Sunteți pe pagina 1din 166

Chapter 2

NB to CP1E-N[]S1 to E5CC TEMP Controller with NB

Objective
Understand The feature of NB Designer (For NB HMI) The feature of CX-Programmer (For PLC) Set up communication for PLC, HMI and E5CC Change E5CC Set point for HMI Monitoring and record E5CC Data End of Lesson Able to bring back the program you have created which include Set up communication between PLC and HMI Control HMI Lamp Insert Number and text Event and Historical Event

Content Page

Chapter 2-1 Hardware Introduction 2-1-1 Basic Introduction on NB HMI 2-1-1i The Complete CP1E-N[]S1 Family 2-1-2 Basic Introduction on NB HMI 2-1-2i The Complete HMI Family 2-1-3 Basic Introduction on Power Supply 2-1-3i The Complete Power Supply Family 2-1-4 Basic Introduction on E5CC 2-1-4i E5CC- Digital Temperature Controller 2-1-5 Wires and cables for connection 2-1-5i Communication Cable Chapter 2-3 Setup For E5CC to communicate with PLC & NB HMI 2-3-1 Communication & Parameter Setting for E5CC Chapter 2-4 How to read E5CC value from PLC? 2-4-1 What will we learn in this topic 2-4-2 Setup CX-Programmer 2-4-3 DM Areas to Read E5CC Data Chapter 2-5 How to NB HMI read E5CC Data? 2-5-1 What will we learn in this topic 2-5-2 Setup NB Designer 2-5-3 Set up I/O list for PV & SV Reading 2-5-4 Create E5CC PV & SV Display

Chapter 2-2 How are we going to connect the components? 2-2-1 Hardware Wiring

Content Page
Chapter 2-5 How to NB HMI read E5CC Data? 2-5-5 Download to NB 2-5-6 View Reading of PV & SV 2-5-7 Address for E5CC Control Status 2-5-8 Create E5CC Alarm 1 Status 2-5-9 Create E5CC Status 2-5-10 Create Stop & Run Button 2-5-11 NB Display 2-5-11i Status between E5CC with HMI Chapter 2-6 How are we going to connect the components? 2-6-1 Write SV Values to E5CC 2-6-2 Create Write Values Button 2-6-3 Create Read Values Button 2-6-4 Download to NB 2-6-5 NB Display 2-6-5i E5CC with HMI Chapter 2-7 Create E5CCs Alarm 1 And Alarm 2 in NB Designer 2-7-1 Create Alarm1 Setting input 2-7-2 Create Alarm2 Setting input 2-7-3 Download to NB 2-7-4 NB Display 2-7-4i Compare E5CC and HMI Chapter 2-8 Compare E5CC and HMI 2-8-1 Create a New Frame Page and Link 2-8-2 Create Trend Curve Graph 2-8-3 Download to NB 2-8-4 NB Display 2-8-4i E5CC with HMI 2-8-4ii Review previous trending

Content Page
Chapter 2-9 How can I get the trend graph data? 2-9-1 Read Trend Graph Data from USB Flash Drive 2-9-2 Decrypt the CSV file 2-9-3 Create Historical Data Display 2-9-4 Safety Remove USB flash Drive 2-9-5 Download to NB 2-9-6 NB Display 2-9-6i Is it safe to remove USB Flash Drive? 2-9-6ii How to view previous data? Information

Chapter 2-1
Hardware Introduction

Chapter 2-1-1 Basic Introduction on PLC


S/N 1
2 3 4 5 6

Product PLC: CP1E-N30S1


NB: NB10W-TW01B Power Supply: S8JX-G03524CD Temperature Controller: E5CC RS232C (Male to Male) USB plug Connector

Qty 1
1 1 1 1 1

Wires

A few

Chapter 2-1-1i The Complete CP1E-N[]S1 Family

Chapter 2-1-1i The Complete CP1E-N[]S1 Family


S1-type 30 I/O points 40 I/O points 60 I/O points

Difference between S1 and S

Chapter 2-1-2 Basic Introduction on NB HMI


S/N
1 PLC: CP1E-N30S1

Product NB: NB10W-TW01B


Power Supply: S8JX-G03524CD Temperature Controller: E5CC RS232C (Male to Male) USB plug Connector

Qty
1

2
3 4 5 6

1
1 1 1 1

Wires

A few

Chapter 2-1-2i The Complete HMI Family

HMI
NB3QTW00B RS-232C RS-422A RS-485 NB3QTW01B USB Memory 10/100 base-T RS-232C RS-422A RS-485 NB5QTW00B NB5QTW01B USB Memory 10/100 base-T RS-232C RS-232C RS-422A RS-485 NB7WTW01B USB Memory 10/100 base-T RS-232C RS-232C RS-422A RS-485

Model Memory interface Ethernet

NB7W-TW00B -

NB10W-TW01B USB Memory 10/100 base-T

Serial (COM1)

RS-232C RS-232C RS-422A RS-485

RS-232C RS-232C RS-422A RS-485

RS-232C RS-232C RS-422A RS-485

Serial (COM2)

Chapter 2-1-3 Basic Introduction on Power Supply


S/N
1 2 PLC: CP1E-N30S1 NB: NB10W-TW01B

Product

Qty
1 1

3
4 5 6

Power Supply: S8JX-G03524CD


Temperature Controller: E5CC RS232C (Male to Male) USB plug Connector

1
1 1 1

Wires

A few

Chapter 2-1-3i The Complete Power Supply Family

Chapter 2-1-4 Basic Introduction on E5CC


S/N
1 2 PLC: CP1E-N30S1 NB: NB10W-TW01B

Product

Qty
1 1

Power Supply: S8JX-G03524CD

4
5 6

Temperature Controller: E5CC


RS232C (Male to Male) USB plug Connector

1
1 1

Wires

A few

Chapter 2-1-4i E5CC- Digital Temperature Controller

Chapter 2-1-5 Wires and cables for connection


S/N
1 2 PLC: CP1E-N30S1 NB: NB10W-TW01B

Product

Qty
1 1

3
4

Power Supply: S8JX-G03524CD


Temperature Controller: E5CC

1
1

5 6

RS232C (Male to Male) USB plug Connector

1 1

Wires

A few

Chapter 2-1-5i Communication Cable


RS232C (Male to Male)
HMI PLC

USB plug Connector

HMI / PLC

PC

XW2Z-200T

Chapter 2-2
How are we going to connect the components? Answer: Just follow the wiring diagram

