24/6.3 24/6.3 36/6.3 36/6.3 36/4

100
12/25 12/25 12/20 12/20 24/16 24/16 24/16 24/10 24/10 36/6.3 36/6.3 36/6.3

125
12/31.5 12/31.5 12/25 12/20 24/20 24/20 24/16 24/10 24/10 36/10 36/6.3 36/6.3

160
12/40 12/31.5 12/25 12/25 24/25 24/20 24/20 24/16 24/16 36/10 36/10 36/10

200
12/40 12/40 12/31.5 12/31.5 24/25 24/25 24/25 24/20 24/20 36/16 36/16 36/10

250
12/50 12/50 12/40 12/31.5 24/31.5 24/31.5 24/25 24/25 24/20 36/20 36/16 36/16

315
12/63 12/50 12/40 12/40 24/31.5 24/31.5 24/31.5 24/25 24/25 36/25 36/20 36/20

400
12/80 12/50 12/50 24/40 24/40 24/40 24/31.5 24/31.5 36/25 36/25 36/25

500

630

800

1000

1250

12/80 (2) 12/100(1) 12/100(2) 12/63 12/63 24/50 24/50 24/40 24/31.5 24/31.5 36/31.5 36/25 36/25 12/80 12/80 24/63 24/63 24/50 24/40 24/40 36/40 36/31.5 36/31.5

12/100(1) 12/80 (1) 24/63 (1) 24/63 (1) 24/63 (2) 24/50 24/40 36/40 36/31.5 36/31.5 24/63

24/50 (2) 24/63 (1) 36/50 (1) 36/63 (1) 36/40 36/40 36/50 (1) 36/50 (1)

(1) No permissible overload. (2) Permissible overloads < 10%..

Replacing fuses
DD0603

45

d 6

When the elimination of a fault involves the blowing of one (or two) fuses, often the properties of the fuses which apparently remain intact are in fact weakened by the action of the short circuit. Returning them to service in these circumstances would entail a high risk of unwanted fuse blowing for very slight overcurrents. It is therefore recommended to replace the 3 fuses in accordance with the IEC 60282-1 standard. Product range Fusarc Rating (Amp)
6.3-10-16-20-25 31.5-40 50-63-80-100 6.3-10-16-20-25 31.5-40 50-63-80 100 6.3-10-16-20 25 31.5-40 50-63

33 e

33 23

e (mm)
292 292 292 442 442 442 442 537 537 537 537

d (mm)
50.5 50.5 76 50.5 50.5 76 86 50.5 50.5 76 86

Weight (kg)
1.2 1.2 3.2 1.7 1.7 4.5 5.7 1.9 1.9 5.4 6.5

CF-12 CF-12 CF-12 CF-24 CF-24 CF-24 CF-24 CF-36 CF-36

* To use 12 kV or 24 kV CF fuses you must buy adapters designed specially for the CAS 36.

CF-36 CF-36

14

Functional units

Accessories

Low-voltage compartment
PE60314

Remote indications

Moreover, to be able to perform satisfactory remote control of the MV switchgear, it is necessary to have in the control centre all the required information on the status of the equipment to be remote controlled: Switch-disconnector position (I or Q) On any of the switch-disconnectors, both line (I) and protection (Q), auxiliary contacts (2NO + 2NC) can be incorporated for remote indication of the position of the switch-disconnector and the earthing switch. Voltage presence by line function (I) For each line function (I), a relay can be incorporated with local indication of voltage presence on each phase and an auxiliary contact for remote indication. Earth fault passage by line function (I) For each line function (I), a relay can be incorporated with combined with a toroidal sensor with local indication of earth fault passage and an auxiliary contact for remote indication.

Voltage presence indicating system


PE1603

Voltage presence indicating system

There is a voltage indicator device in each function (protection line) which makes it possible to check whether or not voltage is present on the wires.

Phase concordance unit


PE56825

Phase concordance unit

This unit is used to check phase concordance. It can be connected to any voltage indicator.

