Documente Academic
Documente Profesional
Documente Cultură
nonlinear restraints (such as +Y, -Z, any restraint with a gap, and so on) or boundary conditions (such as friction). Standard load cases for B31.4 Ch IX, B31.8 Ch VIII, and DNV codes: L1 L2 W+T1+P1 W+P1 (OPE) (SUS)
No expansion stress is calculated for these piping codes. Standard load cases for BS7159 and UKOOA piping codes: L1 W+T1+P1 (OPE)
*HS is the hanger stiffness defined on the Load Case Options tab. ** Use the algebraic combination method on the Load Case Options tab. When you use only predefined spring hangers, there is no need for the first two load cases. However, the letter H is still required in the operating and sustained load cases. Other hanger load cases are required when you use multiple load case design. In such instances, let CAESAR II recommend the load cases. You can then add or edit the non-hanger design load cases as necessary.
* Use the algebraic combination method on the Load Case Options tab.
453
Static Analysis
Case 3 L1-L2 (EXP) Expansion load case
Review any load recommendations made by CAESAR II. CAESAR II does not recommend any occasional load cases. Definition of these is your responsibility. If the recommended load cases do not satisfy the analysis requirements, you can delete or modify them. Conversely, you can reset the load cases at any time to the software recommended set. If you have an operating temperature below ambient in addition to one above ambient you should add another expansion load case as follows: Case 1 Case 2 Case 3 Case 4 Case 5 Case 6 W+D1+T1+P1+H (OPE) W+D2+T2 +P1+H (OPE) W+P1+H (SUS) L1-L3 (EXP) L2-L3 (EXP) L2-L1 (EXP) Operating Operating Sustained load case Expansion load case Expansion load case Add this case because CAESAR II does not recommended it automatically.
459
Technical Discussions
790
Technical Discussions
Pre-Selection Load Case 2 Setting Hanger Deflection through the Operating Case
After the restrained weight case, you must run an operating analysis. The operating case must always be the second load case in the set of defined analysis cases. You can define the operating load cases for hanger design any way you see fit. CAESAR II recommends the load cases it thinks you should run whenever it detects the first attempt to analyze a particular system. You can accept or reject the recommendations. If you define your own hanger design load cases, you must understand exactly what is done in the "restrained weight" and operating passes of the hanger design algorithm.
Post-Selection Load Case (Optional) Setting the Actual Installed (Cold) Load
If you need to calculate the actual hanger installed loads, the third analysis level combination case must define the weight configuration that exists in the field when a spring is installed. Typically, this case includes weight without fluid contents and other live loads. The theoretical cold, or installed load, is the load on the spring when the "unbalanced" installed load is applied and the pipe is not allowed to displace vertically (the load will be "balanced" when the pipe is in the operating or design position). The actual installed load may differ from the theoretical installed load by (K)(d), where (K) is the spring stiffness and (d) is the displacement of the pipe in the installed condition.
791