Packaged Fresh Air Unit

For 100% Outdoor Air Applications


Model FADA/FAHA Product Catalog

December 2002

MUA-PRC004-EN

Introduction
The Packaged Fresh Air Unit...
Tranes DX Packaged Rooftop unit for 100% outside air applications
leads the industry in:
Indoor Air Quality (IAQ) Features
High Quality and Durability
Advanced Controls

Unit mounted IntelliPak


microprocessor control
with easy-to-read human
interface

2 Pleated filter section


with adjustable rack to 4

Standard protective
bird screen on inlet
hood

Horizontal or vertical
discharge openings
Hi-rise electric
(or gas) heat
1 Solid double-wall
panels of foamed-inplace construction

Quiet FC fan

2002 American Standard Inc.

Non-corrosive IAQ
drain pan sloped in
two directions

Optional condenser
reheat coil with
modulating control

Traq damper
available for airflow
measurement
Optional return air
damper for unoccupied
recirculation

MUA-PRC004-EN

Table of
Contents

Features and Benefits

Application Considerations

Selection Procedure

15

General Data

20

Performance Data

21

Controls

77

Electrical Data

86

Dimensions & Weights

90

Mechanical Specifications

MUA-PRC004-EN

112

Features and
Benefits
Features and Benefits
We designed the Packaged Fresh Air
unit based on customer requirements
from across the country. Thorough
analysis of the performance requirements resulted in a robust design with
the ability to effectively operate over an
expansive performance envelope
required for the year-round treatment
of outdoor air.
Also, we took into account todays HVAC
market issues, such as indoor air quality
(IAQ). We equipped the Packaged Fresh
Air unit to meet your ventilation needs
in direct response to the ventilation
and humidity control requirements of
ASHRAE standard 62.1-1999.
Tranes Packaged Fresh Air unit leads
the industry in the key areas of:
indoor air quality (IAQ)
high quality and durability
advanced, integrated controls
flexibility
enhanced serviceability
Indoor Air Quality (IAQ) Features
Non-corrosive drain pan sloped in two
directions to ensure proper drainage
to reduce the potential for microbial
growth
Double-wall foamed panel construction throughout the indoor section of
unit to provide, non-porous, cleanable
interior surfaces

High efficiency throwaway filter option


with standard 2 or 4 adjustable filter
rack
Traq outdoor airflow measurement
damper
total energy wheel option for recovered energy from centralized building
exhaust
Easy filter access encourages frequent
changing
High Quality and Durability
Robust unit construction with 1
double-wall panels and access doors.
High quality, long-lasting latches and
hinges for all access doors.
Protective standard prepainted finish
on cabinet exterior with optional
corrosion inhibiting coatings available
for the unit exterior, interior and coils.
Assured dehumidification performance and control with capability of
providing low dew point supply air.
Optional modulating recovered
refrigerant reheat for unit supply air.
Advanced Controls
All controls are factory-engineered,
mounted, configured and tested to
minimize field startup time.
IntelliPak microprocessor control
with easy-to-read human interface
clear language display (English,
French, or Spanish).
Human interface with 16-button
keypad for monitoring, setting, editing
and controlling.

Capable of supply-air control or zone


control of both temperature and
relative humidity
Occupied and unoccupied control
sequences including unoccupied
economizer logic.
Additional control sequences including
demand limit, exhaust control and
CO2 monitoring.
Optional remote human interface for
ease of control access without going
outdoors.
Optional LonTalk communications
interface (LCI-I) communication link
with a Tracer Summit building
management system or other control
systems that support the LonTalk
discharge air control (DAC) profile.
Generic BAS and ventilation override
capability for added control flexibility
Flexibility
Modular Intellipak controller
designyou only pay for what you
need
Vertical or horizontal discharge
available
Numerous heater options and temperature rise capabilities available.
Standardized roof curb

Figure FB-1. Fan side view of the Trane Packaged fresh air unit
4

MUA-PRC004-EN

Features and
Benefits
Enhanced Serviceability
Five hinged access doors with safety
chains for ease of maintenance and
service
Easy-open door latches
Human Interface (HI) door provides
access without opening control panel
door
Modular control board design with
ability to swing out HI during service
Standard Unit Features
Four unit sizes (031, 040, 051, 066) with
airflow range of 1800-6600 cfm
Double-wall construction with 18g
outer and 20g inner galvanized metal
skin.
Outdoor air inlet hood
Prepainted exterior finish
Air-cooled DX refrigeration system
Completely factory-piped and leaktested refrigeration system
Non-corrosive drain pans sloped in two
planes
Centrifugal double-width, double-inlet
FC fan with permanently lubricated
bearings
Scroll compressors
Terminal block for power connection
Single-point power connections for
non-electric heat units
Filter rack adjustable for two or four
inch filters
UL listing on all standard options

Standard Control Features


Fully integrated, factory-installed and
commissioned microelectronic
controls
Unit mounted human interface panel
FROSTAT coil frost protection
Supply airflow proving
Emergency stop
Mappable sensors and setpoint
sources
Occupied/unoccupied control modes
Timed override for unoccupied mode
Optional Features
Vertical or horizontal discharge
Low or high rise gas heaters (single
bank and dual bank)
Staged or modulating gas heat control
(4:1 max turndown)
409 or 321 stainless steel gas burner
Three or seven stage electric heat
Hydronic heat interface (heat coil fieldprovided)
Condenser reheat with modulating
control
Low-leak parallel blade or Traq
outdoor airflow damper
Return air damper with comparative
or reference enthalpy
Standard or high-efficiency fan motor
total energy wheel
Protective coatings for the unit and/or
coils
Two inch pleated media filters (30%
efficiency)

Dirty filter switch


Supply air or zone control
Larger, more efficient fan option
available for high airflow, low external
static pressure points
LonTalk Communications Interface
module
Generic BAS module
Ventilation override from up to five
external inputs
Remote human interface
Exhaust interface with exhaust
opening integral to unit cabinet
Through-the-door, non-fused disconnect switch
Factory or field-wired convenience
outlet
Extended fan grease lines
Field-Installed Accessories
Roof curb in 14 or 24 height
Remote human interface controls up
to four units
2 cleanable filters
Time clock
Zone sensors with a variety of
different features and functions
Field-installed module kits available
for field upgrade of controls
Remote minimum potentiometer
control
CO2 sensor available with Traq only
Duct-mounted temperature sensor

Figure FB-2. Compressor side view of the Trane Packaged fresh air unit
MUA-PRC004-EN

Application
Considerations
Overview
Fresh Air Unit Functions
The Packaged Fresh Air unit (FAU)
provides conditioned outdoor air
suitable for mechanical ventilation or
make-up air. The FAU conditions
outdoor air as necessary to meet
system performance requirements by
filtration, cooling, dehumidification, and/
or heating. The FAU may deliver
ventilation air in a number of ways. See
the System Configurations section and
Figures AC-1 through AC-3 for more
information.
Filtration
Filtration is necessary for the FAU to
maintain system operating efficiency,
meet occupant comfort and health
needs, and provide adequate building
filtration to aid indoor air quality. The
Packaged FAU offers a variety of filter
options to meet most application needs.
Cooling
When the outdoor air dry-bulb temperature is warmer than space conditions,
the unit cools the outdoor air to the
appropriate supply air dry-bulb temperature. The Packaged FAU provides
cooling using an air-cooled, directexpansion (DX) refrigeration system
with scroll compressors.
Dehumidification (Drying)
The Packaged FAU dehumidifies the
outdoor air when it is more humid than
the required space target conditions.
This helps prevent high relative humidity levels in the space. Occasionally, the
outdoor air may require sub-cooling to
remove excess moisture. When
necessary, the FAU reheats discharge
air to meet space comfort conditions.
The Packaged FAU recovers energy
from the cooling process to reheat the
sub-cooled air as necessary.

Heating
When the outdoor air dry-bulb temperature is colder than space conditions
require, the FAU heats the outdoor air to
meet space temperature requirements.
The Packaged FAU has electric or gas
heat options available.

System Configurations
Dedicated outdoor air systems can
deliver conditioned outdoor air in one of
the following ways:
6

1. Directly to the occupied space, with


the local terminal unit controlling the
space dry-bulb temperature. See
Figure AC-1.
2. Directly to local terminal units, which
deliver a mixture of the conditioned
outdoor air and (conditioned) recirculated return air to the space. See
Figure AC-2.
3. Directly to a single space and control
the space temperature directly. For
example, this application will provide
temperature control of a hotel hallway
and ventilation of the adjacent rooms.
See Figure AC-3.

Figure AC-1. Direct discharge to


conditioned space

Supply Air Temperature


Give careful consideration when
selecting the FAU supply air temperature. Many current system designs
control the fresh air unit discharge air to
a space neutral dry-bulb condition,
typically about 75F. At some operating
conditions, reheating the FAU supply air
will add cooling load to the space, thus
requiring the local terminal units to recool the conditioned outdoor air to
meet the space setpoint. Therefore, to
help lower energy costs, use reheat
only when required to maintain occupant comfort and space relative
humidity. The Capacity Control section
discusses this issue in more detail.
Airside Economizers
Often fresh air units are sized to deliver
the minimum ventilation air required for
the space it serves. However, ventilation air is typically only a portion of the
space supply air. Airside economizing
can provide up to 100% of the space
supply air when outdoor air conditions
are suitable for free cooling capability.
Its important to remember that airside
economizer capability can be lost if
dedicated outdoor air systems are sized
for minimum ventilation air only. To
provide economizer capability on a
dedicated outdoor air system, the
terminal units must be able to introduce
100% outdoor air during the economizer-cooling mode. The terminal units
outdoor air damper should modulate
between fully closed and fully open to
allow the FAU to deliver the ventilation
air design volume to the space. The
terminal unit should enable economizing
only if the outdoor dry-bulb and dew
point conditions are sufficiently low to
justify economizing.

Figure AC-2. Indirect discharge to fan-coil


units

Figure AC-3. Direct hall discharge with fancoil or PTAC units


MUA-PRC004-EN

Application
Considerations

Figure AC-4 shows the FAU system


with a DX refrigerant circuit design
using reheat.
Dehumidification
Consider Chart AC-1. If the outdoor air
dew point is above the drying setpoint
(or in the case of zone control, the zone
RH is above the RH setpoint), the FAU
will:
cool the outdoor air to remove
required moisture and
reheat to meet the discharge temperature setpoint.
At h1, 100% outdoor air enters the FAU.
The FAU filters, cools, and dehumidifies
the air as it moves through the evaporator coil. Air leaves the evaporator coil
saturated at the preset dew point
condition (h3) and is reheated by the

Cooling or Heating
Consider Chart AC-2. If the outdoor air
dew point or zone RH is equal to or
below the drying setpoint, the FAU will
heat or cool the outdoor air to separate
and adjust cooling or heating setpoints.
At t1 or t3, 100% outdoor air enters the
FAU. The FAU filters, and cools or heats
the air as it is drawn through the
evaporators and heating section. The air
leaves the FAU at the cooling or heating
setpoint (t2 or t4) and equal to or below
the dew point setpoint.

h3

h4

Chart AC-1. Psychrometric dhart with


dehumidification and reheat

heating t4
t3

t1
t2

cooling

Dewpoint Temperature

FAU with Reheat

h1

h2

Te
m
pe
ra
tu
re

The Packaged FAU can use either DX


cooling, condenser reheat, electric or
gas heat to condition the outdoor air.
The unit controls cooling and heating
capacity in stages with the exception of
the modulated heat options. Cooling and
heating staging result in supply air
temperature swings. The unit controls
deliver the desired supply air conditions
on a time-based, weighted average.

reheat condenser to the pre-set reheat


temperature setpoint (h4). The reheat
evaporator transfers energy to the
reheat condenser. A liquid solenoid
valve effectively modulates the reheat
condenser capacity. The reheat outdoor
condenser rejects surplus heat. The
reheat evaporator circuit is first on and
last off, so reheat energy is available at
full and part load conditions. For those
conditions where the reheat condenser
capacity is insufficient to meet reheat
demand, optional electric or gas heat
can provide additional reheat capacity.
Since both the dew point setpoint and
discharge temperature setpoint are fully
adjustable, the desired supply air
conditions are maintained at all load
conditions.

W
et
Bu
lb

Packaged FAU Operation

Dry Bulb Temperature

Chart AC-2. Psychrometric chart with


cooling and heating only

Receiver
Subcooler

Figure AC-4. Refrigeration system diagram with reheat


MUA-PRC004-EN

h3

Dry Bulb Temperature

heating t4
t3

t1
t2

cooling

Dewpoint Temperature

Te
m

pe
ra

tu

re

Chart AC-3. Psychrometric chart with


dehumidification, no reheat

lb

Cooling or Heating
Consider Chart AC-4. If the outdoor air
dew point is equal to or below the dew
point setpoint, the FAU will heat or cool
the outdoor air to separate and adjust
cooling or heating setpoints. 100%
outdoor air enters the FAU (t1). The unit
filters and cools or heats the air as it is
drawn through the evaporators and
heating section. The air leaves the FAU
at the cooling or heating setpoint and
equal to or below the dew point
setpoint.

Dehumidification

Bu

Dehumidification (Drying)
Consider Chart AC-3. If the outdoor air
dew point or zone RH is above the
drying setpoint, the FAU will dehumidify
the outdoor air. 100% outdoor air enters
the FAU (h1). The unit filters, cools (h2)
and dehumidifies the air as it is drawn
through the evaporator coils. Air leaves
the evaporator coils saturated at a
preset dew point setpoint (h3). Since the
dew point setpoint is fully adjustable, the
desired dew point condition is maintained at all load conditions.

h1
h2

W
et

Figure AC-5 shows the Packaged FAU


DX system, using a refrigerant circuit
design without reheat.

W
et
Bu
lb

FAU Without Reheat

Dewpoint Temperature

Te
m
pe
ra
tu
re

Application
Considerations

Dry Bulb Temperature

Chart AC-4. Psychrometric chart with


cooling and heating only

Circuit 2 Compressors
Condenser 2

Subcooler
Condenser 1

Circuit 1 Compressor
Evaporator 1
Evaporator 2

FIgure AC-5. Refrigeration system diagram without reheat


8

MUA-PRC004-EN

Application
Considerations
Establishing Capacity
Requirements

3. Design dew point temperature with


single bank option is 50% and the dual
bank is 25%. Calculate the minimum
temperature rise to determine the
heating control capability. mean
coincident dry-bulb temperature

Determining the FAU capacity requirements requires careful thought. Airhandling equipment is typically selected
based on design sensible conditions.
Since latent loads drive the need for the
FAU, base the selection on design latent
conditions.

The design wet-bulb condition typically


represents a significantly higher
outdoor air enthalpy than the design
dry-bulb condition. Use the condition
that represents the highest enthalpy as
the entering evaporator selection
condition.

Cooling & Dehumidification


Selection Criteria

Evaporator Design Leaving Conditions


Due to the uncertainty of the local
terminal units latent capacity at part
load, it is usually most straightforward
to size the FAU to handle the entire
latent load on the system, both indoor
and outdoor. With this design approach,
the terminal units may do some latent
cooling (dehumidification) during
periods of higher sensible load. At these
times, the space will run slightly drier
than the design RH limit. This is why it
makes sense to select the FAU to limit
the space RH to a maximum allowable
level for those conditions when the
terminal units are providing no space
latent cooling. ASHRAE standards 62.1
and 55 recommend using 60% RH

Evaporator Design Entering Conditions


For many climates the peak outdoor air
enthalpy occurs at a time when the
outdoor dry-bulb temperature is not the
highest. Refer to the chapter on climatic
design information in the ASHRAE
Handbook of Fundamentals. The
cooling and dehumidification design
condition data is provided three ways:
1. Design dry-bulb temperature with
mean coincident wet bulb temperature
2. Design wet-bulb temperature with
mean coincident dry-bulb temperature

design limit for comfort cooling. Using


lower design limits may result in an
unnecessary increase in system
operating energy use.
Use Tables AC-1, AC-2, and AC-3, on
pages 9 and 10, to identify the appropriate supply air dew point for specific
design conditions. For a more detailed
discussion on determining the selection
criteria of a FAU, reference Trane
publications SYS-EB-3 or SYS-APM004.

Reheat
The Trane FAU utilizes recovered
energy from the cooling process to
reheat the air leaving the cooling coil as
required to meet the discharge air
setpoint. The reheat refrigerant circuit is
adequate to deliver enough reheat to
supply space temperature neutral air
(e.g. 75F dry-bulb) under most operating conditions. On very low load days,
the reheat circuit may not contain
enough energy to meet the desired
reheat setpoint. Under those operating
conditions, the FAU can use supplemental heat provided in the heating section.
Because the heat section is sized for the
design heating condition, larger than
normal supply air temperature swings
may occur when using it for incremental reheat energy.

Table AC-1. Supply air dew point temperature, 75F at 60% RH space limit
latent load
Btu/h per Person
100
120
140
160
180
200
220
240
260
280

10
54.6
53.3
52.0
50.6
49.2
47.7
46.1

15
56.6
55.8
55.0
54.2
53.3
52.5
51.6
50.6
49.7
48.7

20
57.5
57.0
56.4
55.8
55.2
54.6
54.0
53.3
52.7
52.0

25
58.1
57.6
57.2
56.7
56.3
55.8
55.3
54.8
54.3
53.8

30
58.4
58.1
57.7
57.3
57.0
56.6
56.2
55.8
55.4
55.0

cfm per person


35
58.7
58.4
58.1
57.8
57.4
57.1
56.8
56.5
56.1
55.8

40
58.9
58.6
58.3
58.1
57.8
57.5
57.2
57.0
56.7
56.4

45
59.0
58.8
58.6
58.3
58.1
57.8
57.6
57.3
57.1
56.8

50
59.2
58.9
58.7
58.5
58.3
58.1
57.9
57.6
57.4
57.2

55
59.2
59.1
58.9
58.7
58.5
58.3
58.1
57.9
57.7
57.5

60
59.3
59.2
59.0
58.8
58.6
58.4
58.3
58.1
57.9
57.7

300
320
340
360
380

47.7
46.6
45.5

51.3
50.6
49.9
49.2
48.5

53.3
52.8
52.3
51.7
51.2

54.6
54.2
53.8
53.3
52.9

55.5
55.1
54.8
54.4
54.1

56.1
55.8
55.5
55.2
54.9

56.6
56.3
56.1
55.8
55.5

57.0
56.7
56.5
56.3
56.0

57.3
57.1
56.8
56.6
56.4

57.5
57.3
57.1
57.0
56.8

400
420
440
460
480
500

47.7
46.9
46.1
45.3

50.6
50.1
49.5
48.9
48.3
47.7

52.5
52.0
51.6
51.1
50.6
50.2

53.7
53.3
53.0
52.6
52.2
51.8

54.6
54.3
54.0
53.6
53.3
53.0

55.3
55.0
54.7
54.4
54.2
53.9

55.8
55.6
55.3
55.1
54.8
54.6

56.2
56.0
55.8
55.6
55.4
55.1

56.6
56.4
56.2
56.0
55.8
55.6

Note: Minimum dew point selectable is 45F.

MUA-PRC004-EN

Application
Considerations
Table AC-2. Supply air dew point temperature, 75F at 55% RH space limit
latent Load
Btu/h per Person
100
120
140
160
180
200
220
240
260
280

10
51.6
50.2
48.8
47.2
45.6

15
53.8
53.0
52.1
51.2
50.2
49.3
48.3
47.2
46.2
45.1

20
54.9
54.2
53.6
53.0
52.3
51.6
50.9
50.2
49.5
48.8

25
55.5
55.0
54.5
54.0
53.5
53.0
52.4
51.9
51.4
50.8

30
55.9
55.5
55.1
54.6
54.2
53.8
53.4
53.0
52.5
52.1

cfm per person


35
56.1
55.8
55.5
55.1
54.8
54.4
54.1
53.7
53.3
53.0

40
56.3
56.1
55.8
55.5
55.2
54.9
54.5
54.2
53.9
53.6

45
56.5
56.2
56.0
55.7
55.5
55.2
54.9
54.6
54.4
54.1

50
56.6
56.4
56.2
55.9
55.7
55.5
55.2
55.0
54.7
54.5

55
56.7
56.5
56.3
56.1
55.9
55.7
55.5
55.2
55.0
54.8

60
56.8
56.6
56.4
56.2
56.1
55.9
55.7
55.5
55.3
55.1

300
320
340
360
380

48.0
47.2
46.4
45.6

50.2
49.7
49.1
48.5
47.9

51.6
51.2
50.7
50.2
49.8

52.6
52.2
51.8
51.4
51.0

53.3
53.0
52.6
52.3
52.0

53.8
53.5
53.3
53.0
52.7

54.2
54.0
53.7
53.5
53.2

54.6
54.3
54.1
53.9
53.7

54.9
54.6
54.4
54.2
54.0

400
420
440
460
480
500

47.2
46.6
46.0
45.3

49.3
48.8
48.3
47.8
47.2
46.7

50.6
50.2
49.8
49.4
49.0
48.6

51.6
51.3
50.9
50.6
50.2
49.9

52.4
52.1
51.8
51.5
51.2
50.9

53.0
52.7
52.4
52.2
51.9
51.6

53.4
53.2
53.0
52.7
52.5
52.2

53.8
53.6
53.4
53.2
53.0
52.7

Table AC-3. Supply air dew point temperature, 75 at 50% RH space limit
latent Load
Btu/h per Person

10

15

20

25

30

cfm per person


35

40

45

50

55

60

100
120
140
160
180

48.4
46.8
45.2

50.8
49.8
48.9
47.9
46.8

51.9
51.3
50.6
49.8
49.1

52.6
52.1
51.5
51.0
50.4

53.0
52.6
52.2
51.7
51.3

53.3
53.0
52.6
52.2
51.8

53.6
53.3
52.9
52.6
52.3

53.8
53.5
53.2
52.9
52.6

53.9
53.6
53.4
53.1
52.9

54.0
53.8
53.5
53.3
53.1

54.1
53.9
53.7
53.5
53.3

200
220
240
260
280

45.7

48.4
47.6
46.8
46.0
45.2

49.8
49.3
48.7
48.1
47.4

50.8
50.3
49.8
49.4
48.9

51.5
51.1
50.7
50.3
49.8

51.9
51.6
51.3
50.9
50.6

52.3
52.0
51.7
51.4
51.1

52.6
52.3
52.1
51.8
51.5

52.8
52.6
52.4
52.1
51.9

53.0
52.8
52.6
52.4
52.2

300
320
340
360
380
400
420
440
460
480
500

46.8
46.2
45.5

48.4
47.9
47.3
46.8
46.3
45.7
45.2

49.4
49.0
48.6
48.2
47.7
47.3
46.8
46.3
45.9
45.4

50.2
49.8
49.5
49.1
48.7
48.4
48.0
47.6
47.2
46.8
46.4

50.8
50.5
50.2
49.8
49.5
49.2
48.9
48.5
48.2
47.9
47.5

51.3
51.0
50.7
50.4
50.1
49.8
49.6
49.3
49.0
48.7
48.4

51.6
51.4
51.1
50.9
50.6
50.4
50.1
49.8
49.6
49.3
49.1

51.9
51.7
51.5
51.3
51.0
50.8
50.6
50.3
50.1
49.8
49.6

Note: Minimum dew point selectable is 45F.

Heating
The FAU has electric or gas heat
options. The electric heat option is
available in 30-70F temperature rise
offerings with three to seven capacity
control stages. This means that the
lowest temperature rise provided using
one stage depends on heater size, unit
airflow, and the number of stages
selected. Calculate the temperature rise
to confirm that it provides acceptable
control. The electric heat will cycle to
maintain heating setpoint.
10

If using hot water heat, install it in the


optional rack within the Packaged FAU
or in the supply ductwork of the fresh air
system. The unit controller will modulate a coil control valve. Provide an
ethylene glycol and water mixture or
other means of freeze protection for the
hot water coil if the FAU will be subject
to sub-freezing temperatures.

enough to accommodate a variety of


system applications. These applications
include:
treating outdoor air to supply a single
space or multiple spaces or
simultaneously meet building makeup air needs while controlling the
temperature and relative humidity of
a single space.

Capacity Control

Each of these applications requires


careful consideration to achieve the
desired results.

The capacity control system on the


Packaged Fresh Air unit is flexible

MUA-PRC004-EN

Application
Considerations
Supply Air Control
For many multiple space systems, the
FAU will continuously supply outdoor air
at a dry-bulb setpoint and a dew point
that does not exceed its dew point
setpoint. This control approach is simple
because it allows the FAU to function
independent of local terminal unit
operation or actual space conditions. If
the unit selection criteria is determined
using the method suggested in the
Establishing Capacity Requirements
section, the fresh air unit will limit the
space relative humidity to the target
level.
When space sensible loads are relatively high, the local terminal unit may
perform some latent cooling and drive
the space relative humidity level lower
than the FAU selection limit. Resetting
the supply air dew point from the FAU
will offer system operating cost savings.
See the Dew Point Reset section for
resetting strategies.
Many fresh air systems supply reheated air directly to terminal units or to
spaces that have terminal units performing local sensible cooling. This
results in the local terminal units recooling the previously re-heated
outdoor air. Resetting the supply air drybulb temperature of the fresh air unit
offers the opportunity to minimize the
amount of time re-cooling occurs. See
the Dry-Bulb Reset section for more
information.
Dew Point Reset
The local terminal unit provides sensible
control of the space and as a result may
coincidentally provide latent cooling to
the space. The latent loads in the space
can vary, especially if occupant density
changes. Since the FAU can provide
latent cooling to the space as well, it
may be beneficial to reset the FAU
supply air dew point to prevent overdehumidifying the space and unnecessarily wasting cooling energy. One way
to do this is to place a relative humidity
sensor in the space served by the FAU
or in a common relief air path (like a
return corridor) if the FAU serves
multiple spaces. This relative humidity
sensor can reset the supply air dew
point setpoint of the FAU by responding

MUA-PRC004-EN

to actual space latent conditions. The


Packaged FAU offers this control
capability.
An alternative dew point control
strategy is to reset the leaving dew
point of the fresh air unit based on the
zone with the highest relative humidity.
The building automation system will
determine the zone requiring the driest
(lowest dew point) air and reset the dew
point of the air leaving on the FAU
accordingly. With this approach, the
control and setpoint selection of the
fresh air system is dynamically optimized based on actual demand of the
controlled space. Comfort and indoor air
quality requirements are met while
minimizing system energy consumption. A Trane Integrated ComfortTM
system can provide this control capability.
Dry-Bulb Reset
Because the Trane FAU dehumidifies
the outdoor air by cooling it, this cool
outdoor air can reduce the sensible
cooling load on the local terminal unit. At
low space sensible loads, the cool
outdoor air may sub-cool the space,
causing the local terminal unit to add
heat (new energy heat). Therefore,
reset the dry-bulb temperature of the
dehumidified outdoor air to minimize
space sensible re-cooling so the
terminal unit with the lowest sensible
load is almost at zero cooling capacity
(within the limit of the dew point
setpoint). For chilled water terminal
units (such as fan-coils), determine this
by monitoring the chilled water valve
position. For DX terminal units (such as
water-source heat pumps or packaged
rooftops), determine by monitoring
compressor operation. To take full
advantage of space demand based drybulb reset, size the local terminal units
based on neutral outdoor air temperature. This strategy will more effectively
manage occupant comfort during
seasonal changeover for two-pipe
terminal unit systems. Because the FAU
is not connected to the chiller or boiler
plant, accomplish this by resetting the
fresh air unit dry-bulb temperature to
keep the critical zone at zero heating
capacity when the boiler is off and zero
cooling capacity when the chiller is off. A

Trane Integrated Comfort system can


provide this control capability.
Unoccupied Space Humidity Control
The Packaged FAU provides conditioned outdoor air for the ventilation
and/or make-up air needs of a building
during occupied hours. It can also limit
building relative humidity during
unoccupied hours. To do this, provide a
return air path to the FAU and place a
relative humidity sensor in the space
served by the FAU or in a common
relief air path (like a return corridor) if
the FAU serves multiple spaces. The
unit will cycle as required to limit the
space relative humidity to the unoccupied relative humidity setpoint. Reheat
and return air damper options are
required for this operation. For dedicated outdoor air systems ducted to
terminal units, these units must cycle
with the operation of the Packaged FAU.
A Trane Integrated Comfort system
can provide this control capability.