Tripping coils

Base
DD0803

Together with each protection switch-disconnector (Q), we can supply shunt tripping coils, 220 Vac, / 50/60 Hz, breaking consumption: 8 A (peak value). Switching time 70/80 ms. Other working voltages: 24 Vdc, 48 Vdc and 110 Vdc.

Base

The base (optional) increases the height (C) by 400 mm.

Front case

The front case DB (optional), for housing double terminals or surge arresters, increases the depth (C) by 250 mm.

Indication of fuse blowing

On option, the CAS 36 has in its protection function a contact which indicates blowing of one of its fuses. It can be a mechanical or electrical indication.

DE57990FR

Antiseismic guarantee

CAS 36 has passed antiseismic tests in accordance with the ETGI-1020 tests of Ingendesa (Chile) and UNE-EN 60068-3-3.

15

Functional units

Accessories

T200I
PE1702

Motor pack

In the switch control unit is a space reserved for the gear motor which can be installed in factory, but which the customer can also install on the site, with the busbar or the cable energized and without dismounting the control unit. bb A set of electrical locking systems prevents faulty operations. With the motor pack, the CAS 36 fits in perfectly with a remote control system. bb Only the line functions (I) can be motorized.

Easergy T200I: An interface designed for monitoring MV networks

Easergy T200I is a "plug and play" device or a multifunction device which takes into account all needs for supervision and remote monitoring of a CAS 36. bb Acquisition of various types of information: switch position, fault detection, real current values. bb Transmission of opening/closing orders for the switch. bb Exchange of information with the control centres. Essential during power cuts on the network. Easergy T200I has tried and tested reliability and availability and is capable of ensuring operation of the switch at all times. It is easy to configure and operate.

PE1703

PE1704

bb Easergy T200I is designed to be connected to a MV switch without any type of special converter. bb It plays a front-end monitoring role for local operations. It can be used to actuate electrical mechanisms (local/remote switch) and displays information concerning the switch's status. bb It has an integrated fault detection system for MV networks (overcurrent and zero sequence) with detection of set point values which can be configured channel by channel (current value and fault current).
Local information and control Monitoring and control

Functional unit designed for MV networks

16

Functional units

Accessories

Flair 21D and 21DT


PE56820

Fault passage indicator

The new version of the Flair 21D, Flair 22D and Flair 23DV devices of the Easergy range has a highly visible flashing LED and provides detailed information via the digital display. An external lamp (optional) can indicate the passage of a fault current without any need to enter the substation.. Functions bb Phase-to-phase and phase-to-earth fault indication bb Display of settings bb Display of phase at fault bb Display of the load current and the peak current and frequency bb Combination of fault current passage indication and voltage detection functions (Flair 23DV only). Ease of use and reliability bb Automatic settings on site bb Fault indication by LED or external lamp bb The lifetime of the Flair 22D battery is 15 years bb Fault detection is more precise if the Flair 22D is connected to a VPIS-VO voltage indicator bb Mounting on RM6 possible in factory or else on site bb Adaptation on site can be facilitated by using a split toroid, without having to dismount the MV cables.

61021N

Characteristics
Easergy Flair 21D - 22D - 23DV
PE57783 PE57784

Flair 21D Fault detection Earth fault Phase fault Fault acknowledgement with voltage indication (VPIS-VO) Voltage detection Voltage presence/absence b b 4 digits b b b 1A 10 % b 20 to 160 A 200 to 800 A

Flair 22D 20 to 160 A 200 to 800 A b

Flair 23DV 20 to 160 A 200 to 800 A b

b b 4 digits b b b b 1A 10 % b b (Lithium battery) 2A b b b

b b b 4 digits b b b b 1A 10 % b b (external)(*)

21D
PE57785

22D

Settings Automatic settings Manual settings Display Display Load current Peak current Frequency Phase at fault Current resolution Precision Power supply Self-powering Dual power supply: Other Minimum operating load current External lamp Reset SCADA output 2A b b b 0A b b b

23DV

(*) 12-48 Vdc Thanks to a lithium battery, the Flair 22D can be configured without load current (display of settings, reset time delay > 4 h)

17

Functional units

Locking systems

Mechanical locking by bolt


PE1801

Mechanical locking by bolt

Between protection function (Q), transformer and low voltage:


Missing key Free key Captive key

Line function locking systems


1

CAS-CAS (1 and 2) 2 1 Cross locking between two lines of CAS switchboard (switch of one line with the earthing switch of another line and vice versa); these lines may belong to the same switchboard or another switchboard.

Mechanical locking by key (optional)


P106935

Line switching (3) Locking which prevents two switches of two lines of the same switchboard from being closed at the same time. Free key, switch open. Free key, earthing switch open (4) Locking system which allows the key to be removed when the disconnector of the 533.943.295.407 - (R2) CAS/CAS 533.943.395.018 - (R7/C1 - E21) line earthing switch is closed. 533.943.295.418 - (R2) CAS/SM6 (1 and 2) (3) (4)
Free key, earthing switch closed
533.943.395.205

Free key, switch open Free key, earthing switch open


DD1801

Free key, switch open manual line switching)

1 1

1 1

1 2 1
1

1
1 2

533.943.295.407 - (R2) CAS/CAS 533.943.295.418 - (R2) CAS/SM6

533.943.395.018 - (R7/C1 - E21)

533.943.295.407 533.943.395.205- (R2) CAS/CAS 533.943.295.418 - (R2) CAS/SM6

51098379M0 + 533.943.395.018 533.943.395.018 533.943.395.306 - (R7/C1 - E21) (R8 / C4 - E24)

533.943.295.429 533.943.395.205 51098379M0 (R6) 533.943.295.407 - (R2) CAS/CAS 533.943.295.418 - (R2) CAS/SM6

533.943.395.029 533.943.395.306

533.943.395.018 - (R7/C

Protection function locking systems


(5)
Free key, earthing switch closed
DD1801

(6)
Free key, earthing switch open

Free key, earthing switch open Free key, earthing switch closed

(7)

1
1 1

1
1

51098379M0 + 533.943.395.018 (R8 / C4 - E24) 533.943.295.407 533.943.395.018 - (R2) (R7/C1 CAS/CAS - E21) 533.943.295.418 - (R2) CAS/SM6

533.943.295.429 533.943.395.205 533.943.395.018 - (R7/C1 - E21)

51098379M0 533.943.395.029 + 533.943.395.018 (R8 / C4 - E24) 533.943.395.205 533.943.395.306

533.943.295.429 533.943.395.117 533.943.395.306 51098379M0 (R6)

533.943.395.029 533.943.395.106 + 533.943.395.018 51098379M0 (R6) (R8 / C4 - E24)

533.943.395.117 533.943.295.429

S 6

18
1 1

Functional units

Connections

Connector for the protection function


PE1303

Connection cable glands


PE1401

bb The sections, contacts and dimensions of the CAS 36 connection cable glands are those defined by the UNE-EN 50181 standard. bb 100% of epoxy resin cable glands are subjected to industrial frequency dielectric tests and partial discharge tests. The cable glands convey the current between the outside and inside of the case filled with SF6 gas and ensure insulation between the live conductors and frame earth. There are two types of cable glands, which are defined by their permissible rated current of short duration: bb Type B: 400 A, 16 kA 1 s and 40 kA peak (plug-in) for protection function. bb Type C: 400-630 A, 20 kA 1 s and 50 kA peak (M16 screw-on) for line function.

General

Connection cable glands depend on specific criteria: Installation: bb Amperage of connected equipment: 400, 630 A bb Permissible rated current of short duration in the switch function bb Minimum length of phase expansion bb Type of plug-in connector: vv Plug-in: contact finger vv Screw-on: threaded connection bb Plug-in output connector: straight, elbow, Tee. Installation: bb Rated voltage of: vv the cable vv the network bb Type of conductor: vv Aluminium vv Copper bb Cross section in mm2 bb With insulant bb Cable composition: vv Single-pole vv Three-pole bb Type of insulator: vv Dry vv Impregnated paper (non-migrating) bb Type of screen bb Frame.

