Documente Academic
Documente Profesional
Documente Cultură
September 2011
Sheet 40 001
40.0-1
Contents
Cat Generator Paralleling Switchgear Introduction General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Denitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cat Switchgear Selector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Standard and Custom Congurable Products . . . . . . . . . . . . . . . . . . . Cat Switchgear Control Technology Features. . . . . . . . . . . . . . . . . . . . XLM Switchgear General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Standard Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical DataXLM One-Line Diagrams . . . . . . . . . . . . . . . . . . . . . . Functional Sequences of Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . EGP Switchgear General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Standard Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical DataEGP One-Line Diagrams . . . . . . . . . . . . . . . . . . . . . . . Functional Sequences of Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . Medium Voltage Systems General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . XLM Medium Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EGP Medium Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Custom Systems General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical DataOne-Line Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . Specications See Eatons Product Specication Guide, available on CD or on the Web. CSI Format: . . . . . . . . . . . . . . . . . . . . . . . . . 1995 Low Voltage XLM UL 1558 Switchgear . . . . . . . . . . . . . . . . Low Voltage XLM UL 891 Switchboard . . . . . . . . . . . . . . . . Medium Voltage XLM Metal-Clad Switchgear . . . . . . . . . . . . . . Low Voltage EGP UL 1558 Switchgear . . . . . . . . . . . . . . . . Low Voltage EGP UL 891 Switchboard . . . . . . . . . . . . . . . . Medium Voltage EGP Metal-Clad Switchgear . . . . . . . . . . . . . . Section 16426E Section 16429E Section 16346E Section 16426G Section 16429G Section 16346G 2010
22 23
40.0-2 40.0-4 40.1-1 40.1-2 40.1-3 40.2-1 40.2-2 40.2-3 40.2-4 40.2-10 40.3-1 40.3-2 40.3-3 40.3-4 40.3-12 40.4-1 40.4-4 40.4-8 40.5-1 40.5-2
24 25 26 27 28 29 30 31 32 33 34 35
Section 26 23 13.11 Section 26 24 13.31 Section 26 13 26.13 Section 26 23 13.13 Section 26 24 13.33 Section 26 13 26.16
36 37 38 39 40 41 42 43
CA08104001E
September 2011
Sheet 40 002
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
Introduction
General Description
Cat Generator Paralleling Switchgear is a product developed through a joint venture between Caterpillar and Eaton Corporation. Caterpillar, an industry leader in electric generator sets, and Eaton, an industry leader in Low and Medium Voltage Switchgear have combined forces to create Cat Generator Paralleling Switchgear... the most reliable and feature rich product available in the market today! Cat Switchgear has been designed to integrate hand-in-glove with Caterpillars on-package, microprocessor-based engine control. Exclusively from your Caterpillar dealer, you can now get the markets best efciency, reliability and dependability all in one package.
Cat Switchgear combines the proven low voltage Magnum DS power circuit breaker and Magnum Switchgear with Cat Switchgear control technology. Cat controls technology is for optimal power generation and electrical distribution system performance. It provides advanced, industryleading, microprocessor-based engine generator set control provided exclusively in Cat Switchgear. Medium voltage systems combine VCP-W breakers and VacClad Metal-Clad switchgear with the same proven generator control technology.
Reliable, exible and powerful. Cat Switchgear is designed with the most critical power needs in mind:
Data center/data processing Healthcare Critical industrial/chemical processes Distributed generation/cogeneration Water/wastewater treatment Government/military Banking/credit card processing Landll gas power
Applications
Emergency/legally required standby systems Optional standby backup systems Distributed generation Peak shaving Prime power
Built-in redundancy Reliability Touchscreen interface Simple, intuitive operation Advanced communications capabilities Integrated digital technology Advanced generator control and protection Detailed engine and electrical reports Best-in-class footprint
XLM
Medium Voltage
CA08104001E
September 2011
Sheet 40 003
40.0-3
Standards
Low Voltage Cat Switchgear conforms to the following applicable standards:
22 23 24 25 26 27 28
Overview
NEMA Standard SG-5 CSA ANSI C37.20.1 ANSI C37.51 UL Standard 1558 NFPA 110, NFPA 99 and NFPA 70
The switchgear uses Magnum DS Breakers that are designed to NEMA Standard SG-3; ANSI Standards C37.13, C37.16, C37.17 and UL 1066. Optional switchboard construction is available that is built to UL Standard 891. These switchboards use Magnum SB Breakers for generator mains, utility mains and electrically operated feeders, and molded-case breakers for non-switched feeders. Medium Voltage Cat Switchgear conforms to the following applicable standards: NEMA SG-5 ANSI/IEEE C37.20.2 CSA-C22.2 No. 31-M89 EEMAC G8-3.2. NFPA 70, 99, 110
29 30 31 32 33 34 35 36
The switchgear uses VCP-W vacuum circuit breakers that are designed to meet or exceed all applicable IEEE/ANSI standards including C37.06.
37 38 39 40 41 42 43
Generator Set Control Screen
CA08104001E
September 2011
Sheet 40 004
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
Denitions
The terms and acronyms below are referenced throughout this section on Generator Paralleling Switchgear. These denitions can help the reader fully understand the topics discussed. Alternator: A device for converting mechanical energy into alternating current electrical energy. It may also be called an AC or synchronous generator. ATS: Automatic Transfer Switch. Automatic Transfer Switch: A switch designed to sense the loss of one power source and automatically transfer the load to another source of power. Closed-Transition Transfer: A transfer between sources that provides a momentary paralleling of both power sources during a transfer in either direction. This results in no interruption of power to the loads during the transfer. The closed transition transfer is only possible when the sources are properly synchronized and interfaced. DGPS Distributed Generation Power System: Typically a local engine genset and automation connected to the utility system to peak shave or export power. EGP Switchgear (Engine Generator Paralleling Switchgear): Parallels multiple engine/gensets to serve loads transferred via downstream ATS units. EGPT Switchgear: Same as EGP except with a controlled emergency generator bus tie breaker between sets of generators to segregate loads or areas of the bus. EMCP 3.S: A Caterpillar microprocessor module for switchgear control, rugged, industrially hardened, microprocessor-based synchronizer and load controller designed to work exclusively with Cat enginegenerator sets.
EMCP Electronic Modular Control Panel: A Caterpillar microprocessor module for engine/genset control. Emergency Generator Bus Tie: A bus tie breaker used in EGP type systems to segregate groups of generators and/ or loads. Emergency Generator Bus Tie breakers are used where critical loads, required to be powered in 10 seconds, exceed the capacity of a single genset. EPS Emergency Power System : The emergency power sources and emergency distribution to downstream loads. EPSS Emergency Power System Supplier: Supplier of all the components of the EPS, such as the Caterpillar dealer. Emergency Standby Power Application: Typical usage of 50 hours per year with a maximum of 200 hours per year. Generators can be applied at their Standby rating with a typical variable load factor of 70%. Emergency Tie Breaker: A feeder breaker that is used to connect an EGP type system to a separate piece of Normal (utility) switchgear. Feeder Breaker Controls: Automation controls to allow control of the distribution feeder devices for load shed/load add control and monitoring. Generator: A machine for converting mechanical energy into electrical energy. The electrical energy may be direct current (DC) or alternating current (AC). Generator Bus Tie: A bus tie used in XLM type systems for separating the generator bus and/or loads from the normal utility fed bus and/or loads. Generator Demand Priority: Controls that automatically match the online engine generator capacity to the load to avoid unnecessary engine genset operation when loads are low. (Alternatively called Load Sense Load Demand.)
Generator Tie Breaker: A feeder breaker that is used to connect an XLM type system to a separate piece of Normal (utility) switchgear. Governor: A device that regulates prime mover speed by adjusting the fuel input to maintain constant speed. HMI Human Machine Interface: Typically a touchscreen used by the operator for interfacing with the paralleling generator system. LM Switchgear (Load Management Switchgear): A single generator used in distributed generation power systems. Includes automation controls that allow for the load to be served simultaneously by both utility and generator power sources while managing how much each source contributes. Load Shed/Load Add: Automation controls to control distribution devices (turn OFF and restore ON) when only partial emergency engine gensets are available for duty. Typically accomplished by assigning Priority levels to each controlled distribution device. Master Controls: All processors, HMI and programming to implement the desired modes of operation of engine gensets in a paralleling switchgear system. NFPA 110Standard for Emergency and Standby Power Systems: Standard for the assembly, installation and performance of electrical power systems to supply critical and essential needs during outages of the primary power source. NPS Normal Power System: The utility service entrance equipment and distribution circuits to downstream loads. NPSS Normal Power System Supplier : Supplier of all the components of the NPS, such as the distribution equipment vendors authorized distributor.
CA08104001E
September 2011
Sheet 40 005
40.0-5
Paralleling: The procedure of connecting two or more generators, or other power sources, of the same phase, voltage and frequency characteristics supplying the same load. Peak Shaving: Process by which utility customers minimize peak demand utility charges or exports power to the utility grid. Prime Power Application: Prime Power is when the genset is the only power source. Processor: A specially congured logic controller with appropriate inputoutput capability and programming. SAW (Surface Acoustic Wave): A premium touchscreen sensing technology that offers maximum protection from wear or contaminants.
Station Battery: A power supply used for control of switchgear. Synchronizer: A device that will synchronize an on-coming electric generator set with the bus or another electric generator set, and allows multiple power sources to be connected in parallel. Synchroscope: An instrument that provides a visual indication of proper time for closing of the breaker when synchronizing generators to connect them in parallel with another source. TFT (Thin Film Transistor): A type of touchscreen display technology used in HMI devices that offers high levels of brightness and clarity.
Utility Protection: A collection of protective relays or a multifunction relay required by the utility to detect abnormal conditions and open the utility breaker. XLM Switchgear (Emergency Transfer [Xfer] and Load Management Switchgear): Parallels multiple engine/gensets and the utility to serve downstream loads. Typically does not include downstream ATS units. XLMT Switchgear: Same as XLM except with a controlled generator bus tie breaker between the utility bus and the engine genset bus.
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
CA08104001E
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
CA08104001E
September 2011
Sheet 40 007
40.1-1
22 23 24
Export
Peak Shaving
Standby Application
Emergency (Standby)
Transfer Switches
25
XLM product is used when generators will be paralleled with a utility (even if utility breaker is not located in the same line-up as generator breakers). Allows closed transition transfer to/from utility, continuous paralleling with utility for peak shaving or exporting.
26 27 28 29 30 31
XLM
EGP
32 33 34 35 36 37 38 39 40 41 42 43
MV
CA08104001E
September 2011
Sheet 40 008
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
EGP
EGP (Emergency Generator Paralleling) switchgear is used for paralleling multiple generators that are not directly connected to a utility source. EGP switchgear is primarily used in applications where downstream automatic transfer switches provide the switching between normal and emergency sources. This is what is typically required in medical facilities, hospitals, and water/wastewater treatment facilities when multiple generator sets are paralleled. For detailed EGP product description, specications, layouts, and so on, refer to Section 40.3.
Custom Products
Custom switchgear is available to meet the needs of the most demanding, unique or complicated system congurations. Custom engineered systems are available for special system requirements such as: custom sequences of operation, special load control requirements, multiple utility and tie combinations, unique switchgear locations or layouts, and so on. No matter how complicated or unique the system, Cat Switchgear has the power and exibility to handle it. For detailed custom product description, specications, layouts, and so on, refer to Section 40.5.
These congurations are available for both low voltage and medium voltage applications and represent the most typical paralleling switchgear congurations seen in the industry. Additionally, custom congurations are available to meet the demands of even the most unique and complicated systems.
XLM
XLM (Emergency Transfer (Xfer) and Load Management) switchgear is used when the Generators are paralleled with a normal utility (or multiple utility) power source(s). XLM switchgear allows closed transition, soft-loading and unloading from utility, and peak shaving capability where generators operate continuously in parallel with the utility. Typically, XLM switchgear eliminates the need for automatic transfer switches. Data centers, industrial process, and other critical process loads are prime candidates for XLM switchgear. For detailed XLM product description, specications, layouts, and so on, refer to Section 40.2.
CA08104001E
September 2011
Sheet 40 009
40.1-3
22 23 24
Ethernet
25 26 27
Cat Switchgear For systems with utility interconnect (XLM Type)
Modbus
ATS
28 29
Redundant Ethernet I/O
Touchscreen Processor
30 31 32 33 34
EMCP 3.S
EMCP 3.S
Redundant Hardwired Signals Emergency Start - ATS Run Request - Utility Fail "First Up Dead Bus" Logic
Figure 40.1-1. Cat Switchgear Automation ArchitectureHigh Redundancy Package Features are common to all Low and Medium Voltage congurations. Cat Switchgear uses the EMCP 3.S, an advanced, industry-leading, multifaceted, microprocessor-based generator set control designed to work exclusively with Cat enginegenerator sets. 2. Moving Master Technology. Master control functions, such as modes of operation, load shed controls, generator demand priority controls, and dead bus logic, and so on, reside in the Generator #1 EMCP 3.S. If Generator #1 controller fails for any reason, the next generator controller will assume master control functions without interruption. Each generator controller is redundant to the rst and contains all the settings necessary to assume master control functions. This technology ensures that if a generator set is available, Cat Switchgear will automatically bring it to the bus. 3. Seamless and Bumpless Transfer. With Moving Master Technology, each EMCP 3.S controller monitors system status and data for each generator. Should the EMCP 3.S functioning as the Master controller fail, the new Master already has all the pertinent status and data to seamlessly assume the master controller functions.
For more information, visit: www.eaton.com/consultants
4. Distributed Manual Control. In the highly unlikely case of a complete loss of system automation, distributed manual control is available. 5. Redundant Communication Processing. Two independent communication processors are built into the EMCP 3.S to control the Ethernet Channels A and B. 6. Redundant Ethernet Supervisory Networks. Each EMCP 3.S controller contains dual Ethernet ports and is connected to dual, independent Ethernet networks. 7. Instant Auto Switch. If the touchscreen fails, an Instant Auto switch is provided to place all digital controls in the Auto position, protecting your facility from power outages. A functional touchscreen is not required for complete automatic operation of Cat Switchgear.
35 36 37 38 39 40 41 42 43
CA08104001E
September 2011
Sheet 40 010
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
Touchscreen Interface
Cat Switchgear technology uses a touchscreen for operator interface, monitoring and control of the paralleling switchgear. The screens give the operator an instantaneous, easily understandable view of the entire system status. This feature is standard in all Cat Switchgear. To access system controls, all you have to do is touch the corresponding portion of the screen. The entire engine generator set can be controlled from one touchscreen. The easyto-use touchscreen interface makes it possible to view, monitor and perform multiple functions including:
Engine Data
Metering Engine data Protective relay settings Annunciators Adjust load shed controls and generator demand priority Synchronize and parallel Set modes of operation Voltage and frequency adjustments
Generator Control
With Cat Switchgear, its simple. All the critical information you need is displayed in a manner that is easy to understand. Graphics look exactly like the meters and gauges on conventional switchgear. At a glance, users can easily see how the system is performing and, based on real-time information can quickly do whats necessary to correct or optimize system performance.
Generator Annunciator
CA08104001E
September 2011
Sheet 40 011
40.1-5
Standard Package
15-inch color TFT touchscreen High reliability resistive LCD touchscreen technology Limited alarm and event logging Available moving master Available redundant network
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
Best-in-Class Footprint
Cat Switchgear technology uses less than one-third of the components of conventional generator paralleling switchgear. This translates into less wiring, a smaller footprint, higher mean time between failures, and lower mean time to repair.
19-inch color LCD TFT touchscreen SAW (surface acoustic wave) LCD touchscreen technology for unsurpassed reliability Historical trending of engine generator and electrical parameters Unlimited alarm and event logging Ability to save and archive trend and logging data Automated reporting capability Alarm reports Log reports Generator system reports Joint commission compliant reports Optional automatic transfer switch control Moving master Redundant control network
CA08104001E
September 2011
Sheet 40 012
22 23 24 25 26 27 28 29 30 31 32 33 34 35
Low cost redundancy Enhanced performance UL, NFPA, CSA and IEEE compliant Higher mean time between failure Lower mean time to repair
the remote communications run completely independent of the paralleling switchgear automation. This ensures remote communication devices or systems will not affect the reliability of your Cat Switchgear. Figures 40.1-2 and 40.1-3 show examples of remote communication connections to the Cat Switchgear.
Additional Cat Switchgear advantages include: Less installation wiring Smaller footprint provides better utilization of available space Detailed engine and electrical reports
End User PC - Full Control or View Only (depending on password) - Dedicated Static I.P. Address
End User PC - Full Control or View Only (depending on password) - Dedicated Static I.P. Address
36 37 38 39 40 41 42 43
Switchgear PC - Dedicated Static I.P. Address - Ethernet Port
Ethernet Port End User PC - Full Control or View Only (depending on password) - Dedicated Static I.P. Address
Key Points: 1. Dedicated Ethernet LAN or 2. Utilize customers' LANCoordination with network administrators may be necessary for connection and security issues. 3. Supports multiple clients.
CA08104001E
September 2011
Sheet 40 013
40.1-7
Off-Site
Remote Client - Web Browser
22 23 24 25
View Only
View Only
Remote Client - Web Browser
Cat Switchgear
VPN TUNNEL
Firewall Device - VPN Access
VP N
Ethernet Port
Remote Client - Web Browser
26
EL
Remote Client - Web Browser
N TU N
Switchgear PC
- 1 Web Server - Ethernet Port
27 28 29
Figure 40.1-3. Off-Site Remote(TCP-IP) Web-Based Connection with Multiple Users (View Only)
30 31 32 33 34 35 36 37 38 39 40 41 42 43
CA08104001E
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
CA08104001E
September 2011
Sheet 40 015
40.2-1
XLM
General Description
Cat XLM SwitchgearGenerator Paralleling Switchgear for Emergency Transfer (Xfer) and Load Management control of multiple engine generator sets with one utility source. For systems with multiple utility and/or tie breakers, please refer to the Custom Congurable Switchgear Section 40.5. For medium voltage application, refer to Section 40.4. Automatic transfer to emergency upon utility failure Automatic start, synchronize, parallel, and load share on a common bus for emergency operation Closed transition transfer back to utility upon stable return of power, with soft generator unloading Closed transition Load Management Mode with soft loading and unloading of generator system
Closed transition transfer to Emergency Mode to facilitate maintenance, or for storm threat avoidance with soft loading and unloading of generator system Load shed/load add Generator demand priority Cost-effective, technically superior alternative to conventional ATS arrangement
22 23 24 25 26 27 28 29 30
Cat Switchgear brings the power and reliability of microprocessor technology to your generator switchgear application. Through the use of the operator interface touchscreen display with easy-to-follow graphical representations, the Cat Switchgear merges the features of: Power monitoring Switchgear automation Generator set control Optional remote communications
XLM2 Switchgear
31 32 33 34
35 36 37 38 39 40 41 42
PR = Protective Relay.
43
CA08104001E
September 2011
Sheet 40 016
22 23 24 25 26 27
Equipment
Standard EquipmentXLM
28
29 30 31
32 33 34 35
36 37 38 39 40 41
42 43
Low voltage XLM systems use Magnum DS power circuit breaker switchgear and Magnum power circuit breakers. For complete technical details on Magnum DS switchgear, see Tab 20 Operator Interface Touchscreen (Choose one of the following): 19.00-inch surface acoustic wave LCD TFT color touchscreen with key switch 15.00-inch resistive LCD TFT color touchscreen Direct data communication to Cat microprocessor-based engine generator set control network Full function 0.5% accuracy analog and digital AC metering for utility: voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR Full function 0.5% accuracy analog and digital AC metering for generators: voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR Full function engine gauges; RPM, DC battery voltage, oil pressure, engine coolant temperature, engine hours, number of starts Full function synchronizing and paralleling controls with selection for automatic or manual synchronizing NFPA 110 engine/generator status, pre-alarm, lamp test button, shutdown fault annunciation and 85 dBA alarm horn with silence button Full function 0.5% accuracy analog and digital AC metering for system: voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR System control functions for auto (standby for emergency), closed transition to emergency and load management Automatic load shed control with on-screen operator adjustments for essential, critical, and non-essential loads. Manual load shed/load add control Automatic generator demand priority with on-screen operator adjustments for automatic addition and removal of generator to the load bus System status and alarm annuciation with color display and 85 dbA alarm horn with silence button
Password secured settings and adjustments for generator and system setups and protective relaying Alarm summary reports Settings reports Engine and generator load charts 3-D engine data (available with ADEM 3 or ADEM 4 Governor) UL 891, UL 1558 or CSA listed and labeled NEMA 1 or NEMA 3R, deadfront freestanding construction Copper bus, braced for 100 kA Three-phase, four-wire, 100% neutral,1/4-inch x 2.00-inch copper ground bus Available in 600V, 480/277V or 208/120V, 60 Hz UL 1066 listed power circuit breakers, 42200 kAIC, two-step stored energy drawout mounted electrically operated with long time and instantaneous trip, and circuit breaker control switch with lights Continuous cross bus ratings up to 10,000A at 600 Vac Mechanical lugs for incoming and outgoing conductors Top or bottom conduit entry Plug together control connections across shipping split Distribution sections with electrically operated drawout UL 1066 circuit breakers Circuit breaker trip functionsshort time and/or ground fault (in addition to long time and instantaneous) Steel barriers between switchboard or switchgear sections for compartmentalization Bus/cable barriers Distribution sections with group mounted UL 489 molded case circuit breakers. (UL 891 construction only) Also available in 150 kA (UL 891) or 200 kA (UL 1558) bus bracing congurations Also available in 8000 and 10,000A continuous cross bus ratings at 600 Vac Also available with 4000, 5000 and 6000A UL1066 breakers Trip unit metering and communications (Digitrip 520M, 520MC and 1150) Also available in 5 kV, 15 kV and 27 kV class congurations (see Section 40.4)
Remote monitoring and control Building Automation System or SCADA communications Modbus or Ethernet Remote notication Historical data trending
Optional EquipmentXLM
CA08104001E
September 2011
Sheet 40 017
40.2-3
Engine/Generator Control
Circuit Breakers
100% rated UL 1066 power circuit breakers available 8006000A with two-step stored energy mechanism 42 kAIC standard (50200 kA optional) Some ratings are only available under certain UL ratings (UL 1558200 kA)
15automatic synchronizer 27/59under/overvoltage relay 81 O/Uunder/overfrequency relay Multi-function utility grade, drawout with: 47phase sequence/phase failure relay 32reverse direction relay, utility grade, drawout 32/51reverse direction overcurrent relay, utility grade, drawout 32/62reverse direction timing relay, utility grade, drawout 86reverse power lockout relay, manual reset 25sync check relay
Automatic engine start Adjustable engine cool-down timer 15automatic synchronizer 65microprocessor engine governor load sharing and soft loading control 90VAR/PF and cross current compensation controller 0.5% accuracy Voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37
System Metering
System Control
Drawout mounted (xed optional) some ratings are only available under certain UL ratings. (UL 1558200 kA) 5 cycle closing Electrically operated Auxiliary and bell alarm contacts Electronic trip unit with long time and instantaneous trip functions (short time and ground fault optional) Available as UL 1558, UL 891 or CSA listed and labeled Optionally service entrance rated NEMA 1 or NEMA 3R, deadfront freestanding construction Copper bus 100 kA bus bracing (150200 kA optional) Three-phase, four-wire, 100% neutral bus, 1/4-inch x 2.00-inch ground bus Also available in UL listed and labeled medium voltage 0C to 50C 0 to 95% humidity, noncondensing
Generator Metering
0.5% accuracy Voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR; synchroscope
27/59under/overvoltage relay 81 O/Uunder/overfrequency relay 32reverse power relay 40loss of excitation (reverse VAR) relay 25sync check relay
Automatic standby mode Emergency mode with closed transition to normal Closed transition to emergency mode Load management mode Automatic load shed control with bus underfrequency protection and one four-pole,10A,120 Vac, Form C, dry contact output for each load shed level (1 level for each generator in the system) Automatic generator demand priority control Master shutdown button
Power Supply
Automatic best DC source selector 24 Vdc station battery, sealed jar, 4-hour, external 120 Vac emergency power required for charger Power from 24 Vdc engine cranking batteries Processor power supplies24 Vdc
Environment
Seismic Qualication
Engine Gauges
RPM meter Engine battery volt meter Oil pressure gauge Engine coolant temperature gauge
Technology Communications
Automation networkhigh speed, high reliability, industrially hardened Optional remote communications networkEthernet, modem Optional communication to building automation or SCADA systems for general monitoring Modbus RTU or Ethernet
Refer to Tab 1 for information on seismic qualication for this and other Eaton products.
38 39 40 41 42 43
Low coolant temperature pre-alarm High coolant temperature pre-alarm and shutdown Low oil pressure pre-alarm and shutdown Low fuel alarm (diesel only) Low engine battery alarm Overcrank shutdown Overspeed shutdown
CA08104001E
September 2011
Sheet 40 018
22 23 24 25 26 27 28 29 30 31 32 33 34
Figure 40.2-2. Typical Electrical System with XLM1 Switchgear (One Generator Source, One Utility Source) (For Multiple Utility Sources, see Custom Congurable Switchgear Section 40.5)
PR = Protective Relay.
SECT 1
SECT 2
SECT 3
Dimensions Height Width Depth Weight Lbs (kg) 3400 (1544) 3600 (1634) 78.00 3700 (1981.2) (1680)
35
CELL A
36 37 38 39 40 41 42 43
CELL D
MDS-CXX
52N1 CONTROLS
MDS-CXX
52G1
DIST CONTROLS
800 1600
532
800 1600 1600 99.00 44.00 72.00 3300 (2514.6) (1117.6) (1828.8) (1498) 1600 1600 1600 2000 2000 2000 3000 3200 3200
533 1064
HMI 19 TOUCHSCREEN
MDS-CXX
HORN SILENCE
HORN
CELL C
52G1 CONTROLS UCLOS 86
4000A, 5000A and 6000A breakers available in 44.00-inch wide structure. Contact your local Caterpillar Electric Power dealer for more details. Low voltage switchgear for up to 3500 kW generator set ratings at 480V is also available. Contact local Caterpillar Electric Power dealer for more details. 66.00 (1676.4) with D1 (optional as shown).
52N1
Conduit Space for 22.00-Inch (558.8 mm) Wide Structures Top or Bottom Entry
22.00 (558.8) 66.00 (1676.4) FRONT ELEVATION 22.00 (558.8)
22.00 (558.8)
Structure Depth 66.00 (1676.4) 72.00 (1828.8) 78.00 (1981.2) 84.00 (2133.6)
Rear Conduit Opening Width 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) Depth 19.30 (490.2) 25.30 (642.6) 31.30 (795.0) 37.30 (947.4)
CA08104001E
September 2011
Sheet 40 019
40.2-5
22 23 24 25 26 27 28 29 30 31
Figure 40.2-4. Typical Electrical System with XLM2 Switchgear (Two Generator Sources, One Utility Source) (For Multiple Utility Sources, see Custom Congurable Switchgear Section 40.5)
32 33
PR = Protective Relay.
SECT 1
R
SECT 2
SECT 3
34 35 36 37 38 39 40 41 42 43
CELL A
52N1 CONTROLS
MDS-CXX
800 1600
532
800 1600 1600 99.00 66.00 72.00 5000 (2514.6) (1676.4) (1828.8) (2270) 1600 1600 1600 2000 2000 2000 3000 3200 3200 5200 (2361) 5600 (2542) 84.00 5800 (2133.6) (2633)
533 1064
OPEN
CLOSED
HMI 19 TOUCHSCREEN
52G1 CONTROLS
HORN SILENCE
HORN
52D1
CELL C
52G2 CONTROLS UCLOS 86
MDS-CXX
52D2
4000A, 5000A and 6000A breakers available in 44.00-inch wide structure. Contact your local Caterpillar Electric Power dealer for more details. Low voltage switchgear for up to 3500 kW generator set ratings at 480V is also available. Contact local Caterpillar Electric Power dealer for more details.
CELL D
MDS-CXX MDS-CXX
Conduit Space for 22.00-Inch (558.8 mm) Wide Structures Top or Bottom Entry
52G2
52N1
Structure Depth
22.00 (558.8) 22.00 (558.8) 66.00 (1676.4) FRONT ELEVATION 22.00 (558.8)
Rear Conduit Opening Width 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) Depth 19.30 (490.2) 25.30 (642.6) 31.30 (795.0) 37.30 (947.4)
CA08104001E
September 2011
Sheet 40 020
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38
UCLOS 86
Figure 40.2-6. Typical Electrical System with XLM3 Switchgear (Three Generator Sources,One Utility Source) (For Multiple Utility Sources, see Custom Congurable Switchgear Section 40.5)
PR = Protective Relay.
SECT 1
SECT 2
SECT 3
SECT 4
CELL A
52N1 CONTROLS
MDS-CXX MDS-CXX
52G1
800 1600
532
800 1600 1600 99.00 88.00 72.00 7100 (2514.6) (2235.2) (1828.8) (3223) 1600 1600 1600 2000 2000 2000 3000 3200 3200 7300 (3314) 7700 (3496) 84.00 7800 (2133.6) (3541)
OPEN
CLOSED
OPEN
CLOSED
HMI 19 TOUCHSCREEN
TOUCHSCREEN DISABLE ENABLE HORN SILENCE HORN
533 1064
52G1 CONTROLS
52G3 CONTROLS
MDS-CXX
52D1
SYSTEM
SR750 CONTROLS
OPEN CLOSED
52G2 CONTROLS
MDS-CXX
52D2
39 40 41 42 43
CELL D
MDS-CXX MDS-CXX MDS-CXX
4000A, 5000A and 6000A breakers available in 44.00-inch wide structure. Contact your local Caterpillar Electric Power dealer for more details. Low voltage switchgear for up to 3500 kW generator set ratings at 480V is also available. Contact local Caterpillar Electric Power dealer for more details.
52N1
52G2
52D3
22.00 (558.8)
22.00 (558.8)
88.00 (2235.2)
22.00 (558.8)
22.00 (558.8)
Conduit Space for 22.00-Inch (558.8 mm) Wide Structures Top or Bottom Entry
Structure Depth 66.00 (1676.4) 72.00 (1828.8) 78.00 (1981.2) 84.00 (2133.6) Rear Conduit Opening Width 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) Depth 19.30 (490.2) 25.30 (642.6) 31.30 (795.0) 37.30 (947.4) Recommended Number of 3.50 or 4.00-Inch Conduits 9 12 15 18
FRONT ELEVATION
CA08104001E
September 2011
Sheet 40 021
40.2-7
22 23 24 25 26 27 28 29 30 31
Figure 40.2-8. Typical Electrical System with XLM4 Switchgear (Four Generator Sources, One Utility Source) (For Multiple Utility Sources, see Custom Congurable Switchgear Section 40.5)
32 33
PR = Protective Relay.
SECT 1
SECT 2
SECT 3
SECT 4
SECT 5
34 35 36 37 38 39 40 41 42 43
CELL A
52N1 CONTROLS
MDS-CXX
MDS-CXX
DIST CONTROLS
52G1
52G3
OPEN
CLOSED
OPEN
CLOSED
CELL B
96.06 (2440.0)
HMI 19 TOUCHSCREEN
TOUCHSCREEN DISABLE ENABLE
HORN SILE NCE
HORN
800
MDS-CXX
MDS-CXX
532
110.00 72.00 9100 800 1600 1600 99.00 (2514.6) (2794.0) (1828.8) (4131) 1600 1600 1600 2000 2000 2000 3000 3200 3200 9300 (4222) 9500 (4313) 84.00 9800 (2133.6) (4449)
52G1 CONTROLS
52G3 CONTROLS
52D1
52D3
1600
533 1064
SR750
SYSTEM CONTROLS
OPEN CLOSED
OPEN CLOSED
CELL C
52G2 CONTROLS
UCLOS 86
52D2
52D4
52G4
52N1
52G2
22.00 (558.8)
22.00 (558.8)
22.00 (558.8)
22.00 (558.8)
4000A, 5000A and 6000A breakers available in 44.00-inch wide structure. Contact your local Caterpillar Electric Power dealer for more details. Low voltage switchgear for up to 3500 kW generator set ratings at 480V is also available. Contact local Caterpillar Electric Power dealer for more details.
Conduit Space for 22.00-Inch (558.8 mm) Wide Structures Top or Bottom Entry
Structure Depth 66.00 (1676.4) 72.00 (1828.8) 78.00 (1981.2) 84.00 (2133.6) Rear Conduit Opening Width 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) Depth 19.30 (490.2) 25.30 (642.6) 31.30 (795.0) 37.30 (947.4) Recommended Number of 3.50 or 4.00-Inch Conduits 9 12 15 18
CA08104001E
September 2011
Sheet 40 022
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
Figure 40.2-11. XLMT4 Low Voltage Switchgear Layout
For more information, visit: www.eaton.com/consultants CA08104001E
CELL A
52N1 CONTROLS
DIST CONTROLS
MDS-CXX
MDS-CXX
Figure 40.2-10. Typical Electrical System with XLMT4 Switchgear (Four Generator Sources, One Utility Source, One Generator Bus Tie Breaker) (For Multiple Utility Sources, see Custom Congurable Switchgear Section 40.5)
PR = Protective Relay.
SECT 3
SECT 1
SECT 2
SECT 4
SECT 5
SECT 6
DIST CONTROLS
MDS-CXX
52D4
52G1
52G3
OPEN
CLOSED
OPEN
CLOSED
OPEN
CLOSED
CELL B
96.06 (2440.0)
HMI 19 TOUCHSCREEN
MDS-CXX
TOUCHSCREEN DISABLE ENABLE
HORN SILE NCE
800
52T1 CONTROLS
800 1600
52G1 CONTROLS
MDS-CXX
52G3 CONTROLS
800 99.00 132.00 72.00 9100 (2514.6) (3352.8) (1828.8) (4131) 78.00 9300 (1981.2) (4222) 84.00 9500 (2133.6) (4313) 9800 (4449)
HORN
52D1
52D5
1600
G
R
G
R
MDS-CXX
CELL C
MDS-CXX
52G2 CONTROLS
52T1
MDS-CXX
52G4 CONTROLS
UCLOS
86
52D2
52D6
2000 3000
CELL D
MDS-CXX
MDS-CXX
MDS-CXX
MDS-CXX
MDS-CXX
52N1
52D3
52G2
52D7
52G4
22.00 (558.8)
22.00 (558.8)
22.00 (558.8)
22.00 (558.8)
FRONT ELEVATION
4000A, 5000A, and 6000A breakers available in 44.00-inch wide structure. Contact your local Caterpillar Electric Power dealer for more details. Low voltage switchgear for up to 3500 kW generator set ratings at 480V is also available. Contact local Caterpillar Electric Power dealer for more details.
Conduit Space for 22.00-Inch (558.8 mm) Wide Structures Top or Bottom Entry
Structure Depth 66.00 (1676.4) 72.00 (1828.8) 78.00 (1981.2) 84.00 (2133.6) Rear Conduit Opening Width 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) Depth 19.30 (490.2) 25.30 (642.6) 31.30 (795.0) 37.30 (947.4) Recommended Number of 3.50 or 4.00-Inch Conduits 9 12 15 18
September 2011
Sheet 40 023
40.2-9
22 23 24 25 26 27 28 29
Generator Control
Cat engine generator set communications Network communications for monitoring and display of engine data to switchgear
Signal level
DC control 30 Vdc Signal level For gas engines equipped with AFR controller only 120 Vac/20A emergency circuit for 24 Vdc battery charger power
Battery Systems
Power for 24 Vdc station battery charger 24 Vdc station batteries 24 Vdc station battery charger malfunction Generator battery charger malfunction AC control
30 31 32 33 34 35 36 37 38
DC control 30 Vdc 24 Vdc supply to switchgear controls from 24 Vdc battery system DC control 30 Vdc Alarms DC control 30 Vdc Alarms DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc AC control DC control 30 Vdc DC control 30 Vdc Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms 87G relay alarm/shutdown Indication/alarms/shutdown Indication/alarms/shutdown
Fuel Systems
Low fuel tank level (master fuel tank) Fuel tank rupture basin (master fuel tank) High fuel tank level (master fuel tank) Other fuel tank alarms (master fuel tank) Low fuel tank level (day tank) Fuel tank rupture basin (day tank) High fuel tank level (day tank) Other fuel tank alarms (day tank)
39 40 41 42
Miscellaneous (Optional)
Miscellaneous enclosure alarms Miscellaneous aux. equipment alarms Switchgear 120 Vac space heaters Remote monitoring/control PC
Signal level
All control wiring to be stranded copper unless specied otherwise. Conductor size may have to be increased for voltage drop over long distances. Recommend 20% spares of each size single conductor and one of each multi-conductor cable. Separate metallic conduits should be used for each Signal Type. Signal Level and DC Control Signal 30 Vdc wires may be combined in the same conduit.
43
Note: Specic project and equipment requirements will determine exact number and type of control wiring required.
CA08104001E
September 2011
Sheet 40 024
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
6. The system is now running in Emergency Mode. b. Exit from Emergency Mode 1. The operator removes the System Mode Selector Switch from Transfer to Emergency position and returns it to the Auto position. 2. Following an adjustable time delay (which can be abbreviated by the operator), the generator plant is passively synchronized and paralleled to the utility source by closing the utility main breaker. 3. The generator plant is soft ramp unloaded until the utility source is nominally serving the entire system load. 4. The generator breakers are opened OR
4. [With Generator Bus Tie Breaker] The generator bus tie breaker is opened and then all of generator breakers are opened. 5. The generators are allowed to run for their programmed cool-down period. 6. The system is now back in Automatic/Standby Mode. 4. Load Management Mode a. Entry 1. Select one of the modes of operation: i. Import LimitThe user places the Import/ Export toggle switch in the Import position and places the Base Load/Utility Tracking toggle switch in the Utility Tracking position. The user sets the Utility Import set point to the desired amount of kW that they want to import through the Utility Circuit Breaker during Load Management Mode. ii. Export LimitThe user places the Import/Export toggle switch in the Export position and places the Base Load/Utility Tracking toggle switch in the Utility Tracking position. The user sets the Utility Export Set point to the desired amount of kW that they want to export through the Utility Circuit Breaker during Load Management Mode. iii. Base Load ImportThe user places the Import/Export toggle switch in the Import position and places the Base Load/Utility Tracking toggle switch in the Base Load position. The user sets the Base Load set point to the desired amount of kW that they want the generator plant to assume during Load Management Mode. The controls shall not allow the generator plant to export kW through the Utility Circuit Breaker and shall always maintain a nominal amount of Utility kW imported through the Utility Circuit Breaker. iv. Base Load ExportThe user places the Import/Export toggle switch in the Export position and places the Base Load/Utility Tracking toggle switch in the Base Load position. The user sets the Base Load set point to the desired amount of kW that they want the generator plant to assume during Load Management Mode. The controls shall allow the generator plant to export kW through the Utility Circuit Breaker.
CA08104001E
September 2011
Sheet 40 025
40.2-11
2. The user places the System Mode Selector Switch in the Load Management position. 3. A run request is sent to the generator plant. 4. The generators are allowed to run for a veminute warm-up time (which can be abbreviated by the operator). 5. The generators are synchronized and paralleled to the bus at no load after completion of the warm-up time. 6. When all generators are on the bus they are soft ramp loaded until the generator plant is nominally serving the required amount of the load on the bus to meet the mode of operation selected. 7. The generator output is dynamically adjusted to maintain the set point to meet the mode of operation selected. If at any time the system is unable to maintain the set point then a Set point Exceeded alarm shall be sounded. 8. Should the utility fail at any time during Load Management operation, the utility protective relays shall cause the utility main to open and be locked out, thus placing the system in Emergency Mode until the Utility is restored (as described in Emergency Mode exit). b. Exit 1. The operator removes the System Mode Selector Switch from Load Management position and returns it to the Auto position. 2. The generator plant is soft ramp unloaded until the utility source is nominally serving the entire system load and the generator main breakers are opened. 3. The generators are allowed to run for their programmed cool-down period.
6. Utility Fail Test Mode a. Entrance into Utility Fail Test Mode 1. The Utility Fail Test Switch is placed in the ON position. 2. Voltage sensing at the utility protective relay is opened, which simulates a loss of utility. 3. The system enters into Emergency Mode as described in the Emergency Mode sequence above. b. Exit from Utility Fail Test Mode 1. The Utility Fail Test Switch is placed in the OFF position. 2. Voltage sensing at the utility protective relay is restored, which simulates the return of utility power. 3. The system exits from Emergency Mode as described in the Emergency Mode sequence above. B. When the Generator Sets are carrying the facility load, the EPS Automation shall support two (2) sub-modes: Load Shed/Load Add, and Generator Demand Priority. 1. Load Shed Control a. The System Controls shall include a Load Shed Control function to control the loads served by the generator plant. b. The Load Shed Control shall have one Essential Load Shed Priority Level for each generator in the system plus one Non-Essential Load Shed Priority Level (which is always shed in the Emergency Mode of operation). c. The Load Shed Control shall control each of the distribution circuit breakers that are shown on the drawings. Distribution circuit breakers to be controlled shall be electrically operated. Each electrically operated distribution circuit breaker shall be eld selectable to be assigned to any of the available Load Shed Priority Levels. 1. Provide the following controls for each Essential Load Shed Priority Level i. Shed Delay Timer, adjustable from 0 to 1024 seconds ii. Add Delay Timer, adjustable from 0 to 1024 seconds iii. Load Shed Override Selector (shed/auto/add) iv. Status indicators to show whether the Priority Level is Added or Shed 2. Provide the following controls for each Non-Essential Load Shed Priority i. Load Shed Override Selector (shed/auto/add) ii. Status indicators to show whether the Priority Level is Added or Shed
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
CA08104001E
September 2011
Sheet 40 026
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
CA08104001E
September 2011
Sheet 40 027
40.3-1
EGP
General Description
Cat Emergency Generator Paralleling (EGP) Switchgear for multiple engine generator sets.
EGP Switchgear
Automatic start, synchronize, parallel and load/VAR share on a common bus Main lugs output to feed downstream emergency distribution Optional emergency distribution circuit breakers Load shed/load add Generator demand priority For use with multiple downstream Automatic Transfer Switches Cat Switchgear is designed to integrate hand-in-glove with Cat Automatic Transfer Switches. EGP Switchgear is optionally available with direct communication to Cat ATSs to provide ngertip control and monitoring of all your facility ATSs from one convenient central location
Cat Switchgear brings the power and reliability of microprocessor technology to your generator switchgear application. Through the use of the operator interface touchscreen display with easy-to-follow graphical representation, Cat Switchgear merges the features of: Power monitoring Switchgear automation Generator set control Optional remote communications
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
43
CA08104001E
September 2011
Sheet 40 028
22 23 24 25 26 27 28 29
Equipment
Standard EquipmentEGP
Low voltage EGP systems use Magnum DS power circuit breaker switchgear and Magnum power circuit breakers. For complete technical details on Magnum DS switchgear, see Tab 20 Operator interface touchscreen (Choose one of the following): High Redundancy Product, 19.00-inch surface acoustic wave LCD TFT color touchscreen with key switch Standard product, 15-inch resistive LCD TFT color touchscreen
30 31 32
33 34 35
36 37 38 39 40 41 42 43
Direct data communication to Cat microprocessor-based engine generator set control network (EMCP) System overview screen with one line mimic diagram that depicts real-time metering, status and control Full function 0.5% accuracy analog and digital AC metering for generators: voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR Full function engine gauges: RPM, DC battery voltage, oil pressure, engine coolant temperature, engine hours, number of starts 3-D engine data Full function synchronizing and paralleling controls with selection for automatic or manual synchronizing NFPA 110 engine/generator status, pre-alarm, lamp test button, shutdown fault annunciation and 85 dBA alarm horn with silence button Full function 0.5% accuracy analog and digital AC metering for system: voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR System control functions for auto (standby for emergency), test without load and test with load
Automatic load shed control with on-screen operator adjustments for essential (Life/Safety), critical and non-essential loads. Manual load shed/load add control Automatic generator demand priority with on-screen operator adjustments for automatic addition and removal of generator to the load bus System status and alarm annunciation with color display and 85 dbA alarm horn with silence button Password secured settings and adjustments for generator and system setups and protective relaying Alarm summary reports Settings reports Engine and generator load charts Engine trend data UL 891, UL 1558 or CSA listed and labeled NEMA 1 or NEMA 3R, deadfront freestanding construction Copper bus, braced for 100 kA Three-phase, four-wire, 100% neutral, 0.25-inch x 2.00-inch copper ground bus Available in 600V, 480/277V or 208/120V, 60 Hz UL 1066 listed power circuit breakers, 42200 kAIC, two-step stored energy drawout mounted electrically operated with long time and instantaneous trip, and circuit breaker control switch with lights Continuous cross bus ratings up to 10,000A at 600 Vac Mechanical lugs for incoming and outgoing conductors Top or bottom conduit entry Plug together control connections across shipping splits
Distribution sections with group mounted UL 489 molded case circuit breakers (UL 891 construction only.) Also available in 150 kA or 200 kA bus bracing congurations Also available in 8000 and 10,000A continuous cross bus ratings at 600 Vac Also available with 4000, 5000 and 6000A UL 1066 breakers Trip unit metering and communications (Digitrip 520M, 520MC and 1150) Also available in 5 kV, 15 kV and 27 kV class congurations (See Section 40.4) Remote monitoring and control Building Automation System or SCADA communications Modbus or Ethernet Remote notication Historical data trending Communication to Cat ATS units Automated Joint Commission report
Optional EquipmentEGP
Distribution sections with electrically operated drawout UL 1066 circuit breakers Circuit breaker trip functionsshort time and/or ground fault (in addition to long time and instantaneous) Steel barriers between switchboard or switchgear sections for compartmentalization Bus/cable barriers
CA08104001E
September 2011
Sheet 40 029
40.3-3
System Metering
0.5% accuracy Analog and digital voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR
Circuit Breakers
0.5% accuracy Analog and digital voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR; synchroscope
System Control
Engine Gauges
RPM meter Engine battery volt meter Oil pressure gauge Engine coolant temperature gauge 3-D engine data screens
Low coolant temperature pre-alarm High coolant temperature pre-alarm and shutdown Low oil pressure pre-alarm and shutdown Low fuel alarm (diesel only) Low and high engine battery alarm Battery charger alarm Overcrank shutdown Overspeed shutdown
Automatic standby mode Emergency mode Test without load Test with load Automatic load shed control with bus underfrequency protection and one four-pole,10A, 120 Vac, Form C, dry contact output for each load shed level (1 level for each generator in the system) Automatic generator demand priority control UL 1558, UL 891 or CSA listed and labeled Master shutdown
100% rated UL 1066 power circuit breakers available 8006000A with two-step stored energy mechanism 42 kAIC standard (50200 kAIC optional) Drawout mounted (xed optional) 5 cycle closing Electrically operated Auxiliary and bell alarm contacts Electronic trip unit with long time and instantaneous trip functions (short time and ground fault optional) Available as UL 1558, UL 891 or CSA listed and labeled Optionally service entrance rated NEMA 1 or NEMA 3R, deadfront freestanding construction Copper bus 100 kA bus bracing (150 or 200 kA optional) Three-phase, four-wire, 100% neutral bus 0.25-inch x 2.00-inch ground bus Also available in UL listed and labeled medium voltage 0 to 50C 0 to 95% humidity, noncondensing
22 23 24 25 26 27 28 29 30 31 32 33 34 35
Power Supply
Best DC source selector Power from 24 Vdc engine cranking batteries 24 Vdc station battery, sealed jar, 4-hour, external 120 Vac emergency power required for charger Processor power supplies24 Vdc
Environment
Seismic Qualication
Engine/Generator Control
Automatic engine start Adjustable engine cool-down timer 15automatic synchronizer 65microprocessor engine governor load sharing and soft loading control 90VAR/PF and cross current compensation controller
Communications
Automation networkhigh speed, high reliability, industrially hardened Optional remote communications networkEthernet, Modem Optional communication to building automation or SCADA systems or general monitoring Modbus RTU or Ethernet
Refer to Tab 1 for information on seismic qualication for this and other Eaton products.
36 37 38 39 40 41 42 43
CA08104001E
September 2011
Sheet 40 030
22 23 24 25 26 27 28 29 30 31 32 33 34
Figure 40.3-2. Typical Electrical System with EGP2 Assembly and ATS Units (Two Generator Sources)
SECT 1
R
SECT 2
SECT 3
35 36 37 38
CELL A
52G1 CONTROLS
MDS-CXX
DIST CONTROLS
52G2
0 533
99.00 (2514.6)
66.00 (1676.4)
72.00 (1828.8)
CELL B
HMI 19 TOUCHSCREEN
MDS-CXX
96.06 (2440.0)
52D1
TOUCHSCREEN DISABLE ENABLE
1065 1331
HORN
OPEN
CLOSED
OPEN
CLOSED
CELL C
84.00 (2133.6)
39 40 41
CELL D
MDS-CXX
SYSTEM CONTROLS
52G2 CONTROLS
MDS-CXX
52D2
4000A, 5000A and 6000A breakers available in 44.00-inch wide structure. Contact your local Caterpillar Electric Power dealer for more details. Low voltage switchgear for up to 4000 kW generator set ratings at 480V is also available. Contact local Caterpillar Electric Power dealer for more details.
52G1
Conduit Space for 22.00-Inch (558.8 mm) Wide Structures Top or Bottom Entry
22.00 (558.8) 66.00 (1676.4) 22.00 (558.8)
22.00 (558.8)
Structure Depth 66.00 (1676.4) 72.00 (1828.8) 78.00 (1981.2) 84.00 (2133.6)
Rear Conduit Opening Width 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) Depth 19.30 (490.2) 25.30 (642.6) 31.30 (795.0) 37.30 (947.4)
42 43
FRONT ELEVATION
CA08104001E
Min.
Max.
Generator kW (480V)
September 2011
Sheet 40 031
40.3-5
22 23 24 25 26 27 28 29 30 31 32 33
Figure 40.3-4. Typical Electrical System with EGP3 Assembly and ATS Units (Three Generator Sources)
34 35 36 37 38 39 40
41 42 43
CA08104001E
September 2011
Sheet 40 032
23 24
CELL A
52G1 CONTROLS
MDS-CXX
DIST CONTROLS
52G2
OPEN
CLOSED
0
MDS-CXX
532
CELL B
25 26 27 28 29 30
96.06 (2440.0)
HMI 19 TOUCHSCREEN
TOUCHSCREEN DISABLE ENABLE
800 3200 1600 99.00 66.00 84.00 7000 1 (2514.6) (1676.4) (2133.6) (3178) 1600 5000 2000 1600 4000 3200 2000 6000 2000 2000 4000 3200 3000 6000 2000 3000 6000 3200 88.00 (2235.2) 66.00 (1676.4) 88.00 (2235.2) 66.00 (1676.4) 88.00 (2235.2) 7050 1 (3201) 7500 2 (3405) 7100 1 (3223) 7600 2 (3450) 7200 1 (3269) 7800 2 (3541)
52G2 CONTROLS
52D1
HO RN SILENCE
HO RN
OPEN
CLOSED
OPEN
CLOSED
CELL C
SYSTEM CONTROLS
52G3 CONTROLS
MDS-CXX
52D2
CELL D
MDS-CXX
MDS-CXX
MDS-CXX
52G1
52G3
52D3
22.00 (558.8)
22.00 (558.8)
SECT 2
SECT 3
SECT 4
4000A, 5000A and 6000A breakers available in 44.00-inch wide structure. Contact your local Caterpillar Electric Power dealer for more details. Low voltage switchgear for up to 4000 kW generator set ratings at 480V is also available. Contact local Caterpillar Electric Power dealer for more details.
31 32 33 34 35 36 37 38 39 40 41 42 43
CELL A
52G1 CONTROLS
DIST CONTROLS
MDS-CXX
Conduit Space for 22.00-Inch (558.8 mm) Wide Structures Top or Bottom Entry
52G2
Structure Depth 66.00 (1676.4) 72.00 (1828.8) 78.00 (1981.2) 84.00 (2133.6)
Rear Conduit Opening Width 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) Depth 19.30 (490.2) 25.30 (642.6) 31.30 (795.0) 37.30 (947.4)
OPEN
CLOSED
CELL B
96.06 (2440.0)
HMI 19 TOUCHSCREEN
TOUCHSCREEN DISABLE ENABLE
MDS-CXX
52G2 CONTROLS
52D1
MDS-CXX
52D3
HO RN SILENCE
HO RN
OPEN
CLOSED
OPEN
CLOSED
CELL C
SYSTEM CONTROLS
52G3 CONTROLS
CELL D
MDS-CXX
MDS-CXX
MDS-CXX
MDS-CXX
52G1
52D2
52G3
52D4
22.00 (558.8)
22.00 (558.8)
22.00 (558.8)
Min. Max.
Generator kW (480V)
CA08104001E
Conguration Number
22
SECT 1
SECT 2
SECT 3
September 2011
Sheet 40 033
40.3-7
22 23
G1
G2
G3
G4
24 25
HMI Touchscreen
52G1
Main Service
52G2
52G3
52G4
D1
D2
D3
D4
26 27 28 29
ATS1
To Normal Distribution Circuits
To Emergency Circuits
ATS2 N
ATS3
ATS4
30 31 32
EDP1
EDP2
EDP3
EDP4
LP1
BP1
LP2
BP2
LP3
BP3
LP4
BP4
33 34 35 36 37 38 39
Figure 40.3-7. Automated Joint Commission Report
Figure 40.3-6. Typical Electrical System with EGP4 Assembly and ATS Units (Four Generator Sources)
40 41 42 43
CA08104001E
September 2011
Sheet 40 034
23 24 25 26
CELL A
52G1 CONTROLS
MDS-CXX
DIST CONTROLS
52G2
OPEN
CLOSED
CELL B
96.06 (2440.0)
HMI 19 TOUCHSCREEN
0
52G2 CONTROLS
MDS-CXX
532
MDS-CXX
800 3200 1600 99.00 88.00 78.00 7800 1 (2514.6) (2235.2) (1981.2) (3541) 1600 5000 2000 1600 4000 3200 2000 6000 2000 2000 4000 3200 3000 6000 2000 3000 6000 3200 110.0 (279.4) 88.00 (2235.2) 110.0 (279.4) 88.00 (2235.2) 110.0 (279.4) 7950 1 (3609) 84.00 9500 2 (2133.6) (4313) 8000 1 (3632) 9600 2 (4358) 8200 1 (3723) 9800 2 (4449)
52D1
TOUCHSCREEN DISABLE ENABLE
52D2
HORN SILENCE
HORN
533 1064
OPEN CLOSED
OPEN CLOSED
OPEN
CLOSED
CELL C
SYSTEM CONTROLS
52G3 CONTROLS
52G4 CONTROLS
MDS-CXX
533 1064
52D3
1065 1330
CELL D
MDS-CXX
MDS-CXX
MDS-CXX
MDS-CXX
27 28 29 30 31 32 33
CELL D CELL A
52G1
52G3
52G4
52D4
22.00 (558.8)
22.00 (558.8)
22.00 (558.8)
SECT 1
R
SECT 2
SECT 3
SECT 4
SECT 5
4000A, 5000A and 6000A breakers available in 44.00-inch wide structure. Contact your local Caterpillar Electric Power dealer for more details. Low voltage switchgear for up to 4000 kW generator set ratings at 480V is also available. Contact local Caterpillar Electric Power dealer for more details.
52G1 CONTROLS
MDS-CXX
MDS-CXX
DIST CONTROLS
52G4
52G2
Conduit Space for 22.00-Inch (558.8 mm) Wide Structures Top or Bottom Entry
MDS-CXX
OPEN
CLOSED
OPEN
CLOSED
CELL B
96.06 (2440.0)
CELL C
HMI 19 TOUCHSCREEN
52G2 CONTROLS
52G4 CONTROLS
MDS-CXX
Structure Depth
52D3
Rear Conduit Opening Width 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) Depth 19.30 (490.2) 25.30 (642.6) 31.30 (795.0) 37.30 (947.4)
52D1
TOUCHSCREEN DISABLE ENABLE
HORN SILENCE
HORN
OPEN
CLOSED
OPEN
CLOSED
SYSTEM CONTROLS
52G3 CONTROLS
MDS-CXX
MDS-CXX
52D2
52D4
34 35 36 37 38 39 40 41 42 43
MDS-CXX
MDS-CXX
52G1
52G3
22.00 (558.8)
22.00 (558.8)
22.00 (558.8)
22.00 (558.8)
Min. Max.
Generator kW (480V)
CA08104001E
Conguration Number
22
SECT 1
SECT 2
SECT 3
SECT 4
September 2011
Sheet 40 035
40.3-9
Utility Source
22
G1 G2 G3 G4
23 24
Revenue Metering
25 26
Main Service Emergency Generator Bus Tie D1 D2 Priority 1 Feeder Priority 1 Feeder D3 D4
27 28
~ ~
To Emergency Circuits ATS1 N E ATS2 N
~ ~
E ATS3 N
~ ~
E ATS4 N E
29 30 31
BP4
EDP1
EDP2
EDP3
EDP4
32 33 34 35 36 37 38 39 40 41 42 43
Figure 40.3-9. Typical Electrical System with EGPT4 Switchgear (Four Generator Sources, One Emergency Generator Bus Tie Breaker)
CA08104001E
September 2011
Sheet 40 036
23 24 25 26 27 28
CELL A
52G1 CONTROLS
DIST CONTROLS
OPEN
CLOSED
CELL B
96.06 (2440.0)
HMI 19 TOUCHSCREEN
TOUCHSCREEN DISABLE ENABLE
MDS-CXX
52T1 CONTROLS
MDS-CXX
MDS-CXX
0
52D3
OPEN CLOSED
532
52D1
HORN S ILENCE
52D2
HORN
800 3200 1600 99.00 110.00 78.00 7800 1 (2514.6) (2794.0) (1981.2) (3541) 1600 5000 2000 1600 4000 3200 2000 6000 2000 2000 4000 3200 3000 6000 2000 3000 6000 3200 110.00 (2794.0) 132.00 (3352.8) 110.00 (2794.0) 132.00 (3352.8) 132.00 (3352.8) 7950 1 (3609) 84.00 9500 2 (2133.6) (4313) 8000 1 (3632) 9600 2 (4358) 8200 1 (3722) 9800 2 (4449)
OPEN
CLOSED
OPEN
CLOSED
OPEN
CLOSED
CELL C
SYSTEM CONTROLS
52G2 CONTROLS
MDS-CXX
52G3 CONTROLS
52T1
52G4 CONTROLS
CELL D
MDS-CXX
MDS-CXX
MDS-CXX
MDS-CXX
1065 1330
52G4
52G1
52G2
52G3
22.00 (558.8)
22.00 (558.8)
22.00 (558.8)
22.00 (558.8)
SECT 1
R
SECT 2
SECT 3
SECT 4
SECT 5
29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
CELL A
52G1 CONTROLS
DIST CONTROLS
OPEN
CLOSED
CELL B
96.06 (2440.0)
4000A, 5000A and 6000A breakers available in 44.00-inch wide structure. Contact your local Caterpillar Electric Power dealer for more details. Low voltage switchgear for up to 4000 kW generator set ratings at 480V is also available. Contact local Caterpillar Electric Power dealer for more details.
HMI 19 TOUCHSCREEN
TOUCHSCREEN DISABLE ENABLE
MDS-CXX
52T1 CONTROLS
MDS-CXX
MDS-CXX
52D1
HORN S ILENCE
52D3
52D4
HORN
OPEN
CLOSED
OPEN
CLOSED
OPEN
CLOSED
OPEN
CLOSED
Conduit Space for 22.00-Inch (558.8 mm) Wide Structures Top or Bottom Entry
Structure Depth 66.00 (1676.4) 72.00 (1828.8) 78.00 (1981.2) 84.00 (2133.6) Rear Conduit Opening Width 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) 16.00 (406.4) Depth 19.30 (490.2) 25.30 (642.6) 31.30 (795.0) 37.30 (947.4) Recommended Number of 3.50 or 4.00-Inch Conduits 9 12 15 18
CELL C
SYSTEM CONTROLS
52G2 CONTROLS
MDS-CXX
52G3 CONTROLS
52T1
52G4 CONTROLS
CELL D
MDS-CXX
MDS-CXX
MDS-CXX
MDS-CXX
MDS-CXX
52G1
52D2
52G2
52G3
52G4
22.00 (558.8)
22.00 (558.8)
22.00 (558.8)
22.00 (558.8)
Min. Max.
Generator kW (480V)
CA08104001E
Conguration Number
22
SECT 1
SECT 2
SECT 3
SECT 4
SECT 5
September 2011
Sheet 40 037
40.3-11
22 23 24 25 26 27 28 29
Generator Control
Cat engine generator set communications Network communications for monitoring and display of engine data to switchgear
Signal level
DC control 0 Vdc Signal level For gas engines equipped with AFR controller only 120 Vac/20A emergency circuit for 24 Vdc battery charger power 24 Vdc supply to switchgear controls from 24 Vdc battery system Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms 87G relay/alarm/shutdown Indication/alarms/shutdown Indication/alarms/shutdown
Battery Systems
Power for 24 Vdc station battery charger 24 Vdc station batteries 24 Vdc station battery charger malfunction Generator battery charger malfunction AC control DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc AC control DC control 30 Vdc DC control 0 Vdc
30 31 32 33 34 35 36 37 38
Fuel Systems
Low fuel tank level (master fuel tank) Fuel tank rupture basin (master fuel tank) High fuel tank level (master fuel tank) Other fuel tank alarms (master fuel tank) Low fuel tank level (day tank) Fuel tank rupture basin (day tank) High fuel tank level (day tank) Other fuel tank alarms (day tank)
39 40 41 42
Miscellaneous (Optional)
Miscellaneous enclosure alarms Miscellaneous aux. equipment alarms Switchgear 120 Vac space heaters Remote monitoring/control PC
Signal level
43
All control wiring to be stranded copper unless specied otherwise. Conductor size may have to be increased for voltage drop over long distances. Recommend 20% spares of each size single conductor and one of each multi-conductor cable. Separate metallic conduits should be used for each Signal Type. Signal Level and DC Control Signal 30 Vdc wires may be combined in the same conduit.
Note: Specic project and equipment requirements will determine exact number and type of control wiring required.
CA08104001E
September 2011
Sheet 40 038
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
a. The No Load Test Switch is placed in the OFF position. b. All generator breakers are opened. c. The generators are allowed to run for their programmed cool-down period. d. The system is now back in Automatic/Standby Mode. 5. Utility Fail Test Mode
a. Entrance into Utility Fail Test Mode 1. The Utility Fail Test Switch is placed in the ON position. 2. A dry contact is sent to each ATS, which simulates a loss of utility within the ATS controls. 3. The system enters into Emergency Mode as described in the Emergency Mode sequence above. b. Exit from Utility Fail Test Mode 1. The Utility Fail Test Switch is placed in the OFF position. 2. A dry contact is removed from each ATS, which simulates the return of utility within the ATS controls. 3. The system exits into Emergency Mode as described in the Emergency Mode sequence above. B. When the Generator Sets are carrying the facility load, the EPS Automation shall support two sub-modes: Load Shed/Load Add, and Generator Demand Priority. 1. Load Shed Control a. The System Controls shall include a Load Shed Control function to control the loads served by the generator plant. b. The Load Shed Control shall have one Essential Load Shed Priority Level for each generator in the system plus one Non-Essential Load Shed Priority Level (which is always shed in the Emergency Mode of operation). c. The Load Shed Control shall control each of the distribution circuit breakers that are shown on the drawings. Distribution circuit breakers to be controlled shall be electrically operated. Each electrically operated distribution circuit breaker shall be eld selectable to be assigned to any of the available Load Shed Priority Levels. 1. Provide the following controls for each Essential Load Shed Priority Level i. Shed Delay Timer, adjustable from 0 to 1024 seconds ii. Add Delay Timer, adjustable from 0 to 1024 seconds iii. Load Shed Override Selector (shed/auto/add) iv. Status indicators to show whether the Priority Level is added or Shed
CA08104001E
September 2011
Sheet 40 039
40.3-13
2. Provide the following controls for each Non-Essential Load Shed Priority i. Load Shed Override Selector (shed/auto/add) ii. Status indicators to show whether the Priority Level is Added or Shed 3. Additionally, the Load Shed Controls shall have: i. Load Shed Control Switch (On/Off) ii. User-settable Load Shed % (as a function of on-line generator capacity) iii. User-settable Load Shed Time Delay iv. User-settable Load Add % (as a function of on-line generator capacity) v. User-settable Load Add Time Delay vi. User-settable Bus Under frequency Set point vii. User-settable Bus Under frequency time delay viii. Bus Under frequency Reset Pushbutton ix. Bus Under frequency indicator 4. Conditional Load ShedUpon entrance into Emergency Mode of operation, the Load Shed Control shall shed all Essential and Non-Essential loads. As generators come to the bus, Essential Priority Level loads shall be added conditionally based on the number of generators on line. When the rst generator comes to the bus, Priority Level 1 loads shall be added; Second generator, priority 2, etc. After a time delay that allows all operational generators to come to the bus, Load Shed Mode shall shift to Load Sensitive Mode. 5. Load Sensitive Load ShedAfter all generators have been given sufcient time to come to the bus, load shed shall shift to Load Sensitive mode. The system shall compare current generator on-line capacity (in kW) to current load requirements. If surplus capacity is greater than the calculated Load Add set point, after the Load Add Time Delay the next Load Shed Priority shall be added. This calculation will continue until all Sheddable Loads are added, or until surplus capacity is less than the calculated Load Add setpoint. If surplus capacity is less than the calculated Load Shed setpoint, after the Load Shed Time Delay the next Load Shed Priority shall be shed. This calculation shall continue until all Sheddable Loads are shed, or until surplus capacity is greater than the calculated Load Shed setpoint. The Load Shed Control, in its automatic shedding and adding of loads, shall not override any manual load shed/add operation. 6. Should the load bus frequency fall below the user selected bus underfrequency setpoint for a period longer than the bus underfrequency time delay, then all Priority Level loads shall be shed and load addition shall not resume until the operator has depressed the Bus Underfrequency Reset button. The bus underfrequency protection shall override any manual load add operation.
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
CA08104001E
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
CA08104001E
September 2011
Sheet 40 041
40.4-1
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
(50/51) Instantaneous/ Time Overcurrent (51G) Ground Overcurrent Trip Protection (27/59) Under/Overvoltage (81O/U) Over/Underfrequency (32) Reverse Power Relay (40) Loss of Field (Reverse var) (65) Engine Governor Load Sharing and Soft Loading Control (87G) Generator Differential Phase Fault (15/25) Automatic Synchronizer (25) Manual Paralleling Sync Check (90 PF) Var/Power Factor Controller (86) Lock-out Relay (50/51) Instantaneous/Time Overcurrent (27/59) Under/Overvoltage (81 O/U) Over/Underfrequency (47) Phase Sequence/Phase Failure (32) Reverse Power Relay (32/51) Reverse Direction Overcurrent Relay (15/25) Automatic Synchronizer (25) Manual Paralleling Sync Check Relay (86) Lock-out Relay
General Description
The Cat Generator Paralleling Switchgear Systems described in Section 40.2 for XLM (Emergency Transfer (Xfer) and Load Management), and Section 40.3 for EGP (Emergency Generator Paralleling) are also available for medium voltage systems. These systems use the Eaton VacClad switchgear with VCP-W vacuum circuit breakers and the same Cat generator control technology, features and benets described in Section 40.1.
Continuous Current
Circuit Breakers
1200, 2000 and 3000A (5 and 15 kV) 1200 and 2000A (27 kV)
Main Bus
1200, 2000, 3000 and 4000A (5 and 15 kV) 1200 and 2000A (27 kV)
For complete technical ratings, layouts, and features of VacClad Switchgear and VCP-W vacuum circuit breakers, refer to Tab 5. When reduced footprint, front access only switchgear is required, Cat Switchgear can be built using Eaton Type MEF metal-enclosed front accessible switchgear with Type VCP-T breakers. For complete technical details on MEF switchgear, see Tab 6.
Maximum Voltages
Interrupting Ratings
4.76 kV: Up to 63 kA 8.25 kV: Up to 50 kA 15.0 kV: Up to 63 kA 27.0 kV: Up to 40 kA
CA08104001E
September 2011
Sheet 40 042
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
Generator bus tie breakers can be applied to serve several purposes: 1. Starting of large loadsthe generator bus tie can be opened to allow multiple generators to be paralleled before being connected to large load(s). Once multiple generators are paralleled, the generator bus tie can be closed to power the large loads. 2. Load banksthe generator bus tie can allow the generators to be isolated from the normal utility fed bus. Having a distribution breaker or set of load take-off lugs on the generator side of the bus allows the generators to be load bank tested without affecting any normal utility fed loads. 3. Emergency Standby systems with Automatic Transfer Switchesthe generator bus tie provides isolation between the normal and emergency buses. During a loss of utility power, the generator bus tie can be opened to isolate all normal loads and allow restoration of power to emergency loads. Once emergency loads are restored, the emergency bus tie can be reclosed to restore power to normal loads.
See Page 40.4-7 for an example of an XLM system with generator bus tie breaker.
See Page 40.4-12 for an example of an EGP emergency system with generator bus tie breaker.
43
CA08104001E
September 2011
Sheet 40 043
40.4-3
4. Extensive information on Surge Protection, Arrestors and Capacitors can be found in Tab 5 Metal-Clad Switchgear VacClad-WMedium Voltage. 5. Recommended minimum protection: surge arrester for protection from high overvoltage peaks, or surge capacitor for protection from fast-rising transient. Please note that the surge arresters or surge capacitor alone may not provide adequate surge protection from escalating voltages caused by circuit resonance. 6. Good protection: Surge arrester in parallel with surge capacitor for protection from high overvoltage peaks and fast rising transient. This option may not provide adequate surge protection from escalating voltages caused by circuit resonance. When applying surge capacitors on both sides of a circuit breaker, a surge capacitor on one side of the breaker must be RC Snubber or ZORC, to mitigate possible virtual current chopping. 7. Better protection: RC snubber in parallel with surge arrester for protection from high frequency transients and voltage peaks. 8. Recommended best protection : ZORC, plus proper surge arrester preceding ZORC where needed for protection against lightning. ZORC provides protection from high frequency voltage transients and limits peak magnitude of the transient to 1 to 2 PU (see ZORC description in Tab 5 on Page 5.4-18 for more detail). Surge arrester provides protection from higher voltage peaks resulting from lightning surges.
Surge capacitors are recommended to protect the alternator on 5 kV or 15 kV Gensets. 1. Surge capacitors should be used to protect AC alternators. 2. Surge capacitors are used to prevent regular electric ow from being grounded. 3. Protective Surge Capacitor systems should be designed to operate in conjunction with lightning arresters to provide surge protection for generator alternators. 4. The capacitor should reduce the steepness of the wave front of the voltage surge, thereby reducing the stress on the turn and line-toground insulation. 5. Surge capacitors function best when located as close as possible to the generator alternator output leads. 6. Surge capacitors should be connected line-to-ground, and be on the load side of the breaker to eliminate the chance of a bus short-circuit in the event of capacitor failure. 7. Maximum effectiveness is achieved in limiting impulse voltages, if a low-resistance and low-inductance ground connection is established. All ground connections need to be tied together with a minimum #6 AWG copper conductor. 8. Although surge capacitors are installed line-ground, they should be rated for line-to-line voltage in the event they are installed on an ungrounded or poorly grounded system. 9. Cat Switchgear recommends the following values based on system voltage: 0.5 f on 5 and 7.5 kV, 0.25 f on 15 kV, and 0.13 f on systems operating at 24 kV and higher. 10. Where applicable, the surge capacitor shall conform to NEMA CP-1 standards.
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
CA08104001E
September 2011
Sheet 40 044
22 23
Equipment
Standard EquipmentXLM
Cat Switchgear Medium Voltage XLM systems use Eaton VacClad-W metalclad switchgear with Type VCP-W vacuum breakers. For complete technical details on VCP-W switchgear, see Tab 5. When reduced footprint, front access only switchgear is required, Cat Switchgear can be built using Eaton Type MEF metal-enclosed front accessible switchgear with Type VCP-T breakers. For complete technical details on MEF switchgear, see Tab 6.
SECT 2
SECT 3
24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
CELL B 95.00 (2413.0) CELL A
VTN1
VTG1
Utility Relay
Gen Relay
86
UCLOS
LOCKOUT
HMI 19 TOUCHSCREEN
AUTO
VTB1
52N1
52G1
36.00 (914.4) 36.00 (914.4) 108.00 (2743.2) FRONT ELEVATION 36.00 (914.4)
General Description
Cat XLM Switchgear
Generator Paralleling Switchgear for Emergency Transfer (Xfer) and Load Management control of multiple engine generator sets with one utility source. For systems with multiple utility and/or tie breakers, please refer to the Custom Congurable Switchgear Section 40.5. Automatic transfer to emergency upon utility failure Automatic start, synchronize, parallel, and load share on a common bus for emergency operation Closed transition transfer back to utility upon stable return of power, with soft generator unloading Closed transition Load Management Mode with soft loading and unloading of generator system. Closed transition transfer to Emergency Mode to facilitate maintenance, or for storm threat avoidance with soft loading and unloading of generator system
Load shed/add Generator demand priority Cost-effective, technically superior alternative to conventional ATS arrangement Cat Switchgear is designed to integrate hand-in-glove with Cat automatic transfer switches (ATSs), Generators and Uninterruptible Power Systems (UPSs)
Cat Switchgear brings the power and reliability of microprocessor technology to your generator switchgear application. Through the use of the operator interface (HMI) touchscreen display with easy-tofollow graphical representations, Cat Switchgear merges the features of: Power monitoring Switchgear automation Generator set control Optional remote communications
Operator Interface Touchscreen (Choose one of the following): 19-inch surface acoustic wave LCD TFT color touchscreen with key switch Standard and high redundancy product 15-inch resistive LCD TFT color touchscreen Direct data communication to Cat microprocessor-based engine generator set control network Full function 0.5% accuracy analog and digital AC metering for utility: voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR Full function 0.5% accuracy analog and digital AC metering for generators: voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR Full function engine gauges; RPM, DC battery voltage, oil pressure, engine coolant temperature, engine hours, number of starts Full function synchronizing and paralleling controls with selection for automatic or manual synchronizing NFPA 110 engine/generator status, pre-alarm, lamp test button, shutdown fault annunciation and 85 dBA alarm horn with silence button Full function 0.5% accuracy analog and digital AC metering for system: voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR
CA08104001E
September 2011
Sheet 40 045
40.4-5
System Control
System control functions for auto (standby for emergency), closed transition to emergency and load management Automatic load shed control with on-screen operator adjustments for essential (1 level of essential for every generator in the system) and 1 level of non-essential automatic or manual load shed/load add control Automatic generator demand priority with on-screen operator adjustments for automatic addition and removal of generator to the load bus System status and alarm annunciation with color display and 85 dBA alarm horn with silence button Password secured settings and adjustments for generator and system setups and protective relaying Alarm summary reports Settings reports Engine and generator load charts 3-D engine data Historical data trending UL MV listed and labeled NEMA 1, metal-clad construction IEEE 1547 compliant, when a compliant utility protective relay is selected UL or CSA listed Top or bottom conduit entry Plug together control connections across shipping split Distribution sections with singlehigh or two-high construction Tie breaker sections Also available in 27 kV class congurations Also available in arc-resistant congurations Remote PC and software for additional on-site monitoring and control work stations Remote PC and software for offsite monitoring and control Building Automation System or SCADA communications Modbus or Ethernet Remote notication
Generator Metering
0.5% accuracy Voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR; synchroscope
Engine Gauges
RPM meter Engine battery volt meter Oil pressure gauge Engine coolant temperature gauge
Automatic standby mode Emergency mode with closed transition to normal Closed transition to emergency mode Load management mode Automatic load shed control with bus underfrequency protection and one four-pole, 10A,120 Vac, Form C, dry contact output for each load shed level (1 level of essential for each generator in the system) Automatic generator demand priority control Master shutdown button
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
Power Supply
Automatic best DC source selector 24 Vdc station battery, sealed jar, 4-hour, external 120 Vac emergency power required for charger Power from 24 Vdc engine cranking batteries Processor power supplies24 Vdc
Low coolant temperature pre-alarm High coolant temperature pre-alarm and shutdown Low oil pressure pre-alarm and shutdown Low fuel alarm (diesel only) Low engine battery alarm Overcrank shutdown Overspeed shutdown Automatic engine start Adjustable engine cool-down timer 15automatic synchronizer 65microprocessor engine governor load sharing and soft loading control 90VAR/PF and cross current compensation controller 0.5% accuracy. Voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR
Technology Communications
Automation networkhigh speed, high reliability, industrially hardened Optional remote communications networkEthernet, Modem Optional communication to building automation or SCADA systems for general monitoring Modbus RTU or Ethernet
Engine/Generator Control
Optional EquipmentXLM
Environment
0C to 50C 0 to 95% humidity, noncondensing
System Metering
CA08104001E
September 2011
Sheet 40 046
22 23 24 25 26 27 28 29 30 31 32
Figure 40.4-2. Medium Voltage XLM1 Switchgear (One Generator Source, One Utility Source) (For Multiple Utility Sources, see Custom Congurable Switchgear Section 40.5)
Note: 87B = Bus Differential Protection (if applicable).
SECT 1
R
SECT 2
SECT 3
33 34 35
86
UCLOS
CLOSE LOCKOUT SWITCH
LOCKOUT AUTO
86
36 37 38 39 40 41 42
95.00 (2413.0)
VTB1
CELL B
52N1
52G1
36.00 (914.4)
36.00 (914.4)
43
Note: All structures are 96.25 inches (2444.8 mm) deep. Note: See Figures 40.4-11 and 40.4-12 for typical distribution structure layouts. Note: See Tab 5 Medium Voltage Metal-Clad Switchgear for conduit space, weights, etc.
CA08104001E
September 2011
Sheet 40 047
40.4-7
TO 87B1 TO 87B1
22 23 24 25 26
TO 87B2
TO 87B1
TO 87B1
TO 87B2
TO 87B2
TO 87B2
27 28 29
Figure 40.4-4. Medium Voltage XLMT3 Switchgear (Three Generator Sources, One Utility Source, One Generator Bus Tie Breaker) (For Multiple Utility Sources, see Custom Congurable Switchgear Section 40.5)
Note: 87B = Bus Differential Protection (if applicable); 87B1 = Zone 1; 87B2 = Zone 2.
30 31
SECT 1
R
SECT 2
SECT 5 VTB2
32 33 34 35
UCLOS
CLOSE LOCKOUT SWITCH
LOCKOUT AUTO
HMI 19 TOUCHSCREEN
86
86
86
86
86
86
36 37 38 39 40 41 42 43
36.00 (914.4)
36.00 (914.4)
36.00 (914.4)
36.00 (914.4)
36.00 (914.4)
36.00 (914.4)
36.00 (914.4)
FRONT ELEVATION
CA08104001E
September 2011
Sheet 40 048
22 23
SECT 2
SECT 3
SECT 4
24 25 26 27 28 29 30 31 32 33
Figure 40.4-6. EGP3 5/15 kV Switchgear
36.00 (914.0) CELL B 95.00 (2413.0) CELL A
HMI 19 TOUCHSCREEN
86
86
86
VTB1
52G1
52G2
52G3
36.00 (914.0)
144.00 (3658.0)
36.00 (914.0)
36.00 (914.0)
FRONT ELEVATION
34 35 36 37 38 39 40 41 42 43
General Description
Cat Emergency Generator Paralleling (EGP) Switchgear for multiple engine generator sets.
Automatic start, synchronize, parallel and load share on a common bus Main lugs output to feed downstream emergency distribution Optional emergency distribution circuit breakers Load shed/load add Generator demand priority
For use with multiple downstream Automatic Transfer Switches Cat switchgear is designed to integrate hand-in-glove with Cat Automatic Transfer Switches (ATS), Generators, and Uninterruptible Power Systems (UPS). EGP Switchgear is optionally available with direct communication to Cat ATSs to provide ngertip control and monitoring of all your facility ATSs from one convenient central location
Cat Switchgear brings the power and reliability of microprocessor technology to your generator switchgear application. Through the use of the operator interface (HMI) touchscreen display with easy-to-follow graphical representations, Cat Switchgear merges the features of: Power monitoring Switchgear automation Generator set control Optional remote communications
CA08104001E
September 2011
Sheet 40 049
40.4-9
Equipment
Standard EquipmentEGP
Cat Switchgear Medium Voltage EGP systems use Eaton VacClad-W metalclad switchgear with Type VCP-W vacuum breakers. For complete technical details on VCP-W switchgear, see Tab 5. When reduced footprint, front access only switchgear is required, Cat Switchgear can be built using Eaton Type MEF metal-enclosed front accessible switchgear with Type VCP-T breakers. For complete technical details on MEF switchgear, see Tab 6.
Operator interface touchscreen (Choose one of the following): 19-inch surface acoustic wave LCD TFT color touchscreen with key switch 15-inch resistive LCD TFT color touchscreen Direct data communication to Cat microprocessor-based engine generator set control network (EMCP) System overview screen with oneline mimic diagram that depicts realtime metering, status and control Full function 0.5% accuracy analog and digital AC metering for generators: voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR Full function engine gauges: RPM, DC battery voltage, oil pressure, engine coolant temperature, engine hours, number of starts 3-D engine data Historical data trending Full function synchronizing and paralleling controls with selection for automatic or manual synchronizing NFPA 110 engine/generator status, pre-alarm, lamp test button, shutdown fault annunciation and 85 dBA alarm horn with silence button Full function 0.5% accuracy analog and digital AC metering for system: voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR
System control functions for auto (standby for emergency), test without load and test with load Automatic load shed control with on-screen operator adjustments for essential (one level of essential for each generator in the system) and one level of non-essential automatic or manual load shed/ load add control Automatic generator demand priority with on-screen operator adjustments for automatic addition and removal of generator to the load bus System status and alarm annunciation with color display and 85 dBA alarm horn with silence button Password secured settings and adjustments for generator and system setups and protective relaying Alarm summary reports Settings reports Engine and generator load charts Engine trend data UL MV listed and labeled NEMA 1, metal-clad construction Top or bottom conduit entry Plug together control connections across shipping split Distribution sections with singlehigh or two-high construction Tie breaker sections. Also available in 27 kV class congurations Also available in arc-resistant congurations Remote monitoring and control Building Automation System or SCADA communications Modbus or Ethernet Remote notication Automated Joint Commission reporting Communication to Cat ATS units
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
0.5% accuracy Analog and digital voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR; synchroscope
Engine Gauges
RPM meter Engine battery volt meter Oil pressure gauge Engine coolant temperature gauge 3-D engine data screens
Low coolant temperature pre-alarm High coolant temperature pre-alarm and shutdown Low oil pressure pre-alarm and shutdown Low fuel alarm (diesel only) Low and high engine battery alarm Battery charger alarm Overcrank shutdown Overspeed shutdown
Engine/Generator Control
Automatic engine start Adjustable engine cool-down timer 15automatic synchronizer 65microprocessor engine governor load sharing and soft loading control 90VAR/PF and cross current compensation controller
Optional EquipmentEGP
System Metering
0.5% accuracy Analog and digital voltage 1-2, 2-3, 3-1; current 1, 2, 3; frequency; power factor; kW; kVAR Automatic standby mode Emergency mode Test without load Test with load Automatic load shed control with bus underfrequency protection and one four-pole, 10A, 120 Vac, Form C, dry contact output for each load shed level (one level of essential for each generator in the system) Automatic generator demand priority control Master shutdown
System Control
CA08104001E
September 2011
Sheet 40 050
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
Communications
Automation networkhigh speed, high reliability, industrially hardened Optional remote communications networkEthernet, Modem Optional communication to building automation or SCADA systems or general monitoringModbus RTU or Ethernet
Environment
CA08104001E
September 2011
Sheet 40 051
40.4-11
22 23 24 25 26 27 28 29 30
Figure 40.4-7. Medium Voltage EGP3 Switchgear (Three Generator Sources)
Note: 87B = Bus Differential Protection (if applicable).
31 32
SECT 1
R
SECT 2
SECT 3
SECT 4
33
VTG1 Gen. Relay VTG2 Gen. Relay VTG3
34
Gen. Relay CELL A
HMI 19 TOUCHSCREEN
35
86
G R
86
86
36 37 38
95.00 (2413.0)
CELL B
39
VTB1 52G1 52G2 52G3
40
36.00 (914.4) 36.00 (914.4) 36.00 (914.4) 36.00 (914.4)
41 42 43
144.00 (3657.6)
FRONT ELEVATION
CA08104001E
September 2011
Sheet 40 052
22 23 24 25 26 27
TO 87B1 TO 87B1
TO 87B1 TO 87B1
TO 87B2
TO 87B2
TO 87B1
TO 87B2
TO 87B2
TO 87B2
TO 87B2
28 29 30 31 32
R
Figure 40.4-9. Medium Voltage EGPT4 Switchgear (Three Generator Sources, One Emergency Generator Bus Tie)
Note: 87B = Bus Differential Protection (if applicable); 87B1 = Zone 1; 87B2 = Zone 2.
SECT 1
SECT 2 VTG1
SECT 5 52T1
33 34
86
86
86
86
86
86
86
95.00 (2413.0)
86
86
86
35
CELL B
36 37 38 39 40 41 42 43
36.00 (914.4)
36.00 (914.4)
36.00 (914.4)
36.00 (914.4)
36.00 (914.4)
36.00 (914.4)
36.00 (914.4)
36.00 (914.4)
See Section 40.2 for additional information on EGP systems. See the Product Specication Guide (PSG) Section 16346G for Metal-Clad Emergency Generator Paralleling SwitchgearMedium Voltage specications.
CA08104001E
September 2011
Sheet 40 053
40.4-13
22 23 24 25 26 27 28 29 30 31
32 33 34 35 36 37
86
G R
52D1
CELL A
Dist. Relay
86
95.00 (2413.0)
38
CELL B Dist. Relay
39 40 41
52D2
42 43
CA08104001E
September 2011
Sheet 40 054
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
Generator Control
Cat engine generator set communications Network communications for monitoring and display of engine data from EMCP to switchgear Discrete control (start/stop, emergency stop and crank terminate, includes spares, etc.) 24 Vdc from generator battery system to supplement switchgear 24 Vdc control voltage Bipolar DC bias signal for voltage control
Signal level
DC control 0 Vdc Signal level For gas engines equipped with AFR controller only 120 Vac/20A emergency circuit for 24 Vdc battery charger power 24 Vdc supply to switchgear controls from 24 Vdc battery system Alarms 120 Vac/40A emergency circuit for 125 Vdc battery charger power (circuit size varies with charger ampacity requirements). 125 Vdc supply to from 125 Vdc batteries to MV breaker controls (5 kV and 15 kV only) Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms 87G relay alarm/shutdown Indication/alarms/shutdown Indication/alarms/shutdown Metering input 51G relay alarm/shutdown
Battery Systems
Power for 24 Vdc station battery charger 24 Vdc station batteries 24 Vdc station battery charger malfunction Power for 125 Vdc battery charger (breaker/relay control power) 125 Vdc batteries (breaker/relay control power) 125 Vdc battery charger malfunction Generator(s) battery charger malfunction AC control DC control 30 Vdc DC control 30 Vdc AC control
(4) x 1/c #10 AWG (2 x + 24 Vdc and 2 x24 Vdc) (next to switchgear) (2) x 1/c #14 AWG (2) x 1/c #14 AWG (2) x 1/c #14 AWG (2) x 1/c #14 AWG (2) x 1/c #14 AWG (2) x 1/c #14 AWG (each) (2) x 1/c #14 AWG (2) x 1/c #14 AWG (2) x 1/c #14 AWG (2) x 1/c #14 AWG (each) (2) x 1/c #14 AWG (6) x 1/c #10 AWG (at generator) (1) x #14 AWG shielded twisted quad per reading (at generator) (2) x 1/c #14 AWG thermo-couple wire per reading (at generator) (4) x 1/c #10 AWG per AWG and (6) x 1/c #10 AWG (at generator panel) (2) x 1/c #10 AWG per NGR (at neutral resistors)
DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc DC control 30 Vdc AC control DC control 30 Vdc DC control 30 Vdc AC control AC control
Fuel Systems
Low fuel tank level (master fuel tank) Fuel tank rupture basin (master fuel tank) High fuel tank level (master fuel tank) Other fuel tank alarms (master fuel tank) Low fuel tank level (day tank) Fuel tank rupture basin (day tank) High fuel tank level (day tank) Other fuel tank alarms (day tank)
All control wiring to be stranded copper unless specied otherwise. Conductor size may have to be increased for Voltage Drop over long distances. Recommend 20% spares of each size single conductor and one of each multi-conductor cable. Separate metallic conduits should be used for each Signal Type. Signal Level and DC Control Signal 30 Vdc wires may be combined in the same conduit.
Note: Specic project and equipment requirements will determine exact number and type of control wiring required.
CA08104001E
September 2011
Sheet 40 055
40.4-15
22 23 24 25 26 27
Miscellaneous (Optional)
Miscellaneous enclosure alarms Miscellaneous aux. equipment alarms Switchgear 120 Vac space heaters Remote monitoring/control PC
Signal level
28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
All control wiring to be stranded copper unless specied otherwise. Conductor size may have to be increased for Voltage Drop over long distances. Recommend 20% spares of each size single conductor and one of each multi-conductor cable. Separate metallic conduits should be used for each Signal Type. Signal Level and DC Control Signal 30 Vdc wires may be combined in the same conduit.
Note: Specic project and equipment requirements will determine exact number and type of control wiring required.
CA08104001E
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
CA08104001E
September 2011
Sheet 40 057
40.5-1
Custom Systems
General Description
Cat Generator Paralleling Switchgear has the power and exibility to handle even the most unique or demanding congurations and project requirements. If the standard XLM (Emergency Transfer (Xfer) and Load Management), and EGP (Emergency Generator) congurations do not t the needs of your specic project, Cat Switchgear offers fully customized solutions. In many cases, custom congurable systems are based on standard XLM or EGP congurations with additional requirements such as: Multiple utility connections Multiple tie breakers Unique sequence of operations Special switchgear layout requirements, and so forth
22 23 24 25 26 27
Example Custom Overview Screen
28 29 30 31 32 33 34 35
Regardless of what the project requires, Cat Switchgear can meet your needs. Some examples of Custom System one-line diagrams and layouts are on the following pages.
36
Example Custom Overview Screen
37 38 39 40 41 42 43
CA08104001E
September 2011
Sheet 40 058
22 23 24 25 26 27
52N2
Bus #1
Bus #2
28 29 30 31 32 33 34 35
R
Figure 40.5-1. Low Voltage Main-Generator-Tie-Generator-Main Switchgear (Two Utility Sources, Four Generator Sources, Two Generator Bus Tie Breakers)
PR = Protective Relay.
SECT 2
SECT 3
SECT 4
SECT 5
SECT 6
SECT 7
36 37 38 39
CELL A
52N1 CONTROLS
DIST CONTROLS
MDS-CXX
MDS-CXX
MDS-CXX
52N2 CONTROLS
52G3
52G1
52D4
OPEN
CLOSED
OPEN
CLOSED
OPEN
CLOSED
CELL B
95.00 (2413.0)
HMI 19 TOUCHSCREEN
MDS-CXX
TOUCHSCREEN DISABLE ENABLE
52G1 CONTROLS
52BT1 CONTROLS
MDS-CXX
52G3 CONTROLS
HMI 19 TOUCHSCREEN
TOUCHSCREEN DISABLE ENABLE
HORN SILE NCE
HORN
52D1
52D5
HORN
SYSTEM CONTROLS
OPEN CLOSED
OPEN CLOSED
SYSTEM CONTROLS
G
R
G
R
CELL C
40 41 42
22.00 (558.8)
MDS-CXX
52G2 CONTROLS
52D2
MDS-CXX
MDS-CXX
52G4 CONTROLS
52BT1
52D6
CELL D
MDS-CXX
MDS-CXX
MDS-CXX
MDS-CXX
MDS-CXX
MDS-CXX
52N1
52D3
52G2
52D7
52G4
52N2
22.00 (558.8)
22.00 (558.8)
43
22.00 (558.8)
22.00 (558.8)
22.00 (558.8)
FRONT ELEVATION
September 2011
Sheet 40 059
40.5-3
22 23 24 25 26 27 28
Figure 40.5-3. Medium Voltage Main-Tie-Generator-Tie-Main Switchgear (Two Utility Sources, Two Generator Sources, Two Generator Bus Tie Breakers)
Note: 87B = Bus Differential Protection (if applicable).
29 30 31 32 33
SECT 1
R
SECT 2
SECT 3 52D1
Dist. Relay
SECT 4 52T1
Tie Relay
SECT 5 VTB2
SECT 6 VTG1
Gen. Relay
SECT 7 VTG2
Gen. Relay
SECT 8 52T2
Tie Relay
SECT 9 VTB3
SECT 10 52D3
Dist. Relay
SECT 11 VTN2
Utility Relay
VTN1
Utility Relay
HMI 19 TOUCHSCREEN
86
UCLOS
CLOSE L OCKOUT S WITCH
L OC KOUT A UTO
86
86
86
86
86
86
86
UCLOS
CLOSE L OCKOUT S WITCH
L OC KOUT A UTO
86
86
Dist. Relay
Dist. Relay
34 35 36 37 38 39 40 41 42 43
FRONT ELEVATIO N
CA08104001E
September 2011
Sheet 40 060
22
G1 G2 G3 G4
23 24 25 26 27 28 29 30
Utility TX
Utility TX
Utility Metering
Utility Metering
Utility Metering
UF1
UF6
Tie EF1
Tie
To Other SWGR Assemblies #2 Thru #6 Closed Transition of Paralleling and Utility, Plus Soft Loading/ Unloading
N1
E1
SWGR#1
31 32 33 34 35
Figure 40.5-5. Large Critical Power SystemMultiple Generators Closed Transition and Load Shed/Add LV Complex Utility and Generator Paralleling System
MV Generators X = Number of Units G1 Utility Utility Tie Protection Closed Transition Paralleling and Soft Load/Unload G2 Gx Utility Typical Generator Breaker MV Generator Bus Load Shed/Load Add MV Main Gen Main MV Bus A Typical MV Vacuum Breaker Typical Secondary Substations MV Bus B Synch & Paralleling Closed Transition Soft Loading/Unloading Load Shed/Load Add Gen Main MV Main Gen Synch Utility Tie Protection Closed Transition Paralleling and Soft Load/Unload
36 37 38 39 40 41 42 43
Secondary Main
No Load Shed/Load Add Open Transition Main-Tie-Main Transfer or Closed Transition Momentary Overlap for Main-Tie-Main Tie
LV Bus B
Figure 40.5-6. Large Critical Power SystemMultiple Generators Closed Transition (Active Sync) and Load Shed/Add MV Complex Utility and Generator Paralleling System
For more information, visit: www.eaton.com/consultants CA08104001E
September 2011
Sheet 40 061
40.5-5
22
MV Generators X = Number of Units G1 Utility Utility Tie Protection Closed Transition Paralleling and Soft Load/Unload G2 Gx Utility Typical Generator Breaker MV Generator Bus Load Shed/Load Add MV Main Gen Main MV Bus A Gen Main MV Bus B MV Main Gen Synch Utility Tie Protection Closed Transition Paralleling and Soft Load/Unload
23 24 25 26 27 28 29
Tie Synch & Paralleling Closed Transition Soft Loading/Unloading Load Shed/Load Add
Secondary Main
Closed Transition Soft Load/Unloading Transfer LV Bus A Typical LV Breaker Tie Load Shed/Load Add LV Bus B
30 31 32
Figure 40.5-7. Large Critical Power SystemMultiple Generators MV/LV Closed Transition and MV/LV Load Shed/Add MV Complex Utility and Generator Paralleling System
33 34
MV Generators X = Number of Units G1 Utility Utility Tie Protection Closed Transition Paralleling and Soft Load/Unload G2 Gx Utility Typical Generator Breaker MV Generator Bus Load Shed/Load Add Field Installed Cable by Contractor Synch & Paralleling Closed Transition Soft Loading/Unloading Load Shed/Load Add Closed Transition Soft Load/Unload MV ATS Load Shed/ Load Add Secondary Main LV Bus Typical LV Breaker Typical Secondary Substations Closed Transition Soft Load/Unload MV ATS Load Shed/ Load Add Gen Main MV Bus B MV Main Gen Synch Utility Tie Protection Closed Transition Paralleling and Soft Load/Unload
35 36 37 38 39 40 41 42 43
MV Main
Figure 40.5-8. Large Critical Power SystemMultiple Generators MV Only Closed Transition and MV/LV Load Shed/Add MV Complex Utility and Generator Paralleling System
CA08104001E For more information, visit: www.eaton.com/consultants
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
CA08104001E