Space Control
For single space applications, the
Packaged FAU can control space
temperature and limit space relative
humidity. To do this, size the airflow to
meet whichever is the highest: the
space loads and ventilation and/or
make-up air needs of the application.
Install a temperature sensor in the
space to provide temperature control
and reset the supply air temperature. If
reset of the supply air dew point is
desired, install a space relative humidity
sensor in the space to provide relative
humidity limit control.

Outdoor Airflow Balancing


Establish final unit airflow through a field
air balancing procedure. Change the fan
speed through replacement or fan
sheave adjustment.
To simplify this procedure, optional
TraqTM outdoor airflow measuring
dampers are available for continuous
airflow sensing feedback. The dampers
monitor the outdoor airflow intake and
can help validate and troubleshoot
system airflow issues. Do not use them
for building pressure control.

11

Application
Considerations
Air to Air Energy Recovery
Energy recovery can significantly
reduce HVAC system first-cost and
operating energy costs. You can use
recovered energy for two purposes:
1. to temper or reheat supply air for
independent control of sensible and
latent capacity, or
2. to precondition outdoor air as it
enters the building for ventilation.
The Packaged FAU offers refrigerant
heat recovery for reheating the supply
air. To precondition the outdoor air, use
the total energy wheel option to
recover energy from building exhaust.
Controlling an Energy Recovery
Ventilator
One way to control an energy recovery
device is to turn it on and off with the
FAU system exhaust fan. In this case,
the total energy wheel enables when
the unit is in occupied mode and the
exhaust fan is running. While this
control method is certainly simple and
effective in some applications, it may
not provide the expected energy

saving benefit, particularly when cold


air (vs. neutral air) is supplied to the
building.
Another more effective approach is to
use the outdoor air dry-bulb to determine when to energize or de-energize
the energy recovery device. See Figure
AC-7 for an example of this simplified
version of energy recovery. In addition
to being more effective from a control
standpoint, its also a very simple
control method because the total
energy wheel (only) enables when all of
the following are true:
unit is in occupied mode
exhaust fan is enabled
outside air temperature is above the
upper limit setpoint (default setpoint
80F) or below the lower limit setpoint
(default setpoint 45F)
outside air temperature is above the
frost protection setpoint (default
setpoint 12F).

If using the FAU to deliver cold, dry


conditioned air to the building (outdoor
air is cooled to a low dew point but not
reheated), use the dry-bulb control
option.
Cross Leakage
All energy wheels have some cross
leakage. Therefore, do not use energy
wheels in applications involving toxic or
hazaradous air streams. The percentage of cross leakage depends on the
pressure differentials across the wheel
section. With Trane Packaged FAU
energy wheels, the exhaust air transfer
ratios are typically low (<4%).

Set the upper limit setpoint to the


anticipated return air dry-bulb temperature. Set the lower limit setpoint to 10F
less than the supply air dry-bulb

Figure AC-6. Dry-bulb control in a cold DB/dry DP application

12

setpoint. This control strategy prevents


the energy recovery device from
potentially adding to the load seen by
the cooling and/or heating system of
the unit, but rather utilizing the device
only at those times when it provides
true operating energy savings.

Figure AC-7. Dry-bulb control in a neutral DB/dry DP application

MUA-PRC004-EN

Application
Considerations
Drain Pan Trapping
FAU units are selected based on
dehumidification capability. As such,
condensate can form at an enormous
rate. Therefore, the Packaged FAU drain
pan and condensate line are sized and
designed accordingly. However, an
often-overlooked element of proper
condensate drainage is trapping. An
incorrectly designed and installed trap
on the piping exiting the drain pan can
restrict condensate flow or cause
condensate to spit or geyser. This
can dampen the air handler interior and/
or ductwork, creating an opportunity for
mold infestation. Carefully install and
trap the drain pan to ensure adequate
condensate removal under all
conditons. See Figure AC-8 for the
proper p-trap design for the drain pan.

H = (1 for each 1 of maximum


negative static pressure) + 1
J = half of H
L = H + J+ pipe diameter + insulation

Figure AC-8. P-trap design for drain pan

Acoustical Considerations
Proper unit placement is critical to
reducing transmitted sound levels from
the FAU to the building. Therefore,
consider acoustic concerns during the

MUA-PRC004-EN

design phase and place the unit accordingly. The most economical means of
avoiding an acoustical problem is to
place the unit(s) away from acoustically
critical areas. If possible, do not locate
units directly above areas such as:
offices, conference rooms, executive
office areas, and classrooms. Instead,
ideal locations to consider are: over
corridors, utility rooms, toilets, or other
areas where higher sound levels
directly below the unit(s) are acceptable.

particular job, consider the following:


Do the clearances available allow for
major service work, such as changing
compressors or coils?
Do the clearances available allow for
proper outside air intake, exhaust air
removal, and condenser airflow?
If screening around the unit is used, is
there a possibility of air recirculation
from the exhaust to the outside air
intake or from condenser exhaust to
condenser intake.

Follow these basic guidelines for unit


placement to minimize sound transmission through the building structure.
1. Never cantilever the compressor side
of the unit. A structural cross member
must support this side of the unit.
2. Locate the units center of gravity
close to or over column or main
support beam.
3. If the roof structure is very light,
replace roof joists by a structural
shape in the critical areas described
above.
4. If several units are to be placed on
one span, stagger them to reduce
deflection over that span.

Review any actual clearances that


appear inadequate with your local
Trane sales engineer.

It is impossible to totally quantify the


building structure effect on sound
transmission because it is dependent on
how the roof and building members
respond to the FAU s sound and
vibration. However, following the
guidelines listed above will help reduce
sound transmissions.

Duct Design
It is important to note that the rated
capacities of the FAU can be met only if
the unit is properly installed. A welldesigned duct system is essential to
meet these capacities.

Clearance Requirements
Follow the recommended unit clearances to assure adequate serviceability, maximum capacity, and peak
operating efficiency. Reducing unit
clearances may result in condenser coil
starvation or warm condenser air
recirculation. If the recommended
clearances are not possible on a

When two or more units are placed side


by side, increase the distance between
the units to 150% of the recommended
single unit clearance. Stagger the units
for these two reasons:
1.To reduce span deflection if more than
one unit is placed on a single span.
Reducing deflection discourages
sound transmission.
2.To assure proper exhaust air diffusion
before contact with the adjacent units
outside air intake.

Satisfactory air distribution throughout


the system requires an unrestricted and
uniform airflow from the rooftop
discharge duct.
However, when job conditions dictate
installation of elbows near the FAU
outlet, using guide vanes may reduce
capacity and static pressure loss.

13

Selection
Procedure

Model Number
Description

Packaged Fresh Air unit Model Number Description


Following is a complete description of the Packaged FAU model number. Each digit in the model number has a corresponding code
that identifies specific unit options.

F A D A 040 6 G A,0

0,8,4 0 1 A 0 1 A

0,5,7

0,7 A 0 0 0 E F 0 1

0,0,0

0,0

A A A A

1 2 3 4 5,6,7 8 9 10,11 12,13,141516171819 20 21,22,23 24,25 26 27 28 29 30 31 32 33 34,35,36 37,38 39 40 41 42


Digit 1 Unit model
F = fresh air unit
Digit 2 Unit configuration
A = air cooled
Digit 3 Unit discharge direction
D = downflow
H = horizontal
Digit 4 Development sequence
A = development sequence A
Digits 5, 6, 7 Unit size
031 = 3100 cfm
040 = 4000 cfm
051 = 5100 cfm
066 = 6600 cfm
Digit 8 Unit voltage
3 = 230 volt/60 hz/3 ph
4 = 460 volt/60 hz/3 ph
6 = 208 volt/60 hz/3 ph
Digit 9 Heating system
0 = none
A = gas low rise, single bank, 2-stage
B = gas low rise, single bank, 2:1
modulate
C = gas high rise, single bank, 2-stage
D = gas high rise, single banks, 2:1
modulate
E = gas dual bank, 4-stage
F = gas dual bank 4:1 modulate
G= electric heat, 3-stage
H = electric heat, 7-stage
K = hydronic interface only
Digits 10, 11 Design sequence
** = factory assigned
Digits 12, 13, 14 Heat input
000 = none
020 = 20 kW
026 = 26 kW
032 = 32 kW
042 = 42 kW
056 = 56 kW
070 = 70 kW
084 = 84 kW
100 = 100 kW
122 = 122 kW
125 = 125 MBh

150 = 150 MBh


200 = 200 MBh
250 = 250 MBh
300 = 300 MBh
350 = 350 MBh
400 = 400 MBh
500 = 500 MBh
600 = 600 MBh
700 = 700 MBh
800= 800 MBh
Digit 15 Heat exchanger material
0 = none
1 = 409 stainless steel, 409 stainless
Burner
2 = 321 stainless steel, 409 stainless
burner
Digit 16 Condenser reheat coil
0 = none
1 = condenser hot gas reheat coil
Digit 17 Ventilation damper type
0 = parallel blade damper
1 = TRAQ damper with air flow
measurement
Digit 18 Energy recovery
0 = none
1 = total energy wheel w/occupancy
control
2 = total energy wheel w/dry bulb control
Digit 19 Return air damper
0 = none
1 = bottom return/reference enthalpy
2 = bottom return/comparative enthalpy
Digit 20 Supply fan type1
A = 12 - 9 centrifugal fan
B = 15 - 11 centrifugal fan
C = 18 - 13 centrifugal fan
Digits 21, 22, 23 Supply fan rpm
065 = 650
037 = 375
067 = 675
040 = 400
070 = 700
042 = 425
072 = 725
045 = 450
075 = 750
047 = 475
077 = 775
050 = 500
080 = 800
052 = 525
082 = 825
055 = 550
085 = 850
057 = 575
087 = 875
060 = 600
090 = 900
062 = 625
Note1: The first number in this description indicates the
fan wheel diameter (in.). The second number indicates
the fan wheel width.

14

092 = 925
095 = 950
097 = 975
100 = 1000
102 = 1025
105 = 1050
107 = 1075
110 = 1100
112 = 1125
115 = 1150
117 = 1175
120 = 1200
122 = 1225
125 = 1250
127 = 1275
130 = 1300
132 = 1325
135 = 1350
137 = 1375
140 = 1400
142 = 1425
145 = 1450
147 = 1475
150 = 1500

152 = 1525
155 = 1550
157 = 1575
160 = 1600
162 = 1625
165 = 1650
167 = 1675
170 = 1700
172 = 1725
175 = 1750
177 = 1775
180 = 1800
182 = 1825
185 = 1850
187 = 1875
190 = 1900
192 = 1925
195 = 1950
197 = 1975
200 = 2000
202 = 2025
205 = 2050
207 = 2075
210 = 2100

Digits 24, 25 Supply fan horsepower


01 = 1
02 = 2
03 = 3
05 = 5
07 = 7.5
10 = 10
15 = 15
Digit 26 Fan motor type
A = standard efficiency ODP fan motor
B = high efficiency ODP fan motor
Digit 27 Coil protection
0 = none
A = corrosion inhibiting coating
Digit 28 Unit cabinet protection
0 = standard prepainted steel finish
A = corrosion inhibiting coating
Digit 29 Filter type
0 = field-provided filter
1 = dirty filter switch (DFS) with fieldprovided filter
2 = 2 pleated media filters
3 = 2 pleated media filters & DFS
Digit 30 System control
A = supply air dehumidification
B = supply air dehimidification with zone
RH reference
MUA-PRC004-EN

Selection
Procedure

Model Number
Description

E = zone dehumidification
F = zone dehumidification with OA RH
reference
G= supply air temperature control (no
dehumidification)
J = zone temperature control (no
dehumidification)

Digits 37, 38 Exhaust air fan horsepower


00 = none
01 = 1
02 = 2
03 = 3
05 = 5
07 = 7.5
10 = 10

Digit 31 Control interface options


0 = none
A = LonTalk communications interface
(LCI ) (comm5)
B = LCI (comm5) & generic building
automation system (GBAS) (0-5 VDC)
C = LCI (comm5) & GBAS (0-5 VDC) &
ventilation override module (VOM)
D = LCI (comm5) & VOM
E = GBAS (0-5 VDC)
F = GBAS (0-5 VDC) & VOM
G= VOM

Digit 39 Unit connection type


A = terminal block
B = non-fused disconnect switch
Digit 40 Convenience outlet
0 = none
A = 115V, factory wired
B = 115V, field wired
Digit 41 Extended grease lines
0 = none
A= extended grease lines

Digit 32 Miscellaneous system control


options
0 = none
1 = interface for remote human interface

Digit 42 Agency approval


0 = no agency approval
A = UL approval

Digit 33 Exhaust option


0 = none
1 = exhaust interface

Digit 43 Roof curb


A = 14 curb
B = 24 curb

Digits 34, 35, 36 Exhaust air fan rpm


000 = none
127 = 1275
045 = 450
130 = 1300
047 = 475
132 = 1325
050 = 500
135 = 1350
052 = 525
137 = 1375
055 = 550
140 = 1400
057 = 575
142 = 1425
060 = 600
145 = 1450
062 = 625
147 = 1475
065 = 650
150 = 1500
067 = 675
152 = 1525
070 = 700
155 = 1550
072 = 725
157 = 1575
075 = 750
160 = 1600
077 = 775
162 = 1625
080 = 800
165 = 1650
082 = 825
167 = 1675
085 = 850
170 = 1700
087 = 875
172 = 1725
090 = 900
175 = 1750
092 = 925
177 = 1775
095 = 950
180 = 1800
097 = 975
182 = 1825
100 = 1000
185 = 1850
102 = 1025
187 = 1875
105 = 1050
190 = 1900
107 = 1075
192 = 1925
110 = 1100
195 = 1950
112 = 1125
197 = 1975
115 = 1150
200 = 2000
117 = 1175
202 = 2025
120 = 1200
205 = 2050
122 = 1225
207 = 2075
125 = 1250
210 = 2100
MUA-PRC004-EN

15

Selection
Procedure

Model Number
Description

Packaged Fresh Air unit Accessory Model Number Description


Following is a complete description of the Packaged FAU accessory model number. Each digit in the model number has a
corresponding code that identifies specific accessory options.

031

A0

5, 6, 7

10,11

12

13

14

15

16

17

18

19

20

21

22

23 24

Digit 1 Parts/accessories
P = parts/accessories
Digit 2 Unit type
F = fresh air unit
Digit 3 Field installed kits
K = field installed kits
Digit 4 Development sequence
A = development sequence
Digits 5, 6, 7 Nominal size
031 = 3100 cfm
040 = 4000 cfm
051 = 5100 cfm
066 = 6600 cfm
Digit 8 Unit voltage
3 = 230/60/3
4 = 460/60/3
6 = 208/60/3
Digit 9 Roof curb
0 = none
A = 14
B = 24
C = acoustical
D = 14 curb for unit w/ERV
E = 24 extended for unit w/ERV
F = 24 extended, acoustical for unit w/
ERV
Digits 10, 11 Design sequence
A0 = design sequence
Digit 12 Filter type
0 = none
A = 2 pleated media
B = 2 cleanable

16

C = 2 pleated media total energy wheel


only
D = 2 cleanable total energy wheel only
E = 2 pleated media unit & total energy
wheel
F = 2 cleanable unit & total energy wheel
Digit 13 Control interface kits
0 = none
A = LonTalk communications interface
(LCI) (comm5)
B = LCI (comm5) & generic building
automation system (GBAS) (0-5 VDC)
C = LCI (comm5) & GBAS (0-5 VDC) &
ventilation override module (VOM)
D = LCI (comm5) & VOM
E = GBAS (0-5 VDC)
F = GBAS (0-5 VDC) & VOM
G= VOM
Digit 14 Time clock
0 = none
A = time clock
Digit 15 Remote mounted human
interface
0 = none
A = remote mounted human interface
B = remote mounted human interface
with interprocessor communication
bridge module board kit
C = interprocessor communication bridge
module board kit
Digit 16 Zone sensor
0 = none
A = zone temperature sensor
BAYSENS017*

Digit 17 Zone sensor with timed override


0 = none
A = zone temperature densor with timed
override BAYSENS013*
Digit 18 Zone sensor with timed override
and local setpoint adjustment
0 = none
A = zone temperature sensor with timed
override buttons and local setpoint
adjustment BAYSENS014*
Digit 19 Remote minimum position
potentiometer control
0 = none
A = remote minimum position
potentiomenter control BAYSTAT023*
Digit 20 Dual setpoint sensor
0 = none
A = dual setpoint sensor
Digit 21 Dual setpoint sensor with
system function lights
0 = none
A = dual setpoint sensor with system
function lights
Digits 22 Space relative humidity kit
0 = none
A = space relative humidity kit
Digit 23 Carbon dioxide sensor
0 = none
A = carbon dioxide sensor
Digit 24 Dry-bulb duct sensor
0 = none
A = dry-bulb duct sensor

MUA-PRC004-EN

Selection
Procedure
FAU Selection Procedure
Prior to selecting the fresh air unit (FAU)
for a given application, give careful
consideration to determining the design
latent conditions (as described in the
Applications Considerations section of
this catalog). Use Tables AC-1, AC-2,
and AC-3 on pages 9 and 10 to identify
the appropriate supply air dew point for
specific design conditions. See SYSAPG001-EN or SYS-APM-004 for more
detailed information.
Selection of Trane Packaged Fresh Air
units is divided into five basic areas:
1. cooling/dehumidification capacity
2. air delivery
3. heating capacity
4. unit electrical requirements
5. unit designation
Factors used in unit cooling/dehumidification (drying) selection:
Example
Example unit options include:
parallel blade OA damper
2 pleated media filters
gas heat hi rise, single bank, 2-stage
fan type 12-9
Given conditions:
airflow required for proper ventilation
(per ASHRAE 62) = 2300 cfm
outside air summer design conditions
= 95db/78wb, 95F entering air to
condenser
supply air design dew point requirement = 53F dew point
total peak cooling load = 198 MBh (16.5
tons)
total peak dehumidification load = 90
MBh (7.5 tons)
condenser reheat provided (yes or no)
= for this example, reheat is installed
external static pressure = 0.5 inches
desired supply air db temp. = 75F
Step 1 Determine unit size.
To determine which unit size will meet
your capacity requirements, first review
the airflow ranges found in Table GD-1
on page 21. The specified airflow in this
example of 2300 cfm falls in both the
size 031 and 040 unit airflow ranges.
Step 2 Determine SA dew point
capability.
Check the smaller unit size first to
determine if it has the capacity to meet
the supply air dew point and cooling/
dehumidification requirements. See
MUA-PRC004-EN

Table PD-31 to review the supply air


dew point vs. airflow range that the size
031 unit can provide. At 95db/78wb,
the size 031 produces 53F dew point
supply air at 2301 cfm (value found by
interpolating between the 52F and
54F dew point data provided in the
table). Therefore, the size 031 unit
meets the supply air dew point requirement.
Step 3 Determine unit capacity.
Now check that the size 031 unit meets
the cooling and dehumidification
capacity requirements by reviewing
Table PD-28. At 2300 cfm and 95F db/
78F wb, the size 031 unit produces
201.42 MBh total and 92.68 MBh latent
capacity. This meets our requirement.
Also note that Table PD-27 provides
information very similar to that in Table
PD-28. Use Table PD-27 (and tables like
it for all other units sizes) only when
condenser reheat is not provided. For
this example, we will include condenser
reheat.
Step 4 Determine supply air fan data.
First calculate size 031 unit total static
pressure (tsp) at design supply cfm
using the appropriate air pressure drop
tables. See calculation below:
external static pressure = 0.50
parallel blade OA damper = 0.01
2 pleated media filter =
0.08
main evap coil (wet) =
0.37
reheat evap coil (wet) =
0.19
condenser reheat coil =
0.15
gas heat exchanger =
0.37
unit total static pressure = 1.67
Using 2300 cfm and tsp of 1.67 inches,
refer to Table PD-1, which shows 1017
rpm and 1.06 bhp at 1.6 tsp. Interpolate
the values from the table (between 1.60
and 1.80 tsp), and calculate 1058 rpm
and 1.077 bhp at 1.67 tsp.
Step 5 Determine supply air temperature.
If the unit does not have condenser
reheat, the supply air db is equal to the
supply air dew point (53F). However,
for this example, condenser reheat is
required, and a supply air db temperature of 75F is desired. Go to Table PD30 on page 49 to determine the supply
air db temperature produced by the size
031 unit. At 2300 cfm and 95F db/78F
17

Selection
Procedure
db, the size 031 unit produces condenser reheat max temp rise of 24.9F.
Now calculate the fan motor heat temp
rise for this selection. Go to Figure SP-1
to determine that 1.077 bhp = 3.269
MBh. Supply fan motor heat temp rise =
3269 btu/(1.085 x 2300 cfm) = 1.3F.
Calculate supply air db temp by summing the off-coil supply air db with the
condenser reheat maximum temperature rise and the motor heat temperature rise at the design condition:
Supply air db temperature:
53F + 24.9F + 1.3F = 79.2F

Air Delivery Procedure

Unit Electrical Requirements

Supply Air Fan Selection


Unit supply air fan performance tables
include pressure drops for internal
cabinet static losses. Add static pressure
drops of optional components such as
heat and filters to the external duct
static pressure to determine the total
static pressure.

To determine electrical requirements


for wire sizing amps and maximum
over-current protection, see in the
Electrical Data section on pages 8689.

The supply requirements determined in


Step 4 of the cooling/dehumidification
capacity example was 1.077 bhp at
1058 rpm. Thus, the supply fan motor
size required is two hp at 1075 rpm.

Unit Designation
After determining specific unit capacity
requirements and considering specific
job requirements, determine the
complete unit model number by
referencing pages 1416.

Thus, the size 031 unit has the capability


to meet and slightly exceed the supply
air db temperature requirement of 75F.
So, for this example, the size 031 unit
meets all requirements with a supply air
temperature of 79.2F db/63.1F wb
with a 53F supply air dew point.

Heating Capacity Selection


Example
Given conditions:
winter outdoor design conditions = 0F
heat type = gas
max temp rise or heating kW/MBh
requirement = 80F temperature rise
To select a single bank gas heater as
specified, go to Table PD-73 for the size
031 unit. At 2300 cfm, a 250 MBh gas
heater will produce an 80F temperature rise. Select this heater.

120
110
100

fan motor heat (MBh)

However, if the supply air temp setpoint


at the unit controller is set to 75F, the
unit will modulate the condenser reheat
to meet that supply air condition versus
exceed it. Also note that Table PD-30
provides reheat max temp rise data for
typical design and part load conditions.
This enables you to determine if the
condenser reheat is sufficient to
maintain comfort during typical part
load conditions.

STANDARD MOTOR
HIGH EFFICIENCY MOTOR

90
80
70
60
50
40
30
20
10
0
0

10

15

20

25

30

35

40

motor brake horsepower


Note: Fan motor heat (MBh) includes 1.1 correction factor for motor efficiency.

Figure SP-1. Fan motor heat

If your application requires electric heat,


use the electric heat tables on pages 73
through 74.

18

MUA-PRC004-EN

Selection
Procedure
Fresh Air Unit with Total
Energy Wheel
Common Terms
Following are definitions of common
terms used when selecting a fresh air
unit with a total energy wheel.For more
information on this subject, reference
Trane application manual, Air-to-Air
Energy Recovery in HVAC Systems,
SYS-APM003-EN.
EATR - exhaust air transfer rate
expressed as a percentage, is the tracer
gas concentration difference between
the outdoor airflow entering the total
energy wheel and the supply airflow
leaving the wheel divided by the tracer
gas concentration difference between
the exhaust airflow entering the total
energy wheel and the outdoor airflow
entering the wheel.
OACF - The outside air correction factor
is defined as the supply-side airflow
upstream of the wheel divided by the
supply-side airflow downstream of the
wheel. This value is important for sizing
the fans. Also, if the system includes an
airflow monitoring station or flowmeasuring damper, it allows for the set
point of this device to compensate and
assure that the proper amount of
outdoor air flows into the wheel so that
the required amount of outdoor air
leaves the wheel. The OACF is typically
small unless the pressure difference
between the air streams is greater then
3.0 in H2O.
The term effectiveness is used to
describe the heat transfer efficiency of
an air-to-air heat exchanger. Effectiveness is defined as the actual energy
(sensible, latent, or total) transferred by
Table SP-1. OACF values
2P3

031

unit size
040
051

066

-2
-1.5
-1
-0.5
0
0.5
1
1.5
2
2.5
3

0.98
1.00
1.01
1.03
1.05
1.06
1.08
1.10
1.12
1.13
1.15

0.98
0.99
1.01
1.02
1.04
1.05
1.07
1.08
1.10
1.11
1.13

0.99
1.00
1.01
1.02
1.03
1.04
1.05
1.06
1.07
1.08
1.09

0.99
1.00
1.02
1.03
1.04
1.05
1.06
1.07
1.09
1.10
1.11

Note: EATR and OACF values are for wheels without


purge. EATR for all units = 4%.

MUA-PRC004-EN

the device, divided by the maximum


possible energy transfer between the
two air streams. If the effectiveness of
the device were 100% the condition of
the air leaving the supply-side of the
device would be the same as the
condition of the air entering the exhaust-side of the device.
In addition to understanding the wheel
performance terms, consideration
should be given to airflow performance
in applications with a total energy
wheel. The terms below explain the air
paths through the total energy wheel
and should all be considered when
selecting an energy recovery device.
Entering exhaust airflow represents
the exhaust airflow exiting the building
prior to passing through the total
energy wheel.
Leaving exhaust airflow represents the
exhaust airflow after passing through
the total energy wheel.
Net exhaust airflow represents the
portion of leaving exhaust airflow that
originated as entering exhaust airflow.
Leaving supply airflow represents the
sum of the net supply airflow and the
additional air picked up in the airstream
while passing through the total energy
wheel (difference between entering
and net exhaust airflow).
Outdoor airflow represents the amount
of outdoor air entering the unit.
Net supply airflow represents that
portion of the leaving supply airflow
that originated as outdoor airflow
(equal to 1 - EATR.

Note: EA/OA is the ratio of net exhaust


airflow to net supply airflow (expressed
as a percentage).

Selection Example
Given:
4000 cfm, 100% EA/OA, 95/78F OA
conditions, 72/60F (52 dewpoint) SA
conditions, 1 WC supply ESP, 1 WC
exhaust ESP, 75/63F summer RA
conditions, 70F/30% RH winter RA
conditions

Step 1 - Determine unit size.


