Project Order No. Contract No. Substation:

ELECTRICITY AUTHORITY OF CYPRUS HEAD OFFICE


Format

OUTDOOR SUBSTATIONS
EAC 445/2003
Responsible department

EAC 445/2003
Prepared

Doc. kind: Technical Description Title:

16.11.2004
Approved

KFi

GDE
Take over department Derived from

Project Design Rules & Guidelines


Lang.

KAL
Revision

en
Scale Doc.No. Ref. design. Rev. DCC

EAA ABB Utilities GmbH


Sh./No.sh.

1HDC900037-0001
Function: Location:

A = +

A1 / 20

Revisions A No 16.11.2004 02.11.2004 KFi Date KFi

Date:

02.11.2004 KFi KAL KAL

Client Doc No:

Client:

Project name:

Prepared: Checked :

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

PROJECT DESIGN RULES & GUIDELINES COVER PAGE


Lang: en Resp.Dept: GDE DCC:

Sheet: Cont:

A1
A2

Name Approved:

P101104016

EAC 445/2003

1HDC900037-0001

EAA

REVISION INDEX
A REVISION _ A DATE 12.11.2004 16.11.2004 NAME KFi KFi FIRST ISSUE First issue revised A

DESCRIPTION

C
P101104016 900037

We reserve all rights in this document and the information contained therein.Reproduction,

use or disclosure to third parties without express authority is strictly forbidden.

F
Revisions Date: KFi 02.11.2004 KFi KAL KAL
Client Doc No: Client: Project name:

16.11.2004

Prepared: Checked :

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

PROJECT DESIGN RULES & GUIDELINES REVISION INDEX


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + A2
B1

Sheet: Cont:

No

Date

Name Approved:

P101104016

EAC 445/2003

1HDC900037-0001

EAA

TABLE OF CONTENTS
A FUNCTION /LOCATION PAGE
A1 A2 B1 D1 D2

DESCRIPTION
PROJECT DESIGN RULES & GUIDELINES COVER PAGE PROJECT DESIGN RULES & GUIDELINES REVISION INDEX PROJECT DESIGN RULES & GUIDELINES Table of contents IDENTIFICATION CODES FOR EQUIPMENT DESCRIPTION IDENTIFICATION CODES FOR EQUIPMENT DESCRIPTION IDENTIFICATION CODES FOR EQUIPMENT DESCRIPTION IDENTIFICATION CODES FOR EQUIPMENT DESCRIPTION IDENTIFICATION CODES FOR EQUIPMENT DESCRIPTION ANSI FUNCTION NUMBERS DESCRIPTION Document type Sheet Numbering SYMBOL OVERVIEW FOR SINGLE LINE DIAGRAMS SYMBOL OVERVIEW SYMBOL OVERVIEW FOR CIRCUIT DIAGRAMS TRANSFORMERS,MOTORS,GENERATORS SYMBOL OVERVIEW FOR CIRCUIT DIAGRAMS CONTACTORS,RELAYS,CONTACTS SYMBOL OVERVIEW FOR CIRCUIT DIAGRAMS CONTROL SWITCHES SYMBOL OVERVIEW FOR CIRCUIT DIAGRAMS LAMPS.RESISTORS,DIODES,CAPACITORS,INSTRUMENTS SYMBOL OVERVIEW FOR CIRCUIT DIAGRAMS FUSES,MCBS,CIRCUIT-BREAKERS,DISCONNECTORS SYMBOL OVERVIEW FOR INSTALLATION DRAWINGS EL. DEVICES,LAMPS,SWITCHES,OUTLETS SYMBOL OVERVIEW FOR LOGIC DRAWINGS SYMBOL OVERVIEW Internal Wiring Cable types & Cross sections Internal Wiring Cable types & Cross sections

DCC
EAA EAA EAB EDB EDB EDB EDB EDB EDB EDB EFA EFA EFA EFA EFA EFA EFA EFA EDB EDB

STATUS
PREVIOUS CURRENT

FUNCTION /LOCATION

PAGE

DESCRIPTION

DCC

STATUS
PREVIOUS CURRENT

A A A

D3 D4 D5 D6 D7 E1 E2

A A A

C
P101104016 900037

E3 E4 E5 E6 E7 E8 W1 X1

We reserve all rights in this document and the information contained therein.Reproduction,

use or disclosure to third parties without express authority is strictly forbidden.