Chapter 2-2-1 Hardware Wiring


Connect to DC 24V

USB cable from PC (CX-Programmer) Connect to HMI using RS232 cable

E5CC

Connect to AC 230V

PLC B+ to E5CC Terminal 13 PLC A- to E5CC Terminal 14

Connect to COM1

Connect to DC 24V

Chapter 2-3
Setup For E5CC to communicate with PLC & NB HMI

Chapter 2-3-1 Communication & Parameter Setting for E5CC


Turn ON Communication Writing
Step 1 Step 2 Step 3

Press

for 1 sec and go to STEP 2

Press for up or down to ON the Communication

Press and go to home screen

Chapter 2-3-1 Communication & Parameter Setting for E5CC


Protocol Setting
Step 1 Step 2 Step 3 Step 4

Press

for 3 sec and go to STEP 5

Press

for 1 sec and go to STEP 6

Press for up/down to select FINS Communication

Press

and go to STEP 8

Communication Baud Rate Setting


Step 2
Step 1

Communications Unit No. Setting


Step 1

Set Communication Baud rate to 57.6 (57600bps)

Press for 1 sec and go to STEP 10

Communication Unit set to 0

Chapter 2-3-1 Communication & Parameter Setting for E5CC


Send Data Wait Time Setting
Step 1 Step 2

Highest Communication Unit No. Setting


Step 1 Step 2

Press and go to Send Data Wait Time

Set it to 1 (1ms delay feedback)

Press

for 1 sec and go to

Set it to 0 as its the only E5CC unit

Move out From Setting level


Step 2 Step 1

Home Screen

Press and go to home screen

Chapter 2-3-1 Communication & Parameter Setting for E5CC


Unlock Operation & Initial Setting
Step 1
Step 2 Step 3 Step 4

Press and together for 3 sec and go to STEP 18

Press and go to Initial Setting/communication protect

Set it to 0 as we dont need any restrict movement to the initial Setting

Press and together for 1 sec and go home screen

Set Auxiliary output for Alarm 1 & Alarm 2


Step 4 Step 3
Step 2 Step 1

Press until Auxiliary Output 1 Assignment (SUB1)

Press for up/down to -169 for Alarm 1

Press until Advance Function Setting Level

Press for 3 sec for initial setting level

Chapter 2-3-1 Communication & Parameter Setting for E5CC


Set Auxiliary output for Alarm 1 & Alarm 2
Step 1 Step 2 Step 3 Step 4

Press for up/down to ALM1 for when Alarm 1 activate, SUB1 activate

Press until Auxiliary Output 2 Assignment (SUB2)

Press for up/down to ALM2 for when Alarm 1 activate, SUB2 activate

Press for 3 sec and go to home screen

Set Alarm Type for Alarm 1


Step 4 Step 3 Step 2 Step 1

Press

until Alarm type 2

Press for up/down to 2 for Alarm 1

Press

until Alarm 1

Press

for 3 sec and go to

Chapter 2-3-1 Communication & Parameter Setting for E5CC


Set Alarm Type for Alarm 2
Step 1 Step 2 Step 3

Press for up/down to 1 for Alarm 2

Press

until leave Setting Level

That all for the setting up

Chapter 2-3-1 Communication & Parameter Setting for E5CC


NOTE Communications with PLCs from OMRON (CP1E) and Temperature Controller from OMRON (E5CC) can be performed without creating ladder programming. Program-less communication enables monitoring and changing of settings for CP1E is simply by reading and writing into PLC memory. Designing and work hours spent for the programming of communication with PLC during the setup is significantly reduces with program-less communications.

Chapter 2-4
How to read E5CC value from PLC?

Answer: Using PLCs Data Memory Area

Chapter 2-4-1 What will we learn in this topic


Understand The feature of CX-Programmer (For PLC) Learn how to use DM area for communication from PLC to E5CC Set up communication between PLC and HMI Set up communication between PLC and E5CC

Chapter 2-4-2 Setup CX-Programmer


Basic Feature of a CX-Programmer

Toolbar Project Workspace Diagram Workspace

Status Bar

Chapter 2-4-2 Setup CX-Programmer


Create PLC type
Step Description Chapter 2

Click New icon to create PLC program.


New

Select the correct PLC

Select CP1E

Chapter 2-4-2 Setup CX-Programmer


Create PLC type
Step
3

Description
Choose the correct CPU type

Chapter 2

New

PLC type will be display

Select USB to download/upload

Select USB

Chapter 2-4-2 Setup CX-Programmer


Set the PLC setting to the same as the NB HMI
Step
1

Description
Double click on the Setting

Serial COM (RS232C)

PLC Setting pop-up appear, click on Built-in RS232C Port tab to set the Communications Setting

Type Baud Format Mode 7, 2, E

Set 115200 bps Host Link

Chapter 2-4-2 Setup CX-Programmer


Set the PLC setting to the same as the E5CC
Step
1

Description
Double click on the Setting

COMPOWAY

PLC Setting pop-up appear, click on Serial Option Port tab to set the Communications Setting

Type Baud Format Mode

Set 57600 bps 7, 2, E Host Link

Chapter 2-4-2 Setup CX-Programmer


Set the PLC setting to the same as the NB HMI
Step
1

Description
Download program to PLC 1. Click PLC tab > Transfer > Transfer [PC ->PLC] 2. Ctrl + T 3. Click on the icon Check the Settings before download, else there will be no communication between PLC and Inverter due to setting wasnt being transfer. Click OK!

Transfer Program

Chapter 2-4-3 DM Areas to Read E5CC Data


Checking E5CC data link to which DM area
Step
1

Description
In CX-Programmer, change it to online mode

CX-Programmer

Go to Memory
Click here

Chapter 2-4-3 DM Areas to Read E5CC Data


Checking E5CC data link to which DM area
Step
3

Description
PLC Memory pop-up appear, click D which is Data Memory

CX-Programmer

Data Memory

Click Monitor
Click

Chapter 2-4-3 DM Areas to Read E5CC Data


Checking E5CC data link to which DM area
Step
5

Description
Monitor Memory Areas pop-up appear, click monitor

CX-Programmer

Click Monitor

All Data Memory data appear

Chapter 2-4-3 DM Areas to Read E5CC Data


Refer to Communication Manual

D0003=Status (Upper Word) D0004=Status (Lower Word)

D0007 = Process Value D0008=Internal Set Point

S/N
1

Explanation
Data Memory Allocation function (All Area are FIXED) D0007=Process Value D0008=Internal Set Point D0003=Status (Upper Word) D0004=Status (Lower Word)

Communications Manual

Refer to H175-E1-05 Communications Manual, Page 6-29

Chapter 2-5
How to NB HMI read E5CC Data?

Answer: We need to use NB Designer to read E5CC data value

Chapter 2-5-1 What will we learn in this topic


Understand the feature of NB Designer (For NB HMI) The setting for NB HMI How to create link from main page to motor page How to create button activate the motor Set up communication between PLC and HMI

Chapter 2-5-2 Setup NB Designer


Basic Feature of a NB Designer
Title Menu Toolbar

Project files window Component library window HMI edit window

Compile information window

Component list window

Project structure window

State toolbar

Chapter 2-5-2 Setup NB Designer


Create New Project
Step
1

Description
File > New(N) or Ctrl + N to create new project

Connection

Click to Create New project

Create the project name and click ok


Name the Project you desire (EX.Chapter_Demo)

Choose the location of the project

Chapter 2-5-2 Setup NB Designer


Create software connection
Step
1 to 3
Step 1: Select the HMI NB10W-TW01B cos the hardware is NB10WTW01B Here is where you get your HMI, PLC and Connector

Description

Connection

Step 1 Step 2

Step 2: Select the PLC OMRON CP1H/L/E cos the hardware is CP1E Step 3

Step 3: Select Serial Port cos we be using RS232 Cable

Chapter 2-5-2 Setup NB Designer


Start up
Step
1

Description

Connection

Right click on the NB and click Edit to start

Chapter 2-5-2 Setup NB Designer


Setup Communication Setting
Step
1
For CP1E, the Baud rate read either 57600 or 115200 (Ex. For this case, use 115200)

Description

Connection

Default Setting, changes if necessary

Chapter 2-5-2 Setup NB Designer


Method of downloading the drawing to NB Download way System Manager

Chapter 2-5-2 Setup NB Designer


1. 2. Click Tools at toolbar, click Compile to compile the drawing first, if there no problem carry on the next step. Click download to download the drawing

Chapter 2-5-3 Set up I/O list for PV & SV Reading


We be using this range of I/O for this whole chapter
Name
Word Data Memory Data Memory

Address
W11 W19 D200 D299 D0 D99

Read data from E5CC will be using these I/O address stated below:
Name
PV Display SV Display

Address
D7 D8

Chapter 2-5-4 Create E5CC PV & SV Display


Create Present Value(PV) Display
Step
1

Description
Under Basic Attributes tab

PV Display

Data Memory 7 (D7)

Click on Numeric Data tab


Setting

Chapter 2-5-4 Create E5CC PV & SV Display


Create Present Value(PV) Display
Step
3

Description
Click on Graphic tab

PV Display

Data Memory 7 (D7)

Chapter 2-5-4 Create E5CC PV & SV Display


Create Set Value(SV) Display
Step
1

Description
Under Basic Attributes tab

SV Display

Data Memory 8 (D8)

Click on Numeric Data tab


Setting

Chapter 2-5-4 Create E5CC PV & SV Display


Create Set Value(SV) Display
Step
3

Description
Click on Graphic tab

SV Display

Data Memory 8 (D8)

Chapter 2-5-5 Download to NB


1. 2. Click Tools at toolbar, click Compile to compile the drawing first, if there no problem carry on the next step. Click download to download the drawing

Chapter 2-5-6 View Reading of PV & SV


Run and Test
Step
1

Description
Click on the Chapter 2-1 to go Frame 12

HMI View

You can see the Present Value and Set value display on the NB HMI

Chapter 2-5-6 View Reading of PV & SV


Changing Speed by entering value
E5CC View HMI View

Step 3: STOP button can still stop drive in either mode

The Set value from the E5CC data display on the HMI

Press up to increase the Set value (SV) to 30

Chapter 2-5-7 Address for E5CC Control Status


Refer from the manual
Upper Word Lower Word

S/N
1

Explanation
Status There are 3 status set for the E5CC but we be using 2: Status (Upper Word) Status (Lower Word)

Table

Chapter 2-5-7 Address for E5CC Control Status


Refer from the manual
Upper Word

S/N
2

Explanation
Upper Word Status We be using D0003 and if we want to do a stop button we will use D3.08 In the manual, RUN/STOP is 24 but 1 word is 16 bits and there no 24 in 1 word so we take 16-31 and change it to 0-15 and from there, we assign the bit