To determine which unit size will meet
your capacity requirements, first review
the airflow ranges found in Table GD-1.
The specified airflow in this example of
4000 falls into unit sizes 040, 051, and
066 airflow ranges.
Step 2 - Determine SA dewpoint
capability.
Check the smaller unit size first to
determine if it has the capacity to meet
the supply air dewpoint requirements.
See Table PD-56 on page 63 to review
the supply air dewpoint vs. airflow
range that the size 040 unit can provide.
At 95/78F, the size 040 unit has the
capacity at 4000 cfm to provide a 51 DP
or higher. Therefore, the size 040 unit
meets the supply air dewpoint requirement.
Step 3 - Determine unit and wheel
capacity.
The 040 unit with a total energy wheel
data can be pulled directly of the unit
capacity Tables PD-53 and PD- 54 on
pages 62-63:
The 040 unit with a total energy wheel
produces 391 MBh total capacity and
155 MBh latent capacity.
The 040 wheel only capacity is 152 MBh
total and 92 MBh latent.
Step 4 - Determine exhaust airflow and
actual amount of OA supplied to the
space.
Use the APD lookup tables to find P2
and P3 below for the 040 unit at 4000
cfm:
Find P2 = energy module OA filters +
energy wheel and module (use Table
PD-13)
P2 = 0.23 + 1.34 = 1.57
Find P3 = energy module EA filters +
return ESP, using Table PD-13 on page
34:
P3 = 0.23 + 1 = 1.23
2P3 = 1.57 - 1.23 = 0.34
Find EATR and OACF using 2P3 from
Table SP-1:
EATR = 4.0%
OACF = 1.05
Calculate net OA:
netOA = SA(1-EATR)
netOA = 4000*(1- 0.04) = 3840 cfm
19

Selection
Procedure
Step 5 - Determine supply fan data.
First calculate unit total static pressure
at design cfm of 4000 using the appropriate air pressure drop tables. See
calculation below:
external static pressure = 1.00
energy wheel OA filters = 0.23
energy wheel & module = 1.34
OA dampers (Traq) =
0.28
reheat evap coil (wet) = 0.31
main evap coil (wet) =
0.62
condenser reheat coil = 0.24
unit total static pressure = 4.02
Use SA and TSP with the fan curve/
table to determine the supply fans
operating point.
12-9 FC, 1686 rpm, 5.19 hp
15-11 FC, 1330 rpm, 4.39 hp
Select 15-11 FC, 1350 rpm and 5 hp
motor.
Step 6 - Determine exhaust fan data.
EA = SA[OACF + EATR -1 + (1 EATR)[net EA/net OA]]
net EA = net OA [net EA/net OA]
EA = 4000*(1.05 + 0.04 - 1 + (1 0.04)*1.0) = 4200 cfm
NetEA = 3840*0.8 = 3072 cfm

1763 rpm, 5.07 hp


Select 1775 rpm, 7.5 hp
Step 7 - Determine supply air temperature.
The 040 unit with evap coils plus the
total energy wheel produce a supply air
db of 51F.
The 040 unit plus wheel produces a
reheat rise of 19.8F. See the size 040
unit/wheel reheat temp rise Table PD-55
on page 63.
Motor temp rise is X (for instructions on
calculating motor heat temp rise, review
step 5 under FAU selection procedure
for unit without total energy wheel).
Supply air temp = 51 + 19.8 + X = 70.8 +
X
Step 8 - Determine wheel frost
setpoint.
Find the point on the frost threshold
curve (Table SP-2) that intersects with
your RA winter relative humidity. Then
read the associated OA dry-bulb
temperature. The frost threshold chart
assumes winter RA dry-bulb or 70F.
For other conditions, use the TOPSS
selection program.

indoor relative humidity %

Use EA and P3 with the 040 exhaust fan


curve/tables, Chart PD-6 and Table PD-6

on page 27, to determine the exhaust


fans operating point.

outdoor temperature F
Figure SP-2. Frost threshold based on 70F return air
20

MUA-PRC004-EN

General
Data
Table GD-1. Packaged fresh air unit general data
Unit size
nominal cfm
maximum design cfm
minimum design cfm
Compressor data
reheat circuit (nom. tons R134a)
main circuit (nom. tons R134a)
unit cooling capacity steps %
Supply fan data, FC fan 1/FC fan 2
quantity
size (diameter-width), in.
maximum hp
maximum rpm
Condenser fan data
quantity/fan diameter, in.-type
cfm (reheat, main)
number of motors/hp each
Evaporator coil - main
size, ft2
rows/fin s series
tube diameter, in./surface
Evaporator coil - reheat
size, ft2
rows/fin series
tube diameter, in./surface
Condenser coil - main
size, ft2
rows/fin series
tube diameter, in./surface
Condenser coil - reheat outdoor
size, ft2
rows/fin series
tube diameter, in./surface
Condenser coil - reheat indoor
size, ft2
rows/fin series
tube diameter, in./surface
Heating data
gas heat input, MBh
elec. heat input, kW

031
3100
3100
1800

040
4000
4000
2200

051
5100
5100
2900

3.0T
6.2T + 9.3T
100-66-50-16

4.5T
6.7T + 10.0T
100-69-53-21

6.2T
6.2T + 6.2T + 9.3T
100-67-45-22

1/1
12-9/15-11
7.5/15
2115/1760

1/1
12-9/15-11
7.5/15
2115/1760

1/1
15-11/18-13
15/13.76
1760/1515

1/1
15-11/18-13
15/13.76
1760/1515

1/24;2/26-prop
2900, 8500
3/1.0

3/26-prop
4000, 10500
3/1.0

3/26-prop
5500, 12000
3/1.0

3/26-prop
5500, 13000
3/1.0

6.67
4/168
0.5/enhanced

8.33
4/168
0.5/enhanced

11.11
4/168
0.5/enhanced

14.06
4/168
0.5/enhanced

6.67
2/168
0.5/enhanced

8.33
2/168
0.5/enhanced

11.11
2/168
0.5/enhanced

14.06
2/168
0.5/enhanced

15.62
2/168
0.5/enhanced

17.71
2/168
0.5/enhanced

23.43
2/168
0.5/enhanced

28.13
2/168
0.5/enhanced

5.35
2/168
0.5/enhanced

7.29
2/168
0.5/enhanced

9.38
2/168
0.5/enhanced

9.38
2/168
0.5/enhanced

6.67
2/168
0.5/enhanced

8.33
2/168
0.5/enhanced

11.11
2/168
0.5/enhanced

14.06
2/168
0.5/enhanced

125-350
20-56

125-400
26-84

125-600
32-100

150-800
42-122

28
32
13

34
50
18

OIL00078
Mobil Artic EAL22CC
7/11.5
3.75

OIL00078
OIL00078
7/7/11.5
7

OIL00078
OIL0007
11.5/11.5/11.5
7

4 - 16x20x2
8.4

4 - 16x20x2
8.4

4 - 24x24x2
15.2

4 - 24x24x2
15.2

42
1
/2

48
1
/2

54
3
/4

60
3
/4

1
12-9
7.5
2115

1
12-9
7.5
2115

1
15-11
15
1760

1
15-11
15
1760

Refrigerant operating charge, lbs., R-134a


circuit (circuit 2)
25
reheat circuit (circuit 1)
29
cooling only (circuit 1)
9
Compressor oil data
main circuit POE oil type
OIL00078
reheat circuit POE oil type
Mobil Artic EAL22CC
main circuit, # pints
7/11.5
reheat circuit, # pints
4.13
Filters
number-size, in.
face area, ft2
Total energy (TE) wheel
wheel diameter (in)
wheel drive motor hp
exhaust fan
quantity
size (dia-width in.)
maximum hp
maximum rpm
outdoor air filters
number/size (in.)
face area (ft2)
return air filters
number/size (in.)
face area (ft2)

MUA-PRC004-EN

066
6600
6600
3600
6.2T
10.0T + 10.0T + 10.0T
100-72-45-17

main
48
52
20

4 - 16x20x2
8.4

4 - 16x20x2
8.4

4 - 20x25x2
13.3

4 - 20x25x2
13.3

4 - 16x20x2
8.4

4 - 16x20x2
8.4

4 - 16x25x2
10.5

4 - 16x25x2
10.5

21

Performance
Data

fan data

Chart PD-1. Size 12-9 supply fan, unit size 031

50% WO

2115 rpm
2100 rpm

70% WO

2000 rpm
1900 rpm

80% WO

1800 rpm
1700 rpm

1600 rpm

4000

2000

7.5 bhp

5.0 bhp

3.0 bhp

2.0 bhp

1400 rpm
1300 rpm
1200 rpm
1100 rpm
1000 rpm
900 rpm
800 rpm
700 rpm
600 rpm

1.5 bhp

90% WO

1500 rpm

1.0 bhp

total static pressure, in. wg.

60% WO

25% WO

6000

10000

8000

airflow, cfm
Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat
coils, and TE wheel pressure drops to external duct static pressure.

Table PD-1. Size 12-9 supply fan, unit size 031

cfm
1800
2200
2600
3100

total static pressure, in. wg.


0.0
0.5
1.0
1.5
2.0
3.0
3.5
4.0
5.0
5.5
6.0
7.0
7.5
8.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
401
490
578
690

0.18
0.33
0.55
0.93

609
658
721
802

0.34
0.51
0.75
1.14

802
827
867
929

0.52 976
0.72 982
1.02 1005
1.42 1052

0.71
0.95
1.24
1.76

1148
1126
1138
1169

0.95
1.18
1.51
2.02

1438
1405
1377
1390

1.46
1.73
2.06
2.66

1565
1532
1499
1493

1.73
2.03
2.38
2.98

1677
1654
1618
1590

2.01
2.35 1866 3.01 1965 3.35
2.72 1836 3.44 1935 3.81 2031 4.20
3.31 1792 4.05 1893 4.46 1989 4.88 2169 5.73

outside 25%WO limit


outside rpm limit

22

MUA-PRC004-EN

Performance
Data

fan data

Table PD-2. Size 15-11 supply fan, unit size 031

50% WO

25% WO
1760 rpm

60% WO

6
5

1600 rpm

70% WO

1500 rpm
1400 rpm

80% WO
1300 rpm

1200 rpm

1000 rpm

1100 rpm

7500

15.0 bhp

10.0 bhp

5.0 bhp

3.0 bhp

2.0 bhp

5000

2500

7.5 bhp

1.5 bhp

90% WO

900 rpm
800 rpm
700 rpm
600 rpm
500 rpm
400 rpm

1.0 bhp

total static pressure, in. wg.

1700 rpm

12500

10000

15000

airflow, cfm
Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat
coils, and TE wheel pressure drops to external duct static pressure.

Table PD-2. Supply fan size 15-11, unit size 031


0.0

0.5

1.0

1.5

2.0

3.0

total static pressure, in. wg.


3.5
4.0
5.0

5.5

6.0

7.0

7.5

8.0

cfm

rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

1800
2200
2600
3100

227
277
327
390

0.09
0.16
0.26
0.44

463
479
501
534

0.26
0.37
0.50
0.69

664
648
657
677

0.49
0.59
0.76
1.03

832
813
798
801

0.77
0.89
1.04
1.33

968
956
936
918

1.07
1.23 1185 1.96
1.40 1174 2.20 1275 2.62 1366 3.06
1.66 1150 2.51 1254 2.97 1352 3.47 1523 4.47

outside 25%WO limit

MUA-PRC004-EN

23

Performance
Data

fan data

Chart PD-3. Size 12-9 exhaust fan, unit size 031

8
2115 rpm
2100 rpm
2000 rpm

1900 rpm

30% WO

50% WO

1800 rpm

60% WO

1700 rpm

1600 rpm

70% WO

1500 rpm

90% WO

7.5 bhp

5.0 bhp

1100 rpm
1000 rpm
900 rpm
800 rpm
700 rpm
600 rpm

3.0 bhp

80% WO

2.0 bhp

1400 rpm
1300 rpm
1200 rpm

1.5 bhp

1.0 bhp

total static pressure, in. wg.

0
2000

1000

5000

4000

3000

airflow, cfm
Note: Fan curves include internal energy module cabinet and wheel losses. Curves represent fan performance with an air density of 0.075 lbm/ft3.

Table PD-3. Exhaust fan size 12-9, unit size 031


0.0
rpm

1800 692
2200 845
2600 999
3100 1191

cfm

bhp

0.5
rpm

0.37
0.68
1.13
1.91

895
1013
1143
1314

bhp

1.0
rpm

bhp

1.5
rpm

0.55
0.89
1.37
2.21

1066
1169
1282
1430

0.72
1.11
1.63
2.50

1229
1305
1406
1546

total static pressure, in.wg.


2.0
2.5
bhp
rpm
bhp
rpm
bhp
0.94
1.33
1.87
2.81

1386
1438
1521
1650

1.16
1.58
2.13
3.10

1536
1568
1634
1747

1.39
1.84
2.43
3.38

3.0
rpm

bhp

3.5
rpm

bhp

4.0
rpm

1670
1697
1745
1842

1.61
2.12
2.73
3.72

1788
1822
1856
1937

1.83
2.40
3.05
4.08

1893
1936
1967
2032

bhp
2.03
2.67
3.38
4.44

4.5
rpm

bhp

2046
2075
2124

2.95
3.71
4.81

outside 25%WO limit


outside rpm limit

24

MUA-PRC004-EN

Performance
Data

fan data

Chart PD-4. Unit size 040 with 12-9 supply fan

50% WO

7
6
5

60% WO

25% WO
2115 rpm
2100 rpm

70% WO

2000 rpm
1900 rpm
1800 rpm

80% WO

1700 rpm

1600 rpm
1500 rpm

7.5 bhp

5.0 bhp

3.0 bhp

2.0 bhp

90% WO

1400 rpm
1300 rpm
1200 rpm
1100 rpm
1000 rpm
900 rpm
800 rpm
700 rpm
600 rpm

1.5 bhp

1.0 bhp

total static pressure, in. wg.

6000
4000
airflow, cfm

2000

8000

Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat
coils, and TE wheel pressure drops to external duct static pressure.

Chart PD-4. Supply fan size 12-9, unit size 040


total static pressure, in. wg.
0.0
0.5
1.0
1.5
2.0
3.0
3.5
4.0
5.0
5.5
6.0
7.0
7.5
8.0
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
2200
2600
3000
3400
3800
4000

490
578
667
756
845
890

0.33
0.55
0.84
1.23
1.71
2.00

658
721
786
853
929
968

0.51 827
0.75 867
1.05 915
1.44 975
1.93 1039
2.23 1072

0.72 982
1.02 1005
1.33 1041
1.77 1086
2.30 1138
2.58 1168

0.95
1.24
1.64
2.13
2.61
2.95

1126
1138
1162
1195
1240
1263

1.18
1.51
1.91
2.41
3.09
3.38

1405
1377
1386
1405
1430
1448

1.73
2.06
2.53
3.08
3.71
4.09

1532
1499
1490
1504
1524
1539

2.03
2.38
2.84
3.44
4.10
4.48

1654
1618
1591
1597
1615
1627

2.35
2.72
3.17
3.78
4.51
4.89

1866
1836
1800
1780
1786
1793

3.01
3.44
3.92
4.52
5.29
5.72

1965
1935
1900
1870
1869
1874

3.35
3.81
4.32
4.91
5.69
6.14

2031
1998
1965
1949
1951

4.20
4.74
5.35
6.09
6.54

2179
2145
2111
2104

5.59
6.24
6.97 2196 7.46
7.41 2185 7.89

outside 25% WO limit


outside rpm limit

MUA-PRC004-EN

25

Performance
Data

fan data

Chart PD-5. Unit size 040 with 15-11 supply fan

1760 rpm

60% WO

1700 rpm

1600 rpm

70% WO

6
1500 rpm

1400 rpm

80% WO

1300 rpm

1200 rpm

1100 rpm
1000 rpm

15.0 bhp

10.0 bhp

7.5 bhp

7500
10000
airflow, cfm

5000

2500

5.0 bhp

3.0 bhp

2.0 bhp

90% WO

900 rpm
800 rpm
700 rpm
600 rpm
500 rpm
400 rpm

1.5 bhp

1.0 bhp

total static pressure, in. wg.

50% WO

26% WO

15000

12500

Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat
coils, and TE wheel pressure drops to external duct static pressure.

Table PD-5. Supply fan size 15-11, unit size 040


0.0

0.5

1.0

1.5

2.0

total static pressure, in. wg.


3.0
3.5
4.0

cfm

rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

2200
2600
3000
3400
3800
4000

277
327
377
428
478
503

0.16
0.26
0.40
0.58
0.82
0.95

479
501
526
560
593
611

0.37
0.50
0.65
0.85
1.11
1.26

648
657
672
692
713
725

0.59
0.76
0.97
1.22
1.49
1.64

813
798
800
812
829
839

0.89
1.04
1.27
1.55
1.89
2.07

956
936
920
922
933
939

1.23
1.40
1.60
1.90
2.26
2.46

1174
1155
1135
1123
1125

2.20
2.44
2.72
3.05
3.28

1275
1261
1240
1221
1215

2.62
2.91
3.20
3.54
3.74

5.0

5.5

6.0

7.0

rpm bhp rpm bhp rpm bhp rpm bhp rpm


1354
1337
1317
1308

3.38
3.71
4.06
4.26

1526
1514
1495
1487

7.5

8.0

bhp rpm bhp rpm bhp

4.37
4.78 1594 5.33 1670 5.89
5.18 1577 5.77 1654 6.37 1798 7.59
5.41 1568 6.01 1646 6.62 1793 7.89

outside 25% WO limit


outside rpm limit

26

MUA-PRC004-EN

Performance
Data

fan data

Chart PD-6. Unit size 040 with 12-9 exhaust fan

8
2115 rpm
2100 rpm

total static pressure, in. wg.

2000 rpm

37% WO

1900 rpm

50% WO

1800 rpm

60% WO

5
1700 rpm

70% WO

1600 rpm

1500 rpm
1400 rpm

80% WO

1300 rpm
1200 rpm

1100 rpm

90% WO

7.5 bhp

5.0 bhp

3.0 bhp

2.0 bhp

1.0 bhp

1.5 bhp

1000 rpm
900 rpm
800 rpm
700 rpm
600 rpm

0
0

1000

3000
2000
airflow, cfm

4000

5000

Note: Fan curves include internal energy module cabinet and wheel losses. Curves represent fan performance with an air density of 0.075 ft3/lbm.

Table PD-6. Exhaust fan 12-9, unit size 040


0.00

0.50

1.00

total static pressure, in. wg.


2.00
2.50
3.00

1.50

3.50

4.00

4.50

cfm

rpm

bhp

rpm

bhp

rpm

bhp

rpm

bhp

rpm

bhp

rpm

bhp

rpm

bhp

rpm

bhp

rpm

bhp

rpm

bhp

2200
2600
3000
3400
3800
4000

845
999
1152
1306
1460
1537

0.68
1.13
1.73
2.52
3.52
4.11

1021
1149
1284
1424
1566
1638

0.90
1.38
2.03
2.86
3.90
4.50

1179
1291
1409
1534
1665
1733

1.12
1.65
2.33
3.19
4.27
4.89

1319
1419
1529
1644
1764
1825

1.35
1.90
2.63
3.54
4.64
5.28

1457
1538
1639
1748
1861
1920

1.62
2.18
2.92
3.89
5.04
5.70

1594
1655
1741
1845
1954
2010

1.90
2.49
3.23
4.21
5.43
6.11

1727
1769
1842
1936
2039
2095

2.18
2.80
3.58
4.54
5.78
6.51

1853
1884
1944
2025
2123
2176

2.47
3.13
3.94
4.93
6.15
6.89

1969
1998
2045
2113
2205
2254

2.76
3.47
4.32
5.33
6.56
7.27

2075
2109
2142
2203
-

3.03
3.82
4.68
5.74
-

outside rpm limit

MUA-PRC004-EN

27

Performance
Data

fan data

Chart PD-7. Unit size 051 with 15-11 supply fan

50% WO
1760 rpm

1600 rpm

15.0 bhp

10.0 bhp

5000
7500
airflow, cfm

2500

7.5 bhp

1200 rpm
1100 rpm
1000 rpm
900 rpm
800 rpm
700 rpm
600 rpm
500 rpm
400 rpm

5.0 bhp

90% WO

3.0 bhp

1300 rpm

2.0 bhp

1.5 bhp

1400 rpm

1
0

80% WO

1500 rpm

70% WO

1700 rpm

60% WO

25% WO

1.0 bhp

total static pressure, in. wg.

12500

10000

Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat
coils, and TE wheel pressure drops to external duct static pressure.

Table PD-7. Supply fan size 15-11, unit size 051


0.0

0.5

1.0

1.5

2.0

total static pressure, in. wg.


3.5
4.0
5.0

3.0

5.5

6.0

7.0

7.5

8.0

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
2900
3300
3700
4100
4500
4900
5100

353
402
451
500
548
597
621

0.35
0.51
0.72
0.98
1.29
1.67
1.88

498
525
555
588
620
653
673

0.56
0.75
0.97
1.23
1.53
1.88
2.09

646
662
678
704
731
759
775

0.87
1.09
1.32
1.59
1.94
2.37
2.59

776
784
797
812
829
853
867

1.15
1.41
1.71
2.04
2.40
2.78
3.00

900
896
903
913
928
945
952

1.48
1.74
2.07
2.45
2.88
3.34
3.57

1138
1116
1096
1098
1105
1115
1122

2.29
2.54
2.83
3.26
3.76
4.31
4.62

1243
1220
1196
1184
1187
1194
1198

2.74
3.01
3.30
3.69
4.21
4.79
5.10

1340
1317
1293
1272
1264
1271
1272

3.20
3.49
3.81
4.17
4.66
5.29
5.61

1494
1472
1449
1427
1415
1415

4.52
4.89
5.29
5.73
6.30
6.65

1574
1554
1531
1507
1487
1483

5.06
5.46
5.88
6.33
6.86
7.18

1650
1631
1608
1586
1563
1555

5.60
6.03
6.47
6.96
7.49
7.80

1775
1758
1733
1712
1701

7.22
7.74
8.25
8.84
9.15

1827
1805
1782
1767

8.39
8.95
9.54
9.82

outside 25%WO limit


outside rpm limit

28

MUA-PRC004-EN

Performance
Data

fan data

Chart PD-8. Unit size 051 with 18-13 supply fan

50% WO

60% WO
70% WO

1400 rpm

7
6

29% WO

1515 rpm
1500 rpm

1300 rpm

80% WO

1200 rpm

5
1100 rpm

90% WO

1000 rpm
900 rpm

10.0 bhp

7.5 bhp

5.0 bhp

3.0 bhp

2.0 bhp

800 rpm
700 rpm
600 rpm
500 rpm
400 rpm
300 rpm

1.5 bhp

1.0 bhp

total static pressure, in. wg.

10000
airflow, cfm

5000

20000

15000

Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat
coils, and TE wheel pressure drops to external duct static pressure.

Table PD-8. Supply fan size 18-13, unit size 051


0.00

0.50

1.00

1.50

2.00

3.00

total static pressure, in. wg.


3.50
4.00
5.00

5.50

6.00

7.00

7.50

8.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
2900
3300
3700
4100
4500
4900
5100

217
246
276
306
336
366
380

0.16
0.24
0.34
0.46
0.61
0.79
0.89

411
419
430
445
461
478
486

0.41
0.51
0.63
0.77
0.94
1.13
1.23

573
573
576
581
589
598
604

0.73
0.86
1.00
1.16
1.35
1.57
1.69

707
701
702
703
705
709
714

1.10
1.23
1.41
1.61
1.81
2.05
2.19

827
817
811
810
811
813
814

1.54
1.67
1.84 1008
2.06 999
2.31 995
2.59 992
2.73 993

2.90
3.10
3.36
3.66
3.85

1086
1080
1074
1072

3.70
3.96
4.26
4.43

1169
1160
1152
1148

4.37
4.62
4.91 1298 6.32
5.06 1295 6.50 1363 7.27

outside 25% WO limit

MUA-PRC004-EN

29

Performance
Data

fan data

Chart PD-9. Unit size 051 with 15-11 exhaust fan

1760 rpm
1700 rpm

1600 rpm

6
5

1400 rpm

1300 rpm

50% WO

33% WO

60% WO

1500 rpm

70% WO

1200 rpm
1100 rpm

80% WO

1000 rpm

15.0 bhp

10.0 bhp

7.5 bhp

3.0 bhp

4000
6000
airflow, cfm

2000

5.0 bhp

90% WO
2.0 bhp

800 rpm
700 rpm
600 rpm
500 rpm
400 rpm

1.5 bhp

900 rpm

1.0 bhp

total static pressure, in. wg.

8000

10000

Note: Fan curves include internal energy module cabinet and wheel losses. Curves represent fan performance with an air density of 0.075 lbm/ft3.

Table PD-9. Exhaust fan size 15-11, unit size 051


0.00

0.50

1.00

1.50

total static pressure, in. wg.


2.00
2.50

3.00

3.50

4.00

4.50

cfm

rpm

bhp

rpm

bhp

rpm

bhp

rpm

bhp

rpm

bhp

rpm

bhp

rpm

bhp

rpm

bhp

rpm

bhp

rpm

bhp

2900
3300
3700
4100
4500
4900
5100

537
612
686
760
834
908
945

0.63
0.92
1.30
1.77
2.34
3.02
3.41

700
759
820
883
947
1013
1046

0.94
1.28
1.70
2.21
2.82
3.54
3.95

840
885
935
990
1048
1108
1138

1.28
1.66
2.12
2.66
3.32
4.08
4.51

979
1005
1045
1091
1142
1195
1223

1.69
2.06
2.55
3.14
3.83
4.63
5.07

1151
1130
1153
1189
1232
1281
1306

2.32
2.56
3.03
3.63
4.35
5.19
5.66

1290
1283
1263
1286
1320
1363
1385

2.93
3.28
3.58
4.17
4.89
5.77
6.25

1393
1420
1399
1384
1409
1444
1464

3.44
4.03
4.37
4.78
5.50
6.37
6.86

1483
1518
1533
1505
1498
1524
1541

3.93
4.63
5.26
5.61
6.15
7.01
7.51

1565
1606
1633
1628
1605
1606
1618

4.41
5.20
5.98
6.56
7.01
7.71
8.20

1640
1683
1719
1740
1715
1697
1699

4.88
5.75
6.66
7.52
7.99
8.55
8.97

outside 25%WO limit

30

MUA-PRC004-EN

Performance
Data

fan data

Chart PD-10. Unit size 066 with 15-11 supply fan

50% WO

60% WO

1760 rpm

7
6

70% WO

1700 rpm
1600 rpm

80% WO

1500 rpm

1400 rpm

90% WO

1300 rpm
1200 rpm

2500

15.0 bhp

10.0 bhp

7.5 bhp

5.0 bhp

3.0 bhp

900 rpm
800 rpm
700 rpm
600 rpm
500 rpm

2.0 bhp

1100 rpm
1000 rpm

1.5 bhp

1.0 bhp

total static pressure, in. wg.

25% WO

12500

10000

7500
5000
airflow, cfm

Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat
coils, and TE wheel pressure drops to external duct static pressure.

Table PD-10. Supply fan size 15-11, unit size 066


0.0

0.5

1.0

1.5

2.0

total static pressure, in. wg.


3.5
4.0
5.0

3.0

5.5

6.0

7.0

7.5

8.0

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm
3600
4000
4400
4800
5200
5600
6000
6400
6600

439
487
536
585
634
682
731
780
804

0.66
0.91
1.21
1.57
1.99
2.49
3.06
3.71
4.07

548
580
613
644
683
726
772
818
842

0.91
1.16
1.45
1.78
2.20
2.71
3.30
3.98
4.35

673
696
725
752
782
815
848
879
895

1.26
1.51
1.84
2.26
2.71
3.20
3.76
4.38
4.71

793
809
824
846
875
901
930
961
977

1.63 900
1.96 911
2.31 924
2.68 941
3.12 957
3.69 981
4.35 1010
5.02 1037
5.39 1050

1.98
2.35
2.77
3.23
3.69
4.21
4.80
5.55
5.97

1101
1097
1102
1113
1126
1141
1157
1174
1185

2.75
3.15
3.62
4.17
4.79
5.45
6.14
6.84
7.22

1201
1185
1185
1193
1201
1215
1230
1247
1255

3.22
3.58
4.07
4.64
5.27
5.99
6.77
7.58
7.98

1298
1276
1265
1269
1276
1286
1299
1315
1322

3.72
4.07
4.52
5.12
5.79
6.53
7.35
8.24
8.68

1477
1455
1431
1416
1416
1423
1431
1441
1449

4.79
5.19
5.61
6.13
6.84
7.64
8.51
9.45
9.99

1559 5.35
1535 5.76
1512 6.21
1493 6.73
1484 7.38
1486 8.19
1494 9.10
1504 10.08
1508 10.59

1639 5.94
1615 6.36
1591 6.83
1567 7.34
1552 7.96
1549 8.75
1556 9.71
1562 10.71
1568 11.26

1782 7.11
1763 7.62
1742 8.15
1716 8.67
1694 9.29
1675 9.98
1674 10.93
1677 11.98
1680 12.54

1811 8.81
1787 9.38
1763 9.99
1742 10.68 1810
1733 11.56 1791
1736 12.66 1790
1737 13.23 1790

bhp
11.44
12.22
13.31
13.88

outside 25% WO limit


outside rpm limit but may be used for interpolation purposes

MUA-PRC004-EN

31

Performance
Data

fan data

Chart PD-11. Unit size 066 with 18-13 supply fan

50% WO

29% WO

1515 rpm
1500 rpm

60% WO
70% WO

1400 rpm

6
1300 rpm

80% WO

10.0 bhp

7.5 bhp

800 rpm
700 rpm
600 rpm
500 rpm
400 rpm

5.0 bhp

900 rpm

3.0 bhp

90% WO

1000 rpm

2.0 bhp

1100 rpm

1.5 bhp

1200 rpm

1.0 bhp

total static pressure, in. wg.

20000

15000

10000
airflow, cfm

5000

Note: Fan curves include internal cabinet static losses. To determine total static pressure to be used with these curves, add filter, damper, gas or electric heat, evaporator and reheat
coils, and TE wheel pressure drops to external duct static pressure.

Table PD-11. Supply fan size 18-13, unit size 066


total static pressure, in. wg.
0.00
0.50
1.00
1.50
2.00
3.00
3.50
4.00
5.00
5.50
6.00
7.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm
3600
4000
4400
4800
5200
5600
6000
6400
6600

269
298
328
358
388
418
447
477
492

0.31
0.43
0.57
0.74
0.94
1.18
1.45
1.76
1.93

427
441
457
474
490
507
527
549
560

0.60
0.73
0.90
1.08
1.29
1.52
1.79
2.10
2.28

576
580
587
595
608
621
637
654
662

0.96
1.12
1.30
1.51
1.76
2.03
2.35
2.69
2.88

702
702
704
708
715
723
732
744
752

1.36
1.55
1.76
1.99
2.26
2.55
2.88
3.25
3.46

813
809
811
812
815
818
826
833
838

1.79 1012
1.99 1002
2.25 996
2.52 992
2.80 992
3.11 994
3.48 995
3.86 997
4.07 999

2.86
3.05
3.29
3.58
3.94
4.34
4.75
5.17
5.39

1090
1081
1074
1072
1071
1072
1073
1076

3.66
3.90
4.17
4.53
4.95
5.40
5.88
6.13

1162
1153
1147
1145
1144
1146
1147

4.54
4.83
5.15
5.58
6.06
6.59
6.86

1303
1292
1287
1282
1282
1281

6.28
6.59
6.99
7.45
8.01
8.32

1361
1352
1346
1343
1343

7.36
7.74
8.20
8.73
9.04

1419
1411
1405
1403

7.50
8.00
bhp rpm bhp rpm bhp

8.58
9.01 1531 10.71
9.53
9.80
-

outside 25% WO limit


outside rpm or hp limit

32

MUA-PRC004-EN

Performance
Data

fan data

Chart PD-12. Unit size 066 with 15-11 exhaust fan

1760 rpm
1700 rpm

1600 rpm

31% WO
50% WO

1500 rpm

1400 rpm

1300 rpm

60% WO

70% WO

1200 rpm

80% WO

1100 rpm

1000 rpm

2000

6000

4000

15.0 bhp

10.0 bhp

7.5 bhp

5.0 bhp

3.0 bhp

2.0 bhp

90% WO
1.5 bhp

900 rpm
800 rpm
700 rpm
600 rpm
500 rpm
400 rpm

1.0 bhp

total static pressure, in. wg.

8000

airflow, cfm
Note: Fan curves include internal energy module cabinet and wheel losses. Curves represent fan performance with an air density of 0.075 lbm/ft3.

Table PD-12. Exhaust fan size 15-11, unit size 066


0.00

0.50

1.00

1.50

total static pressure, in. wg.


2.00
2.50

cfm

rpm

bhp

rpm

bhp

rpm

bhp

rpm

bhp

rpm

bhp

3600
4000
4400
4800
5200
5600
6000
6400
6600

608
675
743
810
878
945
1013
1080
1114

1.05
1.44
1.92
2.50
3.17
3.96
4.88
5.92
6.49

755
810
867
925
985
1046
1108
1171
1202

1.44
1.87
2.39
3.00
3.72
4.56
5.52
6.61
7.20

879
927
977
1029
1083
1137
1194
1252
1281

1.84
2.31
2.87
3.53
4.29
5.15
6.14
7.26
7.88

992
1032
1076
1123
1173
1224
1276
1330
1358

2.25
2.76
3.36
4.06
4.86
5.77
6.81
7.97
8.60

1103
1132
1169
1210
1255
1303
1354
1405
1430

2.71
3.23
3.87
4.60
5.43
6.38
7.47
8.67
9.32

MUA-PRC004-EN

rpm

3.00
bhp

1215 3.23
1232 3.75
1260 4.39
1296 5.16
1335 6.03
1379 7.02
1425 8.13
1474 9.37
1499 10.05

rpm

3.50
bhp

1353
3.98
1332
4.32
1351
4.96
1378
5.72
1413
6.63
1453
7.66
1496
8.82
1541 10.09
1565 10.78

rpm

4.00
bhp

1489 4.82
1452 5.10
1440 5.57
1461 6.34
1490 7.26
1525 8.31
1564 9.50
1607 10.82
1628 11.53

rpm

4.50
bhp

rpm

bhp

1595 5.56 1682 6.20


1578 6.02 1694 6.95
1543 6.34 1657 7.29
1545 7.01 1630 7.75
1566 7.91 1643 8.62
1597 8.98 1667 9.68
1633 10.21 1699 10.91
1671 11.55 1734 12.29
1692 12.29 1754 13.05

33

Performance
Data

airside pressure
drop

Table PD-13. Air pressure drop, in. wg.


coils

34

filters

cfm

main evaps
wet
dry

RH evaps
wet
dry

RH
cond
dry

unit
OA

ER
OA

ER
RA

031

1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100

0.26
0.28
0.30
0.33
0.35
0.37
0.40
0.42
0.45
0.48
0.50
0.53
0.56
0.59

0.20
0.22
0.23
0.25
0.27
0.29
0.31
0.33
0.35
0.37
0.40
0.42
0.44
0.46

0.13
0.14
0.15
0.16
0.17
0.19
0.20
0.21
0.23
0.24
0.25
0.27
0.28
0.29

0.10
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.23

0.10
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.23

0.05
0.05
0.06
0.06
0.07
0.08
0.08
0.09
0.10
0.11
0.11
0.12
0.13
0.14

0.05
0.05
0.06
0.06
0.07
0.08
0.08
0.09
0.10
0.11
0.11
0.12
0.13
0.14

040

2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000

0.25
0.27
0.28
0.30
0.32
0.34
0.36
0.38
0.40
0.42
0.44
0.46
0.48
0.50
0.53
0.55
0.57
0.59
0.62

0.19
0.20
0.22
0.23
0.25
0.26
0.28
0.29
0.31
0.33
0.34
0.36
0.38
0.40
0.41
0.43
0.45
0.47
0.49

0.12
0.13
0.14
0.15
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.23
0.24
0.25
0.26
0.27
0.29
0.30
0.31

0.10
0.10
0.11
0.12
0.12
0.13
0.14
0.15
0.16
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.22
0.23
0.24

0.10
0.10
0.11
0.12
0.12
0.13
0.14
0.15
0.16
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.22
0.23
0.24

0.07
0.08
0.08
0.09
0.10
0.11
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.23

0.07
0.08
0.08
0.09
0.10
0.11
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.23

unit
size

dampers
std. Traq

TE wheel
100%
&
RA module

0.05
0.05
0.06
0.06
0.07
0.08
0.08
0.09
0.10
0.11
0.11
0.12
0.13
0.14

0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.02
0.02
0.02
0.02
0.02
0.02
0.02

0.06
0.06
0.07
0.08
0.08
0.09
0.10
0.11
0.12
0.13
0.13
0.14
0.15
0.17

0.02
0.03
0.03
0.03
0.04
0.04
0.04
0.05
0.05
0.05
0.06
0.06
0.07
0.07

0.77
0.81
0.86
0.91
0.95
1.00
1.05
1.09
1.14
1.19
1.24
1.29
1.34
1.38

0.07
0.08
0.08
0.09
0.10
0.11
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.23

0.01
0.01
0.01
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.03
0.04
0.04
0.04
0.04

0.08
0.09
0.10
0.11
0.12
0.13
0.13
0.14
0.15
0.17
0.18
0.19
0.20
0.21
0.22
0.24
0.25
0.26
0.28

0.04
0.04
0.04
0.05
0.05
0.05
0.06
0.06
0.07
0.07
0.07
0.08
0.08
0.09
0.09
0.10
0.10
0.11
0.12

0.60
0.64
0.68
0.71
0.75
0.79
0.83
0.87
0.91
0.95
0.99
1.03
1.07
1.12
1.16
1.21
1.25
1.30
1.34

MUA-PRC004-EN

Performance
Data

airside pressure
drop

Table PD-14. Air pressure drop, in. wg.


coils
unit
size
051

066

MUA-PRC004-EN

filters

cfm

main evaps
wet
dry

RH evaps
wet
dry

RH
cond
dry

2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600

0.25
0.26
0.27
0.28
0.30
0.31
0.33
0.34
0.35
0.37
0.38
0.40
0.41
0.43
0.45
0.46
0.48
0.49
0.51
0.53
0.54
0.56
0.58
0.24
0.25
0.26
0.27
0.28
0.29
0.30
0.31
0.32
0.33
0.35
0.36
0.37
0.38
0.39
0.40
0.42
0.43
0.44
0.45
0.46
0.48
0.49
0.50
0.52
0.53
0.54
0.56
0.57
0.58
0.60

0.12
0.13
0.14
0.14
0.15
0.16
0.16
0.17
0.18
0.18
0.19
0.20
0.21
0.21
0.22
0.23
0.24
0.25
0.25
0.26
0.27
0.28
0.29
0.12
0.12
0.13
0.13
0.14
0.15
0.15
0.16
0.16
0.17
0.17
0.18
0.18
0.19
0.20
0.20
0.21
0.21
0.22
0.23
0.23
0.24
0.25
0.25
0.26
0.26
0.27
0.28
0.28
0.29
0.30

0.09
0.10
0.10
0.11
0.11
0.12
0.13
0.13
0.14
0.14
0.15
0.16
0.16
0.17
0.17
0.18
0.19
0.19
0.20
0.21
0.21
0.22
0.23
0.09
0.09
0.10
0.10
0.11
0.11
0.12
0.12
0.12
0.13
0.13
0.14
0.14
0.15
0.15
0.16
0.16
0.17
0.17
0.18
0.18
0.19
0.19
0.20
0.20
0.21
0.21
0.22
0.22
0.23
0.24

0.19
0.20
0.21
0.22
0.23
0.24
0.25
0.26
0.27
0.29
0.30
0.31
0.32
0.34
0.35
0.36
0.37
0.39
0.40
0.41
0.43
0.44
0.45
0.18
0.19
0.20
0.21
0.21
0.22
0.23
0.24
0.25
0.26
0.27
0.28
0.29
0.29
0.30
0.31
0.32
0.33
0.34
0.35
0.36
0.37
0.38
0.39
0.41
0.42
0.43
0.44
0.45
0.46
0.47

0.09
0.10
0.10
0.11
0.11
0.12
0.13
0.13
0.14
0.14
0.15
0.16
0.16
0.17
0.17
0.18
0.19
0.19
0.20
0.21
0.21
0.22
0.23
0.09
0.09
0.10
0.10
0.11
0.11
0.12
0.12
0.12
0.13
0.13
0.14
0.14
0.15
0.15
0.16
0.16
0.17
0.17
0.18
0.18
0.19
0.19
0.20
0.20
0.21
0.21
0.22
0.22
0.23
0.24

unit
OA

ER
OA

ER
RA

0.04
0.04
0.04
0.04
0.05
0.05
0.05
0.06
0.06
0.06
0.07
0.07
0.07
0.08
0.08
0.08
0.09
0.09
0.10
0.10
0.11
0.11
0.11
0.06
0.06
0.06
0.07
0.07
0.07
0.08
0.08
0.08
0.09
0.09
0.10
0.10
0.11
0.11
0.11
0.12
0.12
0.13
0.13
0.14
0.14
0.15
0.15
0.16
0.16
0.17
0.17
0.18
0.18
0.19

0.05
0.05
0.06
0.06
0.06
0.07
0.07
0.07
0.08
0.08
0.09
0.09
0.10
0.10
0.11
0.11
0.12
0.12
0.13
0.13
0.14
0.14
0.15
0.07
0.08
0.08
0.09
0.09
0.10
0.10
0.11
0.11
0.12
0.12
0.13
0.13
0.14
0.14
0.15
0.16
0.16
0.17
0.17
0.18
0.19
0.19
0.20
0.21
0.22
0.22
0.23
0.24
0.24
0.25

0.08
0.08
0.09
0.09
0.10
0.10
0.11
0.12
0.12
0.13
0.14
0.14
0.15
0.16
0.17
0.18
0.18
0.19
0.20
0.21
0.22
0.23
0.24
0.12
0.12
0.13
0.14
0.14
0.15
0.16
0.17
0.18
0.18
0.19
0.20
0.21
0.22
0.23
0.24
0.24
0.25
0.26
0.27
0.28
0.29
0.30
0.32
0.33
0.34
0.35
0.36
0.37
0.38
0.39

dampers
std. Traq

TE wheel
100%
&
RA
module

0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.04

0.03
0.03
0.03
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.05
0.05
0.06
0.06
0.06
0.06
0.07
0.07
0.07
0.08
0.08
0.08
0.09
0.04
0.05
0.05
0.05
0.05
0.06
0.06
0.06
0.06
0.07
0.07
0.07
0.08
0.08
0.08
0.09
0.09
0.09
0.10
0.10
0.11
0.11
0.11
0.12
0.12
0.12
0.13
0.13
0.14
0.14
0.15

0.07
0.08
0.08
0.09
0.09
0.10
0.10
0.11
0.12
0.12
0.13
0.14
0.14
0.15
0.16
0.16
0.17
0.18
0.19
0.20
0.20
0.21
0.22
0.11
0.12
0.12
0.13
0.14
0.14
0.15
0.16
0.16
0.17
0.18
0.19
0.20
0.20
0.21
0.22
0.23
0.24
0.25
0.26
0.27
0.28
0.29
0.30
0.31
0.32
0.33
0.34
0.35
0.36
0.37

0.70
0.73
0.76
0.78
0.81
0.84
0.86
0.89
0.92
0.95
0.97
1.00
1.03
1.06
1.09
1.11
1.14
1.17
1.20
1.23
1.26
1.29
1.32
0.62
0.65
0.67
0.69
0.72
0.74
0.77
0.79
0.82
0.84
0.87
0.89
0.92
0.94
0.97
1.00
1.03
1.05
1.08
1.11
1.14
1.17
1.19
1.22
1.25
1.28
1.31
1.34
1.38
1.41
1.44

35

Performance
Data

airside pressure
drop

Table PD-15. Single gas duct furnace with 12-9 fan, unit sizes 031 & 040, in. wg.
gas heat input/output (MBh)
unit size

031

040

36

cfm
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000

125/100
0.22
0.25
0.28
0.30
0.33
0.36
0.40
0.43
0.47
0.50
0.54
0.58
0.62

0.33
0.36
0.40
0.43
0.47
0.50
0.54
0.58
0.62

150/120
0.15
0.17
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.33
0.36
0.39
0.41
0.44
0.22
0.24
0.26
0.29
0.31
0.33
0.36
0.39
0.41
0.44
0.47
0.50
0.53
0.56
0.60

200/160
0.22
0.25
0.16
0.17
0.19
0.21
0.22
0.24
0.26
0.28
0.31
0.33
0.35
0.37
0.19
0.21
0.22
0.24
0.26
0.28
0.31
0.33
0.35
0.37
0.40
0.42
0.45
0.48
0.51
0.53
0.56
0.59
0.62

250/200

0.29
0.33
0.37
0.41
0.33
0.37
0.40
0.44
0.47
0.51
0.55
0.33
0.37
0.41
0.33
0.37
0.40
0.44
0.47
0.51
0.55
0.59
0.63
0.67
0.71
0.75
0.80
0.84
0.89
0.94

300/240

0.45
0.50
0.54
0.58
0.63
0.51
0.54

0.45
0.50
0.54
0.58
0.63
0.51
0.54
0.58
0.62
0.66
0.71
0.75
0.79
0.84
0.88
0.93

350/280

0.54
0.57
0.61

0.54
0.57
0.61
0.66
0.70
0.74
0.58
0.61
0.65
0.69
0.72
0.76

400/320

MUA-PRC004-EN

Performance
Data

airside pressure
drop

Table PD-16. Single gas duct furnace with 15-11 fan, unit sizes 031 & 040, in. wg.
unit size

031

040

MUA-PRC004-EN

gas heat input/output MBh)


250/200
300/240

cfm

125/100

150/120

200/160

1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100

0.19
0.22
0.24
0.26
0.29
0.32
0.34
0.37
0.40
0.43
0.47
0.50
0.54

0.11
0.13
0.14
0.15
0.17
0.18
0.20
0.22
0.24
0.25
0.27
0.29
0.31
0.33

0.21
0.24
0.10
0.11
0.12
0.13
0.15
0.16
0.17
0.19
0.20
0.21
0.23
0.24

0.26
0.29
0.31
0.34
0.25
0.27
0.29
0.32
0.34
0.36
0.39

0.37
0.40
0.43
0.46
0.50
0.36
0.38

350/280

0.62
0.66
0.71

400/320

2200
2300
2400
2500
2600

0.29
0.32
0.34
0.37
0.40

0.17
0.18
0.20
0.22
0.24

0.12
0.13
0.15
0.16
0.17

0.29
0.31
0.34
0.25
0.27

0.37
0.40

2700
2800
2900
3000
3100

0.43
0.47
0.50
0.54

0.25
0.27
0.29
0.31
0.33

0.19
0.20
0.21
0.23
0.24

0.29
0.32
0.34
0.36
0.39

0.43
0.46
0.50
0.36
0.38

0.62
0.66
0.71

3200
3300
3400
3500
3600

0.36
0.38
0.40
0.43
0.45

0.26
0.28
0.29
0.31
0.33

0.41
0.44
0.46
0.49
0.52

0.41
0.43
0.46
0.49
0.52

0.75
0.80
0.85
0.69
0.72

3700
3800
3900
4000

0.35
0.37
0.39
0.41

0.55
0.58
0.61
0.64

0.54
0.57
0.60
0.64

0.76
0.80
0.83
0.87

37

Performance
Data

airside pressure
drop

Table PD-17. Dual gas duct furnace with 12-9 fan, unit sizes 031 & 040, in. wg.
unit size

031

040

38

cfm

250/200

300/240

gas heat input/output (MBh)


350/280

400/320

1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100

0.55
0.61
0.66
0.72
0.78
0.85
0.91
0.98
1.05
1.13
1.20

0.47
0.50
0.54
0.59
0.63
0.67
0.72

0.48
0.52
0.55

2200
2300
2400
2500
2600

0.61
0.66
0.72
0.78
0.85

0.47
0.50

2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000

0.91
0.98
1.05
1.13
1.20
1.28
1.36
1.45
1.53
1.62
1.71
1.81
1.90
2.00

0.54
0.59
0.63
0.67
0.72
0.76
0.81
0.86
0.91
0.97
1.02
1.08
1.14
1.19

0.48
0.52
0.55
0.59
0.63
0.67
0.71
0.75
0.79
0.83
0.88
0.92

0.63
0.67
0.71
0.75
0.79
0.83
0.88
0.92

MUA-PRC004-EN

Performance
Data

airside pressure
drop

Table PD-18. Dual gas duct furnace with 15-11 fan, unit sizes 031 & 040, in. wg.
gas heat input/output (MBh)
unit size

031

040

MUA-PRC004-EN

cfm
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600

250/200

0.51
0.56
0.61
0.67
0.72
0.78
0.84
0.91
0.97
1.04
1.11
0.56
0.61
0.67
0.72
0.78
0.84
0.91
0.97
1.04
1.11
1.19
1.26
1.34
1.42
1.50

300/240

0.40
0.43
0.46
0.50
0.53
0.57
0.61

0.40
0.43
0.46
0.50
0.53
0.57
0.61
0.65
0.69
0.73
0.78
0.82

350/280

0.37
0.40
0.42

0.37
0.40
0.42
0.45
0.48
0.51
0.54
0.57

400/320

0.48
0.51
0.54
0.57

3700
3800
3900
4000

1.59
1.67
1.76
1.85

0.87
0.92
0.97
1.02

0.60
0.64
0.67
0.70

0.60
0.64
0.67
0.70

39

Performance
Data

airside pressure
drop

Table PD-19. Electric heat with 12-9 fan, unit sizes 031 & 040, in. wg.
unit size

031

040

40

cfm
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
2200
2300
2400
2500
2600

electric
heat
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
0.17
0.18
0.19
0.21
0.22
0.11
0.12
0.13
0.14
0.15

no
heat
0.07
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.19
0.20
0.10
0.11
0.12
0.13
0.14

2700
2800
2900
3000
3100

0.17
0.18
0.19
0.21
0.22

0.15
0.16
0.17
0.19
0.20

3200
3300
3400
3500
3600

0.23
0.25
0.26
0.28
0.30

0.21
0.22
0.24
0.25
0.27

3700
3800
3900
4000

0.31
0.33
0.35
0.37

0.28
0.30
0.31
0.33

MUA-PRC004-EN

Performance
Data

airside pressure
drop

Table PD-20. Electric heat with 15-11 fan, unit sizes 031 & 040, in. wg.
unit size

031

040

MUA-PRC004-EN

cfm
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000

electric
heat
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.08
0.08
0.09
0.10
0.10
0.11
0.12
0.06
0.06
0.07
0.08
0.08
0.09
0.10
0.10
0.11
0.12
0.13
0.13
0.14
0.15
0.16
0.17
0.18
0.19
0.20

no
heat
0.03
0.04
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.07
0.08
0.08
0.09
0.10
0.05
0.05
0.06
0.06
0.07
0.07
0.08
0.08
0.09
0.10
0.10
0.11
0.12
0.12
0.13
0.14
0.14
0.15
0.16

41

Performance
Data

airside pressure
drop

Table PD-21. Single gas duct furnace with 15-11 fan, unit sizes 051 & 066, in. wg.
gas heat input/output (MBh)
unit size

051

066

42

cfm
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700

125/100
0.50
0.54

150/120
0.29
0.31
0.33
0.36
0.38
0.40
0.43
0.45

200/160
0.21
0.23
0.24
0.26
0.28
0.29
0.31
0.33
0.35
0.37
0.39
0.41
0.43
0.45
0.47
0.49
0.51
0.54
0.56

250/200
0.34
0.36
0.39
0.41
0.44
0.46
0.49
0.52
0.55
0.58
0.61
0.64
0.67
0.71
0.74
0.78
0.81
0.85
0.89

300/240
0.50
0.36
0.38
0.41
0.43
0.46
0.49
0.52
0.54
0.57
0.60
0.64
0.67
0.70
0.74
0.77
0.81
0.84
0.88

350/280
0.48
0.52
0.56
0.60
0.64
0.68
0.52
0.55
0.59
0.62
0.65
0.69
0.72
0.75
0.79
0.82
0.86
0.90
0.93

400/320

0.64
0.67
0.71
0.75
0.79
0.83
0.88
0.71
0.74
0.78
0.82
0.85
0.89
0.94
0.98

4800
4900
5000
5100
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500

0.45

0.59
0.61

0.33
0.35
0.37
0.39
0.41
0.43
0.45
0.47
0.49
0.51
0.54
0.56
0.59
0.61

0.93
0.96
1.00
1.05
0.52
0.55
0.58
0.61
0.64
0.67
0.71
0.74
0.78
0.81
0.85
0.89
0.93
0.96
1.00
1.05
1.09
1.13
1.17
1.22

0.92
0.96
0.99
1.04
0.52
0.54
0.57
0.60
0.64
0.67
0.70
0.74
0.77
0.81
0.84
0.88
0.92
0.96
0.99
1.04
1.08
1.12
1.16
1.20

0.97
1.00
1.04
1.08
0.55
0.59
0.62
0.65
0.69
0.72
0.75
0.79
0.82
0.86
0.90
0.93
0.97
1.00
1.04
1.08
1.12
1.16
1.19
1.23

1.02
1.06
1.11
1.16
0.86
0.90
0.95
0.99
0.71
0.74
0.78
0.82
0.85
0.89
0.94
0.98
1.02
1.06
1.11
1.16
1.20
1.25
1.30
1.35

5600
5700
5800
5900
6000

1.26
1.31
1.35
1.40
1.45

1.25
1.29
1.34
1.39
1.43

1.27
1.31
1.35
1.39
1.43

1.41
1.46
1.51
1.57
1.63

6100
6200
6300
6400
6500
6600

1.50

1.48
1.53
1.58
1.63
1.68
1.74

1.47
1.52
1.56
1.60
1.64
1.69

1.68
1.74
1.80
1.86
1.92
1.99

MUA-PRC004-EN

Performance
Data

airside pressure
drop

Table PD-22. Single gas duct furnace with 18-13 fan, unit sizes 051 & 066, in. wg.
gas heat input/output (MBh)
unit size

051

066

MUA-PRC004-EN

cfm
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100

125/100
0.49
0.52

150/120
0.25
0.27
0.29
0.31
0.33
0.35
0.37
0.39

200/160
0.18
0.19
0.21
0.22
0.23
0.25
0.26
0.28
0.29
0.31
0.33
0.34
0.36
0.38
0.40
0.42
0.44
0.46
0.48
0.50
0.52

250/200
0.26
0.28
0.30
0.32
0.34
0.36
0.38
0.40
0.42
0.44
0.47
0.49
0.52
0.54
0.57
0.59
0.62
0.65
0.68
0.71
0.74
0.77
0.80

300/240
0.42
0.28
0.30
0.31
0.33
0.35
0.37
0.39
0.42
0.44
0.46
0.48
0.51
0.53
0.56
0.59
0.61
0.64
0.67
0.70
0.73
0.76
0.79

350/280
0.40
0.42
0.45
0.48
0.51
0.54
0.37
0.39
0.41
0.43
0.45
0.47
0.50
0.52
0.55
0.57
0.60
0.63
0.65
0.68
0.71
0.74
0.77

400/320

0.71
0.76
0.80
0.85
0.89
0.94
0.99
0.82
0.85
0.89
0.93
0.96
1.00
1.04
1.07
1.11
1.15
1.19
1.22

3600
3700
3800
3900
4000

0.39

0.28
0.29
0.31
0.33
0.34

0.40
0.42
0.44
0.47
0.49

0.39
0.42
0.44
0.46
0.48

0.39
0.41
0.43
0.45
0.47

0.77
0.81
0.86
0.90
0.73

4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000

0.36
0.38
0.40
0.42
0.44
0.46
0.48
0.50
0.52

0.52
0.54
0.57
0.59
0.62
0.65
0.68
0.71
0.74
0.77
0.80
0.83
0.87
0.90
0.93
0.97
1.00
1.04
1.08
1.12

0.51
0.53
0.56
0.59
0.61
0.64
0.67
0.70
0.73
0.76
0.79
0.82
0.85
0.89
0.92
0.96
0.99
1.03
1.06
1.10

0.50
0.52
0.55
0.57
0.60
0.63
0.65
0.68
0.71
0.74
0.77
0.80
0.83
0.86
0.90
0.93
0.96
1.00
1.03
1.07

0.76
0.80
0.83
0.87
0.90
0.94
0.97
1.01
1.05
1.08
1.12
1.15
1.19
1.23
1.26
1.30
1.34
1.38
1.42
1.45

6100
6200
6300
6400
6500
6600

1.15

1.14
1.18
1.22
1.26
1.30
1.34

1.11
1.14
1.18
1.22
1.26
1.30

1.49
1.53
1.57
1.61
1.65
1.69

43

Performance
Data

airside pressure
drop

Table PD-23. Dual gas duct furnace with 15-11 fan, unit sizes 051 & 066, in. wg.
unit size

051

061

44

gas heat input/output (MBh)


400/320
500/400
600/480

cfm

250/200

300/240

350/280

700/560

800/640

2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700

0.97
1.04
1.11
1.19
1.26
1.34
1.42
1.50
1.59
1.67
1.76
1.85
1.95
2.04
2.14
2.24
2.35
2.45

0.53
0.57
0.61
0.65
0.69
0.73
0.78
0.82
0.87
0.92
0.97
1.02
1.07
1.12
1.18
1.23
1.29
1.35
1.40

0.37
0.40
0.42
0.45
0.48
0.51
0.54
0.57
0.60
0.64
0.67
0.70
0.74
0.78
0.81
0.85
0.89
0.93
0.97

0.48
0.51
0.54
0.57
0.60
0.64
0.67
0.70
0.74
0.78
0.81
0.85
0.89
0.93
0.97

0.86
0.90
0.94
0.99
1.03
1.08
1.13

4800
4900
5000
5100
3600
3700
3800
3900
4000

1.50
1.59
1.67
1.76
1.85

1.46
1.53
1.59
1.65
0.82
0.87
0.92
0.97
1.02

1.01
1.06
1.10
1.15
0.57
0.60
0.64
0.67
0.70

1.01
1.06
1.10
1.15
0.57
0.60
0.64
0.67
0.70

1.18
1.23
1.28
1.33

1.26
1.31

4100
4200
4300
4400
4500

1.95
2.04
2.14
2.24
2.35

1.07
1.12
1.18
1.23
1.29

0.74
0.78
0.81
0.85
0.89

0.74
0.78
0.81
0.85
0.89

0.86
0.90
0.94
0.99
1.03

4600
4700
4800
4900
5000

2.45

1.35
1.40
1.46
1.53
1.59

0.93
0.97
1.01
1.06
1.10

0.93
0.97
1.01
1.06
1.10

1.08
1.13
1.18
1.23
1.28

1.26

5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600

1.65
1.72
1.79
1.85
1.92

1.15
1.19
1.24
1.28
1.33
1.38
1.43
1.48
1.53
1.59
1.64
1.69
1.75
1.80

1.15
1.19
1.24
1.28
1.33
1.38
1.43
1.48
1.53
1.59
1.64
1.69
1.75
1.80
1.86
1.92

1.33
1.38
1.43
1.49
1.54
1.60
1.66
1.72
1.78
1.84
1.90
1.96
2.03
2.09
2.16
2.23

1.31
1.36
1.41
1.47
1.52
1.58
1.63
1.69
1.75
1.81
1.87
1.93
2.00
2.06
2.13
2.19

1.61
1.66
1.71
1.76
1.81
1.86
1.91
1.96
2.02

2.24

MUA-PRC004-EN

Performance
Data

airside pressure
drop

Table PD-24. Dual gas duct furnace with 18-13 fan, unit sizes 051 & 066, in. wg.
gas heat input/output (MBh)
unit size

051

066

cfm
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700

250/200
0.96
1.03
1.10
1.17
1.24
1.32
1.40
1.48
1.56
1.65
1.74
1.83
1.92
2.01
2.11
2.21
2.31
2.42

300/240
0.50
0.53
0.57
0.60
0.64
0.68
0.72
0.76
0.81
0.85
0.90
0.94
0.99
1.04
1.09
1.14
1.19
1.25
1.30

350/280
0.34
0.36
0.39
0.41
0.44
0.46
0.49
0.52
0.55
0.58
0.61
0.64
0.67
0.71
0.74
0.78
0.81
0.85
0.89

400/320

0.44
0.46
0.49
0.52
0.55
0.58
0.61
0.64
0.67
0.71
0.74
0.78
0.81
0.85
0.89

500/400

0.70
0.73
0.77
0.80
0.84
0.88
0.92

600/480

700/560

800/640

4800
4900
5000
5100
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500

1.48
1.56
1.65
1.74
1.83
1.92
2.01
2.11
2.21
2.31
2.42

1.36
1.42
1.47
1.53
0.76
0.81
0.85
0.90
0.94
0.99
1.04
1.09
1.14
1.19
1.25
1.30
1.36
1.42
1.47
1.53
1.59
1.66
1.72
1.78

0.92
0.96
1.00
1.04
0.52
0.55
0.58
0.61
0.64
0.67
0.71
0.74
0.78
0.81
0.85
0.89
0.92
0.96
1.00
1.04
1.09
1.13
1.17
1.21

0.92
0.96
1.00
1.04
0.52
0.55
0.58
0.61
0.64
0.67
0.71
0.74
0.78
0.81
0.85
0.89
0.92
0.96
1.00
1.04
1.09
1.13
1.17
1.21

0.96
1.00
1.04
1.08

0.70
0.73
0.77
0.80
0.84
0.88
0.92
0.96
1.00
1.04
1.08
1.13
1.17
1.22
1.26

1.02
1.06

1.02
1.06
1.11
1.15
1.19
1.24

5600
5700
5800
5900
6000

1.26
1.30
1.35
1.40
1.44

1.26
1.30
1.35
1.40
1.44

1.31
1.36
1.41
1.46
1.51

1.29
1.33
1.38
1.43
1.48

1.25
1.30
1.34

6100
6200
6300
6400
6500
6600

1.49
1.54
1.59
1.64

1.49
1.54
1.59
1.64
1.70
1.75

1.56
1.61
1.66
1.72
1.77
1.83

1.53
1.58
1.63
1.69
1.74
1.80

1.39
1.43
1.48
1.53
1.58
1.63

1.94

MUA-PRC004-EN

45

Performance
Data

airside pressure
drop

Table PD-25. Electric heat with 15-11 fan, unit sizes 051 & 066, in. wg.
unit size

051

066

46

cfm

electric
heat

no
heat

2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100

0.10
0.11
0.12
0.13
0.13
0.14
0.15
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.23
0.24
0.25
0.26
0.27
0.28
0.29
0.31
0.32

0.08
0.09
0.10
0.10
0.11
0.12
0.12
0.13
0.14
0.14
0.15
0.16
0.17
0.18
0.19
0.19
0.20
0.21
0.22
0.23
0.24
0.25
0.26

3600
3700
3800
3900
4000

0.16
0.17
0.18
0.19
0.20

0.13
0.14
0.14
0.15
0.16

4100
4200
4300
4400
4500

0.21
0.22
0.23
0.24
0.25

0.17
0.18
0.19
0.19
0.20

4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600

0.26
0.27
0.28
0.29
0.31
0.32
0.33
0.34
0.36
0.37
0.38
0.40
0.41
0.43
0.44
0.46
0.47
0.49
0.50
0.52
0.53

0.21
0.22
0.23
0.24
0.25
0.26
0.27
0.28
0.29
0.30
0.31
0.33
0.34
0.35
0.36
0.37
0.39
0.40
0.41
0.42
0.44

MUA-PRC004-EN

Performance
Data

airside pressure
drop

Table PD-26. Electric heat with 18-13 fan, unit sizes 051 & 066, in. wg.
unit size

051

066

MUA-PRC004-EN

cfm
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100

electric
heat
0.06
0.07
0.07
0.07
0.08
0.08
0.09
0.09
0.10
0.11
0.11
0.12
0.12
0.13
0.13
0.14
0.15
0.15
0.16
0.17
0.17
0.18
0.19

no
heat
0.04
0.05
0.05
0.05
0.05
0.06
0.06
0.07
0.07
0.07
0.08
0.08
0.08
0.09
0.09
0.10
0.10
0.11
0.11
0.12
0.12
0.13
0.13

3600
3700
3800
3900
4000

0.09
0.10
0.11
0.11
0.12

0.07
0.07
0.07
0.08
0.08

4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000

0.12
0.13
0.13
0.14
0.15
0.15
0.16
0.17
0.17
0.18
0.19
0.20
0.20
0.21
0.22
0.23
0.24
0.24
0.25
0.26

0.08
0.09
0.09
0.10
0.10
0.11
0.11
0.12
0.12
0.13
0.13
0.14
0.14
0.15
0.15
0.16
0.16
0.17
0.17
0.18

6100
6200
6300
6400
6500
6600

0.27
0.28
0.29
0.30
0.31
0.32

0.19
0.19
0.20
0.21
0.21
0.22

47

unit
capacity

Performance
Data
Table PD-27. Size 031 cooling capacity without reheat installed, MBh
cfm

105/80

115/76

115/78

115/80

total
latent

179.28
95.94

186.37
107.02

193.74
118.48

173.48
74.21

180.28
84.98

187.35
96.11

168.58
53.76

174.16
63.66

180.52
73.84

164.83
35.19

170.12
44.31

175.65
53.70

1900

total
latent

183.27
98.41

190.49
109.87

197.98
121.69

177.18
75.45

184.10
86.58

191.29
98.05

172.35
54.21

177.98
64.34

184.24
74.69

168.39
34.62

173.77
44.02

179.38
53.69

2000

total
latent
total
latent
total
latent
total
latent

187.00
100.69
190.48
102.78
193.74
104.70
196.79
106.47

194.33
112.49
197.91
114.92
201.26
117.17
204.41
119.24

201.93
124.66
205.62
127.43
209.06
129.99
212.29
132.38

180.63
76.51
183.86
77.46
186.90
78.30
189.76
79.00

187.65
87.97
190.97
89.18
194.07
90.22
196.97
91.11

194.95
99.78
198.36
101.31
201.55
102.66
204.52
103.85

175.87
54.49
179.16
54.63
182.24
54.63
185.14
54.51

181.58
64.44
184.95
64.84
188.10
65.10
191.05
65.22

187.74
75.36
191.03
75.88
194.17
76.29
197.21
76.63

171.71
33.90
174.82
33.04
177.73
32.07
180.46
30.99

177.17
43.57
180.35
42.97
183.32
42.24
186.10
41.39

182.86
53.50
186.11
53.15
189.14
52.66
191.97
52.05

2400

total
latent

199.66
108.09

207.35
121.17

215.31
134.60

192.46
79.57

199.69
91.86

207.31
104.88

187.86
54.27

193.83
65.22

200.02
76.43

183.02
29.81

188.72
40.44

194.64
51.32

2500

total
latent

202.36
109.58

210.12
122.94

218.15
136.67

195.01
80.04

202.24
92.48

209.92
105.77

190.42
53.94

196.45
65.11

202.68
76.54

185.43
28.55

191.17
39.39

197.14
50.49

2600

total
latent
total
latent
total
latent
total
latent
total
latent

204.90
110.94
207.30
112.20
209.57
113.34
211.71
114.39
213.74
115.35

212.73
124.59
215.18
126.11
217.50
127.53
219.69
128.83
221.77
130.05

220.81
138.59
223.32
140.39
225.69
142.06
227.93
143.63
230.05
145.09

197.42
80.41
199.70
80.70
201.88
80.91
203.96
81.05
205.96
81.14

204.66
93.03
206.94
93.51
209.10
93.90
211.15
94.20
213.09
94.42

212.38
106.54
214.69
107.20
216.88
107.75
218.93
108.20
220.88
108.57

192.84
53.51
195.12
53.01
197.28
52.43
199.33
51.77
201.27
51.07

198.91
64.90
201.23
64.60
203.42
64.22
205.50
63.77
207.47
63.25

205.18
76.54
207.54
76.46
209.77
76.28
211.88
76.02
213.87
75.69

187.71
27.21
189.85
25.80
191.88
24.33
193.80
22.80
195.61
21.23

193.49
38.26
195.67
37.05
197.73
35.78
199.68
34.45
201.53
33.06

199.49
49.56
201.71
48.56
203.80
47.48
205.78
46.34
207.65
45.14

total
latent

215.67
116.23

223.74
131.17

232.05
146.46

207.87
81.18

214.94
94.58

222.72
108.85

203.11
50.30

209.33
62.67

215.76
75.29

197.37
19.85

203.28
31.63

209.43
43.89

dry-bulb / wet-bulb temperature (F)


95/78
95/80
105/76
105/78

2200
2300

2700
2800
2900
3000
3100

85/78

85/80

95/76

dry-bulb / wet-bulb temperature (F)


95/78
95/80
105/76
105/78

1800

2100

85/76

Table PD-28. Size 031 cooling capacity with reheat installed, MBh
cfm

85/76

85/78

85/80

95/76

105/80

115/76

115/78

115/80

total
latent
total
latent
total
latent
total
latent

182.16
96.98
186.24
99.50
190.05
101.81
193.60
103.93

188.99
108.09
193.20
110.98
197.12
113.65
200.78
116.11

196.07
119.54
200.41
122.81
204.44
125.83
208.21
128.64

177.53
75.51
181.40
76.86
185.03
78.03
188.43
79.02

184.02
86.16
187.99
87.84
191.69
89.32
195.15
90.61

190.84
97.29
194.91
99.28
198.70
101.05
202.22
102.61

174.42
55.83
178.41
56.41
182.14
56.83
185.64
57.10

179.76
65.23
183.84
66.11
187.66
66.80
191.22
67.33

185.68
75.55
189.67
76.45
193.44
77.18
197.03
77.76

172.31
37.93
176.19
37.55
179.82
37.02
183.23
36.34

177.36
47.08
181.34
46.98
185.05
46.72
188.52
46.30

182.67
56.49
186.72
56.67
190.50
56.67
194.04
56.50

2200

total
latent

196.93
105.88

204.20
118.39

211.72
131.24

191.63
79.86

198.38
91.72

205.52
104.01

188.92
57.22

194.57
67.70

200.45
78.45

186.43
35.54

191.78
45.74

197.35
56.19

2300

total
latent

200.05
107.66

207.41
120.49

215.01
133.66

194.64
80.56

201.42
92.68

208.60
105.25

192.00
57.21

197.71
67.94

203.64
78.93

189.44
34.62

194.84
45.05

200.46
55.73

2400

total
latent
total
latent
total
latent
total
latent

202.98
109.29
205.73
110.78
208.32
112.15
210.76
113.40

210.41
122.43
213.23
124.22
215.89
125.88
218.39
127.41

218.08
135.91
220.97
138.00
223.69
139.94
226.25
141.76

197.49
81.14
200.18
81.60
202.75
81.97
205.20
82.24

204.28
93.50
206.97
94.19
209.51
94.76
211.91
95.23

211.50
106.33
214.21
107.27
216.77
108.08
219.18
108.78

194.90
57.09
197.64
56.86
200.22
56.53
202.65
56.11

200.66
68.05
203.44
68.04
206.06
67.93
208.53
67.72

206.63
79.26
209.45
79.47
212.11
79.58
214.61
79.57

192.27
33.60
194.93
32.48
197.45
31.28
199.83
30.01

197.71
44.25
200.42
43.35
202.97
42.36
205.39
41.29

203.38
55.15
206.12
54.47
208.71
53.68
211.15
52.81

2800

total
latent

213.07
114.54

220.75
128.83

228.66
143.44

207.54
82.45

214.18
95.60

221.46
109.36

204.96
55.61

210.87
67.42

216.98
79.47

202.08
28.66

207.67
40.14

213.46
51.85

2900

total
latent

215.25
115.57

222.98
130.13

230.93
145.02

209.80
82.79

216.35
95.88

223.61
109.85

207.14
55.04

213.08
67.04

219.22
79.29

204.22
27.25

209.83
38.92

215.64
50.83

3000

total
latent
total
latent

217.31
116.52
219.27
117.38

225.09
131.34
227.08
132.45

233.08
146.48
235.12
147.85

211.92
82.98
213.94
83.10

218.40
96.08
220.36
96.21

225.65
110.25
227.60
110.57

209.21
54.41
211.18
53.71

215.17
66.60
217.17
66.09

221.34
79.03
223.35
78.71

206.24
25.79
208.16
24.28

211.87
37.65
213.82
36.32

217.72
49.73
219.68
48.58

1800
1900
2000
2100

2500
2600
2700

3100

48

MUA-PRC004-EN

Performance
Data

unit
capacity

Table PD-29. Size 031 reheat data, MBh


cfm 55/48 55/50 55/52 65/56
1800 39.3 40.9 42.4 45.4
1900 39.7 41.2 42.8 45.8
2000 40.0 41.6 43.1 46.1
2100 40.3 41.9 43.4 46.4
2200 40.6 42.1 43.7 46.7
2300 40.8 42.4 43.9 46.9
2400 41.1 42.6 44.1 47.2

65/58
46.9
47.3
47.6
47.9
48.2
48.4
48.6

65/60
48.4
48.8
49.1
49.4
49.7
49.9
50.1

dry-bulb / wet-bulb temperature (F)


75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
52.8 54.2 55.7 60.0 61.4 62.8 59.9 61.2 62.6
62.9 62.8
63.2 68.1 67.9
67.8
53.1 54.6 56.1 60.3 61.8 63.2 60.3 61.6 63.0
63.9 63.7
63.8 69.2 69.0
68.8
53.5 54.9 56.4 60.7 62.1 63.6 60.7 61.9 63.3
64.8 64.6
64.5 70.2 70.0
69.8
53.8 55.2 56.7 61.0 62.4 63.9 61.2 62.3 63.6
65.6 65.4
65.2 71.1 70.9
70.7
54.0 55.5 57.0 61.2 62.7 64.1 61.5 62.6 63.9
66.3 66.2
66.0 71.9 71.7
71.5
54.3 55.8 57.2 61.5 62.9 64.4 61.9 62.9 64.2
67.0 66.9
66.7 72.7 72.5
72.3
54.5 56.0 57.5 61.7 63.2 64.6 62.3 63.2 64.4
67.7 67.5
67.3 73.5 73.2
73.0

2500
2600
2700
2800
2900
3000
3100

48.8
49.0
49.2
49.3
49.5
49.6
49.8

50.3
50.5
50.7
50.9
51.0
51.1
51.3

54.7
54.9
55.0
55.2
55.3
55.5
55.6

41.3
41.5
41.7
41.9
42.1
42.2
42.4

42.8
43.0
43.1
43.3
43.5
43.6
43.7

44.3
44.5
44.7
44.9
45.0
45.2
45.3

47.4
47.6
47.8
48.0
48.2
48.3
48.5

56.2
56.4
56.5
56.7
56.8
57.0
57.1

57.7
57.9
58.0
58.2
58.3
58.5
58.6

61.9
62.1
62.3
62.4
62.6
62.7
62.9

63.4
63.6
63.8
63.9
64.1
64.2
64.3

64.8
65.0
65.2
65.4
65.5
65.7
65.8

62.7
63.1
63.5
63.9
64.4
64.8
65.1

63.5
63.8
64.1
64.3
64.6
64.9
65.1

64.7
64.9
65.1
65.3
65.5
65.7
65.9

68.3
68.9
69.4
70.0
70.4
70.9
71.3

68.1
68.7
69.2
69.8
70.2
70.7
71.1

67.9
68.5
69.0
69.5
70.0
70.5
70.9

74.2
74.8
75.4
76.0
76.5
77.1
77.5

73.9
74.6
75.2
75.8
76.3
76.8
77.3

73.7
74.3
74.9
75.5
76.0
76.6
77.0

Table PD-30. Size 031 condenser reheat max temperature rise,F


cfm
1800
1900
2000
2100
2200
2300
2400

55/48
20.1
19.2
18.4
17.7
17.0
16.3
15.8

55/50
20.9
20.0
19.1
18.4
17.6
17.0
16.3

55/52
21.7
20.7
19.9
19.0
18.3
17.6
16.9

65/56
23.2
22.2
21.2
20.3
19.5
18.8
18.1

dry-bulb / wet-bulb temperature (F)


65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80
24.0 24.7 26.9 27.7 28.4
30.4 31.1 31.8 30.4
31.0 31.7
22.9 23.6 25.7 26.4 27.1
29.0 29.7 30.3 29.0
29.6 30.2
21.9 22.6 24.5 25.2 25.8
27.7 28.3 28.9 27.7
28.2 28.8
21.0 21.6 23.5 24.1 24.7
26.5 27.1 27.7 26.6
27.0 27.6
20.1 20.7 22.5 23.1 23.7
25.4 26.0 26.5 25.5
25.9 26.4
19.3 19.9 21.6 22.2 22.8
24.4 24.9 25.5 24.5
24.9 25.4
18.6 19.2 20.8 21.3 21.9
23.4 23.9 24.5 23.6
24.0 24.4

2500
2600
2700
2800
2900
3000
3100

15.2
14.7
14.2
13.8
13.4
13.0
12.6

15.8
15.2
14.7
14.2
13.8
13.4
13.0

16.3
15.8
15.2
14.7
14.3
13.8
13.4

17.4
16.8
16.3
15.7
15.3
14.8
14.4

17.9
17.3
16.7
16.2
15.7
15.2
14.7

18.5
17.8
17.2
16.7
16.1
15.6
15.2

20.0
19.3
18.7
18.0
17.5
16.9
16.4

20.6
19.8
19.1
18.5
17.9
17.3
16.8

21.1
20.3
19.6
19.0
18.4
17.8
17.2

22.6
21.7
21.0
20.3
19.6
19.0
18.4

23.1
22.2
21.5
20.7
20.1
19.4
18.8

23.5
22.7
21.9
21.2
20.5
19.8
19.2

22.8
22.1
21.4
20.8
20.2
19.6
19.1

23.1
22.3
21.6
20.9
20.2
19.6
19.0

23.5
22.6
21.9
21.1
20.5
19.8
19.2

105/76 105/78 105/80 115/76 115/78 115/80


31.9 31.8
32.0
34.6
34.5 34.3
30.7 30.6
30.6
33.3
33.1 33.0
29.6 29.4
29.3
32.0
31.9 31.8
28.5 28.4
28.3
30.9
30.8 30.6
27.5 27.4
27.3
29.8
29.7 29.6
26.6 26.5
26.3
28.8
28.7 28.6
25.7 25.6
25.5
27.9
27.8 27.6
24.9
24.1
23.4
22.7
22.1
21.5
20.9

24.8
24.0
23.3
22.6
22.0
21.4
20.8

24.7
23.9
23.2
22.5
21.9
21.3
20.7

27.0
26.2
25.4
24.7
24.0
23.4
22.8

26.9
26.1
25.3
24.6
23.9
23.3
22.6

26.8
26.0
25.2
24.5
23.8
23.1
22.5

Table PD-31. Size 031 design supply air dew point, cfm
dry-bulb
(F)

wet-bulb
(F)

46

48

58

60

62

76
78
80

1896

2069
1868

2267
2038
1840

2497
2231
2005

2767
2455
2194

3090
2717
2412

3031
2668

2972

76
78
80
76
78
80
76
78
80

1863

1898

1996

2037
1827

2098
1813

2211
1893

2239
1995

2332
2003

2466
2093
1801

2476
2188
1957
2611
2223
1926
2779
2330
1989

2762
2414
2143
2952
2483
2122

2615
2210

2683
2360

2798
2369

2969
2474

3010
2617

2663

2797

2928

3024

85

95

105

115

MUA-PRC004-EN

design supply air dew point (F)


50
52
54
56

49

unit
capacity

Performance
Data
Table PD-32. Size 040 cooling capacity without reheat installed, MBh

total
latent
total
latent
total
latent

85/76
219.44
117.88
223.41
120.35
227.15
122.65

85/78
228.12
131.46
232.20
134.29
236.05
136.94

85/80
237.12
145.48
241.32
148.67
245.27
151.66

95/76
212.23
91.23
215.93
92.48
219.40
93.56

dry-bulb / wet-bulb temperature (F)


95/78
95/80
105/76
105/78
220.60
229.27
204.86
212.50
104.45
118.07
65.34
77.44
224.39
233.17
208.50
216.09
106.03
120.00
65.65
77.95
227.97
236.84
212.00
219.49
107.45
121.74
65.85
78.32

105/80
220.74
90.34
224.35
91.01
227.75
91.56

115/76
200.66
41.86
204.34
41.29
207.82
40.60

115/78
206.97
52.89
210.72
52.59
214.27
52.15

115/80
213.53
64.21
217.34
64.18
220.95
64.00

2500

total
latent

230.68
124.80

239.67
139.42

248.98
154.47

222.68
94.49

231.33
108.70

240.29
123.32

215.42
66.01

222.72
78.55

230.97
92.02

211.11
39.78

217.61
51.59

224.35
63.68

2600

total
latent

234.01
126.79

243.09
141.74

252.48
157.11

225.77
95.29

234.51
109.81

243.53
124.73

218.65
65.25

225.79
78.68

234.01
92.35

214.23
38.86

220.78
50.91

227.56
63.24

2700

total
latent
total
latent
total
latent
total
latent

237.16
128.65
240.15
130.37
242.98
131.97
245.67
133.47

246.33
143.90
249.38
145.93
252.28
147.83
255.03
149.60

255.79
159.58
258.92
161.91
261.88
164.10
264.68
166.16

228.70
95.96
231.46
96.51
234.08
96.96
236.57
97.29

237.50
110.78
240.34
111.62
243.02
112.34
245.55
112.96

246.60
125.99
249.49
127.12
252.23
128.13
254.82
129.01

221.72
65.17
224.62
65.00
227.39
64.73
230.02
64.37

228.73
78.71
231.56
78.67
234.30
78.56
236.99
78.42

236.90
92.55
239.65
92.65
242.26
92.65
244.75
92.56

217.18
37.85
219.99
36.74
222.65
35.55
225.18
34.29

223.77
50.12
226.62
49.24
229.32
48.27
231.88
47.22

230.60
62.68
233.48
62.02
236.21
61.27
238.81
60.43

3100

total
latent

248.22
134.85

257.63
151.26

267.34
168.09

238.93
97.54

247.96
113.47

257.28
129.79

232.53
63.94

239.54
77.43

247.14
92.39

227.60
32.96

234.33
46.10

241.28
59.51

3200

total
latent

250.64
136.13

260.11
152.82

269.87
169.92

241.17
97.70

250.25
113.89

259.62
130.47

234.91
63.44

241.95
77.13

249.43
92.15

229.89
31.57

236.66
44.91

243.63
58.51

3300

total
latent

252.95
137.33

262.47
154.28

272.27
171.64

243.32
97.84

252.43
114.22

261.84
131.06

237.18
62.86

244.26
76.76

251.63
91.86

232.09
30.12

238.87
43.66

245.87
57.45

3400

total
latent
total
latent
total
latent
total
latent

255.16
138.43
257.26
139.46
259.26
140.41
261.18
141.29

264.71
155.64
266.86
156.92
268.90
158.12
270.85
159.24

274.56
173.26
276.73
174.79
278.81
176.23
280.79
177.60

245.38
97.94
247.35
97.99
249.23
97.97
251.04
97.90

254.50
114.47
256.48
114.64
258.36
114.75
260.16
114.79

263.94
131.55
265.95
131.97
267.87
132.32
269.70
132.59

239.36
62.23
241.44
61.53
243.42
60.79
245.33
60.00

246.46
76.32
248.56
75.82
250.57
75.26
252.49
74.65

253.77
91.52
255.85
91.15
257.89
90.76
259.86
89.57

234.18
28.62
236.18
27.08
238.10
25.49
239.93
23.86

240.99
42.35
243.01
40.99
244.95
39.58
246.80
38.13

248.01
56.33
250.06
55.16
252.01
53.93
253.87
52.66

3800

total
latent

263.01
142.10

272.71
160.29

282.69
178.88

252.78
97.77

261.88
114.77

271.45
132.80

247.16
59.17

254.33
73.99

261.72
89.09

241.76
22.80

248.57
36.64

255.66
51.34

3900

total
latent

264.77
142.85

274.50
161.28

284.50
180.10

254.45
97.61

263.52
114.69

273.11
132.94

248.91
58.29

256.10
73.29

263.50
88.56

243.54
21.89

250.27
35.12

257.37
49.99

4000

total
latent

266.45
143.54

276.21
162.20

286.23
181.25

256.05
97.40

265.10
114.56

274.70
133.04

250.59
57.38

257.79
72.55

265.20
87.99

245.28
20.98

251.90
33.57

259.02
48.61

cfm
2200
2300
2400

2800
2900
3000

3500
3600
3700

50

MUA-PRC004-EN

Performance
Data

unit
capacity

Table PD-33. Size 040 cooling capacity with reheat installed, MBh

total
latent
total
latent
total
latent

85/76
222.46
118.93
226.56
121.47
230.43
123.83

85/78
230.61
132.42
234.83
135.31
238.80
138.02

85/80
239.01
146.28
243.34
149.54
247.42
152.60

95/76
216.71
92.44
220.61
93.80
224.28
94.99

dry-bulb / wet-bulb temperature (F)


95/78
95/80
105/76
105/78
224.59
232.71
211.69
218.58
105.57
119.09
67.18
79.36
228.58
236.81
215.78
222.51
107.23
121.09
67.60
79.95
232.33
240.66
219.64
226.25
108.71
122.91
67.95
80.40

105/80
226.08
92.13
230.02
92.99
233.75
93.68

115/76
209.29
45.08
213.32
44.71
217.14
44.21

115/78
215.28
56.13
219.37
56.02
223.24
55.78

115/80
221.52
67.45
225.66
67.61
229.58
67.62

2500

total
latent

234.08
126.02

242.55
140.56

251.25
155.47

227.76
96.03

235.86
110.02

244.28
124.54

223.30
68.24

229.82
80.72

237.27
94.21

220.75
43.58

226.90
55.40

233.28
67.49

2600

total
latent

237.53
128.06

246.08
142.93

254.87
158.17

231.04
96.94

239.20
111.17

247.69
126.01

226.77
68.42

233.26
80.93

240.62
94.61

224.18
42.84

230.37
54.90

236.79
67.22

2700

total
latent
total
latent
total
latent
total
latent

240.79
129.96
243.88
131.72
246.80
133.36
249.58
134.87

249.42
145.14
252.58
147.21
255.57
149.15
258.41
150.96

258.28
160.70
261.51
163.08
264.57
165.31
267.46
167.41

234.15
97.71
237.10
98.36
239.91
98.90
242.58
99.34

242.35
112.21
245.34
113.13
248.17
113.93
250.86
114.61

250.91
127.33
253.94
128.50
256.82
129.54
259.54
130.45

230.06
68.48
233.19
68.43
236.16
68.29
239.00
68.05

236.59
81.06
239.77
81.27
242.78
81.34
245.64
81.32

243.80
94.88
246.83
95.04
249.74
95.09
252.53
95.06

227.43
42.00
230.52
41.06
233.47
40.04
236.27
38.93

233.66
54.29
236.79
53.57
239.76
52.76
242.59
51.86

240.12
66.84
243.27
66.34
246.27
65.74
249.12
65.05

3100

total
latent

252.22
136.28

261.10
152.66

270.21
169.39

245.12
99.69

253.42
115.20

262.12
131.25

241.70
67.73

248.37
81.21

255.23
94.96

238.94
37.75

245.28
50.89

251.84
64.28

3200

total
latent

254.72
137.59

263.66
154.24

272.82
171.26

247.55
99.95

255.85
115.68

264.57
131.95

244.27
67.34

250.96
81.02

257.86
94.81

241.49
36.50

247.85
49.83

254.43
63.42

3300

total
latent

257.11
138.80

266.09
155.73

275.30
173.01

249.87
100.12

258.17
116.08

266.90
132.55

246.73
66.87

253.44
80.75

260.37
94.89

243.93
35.19

250.31
48.71

256.90
62.49

3400

total
latent
total
latent
total
latent
total
latent

259.38
139.91
261.55
140.95
263.62
141.90
265.60
142.78

268.41
157.11
270.62
158.41
272.73
159.62
274.74
160.75

277.65
174.66
279.90
176.22
282.04
177.69
284.09
179.07

252.10
100.23
254.23
100.26
256.27
100.24
258.24
100.16

260.38
116.39
262.49
116.62
264.51
116.79
266.44
116.89

269.13
133.09
271.25
133.54
273.27
133.92
275.21
134.23

249.08
66.33
251.32
65.73
253.47
65.08
255.53
64.37

255.80
80.40
258.07
80.00
260.23
79.53
262.30
79.00

262.75
94.74
265.02
94.51
267.20
94.22
269.28
93.88

246.26
33.82
248.48
32.40
250.61
30.93
252.66
29.41

252.65
47.53
254.89
46.30
257.04
45.00
259.09
43.67

259.25
61.49
261.51
60.44
263.66
59.32
265.72
58.16

3800

total
latent

267.49
143.59

276.66
161.81

286.04
180.38

260.14
100.02

268.30
116.93

277.05
134.47

257.50
63.62

264.29
78.42

271.28
93.47

254.61
27.86

261.06
42.28

267.70
56.95

3900

total
latent

269.30
144.33

278.50
162.80

287.91
181.61

261.97
99.84

270.08
116.91

278.82
134.65

259.40
62.82

266.19
77.79

273.19
93.01

256.49
26.27

262.94
40.86

269.60
55.69

4000

total
latent

271.03
145.02

280.26
163.73

289.70
182.78

263.73
99.62

271.79
116.84

280.52
134.77

261.21
61.98

268.02
77.12

275.02
92.51

258.29
24.64

264.76
39.41

271.42
54.40

cfm
2200
2300
2400

2800
2900
3000

3500
3600
3700

MUA-PRC004-EN

51

unit
capacity

Performance
Data
Table PD-34. Size 040 reheat data, MBh
cfm
2200
2300
2400
2500
2600

dry-bulb / wet-bulb temperature (F)


55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76
58.8 60.8 62.7 66.7 68.8 71.0 77.4 79.7 82.0 88.5 90.7 92.9 88.2 90.5 92.7 90.2
91.2
92.8
97.6
59.3 61.2 63.2 67.2 69.3 71.5 78.0 80.2 82.5 89.0 91.3 93.5 88.8 91.0 93.2 91.4
92.0
93.5
98.9
59.7 61.7 63.7 67.7 69.8 72.0 78.5 80.7 83.0 89.5 91.8 94.0 89.3 91.5 93.7 92.6
92.8
94.1 100.2
60.1 62.1 64.1 68.1 70.2 72.4 78.9 81.2 83.5 90.0 92.3 94.5 89.9 92.0 94.2 93.6
93.7
94.8 101.4
60.5 62.4 64.4 68.5 70.6 72.8 79.3 81.6 83.9 90.4 92.7 94.9 90.3 92.4 94.6 94.7
94.5
95.4 102.6

2700
2800
2900
3000
3100

60.8
61.1
61.4
61.7
61.9

62.8
63.1
63.4
63.7
64.0

64.8
65.1
65.4
65.7
66.0

68.9
69.2
69.5
69.8
70.1

71.0
71.4
71.7
72.0
72.3

73.2
73.6
73.9
74.2
74.5

79.7
80.1
80.4
80.8
81.1

82.0
82.4
82.7
83.0
83.3

84.3
84.6
85.0
85.3
85.6

90.8
91.2
91.6
91.9
92.2

93.1
93.5
93.8
94.2
94.5

95.3
95.7
96.1
96.4
96.7

90.8
91.2
91.7
92.1
92.5

92.8
93.2
93.6
94.0
94.3

95.0
95.4
95.8
96.1
96.4

95.6
96.6
97.4
98.3
99.1

95.5
96.4
97.3
98.1
98.9

96.1
96.7
97.4
98.0
98.7

103.6
104.7
105.6
106.6
107.5

103.5
104.5
105.5
106.4
107.3

103.4
104.4
105.3
106.2
107.1

3200
3300
3400
3500
3600

62.2
62.4
62.6
62.9
63.1

64.2
64.4
64.7
64.9
65.1

66.3
66.5
66.7
67.0
67.2

70.4
70.6
70.9
71.1
71.3

72.6
72.8
73.1
73.3
73.5

74.8
75.0
75.3
75.5
75.7

81.3
81.6
81.9
82.1
82.3

83.6
83.9
84.1
84.4
84.6

85.9
86.2
86.4
86.7
86.9

92.5
92.8
93.0
93.3
93.5

94.8
95.0
95.3
95.6
95.8

97.0
97.3
97.6
97.8
98.0

92.9
93.3
93.6
94.0
94.4

94.7
95.0
95.3
95.6
95.9

96.7
97.0
97.3
97.5
97.8

99.8
100.5
101.2
101.9
102.5

99.7
100.4
101.1
101.7
102.3

99.5
100.2
100.9
101.5
102.2

108.3
109.1
109.9
110.6
111.3

108.1
108.9
109.7
110.4
111.1

107.9
108.7
109.5
110.2
110.9

3700
3800
3900
4000

63.3
63.5
63.6
63.8

65.3
65.5
65.6
65.8

67.4
67.5
67.7
67.9

71.6
71.8
72.0
72.2

73.7
73.9
74.1
74.3

75.9
76.1
76.3
76.5

82.5
82.7
82.9
83.1

84.8
85.0
85.2
85.4

87.1
87.3
87.5
87.7

93.7
93.9
94.1
94.3

96.0
96.2
96.4
96.6

98.3
98.5
98.7
98.9

94.8
95.1
95.5
95.9

96.1
96.4
96.7
97.0

98.0
98.3
98.5
98.7

103.1
103.7
104.3
104.8

102.9
103.5
104.1
104.6

102.8
103.3
103.9
104.4

112.0
112.7
113.3
113.9

111.8
112.4
113.1
113.7

111.6
112.2
112.8
113.4

115/78 115/80
97.5
97.4
98.8
98.7
100.1 100.0
101.3 101.2
102.4 102.3

Table PD-35. Size 040 condenser reheat max temperature rise, F


cfm

dry-bulb / wet-bulbtemperature (F)


55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

2200
2300
2400
2500
2600

24.7
23.8
22.9
22.2
21.4

25.5
24.5
23.7
22.9
22.1

26.3
25.3
24.4
23.6
22.8

27.9
26.9
26.0
25.1
24.2

28.8
27.7
26.8
25.8
25.0

29.7
28.6
27.6
26.6
25.7

32.3
31.1
30.0
29.0
28.0

33.2
32.0
30.8
29.8
28.8

34.2
32.9
31.7
30.6
29.5

36.8
35.4
34.1
32.9
31.7

37.6
36.2
34.9
33.6
32.5

38.5
37.0
35.7
34.4
33.2

36.7
35.3
34.0
32.8
31.7

37.5
36.1
34.8
33.5
32.4

38.4
36.9
35.6
34.3
33.1

37.5
36.3
35.2
34.2
33.2

37.8
36.5
35.3
34.1
33.1

38.4
37.0
35.7
34.5
33.4

40.5
39.3
38.1
37.0
36.0

40.4
39.2
38.0
36.9
35.9

40.4
39.1
37.9
36.8
35.8

2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000

20.7
20.1
19.5
18.9
18.4
17.9
17.4
17.0
16.5
16.1
15.7
15.4
15.0
14.7

21.4
20.8
20.1
19.5
19.0
18.5
18.0
17.5
17.1
16.6
16.2
15.8
15.5
15.1

22.1
21.4
20.8
20.2
19.6
19.1
18.5
18.1
17.6
17.2
16.7
16.3
16.0
15.6

23.5
22.7
22.0
21.4
20.8
20.2
19.7
19.2
18.7
18.2
17.8
17.3
16.9
16.6

24.2
23.4
22.7
22.1
21.4
20.8
20.3
19.7
19.2
18.7
18.3
17.8
17.4
17.0

24.9
24.1
23.4
22.7
22.1
21.4
20.9
20.3
19.8
19.3
18.8
18.4
17.9
17.5

27.1
26.2
25.4
24.7
23.9
23.3
22.6
22.0
21.5
20.9
20.4
19.9
19.4
19.0

27.8
26.9
26.1
25.3
24.6
23.9
23.2
22.6
22.0
21.5
20.9
20.4
19.9
19.5

28.6
27.7
26.8
26.0
25.2
24.5
23.9
23.2
22.6
22.0
21.5
21.0
20.5
20.0

30.7
29.7
28.8
27.9
27.1
26.3
25.6
24.9
24.2
23.6
23.0
22.5
21.9
21.4

31.4
30.4
29.4
28.5
27.7
26.9
26.2
25.5
24.8
24.1
23.5
23.0
22.4
21.9

32.1
31.1
30.1
29.2
28.3
27.5
26.7
26.0
25.3
24.7
24.1
23.5
22.9
22.4

30.7
29.7
28.8
28.0
27.2
26.4
25.7
25.0
24.4
23.8
23.3
22.7
22.2
21.8

31.3
30.3
29.4
28.5
27.7
26.9
26.1
25.4
24.8
24.2
23.6
23.0
22.5
22.0

32.0
31.0
30.0
29.1
28.2
27.4
26.7
25.9
25.2
24.6
24.0
23.4
22.9
22.3

32.3
31.4
30.6
29.8
29.1
28.4
27.7
27.1
26.5
25.9
25.3
24.8
24.3
23.8

32.2
31.3
30.5
29.7
29.0
28.3
27.6
27.0
26.4
25.8
25.2
24.7
24.2
23.7

32.3
31.4
30.5
29.7
28.9
28.2
27.5
26.9
26.3
25.7
25.1
24.6
24.1
23.6

35.0
34.1
33.2
32.4
31.6
30.8
30.1
29.4
28.8
28.1
27.5
27.0
26.4
25.9

34.9
34.0
33.1
32.3
31.5
30.7
30.0
29.3
28.7
28.0
27.4
26.9
26.3
25.8

34.8
33.9
33.0
32.2
31.4
30.6
29.9
29.2
28.5
27.9
27.3
26.7
26.2
25.7

Table PD-36. SIze 040 design supply air dew point, cfm
drybulb
(F)
85

95

105

115

52

wetbulb
(F)
76
78
80
76
78
80
76
78
80

46
2329

2280

2271

48
2539
2291

2491
2238

2509
2200

50
2780
2497
2252
2734
2441

2792
2410

design supply air dew point (F)


52
54
56
3058
3385
3776
2731
3002
3319
2452
2680
2944
3018
3358
3772
2673
2945
3268
2395
2620
2881
3127
3535

2658
2969
3345
2343
2573
2845

58

3698
3252

3658
3188

3812
3174

60

3620

3560

3609

62

76
78
80

2387

2648
2260

2958
2503

3334
2789
2375

3346

3833

3804
3133
2641

3556
2958

MUA-PRC004-EN

Performance
Data

unit
capacity

Table PD-37. Size 051 cooling capacity without reheat installed, MBh

total
latent
total
latent
total
latent

85/76
278.02
148.46
281.82
150.83
285.49
153.09

dry-bulb / wet-bulb temperature (F)


85/78
85/80
95/76
95/78
289.08
300.62
268.58
279.28
165.70
183.52
114.49
131.30
293.05
304.71
272.15
282.96
168.44
186.62
115.70
132.84
296.84
308.61
275.56
286.47
171.05
189.57
116.80
134.27

95/80
290.40
148.63
294.15
150.50
297.74
152.24

105/76
258.64
81.51
262.07
81.82
265.38
82.04

105/78
268.53
96.68
271.96
97.21
275.21
97.63

105/80
279.12
113.21
282.58
113.86
285.87
114.38

115/76
253.32
52.28
256.95
51.93
260.43
51.49

115/78
260.79
65.40
264.45
65.27
267.97
65.05

115/80
268.53
80.43
272.18
80.42
275.80
80.39

3200

total
latent

289.01
155.25

300.46
173.54

312.29
192.37

278.81
117.79

289.83
135.57

301.17
153.85

268.58
82.19

278.35
97.95

289.01
114.79

263.77
50.97

271.35
64.75

279.22
78.86

3300

total
latent

292.38
157.29

303.93
175.90

315.84
195.04

281.93
118.67

292.99
136.74

304.44
155.33

271.67
82.27

281.37
98.19

292.01
115.12

266.94
50.35

274.59
64.36

282.50
78.69

3400

total
latent
total
latent
total
latent
total
latent

295.62
159.22
298.72
161.06
301.69
162.79
304.55
164.44

307.26
178.15
310.39
180.27
313.43
182.29
316.34
184.22

319.23
197.59
322.47
200.03
325.58
202.35
328.55
204.56

284.92
119.46
287.77
120.16
290.48
120.75
293.09
121.27

296.04
137.82
298.96
138.80
301.76
139.69
304.43
140.48

307.56
156.71
310.55
157.98
313.39
159.13
316.13
160.20

274.64
82.28
277.56
82.24
280.41
82.17
283.21
82.08

284.27
98.34
287.05
98.41
289.75
98.42
292.35
98.36

294.88
115.46
297.65
115.73
300.31
115.91
302.86
116.01

270.01
49.68
272.96
48.95
275.80
48.15
278.53
47.29

277.70
63.90
280.68
63.37
283.55
62.76
286.31
62.10

285.64
78.44
288.67
78.10
291.57
77.70
294.36
77.22

3800

total
latent

307.24
165.98

319.13
186.06

331.41
206.68

295.60
121.71

307.00
141.20

318.75
161.18

285.99
81.97

294.86
98.25

305.32
116.04

281.16
46.38

288.97
61.38

297.04
76.69

3900

total
latent

309.87
167.45

321.82
187.81

334.12
208.68

298.01
122.09

309.47
141.83

321.26
162.08

288.60
80.13

297.29
98.07

307.69
116.01

283.69
45.42

291.53
60.60

299.62
76.09

4000

total
latent
total
latent
total
latent
total
latent

312.39
168.85
314.81
170.17
317.15
171.42
319.39
172.60

324.39
189.47
326.87
191.05
329.26
192.56
331.55
194.00

336.75
210.61
339.28
212.46
341.71
214.22
344.05
215.91

300.33
122.39
302.56
122.62
304.70
122.80
306.76
122.92

311.83
142.40
314.11
142.89
316.29
143.31
318.40
143.67

323.68
162.90
326.00
163.64
328.22
164.31
330.36
164.91

291.09
79.89
293.51
79.62
295.85
79.29
298.10
78.92

299.65
97.86
301.95
97.61
304.19
97.32
306.39
97.00

309.97
115.91
312.18
115.76
314.31
115.56
316.37
115.31

286.13
44.42
288.48
43.37
290.76
42.28
292.95
41.16

294.00
59.78
296.37
58.91
298.67
57.99
300.88
57.03

302.11
75.44
304.51
74.74
306.82
73.99
309.05
73.20

4400

total
latent

321.56
173.72

333.76
195.37

346.29
217.52

308.75
122.98

320.43
143.98

332.43
165.45

300.28
78.50

308.54
96.67

318.36
115.02

295.07
40.00

303.02
56.04

311.20
72.36

4500

total
latent

323.65
174.78

335.89
196.67

348.46
219.06

310.66
122.99

322.38
144.23

334.41
165.93

302.39
78.05

310.66
96.32

320.30
114.69

297.12
38.81

305.08
55.01

313.28
71.49

4600

total
latent
total
latent
total
latent
total
latent

325.67
175.78
327.61
176.72
329.49
177.62
331.31
178.46

337.95
197.91
339.93
199.09
341.85
200.22
343.69
201.29

350.55
220.54
352.56
221.95
354.51
223.31
356.39
224.61

312.52
123.05
314.33
123.10
316.08
123.11
317.77
123.08

324.26
144.42
326.08
144.57
327.81
144.65
329.49
144.70

336.32
166.35
338.17
166.72
339.94
167.04
341.66
167.31

304.42
77.56
306.39
77.03
308.30
76.47
310.14
75.88

312.76
95.97
314.79
94.01
316.71
93.60
318.57
93.16

322.18
114.33
324.01
113.93
325.79
113.50
327.53
113.05

299.10
37.59
301.02
36.34
302.88
35.07
304.68
33.78

307.08
53.94
309.01
52.85
310.88
51.73
312.69
50.58

315.29
70.58
317.23
69.64
319.11
68.67
320.93
67.67

5000

total
latent

333.07
179.26

345.48
202.32

358.20
225.85

319.41
123.01

331.13
144.72

343.32
167.54

311.93
75.26

320.37
92.69

329.22
112.57

306.42
32.46

314.45
49.41

322.70
66.64

5100

total
latent

334.77
180.01

347.18
203.27

359.95
227.04

321.00
122.92

332.70
144.69

344.92
167.73

313.67
74.62

322.12
92.20

330.87
112.08

308.11
31.15

316.15
48.22

324.41
65.59

cfm
2900
3000
3100

3500
3600
3700

4100
4200
4300

4700
4800
4900

MUA-PRC004-EN

53

unit
capacity

Performance
Data
Table PD-38. Size 051 cooling capacity with reheat installed, MBh
cfm

105/80

115/76

115/78

115/80

total
latent

281.82
149.66

291.93
166.68

302.45
184.21

274.57
115.78

284.42
132.42

294.57
149.51

267.62
83.56

276.50
98.93

285.98
114.97

264.92
55.86

271.94
68.99

279.17
82.74

3000

total
latent
total
latent
total
latent
total
latent

285.78
152.10
289.58
154.41
293.26
156.62
296.78
158.72

296.07
169.50
300.03
172.18
303.81
174.73
307.43
177.16

306.71
187.38
310.78
190.41
314.62
193.28
318.31
196.03

278.37
117.06
281.99
118.21
285.45
119.25
288.77
120.20

288.33
134.05
292.06
135.54
295.63
136.90
299.04
138.15

298.58
151.47
302.37
153.28
306.02
154.96
309.49
156.51

271.41
83.91
275.08
84.17
278.63
84.35
282.07
84.46

280.29
99.52
283.92
99.99
287.40
100.37
290.71
100.63

289.76
115.81
293.40
116.54
296.89
117.15
300.22
117.65

268.90
55.67
272.72
55.40
276.39
55.04
279.92
54.61

275.97
69.05
279.85
69.01
283.53
68.86
287.09
68.63

283.28
82.72
287.18
82.90
290.93
82.98
294.52
82.97

3400

total
latent

300.15
160.70

310.90
179.47

321.84
198.64

291.95
121.10

302.25
139.27

312.81
157.95

285.44
84.52

293.93
100.81

303.41
118.05

283.31
54.10

290.50
68.32

297.97
82.86

3500

total
latent

303.38
162.58

314.18
181.64

325.22
201.14

295.00
121.91

305.36
140.29

315.99
159.27

288.75
84.53

297.02
100.91

306.48
118.35

286.58
53.51

293.79
67.94

301.28
82.68

3600

total
latent
total
latent
total
latent
total
latent
total
latent

306.48
164.36
309.46
166.05
312.32
167.64
315.02
169.13
317.64
170.55

317.34
183.72
320.37
185.70
323.29
187.58
326.08
189.37
328.75
191.06

328.46
203.52
331.56
205.79
334.53
207.96
337.38
210.03
340.12
212.01

297.94
122.62
300.71
123.24
303.41
123.79
306.00
124.26
308.50
124.67

308.33
141.22
311.17
142.05
313.90
142.79
316.52
143.44
319.01
144.00

319.02
160.48
321.93
161.60
324.72
162.62
327.40
163.54
329.96
164.39

291.93
84.23
294.96
84.29
297.88
84.28
300.69
84.22
303.40
84.09

300.01
100.93
302.91
100.89
305.72
100.80
308.45
100.64
311.12
100.45

309.43
118.56
312.27
118.69
315.00
118.75
317.63
118.73
320.18
118.65

289.68
52.85
292.69
52.13
295.60
51.36
298.40
50.54
301.10
49.66

296.95
67.49
299.99
66.96
302.92
66.38
305.74
65.73
308.46
65.03

304.47
82.42
307.53
82.09
310.48
81.68
313.32
81.22
316.06
80.69

4100

total
latent

320.17
171.89

331.32
192.67

342.75
213.90

310.90
125.00

321.44
144.56

332.42
165.15

306.01
83.91

313.74
100.22

322.64
118.51

303.71
48.73

311.08
64.28

318.69
80.11

4200

total
latent

322.60
173.16

333.80
194.21

345.28
215.71

313.22
125.28

323.77
145.05

334.79
165.84

308.54
83.67

316.31
99.96

325.03
118.31

306.22
47.76

313.62
63.48

321.24
79.48

4300

total
latent
total
latent
total
latent
total
latent

324.94
174.36
327.19
175.49
329.37
176.56
331.46
177.57

336.19
195.68
338.49
197.07
340.70
198.39
342.84
199.65

347.72
217.43
350.06
219.08
352.31
220.66
354.49
222.17

315.46
125.50
317.62
125.66
319.71
125.78
321.73
125.84

326.01
145.48
328.17
145.84
330.26
146.15
332.28
146.41

337.07
166.45
339.25
167.00
341.36
167.48
343.39
167.90

310.97
83.39
313.33
83.06
315.60
82.69
317.81
82.28

318.83
99.71
321.20
99.55
323.49
99.34
325.70
99.09

327.34
118.07
329.58
117.77
331.76
117.44
333.89
117.07

308.65
46.75
311.00
45.70
313.28
44.62
315.47
43.50

316.06
62.64
318.42
61.75
320.71
60.83
322.91
59.86

323.70
78.80
326.07
78.07
328.36
77.30
330.58
76.49

4700

total
latent

333.49
178.52

344.90
200.85

356.58
223.61

323.69
125.86

334.22
146.61

345.34
168.26

319.94
81.83

327.85
98.79

335.96
116.66

317.60
42.35

325.05
58.86

332.72
75.64

4800

total
latent

335.44
179.42

346.89
201.99

358.61
225.00

325.58
125.83

336.10
146.77

347.23
168.57

322.00
81.34

329.92
98.46

337.99
116.23

319.66
41.17

327.12
57.83

334.80
74.76

4900

total
latent
total
latent
total
latent

337.33
180.26
339.15
181.06
340.91
181.80

348.81
203.07
350.66
204.10
352.46
205.08

360.56
226.32
362.44
227.58
364.27
228.80

327.41
125.77
329.19
125.67
330.92
125.53

337.92
146.88
339.68
146.95
341.38
146.97

349.05
168.83
350.81
169.03
352.51
169.22

323.99
80.82
325.93
80.27
327.80
79.68

331.92
98.09
333.86
97.69
335.75
97.25

339.99
115.78
341.95
115.31
343.89
114.83

321.65
39.96
323.58
38.73
325.46
37.48

329.12
56.78
331.06
55.69
332.94
54.58

336.80
73.84
338.75
72.90
340.63
71.93

3200
3300

3700
3800
3900
4000

4400
4500
4600

5000
5100

54

85/78

85/80

95/76

dry-bulb / wet-bulb temperature F


95/78
95/80
105/76
105/78

2900

3100

85/76

MUA-PRC004-EN

Performance
Data

unit
capacity

Table PD-39. Size 051 reheat data, MBh


cfm
2900
3000
3100
3200
3300
3400

dry-bulb / wet-bulb temperature (F)


55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78
82.8 85.5 88.4 94.1 97.2 100.3 109.7 113.0 116.4 126.4 129.9 133.4 126.0 129.5
83.3 86.1 89.0 94.7 97.8 100.9 110.3 113.7 117.0 127.1 130.6 134.1 126.7 130.2
83.8 86.6 89.5 95.3 98.4 101.5 110.9 114.3 117.7 127.7 131.2 134.7 127.3 130.8
84.3 87.1 90.0 95.8 98.9 102.1 111.5 114.9 118.3 128.3 131.8 135.3 127.9 131.4
84.8 87.6 90.5 96.3 99.4 102.6 112.1 115.4 118.8 128.9 132.4 135.9 128.5 132.0
85.2 88.1 91.0 96.8 99.9 103.1 112.6 115.9 119.4 129.4 132.9 136.5 129.0 132.5

95/80
133.0
133.7
134.3
134.9
135.5
136.0

3500
3600
3700
3800
3900
4000

85.6
86.0
86.4
86.8
87.1
87.5

88.5
88.9
89.3
89.7
90.0
90.4

91.5
91.9
92.3
92.7
93.0
93.4

97.3
97.7
98.1
98.5
98.9
99.3

100.4
100.8
101.3
101.7
102.0
102.4

103.6
104.0
104.4
104.9
105.2
105.6

113.1
113.6
114.0
114.4
114.8
115.2

116.4
116.9
117.4
117.8
118.2
118.6

119.9
120.3
120.8
121.2
121.6
122.0

129.9
130.4
130.9
131.3
131.7
132.1

133.5
133.9
134.4
134.9
135.3
135.6

137.0
137.5
137.9
138.4
138.8
139.2

129.5
130.0
130.5
131.0
131.5
131.9

133.0
133.5
134.0
134.4
134.8
135.2

136.5
137.0
137.5
137.9
138.3
138.7

133.6
134.8
135.9
136.9
137.8
138.8

134.6
135.4
136.2
137.0
137.8
138.6

137.0
137.6
138.2
138.8
139.4
140.0

145.3
146.5
147.7
148.8
149.9
151.0

145.3
146.5
147.6
148.8
149.8
150.9

145.2
146.4
147.6
148.7
149.8
150.8

4100
4200
4300
4400
4500
4600

87.8
88.1
88.4
88.6
88.9
89.2

90.7
91.0
91.3
91.6
91.9
92.1

93.7
94.0
94.3
94.6
94.9
95.2

99.6
99.9
100.2
100.5
100.8
101.1

102.8
103.1
103.4
103.7
104.0
104.3

106.0
106.3
106.6
106.9
107.2
107.5

115.6
115.9
116.2
116.6
116.9
117.2

119.0
119.3
119.6
120.0
120.3
120.6

122.4
122.7
123.1
123.4
123.7
124.0

132.5
132.9
133.2
133.5
133.9
134.2

136.0
136.4
136.7
137.1
137.4
137.7

139.6
140.0
140.3
140.6
141.0
141.3

132.4
132.8
133.2
133.6
134.0
134.4

135.6
136.0
136.3
136.7
137.0
137.3

139.1
139.5
139.8
140.2
140.5
140.8

139.7
140.6
141.4
142.2
143.0
143.8

139.5
140.4
141.3
142.1
142.9
143.7

140.6
141.2
141.8
142.4
143.0
143.7

152.0
153.0
153.9
154.9
155.7
156.6

151.9
152.9
153.8
154.7
155.6
156.5

151.8
152.8
153.7
154.6
155.5
156.4

4700
4800
4900
5000
5100

89.4
89.6
89.9
90.1
90.3

92.4
92.6
92.8
93.1
93.3

95.4
95.7
95.9
96.1
96.3

101.4
101.6
101.9
102.1
102.3

104.6
104.8
105.1
105.3
105.5

107.8
108.1
108.3
108.5
108.8

117.4
117.7
118.0
118.2
118.4

120.9
121.1
121.4
121.6
121.9

124.3
124.6
124.8
125.1
125.3

134.5
134.7
135.0
135.3
135.5

138.0
138.3
138.6
138.8
139.1

141.6
141.9
142.1
142.4
142.7

134.8
135.1
135.5
135.9
136.2

137.7
138.0
138.3
138.6
138.9

141.1
141.4
141.6
141.9
142.1

144.5
145.3
146.0
146.6
147.3

144.4
145.1
145.8
146.5
147.1

144.3
144.9
145.6
146.2
147.0

157.4
158.3
159.0
159.8
160.5

157.3
158.1
158.9
159.6
160.4

157.2
158.0
158.8
159.5
160.2

105/76 105/78
127.3 129.8
128.3 130.6
129.3 131.4
130.3 132.3
131.4 133.0
132.5 133.8

105/80 115/76115/78115/80
132.8 137.0 137.0 137.0
133.5 138.5 138.5 138.6
134.3 140.0 140.0 140.0
135.0 141.4 141.4 141.4
135.6 142.7 142.7 142.7
136.3 144.1 144.0 144.0

Table PD-40. Size 051 condenser reheat max temperature rise, F


cfm
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600

55/48
26.3
25.6
24.9
24.3
23.7
23.1
22.5
22.0
21.5
21.0
20.6
20.1
19.7
19.3
18.9
18.5
18.2
17.8

55/50
27.2
26.5
25.7
25.1
24.5
23.9
23.3
22.7
22.2
21.7
21.2
20.8
20.4
19.9
19.5
19.1
18.8
18.4

dry-bulb / wet-bulb temperature F


55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
28.1 29.9 30.8 31.8 34.7 35.7 36.8 39.8 40.8 41.9 39.7 40.7 41.8 40.1
40.8
41.7
43.1
43.1
43.0
27.3 29.1 30.0 30.9 33.7 34.7 35.7 38.7 39.7 40.7 38.5 39.6 40.6 39.0
39.7
40.5
42.2
42.1
42.0
26.6 28.3 29.2 30.1 32.8 33.8 34.7 37.6 38.6 39.5 37.5 38.4 39.4 38.1
38.6
39.4
41.2
41.2
41.1
25.9 27.5 28.4 29.3 32.0 32.9 33.8 36.6 37.5 38.5 36.5 37.4 38.3 37.2
37.6
38.4
40.3
40.3
40.2
25.3 26.9 27.7 28.6 31.1 32.0 32.9 35.6 36.5 37.4 35.5 36.4 37.3 36.3
36.7
37.4
39.5
39.4
39.3
24.6 26.2 27.0 27.8 30.3 31.2 32.1 34.7 35.6 36.5 34.6 35.5 36.4 35.5
35.8
36.4
38.7
38.6
38.5
24.0 25.6 26.4 27.2 29.6 30.5 31.3 33.8 34.7 35.6 33.7 34.6 35.4 34.8
35.0
35.5
37.9
37.8
37.7
23.5 25.0 25.7 26.5 28.9 29.7 30.6 33.0 33.8 34.7 32.9 33.7 34.6 34.1
34.2
34.7
37.1
37.0
37.0
22.9 24.4 25.1 25.9 28.2 29.0 29.8 32.2 33.0 33.8 32.1 32.9 33.7 33.4
33.5
33.9
36.4
36.3
36.2
22.4 23.8 24.6 25.3 27.6 28.4 29.2 31.5 32.3 33.1 31.4 32.2 32.9 32.8
32.8
33.2
35.7
35.6
35.5
21.9 23.3 24.0 24.8 27.0 27.7 28.5 30.7 31.5 32.3 30.7 31.4 32.2 32.2
32.1
32.4
35.0
34.9
34.9
21.5 22.8 23.5 24.2 26.4 27.1 27.9 30.1 30.8 31.6 30.0 30.7 31.5 31.6
31.5
31.8
34.4
34.3
34.2
21.0 22.3 23.0 23.7 25.8 26.5 27.3 29.4 30.1 30.9 29.4 30.0 30.8 31.0
30.9
31.1
33.8
33.7
33.6
20.6 21.9 22.5 23.2 25.3 26.0 26.7 28.8 29.5 30.2 28.8 29.4 30.1 30.5
30.4
30.5
33.2
33.1
33.0
20.2 21.4 22.1 22.7 24.7 25.4 26.1 28.2 28.9 29.6 28.2 28.8 29.5 29.9
29.8
29.9
32.6
32.5
32.4
19.8 21.0 21.6 22.3 24.2 24.9 25.6 27.6 28.3 29.0 27.6 28.2 28.9 29.4
29.3
29.3
32.0
32.0
31.9
19.4 20.6 21.2 21.8 23.8 24.4 25.1 27.0 27.7 28.4 27.1 27.6 28.3 28.9
28.8
28.8
31.5
31.4
31.3
19.0 20.2 20.8 21.4 23.3 23.9 24.6 26.5 27.2 27.8 26.5 27.1 27.7 28.4
28.3
28.3
31.0
30.9
30.8

4700
4800
4900
5000
5100

17.5
17.2
16.9
16.6
16.3

18.1
17.7
17.4
17.1
16.8

18.7
18.3
18.0
17.7
17.4

19.8
19.4
19.1
18.7
18.4

20.4
20.0
19.7
19.3
19.0

21.0
20.6
20.3
19.9
19.5

22.8
22.4
22.0
21.6
21.2

23.5
23.0
22.6
22.2
21.8

24.1
23.7
23.2
22.8
22.4

26.0
25.5
25.0
24.6
24.1

26.6
26.1
25.6
25.2
24.7

27.3
26.7
26.2
25.8
25.3

26.0
25.6
25.1
24.7
24.2

26.6
26.1
25.6
25.1
24.7

27.2
26.6
26.1
25.7
25.2

28.0
27.5
27.1
26.6
26.2

27.9
27.4
27.0
26.6
26.2

27.8
27.3
26.9
26.5
26.1

30.5
30.0
29.5
29.1
28.6

30.4
29.9
29.4
29.0
28.5

30.3
29.8
29.3
28.9
28.4

Table PD-41. Size 051 design supply air dew point, cfm
drybulb
(F)
85

wetbulb
(F)
76
78
80
76
78
80

46

48
3083

3054

50
3399
3023

3372
2989

design supply air dew point F


52
54
56
3764
4190
4700
3332
3685
4098
2962
3262
3606
3748
4195
4741
3296
3649
4067
2923
3220
3563

58

4590
4006

4579
3966

60

4482

4448

62

5058

5041

105

76
78
80

3091

3447
2975

3894
3298

4468
3681
3185

4153
3541

4791
3969

4497

115

76
78
80

3000

3380

3833
3117

4393
3525
2905

4020
3267

4639
3713

4262

4964

95

MUA-PRC004-EN

55

unit
capacity

Performance
Data
Table PD-42. Size 066 cooling capacity without reheat installed, MBh
cfm

105/80

115/76

115/78

115/80

total
latent

337.10
179.72

350.17
200.65

363.81
222.26

324.98
137.28

337.61
157.65

350.70
178.63

313.71
98.17

324.30
115.68

336.34
134.66

307.48
63.01

316.54
79.12

325.94
95.64

3700

total
latent
total
latent
total
latent
total
latent

340.68
181.95
344.13
184.08
347.50
186.13
350.75
188.09

353.90
203.23
357.49
205.71
360.94
208.08
364.27
210.35

367.64
225.18
371.32
227.99
374.86
230.68
378.27
233.26

328.32
138.34
331.53
139.30
334.63
140.17
337.61
140.96

341.04
159.02
344.35
160.30
347.52
161.48
350.58
162.57

354.22
180.33
357.61
181.92
360.87
183.40
364.00
184.79

317.21
96.85
320.58
97.19
323.84
97.45
326.98
97.64

327.59
116.13
330.78
116.50
333.88
116.81
336.90
117.07

339.60
135.30
342.75
135.86
345.79
136.32
348.72
136.71

310.85
62.53
314.10
61.99
317.24
61.37
320.27
60.70

319.96
78.88
323.26
78.56
326.45
78.17
329.52
77.70

329.41
95.62
332.75
95.53
335.98
95.35
339.09
95.10

4100

total
latent

353.88
189.96

367.48
212.53

381.56
235.75

340.49
141.67

353.53
163.57

367.02
186.08

330.02
97.77

339.85
117.28

351.55
137.03

323.19
59.96

332.48
77.18

342.09
94.78

4200

total
latent

356.90
191.75

370.58
214.62

384.73
238.13

343.26
142.31

356.37
164.49

369.92
187.29

332.96
97.83

342.75
117.46

354.30
137.28

326.02
59.17

335.35
76.59

344.98
94.39

4300

total
latent
total
latent
total
latent
total
latent

359.81
193.46
362.63
195.09
365.35
196.64
367.98
198.13

373.57
216.62
376.45
218.54
379.23
220.38
381.92
222.14

387.78
240.43
390.73
242.63
393.57
244.75
396.32
246.79

345.93
142.87
348.51
143.36
351.01
143.78
353.41
144.15

359.11
165.34
361.75
166.10
364.30
166.80
366.76
167.43

372.72
188.41
375.42
189.45
378.02
190.41
380.53
191.30

335.80
97.83
338.54
97.78
341.20
97.66
343.78
97.50

345.61
117.61
348.46
117.78
351.12
116.22
353.73
116.26

356.96
137.47
359.54
137.60
362.05
137.67
364.49
137.70

328.76
58.33
331.40
57.44
333.96
56.50
336.44
55.52

338.11
75.95
340.79
75.25
343.38
74.50
345.89
73.71

347.78
93.95
350.48
93.44
353.10
92.88
355.63
92.27

total
latent
total
latent

370.52
199.55
372.98
200.90

384.52
223.83
387.04
225.45

398.97
248.75
401.54
250.63

355.76
144.55
358.03
144.94

369.13
167.99
371.44
168.49

382.95
192.12
385.30
192.88

346.27
97.29
348.70
97.04

356.25
116.23
358.69
116.16

366.86
137.69
369.19
137.64

338.84
54.49
341.17
53.43

348.31
72.87
350.66
71.98

358.08
91.61
360.45
90.90

total
latent
total
latent
total
latent
total
latent

375.37
202.19
377.67
203.42
379.91
204.60
382.07
205.72

389.47
227.01
391.83
228.50
394.11
229.93
396.32
231.30

404.02
252.45
406.41
254.19
408.74
255.88
410.98
257.49

360.24
145.27
362.38
145.56
364.46
145.80
366.48
146.00

373.65
168.93
375.80
169.32
377.88
169.65
379.89
169.94

387.56
193.57
389.75
194.20
391.86
194.78
393.91
195.30

351.03
96.73
353.30
96.39
355.51
96.01
357.65
95.59

361.06
116.04
363.35
115.88
365.58
115.67
367.74
115.42

371.46
137.55
373.69
137.44
375.89
137.32
378.06
137.19

343.43
52.33
345.62
51.19
347.74
50.02
349.80
48.83

352.94
71.06
355.15
70.09
357.29
69.10
359.37
68.07

362.74
90.15
364.97
89.35
367.12
88.52
369.22
87.65

5300

total
latent

384.17
206.79

398.46
232.62

413.16
259.05

368.45
146.16

381.84
170.17

395.90
195.77

359.73
95.13

369.84
115.14

380.23
137.06

351.81
47.60

361.39
67.00

371.25
86.75

5400

total
latent

386.21
207.81

400.53
233.88

415.27
260.56

370.36
146.29

383.73
170.36

397.82
196.19

361.75
94.64

371.87
114.81

382.29
135.36

353.75
46.34

363.35
65.91

373.22
85.82

5500

total
latent
total
latent
total
latent
total
latent

388.19
208.78
390.11
209.70
391.97
210.58
393.78
211.42

402.55
235.09
404.50
236.25
406.39
237.36
408.24
238.43

417.32
262.00
419.31
263.40
421.23
264.74
423.10
266.04

372.21
146.38
374.02
146.43
375.79
146.45
377.50
146.45

385.56
170.50
387.34
170.61
389.06
170.67
390.74
170.70

399.68
196.57
401.49
196.90
403.24
197.18
404.94
197.43

363.71
94.12
365.61
93.57
367.47
92.98
369.27
92.38

373.85
114.46
375.77
114.07
377.64
113.64
379.46
113.19

384.28
135.16
386.21
134.93
388.09
134.67
389.92
134.37

355.64
45.07
357.48
43.79
359.33
43.26
361.15
42.72

365.25
64.79
367.10
63.64
368.90
62.47
370.65
61.28

375.13
84.85
376.99
83.86
378.80
82.84
380.56
81.80

5900

total
latent

395.54
212.22

410.02
239.46

424.92
267.29

379.18
146.42

392.38
170.77

406.59
197.64

371.03
91.74

381.22
112.71

391.69
134.04

362.93
42.15

372.35
60.06

382.27
80.73

6000

total
latent

397.24
212.98

411.76
240.44

426.68
268.50

380.82
146.36

393.98
170.84

408.20
197.81

372.73
91.09

382.94
112.21

393.42
133.68

364.68
41.56

374.01
58.83

383.93
79.64

6100

total
latent
total
latent
total
latent
total
latent

398.91
213.70
400.52
214.38
402.10
215.03
403.63
215.65

413.45
241.38
415.09
242.29
416.69
243.16
418.25
243.99

428.39
269.66
430.06
270.78
431.68
271.86
433.26
272.91

382.41
146.28
383.98
146.18
385.50
146.05
387.00
145.91

395.54
170.87
397.05
170.88
398.53
170.87
399.97
170.83

409.75
197.94
411.27
198.05
412.74
198.11
414.17
198.15

374.40
90.41
376.02
89.70
377.60
88.98
379.14
88.24

384.62
111.68
386.25
111.12
387.83
110.54
389.38
109.94

395.11
133.30
396.74
132.89
398.34
132.45
399.89
131.99

366.40
40.96
368.09
40.35
369.75
39.73
371.39
39.09

375.62
57.58
377.19
56.30
378.72
55.02
380.21
53.71

385.55
78.53
387.13
77.40
388.66
76.25
390.16
75.08

6500

total
latent

405.12
216.24

419.76
244.79

434.79
273.92

388.46
145.75

401.37
170.76

415.56
198.16

380.64
87.48

390.89
109.32

401.40
131.51

373.00
38.45

381.72
52.97

391.61
73.90

6600

total
latent

406.57
216.79

421.23
245.55

436.28
274.89

389.90
145.58

402.74
170.68

416.91
198.14

382.10
86.70

392.36
108.69

402.88
131.01

374.58
37.80

383.21
52.30

393.03
72.71

3900
4000

4400
4500
4600
4700
4800
4900
5000
5100
5200

5600
5700
5800

6200
6300
6400

56

85/78

85/80

95/76

dry-bulb / wet-bulb temperature (F)


95/78
95/80
105/76
105/78

3600

3800

85/76

MUA-PRC004-EN

Performance
Data

unit
capacity

Table PD-43. Size 066 cooling cpacity with reheat installed, MBh
total
latent

85/76
343.28
181.96

85/78
355.54
202.82

85/80
368.32
224.32

95/76
333.64
139.62

dry-bulb / wet-bulb temperature (F)


95/78
95/80
105/76
105/78
345.54
357.84
325.90
335.63
159.91
180.84
100.12
118.67

105/80
346.72
138.02

115/76
322.18
67.63

115/78
330.78
83.80

115/80
339.71
100.36

3700

total
latent

346.99
184.24

359.41
205.47

372.29
227.32

337.16
140.79

349.16
161.35

361.56
182.60

329.64
100.67

339.22
119.14

350.28
138.71

325.87
67.32

334.52
83.72

343.49
100.51

3800

total
latent

350.57
186.42

363.13
208.01

376.11
230.19

340.57
141.88

352.65
162.68

365.13
184.25

333.26
101.13

342.71
119.54

353.72
139.30

329.43
66.94

338.12
83.57

347.13
100.58

3900

total
latent
total
latent
total
latent
total
latent

354.02
188.51
357.39
190.52
360.64
192.43
363.77
194.26

366.71
210.45
370.17
212.78
373.49
215.01
376.70
217.15

379.78
232.95
383.32
235.61
386.73
238.15
390.00
240.60

343.86
142.88
347.04
143.80
350.10
144.63
353.06
145.38

356.00
163.91
359.22
165.04
362.33
166.08
365.32
167.04

368.56
185.80
371.86
187.24
375.04
188.58
378.10
189.83

336.75
101.52
340.12
101.84
343.38
102.08
346.53
102.26

346.10
119.86
349.42
120.12
352.66
120.34
355.87
120.52

357.04
139.80
360.24
140.22
363.35
140.56
366.36
140.83

332.87
66.49
336.19
65.97
339.41
65.39
342.51
64.74

341.60
83.34
344.96
83.03
348.21
82.66
351.35
82.22

350.65
100.56
354.04
100.47
357.32
100.30
360.48
100.06

4300

total
latent

366.79
196.01

379.80
219.20

393.17
242.95

355.92
146.07

368.20
167.93

381.04
190.99

349.59
102.38

358.99
120.57

369.28
141.03

345.52
64.04

354.38
81.72

363.54
99.76

4400

total
latent

369.71
197.67

382.78
221.16

396.22
245.20

358.69
146.68

371.00
168.78

383.89
192.07

352.54
102.43

361.97
120.83

372.11
141.16

348.43
63.29

357.32
81.16

366.50
99.39

4500

total
latent
total
latent
total
latent
total
latent

372.53
199.26
375.25
200.77
377.89
202.21
380.43
203.59

385.67
223.04
388.45
224.84
391.14
226.57
393.75
228.22

399.16
247.38
402.01
249.46
404.75
251.47
407.41
253.40

361.37
147.23
363.96
147.71
366.47
148.13
368.91
148.50

373.69
169.57
376.30
170.28
378.82
170.92
381.26
171.51

386.63
193.06
389.28
193.98
391.83
194.82
394.29
195.59

355.39
102.43
358.16
102.37
360.85
102.26
363.44
102.10

364.86
121.02
367.65
121.16
370.35
121.24
372.98
121.26

374.87
141.24
377.56
141.27
380.19
141.26
382.76
141.20

351.25
62.49
353.98
61.64
356.63
60.74
359.20
59.80

360.16
80.55
362.91
79.88
365.58
79.17
368.16
78.41

369.36
98.96
372.13
98.48
374.82
97.94
377.42
97.36

4900

total
latent

382.90
204.90

396.26
229.80

409.97
255.25

371.27
148.81

383.63
172.03

396.67
196.30

365.97
101.89

375.52
121.24

385.30
141.12

361.69
58.82

370.67
77.60

379.93
96.72

5000

total
latent

385.29
206.15

398.70
231.32

412.45
257.04

373.56
149.07

385.92
172.50

398.98
196.94

368.41
101.64

377.98
121.16

387.81
141.02

364.10
57.80

373.10
76.76

382.38
96.04

5100

total
latent
total
latent
total
latent
total
latent

387.60
207.34
389.83
208.47
392.01
209.54
394.11
210.57

401.06
232.77
403.34
234.17
405.55
235.50
407.70
236.78

414.86
258.75
417.18
260.41
419.43
262.00
421.61
263.53

375.79
149.29
377.96
149.46
380.07
149.59
382.12
149.68

388.13
172.91
390.28
173.27
392.37
173.59
394.39
173.85

401.20
197.52
403.36
198.04
405.44
198.51
407.47
198.96

370.79
101.35
373.09
101.02
375.33
100.64
377.50
100.23

380.37
121.04
382.69
120.88
384.94
120.67
387.13
120.43

390.25
141.10
392.58
141.10
394.84
141.06
397.04
140.98

366.44
56.75
368.72
55.66
370.93
54.54
373.08
53.39

375.46
75.87
377.74
74.95
379.97
73.99
382.12
72.99

384.74
95.32
387.04
94.56
389.27
93.76
391.44
92.93

5500

total
latent

396.15
211.54

409.78
238.01

423.73
265.00

384.12
149.73

396.36
174.08

409.43
199.38

379.61
99.78

389.25
120.14

399.17
140.85

375.16
52.20

384.22
71.97

393.54
92.06

5600

total
latent

398.13
212.46

411.79
239.18

425.78
266.42

386.06
149.74

398.27
174.26

411.34
199.75

381.66
99.31

391.32
119.83

401.24
140.69

377.19
51.00

386.26
70.92

395.58
91.16

5700

total
latent
total
latent
total
latent
total
latent

400.05
213.34
401.92
214.18
403.73
214.97
405.50
215.72

413.75
240.30
415.65
241.38
417.49
242.41
419.29
243.40

427.77
267.79
429.70
269.11
431.57
270.38
433.39
271.60

387.96
149.73
389.82
149.68
391.63
149.60
393.40
149.49

400.14
174.40
401.94
174.50
403.70
174.57
405.41
174.60

413.19
200.08
414.99
200.37
416.74
200.62
418.43
200.82

383.66
98.80
385.60
98.26
387.49
97.69
389.33
97.10

393.32
119.47
395.27
119.09
397.17
118.68
399.02
118.23

403.25
140.49
405.21
140.26
407.12
140.00
408.97
139.70

379.17
49.76
381.09
48.51
382.96
47.23
384.77
45.93

388.24
69.84
390.17
68.73
392.04
67.60
393.87
66.45

397.57
90.23
399.50
89.27
401.38
88.28
403.21
87.27

6100

total
latent

407.21
216.43

421.03
244.35

435.16
272.78

395.14
149.36

407.08
174.60

420.09
201.00

391.12
96.48

400.82
117.76

410.77
139.38

386.56
44.95

395.64
65.27

404.99
86.24

6200

total
latent

408.88
217.10

422.72
245.25

436.88
273.91

396.84
149.21

408.70
174.57

421.70
201.14

392.87
95.84

402.57
117.26

412.53
139.02

388.31
44.38

397.37
64.08

406.72
85.18

6300

total
latent
total
latent
total
latent
total
latent

410.50
217.74
412.07
218.34
413.61
218.91
415.10
219.44

424.37
246.12
425.97
246.95
427.53
247.74
429.05
248.50

438.55
275.01
440.17
276.06
441.76
277.08
443.30
278.06

398.51
149.04
400.14
148.85
401.75
148.64
403.34
148.42

410.29
174.51
411.83
174.43
413.34
174.31
414.82
174.18

423.26
201.24
424.78
201.32
426.26
201.36
427.70
201.38

394.57
95.17
396.22
94.48
397.84
93.78
399.41
93.05

404.27
116.74
405.93
116.20
407.55
115.63
409.13
115.04

414.23
138.64
415.90
138.23
417.52
137.80
419.10
137.35

390.04
43.79
391.74
43.19
393.41
42.58
395.05
41.95

399.06
62.86
400.70
61.63
402.30
60.38
403.86
59.11

408.41
84.10
410.05
83.00
411.65
81.89
413.21
80.76

cfm
3600

4000
4100
4200

4600
4700
4800

5200
5300
5400

5800
5900
6000

6400
6500
6600

MUA-PRC004-EN

57

unit
capacity

Performance
Data
Table PD-44. Size 066 reheat data, MBh

dry-bulb / wet-bulb temperature F


cfm 55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
3600
3700
3800
3900
4000

88.1
88.5
88.9
89.3
89.6

91.0
91.5
91.9
92.2
92.6

94.1
94.5
94.9
95.3
95.7

100.1
100.5
100.9
101.3
101.7

103.3
103.7
104.2
104.6
105.0

106.5
107.0
107.4
107.9
108.3

116.3
116.8
117.2
117.7
118.1

119.7
120.2
120.7
121.1
121.6

123.2
123.7
124.2
124.7
125.1

133.5
134.0
134.5
135.0
135.4

137.1
137.7
138.1
138.6
139.1

140.8
141.3
141.8
142.3
142.7

133.1
133.6
134.1
134.6
135.1

136.7
137.2
137.6
138.1
138.5

140.3
140.8
141.3
141.8
142.2

137.1
138.2
139.3
140.4
141.5

138.0
138.8
139.6
140.5
141.4

140.5
141.2
141.8
142.5
143.1

149.0
150.3
151.6
152.8
154.0

149.0
150.3
151.5
152.7
153.9

148.9
150.2
151.4
152.6
153.8

4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600

89.9
90.3
90.6
90.9
91.2
91.4
91.7
92.0
92.2
92.4
92.6
92.9
93.1
93.3
93.5
93.7
93.9
94.1
94.2
94.4
94.6
94.8
94.9
95.1
95.2
95.4

93.0
93.3
93.6
93.9
94.2
94.5
94.8
95.0
95.3
95.5
95.7
96.0
96.2
96.4
96.6
96.8
96.9
97.1
97.3
97.5
97.6
97.8
97.9
98.1
98.2
98.3

96.0
96.4
96.7
97.0
97.3
97.6
97.9
98.2
98.4
98.6
98.9
99.1
99.3
99.5
99.7
99.9
100.1
100.3
100.5
100.6
100.8
101.0
101.1
101.3
101.4
101.5

102.1
102.5
102.8
103.1
103.4
103.7
104.0
104.3
104.5
104.8
105.0
105.3
105.5
105.7
105.9
106.2
106.4
106.6
106.8
107.0
107.1
107.3
107.5
107.7
107.9
108.0