NOTE:THE SYMBOL "*" IN COLUMN "STATUS"S MEANS NEW PAGE

F
Revisions Date: KFi 02.11.2004 KFi KAL KAL
Client Doc No: Client: Project name:

16.11.2004

Prepared: Checked :

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

PROJECT DESIGN RULES & GUIDELINES Table of contents


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + B1
D1

Sheet: Cont:

No

Date

Name Approved:

P101104016

EAC 445/2003

1HDC900037-0001

EAB

A THE IDENTIFICATION CODE FOR ELECTRICAL EQUIPMENT IS LAID DOWN IN DIN REGULATION 40719 HARMONIZED WITH IEC PUBLICATION 61346. THIS STANDARD CONTAINS THE RULES FOR COMPLETE IDENTIFICATION CODES FOR ELECTRICAL EQUIPMENTS. ACCORDING TO THESE AN ITEM IS IDENTIFIED BY A NUMBER OF DESIGNATION BLOCKS SEPARATED FROM EACH BY MATHEMATIC SYMBOLS B

N:a numerical data position A:an alfabetic data position

=
C
P101104016 900037

HIGH LEVEL DESIGNATION

LOCATION

DEVICE

TERMINAL DESIGNATION
C

=
D

NAANN
prefix sign numbering of systems

+ +: N: A: NN:

NAANN

-: N: A: NNN:

NANNN
prefix sign numbering of systems Kind Number

11
D

=: N:
We reserve all rights in this document and the information contained therein.Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

prefix sign numbering of systems Voltage level,higher order facilities Subdivision of these units

A: A: NN:

Voltage level,higher order facilities A: Subdivision of these Switchbays,units

example: =
Revisions Date:

1NE00
02.11.2004 KFi KAL KAL
Client Doc No:

+
Client:

N01
Project name:

Item Des: Doc Kind: Doc.No :

K01

11
F
Function: Location:

Prepared: Checked : No Date Name Approved:

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Contract No:

IDENTIFICATION CODES FOR EQUIPMENT DESCRIPTION


Lang: en Resp.Dept: GDE DCC:

= + D1
D2

Sheet: Cont:

P101104016

EAC 445/2003

1HDC900037-0001

EDB

High Level Designation block

NAANN Rated voltage of plant

Designation block

NAANN Rated voltage of plant


< 1kV AC 500V to 1000V AC 500V to 1000V AC 500V to 1000V not used AC 400/230V AC 400/230V AC 400/230V AC 400/230V not used DC 220/110V DC 220/110V DC 220/110V DC 220/110V not used DC 60/48V DC 60/48V DC 60/48V not used DC 24/12V DC 24/12V DC 24/12V not used

Letter Code
=A
B

Letter Code
=N = NA = NB = NC = ND = NE = NF = NG = NH = NJ = NK = NL = NM = NN = NP = NQ = NR = NS = NT = NU = NV = NW = NX,NY,NZ

objects related to two or more classes of infrastructure objects classes B to Z

=B =C =D =E =F =G
P101104016 900037

> 420kV 380kV - < 420kV 220kV - < 380kV 110kV - < 220kV 60kV - < 110kV 45kV - < 60kV 30kV - < 45kV 20kV - < 30kV 10kV - < 20kV 5kV - < 10kV 1kV - < 5kV < 1kV objects for equipotential bonding not used not used not used Facilities for transformers Facilities for control,signalling&aux.equipment not used Facilities for control rooms Central facilities e.g.process computers,alarm systems Facilities for telecomunications & information tasks
Objects for housing or enclosing technical systems or installations like areas & buildings
Date: 02.11.2004 KFi KAL KAL
Client Doc No: Client: Project name:

=H =J =K =L =M

=N =P =Q
We reserve all rights in this document and the information contained therein.Reproduction,

=R
use or disclosure to third parties without express authority is strictly forbidden.

=S =T =U =V =W =X =Y =Z
Revisions Prepared: Checked :

F
OUTDOOR SUBSTATIONS Item Des: Doc Kind: Doc.No :

ABB SA

EAC
Order No:

Contract No:

IDENTIFICATION CODES FOR EQUIPMENT DESCRIPTION


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + D2
D3

Sheet: Cont:

No

Date

Name Approved:

P101104016

EAC 445/2003

1HDC900037-0001

EDB

Location Designation block

NAANN Rated voltage of plant


objects related to two or more classes of infrastructure objects classes B to Z

Designation block

NAANN Rated voltage of plant


Circuit breaker accessories Multiply,reposition,decouple Instrument transformer accessories Compressed air,hydraulics not used not used not used not used automatic,closed loop control not used Simulating network,voltage selection measurement system devices recorder metering Protection Syncronizing Transformers Auxiliaries Main,secondary busbars Display,operation,supervision alarm system not used not used note *1:usually not used note *2:usually used for Objects for administrative or social purposes
Function: Location:

Letter Code
+A
B

Letter Code
A B C D E F G H J K L M N P Q R S T U V W X Y Z
Project name:

+B +C +D +E +F +G
P101104016 900037

> 420kV 380kV - < 420kV 220kV - < 380kV 110kV - < 220kV 60kV - < 110kV 45kV - < 60kV 30kV - < 45kV 20kV - < 30kV 10kV - < 20kV 5kV - < 10kV 1kV - < 5kV < 1kV not used not used Cubicles for protective devices *1 Cubicles decentralized *1 Cubicles for transformers Cubicles for for control,signalling&aux.systems marshalling cubicles control room board *2 Cubicles for central facilities e.g.process computers,alarm systems Cubicles for telecomunications not used
Date: KFi 02.11.2004 KFi KAL KAL
Client Doc No: Client:

+H +J +K +L +M

+N +P +Q
We reserve all rights in this document and the information contained therein.Reproduction,

+R
use or disclosure to third parties without express authority is strictly forbidden.

+S +T +U +V +W +X +Y +Z
Revisions 16.11.2004 Prepared: Checked :

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

IDENTIFICATION CODES FOR EQUIPMENT DESCRIPTION


Lang: en Resp.Dept: GDE DCC:

= + D3
D4

Sheet: Cont:

No

Date

Name Approved:

P101104016

EAC 445/2003

1HDC900037-0001

EDB

Device Design.block
A

NANN Kind of item

Note:table according to IEC 61346-2


A

Letter Code -A -B
B

Examples for typical electrical products


Buchholz relay,protective relay, detector,measuring element,relay, transformer,shunt),photo cell,pilot switch, position switch,sensor, video camera,_ buffer, battery, capacitor, recorder, hard disk,memory,RAM boiler, lamp, heater, laser, radiator cathodic protection, anode, fuse, miniature circuit breaker, surge diverter, thermal overload relay C

Two or more purposes(this class is only for objects for which no main purpose can be identified) converting an in variable (physical property,condition or event)into signal for further processing) storing of material, energy reserved for future standardization providing radiant or thermal energy protecting directly (selfacting) a flow of energy,signals, personel or equipment from dangerous or unwanted conditions including: systems and equipment for protective purposes

-C -D -E

C
P101104016 900037

-F -G -H -J

Initiating a flow of energy or material Generating signals used as information carriers or reference Dry cell battery,dynamo, fuel cell,generator,solar cell source Producing a new kind of energy, material or product Reserved for future standardization Reserved for future standardization Processing (receiving,treating and providing)signals or information (excluding objects for protective purposes, see class F) All-or-nothing relay,Analogue integrated circuit,Automatic paralleling device,Binary integrated circuit,Contactor relay, D CPU, delay element,electronic valve, electronic tube,feedback controller, filter,microprocessor, process computer, programmable controller, synchronizing device, time relay,transistor Actuator,actuator coil,electric motor, linear motor ammeter,voltmeter,indicator,display unit,signal lamp,bell,loudspeaker,printer,led,recorder,clock,counter Circuit breaker, contactor (for power),disconnector, fuse switch, motor starter,power transistor, slip-ring, thyristor Diode, inductor, limiter, resistor F

-K

We reserve all rights in this document and the information contained therein.Reproduction,

-L
use or disclosure to third parties without express authority is strictly forbidden.

Reserved for future standardization Providing mechanical energy (rotational or linearmechanical motion) for driving purposes Reserved for future standardization Presenting information Controlled switching or varying a flow of energy,of signals or of material Restricting or stabilizing motion or a flow of energy,information or material

-M -N -P -Q -R

Revisions A 16.11.2004 KFi

Date:

02.11.2004 KFi KAL KAL

Client Doc No:

Client:

Project name:

Prepared: Checked :

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

IDENTIFICATION CODES FOR EQUIPMENT DESCRIPTION


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + D4
D5

Sheet: Cont:

No

Date

Name Approved:

P101104016

EAC 445/2003

1HDC900037-0001

EDB

Device Design.block
A

NANN Kind of item

Note:table according to IEC 61346-2


A

Letter Code -S -T
B

Examples for typical electrical products


Control switch, discrepancy switch, keyboard,light pen, mouse, push-button,selector switch, set-point adjuster AC/DC converter, amplifier, antenna,demodulator, frequency changer, measuringtransducer/transmitter, transformer, rectifier, signal converter/transformer, transducer, telephone set B Insulator Filter Busbar, cable, conductor, information bus, optical fibre, through bushing, Connector, plug connector, terminal, C

Converting a manual operation into a signal for further processing Conversion of energy maintaining the kind of energy Conversion of an established signal maintaining the content of informationConversion of the form orshape of a material Keeping objects in a defined position Processing (treating) of material or products (including preparatory andpost-treatment) Guiding or transporting energy, signals, materialor products from oneplace to another Connecting objects Reserved for future standardization

-U -V -W
C
P101104016 900037

-X -Y -Z

Reserved for future standardization

We reserve all rights in this document and the information contained therein.Reproduction,

use or disclosure to third parties without express authority is strictly forbidden.

F
Revisions Date: KFi 02.11.2004 KFi KAL KAL
Client Doc No: Client: Project name:

16.11.2004

Prepared: Checked :

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

IDENTIFICATION CODES FOR EQUIPMENT DESCRIPTION


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + D5
D6

Sheet: Cont:

No

Date

Name Approved:

P101104016

EAC 445/2003

1HDC900037-0001

EDB

ANSI Function Numbers


A

ANSI/IEEE (C37.2))Device Numbers Protective relays are generally referred to by standard device numbers. For example, a time overcurrent relay is designated a 51 device, while an instantaneous overcurrent is a 50 device. Multifunction relays have combinations of device numbers. A 27/59 device, for example, is a combination under/over voltage relay. Letters can be added to clarify application (87T for transformer differential, 59G for ground overvoltage).

CODE 24 25 25A 27 27N 32 37 40 46


C
P101104016 900037

DESCRIPTION
OVEREXCITATION RELAY - Functions with time delay (inverse, step or definite time) for overexcitation conditions as evidenced by Volts/Hertz. SYNC-CHECK RELAY - Functions when two ac circuits are within desired limits of frequency, phase angle and voltage to permit the paralleling of these two circuits. AUTOMATIC SYNCHRONIZING RELAY - Acts to bring two ac circuits within desired limits of frequency, phase angle and voltage, then initiates the paralleling of these two circuits. UNDERVOLTAGE RELAY - Functions on a given value of undervoltage. GROUND FAULT UNDERVOLTAGE RELAY - Functions on a given value of third harmonic undervoltage. POWER RELAY - Functions on a desired value of power flow in a given direction. UNDERCURRENT RELAY - Functions on a given value of undercurrent. LOSS OF FIELD RELAY - Functions on a given value of dc field current. PHASE BALANCE CURRENT RELAY - Functions on a given degree of unbalance between the polyphase currents. NEGATIVE SEQUENCE OVERCURRENT - Functions when the polyphase currents contain negative sequence components above a given value. PHASE SEQUENCE VOLTAGE RELAY - Functions on a given value of polyphase voltage in the desired phase sequence. NEGATIVE SEQUENCE VOLTAGE RELAY - Functions on a given value of the negative sequence component of the polyphase voltage. THERMAL RELAY - Functions when the temperature of a machine, transformer or other load-carrying winding exceeds a given value. INSTANTANEOUS OVERCURRENT RELAY - Functions without intentional time delay when the current exceeds a given value. BREAKER FAILURE RELAY - Functions when current continues to flow after the monitored breaker should have interrupted a fault. TIME OVERCURRENT RELAY - Functions with a definite or inverse time characteristic when the current exceeds a given value. VOLTAGE CONTROLLED TIME OVERCURRENT RELAY - A time overcurrent relay whose pickup is adjusted by an undervoltage function. VOLTAGE RESTRAINED TIME OVERCURRENT RELAY - A time overcurrent relay whose pickup is adjusted by an undervoltage function. OVERVOLTAGE RELAY - Functions as a given value of overvoltage. GROUND FAULT OVERVOLTAGE RELAY - Functions on a given value of Overvoltage at the fundamental frequency. VOLTAGE BALANCE RELAY - Functions on a quantitative voltage difference between two circuits. AC DIRECTIONAL OVERCURRENT RELAY - Functions on a desired value of ac overcurrent flowing in a predetermined direction. AC RECLOSING RELAY - Controls the automatic reclosing and locking out of an ac circuit interrupter. FREQUENCY RELAY - Functions on a predetermined value of requency (either under or over or on normal system frequency) or rate of change of frequency. LOCKOUT RELAY - A hand or electrically reset auxiliary relay that is operated upon the occurence of abnormal conditions to maintain associated equipment or devices inoperative until it is reset. DIFFERENTIAL PROTECTIVE RELAY - Functions on a percentage or phase angle or other quantitative difference of two currents or of some other electrical quantities. E D C B

46N 47 47N 49 50 50BF 51 51/27C 51/27R 59


use or disclosure to third parties without express authority is strictly forbidden.

We reserve all rights in this document and the information contained therein.Reproduction,

59N 60 67 79 81 86 87

For a complete listing, refer to ANSI/IEEE C37.2.


Revisions Date: 02.11.2004 KFi KAL KAL
Client Doc No: Client: Project name:

Prepared: Checked : No Date Name Approved:

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

ANSI FUNCTION NUMBERS DESCRIPTION


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + D6
D7

Sheet: Cont:

P101104016

EAC 445/2003

1HDC900037-0001

EDB

Page Designation A B C D E F G H I J

Document kind description Cover page/Revision Index Table of contents not used Technical description Overview diagrams-Single line diagrams Function diagrams/Flowcharts/Signal Lists not used not used not used not used Connection Diagrams Arrangement Drawings not used not used not used Part Lists/Label list not used not used not used not used not used not used Cable list/Cable connection table

Document kind Code EAA EAB EDB EFA EFF/EFB/EFP

C
P101104016 900037

K L M N O P

EFS ELU

EPB
D

Q R
We reserve all rights in this document and the information contained therein.Reproduction,

S
use or disclosure to third parties without express authority is strictly forbidden.

T U V W X Y Z

EMB EMA NOTE these page designations are use for combined documents mostly documents for panel and systems. The criterion is the kind of document described in the specific page.

Terminal overview table/Terminal connection table not used not used

Revisions A 16.11.2004 KFi

Date:

02.11.2004 KFi KAL KAL

Client Doc No:

Client:

Project name:

Prepared: Checked :

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

Document type Sheet Numbering


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + D7
E1

Sheet: Cont:

No

Date

Name Approved:

P101104016

EAC 445/2003

1HDC900037-0001

EDB

A
ROTARY SWITCH DISCONNECTOR CAPACITOR VOLTAGE DEVICE POWER TRANSFORMER 3-PHASE TRANSFORMER WITH SCREEN CAPACITOR VOLTAGE DEVICE WITH CT

AMMETER

DISCONNECTOR (ISOLATOR)

V B

VOLTMETER

FUSE DISCONNECTOR

CIRCUIT BREAKER (CB)

var

B
VARMETER TRANSFORMER WITH VARIABLE COUPLING RESIDUAL-CURRENT OPERATED CB 3-PHASE TRANSFORMERC WITH 3 WINDINGS

GENERATOR

cos

POWER FACTOR METER

Hz C
P101104016 900037

FREQUENCY METER FUSE SWITCH DISCONNECTOR

CURRENT TRANSFORMER

VOLTAGE TRANSFORMER

M ~3 M ~1

3-PHASE INDUCTION MOTOR SQUIRREL CAGE

WATTMETER

CURRENT T/F WITH 2 SECONDARY WINDINGS ON ONE CORE

VOLTAGE TRANSFORMER WITH 3 WINDINGS

1-PHASE INDUCTION MOTOR SQUIRREL CAGE

CURRENT T/F WITH 2 CORES AND 2 SECONDARY WINDINGS

CAPACITOR BANK

We reserve all rights in this document and the information contained therein.Reproduction,

use or disclosure to third parties without express authority is strictly forbidden.

F
Revisions Date: 02.11.2004 KFi KAL KAL
Client Doc No: Client: Project name:

Prepared: Checked : No Date Name Approved:

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

SYMBOL OVERVIEW FOR SINGLE LINE DIAGRAMS SYMBOL OVERVIEW


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + E1
E2

Sheet: Cont:

P101104016

EAC 445/2003

1HDC900037-0001

EFA

CURRENT TRANSFORMER(CT)

1-PHASE T/F WITH SHIELDING

3-PHASE T/F CONNECTION DELTA-STAR

DC MOTOR

TACHO GENERATOR

M ~1

1-PHASE AC MOTOR

B
3-PHASE T/F WITH SHIELDING CONNECTION STAR-STAR U1 V1 W1 3-PHASE MOTOR 3 TERMINALS PE

U1

W1

PE 3PHASE MOTOR WITH PTC THERMISTOR

CT WITH 2 SECONDARY WINDINGS ON ONE CORE

3-PHASE T/F CONNECTION STAR-STAR

M ~3

M ~3
V1

C
P101104016 900037 TOROIDAL CT

3-PHASE T/F WITH SHIELDING CONNECTION DELTA-STAR

U1

V1

W1

PE

C
3-PHASE INDUCTION MOTOR WITH WOUND ROTOR

M ~3
K L M

CT WITH INTERMIDIATE TAP

We reserve all rights in this document and the information contained therein.Reproduction,

use or disclosure to third parties without express authority is strictly forbidden.

2-PHASE POWER TRANSFORMER

VOLTAGE TRANSFORMER(VT)

T/F WITH CENTRE TAP

VT WITH 2 SECONDARY WINDINGS

2-PHASE T/F WITH 3 SECONDARY WINDINGS

F
Revisions Date: 02.11.2004 KFi KAL KAL
Client Doc No: Client: Project name:

Prepared: Checked : No Date Name Approved:

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

SYMBOL OVERVIEW FOR CIRCUIT DIAGRAMS TRANSFORMERS,MOTORS,GENERATORS


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + E2
E3

Sheet: Cont:

P101104016

EAC 445/2003

1HDC900037-0001

EFA

A
MAKE CONTACT NORMALLY OPEN WIPE CONTACT TO THE RIGHT BREAK CONTACT CHANGEOVER CONTACT RELAY COIL RELAY COIL OF AN AC RELAY

MAKE CONTACT EARLY CLOSE

13

K?

14

NORMALLY OPEN WIPE CONTACT TO THE LEFT

BREAK CONTACT LATE TO OPEN MAKE CONTACT DELAYED WHEN OPENING

CHANGEOVER CONTACT DELAYED WHEN CLOSING TO THE RIGHT

RELAY COIL OF A SLOW OPERATING RELAY

RELAY COIL OF A MULTIFUNCTIONAL RELAY

WIPE CONTACT RIGHT LEFT

A1 CHANGEOVER CONTACT FOR TEST SWITCH

K?

A2

C
P101104016 900037

BREAK CONTACT DELAYED WHEN CLOSING MAKE CONTACT DELAYED WHEN CLOSING BREAK CONTACT DELAYED WHEN OPENING NORMALLY OPENED THERMAL CONTACT NORMALLY CLOSED THERMAL CONTACT

RELAY COIL OF A SLOW RELEASING RELAY

RELAY COIL OF A PULSE RELAY

CHANGEOVER CONTACT DELAYED WHEN CLOSING TO THE LEFT

RELAY COIL OF A SLOW RELEASING & SLOW OPERATING RELAY

RELAY COIL OF AN REMANENCE RELAY

D
MAKE POWER CONTACT

We reserve all rights in this document and the information contained therein.Reproduction,

BREAK POWER CONTACT


use or disclosure to third parties without express authority is strictly forbidden.

POSITION SWITCH/ LIMIT SWITCH MAKE CONTACT POSITION SWITCH/ LIMIT SWITCH BREAK CONTACT

F
Revisions Date: 02.11.2004 KFi KAL KAL
Client Doc No: Client: Project name:

Prepared: Checked : No Date Name Approved:

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

SYMBOL OVERVIEW FOR CIRCUIT DIAGRAMS CONTACTORS,RELAYS,CONTACTS


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + E3
E4

Sheet: Cont:

P101104016

EAC 445/2003

1HDC900037-0001

EFA

NO

NC
GENERAL SWITCH

NO

NC
EMERGENCY SWITCH MUSHROOM-HEAD SAFETY FEATURE

NO
13

NC
11

S?

14

S?

FLOW SWITCH 12

PUSHBUTTON

KEY SWITCH NON AUTOMATIC RETURN

S?

CAM SWITCH

TURN SWITCH NON AUTOMATIC RETURN

KEY SWITCH

FLOAT SWITCH

C
P101104016 900037 RETAINED HANDLE PEDAL SWITCH NON RETAINED HANDLE

C P P
PRESSURE SWITCH

PUSHBUTTON NON AUTOMATIC RETURN

MOTOR OPERATION DEVICE

THERMOSTAT

We reserve all rights in this document and the information contained therein.Reproduction,

LIMIT SWITCH OPERATED BY ROLLER


use or disclosure to third parties without express authority is strictly forbidden.

MECHANICAL OPERATION DEVICE

SWITCH OPERATED BY STORED MECHANICAL ENERGY

F
Revisions Date: 02.11.2004 KFi KAL KAL
Client Doc No: Client: Project name:

Prepared: Checked : No Date Name Approved:

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

SYMBOL OVERVIEW FOR CIRCUIT DIAGRAMS CONTROL SWITCHES


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + E4
E5

Sheet: Cont:

P101104016

EAC 445/2003

1HDC900037-0001

EFA

A
LAMP SIGNAL LAMP PTC RESISTOR SIREN

VOLTMETER

RESISTOR

BATTERY

FIELD WINDING

SIGNAL LAMP FLASHING TYPE

HORN

NTC RESISTOR AMMETER


V

VARISTOR

FILTER

IRON CORED REACTOR

BEACON

BELL

THERMOCOUPLE WATTMETER VARIABLE RESISTOR ENCODER

EARTING

C
P101104016 900037 LAMP WITH BUILT IN TRANSFORMER

C n
TACHOMETER THYRISTOR PHASE ANGLE METER HEATER ELEMENT CAPACITOR

GALVANOMETER

cos

POWER FACTOR METER

POTENTIOMETER`

DIODE

MEASURING BRIDGE

We reserve all rights in this document and the information contained therein.Reproduction,

SYNCHRONOSCOPE LED
use or disclosure to third parties without express authority is strictly forbidden.

Hz

FREQUENCY METER

LIGHT-DEPENDENT RESISTOR

TRIAC

INDICATOR ELECTROMECHANICAL /ANNUNCIATOR ELEMENT

SHUNT THERMOMETER COUNTER

ZENER DIODE

CLOCK

Wh

Wh-METER

OPERATION TIME COUNTER

RC ELEMENT

PHOTOELECTRIC CELL

F
Revisions Date: 02.11.2004 KFi KAL KAL
Client Doc No: Client: Project name:

Prepared: Checked : No Date Name Approved:

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

SYMBOL OVERVIEW FOR CIRCUIT DIAGRAMS LAMPS.RESISTORS,DIODES,CAPACITORS,INSTRUMENTS


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + E5
E6

Sheet: Cont:

P101104016

EAC 445/2003

1HDC900037-0001

EFA

A
CIRCUIT BREAKER (CB) FUSE

MINIATURE CIRCUIT BREAKER

DISCONNECTOR(ISOLATOR)

RETAINED HANDLE FUSE DISCONNECTOR NON RETAINED HANDLE RESIDUAL-CURRENT OPERATED CB

C
P101104016 900037 ROTARY SWITCH DISCONNECTOR FUSE SWITCH DISCONNECTOR

C M
MOTOR OPERATION DEVICE

ON LOAD BREAK SWITCH

MECHANICAL OPERATION DEVICE

We reserve all rights in this document and the information contained therein.Reproduction,

I>
use or disclosure to third parties without express authority is strictly forbidden.

I>

I>

THERMOMAGNETIC RELEASE

U>

OVERVOLTAGE RELEASE

LIGHTNING ARRESTER

EARTHING
U<

UNDERVOLTAGE RELEASE

F
Revisions Date: 02.11.2004 KFi KAL KAL
Client Doc No: Client: Project name:

Prepared: Checked : No Date Name Approved:

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

SYMBOL OVERVIEW FOR CIRCUIT DIAGRAMS FUSES,MCBS,CIRCUIT-BREAKERS,DISCONNECTORS


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + E6
E7

Sheet: Cont:

P101104016

EAC 445/2003

1HDC900037-0001

EFA

A
SWITCH SELF-CONTAINED EMERGENCY LIGHTING LUMINAIRE EMERGENCY LIGHTING LUMINAIRE ON SPECIAL CIRCUIT

* * * ** B * **

AIR CONDITIONER

FIRE ALARM

FREEZER

1-POLE SWITCH WITH PILOT LIGHT

FIRE DETECTOR

B
REFRIDGERATOR 1-POLE SWITCH 2-POLE SWITCH TIME CLOCK LIGHTING OUTLET POSITION MANUALLY OPERATED CLOCK FOR TIME CARDS FLOOD LIGHT

WATER FREEZER

C
P101104016 900037 WATER HEATER

1-POLE TWO WAY SWITCH

CLOCK

SPOT LIGHT

=
PROJECTOR

FAN

PUSHBUTTON

D
TELECOMMUNICATIONS OUTLET
We reserve all rights in this document and the information contained therein.Reproduction,

SOCKET OUTLET WITH PROTECTIVE CONTACT

D
PUSHBUTTON WITH PILOT LIGHT

use or disclosure to third parties without express authority is strictly forbidden.

TELEPHONE CENTRE PUSHBUTTON WITH RESTRICTED ACCSESS TELEPHONE DEVICE ELECTRIC LOCK

Lx< ANTENNA

TWILIGHT SWITCH

F
Revisions Date: 02.11.2004 KFi KAL KAL
Client Doc No: Client: Project name:

Prepared: Checked : No Date Name Approved:

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

SYMBOL OVERVIEW FOR INSTALLATION DRAWINGS EL. DEVICES,LAMPS,SWITCHES,OUTLETS


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + E7
E8

Sheet: Cont:

P101104016

EAC 445/2003

1HDC900037-0001

EFA

ABS

ABSOLUTE VALUE

DIV

DIVIDER

P P-Q Q

SUBSTRACTOR

MSR

A
MEASUREMENT ON OPERATOR STATION

ADDER

MULTIPLIER

TIMER OFF DELAY AUDIO SIGNAL ON OPERATOR STATION

B
AMPLIFIER OR GATE t 0 ON DELAY TIMER

MESSAGE ON PRINTER

C
P101104016 900037

&

DYNAMIC INPUT AND GATE PULSE

C ICON
MIMIC ON ORERATOR STATION

=
t1 t2 TIMER

XNOR GATE

1 D

XOR GATE

COM
PULSE INPUT

COMMAND BY ORERATOR STATION

=1

XOR GATE

We reserve all rights in this document and the information contained therein.Reproduction,

COMP P P<Q P=Q use or disclosure to third parties without express authority is strictly forbidden. Q P>Q

COMPERATOR

PULSE GENERATOR FLASH

SGN
SIGNAL ON ORERATOR STATION

EN

CTR
CT<0 CT=0 CT>0 CT COUNTER

E
R S Q SET RESET ELEMENT

DOWN UP CT=0 C5[LOAD] CT=C5

MSG

MESSAGE ON ORERATOR STATION

F
Revisions Date: 02.11.2004 KFi KAL KAL
Client Doc No: Client: Project name:

Prepared: Checked : No Date Name Approved:

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

SYMBOL OVERVIEW FOR LOGIC DRAWINGS SYMBOL OVERVIEW


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + E8
W1

Sheet: Cont:

P101104016

EAC 445/2003

1HDC900037-0001

EFA

INTERNAL WIRING
A Cross-section (mm-MIN) Type Colour A

Function AC distribution Protection & measuring CTs secondary circuits Protection & measuring VTs secondary circuits DC distribution Neutral connections Earthing connections

2,5 4 2,5 1,5 2,5-4 2,5

RD/YE/BU RD/YE/BU RD/YE/BU GY BK GNYE

C
P101104016 900037

We reserve all rights in this document and the information contained therein.Reproduction,

use or disclosure to third parties without express authority is strictly forbidden.

ACCORDING TO EAC SPEC:14-019 CHAPTER 3,29


Revisions Date: 02.11.2004 KFi KAL KAL
Client Doc No: Client: Project name:

Prepared: Checked : No Date Name Approved:

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

Internal Wiring Cable types & Cross sections


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + W1
X1

Sheet: Cont:

P101104016

EAC 445/2003

1HDC900037-0001

EDB

Terminal Designation
A
STRIP DESIGNATION DESCRIPTION

Terminal type

Max cross section cable

notes

-X1 -X2 -X3 -X4 B -X5A -X5V -XS -X6 -X7

AC Distribution DC distribution DC internal distribution external digital connections for analogue input (current) for analogue input (voltage) socket outlet internal connection with aux.equipment located in panel front door -ENTRELEC 4mm M4/6-ENTRELEC M4/6-ENTRELEC M4/6-ENTRELEC M4/6-ENTRELEC M4/6-ENTRELEC 4mm 4mm 4mm 4mm 4mm
subject to be changed according to CT calculations

C
P101104016 900037

We reserve all rights in this document and the information contained therein.Reproduction,

use or disclosure to third parties without express authority is strictly forbidden.

F
Revisions Date: KFi 02.11.2004 KFi KAL KAL
Client Doc No: Client: Project name:

16.11.2004

Prepared: Checked :

ABB SA

EAC
Order No:

OUTDOOR SUBSTATIONS

Item Des: Doc Kind: Doc.No :

Contract No:

Internal Wiring Cable types & Cross sections


Lang: en Resp.Dept: GDE DCC:

Function: Location:

= + X1

Sheet: Cont:

No

Date

Name Approved:

P101104016

EAC 445/2003

1HDC900037-0001

EDB