Sunteți pe pagina 1din 2

CALCULO DEL SISTEMA DE ABASTECIMIENTO DE AGUA POTABLE

1.- PROYECTO
MEJORAMIENTO Y AMPLIACION DEL SERVICIO DE AGUA POTABLE Y DISPOSICION SANITARIA DE EXCRETAS EN EL C.P. EL MILAGRO, DISTRITO DE PICHANAQUI,
PROVINCIA DE CHANCHAMAYO, DEPARTAMENTO JUNIN.
A.- POBLACION ACTUAL (ESTIMADO)

206

AO BASE 2013(PADRN)

209 AO CERO 2014


B.- TASA DE CRECIMIENTO (%)

1.25

C.- PERIODO DE DISEO (AOS)

20

D.- POBLACION FUTURA

268

Pf = Po * ( 1+ r*t/100 )
E.- DOTACION (LT/HAB/DIA)

120.00

F.- CONSUMO PROMEDIO ANUAL (LT/SEG)


Q = Pob.F.* Dot./86,400

A 0 AOS

0.29

25.08

QF = Pob.F.* Dot./86,400

A 20 AOS

0.37

32.16

G.- CONSUMO MAXIMO DIARIO (LT/SEG)


Qmd = 1.30 * QF

0.65

H.- CAUDAL DE LA FUENTE (LT/SEG)

1.82

157.25

I.- VOLUMEN DEL RESERVORIO (M3)


V = 0.20 * Qmd *86400/1000

11.15
15.00

A UTILIZAR :
J.- CONSUMO MAXIMO HORARIO (LT/SEG)
Qmh = 2 * Qmd = 2.60 Q

1.29

LINEA DE CONDUCCION
TRAMO
CAPT. 1
PTO 2
PTO2
PTO3
PTO3
PTO4

NIVEL
LONGITUD
DINAMICO
(KM)
837.32
785.00
785.00
730.00
730.00
675.00

CAUDAL
DIAM.
PENDIENT DIAMETRO
DEL
COMERCI
E
(")
TRAMO
AL

VELOCIDAD
FLUJO

Hf

0.740

0.65

70.70

1.03

1.50

0.57

8.41

0.312

0.65

176.28

0.85

1.00

1.27

25.54

0.129

0.65

426.36

0.71

1.00

1.27

10.56

ALTURA
CLASE DE PRESION
PIEZOMETRI PRESION
TUBERIA ESTATICA
CA
837.32
828.91
785.00
759.46
730.00
719.44

43.91

C-7.5

52.32 C-7.5

29.46

C-5

55.00 C-10

44.44

C-7.5

55.00 C-10

PTO4
PTO5
PTO 5
PTO 6
PTO 6
PTO 7
PTO 7
PTO 8

675.00
620.00
620.00
565.00
565.00
510.00
510.00
455.00

0.138

0.65

398.55

0.72

1.00

1.27

11.30

0.249

0.65

220.88

0.82

1.00

1.27

20.38

0.228

0.65

241.23

0.80

1.00

1.27

18.67

0.154

0.65

357.14

0.74

1.00

1.27

12.61

VELOCIDAD
FLUJO

Hf

675.00
663.70
620.00
599.62
565.00
546.33
510.00
497.39

43.70

C-7.5

55.00 C-10

34.62

C-5

55.00 C-10

36.33

C-7.5

55.00 C-10

42.39

C-7.5

55.00 C-10

LINEA DE ADUCCION
TRAMO

NIVEL
LONGITUD
DINAMICO
(KM)

RESERVORIO
PTO- 8.1
RESERVORIO
PTO-12

455.00
438.00
455.00
445.80

LINEA DE DISTRIBUCION
TRAMO

PTO - 8.1
PTO -9
PTO 9
PTO 12
PTO-13
PTO14
PTO-15
PTO -16
PTO -17
PTO-18
PTO-16
PTO-17
PTO-18
PTO-12
PTO-27
PTO-27
PTO-26
PTO-25
PTO-25
PTO-24
PTO-23
PTO-22
PTO-21

PTO - 9
PTO-10
PTO-11
PTO13
PTO-14
PTO-15
PTO-16
PTO -17
PTO-18
PTO-19
PTO-30
PTO-31
PTO-32
PTO-27
PTO-28
PTO-26
PTO-25
PTO-29
PTO-24
PTO-23
PTO-22
PTO-21
PTO-20

CAUDAL
DIAM.
PENDIENT DIAMETRO
DEL
COMERCI
E
(")
TRAMO
AL

0.949

0.21

17.91

0.89

1.50

0.18

1.35

0.214

1.17

42.99

1.43

1.50

1.03

7.31

Q
(lts./ s.)

hf
( m/m. )

ALTURA
CLASE DE PRESION
PIEZOMETRI PRESION
TUBERIA ESTATICA
CA
455.00
453.65
455.00
447.69

15.65

C-5

17.00 C-5

1.89

C-5

9.20 C-5

COTA DE TERRENO

COTA PIEZOM.