Table

Chapter 2-5-7 Address for E5CC Control Status


Refer from the manual
Lower Word

S/N
2

Explanation
Lower Word Status We be using D0004 and if we want an alarm 1 to activate, we will use D4.12

Table

Chapter 2-5-8 Create E5CC Alarm 1 Status


Create E5CC Status (Alarm 1)
Step
1

Description
Under Basic Attributes tab

Alarm 1 Status

Click on Bit State Lamp tab

Chapter 2-5-8 Create E5CC Alarm 1 Status


Create E5CC Status (Alarm 1)
Step
3 Click Tag tab

Description

Alarm 1 Status

Name the Indicating Lamp

Click on Graphics tab

Choose any Lamp picture

Chapter 2-5-9 Create E5CC Status


Let try create Alarm 2, Output Control, Communication and Stop
S/N
1

Description
The address is stated below Alarm 2

Example

Output Control

Communication

Stop

Chapter 2-5-10 Create Stop & Run Button


Create STOP and RUN button for the E5CC
Step
1

Description
Under Basic Attributes tab
Explanation on the next few slide

STOP Button

Setting Mode

Chapter 2-5-10 Create Stop & Run Button


Create STOP and RUN button for the E5CC
Step
3 Click on Tag tab

Description

STOP Button

Click on Bit State Lamp tab

Chapter 2-5-10 Create Stop & Run Button


Create STOP and RUN button for the E5CC
Step
5

Description
Click on Graphics tab

STOP Button

Chapter 2-5-10 Create Stop & Run Button


Create STOP and RUN button for the E5CC
Step
6

Description
Click on Control Setting, at the Touching Enable Setting
Using Register to control the button. (Ex. If D16.00 is ON, then the STOP button is able to click)

STOP Button

At Control Register, Set to D16.00

Using a fix register control

Chapter 2-5-10 Create Stop & Run Button


Create STOP and RUN button for the E5CC
Step
1

Description
Under Basic Attributes tab

RUN Button

Click on Bit State Lamp tab

Chapter 2-5-10 Create Stop & Run Button


Create STOP and RUN button for the E5CC
Step
3

Description
Click on Tag tab, Name the button RUN

RUN Button

Font Size and color

Chapter 2-5-10 Create Stop & Run Button


Create STOP and RUN button for the E5CC
Step
5

Description
Click on Graphics tab

RUN Button

Chapter 2-5-10 Create Stop & Run Button


1. 2. Click Tools at toolbar, click Compile to compile the drawing first, if there no problem carry on the next step. Click download to download the drawing

Chapter 2-5-11 NB Display


Test the E5CC Status
Step
1

Description
Click on the Chapter 2-1 to go Frame 12

HMI View

You can see the Status of the E5CC on the NB HMI display

Chapter 2-5-11i Status between E5CC with HMI


Changing Speed by entering value
E5CC View HMI View

E5CC currently in RUN mode, Output Control is active

You can see that the OUT1 is activated

Step 2: You can see that the Output Control is OFF

Step 1: Press Stop to stop the E5CC Output Control

Step 3: You can see that the OUT1 is OFF and STOP is activated

Chapter 2-6
Writing to E5CC using NB Designer

Chapter 2-6-1 Write SV Values to E5CC


Write data will be using these I/O address stated below:
Name
Change SV value

Address
D17

Chapter 2-6-1 Write SV Values to E5CC


Create SV Number Input
Step
1

Description
Under Basic Attributes tab, enter address D17

SV Number Input

Click on Numeric Data tab


Setting

Chapter 2-6-1 Write SV Values to E5CC


Create SV Number Input
Step
3

Description
Click on Graphics tab

SV Number Input

Chapter 2-6-1 Write SV Values to E5CC


Create SV Number Input
Step
4

Description
Under Basic Attributes tab, enter address D17

SV Add

Click on Numeric Data tab

Setting

Chapter 2-6-1 Write SV Values to E5CC


Create SV Number Input
Step
6

Description
Click on Graphic tab

SV Add

Chapter 2-6-1 Write SV Values to E5CC


Create SV Number Input
Step
7

Description
Under Basic Attributes tab, enter address D17

SV Subtract

Click on Numeric Data tab

Setting

Chapter 2-6-1 Write SV Values to E5CC


Create SV Number Input
Step
9

Description
Click on Graphic tab

SV Subtract

Chapter 2-6-2 Create Write Values Button


Create Send Values button
Step
1

Description
Under Basic Attributes tab, enter address D15.00

SV Number Input

Click on Bit State Switch tab

Setting

This is to enable the Data to be send to E5CC

Chapter 2-6-2 Create Write Values Button


Create Send Values button
Step
3

Description
Click on tag tab to name the Button

SV Number Input

Click on Graphic tab

This is to enable the Data to be send to E5CC

Chapter 2-6-2 Create Write Values Button


Create Send Values button
Step
5

Description
Click on Control Setting tab, Set condition that when the register the activated the button can be press

SV Number Input

The Register that control is W16.00 which the communication is ON

This is to enable the Data to be send to E5CC

Chapter 2-6-3 Create Read Values Button


Create Read Values Button
Step
1

Description
Under Basic Attributes tab, Component List will be Multiple State Setting

Read Values Button

Writing Address using D15

This is to enable the Data to be Read from E5CC

Chapter 2-6-3 Create Read Values Button


Create Read Values Button
Step
3

Description
Setting Mode set as constant and value is 2

Read Values Button

Click on Tag tab to name the button

This is to enable the Data to be Read from E5CC

Chapter 2-6-3 Create Read Values Button


Create Read Values Button
Step
5

Description
Click on Graphics tab

Read Values Button

Click on Control Setting tab, Set conditional Enabling

This is to enable the Data to be Read from E5CC

Chapter 2-6-3 Create Read Values Button


Create Read Values Button
Step
7

Description
Enter the Register to control the button, D16.00 bit

Read Values Button

This is to enable the Data to be Read from E5CC

Chapter 2-6-4 Download to NB


1. 2. Click Tools at toolbar, click Compile to compile the drawing first, if there no problem carry on the next step. Click download to download the drawing

Chapter 2-6-5 NB Display


Testing Write and Read Values
Step
1

Description
Click on the Chapter 2-1 to go Frame 12

HMI View

Next slide show the result

Chapter 2-6-5i E5CC with HMI


2 method of writing Set value to E5CC through NB HMI
HMI View E5CC View

Method 1: Clicking on the display input, tenkey pad popup appear for you to key in the value (Ex. We key in 50)

Method 2: Clicking on the plus or minus button to increase/decrease the value (Ex. We key in 50)

Chapter 2-6-5i E5CC with HMI


We will write Set value to E5CC through NB HMI
HMI View E5CC View

Step 1: Press Write Value button

The value have been overwritten to the E5CC

The value have been overwritten to the E5CC from 30 to 50

Chapter 2-6-5i E5CC with HMI


We will Read Set value from E5CC to NB HMI
E5CC View HMI View

Let Decrease the set value (SV) from E5CC (Ex. Decrease value to 30.0)

Step 1: Press Read Value button

Chapter 2-6-5i Compare E5CC and HMI


We will Read Set value from E5CC to NB HMI
E5CC View HMI View

Step2: Value from the E5CC will send to NB HMI display (Ex. Display value 30)

Chapter 2-7
Create E5CCs Alarm 1 And Alarm 2 in NB Designer

Chapter 2-7-1 Create Alarm1 Setting input


Create Alarm 1 Setting
Step
1

Description
Under Basic Attributes tab, enter address D21

Alarm 1 (SUB1)

Create Alarm 1 Display

Click on Numeric tab

Chapter 2-7-1 Create Alarm1 Setting input


Create Alarm 1 Setting
Step
3

Description
Click on Graphics tab

Alarm 1 (SUB1)

Chapter 2-7-2 Create Alarm2 Setting input


Create Alarm 2 Setting
Step
1

Description
Under Basic Attributes tab, enter address D25

Alarm 2 (SUB2)

Click on Numeric tab


Create Alarm 2 Upper Limit

Chapter 2-7-2 Create Alarm2 Setting input


Create Alarm 2 Setting
Step
3

Description
Click on Graphics tab

Alarm 2 (SUB2)

Chapter 2-7-2 Create Alarm2 Setting input


Create Alarm 2 Setting
Step
4

Description
Under Basic Attributes tab, enter address D26

Alarm 2 (SUB2)

Click on Numeric tab


Create Alarm 2 Lower Limit

Chapter 2-7-2 Create Alarm2 Setting input


Create Alarm 2 Setting
Step
6

Description
Click on Graphics tab

Alarm 2 (SUB2)

Chapter 2-7-3 Download to NB


1. 2. Click Tools at toolbar, click Compile to compile the drawing first, if there no problem carry on the next step. Click download to download the drawing

Chapter 2-7-4 NB Display


Test it out
Step
1

Description
Click on the Chapter 2-1 to go Frame 12

HMI View

Next slide show the result

Chapter 2-7-4i Compare E5CC and HMI


Function of Alarm 1 (SUB1)
HMI View E5CC View

Key in value 1 (This mean that PV must not be more than the Set Value by 1)

You need to click on Write value button as to transfer the setting to E5CC

Chapter 2-7-4i Compare E5CC and HMI


Function of Alarm 1 (SUB1)
HMI View E5CC View

Value for the SV and PV is the same so the Alarm 1 sill not be activate Alarm 1 (SUB1) is not activate as PV is not higher than SV by 1

Value for the SV is higher then the PV by 1, so Alarm 1 activate and Output Control de-activated
Alarm 1 (SUB1) is activated as PV is higher than SV by 1

Chapter 2-7-4i Compare E5CC and HMI


Function of Alarm 2 (SUB2)
HMI View E5CC View

Key in value for upper limit and lower limit range (Ex. Upper = 5.0 and Lower is 5.0)

You need to click on Write value button as to transfer the setting to E5CC

Chapter 2-7-4i Compare E5CC and HMI


Function of Alarm 2 (SUB2)
HMI View E5CC View

Alarm 2 (SUB2) is de-activated as the PV is within the upper and the lower limit of SV (Ex. PV must not be higher then 35 and lower then 25)

Alarm 2 (SUB2) is activated as the PV is over the upper limit of SV (Ex. PV now is higher then 35)

Chapter 2-8
Create Trend Curve to view different value at different time

Chapter 2-8-1 Create a New Frame Page and Link


Create a Frame13
Step
1

Description
Go to Toolbar
Click on the Add Window icon

New Frame

Pop-up appear

Frame ID start from 10 as Frame 1 to 9 is used for special window

Frame Name start from Frame10 as Frame 1 to 9 is used for special window. (Name can be change)

New Frame being created

View form Toolbar

Frame has be added once click OK in Step 2

Chapter 2-8-1 Create a New Frame Page and Link


Create a button to go to Frame13
Step
1

Description
Function Key tab

Chapter 4-1 Button

Click on Tag tab


Check Use Tag to display text on the icon When it not activate is state 0, display text

Click and drag the icon and do the setting, after finishes the setting, click to the location you desire.

Click on Graphic tab

Select the design of the button

Chapter 2-8-2 Create Trend Curve Graph


Create Trend Graph to view PV and SV value
Step
1

Description
Under Basic Attributes tab, enter address D7 for PV

Trend Graph

Chapter 2-8-2 Create Trend Curve Graph


Create Trend Graph to view PV and SV value
Step
2

Description
Under Trend Graphics tab
1st: Set this to enable SCROL

Trend Graphic

2nd : 2 signal

Under Control Register Setting, Check PauseClear as to pause the trend graphic

We will be using LB15 to pause the trend graph

Chapter 2-8-2 Create Trend Curve Graph


Create Trend Graph to view PV and SV value
Step
4

Description
Check SCROL as to browse multiple trend
Word length is 3 so if the specified register is LW90 then LW90, LW91 and LW92 will be the current browsing index value

Trend Graphic

Check Time is to save the time of the trend graph


For Starting point is LW30, LW31, LW32, LW33, LW34, LW35 respectively, and the Second, Minute, Hour, Day, Month, Year For the end point is LW36, LW37, LW38, LW39, LW40, LW41 respectively.

Chapter 2-8-2 Create Trend Curve Graph


Create Trend Graph to view PV and SV value
Step
6

Description
Click Channel tab to add 2 trends graphic

Trend Graphic

Set min = 0 and max = 50

Click Extended Attributes tab to change the line & columns and the color of the trend

Chapter 2-8-2 Create Trend Curve Graph


Create Trend Graph to view PV and SV value
Step
8

Description
Click Save Historical Data tab then check on the Save to External Device.

Trend Graphic

Save the Data to the Subdirectory(Folder )

Chapter 2-8-2 Create Trend Curve Graph


Create Pause button for trend graph
Step
1

Description
Click Basic Attribute tab to add address

Pause Button

Click Bit State Switch tab to make the button toggle

Chapter 2-8-2 Create Trend Curve Graph


Create Pause button for trend graph
Step
3

Description
Click Tag tab to name the button

Pause Button

Click Graphics tab to Select the button design

Chapter 2-8-2 Create Trend Curve Graph


Create Scroll bar to scroll back
Step
1

Description
Click Basic Attribute tab to add address

Trend Graphic

Chapter 2-8-2 Create Trend Curve Graph


Create Scroll bar to scroll back
Step
2

Description
Click Scroll Bar tab, at background Image

Trend Graphic

We will be selecting DIS_BAR002.vg (You can get more image at Import Image)

Button Image is to color the scrolling button

We will be selecting button2-04.bg (You can get more image at Import Image)

Chapter 2-8-2 Create Trend Curve Graph


Create Scroll bar to scroll back
Step
4

Description
Click Scroll Bar Extended Attributes tab as to set the scrolling distance
Select Slider Width and set the distance you required

Trend Graphic

Variable Max/Min Value

When register is LW90, LW91 and LW92 will be the current browsing index value, the starting browsing index value and the maximum browsing index value of Scroll Bar respectively. This option is valid only when Multiple pages is selected. SCRO can be used to browse the multiple Trend Curves and can be in combination with the Scroll Bar.

Chapter 2-8-2 Create Trend Curve Graph


Let create start display 1st
Step
1

Description
Create a background graphic by drawing a rectangle

Trend Graphic

Geographic Figure

Create a background Let choose white line and white background color

Chapter 2-8-2 Create Trend Curve Graph


Let create start display 1st
Step
1

Description
Under Basic Attributes tab as to set the scrolling distance

Timing (Second)

Click Numeric Data tab, value is up to 59 as it seconds is from 0-59

When the specified address is LW30, the Second, Minute, Hour, Day, Month, Year for the start point in the current page is LW30, LW31, LW32, LW33, LW34, LW35 respectively, and the Second, Minute, Hour, Day, Month, Year for the end point is LW36, LW37, LW38, LW39, LW40, LW41 respectively.

Chapter 2-8-2 Create Trend Curve Graph


Let create start display 1st
Step
3

Description
Click Font tab as change color and size

Timing (Second)

When the specified address is LW30, the Second, Minute, Hour, Day, Month, Year for the start point in the current page is LW30, LW31, LW32, LW33, LW34, LW35 respectively, and the Second, Minute, Hour, Day, Month, Year for the end point is LW36, LW37, LW38, LW39, LW40, LW41 respectively.

Chapter 2-8-2 Create Trend Curve Graph


Let create start display 1st
Step
4

Description
Under Basic Attributes tab as to set the scrolling distance

Timing (Minutes)

Click Numeric Data tab, value is up to 59 as it seconds is from 0-59

When the specified address is LW30, the Second, Minute, Hour, Day, Month, Year for the start point in the current page is LW30, LW31, LW32, LW33, LW34, LW35 respectively, and the Second, Minute, Hour, Day, Month, Year for the end point is LW36, LW37, LW38, LW39, LW40, LW41 respectively.

Chapter 2-8-2 Create Trend Curve Graph


Let create start display 1st
Step
6

Description
Click Font tab as change color and size

Timing (Minutes)

When the specified address is LW30, the Second, Minute, Hour, Day, Month, Year for the start point in the current page is LW30, LW31, LW32, LW33, LW34, LW35 respectively, and the Second, Minute, Hour, Day, Month, Year for the end point is LW36, LW37, LW38, LW39, LW40, LW41 respectively.

Chapter 2-8-2 Create Trend Curve Graph


Let create start display 1st
Step
7

Description
Under Basic Attributes tab as to set the scrolling distance

Timing (Hour)

Click Numeric Data tab, value is up to 59 as it seconds is from 0-59

When the specified address is LW30, the Second, Minute, Hour, Day, Month, Year for the start point in the current page is LW30, LW31, LW32, LW33, LW34, LW35 respectively, and the Second, Minute, Hour, Day, Month, Year for the end point is LW36, LW37, LW38, LW39, LW40, LW41 respectively.

Chapter 2-8-2 Create Trend Curve Graph


Let create start display 1st
Step
9

Description
Click Font tab as change color and size

Timing (Hour)

When the specified address is LW30, the Second, Minute, Hour, Day, Month, Year for the start point in the current page is LW30, LW31, LW32, LW33, LW34, LW35 respectively, and the Second, Minute, Hour, Day, Month, Year for the end point is LW36, LW37, LW38, LW39, LW40, LW41 respectively.

Chapter 2-8-2 Create Trend Curve Graph


Let insert : in between hour & minutes and minutes & second
Step
10

Description
Click Text at the toolbar, Text Attribute pop-up appear. At the content, type : and click ok. Place it between hour & minutes and minutes & second

Insert :

Chapter 2-8-2 Create Trend Curve Graph


Let create END display timing
Step
1

Description
Under Basic Attributes tab as to set the scrolling distance

Timing (Second)

Click Numeric Data tab, value is up to 59 as it seconds is from 0-59

When the specified address is LW30, the Second, Minute, Hour, Day, Month, Year for the start point in the current page is LW30, LW31, LW32, LW33, LW34, LW35 respectively, and the Second, Minute, Hour, Day, Month, Year for the end point is LW36, LW37, LW38, LW39, LW40, LW41 respectively.

Chapter 2-8-2 Create Trend Curve Graph


Let create END display timing
Step
3

Description
Click Font tab as change color and size

Timing (Second)

When the specified address is LW30, the Second, Minute, Hour, Day, Month, Year for the start point in the current page is LW30, LW31, LW32, LW33, LW34, LW35 respectively, and the Second, Minute, Hour, Day, Month, Year for the end point is LW36, LW37, LW38, LW39, LW40, LW41 respectively.

Chapter 2-8-2 Create Trend Curve Graph


Let create END display timing
Step
4

Description
Under Basic Attributes tab as to set the scrolling distance

Timing (Minutes)

Click Numeric Data tab, value is up to 59 as it seconds is from 0-59

When the specified address is LW30, the Second, Minute, Hour, Day, Month, Year for the start point in the current page is LW30, LW31, LW32, LW33, LW34, LW35 respectively, and the Second, Minute, Hour, Day, Month, Year for the end point is LW36, LW37, LW38, LW39, LW40, LW41 respectively.

Chapter 2-8-2 Create Trend Curve Graph


Let create END display timing
Step
6

Description
Click Font tab as change color and size

Timing (Minutes)

When the specified address is LW30, the Second, Minute, Hour, Day, Month, Year for the start point in the current page is LW30, LW31, LW32, LW33, LW34, LW35 respectively, and the Second, Minute, Hour, Day, Month, Year for the end point is LW36, LW37, LW38, LW39, LW40, LW41 respectively.

Chapter 2-8-2 Create Trend Curve Graph


Let create END display timing
Step
7

Description
Under Basic Attributes tab as to set the scrolling distance

Timing (Hour)

Click Numeric Data tab, value is up to 59 as it seconds is from 0-59

When the specified address is LW30, the Second, Minute, Hour, Day, Month, Year for the start point in the current page is LW30, LW31, LW32, LW33, LW34, LW35 respectively, and the Second, Minute, Hour, Day, Month, Year for the end point is LW36, LW37, LW38, LW39, LW40, LW41 respectively.

Chapter 2-8-2 Create Trend Curve Graph


Let create END display timing
Step
9

Description
Click Font tab as change color and size

Timing (Hour)

When the specified address is LW30, the Second, Minute, Hour, Day, Month, Year for the start point in the current page is LW30, LW31, LW32, LW33, LW34, LW35 respectively, and the Second, Minute, Hour, Day, Month, Year for the end point is LW36, LW37, LW38, LW39, LW40, LW41 respectively.

Chapter 2-8-2 Create Trend Curve Graph


Let insert : in between hour & minutes and minutes & second
Step
10

Description
Click Text at the toolbar, Text Attribute pop-up appear. At the content, type : and click ok. Place it between hour & minutes and minutes & second

Insert :

Chapter 2-8-3 Download to NB


1. 2. Click Tools at toolbar, click Compile to compile the drawing first, if there no problem carry on the next step. Click download to download the drawing

Chapter 2-8-4 NB Display


Test Trend Graph Function
Step
1

Description
Click on the Chapter 2-2 to go Frame 13

HMI View

Next slide show the result

Chapter 2-8-4i E5CC with HMI


Monitor PV and SV trend graph
HMI View E5CC View

The PV and SV display

The time value display show the starting of the NB HMI

The time value display show the current timing

The PV and SV display

Scrolling is unable to sc

Chapter 2-8-4ii Review previous trending


Review previous trend or previous page
HMI View E5CC View

1st: Click on the Pause button to pause the on going trending 2nd: Scroll left to view newest trend graph and right to earliest trend graph

When you start scrolling to view the earlier trend graph, the start timing display will indicate the time when the trend start and the end timing display will indicate the time when the trend end.

Chapter 3-9
How can I get the trend graph data?

Answer: From the USB Flash Drive

Chapter 2-9-1 Read Trend Graph Data from USB Flash Drive
From the USB Flash Drive
Step
1

Description
Unplug the USB Drive from the NB HMI

USB Flash Drive

Plug in the USB Drive to the PC, go to my computer to find the USB Flash Drive

Chapter 2-9-1 Read Trend Graph Data from USB Flash Drive
From the USB Flash Drive
Step
3

Description
Double click on the USB Flash Drive and double click on trend folder

USB Flash Drive

Double click on Historytrend folder and you will see the CSV file of the trend curve with the name of YYYYMMDD format

Chapter 2-9-1 Read Trend Graph Data from USB Flash Drive
From the USB Flash Drive
Step
5

Description
Double click on the csv file, excel will activate and the file will open in encrypted format

USB Flash Drive

Detail unreadable

Chapter 2-9-2 Decrypt the CSV file


2 Method to NBManager
Method 1
At the toolbar, click on Tools > System Manager > Decompile Operate

Method 2
Click on Start > All Programs > scroll to Omron folder > NB Designer > Tools > NBManager

Chapter 2-9-2 Decrypt the CSV file


2 Method to NBManager
Step
1

Description
Click on the Decrypte Historic Data File at Decrypte Operation

Timing (Second)

Pop-up Open appear. At Look in, look for Computer > Find USB Flash Drive

Chapter 2-9-2 Decrypt the CSV file


2 Method to NBManager
Step
3

Description
Click on the CSV file of the trend curve with the name of YYYYMMDD format. Click OPEN

Timing (Second)

Pop-up message appear informing Decrypte success

Chapter 2-9-2 Decrypt the CSV file


2 Method to NBManager
Step
5

Description
Go to Computer > Double click on the USB Flash Drive

Timing (Second)

Double click on Trend > Double click on HistoryTrend

After Decrypted the file name remain the same with _new to it

Chapter 2-9-2 Decrypt the CSV file


From the USB Flash Drive
Step
7

Description
Double click on the csv file, excel will activate and the file will open in decrypted format

Timing (Second)

Now detail is readable

Chapter 2-9-3 Create Historical Data Display


Let create background for the Date and Time
Step
1

Description
At the Filling sector, change the background color of your liking. (Ex. For this project, we be using white color)
Place the background here

Date

Chapter 2-9-3 Create Historical Data Display


Let create Date display
Step
2

Description
Under Time tab, check on the Display Date > set it to YY*MM*DD format and the Date Separator /.
Place the Date/Time here

Date

Want to view what day is it? Just check on the Display Week

We want to view the full display of the year so by checking on the Year 4-digit Display

Normally, Date/Time can be put together but for this case, we separate it

Chapter 2-9-3 Create Historical Data Display


Let create Time display
Step
3

Description
Under Time tab, check on the Display Time > set it to HH*MM*SS format and the Date Separator /.

Time
Place the Date/Time here

Want to view timing in AM and PM format? Check on this

Normally, Date/Time can be put together but for this case, we separate it

Chapter 2-9-3 Create Historical Data Display


Create Historical Data Display
Step
1

Description
Under Basic Attributes tab, fill in the Address D7

Display

Chapter 2-9-3 Create Historical Data Display


Create Historical Data Display
Step
2

Description
Click on Display Properties tab, select 2 channel as we going to get 2 data. From D7 and D8

Display

Check on Historical Data Query, Key in the Address D100

Chapter 2-9-3 Create Historical Data Display


Create Historical Data Display
Step
4

Description
Click on Background Attribute tab

Display

2nd : Select Time sampling as we are getting sample every cycle

1st: Select continue as we want to keep reading data

3rd: Select how many sample you want every cycle

4th : Select how many cycle within a time frame

Chapter 2-9-3 Create Historical Data Display


Create Historical Data Display
Step
5

Description
Click on Channel Properties tab

Display

1st: Set the data type to 16-bit signed

2nd : Set the minimum value

4th : Set to 2 integer as 2 digit only

3rd : Set the maximum value

Chapter 2-9-3 Create Historical Data Display


Create Historical Data Display
Step
6

Description
Click on Save historical Data tab
1st: Set the data type to 16-bit signed

Display

2nd : Name the file where the data going to keep 3rd : Set it to default as it keep on saving data

Chapter 2-9-3 Create Historical Data Display


Create Historical Data Display
Step
7

Description
Click on Title bar Properties tab

Display

Name the Channel 0 as PV as it start from D7

This show the sequence in the display

Name the Channel 1 as SV as it start from D8

Chapter 2-9-3 Create Historical Data Display


Create Query By Date function with
Step
1

Description
Under Basic Attributes tab, set address to D100

Date

Click on Numeric Data


Value is 8 as the date is 8 digit yyyymmdd 1 word = 4 digit 2 word = 8 digit

Chapter 2-9-3 Create Historical Data Display


Create Query By Date function with
Step
3

Description
Click Graphics tab and select DISP_Bar002.vg

Date

Chapter 2-9-4 Safety Remove USB flash Drive


Let create safety remove button
Step
1

Description
Under Basic Attributes tab, select System Register and choose LB9154

Date

Click on Bit State Switch tab, select Toggle

Chapter 2-9-4 Safety Remove USB flash Drive


Let create safety remove button
Step
3 Click Tag tab
1st: Set the data type to 16-bit signed

Description

Date

Click on Graphics
1st: Set the data type to 16-bit signed

Chapter 2-9-5 Download to NB


1. 2. Click Tools at toolbar, click Compile to compile the drawing first, if there no problem carry on the next step. Click download to download the drawing

Chapter 2-9-6 NB Display


Test it out
Step
1

Description
Click on the Chapter 2-2 to go Frame 13

HMI View

Next slide show the result

Chapter 2-9-6i Is it safe to remove USB Flash Drive?


Let try safety remove USB Flash Drive
HMI View HMI Hardware

Click on the button to safety remove the USB Flash Drive

Click on the button to safety remove the USB Flash Drive

This mean that the USB Flash Drive is removed

Chapter 2-9-6ii How to view previous data?


Let try to view previous data
HMI View HMI Hardware

Type in the date that you want to view the past data (Ex. Let view 20130530 data)

Insert the USB Flash Drive to the HMI

The data on the previous day will be display

Information

E5CC Catalogs/Manuals: http://www.omron-ap.com/downloads/pdf_listing.asp?product_model=E5CC&catlvl=78 E5CC Communication Manual (H175-E1-05): http://www.omronap.com/admin/access_download.asp?from=pdf_E5CC&catlvl=78&to=H175&product_m odel=E5CC&open=0

END of Chapter 2
Thank you!