Sunteți pe pagina 1din 24

Motors and ActuatorsFoot-Mounted

Modutrol IV Family of Motors Contractor-Friendly design for service and retrofit

Internal Field-Addable Transformer

Internal Field-Addable Auxiliary Switches

Resistor Board
Modutrol IV Motors replace all present generation Modutrol motors and set a new, certifiable standard for the industry. Modutrol IV Motors retain all the features that made Honeywell Modutrol motors the most reliable produced, and go even further with 20 quality improvements. TRADELINE models provide these features and benefits: 1. Dual shafts. Both drive and auxiliary shafts have equal torque ratings, allowing auxiliary shaft to drive full torque loads. This provides a more flexible motor. For example, a spring-return, normally closed motor will provide normally open operation simply by using the auxiliary shaft. 2. NEMA 3 housing. Modutrol IV motor housings protect the motor from driving rain if motor is mounted in the upright position (as shown in above photo). May be mounted outdoors without a weatherproofing kit. 3. Higher holding torques. Holding torques have been increased by 35-100%. More reliable performance on the job. Greatly reduced likelihood of dithering once motor has stabilized in position. 4. Improved spring return drive torque. Rating increased from 50 lb-in. to 60 lb-in. for the high torque M9185 style motor (old M945/955 motor). 5. Reduced power consumption. Motor power needs can always be satisfied with a 40 VA transformer. 6. Internal quality improvements. Result in improved performance and longer life. These significant quality improvements include:

Crank Arm

Controller Interface Module

M16727

Common Bore Motor precisely aligns bearings, end caps, stator and rotor for increased performance and reliability. One Piece Stator provides greater durability plus improved efficiency. Stronger Gear Train, the most reliable in the industry. Die-Cast Housing with tongue and groove seal design provides superior oil-seal integrity. Plus significant improvements in the drive shaft, terminal block, and more. A total of more than 20 improvements have gone into the design and manufacture of Modutrol IV MotorsThe Performers. Fourteen TRADELINE motors and appropriate accessories can be configured to replace all previous Honeywell Modutrol motors, as well as most OEM modutrol motors. The TRADELINE motors are: M6184D1035 M6194D1017 M6284D1000 M6294D1008 M9164D1009 M9174D1007 M9184D1013 M9184D1021 M9194D1003 M8185D1006 M6285A1005 M6285A1013 M9175D1014 M9185D1004

Building Controls and Systems

The appropriate accessories are listed in Parts and Accessories, a table near the end of this section of the catalog.

385

Motors and ActuatorsFoot-Mounted


Modutrol IV Family of Motors
The following Modutrol IV motors can replace the old style Modutrol motors as shown below.
New Mod IV Replacement NonSpring Return M6184 M6194 M6284 M6294 M7164 M7274 M7284 M7294 M7364 M7384 M7964 M7984 M9164 M9174 M9184 M9194 M9484 M9494 M644 M744 M941 M944 M954 Old Motors Replaced M734 M934

High Torque Spring Return

M4185 M4186 M6285 M6286 M7185 M7186 M7285

M7286 M7385 M7685 M8185 M9185 M9186

M445 M745 M845 M945 M955

Medium Torque Spring Return

M7975 M9175

M765 M865 M965 M975

386

Motors and ActuatorsFoot-Mounted


The Honeywell Family of Modutrol IV Foot-Mounted Actuators
*TRADELINE models. Voltage Vac Actuator M4185A1001 M4185B1009 M4185B1017 M4185B1058 M6184A1015 M6184A1023 M6184D1001 *M6184D1035 M6184D1068 M6184F1014 *M6194B1011 *M6194D1017 M6194E1006 M6284A1048 M6284A1055 M6284A1063 *M6284D1000 M6284F1013 *M6285A1005 *M6285A1013 M6285C1001 M6286G1001 *M6294D1008 M7164A1017b M7164G1030
b

Control Input Thermistor 25 35

Torque (lb-in.) 50 60 ! ! ! ! 75 Spring Recommended 150 300 Return Controller ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! T775; T4031 T775; T4031 T775; W7080 T775; T4031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; T7075; T675; T678; T6031 T775; W7080 T775; W7080 ! ! ! ! ! ! ! ! ! ! T775; W7080 T775, EXCEL 5000 T775, EXCEL 5000 T775, EXCEL 5000 T775, EXCEL 5000 T775, EXCEL 5000 T775, EXCEL 5000 T775, EXCEL 5000 DDC continued next page 387

On/ Spdt 24a 120 208 220 240 Stroke Timing Off Floating Modulating ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! 160 160 ! 160 ! 90 90 160 60 60 60 30 30 30 ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! 10.5-13.5 Vdc 10.5-13.5 Vdc 4-7 Vdc 4-20 mA 4-20 mA 4-20 mA 4-20 mA 2-10 Vdc 4-20 mA 4-20 mA ! 4-20 mA

90-160 15-30 90-160 30-60 90-160 120-240 90-160 30-60 90 60

90-160 120-240 90-160 120-240 160 90 160 60 30 160

Building Controls and Systems

90-160 30-60 90-160 30-60 160 90 160 160 60 30 60 60

90-160 120-240 90 90 160 90 160 90 90 160 90 160 90 30 30 60 30 60 15 30 60 30 60 30

! !

M7185A1004b M7284A1004b M7284A1012b M7284A1038 M7284A1046


b b

M7284A1079b M7284C1000 M7284C1018 M7284C1059


b b

Motors and ActuatorsFoot-Mounted


The Honeywell Family of Modutrol IV Foot-Mounted Actuators continued *TRADELINE models. Voltage Vac Actuator M7284C1067 M7284G1001b M7284Q1009 M7284Q1033 M7284Q1041 M7285A1003b M7285A1011b M7285A1045
b b b

Control Input Thermistor 25 35

Torque (lb-in.) 50 60 75 Spring Recommended 150 300 Return Controller ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! DDC T775, EXCEL 5000 T775, EXCEL 5000 T775, EXCEL 5000 DDC DDC T775, EXCEL 5000 T775, EXCEL 5000 T775, EXCEL 5000 T775, EXCEL 5000 T775, EXCEL 5000 T775, EXCEL 5000 T775, EXCEL 5000 T775, EXCEL 5000 T775, EXCEL 5000 T775, EXCEL 5000 T775, EXCEL 5000 T775; W7080 T7047 T7047 T7047 T7047 T7047 T775 T775 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 ! ! ! ! ! ! ! ! ! ! ! ! ! ! T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 continued next page

On/ Spdt 24a 120 208 220 240 Stroke Timing Off Floating Modulating ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! 160 160 90 160 90 160 90 160 160 90 160 90 160 160 160 160 90 90 90 90 160 90 90 160 90 ! 160 160 160 160 90 160 160 90 90 160 90 160 60 60 30 60 30 60 30 60 60 30 60 30 60 60 120 120 60 30 30 30 60 30 30 60 30 60 60 60 60 30 60 60 30 30 60 30 60 ! ! 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm ! ! ! 4-20 mA 2-10 Vdc 4-20 mA 4-20 mA 4-20 mA 4-20 mA 4-20 mA 4-20 mA 2-10 Vdc 4-20 mA 4-20 mA 4-20 mA 4-20 mA 2-10 Vdc 2-10 Vdc 2-10 Vdc 4-20 mA 14-17 Vdc

M7284Q1017b

M7285C1009

M7285C1017b M7285Q1008b M7285Q1016 M7286G1009 M7294A1010


b b

M7294G1009b M7294Q1007b M7685A1025 M7964B1009


b,c

M7964A1001b
b

M7964B1017b M7964C1007 M8185A1002 *M8185D1006 M9164A1005 M9164A1013 M9164A1021 M9164A1070 M9164A1088 M9164A1120 M9164C1001 M9164C1050 M9164C1068 *M9164D1009 M9174B1027 M9174B1043 M9174C1025 M9174C1033 *M9174D1007 M9175D1006 *M9175D1014 M9184A1019 M9184A1035 M9184C1031 M9184D1005 *M9184D1013
b

M7964C1015b

90-160 30-60

! ! ! ! ! ! ! ! ! !

90-160 30-60

90-160 30-60 90-160 30-60 90-160 30-60 160 90 90 60 30 30

90-160 15-30 90-160 30-60

388

Motors and ActuatorsFoot-Mounted


The Honeywell Family of Modutrol IV Foot-Mounted Actuators continued *TRADELINE models. Voltage Vac Actuator *M9184D1021 M9184F1000 M9184F1034 M9185A1018 M9185A1026 M9185C1006 *M9185D1004 M9185E1019 M9186G1006 *M9194D1003 M9194E1000
a

Control Input Thermistor 25 35

Torque (lb-in.) 50 60 75 Spring Recommended 150 300 Return Controller ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991 T775; T915; T991

On/ Spdt 24a 120 208 220 240 Stroke Timing Off Floating Modulating ! ! ! ! ! ! ! ! ! ! ! 90-160 30-60 90-160 30-60 90-160 30-60 160 90 160 60 30 60 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm 135 ohm

90-160 30-60 90-160 30-60 160 60 90-160 120-240 90-160 120-240

All 24 Vac Modutrol motors have CE approval. b Available only through Honeywell Authorized Distributors. c Includes minimum position potentiometer.

Modutrol IV Motor Order Number Guide


OUTPUT DRIVE ROTATION 4 5 6 1 2 3 N.C. N.O. N.C. N.O. NON-SPRING RETURN SPRING RETURN 1 ACTION NON-SPRING RETURN SPRING RETURN SHAFT DUALENDED SHAFT SINGLEENDED SHAFT SPECIFICATION NUMBER

M918 4 D1021
TORQUE DESIGNATION TORQUE SPRING RETURN 6 7 8 9 25 LB-IN. 60 LB-IN. NON-SPRING RETURN 35 LB-IN. 75 LB-IN. 150 LB-IN. 300 LB-IN. 1 NUMBER OF AUX. SWITCHES 0 A N 2 V D G W E H L Y F 1 B 2 C Q SPECIAL FUNCTION STANDARD ADJ. ZERO AND SPAN MINIMUM POSTITION STANDARD STANDARD STANDARD FIXED STROKE

FURTHER IDENTIFIES MOTOR

Building Controls and Systems

CONTROL SERIES (FIRST TWO DIGITS) 41 SERIES 40, TWO-POSITION, LINE VOLTAGE 61 SERIES 60, FLOATING CONTROL 62 SERIES 60, FLOATING WITH FEEDBACK POTENTIOMETER 71 4-7, 6-9, 10.5-13.5 VDC CONTROL 72 4-20 mA OR 2-10 VDC CONTROL 73 W936 CONTROL 76 14-17 VDC WITH MINIMUM POSITION 1 79 SPECIALS 81 SERIES 80, TWO-POSITION, LOW VOLTAGE 91 SERIES 90, PROPORTIONING CONTROL 94 PROPORTIONAL FLAME SAFEGUARD 1 FIRING RATE MOTOR

SUFFIX LETTER APPLIES TO ALL MODELS EXCEPT SERIES 79 ELECTRICAL ROTATION

N.C.

ADJUSTABLE FIXED ADJUSTABLE N.O.

1 2

MODEL NUMBERS IN SHADED AREAS ARE AVAILABLE SPECIAL ORDER ONLY. CONTACT YOUR HONEYWELL SALES REPRESENTATIVE. SUFFIX LETTERS IN BOLD ARE OBSOLETE.
M17507

389

Motors and ActuatorsFoot-Mounted


M4185; M4186; M8185 Modutrol IV Motors
Integral helical spring that returns the motor shaft to the normal position (fully closed for M4185 and M8185; fully open for M4186) on power interruption. Internal actuator motor and circuitry operate from 24 Vac Line voltage models shipped with internal transformers. Double-ended, 3/8 in. (10 mm) square crankshaft. APPROVALS: Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX. Canadian Standards Association Certified: File LR1620, Guide 400-E. TEMPERATURE RATINGS: Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle. ELECTRICAL RATINGS: Auxiliary Switch Ratings (A): One Contacta Full Load Locked Rotor
a

Two-position, spring return motors used to operate dampers and valves. Used to operate dampers and valves in applications where it is necessary or desirable to have the controlled element return to the starting position in the event of power failure or interruption. Replace M445A,D; M845A,C,E; and M865B motors. Available with factory-installed transformers, or an internal transformer can be added in the field. Oil-immersed motor and gear train provide reliable performance and long life. Provide NEMA 3 weather protection with wiring box, when mounted upright. Electrically normally closed (at closed position when control signal is at minimum level) and rotate clockwise to open with a signal increase. *TRADELINE model. Electrical Ratings Power ORDER NUMBER M4185A1001 M4185B1009 M4185B1017 M4185B1058 M8185A1002 *M8185D1006
a Torque

120V 7.2 43.2

240V 3.6 21.6

40 VA pilot duty, 120/240 Vac on opposite contact. ELECTRICAL CONNECTIONS: Quick-connect terminals are standard; screw terminal adapter available.

Torquea lb-in. Nm 60 6.8

Power Supply 120 Vac at 50/60 Hz 120/208/240 Vac at 50/60 Hz 24 Vac at 50/60 Hz

W 25

VA 30

Stroke Timing (degrees) Includes 60 sec 160 1 spdt auxiliary switch 30 sec 90

Comments

20

21

60 sec 160 30 to 90 to 160 60 sec

220738A adapter bracket to Shorter timing applies match height of Mod III motors to 90 degree stroke.

given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.

M6184; M6194 Modutrol IV Motors


APPROVALS: Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX. Canadian Standards Association Certified: File LR1620, Guide 400-E. TEMPERATURE RATINGS: Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle. ELECTRICAL RATINGS: Auxiliary Switch Ratings (A): One Contacta Reversing, three-wire spdt or floating control motors used to operate dampers and valves. Replace M644-A-E motors. Available with fixed or adjustable stroke. Internal actuator motor and circuitry operate from 24 Vac. Line voltage models shipped with internal transformers. Double-ended, 3/8 in. (10 mm) square crankshaft. Full Load Locked Rotor
a 40

120V 7.2 43.2

240V 3.6 21.6

VA pilot duty, 120/240 Vac on opposite contact.

continued next page 390

Motors and ActuatorsFoot-Mounted


M6184; M6194 continued *TRADELINE models. Electrical Ratings Power ORDER NUMBER M6184A1015 M6184A1023 M6184D1001 *M6184D1035 M6184D1068 M6184F1014 M6194B1011 *M6194D1017 M6194E1006
a

Torquea lb-in. Nm 150 75 17.0 8.5 Timing 30 sec 30 sec

Power Supply 24 Vac at 50/60 Hz 24 Vac at 50/60 Hz

W 15 15

VA 17 25 17

Stroke (degrees) Includes 90 160

Comments Shorter timing applies to 90 degree stroke.

120 Vac at 50/60 Hz 20

15 to 30 90 to 160 sec 150 17.0 30 to 60 90 to 160 sec 120 to 240 sec 30 to 60 sec 300 34.0 60 sec 90 220738A adapter bracket to match height of Mod III motors.

220738A adapter bracket to Shorter timing applies match height of Mod III motors. to 90 degree stroke.

120 to 90 to 160 240 sec

Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.

M6284; M6294 Modutrol IV Motors


APPROVALS: Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX. Canadian Standards Association Certified: File LR1620, Guide 400-E. TEMPERATURE RATINGS: Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle. ELECTRICAL RATINGS: Auxiliary Switch Ratings (A): One Contacta Reversing, three-wire floating-control motors with feedback potentiometer. Used with controllers that provide a spdt output to operate dampers and valves. Replace M944B,E,G,S motors. Internal actuator motor and circuitry operate from 24 Vac. Line voltage models shipped with internal transformers. Double-ended, 3/8 in. (10 mm) square crankshaft. *TRADELINE models. Electrical Ratings Power ORDER NUMBER M6284A1048 M6284A1055 M6284A1063 *M6284D1000 M6284F1013 *M6294D1008
a

Building Controls and Systems

120V 7.2 43.2

240V 3.6 21.6

Full Load Locked Rotor


a

40 VA pilot duty, 120/240 Vac on opposite contact.

Torquea lb-in. Nm Timing 150 17 60 sec 30 sec 60 sec

Power Supply

VA 25 17

Stroke (degrees) Includes 160 90 160 Auxiliary cams, MOVs and screw terminal adapter.

Comments

120 Vac at 50/60 Hz 20 15 24 Vac at 50/60 Hz

30 to 60 90 to 160 220738A adapter bracket to sec match height of Mod III motors. 2 spdt auxiliary switches. 300 34 120 to 240 sec 220738A adapter bracket to match height of Mod III motors.

Shorter timing applies to 90 degree stroke.

Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.

391

Motors and ActuatorsFoot-Mounted


M6285; M6286 Modutrol IV Motors
Factory-installed transformer models available, or an internal transformer can be added in the field. Double-ended, 3/8 in. (10 mm) square crankshaft. APPROVALS: Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX. Canadian Standards Association Certified: File LR1620, Guide 400-E. TEMPERATURE RATINGS: Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle. ELECTRICAL RATINGS: Auxiliary Switch Ratings (A): One Contacta Full Load Locked Rotor
a

Spring return motors with isolated feedback potentiometer, used with spdt or floating controls to operate dampers and valves. Replace M945B,C,G motors. Contain integral springs that return motor shafts to normal position (full open for M6286, full closed for M6285) when power is interrupted. Include electrically isolated feedback potentiometers to provide indication of shaft position. Oil-immersed motor and gear train provide reliable performance and long life. Includes adapter brackets to match shaft height of older motors. Provide NEMA 3 weather protection with wiring box, when mounted upright. *TRADELINE models. Electrical Ratings Power ORDER NUMBER *M6285A1005 *M6285A1013 M6285C1001 M6286G1001
a

120V 7.2 43.2

240V 3.6 21.6

40 VA pilot duty, 120/240 Vac on opposite contact. ELECTRICAL CONNECTIONS: Quick-connect terminals are standard; screw terminal adapter available.

Torquea 6.8

Power Supply 24 Vac at 50/60 Hz

W 20

VA lb-in. Nm 21 60

Stroke Timing (degrees) Includes 60 sec 30 sec 60 sec 160 90 160 2 spdt auxiliary switches. 220738A adapter bracket to match height of Mod III motors.

Torque given is normal running torque. Breakaway torque rating is 200 lb.-in. and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.

M7164; M7185 Modutrol IV Motors


M7164A and M7185A are normally closed (at closed position when control signal is at a minimum) and rotate clockwise to open with a signal increase. M7164G is electrically normally open (at open position when control signal is at a minimum) and rotate counterclockwise to close with a signal increase. M7185 motor has a helical spring that returns the motor to the normal position on power interruption. Internal actuator motor and circuitry operate from 24 Vac. Line voltage models shipped with internal transformers. Separate transformer may be required for 24 Vac models of M7164 motors for proper system operation. Double-ended, 3/8 in. (10 mm) square crankshaft. APPROVALS: Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX. Canadian Standards Association Certified: File LR1620; Guide 400-E. TEMPERATURE RATINGS: Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle. ELECTRICAL CONNECTIONS: Quick-connect terminals are standard; screw terminal adapter available.

M7164

M7185, M7186

Proportional motors used to operate dampers and valves when used with a modulating dc voltage source such as W7080 panel. M7164 replaces M734H,J motors; M7185 replaces M745P motors. Oil-immersed motor and gear train provide reliable performance and long life. Provide NEMA 3 weather protection with wiring box when mounted upright.

continued next page 392

Motors and ActuatorsFoot-Mounted


M7164; M7185 continued Available only through Honeywell Authorized Commercial Wholesalers and Honeywell Authorized Distributors. Electrical Ratings Power ORDER NUMBER M7164A1017 M7164G1030 M7185A1004
a

Torquea lb-in. Nm 35 4 Timing 30 sec

Power Supply 24 Vac at 50/60 Hz 120 Vac at 50/60 Hz 24 Vac at 50/60 Hz

W 14 19 23

VA 15 24

Stroke (degrees) Signal, Input 90 10.5 to 13.5 Vdc

Rotation Direction CWb CCWc CWb

60

6.8

60 sec

160

4 to 7 Vdc

Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING. b CW means motor is electrically normally closed and rotates clockwise with an increase in signal. Motor is in closed position when input signal is at minimum value. c CCW means motor is electrically normally open and rotates counterclockwise with an increase in signal. Motor is in open position when input signal is at minimum value.

M7284A,G; M7285A; M7286G; M7294A,G,Q Modutrol IV Motors


Internal actuator motor and circuitry operate from 24 Vac. Line voltage models shipped with internal transformers. Double-ended, 3/8 in. (10 mm) square crankshaft. APPROVALS: Underwriters Laboratories Inc. Listed: File E4436; Guide XAPX. Canadian Standards Association Certified: File No. LR1620; Guide 400-E. TEMPERATURE RATINGS: Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle. ELECTRICAL RATINGS: Auxiliary Switch Ratings (A): One Contacta Full Load Locked Rotor
a

M7284, M7294

M7285, M7286

Proportional motors operate valves when used with a modulating 2-10 Vdc or 4-20 mA input signal, such as EXCEL 5000 system. Oil-immersed motor and gear train provide reliable performance and long life. Provide NEMA 3 weather protection with wiring box, when mounted upright. M7285 motors have helical springs that return motor shaft to closed position on power interruption. Electrical Ratings Power ORDER NUMBER M7284A1079 M7284G1001 M7285A1045 M7286G1009 M7294A1010 M7294G1009 M7294Q1007
a

120V 7.2 43.2

240V 3.6 21.6

Building Controls and Systems

40 VA pilot duty, 120/240 Vac on opposite contact. ELECTRICAL CONNECTIONS: Quick-connect terminals are standard; screw terminal adapter available.

Available only through Honeywell Authorized Commercial Wholesalers and Honeywell Authorized Distributors. Torquea
b

Power Supply 24 Vac at 50/60 Hz

W 19 23 19

VA 20 24 20 29

lb-in. 150 60 300

Nm 17 6.8 34

Timingb 60 sec

Stroke (degrees) Comments 160 Normally Open Normally Open

Signal, Input 2-10 Vdc

120 sec 60 sec 90

Normally Open 4-20 mA

120 Vac at 50/60 Hz

23

Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING. b VA figures listed are for 60 Hz. Values will be higher by 5 VA at 50 Hz.

393

Motors and ActuatorsFoot-Mounted


M7284A,C,Q; M7285A,C,Q Modutrol IV Motors
Internal actuator motor and circuitry operate from 24 Vac. Line voltage models shipped with internal transformers. Double-ended, 3/8 in. (10 mm) square crankshaft. APPROVALS: Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX. Canadian Standards Association Certified: File LR1620, Guide 400-E. TEMPERATURE RATINGS: Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle. ELECTRICAL RATINGS: Auxiliary Switch Ratings (A): One Contacta Full Load Locked Rotor
a

M7284

M7285

Proportional motors used to operate dampers and valves when used with a modulating 4-20 mA current source. Replace M744S,T,Y and M745S,T,Y motors. Oil-immersed motor and gear train provide reliable performance and long life. Provide NEMA 3 weather protection with wiring box when mounted upright. M7285 motors have helical springs that return motor shaft to closed position on power interruption. Electrical Ratings ORDER NUMBER M7284A1004 M7284A1012 M7284A1038 M7284A1046 M7284C1000 M7284C1018 M7284C1059 M7284C1067 M7284Q1009 M7284Q1017 M7284Q1033 M7284Q1041 24 Vac at 50/60 Hz 60 sec 30 sec 60 sec 30 sec 60 sec 30 sec 60 sec 160 90 160 90 160 90 160 Power Supply Power W 29

120V 7.2 43.2

240V 3.6 21.6

40 VA pilot duty, 120/240 Vac on opposite contact. ELECTRICAL CONNECTIONS: Quick-connect terminals are standard; screw terminal adapter available.

Available only through Honeywell Authorized Commercial Wholesalers and Honeywell Authorized Distributors. Torquea 17 8.5 17

Stroke Signal, VAb lb-in. Nm Timing (degrees) Input 150 75 150 30 sec 60 sec 15 sec 30 sec 90 160 90

Includes

Comments

120 Vac at 23 50/60 Hz

4-20 mA

2 auxiliary switches 4-20 mA, spdt floating 4-20 mA 4-20 mA, spdt floating Enhanced Series 72 Modutrol Motors More repositions, direct/reverse acting user selectable, reversal adjustments, and include 220738A adapter plate. Inputs have adjustable zero and span for split range applications. Inputs have adjustable zero and span for split range applications. Enhanced Series 72 Modutrol Motors More repositions, direct/ reverse acting user selectable, reversal adjustments, and include 220738A adapter plate. Zero offset adjustment.

120 Vac at 50/60 Hz 24 Vac at 50/60 Hz

M7285A1003 M7285A1011 M7285C1009 M7285C1017 M7285Q1008 M7285Q1016


a

120 Vac at 28 50/60 Hz

34

60

6.8

30 sec 60 sec 30 sec 60 sec 30 sec 60 sec

90 160 90 160 90 160

4-20 mA 2 auxiliary switches

Inputs have adjustable zero and span for split range applications.

Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING. b VA figures listed are for 60 Hz. Values will be higher by 5 VA at 50 Hz.

394

Motors and ActuatorsFoot-Mounted


M7685 Modutrol IV Motor
Provides NEMA 3 weather protection with wiring box, when mounted upright. Normally closed (at closed position when control signal is at a minimum) and rotate clockwise to open with a signal increase. Includes a helical spring that returns the motor to the normal position on power interruption. Double-ended, 3/8 in. (10 mm) square crankshaft. APPROVALS: Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX. Canadian Standards Association Certified: File LR1620, Guide 400-E. TEMPERATURE RATINGS: Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle. ELECTRICAL CONNECTIONS: Quick-connect terminals are standard; screw terminal adapter available.

Proportional, spring-return motors for use with Honeywell W7080 panel 14-17 Vdc output; with minimum position adjustment. Replaces M745L motors. Oil-immersed motor and gear train provide reliable performance and long life.

Electrical Ratings Power ORDER NUMBER M7685A1025 Power Supply 24 Vac at 50/60 Hz W 23 VA 24 lb-in. 60 Torque Nm 6.8 Timing 30 sec Stroke (degrees) Includes 90 Minimum position potentiometer.

M7964 Modutrol IV Motor


M7984N replaces M744J motors (for Despatch Industries), and has a voltage input that can be adjusted from -0.9 to 2.6 Vdc to 1.0 to 2.4 Vdc and is designed to be controlled by a voltage source with series resistance of 2740 ohms. Internal actuator motor and circuitry operate from 24 Vac. Line voltage models shipped with internal transformers. Double-ended, 3/8 in. (10 mm) square crankshaft. Includes 220738A Adapter Bracket to match height of Mod III motors. APPROVALS: Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX. Canadian Standards Association Certified: File LR1620, Guide 400-E. TEMPERATURE RATINGS: Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle.

Building Controls and Systems

Proportional motors specially designed for specific controllers. M7964A,B,C replaces M734A,B,C Motors (for ITT Nesbitt multizone systems), and are used with T7047 thermistor-type thermostats.

Available only through Honeywell Authorized Commercial Wholesalers and Honeywell Authorized Distributors. Electrical Ratings ORDER NUMBER M7964A1001 Torquea Power Power Supply W VA lb-in. Nm 120 Vac 19 24 35 at 50/60 Hz 4.0 Stroke Signal, Timing (degrees) Input 30 sec 90 T7047 Rotation Direction CW; motor is electrically normally closed and rotates clockwise with an increase in signal. Motor is in closed position when input signal is at minimum value. CCW; motor is electrically normally open and rotates counterclockwise with an increase in signal. Motor is in open position when input signal is at minimum value. Comments Motor equipped with Molex plugs required in ITT Nesbitt multizone applications. Separate motor transformer may be required for proper system operation. Motor equipped with Molex plugs required in ITT Nesbitt multizone applications. Motor equipped with Molex plugs required in ITT Nesbitt multizone applications.

M7964B1009

M7964B1017 M7964C1007 M7964C1015


a

60 sec 30 sec

160 90

T7047 with ramp. Motor outputs a voltage ramp signal when shaft rotates to a limit.

CW; motor is electrically normally closed and rotates clockwise with an increase in signal. Motor is in closed position when input signal is at minimum value.

Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.

395

Motors and ActuatorsFoot-Mounted


M9164; M9174 Modutrol IV Motors
Internal actuator motor and circuitry operate from 24 Vac. Line voltage models shipped with internal transformers. Separate transformer may be required for 24V models for proper system operation. Double-ended, 3/8 in. (10 mm) square crankshaft. APPROVALS: Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX. Canadian Standards Association Certified: File LR1620, Guide 400-E. TEMPERATURE RATINGS: Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle. ELECTRICAL RATINGS: Auxiliary Switch Ratings (A): One Contacta Full Load Locked Rotor
a

Reversing, proportional motors used to operate dampers and valves. Replace M934 Motors. Electronic drive circuit. Can drive up to six Modutrol motors using 4074BYK Resistor Bag Assembly or 221508A Resistor Board Kit (see Accessories section). Interface modules available for series 70 (electronic) control. *TRADELINE models. Electrical Ratings Power ORDER NUMBER M9164A1005 M9164A1013 M9164A1021 M9164A1070 M9164A1088 M9164A1120 M9164C1001 M9164C1050 M9164C1068 *M9164D1009 M9174B1027 M9174B1043 M9174C1025 M9174C1033 *M9174D1007
a

120V 7.2 43.2

240V 3.6 21.6

40 VA pilot duty, 120/240 Vac on opposite contact.

Torquea Stroke Nm Timing (degrees) Includes 4.0 30 sec 60 sec 90 160 Comments

Power Supply

lbVA in. 24 35

120 Vac at 19 50/60 Hz 240 Vac at 50/60 Hz 120 Vac at 50/60 Hz 24 Vac at 50/60 Hz 14

15 24 15 24 30 sec 15 27 75 8.5 90 220738A adapter bracket to match height of Shorter timing applies Mod III motors. to 90 degree stroke. 1 spdt auxiliary switch 2 spdt auxiliary switches 220738A adapter bracket to match height of Shorter timing applies Mod III motors. to 90 degree stroke. 30 to 60 90 to 160 sec 30 sec 60 sec 30 sec 60 sec 90 160 90 160 30 sec 60 sec 90 160 2 spdt auxiliary switches

220 Vac at 19 50/60 Hz 24 Vac at 50/60 Hz 14

120 Vac at 19 50/60 Hz 24 Vac at 50/60 Hz 14

120 Vac at 21 50/60 Hz

24 Vac at 50/60 Hz

16

17

30 to 60 90 to 160 sec

Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.

396

Motors and ActuatorsFoot-Mounted


M9175; M9185; M9186 Modutrol IV Motors
Up to six Modutrol motors can be driven by one series 90 controller using 4074BYK Resistor Bag Assembly or 221508A Resistor Board (see Accessories). Internal actuator motor and circuitry operate from 24 Vac. Line voltage model shipped with internal transformer. Double-ended, 3/8 in. (10 mm) square crankshaft. APPROVALS: Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX. Canadian Standards Association Certified: File LR1620, Guide 400-E. TEMPERATURE RATINGS: Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle. ELECTRICAL RATINGS: Auxiliary Switch Ratings (A): One Contacta Full Load Locked Rotor
a

M9175

M9185, M9186

Reversing, proportional, spring-return motors used to operate dampers and valves when used in a series 90 control circuit. M9185; M9186 replace M945A,D,F and M955 motors; M9175 replaces M965 and M975 motors. Can be adapted to series 70 control with interface modules. Contain integral helical springs to return motor shafts to normal position (full closed for M9175 and M9185, full open for M9186) on power interruption. Oil-immersed motor and gear train provide reliable performance and long life. Provide NEMA 3 weather protection with wiring box, when mounted upright. *TRADELINE models. Electrical Ratings ORDER NUMBER M9175D1006 *M9175D1014 M9185A1018 M9185A1026 M9185C1006 *M9185D1004 M9185E1019 M9186G1006 60 sec 160 Power Supply Power W 31 22 24 60 6.8 60 sec 160 30 sec 90 60 sec 160 Torque 25 2.8 VA lb-in. Nm

120V 7.2 43.2

240V 3.6 21.6

40 VA pilot duty, 120/240 Vac on opposite contact. ELECTRICAL CONNECTIONS: Quick-connect terminals are standard; screw terminal adapter available.

Stroke Timing (degrees) Includes 30 to 90 to 160 60 sec 220738A Adapter Bracket to match height of Mod III motors. 2 spdt auxiliary switches 220738A Adapter Bracket to match height of Mod III motors. 1 spdt auxiliary switch

Comments Shorter timing applies to 90 degree stroke.

120 Vac at 26 50/60 Hz 24 Vac at 50/60 Hz 21 23

Building Controls and Systems

30 to 90 to 160 60 sec

Shorter timing applies to 90 degree stroke. M9186G drives to full open position when powered with control wiring not connected.

397

Motors and ActuatorsFoot-Mounted


M9184; M9194 Modutrol IV Motors
Internal actuator motor and circuitry operate from 24 Vac. Double-ended, 3/8 in. (10 mm) square crankshaft. Available with tapped (8-32) shafts for Flame Safeguard applications. APPROVALS: Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX. Canadian Standards Association Certified: File LR1620, Guide 400-E. TEMPERATURE RATINGS: Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle. ELECTRICAL RATINGS: Auxiliary Switch Ratings (A): One Contacta Full Load Locked Rotor
a

Reversing, proportional motors used to operate dampers and valves. Replace M944A,C,D and M954 motors. Electronic drive circuit. Available with fixed or adjustable stroke. Can drive up to six Modutrol motors using 4074BYK Resistor Bag Assembly or 221508A Resistor Board Kit (see Accessories section). Interface modules available for series 70 (electronic) control. *TRADELINE models. Electrical Ratings Power ORDER NUMBER M9184A1019 M9184A1035 M9184C1031 M9184D1005 *M9184D1013 *M9184D1021 M9184F1000 M9184F1034 *M9194D1003 M9194E1000
a

120V 7.2 43.2

240V 3.6 21.6

40 VA pilot duty, 120/240 Vac on opposite contact.

Torquea lb-in. Nm 150 17.0

Power Supply

VA 19

Stroke Timing (degrees) Includes 60 30 160 90 2 spdt auxiliary switches, tapped shaft. 90 to 160 220738A adapter bracket to match height of Mod III motors. Tapped shaft; 220738A adapter bracket to match height of Mod III motors. 2 spdt auxiliary switches. 2 spdt auxiliary switches, tapped shaft.

Comments

24 Vac at 50/60 Hz 18

75 150

8.5 17.0

15 to 30 30 to 60

Shorter timing applies to 90 degree stroke.

300

34.0

120 to 240

220738A adapter bracket to match height of Mod III motors. 1 spdt auxiliary switch.

Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.

398

Motors and ActuatorsFoot-Mounted


Modutrol IV Cross Reference
USE DIRECT REPLACEMENTS OR CONFIGURE MODELS TO MINIMIZE YOUR INVENTORY. (See notes at the end of this cross reference table.) TRADELINE Replacement Motor To Be Replaced M445A1000 M445A1042 M445A1067 M445D1007 M644A1016 M644A1024 M644B1049 M644C1006 M644C1014 M644D1005 M644E1012 M644E1053 M734D1004 M734D1012 M734D1038 M734H1000 M734H1018 M734H1026 M734J1015 M734J1056 M734J1072 M744A1006 M744A1014 M744D1003 M744S1005 M744S1013 M744T1004 M744T1012 M744Y1009 M744Y1017 M745A1003 M745A1011 M745G1007 M745L1027 M745L1043 M745P1007 M745S1002 M745S1010 M745T1001 M745T1019 TRADELINE Motor M8185D1006 M8185D1006 M8185D1006 M8185D1006 M6184D1035 M6184D1035 M6184D1035 M6184D1035 M6194D1017 M6184D1035 M6194D1017 M6194D1017 M9164D1009 M9164D1009 M9164D1009 M9164D1009 M9164D1009 M9164D1009 M9164D1009 M9164D1009 M9164D1009 M9184D1021 M9184D1021
a a

Set Stroke Tob 160 160 160 160 160 90 160 Adjustable Adjustable Adjustable 90 Adjustable 160 90 160 90 90 160 160 90 160 160 90 160 90 160 90 160 90 160 90 160 160 160 90 160 90 160 90 160

Add Internal Transformer 198162EA 198162AA 198162GA 198162EA

Add Switch 220736A 220736A 220736A

Comments

Functional Replacemente M4185B1009 M4185B1017 M4185A1001 M6184D1035 M6184A1015

198162EA

Replaced motor has 30 second timing. Replaced motor has 15/30 second timing. 220736B 220736A 220736A Replaced motor has 60 second timing. Add Q7330A . Add Q7330Ac. Add Q7330Ac. Add Q7130Ac, set at 10.5-13.5 Vdc, select CCW. Add Q7130A , set to 4-7 Vdc, select CCW. Add Q7130Ac, set to 4-7 Vdc, select CCW. Add Q7130Ac, set to 4-7 Vdc. Add Q7130Ac, set to 10.5-13.5 Vdc.
c c

M6184A1023 M6184D1001 M6194D1017 M6184F1014 M6194B1011 M6194E1006

198162EA 198162EA

198162EA 198162EA

M7164G1030

M7164A1017c

Building Controls and Systems

198162EA

220736A

Add

Q7130Ac,
c

set to 4-7 Vdc.

Add Q7330A . Add Q7330Ac. Add Q7130Ac, set to 4-7 Vdc. 198162EA 198162EA 198162EA 198162EA 198162EA 198162EA 220736B 220736B 220736B 220736B Add Q7230Ac, set to 4-20 mA. Add Q7230A , set to 4-20 mA. Add Q7230Ac, set to 4-20 mA. Add Q7230Ac, set to 4-20 mA. Add Q7230Ac, set to desired range. Add Q7230A , set to desired range. Add Q7330Ac. Add Q7330Ac. Add Q7130Ac, set to 4-7 Vdc, select CCW. Add Q7630Ac. Add Q7630Ac. Add Q7130Ac, set to 4-7 Vdc. 198162EA 198162EA 198162EA 198162EA 220736B 220736B Add Q7230Ac, set to 4-20 mA. Add Q7230Ac, set to 4-20 mA. Add Q7230Ac, set to 4-20 mA. Add Q7230A , set to 4-20 mA.
c c c

M9184D1021a M9184D1021a M9184D1021


a

M7284A1004c M7284A1012c M7284C1000c M7284C1018c M7284Q1009c M7284Q1017c

M9184D1021a M9184D1021a M9184D1021a M9184D1021 M9185D1004 M9185D1004 M9185D1004 M9185D1004 M9185D1004 M9185D1004 M9185D1004 M9185D1004 M9185D1004 M9185D1004
a

M7685A1025c M7185A1004c M7285A1003c M7285A1011c M7285C1009c M7285C1017c continued next page 399

Motors and ActuatorsFoot-Mounted


Modutrol IV Cross Reference continued TRADELINE Replacement Motor To Be Replaced M745Y1006 M745Y1014 M845A1001 M845A1027 M845A1035 M845C1009 M845E1007 M934A1201 M934A1219 M934A1227 M934A1235 M934A1243 M934A1250 M934A1268 M934A1284 M934A1292 M934A1318 M934A1326 M934A1334 M934A1342 M934D1000 M934D1018 M934D1026 M934D1034 M941A1008 M941A1016 M941A1024 M941A1032 M941A1057 M941C1006 M941C1014 M941C1022 M941C1030 M941C1063 M941D1005 M941D1021 M941D1039 M941D1047 M944A1010 M944A1028 M944B1175 M944B1191 M944B1241 M944C1000 M9184D1021 M6284D1000 M6294D1008 M6294D1008 M9184D1021
a a

TRADELINE Motor M9185D1004 M9185D1004 M8185D1006 M8185D1006 M8185D1006 M8185D1006 M8185D1006 M9164D1009 M9164D1009 M9164D1009 M9164D1009 M9164D1009 M9164D1009 M9164D1009 M9164D1009 M9164D1009 M9164D1009 M9164D1009 M9164D1009 M9164D1009 M9174D1007 M9174D1007 M9174D1007 M9174D1007

Set Stroke Tob 90 160 160 160 90 160 160 160 160 160 160 160 160 160 160 160 90 90 90 160 160 160 90 90

Add Internal Transformer 198162EA 198162EA 198162AA 198162AA 198162EA 198162AA 198162EA 198162GA

Add Switch 220736B 220736B 220736A 220736A 220736A

Comments Add Q7230Ac, set to desired range. Add Q7230Ac, set to desired range. 220736A

Functional Replacemente M7285Q1008c M7285Q1016c

M4185B1058 M8185A1002 Replaced motor is Normally Open .


d

M4185B1009 M9164A1013 M9164A1021 M9164D1009 M9164A1088

220736B 198162EA 198162AA 198162EA 198162EA 198162EA 198162EA 220736B 220736B 220736B 220736B

M9164C1050 M9164C1050 M9164A1021 M9164C1050 M9164C1068 M9164A1005 M9164A1021

198162EA 198162EA 198162EA 198162EA

220736A 220736B 220736A 220736B

M9174B1043 M9174C1033 M9174B1027 M9174C1025 M9484D1002c M9484D1010c M9484D1002 M9484D1020c M9484D1002c M9484E1009c M9484E1017c M9484E1033c M9484E1033c M9484E1033c M9484F1007c M9484F1023c M9484F1031c M9484F1049c

160 90 160 160 160 Adjustable 220736A Replaced motor has 15/30 second timing.

M9184A1019c M9184A1035c M6284D1000

M9184D1021a

M9184D1005 continued next page

400

Motors and ActuatorsFoot-Mounted


Modutrol IV Cross Reference continued TRADELINE Replacement Motor To Be Replaced M944C1018 M944C1042 M944C1059 M944D1017 M944E1040 M944G1089 M944G1097 M944S1027 M945A1017 M945A1082 M945A1157 M945B1057 M945B1065 M945C1015 M945D1006 M945F1004 M945G1037 M954A1035 M954B1034 M954D1016 M955A1024 M955C1014 M975A1089 M975A1097
a b

TRADELINE Motor M9194D1003 M9184D1013a M9194D1003 M9184D1021a M6284D1000 M6284D1000 M6284D1000 M6284D1000 M9185D1004 M9185D1004 M9185D1004 M6285A1005 M6285A1013 M6285A1005 M9185D1004 M9185D1004 M6285A1005 M9184D1021a M9184D1021a M9184D1021 M9185D1004 M9185D1004 M9175D1014 M9175D1014
a

Set Stroke Tob Adjustable Adjustable Adjustable Adjustable Adjustable 160 90 Adjustable 160 90 Adjustable

Add Internal Transformer

Add Switch

Comments

Functional Replacemente M9194D1003 M9184D1013

220736A 220736B 220736B 198162EA 198162EA 198162EA 220736B

M9194E1000 M9184F1000 M6284F1013 M6284A1048 M6284A1055 M6284F1013 M9185A1018 M9185A1026 M9185D1004 M6285A1005 M6285A1013

220736B 160 160 220736B Replaced motor is Normally Open . Replaced motor is Normally Opend. Adjustable 90 Adjustable Adjustable Adjustable 160 160 198162EA 220736A 220736B 220736B
d

M6285C1001 M9185C1006 M9186G1006 M9184D1021 M9184C1031 M9184F1034 M9185D1004 M9185E1019 M9175D1014 M9175D1014

Building Controls and Systems

The M9184D1013 and M9184D1021 have the same features and functions, except the M9184D1021 has a tapped shaft. Adjustable indicates original motor has adjustable stroke. c Available only through Authorized Honeywell Distributors. d Can use auxiliary end of TRADELINE model, which is N.C. motor. e Functionally equivalent motor, may require 220738A adapter bracket (order separately) to match shaft height of Mod III motor being replaced. All Mod IV TRADELINE motors include 220738A adapter bracket.

401

Motors and ActuatorsFoot-Mounted


Q7130; Q7230; Q7330; Q7630 Interface Modules
DIMENSIONS, APPROXIMATE: Circuit Module: 3-1/2 in. (89 mm) wide, 2 in. (51 mm) deep, 1 in. (25 mm) high. Terminal Block: 3-1/2 in. (89 mm) wide, 1 in. (25 mm) deep, 1/2 in. (13 mm) high. Ribbon Connector: 4 in. (102 mm). NOTE: Q7330A consists only of terminal block. For converting series 90 Modutrol IV motors to series 70 (electronic) control. Mounts and works inside wiring box of any series 90 Modutrol IV Motor. Protected from weather by motor's NEMA 3 wiring box. Mates to motor's quick-connect terminals and provides screw terminals for control wiring connections. Features solid-state circuitry with surface mount components. Plastic enclosure provides easy handling and protection for circuitry. Includes (except Q7330A) reversing switch to allow replacement of electrically normally open or electrically normally closed motors. Available only through Authorized Honeywell Distributors. *TRADELINE models. ORDER NUMBER *Q7130A1006 Application Replaces Replaces M7164G1006 M7164G1014 M7164G1022 M7164A1009 M7164A1017 M7164B1007 M7184A1005 M7186G1000 M7185A1004 M7284A1004 M7284A1012 M7284C1000 M7284C1018 M7284Q1009 M7284Q1017 M7285A1003 M7285A1011 M7285C1009 M7285C1017 M7285Q1008 M7285Q1016 M7364A1007 M7364A1015 M7364A1023 M7384A1003 M7384A1011 M7385A1002 M7385A1010 M7685A1009 M7685A1017 M7685A1009 M7685A1041 M7685A1033 M9185D1004 M9185D1004 M9184D1013 M9164D1009 M9185D1004 M9184D1013 M9186G1006 M9185D1004 M9184D1013 Use With M9164D1009 Provides selectable voltage ranges: 4 to 7, 6 to 9 or 10.5 to M734H1034, M734H1000 13.5 Vdc. Adapts M91XX Modutrol IV motor to function as M734H1018 M71XX model for M734H,J; M744D; M745G,P M734H1026 replacements. M734J1015 M734J1031, M734J1023, M734J1056 M734J1007, M734J1072 M744D1011, M744D1003 M745G1007 M745P1007 *Q7230A1005 Provides adjustable zero and span, voltage or current M744S1005 control (includes 4 to 20 mA and 2 to 10 Vdc). Adapts M744S1013 M91XX Modutrol IV motors to function as M72XX model for M744T1004 M744S,T,Y; M745S,T,Y replacements. M744T1012 M744Y1009 M744Y1017 M745S1002 M745S1010 M745T1001 M745T1019 M745Y1006 M745Y1014 *Q7330A1004 Provides interface to W936 Control. Adapts M91XX Modutrol IV motor to function as M73XX model for M734D; M744A; M745A replacements. M734D1004 M734D1012 M734D1038 M744A1006 M744A1014 M745A1003 M745A1011 *Q7630A1001 Provides 3-wire 14 to 17 Vdc control with minimum position M745L1027 capability. Adapts M91XX Modutrol IV motors to function as M745L1035, M745L1043 M76XX model for M745 replacements. M745H1006 M745L1001 M745L1019 402 TEMPERATURE RATINGS: Ambient: -40 F to +150 F (-40 C to +66 C). ELECTRICAL RATINGS: Power Supply: 24 Vac, 50/60 Hz. Power Consumption: 2 VA. Input Impedance: Q7130A: >100K ohms. Q7230A: Voltage input >100K ohms; Current input = 67 ohms. Q7630A: >50K ohms.

Motors and ActuatorsFoot-Mounted


Parts and Accessories
The following pages contain replacement parts and accessories for use with foot-mounted motors and actuators.

198162 Internal Transformers


Convert Modutrol IV motors from low voltage to line voltage. Single- or multi-tap available to match 24 Vac power supply. ELECTRICAL RATINGS: Power Consumption: 40 VA.

ORDER NUMBER 198162JA 198162EA 198162GA 198162AA

Primary Voltage 24 (for electrical isolation) 120 Vac at 50/60 Hz 220 Vac at 50/60 Hz 120/208/240 Vac at 50/60 Hz

Includes Transformer, screws, instructions for mounting internally in Modutrol IV motors.

220736 Internal Auxiliary Switch Kits


Selectable switch differentials of one or ten degrees of rotation. Switch adjustment procedures same as for factory-installed switches in certain motor models. ELECTRICAL RATINGS: Auxiliary Switch Ratings (A): One Contacta Control auxiliary equipment as a function of motor shaft position. For installation in any TRADELINE Modutrol IV Motor. Cams can be set to actuate switches at any angle within stroke of motor. ORDER NUMBER 220736A 220736B Switches 1 spdt 2 spdt Applicable Motors TRADELINE Modutrol IV motors Full Load Locked Rotor
a

120V 7.2 43.2

240V 3.6

Building Controls and Systems

21.6

40 VA pilot duty, 120/240 Vac on opposite contact.

Includes One Micro Switch V3 precision switch, which is actuated by adjustable cams inside the motor. Two Micro Switch V3 precision switches, which are actuated by adjustable cams inside the motor.

221508 Modutrol IV Motor Resistor Board


Board can be configured for any application listed by setting dip switch: In 4074BYK application, board allows single series 90 controller to operate up to six motors in unison. In 4074EDC, EED application, board permits operation of one to four motors from 4-20 mA controller. In 4074EAU application, board allows W973 Single-zone Logic Panel to drive two or three motors. Board snaps on easily to any M91XX Modutrol IV motor.

Mounts inside wiring box of any M91XX Modutrol IV motor; can be used in place of 4074BYK, 4074EAU, 4074EDC or 4074EED resistor kits. ORDER NUMBER 221508A Description

Resistor board for use with Modutrol IV motors. One board can be configured for any application listed above.

403

Motors and ActuatorsFoot-Mounted


Parts and Accessories
Description Hardware Housing, explosion-proof. Modutrol IV motors, requires 7617DM coupling. For ordering information, contact: O-Z/Gedney, Nelson Enclosures & Controls, (918) 641-7381 or (918) 641-7374 and ask for E & C Customer Service; or write to: O-Z/Gedney, Nelson Enclosures & Controls, P.O. Box 471650, Tulsa, OK 74147-1650. Modutrol IV motors. Modutrol IV motors. Used with Mod IV Actuator to match shaft height of Mod III Actuator. Auxiliary equipment for Modutrol III and Modutrol IV motors. Auxiliary equipment (for TRADELINE Modutrol IV motors only). 220736A 220736B Q5001D Q605F,G,H,J Q100 Q181 Q68B Q209E,F Q7130A1006 Q7230A1005 Q7330A1004 Q7630A1001 4074BYK 4074EAU 4074EDC 4074EED 221508A 17947A ES-650-117 Use With Order Number

Motor crank arm. Screw terminal adapters. Mod III Adapter Bracket Switch Kits External auxiliary switch kits. Internal auxiliary switch kits: One switch Two switches Linkages

221455A 220741A 203977A 220738A Q607A,B

Economizer adapter assembly Mounts W859 Economizer on any Modutrol IV motor.

Bracket and linkage assembly. Water or steam valves. Damper linkage. Linkage. Potentiometers Auxiliary potentiometer. Dual control potentiometer. Potentiometer. Interface Modules Interface modules: M71XX function M72XX function M73XX function M76XX function Resistor kits. M91XX motors. Available only through Authorized Honeywell Distributors. 1 to 4 additional motors. 1 to 5 additional motors. Series 90 Modutrol IV motors (M91XX models). Dampers with Modutrol IV motors. Butterfly valves.

Up to six M91XX motors in unison. Up to three M91XX motors from one W973 Single zone Logic Panel or T775. One M91XX motor from a 4-20 mA controller. Up to six M91XX motors from a 4-20 mA controller.

Resistor board Replacement Oil Replacement Oil; 4 oz. container Transformers Transformers. 24 Vac 120 Vac 220 Vac 120/208/240 Vac Weatherproofing Kit NEMA 3 Weatherproofing kit

M91XX motors. May be used in place of 4074BYK, EAU, EDC, EED resistor kits. All Modutrol motors.

Modutrol IV motors.

198162JA 198162EA 198162GA 198162AA

Fits all Modutrol IV motors. Protects motor from driving rain when mounted in any position. Not needed if motor is mounted upright.

4074ERU

404

Motors and ActuatorsFoot-Mounted


Q181 Auxiliary Potentiometer
Mounts on master motor and operates controlled motors in unison or in sequence. Controls motors with mechanical balance relay and solid state drive circuit. Use with 24V motors. THROTTLING RANGE: Adjustable, 40 to 160 degrees on each 135 ohm potentiometer. DIMENSIONS, APPROXIMATE: 3-3/16 in. (81 mm) high, 3-1/4 in. (83 mm) wide, 3-3/8 in. (86 mm) deep. ACCESSORIES: 7640JK Adapter Plate for mounting Q181 on early motors without bosses on gear end or for mounting over an external return spring. Cover Yes Yes No No

Controls one to four Modutrol (series 90) motors from one master motor. Compatible with Modutrol III and Modutrol IV motors. ORDER NUMBER Q181A1007 Q181A1015 Q181A1064 Q181A1072 Motors Controlled 1 2 3 4

Q209 Manual Potentiometers


Typical hookup diagram for Q209 and a Modutrol motor (cooling hookup shown).
Q209 R R

W BLUE RED

WHITE

Building Controls and Systems

Used to limit minimum position of a proportioning Modutrol motor. Mount directly in motor. All wiring is accomplished within motor wiring compartment. Color-coded leadwires. DIMENSIONS, APPROXIMATE: Q209E Q209F 3-1/4 in. (83 mm) x 3-3/8 in (86 mm) x 3-7/8 in. (98 mm) 1 in. (25 mm) x 1-3/8 in. (35 mm) x 2-5/8 in. (67 mm) Resistance 150 ohms 300 ohms Internal mount to Modutrol IV motors. 150 ohms 300 ohms Terminal board. Includes Quick-connect terminals with leadwires.
W B

SERIES 90 CONTROLLER

SERIES 90 MOTOR
M3280

ORDER NUMBER Application Q209E1002 Q209E1010 Q209F1001 Q209F1019 External mount onto Modutrol IV motors.

405

Motors and ActuatorsFoot-Mounted


S443 Manual Potentiometer
DIMENSIONS, APPROXIMATE: 3-3/4 in. (95 mm) high, 3-3/8 in. (86 mm) wide, 3-1/4 in. (83 mm) deep (including knob). REPLACEMENT PART: 30112A Potentiometer, 135 ohm. Internal schematic of S443A.
TERMINALBLOCK R W W MANUAL B B POTENTIOMETER

Used for remote manual control of proportioning (series 90) motors and relays. Compatible with Modutrol III and Modutrol IV motors. Select automatic or manual control with dpst toggle switch. Suitable for series 90, M7385; M7186; M7685; M7185; and M7285 motors controlled by 135 ohm slidewire inputs. Surface mounted, with conduit outlet on each side of case. Screw terminals. Scale marked OPEN-CLOSE. ORDER NUMBER S443A1007 Resistance 135 ohm Use with
AUTO

DPDT SWITCH

M17510

M9164; M9484; M9184; M9185 and motors replaced by these models.

Q100 Linkage
Contains necessary hardware to link Modutrol motors to a V51B Butterfly Valve. Compatible with Modutrol III and Modutrol IV motors. (Requires adapter bracket, which is standard on all Modutrol IV motors included in this catalog.) Adaptable for all sizes of V51B Valves. Strain release and stop bracket are provided with V51B.

Dimensions, Linkage Rod ORDER NUMBER Q100A1015 Q100A1023 V51 Valve Size (NPT) in. 2-1/2 and 3 in. 4 in. 6-5/8 7-1/4 mm 168 184 Comments Connecting holes for pins are 5/16 in. (8 mm) in diameter and 1/4 in. (6 mm) from each end of rod.

Q5001 Valve Linkage for Modutrol IV Motors


Easy-to-read position indicator. Valve stem lift height cam selectable. Overtravel permits tight closeoff without excessive motor strain. Available brackets make linkages adaptable to many valve bodies. Models available with 80 lb, 160 lb, and 320 lb stem force. Reversible cams on the Q5001 allow field selection of normally open or normally closed valve operation. All models have anti-spin. The Q5001 Valve Linkage connects a Modutrol Motor to a 2- or 3-Way valve. It is used primarily on V5011 or V5013 steam and water valves. Q5001 Valve Linkage is applicable to 2-Way or 3-Way valves in modulating or two-position service. Linkage requires no adjustment when used with Honeywell valves and Modutrol IV Motors. Q5001 Valve Linkage replaces Q601 and Q618 Valve Linkages. Linkage mounts directly to the valve bonnet; motor mounts to linkage bracket. TEMPERATURE RATINGS: Ambient: -40 F to +150 F (-40 C to +66 C) air temperature; -40 F to +337 F (-40 C to +169 C) valve bonnet temperature. STROKE: 160 degrees rotation for motor. BONNET CONNECTION: Setscrew. CONNECTIONS:Stem: Button and Clip. DIMENSIONS, APPROXIMATE: 5-13/16 in. (148 mm) wide, 10-1/4 to 10-1/2 in. (260 to 267 mm) high, 8-13/64 in. (212 mm) deep. Note: motor will add up to 2-1/8 in. (54 mm) to depth.

continued next page 406

Motors and ActuatorsFoot-Mounted


Q5001 continued ACCESSORIES: Valve Adapter Kits (order separately): 220829BCQ1Barber-Colman Valves. 220829JCQ1Johnson Control Valves. 220829LGQ1Landis & Gyr Powers Valves (bonnet nut 1-3/32 in., bonnet bracket 1-3/32 in.). 220829LGQ2Landis & Gyr Powers Valves (bonnet nut 1-3/8 in., bonnet bracket 1-3/8 in.). 220829LGQ3Landis & Gyr Powers Valves (bonnet nut 1 in., bonnet bracket 1-3/8 in.). 220845 Retainer clip for stem button. Required Torquea in lb-in. Cam Number 220855A 220858A 220861A 220862A 220863A 220864A 220865A 220866A 220867A
a b

CAMS: 160 lb Stem 320 lb Stem Force Forceb Application 50 100 V5047A, 1 in. to 1-1/2 in. V5011/V5013, 1/2 in. to 3 in.; V5047, 2 in. 60 1 1-1/8 1-1/4 1-3/8 Standard 1-1/2 V5011/V5013, 4 in. to 6 in. 50 100 200 30 120 60 240 120

Type Custom Standard 60 degrees overtravel for Auxiliary Switch Custom

80 lb Stem Lift in in. Force 1/4 9/16 3/4 25

Select a Modutrol IV Motor with equal or greater torque. Use the 320 lb stem force linkage with a 300 lb-in. torque motor. HONEYWELL VALVE/LINKAGE SELECTION GUIDE Valve V5011A V5011A,B V5011F V5011G V5013N V5047A V5051A 3-Way 2-Way Threaded Flanged 1, 1-1/4, 1-1/2 in. 2 in. 2-1/2, 3, 4, 5, 6 in. 1-3/8 9/16a 3/4 1-1/2 Threaded Type 2-Way Valve Body Flanged Dimensions, Approximate, Pipe Size 2-1/2, 3 in. 4, 5, 6 in. 1/2, 3/4, 1, 1-1/4, 1-1/2, 2, 2-1/2, 3 in. Linkage Q5001D Bonnet Size 1-3/8 1-7/8 1-3/8 Lift (in.) 3/4 1-1/2 3/4

Building Controls and Systems

Merchandise cam required (see cam table). Stem Force

*TRADELINE models. ORDER NUMBER *Q5001D1000 *Q5001D1018 *Q5001D1026


a b

lb 80, 160 160, 320

N 356, 712 712, 1355

Lift Adjustment 3/4 fixed

Bonnet Size 1-3/8 in.

Linkage Replaced Q601J,K,L,Ma; Q618A. Q601J,K,Q; Q618A1008a; Q618A1024. Q601E,Pb

1-1/2 fixed

1-7/8 in.

If valve lift is not 3/4 in., order a merchandise cam (see Cam table). If valve lift is not 1-1/2 in., order a merchandise cam (see Cam table).

407

Motors and ActuatorsFoot-Mounted


Q607 Auxiliary Switches
Wrap-around cover for easy access to switch adjustments and wiring. Maintenance-free protection of the switches and cams. APPROVALS: Underwriters Laboratories Inc. Listed. Canadian Standards Association Component Recognized. DIMENSIONS, APPROXIMATE: Mounting: 6-7/16 in. (164 mm) high, 5-3/16 in. (132 mm) wide, 2-1/8 in. (54 mm) deep (3-7/16 in. (87 mm) required for cover removal). ELECTRICAL RATINGS: Current Draw: 120V Full Load Locked Rotor 9.8A 58.8A 240V 4.9A 29.4A 480V 2.45A 14.7A

For control of auxiliary equipment as a function of motor shaft position. Compatible with Modutrol III and Modutrol IV motors. (Requires 220738A adapter bracket for use with Modutrol IV motors). Micro Switch precision switches, adjustable. Indicate motor position by use of a scale plate anchored to a common shaft, which allows Q607 to be adjusted for operational sequence before mounting. Adjustable plate allows universal mounting on either end of motor. *TRADELINE models. ORDER NUMBER Q607A1050 *Q607A1076a Q607B1067 *Q607B1083a
a

Pilot Duty: 75 VA at 24V and 277V. Resistive Load: 22A at 24V, 120V, 240V, 277V; 15A at 480V.

Switches 1 spdt 2 spdt

Applicable Motors Post 1969 Honeywell Modutrol motors. Pre/Post 1969 Honeywell Modutrol motors. Post 1969 Honeywell Modutrol motors. Pre/Post 1969 Honeywell Modutrol motors.

With adapter plate for mounting over the spring-return assembly on cover end of motor. Adapter plate to be used to mount Q607 gear end of older motors without bosses or for mounting over spring-return assembly on cover end of motor.

408