2011 May 2011 Advanced Training BOGE KOMPRESSOREN 1


BOGE air. The air to work.
Focus Controller
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 2
Focus Controller
Overview of Capabilities
Focus Hardware
Focus Interface
Parameters
Faults
Base Load Switching
Leak Detection
Software Updates
Modules
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 3
Focus Basics
General Capabilities
All Ratio Capabilities, Plus:
Control of 1-4 Compressors via Integrated ModBus
Control of VFD Setpoint in SF Machines
Efficiency Display
Leak Detection Mode
Clock/Sequencer Function
More User-Friendly Interface
Two Remote-Switchable Pressure Profiles
Multiple Add-On Modules to Expand Capabilities Further
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 4
Focus Basics
Focus Hardware
Focus TAN
Display Module
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 5
Focus Basics
Focus Hardware
Focus Base Module
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 6
Focus Basics
Focus Hardware
Additional Modules
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 7
Focus Controller
Focus Interface
Net/Line Pressure
Compressor Status
Air End
Temperature
Press Right Arrow for Next Screen
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 8
Focus Controller
Focus Interface
Net/Line Pressure
Press Right Arrow for Next Screen
Sump/System
Pressure
Compressor Status
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 9
Focus Controller
Focus Interface
Press Right Arrow for Next Screen
Hours Until Motor
Servicing Due
Hours Until
Compressor
Servicing Due
Load Cycles Until
Separator
Servicing Due
Battery Voltage
>2.8v is Normal
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 10
Focus Controller
Focus Interface
Right Arrow for Next Screen
Total Hours
Idle Hours
Efficiency
Load Cycles
Up Arrow for Leakage Monitor
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 11
Focus Controller
Focus Interface
Press Right Arrow for Next Screen
ModBus Status
Key Switch Status
Release Type
Auto Restart
After Power Loss
Delay
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 12
Focus Controller
Focus Interface
Press Right Arrow for Next Screen
Pressure Range
Net Pressure Timer Status
Sequencer Status
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 13
Focus Controller
Focus Interface
Press Right Arrow for Next Screen
Hold Enter to
Change Date/Time
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 14
Focus Controller
Focus Interface
Software Version
Press Right Arrow
for Main Screen
Press Enter for
Code Entry
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 15
Focus Controller
Focus Interface
Use Navi Keys to
Enter Access Code
Press Enter
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 16
Focus Controller
Focus Interface
Parameter Access
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 17
Focus Controller
Focus Interface
Parameter Access
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 18
Focus Controller
Focus Parameters
Parameter List in Functional Description
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 19
Focus Controller
Focus Faults
Fault Table
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 20
FOCUS base load switch (BLS)
FOCUS base load switch
- Integrated BLS for up to 4 machines (via RS485 / optional relay module)
- Modular expendability (max. 5 additional modules)
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 21
Focus Controller
Base Load Switching
RS485 RS485 RS485
BLS is Intended to Sequence/Cycle 4 Machines of the Same or Similar Size
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 22
Focus Controller
Base Load Switching
51 GND
52 RS485 +
53 RS485 -
120ohm Termination Resistor Jumper
Wiring
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 23
Base load switch only by RS 485
FOCUS
Bus address
0
MASTER
FOCUS
Bus address
2
SLAVE
Bus address
3
SLAVE
Bus address
4
SLAVE
+ RS485 Interface
RATIO
+ RS485 Interface
RATIO
3 3 3
FOCUS base load switch (BLS)
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 24
Contact
Base load switch only by contact (Relay module)
FOCUS
+ 3x Relay
module
RATIO BASIC
Relay address
2
SLAVE
Relay address
3
SLAVE
Relay address
4
SLAVE
Output release Output release Output release
22 2
FOCUS base load switch (BLS)
Other
brand
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 25
22 3
Base load switch with combination of contact and RS 485
Contact
Bus address
0
MASTER
FOCUS
+ 2x Relay
module
FOCUS
RS 485
Bus address
2
SLAVE
Relay address
3
SLAVE
Relay address
4
SLAVE
FOCUS base load switch (BLS)
Autotronic
Output release
Other
brand
Output release
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 26
- A differential pressure between pressure transducers of machines and BLS must be
- considered during adjustment of machine pressure settings
9.0 bar
8.0 bar
- The cut in and cut off pressures of the compressors must be above the values of the BLS
Pressure switch points
compressors
Pressure switch points
BLS
8.3 bar
9.5 bar
C 3
C 3
8.5 bar
9.6 bar
C 2
C 2
8.7 bar
9.7 bar
C 1
C 1
- The machine switching points of the machines should be cascaded
Example parameters for base load switch
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 27
8.0 bar
9.0 bar
Cut in and cut off characteristic of the BLS

Priority 1

Priority 2

Priority 3

Priority 4
Priority 1

Priority 4

Priority 2

Priority 3

Example parameters for base load switch


03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 28
FOCUS FOCUS
+ RS485 Interface
RATIO
+ RS485 Interface
RATIO
- The RATIO controller must be equipped with the RS 485 BUS Interface
RS485
- The machines need to be connected from controller to controller
- Connection sequence in any direction is possible - the Bus address defines the Compressor
- At great cable length a resistor (120 ) must be set on both ends of the line
Example with only bus-compatible controllers
3 3 3
Example parameters for base load switch
- The pressure control must be active on all Slave-Machines (Bridge on X2:18/19)
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 29
BLS
(Priority change based on hours)
by only RS485 connection with FOCUS
Requirements:
- 4 Machines connected (2x FOCUS and 2x RATIO)
- all machines on the same or similar size
- 7 hours changeover
Example parameters for base load switch
- Pressure range of installation 8bar - 9bar
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 30
Number of connected machines
base-change cycle in hours
P070 4
P071 7hrs
RS485
P050 0
P051 9600
P052 8E1
FOCUS
Cut off pressure Operating range of
Cut in pressure base load switch
Parameter settings of FOCUS Master machine
MASTER SLAVE SLAVE SLAVE
RATIO
+Interface
RATIO
+Interface
FOCUS
33 3
Example parameters for base load switch
P012 9.0bar
P013 8.0bar
Modbus address MASTER = 0
Modbus baud rate MASTER = SLAVE
Modbus communication parameter MASTER = SLAVE
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 31
RS485
FOCUS
P063 2
P050 2
P051 9600
P052 8E1
P012 9.3bar
P013 8.3bar
Cut off pressure Operating range for
Cut in pressure failure of BLS
Modbus address SLAVE = 2
Modbus baud rate MASTER = SLAVE
Modbus communication parameter MASTER = SLAVE
External release via Bus MASTER controls SLAVE
Parameter settings of FOCUS Slave machine
SLAVE
RATIO
+Interface
RATIO
+Interface
FOCUS
33
3
Example parameters for base load switch
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 32
CODE 2
210
CODE 3
830 96
8E1
Cut off pressure Operating range for
Cut in pressure failure of BLS
Parameter settings of RATIO Slave machine
Modbus address SLAVE = 3
Modbus baud rate MASTER = SLAVE
Modbus communication parameter MASTER = SLAVE
External release via Bus MASTER controls SLAVE
SLAVE
RS485
FOCUS FOCUS RATIO
+Interface
RATIO
+ RS485 Interface
RATIO
3
3 3
Example parameters for base load switch
CODE 9.5bar
360 8.5bar
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 33
CODE 2
210
CODE 4
830 96
8E1
Cut off pressure Operating range for
Cut in pressure failure of BLS
SLAVE
Parameter settings of RATIO Slave machine
RS485
RATIO
+Interface
FOCUS FOCUS
RATIO
+ RS485 Interface
RATIO
Modbus address SLAVE = 4
Modbus baud rate MASTER = SLAVE
Modbus communication parameter MASTER = SLAVE
External release via Bus MASTER controls SLAVE
3
3
3
Example parameters for base load switch
CODE 9.7bar
360 8.7bar
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 34
Code 360
9.5bar / 8.5bar
Code 830
3 / 96 / 8E1
Code 210
2
P012 9.3bar
P013 8.3bar
P050 2
P051 9600
P052 8E1
P063 2
P012 9.0bar
P013 8.0bar
P050 0
P051 9600
P052 8E1
P070 4
P071 7hrs
FOCUS FOCUS
+ RS485 Interface
RATIO
+ RS485 Interface
RATIO
Code 360
9.7bar / 8.7bar
Code 830
4 / 96 / 8E1
Code 210
2
RS485
33 3
Example parameters for base load switch
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 35
- all machines on the same or similar size
- 23 hours changeover
- Pressure range of installation 8bar - 9bar
- 4 machines connected (1x FOCUS, 1x RATIO, 1x BASIC
and 1x Other brand controller)
Example parameters for base load switch
BLS
(Priority change based on hours)
by only relay module connection with FOCUS
Requirements:
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 36
Contact
FOCUS
+ 3x Relay
module
RATIO BASIC Other
brand
Output release Output release
- The FOCUS Master machine must be equipped with the relay modules for the
- connected compressors
Output release
Signal line
- Every single relay module has to be connected to the output release of the machines
- Every single relay module must be configured with its own rotary switch
- The cable length should not be longer then 50m
22 2
Example parameters for base load switch
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 37
MASTER
Parameter settings of FOCUS Master machine
FOCUS
RATIO Other
brand
BASIC
22 2
Contact
Example parameters for base load switch
P012 9.0bar
P013 8.0bar
Cut off pressure Operating range of
Cut in pressure base load switch
P070 4
P071 23hrs
Number of connected machines
base-change cycle in hours
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 38
FOCUS
SLAVE
Parameter settings of RATIO Slave machine
RATIO
BASIC
The Relay module in the switch cabinet of the master machine, has to be configured to 2.
CODE 9.3bar
360 8.3bar
Cut off pressure Operating range for
Cut in pressure failure of BLS
CODE 1
210
External release via contact MASTER controls SLAVE
22
2
Contact
Example parameters for base load switch
Other
brand
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 39
The Relay module in the switch cabinet of the master machine, has to be configured to 3.
Parameter settings of BASIC Slave machine
SLAVE
RATIO FOCUS
BASIC
2
2 2
Contact
Example parameters for base load switch
CODE 1
210
External release via contact MASTER controls SLAVE
CODE 9.5bar
360 8.5bar
Cut off pressure Operating range for
Cut in pressure failure of BLS
Other
brand
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 40
The Relay module in the switch cabinet of the master machine, has to be configured to 4.
9.7bar
8.7bar
Cut off pressure Operating range for
Cut in pressure failure of BLS
External release via contact MASTER controls SLAVE
SLAVE
Parameter settings of other brand Slave machine
RATIO FOCUS BASIC
Other
brand
2
2
2
Contact
Example parameters for base load switch
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 41
FOCUS
+ 3x Relay
module
RATIO BASIC Other
brand
Signal line
Code 360:
9.5bar / 8.5bar
Code 210:
1
Code 360:
9.3bar / 8.3bar
Code 210:
1
P012 9.0bar
P013 8.0bar
P070 4
P071 23hrs
Pressure settings:
9.7bar / 8.7bar
Output release:
active
22 2
Contact
Example parameters for base load switch
Output release Output release Output release
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 42
FOCUS
+ 3x Relay
module
RATIO BASIC Other
brand
22 2
Contact
Example parameters for base load switch
Output release Output release Output release
Settings of rotary
switches of relay
modules
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 43
BLS
(Clock switch based priority change)
by combination of contact and RS485
with FOCUS
Requirements:
- 4 machines connected ( 1x FOCUS 55 kW, 1x FOCUS 37 kW,
- 1x Autotronic 22 kW und 1x other brand 37 kW
- Working time: 6.00Uhr to 19.30Uhr
Example parameters for base load switch
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 44
- Pressure range of installation 10.5bar - 11.5bar
- The 55 kW machine is frequency controlled
- The 55 kW compressor is base load machine
- Both 37 kW compressors are peak load machines
- The 22 kW compressor is a reserve machine
Example parameters for base load switch
BLS
(Clock switch based priority change)
by combination of contact and RS485
with FOCUS
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 45
RS485
- The FOCUS must be equipped with two relay modules
FOCUS
+ 2x Relay
module
FOCUS
- The FOCUS machines are connected from controller to controller
- On great cable length resistor terminator (120 ) has to be set on the end of the bus
- Every single relay module must be configured with its own rotary switch
- Every single relay module has to be connected to the output release of the machines
- The cable length should not be longer then 50m from relay module to machine controller
22 3
Contact
Example parameters for base load switch
Autotronic
Output release
Other
brand
Output release
- The pressure control must be active on all Slave-Machines (Bridge on X2:18/19)
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 46
RS485
MASTER
FOCUS
Parameter settings of FOCUS Master machine
BASIC Auto-
tronic
Other
brand
FOCUS
FOCUS
22 3
Contact
Example parameters for base load switch
Number of connected machines
base-change cycle = 0 deactivates BLS based on hours
P070 4
P071 0hrs
P050 0
P051 9600
P052 8E1
Cut off pressure Operating range of
Cut in pressure base load switch
P012 11.5bar
P013 10,5bar
Modbus address MASTER = 0
Modbus baud rate MASTER = SLAVE
Modbus communication parameter MASTER = SLAVE
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 47

Canal A
MO 6:00
1243
Canal B
MO 19:30
3241
Channel A
MO 6:00
1243
Channel B
MO 19:30
3241
Canal D
DI 19:30
3421
Canal C
DI 6:00
1423
Channel C
TU 6:00
1423
Channel D
TU 19:30
3421
Canal I
FR 6:00
1423
Channel I
FR 6:00
1423
Canal J
FR 11:00
1243
Channel J
FR 11:00
1243
Clock switch settings of FOCUS Master machine
RS485
MASTER
FOCUS BASIC Auto-
tronic
Other
brand
FOCUS
FOCUS
22 3
Contact
Example parameters for base load switch
Canal K
FR 16:00
3241
Channel K
FR 16:00
3241
Canal K
FR 16:00
0000
Channel K
FR 16:00
0000
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 48
SLAVE
Parameter settings of FOCUS Slave machine
FOCUS BASIC Auto-
tronic
Other
brand
RS485
FOCUS
22
3
Contact
Example parameters for base load switch
External release via bus MASTER controls SLAVE P063 2
P050 2
P051 9600
P052 8E1
Modbus address MASTER = 2
Modbus baud rate MASTER = SLAVE
Modbus communication parameter MASTER = SLAVE
P012 11.5bar
P013 10,5bar
Cut off pressure Operating range for
Cut in pressure failure of BLS
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 49
Contact to
pressure switch
External release via Contact MASTER controls SLAVE
SLAVE
Parameter settings of Autotronic Slave machine
FOCUS FOCUS Other
brand
RS485
Auto-
tronic
2
2 3
Contact
Example parameters for base load switch
The Relay module in the switch cabinet of the master machine, has to be configured to 3.
PS- 12bar
set. 11bar
Cut off pressure Operating range for
Cut in pressure failure of BLS
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 50
FOCUS
External release via Contact MASTER controls SLAVE
SLAVE
Parameter settings of other brand Slave machine
BASIC Auto-
tronic
FOCUS
RS485
Other
brand
2
2
3
Contact
Example parameters for base load switch
The Relay module in the switch cabinet of the master machine, has to be configured to 4.
12.2bar
11.2bar
Cut off pressure Operating range for
Cut in pressure failure of BLS
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 51
Autotronic
Output release
Pressure settings:
12.2bar / 11.2bar
Output release:
active
Pressure switch
12bar / 11bar
Contact to
pressure switch
P012 11.8bar
P013 10.8bar
P050 2
P051 9600
P052 8E1
P063 2
P012 11.5bar
P013 10.5bar
P050 0
P051 9600
P052 8E1
P070 4
P071 0hrs
Contact
RS485
FOCUS
+ 2x Relay
module
FOCUS
22 3
Example parameters for base load switch
Other
brand
Output release
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 52
Example parameters for base load switch
Contact
RS485
FOCUS
+ 2x Relay
module
FOCUS
Autotronic
Output release
Settings of rotary
switches of relay
modules
22 3
Other
brand
Output release
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 53
Focus Controller
Leak Detection (>v1.15 Only)
Single Measurement
Continuous
Measurement
Hours of Run Time
Used Only for Leaks
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 54
Focus Controller
Leak Detection (v1.15 Only)
Conditions:
All Plant Usage Must be Off
Compressors Must be Enabled / Green
These conditions must remain for 6 hours
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 55
Focus Controller
Leak Detection (v1.15 Only)
Starting a Test:
1. Navigate to the Leak Detection Screen
2. Hold Enter for 2 secs, until Le starts flashing, then release Enter
3. Hold Enter for another 2 secs to initiate a 6hr test
4. After 6 hours, values will appear showing calculated wasted run
hours
5. The system will monitor in 6hr intervals, and will update the values if
a lower load period is detected
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 56
Focus Controller
Leak Detection (v1.15 Only)
Faults:
9999 = Power Failure
9990 = Loss of Ready Status
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 57
Focus Controller
Software Updates
Potential Damage to Focus Controller and PC
Follow Directions Exactly
NEVER Disconnect Flashing Cables With the
Focus Energized
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 58
Focus Controller
Software Updates
Focus Flashing Device
and Serial Cable
Boge P/Ns:
659003101 & 681004805
CS Manager +
Laptop w/ Serial Port
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 59
Focus Controller
Software Updates
Remove Power from the Focus
the Screen Must Turn Off
Breaker 4F is Sufficient
Main Panel Disconnect is Safest
The E-Stop Will Not Power Down
the Focus
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 60
Focus Controller
Software Updates
Connect Flash Device
Ground to Term 32
Connect the Flash Device
Cable to the Software
Update Port and the
Serial Cable to your PC
Disconnect the Digital
Outputs
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 61
Focus Controller
Software Updates
Disconnect the
Transformer Ground
Power On the Focus
Controller
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 62
Focus Controller
1
2
3
4
5 1. Restrict Selection
2. Identify
3. Ensure Type Turns
Green Indicates Comm
4. Select Correct Program
and Version
5. Write to Flash
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 63
Focus Controller
Red Indicates a Comm
Problem
Check Cables, Port
Settings, and Power
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 64
Focus Controller
Software Updates
Wait for Flashing to Finish
Ignore Any Faults
De-energize the Focus
Wait 10 Seconds
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 65
Focus Controller
Software Updates
After Waiting 10 Seconds:
1. Disconnect the Flash
Cable from the Focus Base
2. Connect the Flash Cable to
the Focus TAN
3. Energize the Focus and
Repeat the CSM+ Process
4. De-Energize
5. Wait 10 Seconds
6. Disconnect All Flash
Cables, Reconnect
Transformer Ground