Application
The MRA4 is a protection relay which uses the latest Dual-Core-Processor Technology to provide precise and reliable protective functions and is very easy to operate. Its various protective functions are specifically tailored to the protection of incoming and outgoing feeders in MV systems. It also can be used for grid and generator protection. All inclusive: All protection features without extra charge Parameter setting and evaluation software Disturbance record analysis software Six stages phase overcurrent protection Directional and non-directional overcurrent/short-circuit protection Tripping characteristics: DEFT ANSI: NINV, VINV, EINV IEC: NINV, VINV, LINV, EINV Thermal Flat, IT, I2T, I4T Voltage controlled
Functional Overview
PRotEctIVE FUNctIoNs
I, time overcurrent and short circuit protection, all stages can be configured for directional or non-directional supervision. Tremendous reset options (instantaneous, definite time, reset characteristics according to IEC and ANSI). Voltage controlled overcurrent protection by means of adaptive parameters. I2>, unbalanced load protection with evaluation of the negative phase sequence currents IB, overload protection with thermal replica and separate pick-up values for alarm and trip functions IH2/In, inrush detection with evaluation of the 2nd harmonic IE, earth overcurrent and short circuit protection, all stages can be configured for directional or nondirectional supervision. Tremendous reset options (instantaneous, definite time, reset characteristics according to IEC and ANSI). Voltage controlled overcurrent protection by means of adaptive parameters. V<, V>, V(t)<, under- and overvoltage protection, time dependent undervoltage protection Voltage asymmetry supervision (V012) V1, under and overvoltage in positive phase sequence system V2, overvoltage in negative phase sequence system Each of the six frequency protection stages can be used as: f< or f> (over- and under frequency supervision) df/dt rate of change of frequency (ROCOF) (f< and df/dt) or (f> and df/dt) combination of over-, under- and rate of change of frequency (ROCOF) (f< and DF/DT) or (f> and DF/DT) combination of over-, under- and increase of frequency Delta Phi (Vector surge) VE, residual voltage protection AR, automatic reclosing ExP, External alarm and trip functions PQS, Power protection PF, Power factor 2 1 4 6 2 32, 37 55 78 59N 79
Elements
6
ANSI
50P, 51P, 67P
6 2 1 1 4
4 4 6 6
51V 27, 59 47
81U/O 81R
SUpERVIsIoN fUNctIoNs
CBF, circuit breaker failure protection TCS, trip circuit supervision VTS, voltage transformer supervision by comparing phase and residual voltages VTS, fuse failure protection via digital input CTS, current transformer supervision CLPU, cold load pickup SOTF, switch onto fault Non volatile event recorder up to 120 s with 32 samples per cycles
Elements
1 1 1 1 1 1 1
ANSI
50BF 74TC 60FL 60FL 60L
79
74 TC
46
49
Inrush
50 BF
50P
51P
67P
67N
V, VE, V012, I, IG, f, IGH2, I012, P, Q, S, PF, cos phi, W Fault recorder Event recorder
3 1
37 32 47 60L 55
SOTF
CLPU
Disturbance recorder
Connections
MRA4
Hardware variant 2 Standard Housing and mounting Door mounting Door mounting 19 (flush mounting) Communication protocol Protocol/without protocol RS485/terminals, Modbus RTU, IEC60870-5-103 Ethernet (RJ45), Modbus TCP, IEC61850* prepared (Hardware/Interface) Optic fiber, Modbus RTU, IEC60870-5-103 RS485/D-SUB, Profibus**, Modbus RTU, IEC60870-5-103 Presetting of available menu languages Standard English/German
* Additional cost for the software update tool IEC61850 per device are 250 . The devices can be updated via device front interface (RS232) and PC locally Expected availability: 01.01.2010 **expected 07.09
Current inputs Voltage inputs Digital Inputs Power supply Terminals Mounting Type of enclosure Dimensions of housing Weight (max. components)
4 (1 A and 5 A) with automatic short circuiters 4 (0 - 800 V) Switching thresholds adjustable via software Wide range power supply All terminals plug type Door mounting IP54 212.7 mm x 173 mm x 209 mm (W x H x D) approx. 4 kg