How to define connection cable glands

Table of connectors (CAS 400 A/16 kA)


Brand Cable gland CAS 36 functions Description of plug-in connector Elbow connector 400 A - 15 kA "T" connector M16 400 A - 28 kA Elbow connector 400 A - 36 kV "T" connector M16 630 A M16 630 A - 20 kA Line (I) Screw-on 400 A - 12.5 kA Protection (Q) Plug-in M400LR M400TB PMA-4/400/36 PMA-5/400/36AC Cable type 1-pole dry Cross sections 35-240 mm2 18/30 kV 35-240 mm2 18/30 kV 25-240 mm2 18/30 kV 25-240 mm2 18/30 kV

EUROMOLD (with screen) PRYSMIAN (with screen)

Table of connectors (CAS 630 A/20 kA)


Brand Bushings CAS 36 functions Description of plug-in connector Elbow connector 400 A - 15 kA "T" connector M16 630 A - 28 kA Elbow connector 400 A - 36 kV "T" connector M16 630 A M16 630 A - 20 kA Line (I) Screw-on 400 A - 12.5 kA Protection (Q) Plug-in M400LR M440TB PMA-4/400/36 PMA-5/400/36AC Cable type 1-pole dry Cross sections 35-240 mm2 18/30 kV 400-630 mm2 18/30 kV 25-240 mm2 18/30 kV 25-240 mm2 18/30 kV 19

EUROMOLD (with screen) PRYSMIAN (with screen)

Installation

Civil engineering

CAS 36
PE2001

Cable channel 25
PE2002

400

50 50 20

400

Cable channel

Dimensions A, B and C (min. 100 mm) as per the criterion: radius of curvature = 15 times total cable diameter. (*) Cable with 18/30 kV solid insulation in accordance with the IEC standard.

30

540

(Min. 100 mm)

Switchboard type CAS 36 2I+1Q CAS 36 2I+2Q CAS 36 3I CAS 36 3I+1Q CAS 36 4I CAS 36 1I CAS 36 0I+1Q CAS 36 3I+2Q CAS 36 0I-T+1Q CAS 36 0I+1I+1Q CAS 36 0I+2I+1Q

Dimension A (mm) 1050 1200 1050 1200 1200 600 600 1700 600 925 1600

50 30

20

Dimension B (mm) 1005 1005 980 1005 980 980 1005 1005 1005 1005 1005

Dimension C (mm) 100 100 100 100 100 100 100 100 100 100 100

CAS 36 2I+1Q
PE55643

A
PE55644

The cable fasteners can be placed at various levels.

Dimensions A, B and C (minimum 100 mm) in accordance with the following criterion: the radius of curvature shall be 15 times the total cable diameter. (*) Cable with 18/30 kV solid insulation in according with the IEC standard.

Cross section (mm2) 50 70 95 120 150 185 240

Cable exit position Dimension A (mm) 100 100 130 150 180 220 260

Dimension B (mm) 100 100 130 150 180 220 260

Dimension C (mm) 100 110 120 125 130 140 155

20

Installation

Civil works

CAS 36 2I+2Q
A
PE55643 PE55646

Dimensions A, B and C (minimum 100 mm) in accordance with the following criterion: The radius of curvature shall be 15 times the total cable diameter. (*) Cable with 18/30 kV solid insulation in accordance with the IEC standard.

Cross section (mm2) 50 70 95 120 150 185 240

Cable exit position Dimension A (mm) 100 100 130 150 180 220 260

Dimension B (mm) 100 110 120 125 130 140 155

Dimension C (mm) 100 110 120 125 130 140 155

CAS 36 3I
PE55641 PE55642

Dimensions A, B and C (minimum 100 mm) in accordance with the following criterion: The radius of curvature shall be 15 times the total cable diameter. (*) Cable with 18/30 kV solid insulation in accordance with the IEC standard.

Cross section (mm2) 50 70 95 120 150 185 240

Cable exit position Dimension A (mm) 320 350 380 400 425 460 500

Dimension B (mm) 320 350 380 400 425 460 500

Dimension C (mm) 570 600 630 650 675 710 750

21

Decision Diagram
Order No. Date Delivery time Country

CAS 36 range Standard unit and options


An

should be marked or the desired value filled in only once for each horizontal line.

The green boxes

entail no extra cost. Quantity

Configuration of the standard switchboard


fill in from right to left)

Basic configuration (one function per box,


Example 0I+1I+1Q V

function 0I

1st

function I

2nd

function Q

3rd

function

4th

< 6 kV 6-10 kV 10 - 20 kV 20 - 33 kV

Working voltage of the device

400 A - 16 kA / 40 kA 630 A - 20 kA / 50 kA 50 Hz 60 Hz

Rated current Current of short duration (1s) / peak current Rated frequency
( )

Service altitude

< 1000 m > 1000 m (up to 1700 m)

Remote operation for line function (motor pack) Includes motor pack and 48 Vdc auxiliary contacts Switches, 2 NO - 2 NC and ISO Earth, 2 NO - 2 NC Auxiliary contacts (fill in only where applicable and if the line motor pack option is not chosen) Switches, 2 NO - 2 NC and ISO Earth, 2 NO - 2 NC Fault passage detectors Flair 21D Flair 21DT Flair 22D Flair 23D

Line options [except 0I (T)]

48 V dc 125 V dc

Short-circuit current setting 3 x tor. 3 x tor.

200 A 600 A 2 x tor.+ hom.. 2 x tor.+ hom..

400 A 800 A 1 x hom.

Auxiliary contacts Switches, 2 NO - 2 NC and earthing switch 2 NO - 2 NC Switch, 2 NO - 2 NC Tripping coil Indication of fuse blowing Mechanical indication Mechanical + electrical indication (*) Please consult us

Options of the Protection function

50 Hz 110 V dc

60 Hz 48 V dc

220 V ac 24 V dc

22

Decision Diagram

CAS 36 range Standard unit and options


An

should be marked or the desired value filled in only once for each horizontal line.

The green boxes

entail no extra cost. Quantity

Configuration of the standard switchboard


fill in from right to left)

Basic configuration ((one function per box,


Example V

function 0I

1st

function I

2nd

function Q

3rd

function

4th

Access to lower front cables compartment Possible only with ISO Earth, line function, closed Access to fuse compartment Possible only with earthing switch, protection function, closed Key locking (look up available functions) For lines 1I (except 0I) INCOMPATIBLE WITH POWER OPERATION OF THE LINE (1*) Type R2 (CAS-CAS) free key, open switch. (2*) Type R2 (CAS-SM6) free key, open earthing switch. (3*) (CAS-CAS) manual switching of the 2 lines (4*) (CAS) (earthing switch closed, free key) For protective devices (5*) R7-C1-E21 (earthing switch closed, free key) (6*) R6 (earthing switch open, free key) (7*) R8-C4-E24 (R7-C1-E21+R6)

Locking options

always provided by default always provided by default

Double terminal case (possibility of double connector or surge arrester Possible only for lower front cable compartments) Protection against internal arc 20 kA 1s (lateral function 0I not included. Not compatible with double connector option) AFL AFLR IP3X closing (Possible only for lower front cable compartments) Option with seismic resistance Packaging type Land Maritime Maritime with crate

Other options

Fusarc CF MV fuses MV fuses Fusarc CF

Accessories

Fuse adapter

H = 400 mm rating (kV/A) rating (kV/A) rating (kV/A) 12 kV (292 mm) 24 kV (442 mm)

Quantity Quantity Quantity Quantity Quantity

* See drawings on page 18

23

Schneider Electric Industries SAS


35, rue Joseph Monier CS 30323 F- 92506 Rueil Malmaison Cedex RCS Nanterre 954 503 439 Capital social 896 313 776 www.schneider-electric.com

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Printed on ecological paper Publishing: Schneider Electric Design-Layout: Schneider Electric Printing: Altavia Connexion - made in France

AMTED304013EN