INICIAL
( msnm )

FINAL
( msnm )

LONG.
(m)

Viviendas
Alimentadas
(Metros)

438.00
427.80
427.80
445.80
438.00
433.00
431.50
429.50
429.00
427.30
429.50
429.00
427.30
446.00
437.00
437.00
434.50
432.50
432.50
430.50
429.80
427.00
427.00

427.80
427.00
424.00
438.00
433.00
431.50
429.50
429.00
427.30
426.00
430.00
428.00
427.00
437.00
436.00
434.50
432.50
432.10
430.50
429.80
428.00
426.00
426.00

198.65
46.17
25.86
68.00
83.00
87.00
85.00
82.00
85.00
85.00
53.00
49.00
41.00
59.00
49.00
59.00
85.00
29.00
86.00
84.00
83.00
83.00
90.00

9
2
2
54
54
54
54
52
51
51
2
1
1
54
54
54
54
54
54
54
52
51
2

0.354
1.000
1.000
0.137
0.137
0.137
0.137
0.140
0.141
0.141
1.000
0.150
0.150
0.137
0.137
0.137
0.137
0.137
0.137
0.137
0.140
0.141
1.000

0.477
0.300
0.300
1.106
1.106
1.106
1.106
1.065
1.045
1.045
0.300
0.150
0.150
1.106
1.106
1.106
1.106
1.106
1.106
1.106
1.065
1.045
0.300

D
( pulg. )
sistema 1
0.051347
1.00
0.017327
1.05
0.146945
0.67
0.114706
1.16
0.060241
1.33
0.017241
1.73
0.023529
1.62
0.006098
2.12
0.020000
1.64
0.015294
1.74
0.009434
1.20
0.020408
0.78
0.007317
0.97
0.152542
1.09
0.020408
1.67
0.042373
1.43
0.023529
1.62
0.013793
1.81
0.023256
1.63
0.008333
2.02
0.021687
1.63
0.012048
1.83
0.011111
1.16

D Comerc.
( pulg. )

V ideal
(m./s.)

V
(m./s.)

Hf
Tramo
( m. )

1
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1
1
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2

0.412
0.445
0.445
0.445
0.445
0.445
0.445
0.445
0.445
0.445
0.445
0.412
0.412
0.445
0.445
0.445
0.445
0.445
0.445
0.445
0.445
0.445
0.445

0.942
0.263
0.263
0.970
0.970
0.970
0.970
0.934
0.916
0.916
0.263
0.296
0.296
0.970
0.970
0.970
0.970
0.970
0.970
0.970
0.934
0.916
0.263

9.052
0.124
0.070
2.046
2.497
2.618
2.558
2.301
2.301
2.301
0.143
0.262
0.219
1.775
1.474
1.775
2.558
0.873
2.588
2.528
2.329
2.247
0.242

El criterio de asignacin de caudales en tramos terminales es e de Simultaneidad de uso: Q = 0.15xNxK; en donde:


0.15 es el caudal en litros por segundo asignado a una conexin domiciliaria.
N es el nmero de conexiones domiciliarias del tramo.
K es el coeficiente de simultaneidad, nunca infrior a 0.2.
63
206.00
120
0.65
1.29
15
0.020

vi.
hab.
lts./hab./da
lts./seg.
lts./seg.
m3.
lts./seg/viv.

455.00
445.95
445.82
455.00
452.95
450.46
447.84
445.28
442.98
440.68
445.28
442.98
440.68
455.00
455.00
455.00
453.22
450.67
450.67
448.08
445.55
443.22
440.98

FINAL
PRESION
( msnm ) INICIO
SALIDA
445.95
445.82
445.75
452.95
450.46
447.84
445.28
442.98
440.68
438.38
445.14
442.72
440.46
453.22
453.53
453.22
450.67
449.79
448.08
445.55
443.22
440.98
440.73

K= (N-1)^-0.5

DATOS :
Total Edificaciones
Poblacin Actual (Pa)
Dotacin (d)
Consumo Mximo Diario ( Qmd )
Consumo Mximo Horario ( Qmh )
Volmen del Reservorio ( V )
Consumo Unitario ( Q unit. )

INICIAL
( msnm )

0.204820694

17.00
18.15
18.02
9.20
14.95
17.46
16.34
15.78
13.98
13.38
15.78
13.98
13.38
9.00
18.00
18.00
18.72
18.17
18.17
17.58
15.75
16.22
13.98

18.15
18.82
21.75
14.95
17.46
16.34
15.78
13.98
13.38
12.38
15.14
14.72
13.46
16.22
17.53
18.72
18.17
17.69
17.58
15.75
15.22
14.98
14.73

COMP
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK