SiPass Entro MP6.0, SR35i, RF30 and RF9 Import/export function When using the import- and export functions of SiPass Entro MP6.0 there are some limitations/restrictions. Second free field of the cardholder isnt supported. If personal codes without cards are used, these codes are not supported by the import- and export tool. Please note that personal codes used with cards are supported. If extra cards for cardholders are used, the extra cards are not supported by the import- and export tool. In SiPass Entro Lite, theres a possibility to have cardholder names with up to 50 characters, while SiPass Entro only stores 32 characters/cardholder. This results in a loss of cardholder when importing a cardholder with more than 32 characters in the name. To overcome this, please reformat cardholders with long names before importing to SiPass Entro. Upgrade path, SiPass Entro Lite-> SiPass Entro SiPass Entro provides an upgrade path for SiPass Entro Lite. When running such set-up, there are certain restrictions/limitations Relay with connectors 6, 7 and 8 on the PCB of the DC800 In SiPass Entro, the duress function is managed by the IOR-6. Therefore a reconfiguration is needed to keep functionality. Warning-, Alert- and temporary alarm by-pass functionality is not supported on the DC800 by SiPass Entro MP6.0 RED LED When using RED LED to indicate locked door, the LEDs of the readers connected to DC800's are not affected. Wiegand support in SiPass Entro The SiPass Entro door controllers supports readers providing either 26 bit or 32 bit Wiegand interfaces, the most commonly used OEM formats available. Most of the 26 bit or 32 bit data formats contain in addition to the card number, data
uiding 1echnoogies Known limilalions and bugs Fire Saely & Securily Producls Date: 2009-01-14
Authors: Siemens 8uilding Technologies. Fire Saely & Securily Producls Lnglundavgen 7, 171 41 Solna, Sweden Name: Jan-Lrik Jones and Per Nordn 1e.: +46 (0)730 25 74 40, +46 (0)730 25 74 83 Page: 2 | 4
relating to site code (or facility code), parity bits and in some formats card issue state. The physical timing of data transferred on the interface also varies between different readers.
The SiPass Entro system supports these two formats by interpreting the card data received as a single number (26 or 32 bits) rather than in the format as defined for the associated cards. That means, for the 26 Bit Wiegand interface, that the parity bits are used as a part of the card number and that no parity checking is done.
A result of this is that a card number printed on the card is very unlikely to be the same number as interpreted by SiPass Entro when connecting the reader to the system.
The most convenient way to enter a correct card number in this case is to use the Enrolment reader USB-RIF (First released version of USB-RIF(July 05) was just supporting 26bit Wiegand + Clock & Data). Or, as an option, you could double click on the event Unknown card in the event log after using the card at one of the systems readers. In SiPass Entro MP5.0 or later, this will open the New person tab, and allow you to enter the necessary parameters.
PIN entry is supported by means of 8 bit burst Wiegand data. Keys 0-9 are transmitted as hex-values 0-9. Keys A/B (or */# on some readers) are used as commands within Entro and are transmitted as hex values A and B. Any key press retrieved with a value higher than B (hex) is ignored by the DC12/22.
For 26-bit usage the number of digits in card number needs to be set to 8, and for 32 bit usage, the setting has to be 10.
uiding 1echnoogies Known limilalions and bugs Fire Saely & Securily Producls Date: 2009-01-14
Authors: Siemens 8uilding Technologies. Fire Saely & Securily Producls Lnglundavgen 7, 171 41 Solna, Sweden Name: Jan-Lrik Jones and Per Nordn 1e.: +46 (0)730 25 74 40, +46 (0)730 25 74 83 Page: 3 | 4
Settings for 26 bit format 32-bit format
Its also worth knowing that no consideration is taken to the setting for the starting position in the card reading parameter section.
It is therefore very important to verify that specific Wiegand readers (and cards) can be supported by the SiPass Entro system before advising a customer accordingly.
RF30EM RED LED When using RED LED to indicate closed door, the RED LED on RF30EM will lit for 1-2 minutes after user interaction (key press, card read or wake-up by PIR) and then be turned off. Save batteries. RF30EM and alarm control Recommend not to use RF30EM with ASF. Due do timing issues related to the ASF function (the alarm status feedback send to RF30EM might be missed by RF30EM due to timing/time). Pre-warning indication on RF30EM only on user interaction (key press, card read or wake-up by PIR).
uiding 1echnoogies Known limilalions and bugs Fire Saely & Securily Producls Date: 2009-01-14
Authors: Siemens 8uilding Technologies. Fire Saely & Securily Producls Lnglundavgen 7, 171 41 Solna, Sweden Name: Jan-Lrik Jones and Per Nordn 1e.: +46 (0)730 25 74 40, +46 (0)730 25 74 83 Page: 4 | 4
Alarm set indication, RED LED lit, only on user interaction (key press, card read or wake-up by PIR). Save batteries. RF30EM and access granted in Entro If bad communication between SR35i and RF30EM, possible to get Access granted in Entro even log without unlocking the door on RF30EM. RF9 test mode Not allowed to have more the one RF9 in test mode at same time. If so the RF9s can stop sending information and need to by restart. RF9 address collision In some situation during installation it is possible to set two RF9 with same address without any warning indication from the RF9. To prevent this from happen make sure that the number of RF9 in the system is the same as number of RF9 shown in Entro - System information. If not one RF9 will be lost next time the system restarts. RF9 strength indication on start up During the first 30 seconds after start up the RF9 is shown the signal strength. If not and signal strength indication is needed, restart the RF9 or use Test mode. RF30EM manual changes/errors Chapter: Present Administrator code is not known. This chapter is not relevant any more. Chapter: Erase memory. In English manual it says that old cards/codes should remain witch is wrong, it should say old cars/codes will be erased after erasing the memory. Changing radio channels If radio channel is manual changed in SR35i the channel is stored in the memory even after erasing the memory.