105.3
105.7
106.1
106.4
106.7
107.0
107.3
107.6
107.8
108.1
108.3
108.6
108.8
109.0
109.2
109.4
109.6
109.8
110.0
110.2
110.3
110.5
110.7
110.8
111.0
111.1

108.6
109.0
109.4
109.7
110.0
110.3
110.6
110.9
111.2
111.4
111.7
111.9
112.2
112.4
112.6
112.8
113.0
113.2
113.4
113.6
113.7
113.9
114.1
114.2
114.4
114.5

118.5
118.9
119.2
119.6
119.9
120.2
120.5
120.8
121.1
121.4
121.6
121.9
122.1
122.3
122.6
122.8
123.0
123.2
123.4
123.5
123.7
123.9
124.1
124.2
124.4
124.5

122.0
122.4
122.7
123.1
123.4
123.7
124.0
124.3
124.6
124.9
125.1
125.4
125.6
125.9
126.1
126.3
126.5
126.7
126.9
127.1
127.3
127.4
127.6
127.8
127.9
128.1

125.5
125.9
126.3
126.6
127.0
127.3
127.6
127.9
128.2
128.4
128.7
129.0
129.2
129.4
129.7
129.9
130.1
130.3
130.5
130.7
130.9
131.0
131.2
131.4
131.5
131.7

135.8
136.2
136.6
137.0
137.3
137.6
138.0
138.3
138.6
138.8
139.1
139.4
139.6
139.9
140.1
140.3
140.5
140.7
140.9
141.1
141.3
141.5
141.7
141.8
142.0
142.2

139.5
139.9
140.3
140.6
141.0
141.3
141.6
141.9
142.2
142.5
142.8
143.1
143.3
143.6
143.8
144.0
144.2
144.5
144.7
144.9
145.0
145.2
145.4
145.6
145.7
145.9

143.2
143.6
143.9
144.3
144.7
145.0
145.3
145.7
146.0
146.2
146.5
146.8
147.0
147.3
147.5
147.8
148.0
148.2
148.4
148.6
148.8
149.0
149.2
149.3
149.5
149.7

135.5
136.0
136.4
136.8
137.3
137.7
138.1
138.5
138.9
139.2
139.6
140.0
140.4
140.7
141.1
141.5
141.8
142.2
142.6
143.0
143.3
143.7
144.1
144.5
144.9
145.3

139.0
139.4
139.7
140.1
140.5
140.8
141.2
141.5
141.9
142.2
142.5
142.8
143.1
143.4
143.7
144.0
144.3
144.5
144.8
145.1
145.3
145.6
145.8
146.1
146.4
146.6

142.6
143.0
143.4
143.8
144.1
144.5
144.8
145.1
145.4
145.7
146.0
146.2
146.5
146.7
147.0
147.2
147.5
147.7
147.9
148.1
148.4
148.6
148.8
149.0
149.2
149.4

142.5
143.5
144.4
145.3
146.2
147.1
147.9
148.7
149.5
150.3
151.0
151.7
152.4
153.1
153.8
154.4
155.0
155.7
156.2
156.8
157.4
157.9
158.5
159.0
159.5
160.0

142.3
143.3
144.3
145.2
146.1
146.9
147.8
148.6
149.3
150.1
150.8
151.5
152.2
152.9
153.6
154.2
154.8
155.4
156.0
156.6
157.1
157.7
158.2
158.7
159.2
159.7

143.7
144.4
145.0
145.6
146.3
147.0
147.6
148.3
149.1
149.9
150.6
151.4
152.0
152.7
153.4
154.0
154.6
155.2
155.8
156.4
156.9
157.5
158.0
158.5
159.0
159.5

155.1
156.3
157.3
158.4
159.4
160.3
161.3
162.2
163.1
164.0
164.8
165.6
166.4
167.2
167.9
168.7
169.4
170.1
170.7
171.4
172.0
172.6
173.2
173.8
174.3
174.9

155.0
156.1
157.2
158.2
159.2
160.2
161.1
162.0
162.9
163.8
164.6
165.4
166.2
167.0
167.7
168.4
169.1
169.8
170.5
171.1
171.8
172.4
173.0
173.6
174.2
174.7

154.9
156.0
157.0
158.1
159.1
160.0
160.9
161.9
162.7
163.6
164.4
165.2
166.0
166.8
167.5
168.2
168.9
169.6
170.3
170.9
171.5
172.2
172.8
173.3
173.9
174.5

Table PD-45. Size 066 condenser reheat max temperature rise, F


cfm

dry-bulb / wet-bulb temperature F


55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500

22.5
22.0
21.6
21.1
20.6
20.2
19.8
19.4
19.0
18.7
18.3
18.0
17.6
17.3
17.0
16.7
16.4
16.2
15.9
15.6

23.3
22.8
22.3
21.8
21.3
20.9
20.5
20.0
19.6
19.3
18.9
18.6
18.2
17.9
17.6
17.3
17.0
16.7
16.4
16.1

24.1
23.6
23.0
22.5
22.0
21.6
21.1
20.7
20.3
19.9
19.5
19.2
18.8
18.5
18.1
17.8
17.5
17.2
16.9
16.7

25.6
25.0
24.4
23.9
23.4
22.9
22.4
22.0
21.5
21.1
20.7
20.3
20.0
19.6
19.3
18.9
18.6
18.3
18.0
17.7

26.4
25.8
25.2
24.6
24.1
23.6
23.1
22.7
22.2
21.8
21.4
21.0
20.6
20.2
19.8
19.5
19.2
18.8
18.5
18.2

27.2
26.6
26.0
25.4
24.9
24.3
23.8
23.4
22.9
22.4
22.0
21.6
21.2
20.8
20.4
20.1
19.7
19.4
19.1
18.8

29.6
28.9
28.3
27.7
27.1
26.5
25.9
25.4
24.9
24.4
23.9
23.5
23.0
22.6
22.2
21.8
21.4
21.1
20.7
20.4

30.5
29.8
29.1
28.5
27.8
27.2
26.7
26.1
25.6
25.1
24.6
24.1
23.7
23.3
22.8
22.4
22.0
21.7
21.3
20.9

31.3
30.6
29.9
29.3
28.6
28.0
27.4
26.8
26.3
25.8
25.3
24.8
24.3
23.9
23.5
23.0
22.6
22.2
21.9
21.5

33.9
33.1
32.3
31.6
30.9
30.2
29.6
28.9
28.3
27.8
27.2
26.7
26.2
25.7
25.3
24.8
24.4
23.9
23.5
23.1

34.7
33.9
33.1
32.4
31.7
31.0
30.3
29.7
29.1
28.5
27.9
27.4
26.9
26.4
25.9
25.4
25.0
24.5
24.1
23.7

35.6
34.8
34.0
33.2
32.4
31.7
31.1
30.4
29.8
29.2
28.6
28.1
27.5
27.0
26.5
26.0
25.6
25.1
24.7
24.3

33.7
32.9
32.2
31.5
30.8
30.1
29.5
28.9
28.3
27.8
27.2
26.7
26.2
25.8
25.3
24.9
24.5
24.1
23.7
23.3

34.6
33.8
33.0
32.2
31.5
30.8
30.2
29.6
29.0
28.4
27.8
27.3
26.8
26.3
25.8
25.4
24.9
24.5
24.1
23.7

35.5
34.6
33.8
33.1
32.3
31.6
30.9
30.3
29.7
29.1
28.5
27.9
27.4
26.9
26.4
25.9
25.5
25.0
24.6
24.2

34.7
34.1
33.5
32.8
32.3
31.7
31.1
30.6
30.1
29.6
29.1
28.7
28.2
27.8
27.4
26.9
26.5
26.2
25.8
25.4

34.9
34.2
33.5
32.8
32.2
31.6
31.0
30.5
30.0
29.5
29.0
28.6
28.1
27.7
27.3
26.9
26.5
26.1
25.7
25.3

35.5
34.7
33.9
33.2
32.5
31.9
31.2
30.6
30.0
29.5
29.0
28.5
28.0
27.6
27.2
26.8
26.4
26.0
25.6
25.3

37.8
37.1
36.4
35.8
35.1
34.5
33.9
33.4
32.8
32.3
31.8
31.3
30.8
30.3
29.9
29.4
29.0
28.6
28.2
27.8

37.7
37.0
36.3
35.7
35.0
34.4
33.8
33.3
32.7
32.2
31.7
31.2
30.7
30.2
29.8
29.3
28.9
28.5
28.1
27.7

37.6
36.9
36.2
35.6
35.0
34.3
33.8
33.2
32.6
32.1
31.6
31.1
30.6
30.1
29.7
29.2
28.8
28.4
28.0
27.6

5600
5700
5800
5900
6000

15.4
15.2
14.9
14.7
14.5

15.9
15.6
15.4
15.2
14.9

16.4
16.1
15.9
15.6
15.4

17.4
17.1
16.9
16.6
16.4

17.9
17.6
17.4
17.1
16.8

18.5
18.2
17.9
17.6
17.3

20.0
19.7
19.4
19.1
18.8

20.6
20.3
19.9
19.6
19.3

21.2
20.8
20.5
20.2
19.9

22.8
22.4
22.0
21.7
21.4

23.3
22.9
22.6
22.2
21.9

23.9
23.5
23.1
22.8
22.4

23.0
22.6
22.3
21.9
21.6

23.3
22.9
22.6
22.2
21.9

23.8
23.4
23.0
22.7
22.3

25.1
24.7
24.4
24.1
23.7

25.0
24.6
24.3
24.0
23.7

24.9
24.6
24.2
23.9
23.6

27.4
27.0
26.7
26.3
26.0

27.3
26.9
26.6
26.2
25.9

27.2
26.8
26.5
26.1
25.8

6100
6200
6300
6400
6500
6600

14.3
14.1
13.9
13.7
13.5
13.3

14.7
14.5
14.3
14.1
13.9
13.7

15.2
15.0
14.7
14.5
14.3
14.1

16.1
15.9
15.7
15.4
15.2
15.0

16.6
16.3
16.1
15.9
15.6
15.4

17.1
16.8
16.6
16.3
16.1
15.9

18.5
18.3
18.0
17.7
17.5
17.2

19.0
18.8
18.5
18.2
18.0
17.7

19.6
19.3
19.0
18.7
18.4
18.2

21.0
20.7
20.4
20.1
19.8
19.5

21.5
21.2
20.9
20.6
20.3
20.0

22.1
21.7
21.4
21.1
20.8
20.5

21.3
21.0
20.8
20.5
20.2
20.0

21.6
21.3
21.0
20.7
20.4
20.1

22.0
21.7
21.3
21.0
20.7
20.4

23.4
23.1
22.8
22.6
22.3
22.0

23.4
23.1
22.8
22.5
22.2
21.9

23.3
23.0
22.7
22.4
22.1
21.8

25.6
25.3
25.0
24.7
24.4
24.1

25.6
25.2
24.9
24.6
24.3
24.0

25.5
25.1
24.8
24.5
24.2
23.9

58

MUA-PRC004-EN

Performance
Data

unit
capacity

Table PD-46. Size 066 design supply air dew point, cfm
dry-bulb
F

wet-bulb
F
76
78
80

46

48
3680

design supply air dew point, F


50
52
54
4054
4485
4990
3610
3975
4395

3896

56
5593
4884
4304

58
6328
5467
4779

60

6175
5342

62

6025

95

76
78
80

3636

4018

4463
3918

4994
4337
3833

5643
4838
4238

6468
5444
4712

6198
5279

5986

105

76
78
80

3700

4169

4725
3933

5405
4410
3790

6267
5026
4213

5793
4725

5399

6285

115

76
78
80

3638

4083

4614
3777

5267
4257

6128
4837
3956

5562
4482

6508
5126

5948

85

MUA-PRC004-EN

59

unit w/TE wheel


capacity

Performance
Data
Table PD-47. Size 031 cooling capacity without reheat, MBh
cfm
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100

total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent

entering dry-bulb/wet-bulb F
95/78
95/80
105/76

85/76

85/78

85/80

95/76

332.54
142.54
334.92
143.45
337.20
144.36
339.37
145.75
342.53
141.73
344.56
142.46

334.18
145.91
336.62
147.03
338.95
148.09
341.18
149.64
344.39
145.78
346.48
146.66

330.52
146.41
334.11
143.45
335.82
149.28
338.32
150.60
340.71
151.82
342.99
153.53
346.26
149.82
348.40
150.87

327.29
134.30
329.56
134.82
331.73
135.35
333.81
136.11
336.87
131.71
338.81
132.04

328.93
137.67
331.26
138.40
333.49
139.08
335.62
140.00
338.73
135.75
340.73
136.24

325.51
138.96
328.99
135.57
330.57
141.04
332.96
141.97
335.24
142.81
337.43
143.89
340.60
139.80
342.65
140.45

322.05
126.05
324.20
126.19
326.26
126.34
328.24
126.47
331.21
121.68
333.06
121.62

105/78

105/80

115/76

115/78

115/80

323.69
129.42
325.90
129.77
328.02
130.07
330.05
130.36
333.07
125.73
334.98
125.82

320.50
131.50
323.88
127.70
325.33
132.79
327.60
133.34
329.78
133.80
331.86
134.25
334.94
129.77
336.90
130.03

316.81
117.81
318.84
117.56
320.80
117.33
322.67
116.84
325.54
111.65
327.31
111.20

318.45
121.18
320.54
121.13
322.55
121.06
324.48
120.72
327.41
115.70
329.23
115.40

315.50
124.04
318.76
119.83
320.09
124.55
322.24
124.71
324.31
124.79
326.29
124.61
329.27
119.75
331.15
119.61

Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63F. Dashed fields indicate that the unit will cycle
compressor to maintain the DP setpoint above 45F.

Table PD-48. Size 031 cooling capacity with reheat, MBh


cfm
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100

total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent

entering dry-bulb/wet-bulb F
95/78
95/80
105/76

85/76

85/78

85/80

95/76

342.40
142.16
344.68
143.04
346.86
143.85
348.95
144.61

341.72
144.94
344.16
146.03
346.50
147.05
348.73
148.02
350.88
148.94

338.10
146.01
340.81
147.29
343.44
148.66
345.93
149.90
348.32
151.07
350.60
152.19
352.80
153.26

338.19
133.28
340.40
133.76
342.52
134.19
344.55
134.56

337.60
136.44
339.96
137.14
342.22
137.78
344.39
138.35
346.48
138.88

334.16
138.29
336.78
139.19
339.32
140.16
341.73
141.01
344.04
141.79
346.26
142.52
348.40
143.20

336.12
124.48
338.18
124.52
340.15
124.50

105/78

105/80

115/76

115/78

115/80

333.48
127.94
335.75
128.26
337.94
128.50
340.05
128.69
342.08
128.83

332.75
131.09
335.19
131.66
337.52
132.12
339.76
132.52
341.92
132.85
344.00
133.15

331.84
115.21
333.83
114.85
335.75
114.45

329.35
119.44
331.55
119.37
333.66
119.22
335.70
119.02
337.68
118.77

328.72
122.99
331.07
123.16
333.32
123.24
335.48
123.24
337.57
123.19
339.60
123.09

Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63F. Dashed fields indicate that the unit will cycle
compressor to maintain the DP setpoint above 45F.

60

MUA-PRC004-EN

Performance
Data

unit w/TE wheel


capacity

Table PD-49. Size 031 reheat, MBh


cfm

55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68

entering dry-bulb/wet-bulb F
75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

1800
2200
2600
3100

46.5
47.9
49.2
49.8

49.8
51.2
52.5
53.6

46.8
48.1
49.4
49.9

47.0
48.3
49.5
50.0

47.8
49.2
50.6
51.5

48.0
49.4
50.8
51.6

48.3
49.6
50.9
51.7

49.3
50.8
52.2
53.4

49.5
51.0
52.3
53.5

50.8
52.3
53.7
55.2

51.0
52.5
53.9
55.3

51.2
52.7
54.0
55.5

51.1
52.9
54.6
56.5

51.3
53.1
54.8
56.6

51.5
53.3
54.9
56.7

51.4
53.5
55.5
57.7

51.6
53.7
55.6
57.8

51.8
53.9
55.8
57.9

51.6
54.1
56.4
58.9

51.9
54.3
56.5
59.1

52.1
54.4
56.7
59.2

Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63F).

Table PD-50. Size 031 condenser reheat max temperature rise, F


cfm

55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68

entering dry-bulb/wet-bulb F
75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

1800
2200
2600
3100

24.4
20.6
17.9
15.2

26.0
21.9
19.0
16.3

24.5
20.7
18.0
15.3

24.7
20.7
18.0
15.3

25.0
21.1
18.4
15.7

25.1
21.2
18.4
15.7

25.3
21.3
18.5
15.8

25.8
21.7
18.9
16.2

25.9
21.8
18.9
16.2

26.5
22.3
19.4
16.7

26.6
22.4
19.4
16.7

26.7
22.5
19.5
16.8

26.6
22.6
19.7
17.1

26.7
22.6
19.7
17.1

26.9
22.7
19.8
17.1

26.8
22.8
20.0
17.4

26.9
22.9
20.1
17.5

27.0
23.0
20.1
17.5

26.9
23.0
20.3
17.8

27.0
23.1
20.4
17.8

27.1
23.2
20.4
17.9

Note: Temperature rises are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63F).

Table PD-51. Size 031 design supply air dew point, cfm
dry-bulb
(F)
85

95

105

wet-bulb
(F)
76
78
80
76
78
80
76
78
80

46
2781
2656
2531
2742
2617
2492
2704
2579
2453

48
3043
2918
2792
3004
2879
2754
2965
2840
2715

design supply air dew point (F)


50
52
54
56

3054

2977

58

60

62

76
78
80

2665
2540
2415

2927
2802
2677

3063
2938

115

Note: Dew point temps are with all compressors running, balanced supply and exhaust airflow and ARI 1060 return air conditions of 75/63F.

MUA-PRC004-EN

61

unit w/TE wheel


capacity

Performance
Data
Table PD-52. Size 040 cooling capacity without reheat, MBh
cfm
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000

85/76
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent

369.53
158.83
373.14
153.96
374.21
160.79
376.12
161.38
378.16
162.12
380.13
162.81
383.53
157.50
385.41
158.11

85/78
341.18
149.64
366.53
160.06
366.53
160.06
369.05
161.20
371.47
162.85
375.13
158.12
376.20
165.05
378.19
165.84
380.28
166.73
382.29
167.57
385.75
162.40
387.66
163.15

85/80
342.99
153.53
368.38
163.79
368.38
163.79
370.95
165.08
373.41
166.87
377.11
162.29
378.18
169.32
380.27
170.30
382.40
171.33
384.46
172.32
387.96
167.30
389.92
168.20

95/76

entering dry-bulb/wet-bulb F
95/78
95/80
105/76

362.89
148.65
366.42
143.42
367.33
149.81
369.25
150.11
371.22
150.50
373.12
150.83
376.47
145.14
378.28
145.38

335.62
140.00
360.07
150.84
360.07
150.84
362.50
151.63
364.83
152.67
368.41
147.58
369.32
154.07
371.32
154.57
373.34
155.10
375.29
155.58
378.68
150.04
380.54
150.42

337.43
143.89
361.92
154.56
361.92
154.56
364.39
155.50
366.77
156.69
370.39
151.75
371.31
158.34
373.40
159.03
375.46
159.71
377.46
160.33
380.89
154.94
382.80
155.46

356.25
138.48
359.70
132.87
360.46
138.82
362.38
138.85
364.28
138.87
366.12
138.84
369.40
132.78
371.16
132.64

105/78
330.05
130.36
353.61
141.61
353.61
141.61
355.94
142.05
358.19
142.50
361.68
137.04
362.44
143.09
364.45
143.31
366.40
143.48
368.28
143.59
371.61
137.68
373.41
137.68

105/80
331.86
134.25
355.45
145.34
355.45
145.34
357.84
145.92
360.13
146.52
363.67
141.20
364.43
147.35
366.53
147.77
368.52
148.09
370.45
148.35
373.83
142.58
375.67
142.72

115/76
349.61
128.30
352.98
122.33
353.58
127.84
355.50
127.59
357.34
127.25
359.11
126.85
362.34
120.42
364.03
119.90

115/78
324.48
120.72
347.15
132.38
347.15
132.38
349.39
132.47
351.55
132.32
354.96
126.50
355.57
132.11
357.58
132.05
359.46
131.86
361.28
131.61
364.55
125.32
366.29
124.94

115/80
326.29
124.61
348.99
136.11
348.99
136.11
351.28
136.34
353.49
136.34
356.95
130.66
357.55
136.37
359.66
136.51
361.58
136.46
363.45
136.36
366.76
130.22
368.55
129.99

Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63F. Dashed fields indicate that the unit will cycle
compressor to maintain the DP setpoint above 45F.

Table PD-53. Size 040 cooling capacity with reheat, MBh


cfm
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000

85/76
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent

381.56
158.11
383.66
158.77
385.82
159.51
387.89
160.67
389.91
161.33
391.86
161.98
393.75
162.60

85/78
381.13
161.45
383.60
162.56
385.78
163.40
387.98
164.29
390.09
165.61
392.15
166.43
394.14
167.22
396.07
167.99

85/80
378.05
163.33
380.66
164.59
383.17
165.80
385.64
167.01
387.90
168.04
390.14
169.08
392.29
170.54
394.39
171.53
396.42
172.47
398.39
173.38

95/76
376.22
147.54
378.35
147.90
380.47
148.28
382.51
148.80
384.51
149.10
386.43
149.37
388.30
149.61

entering dry-bulb/wet-bulb F
95/78
95/80
105/76
375.91
151.31
378.26
151.99
380.47
152.53
382.63
153.06
384.71
153.74
386.75
154.19
388.71
154.61
390.62
155.00

372.95
153.96
375.50
154.84
377.95
155.66
380.30
156.44
382.59
157.17
384.79
157.85
386.91
158.68
388.98
159.29
390.99
159.86
392.94
160.39

373.03
137.03
375.12
137.05
377.14
136.94
379.10
136.86
381.00
136.76
382.85
136.63

105/78
370.69
141.18
372.93
141.41
375.15
141.66
377.28
141.84
379.34
141.88
381.34
141.96
383.28
142.00
385.17
142.01

105/80
367.86
144.59
370.33
145.10
372.73
145.53
374.97
145.87
377.27
146.30
379.44
146.62
381.54
146.81
383.58
147.06
385.56
147.25
387.49
147.40

115/76
367.72
126.16
369.77
125.82
371.77
125.07
373.70
124.63
375.57
124.15
377.39
123.64

115/78
365.47
131.04
367.59
130.84
369.84
130.79
371.93
130.61
373.97
130.01
375.94
129.73
377.85
129.39
379.71
129.03

115/80
362.76
135.22
365.17
135.35
367.51
135.39
369.63
135.29
371.96
135.43
374.09
135.39
376.17
134.95
378.18
134.82
380.13
134.64
382.03
134.41

Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63F. Dashed fields indicate that the unit will cycle
compressor to maintain the DP setpoint above 45F.

62

MUA-PRC004-EN

Performance
Data

unit w/TE wheel


capacity

Table PD-54. Size 040 reheat, MBh


cfm

entering dry-bulb/wet-bulb F
55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

2200
2600
3000
3400
3800
4000

68.6
70.1
71.3
72.6
73.3
73.7

69.0
70.5
71.7
72.9
73.6
74.0

69.4
70.9
72.0
73.2
74.0
74.2

70.4
72.1
73.5
74.9
75.9
76.3

70.8
72.5
73.9
75.2
76.2
76.6

71.2
72.9
74.2
75.6
76.4
76.9

72.7
74.5
76.1
77.6
78.7
79.3

73.1
74.9
76.4
77.9
79.0
79.5

73.5
75.3
76.8
78.2
79.3
79.8

75.0
77.0
78.6
80.2
81.5
82.2

75.4
77.3
79.0
80.5
81.8
82.5

75.8
77.7
79.4
80.8
82.1
82.8

75.2
77.4
79.4
81.2
82.9
83.7

75.6
77.8
79.7
81.6
83.2
84.0

76.0
78.2
80.1
81.9
83.5
84.3

75.5
77.9
80.1
82.3
84.3
85.3

75.9
78.3
80.5
82.6
84.6
85.6

76.3
78.7
80.8
82.9
84.9
85.8

75.8
78.3
80.9
83.3
85.7
86.8

76.2
78.7
81.2
83.6
86.0
87.1

76.6
79.1
81.6
84.0
86.3
87.4

Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63F).

Table PD-55. Size 040 condenser reheat max temperature rise, F


cfm

entering dry-bulb/wet-bulb F
55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

2200
2600
3000
3400
3800
4000

29.3
25.4
22.4
20.1
18.2
17.4

29.4
25.5
22.5
20.2
18.3
17.4

29.6
25.6
22.6
20.3
18.3
17.5

30.0
26.0
23.0
20.7
18.8
17.9

30.2
26.2
23.1
20.8
18.8
18.0

30.3
26.3
23.2
20.9
18.9
18.0

30.9
26.8
23.7
21.4
19.4
18.6

31.1
27.0
23.8
21.4
19.4
18.6

31.2
27.1
23.9
21.5
19.5
18.7

31.8
27.6
24.5
22.0
20.0
19.2

32.0
27.8
24.6
22.1
20.1
19.2

32.1
27.9
24.7
22.2
20.1
19.3

31.9
27.8
24.7
22.3
20.3
19.5

32.1
27.9
24.8
22.4
20.4
19.6

32.2
28.1
24.9
22.4
20.5
19.6

32.0
27.9
24.9
22.6
20.7
19.9

32.2
28.1
25.0
22.6
20.7
19.9

32.4
28.2
25.1
22.7
20.8
20.0

32.1
28.1
25.1
22.8
21.0
20.2

32.3
28.2
25.2
22.9
21.1
20.3

32.5
28.4
25.3
23.0
21.1
20.3

Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63F).

Table PD-56. Size 040 design supply air dewpoint, cfm


dry-bulb
(F)

wet-bulb
(F)

46

48

76
78
80
76
78
80
76
78
80
76
78
80

3422
3271
3121
3368
3218
3067
3315
3164
3014
3261
3111
2960

3754
3603
3453
3700
3550
3399
3647
3496
3346
3593
3443
3292

85

95

105

115

design supply air dew point (F)


50
52
54
56

3936
3785

3882
3731
3979
3828
3678
3925
3775
3624

3956

58

60

62

Note: Dew point temps are with all compressors running, balanced supply and exhaust airflow and ARI 1060 return air conditions of 75/63F.

MUA-PRC004-EN

63

unit w/TE wheel


capacity

Performance
Data
Table PD-57. Size 051 cooling capacity without reheat, MBh
cfm
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100

85/76
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent

418.18
179.55
420.61
180.55
422.97
181.48
425.27
182.39
427.50
183.23
429.68
183.99
433.68
177.91
433.86
185.50
435.87
186.20
437.82
186.87
439.72
187.55
443.61
181.25
445.43
181.86

85/78
415.39
182.04
418.02
183.20
420.58
184.35
423.06
185.47
425.46
186.53
427.81
187.56
430.09
188.53
432.31
189.44
436.35
183.50
436.57
191.23
438.63
192.08
440.62
192.89
442.56
193.71
446.49
187.54
448.36
188.28

85/80
414.93
185.25
417.69
186.60
420.38
187.88
422.98
189.15
425.50
190.39
427.96
191.58
430.35
192.73
432.67
193.83
434.93
194.89
439.02
189.09
439.29
196.97
441.38
197.96
443.42
198.92
445.40
199.87
449.38
193.82
451.28
194.69

95/76
409.70
167.66
412.03
168.32
414.30
168.92
416.51
169.47
418.66
169.98
420.75
170.41
424.68
164.00
424.79
171.26
426.73
171.64
428.63
171.97
430.46
172.32
434.30
165.68
436.07
165.96

entering dry-bulb/wet-bulb F
95/78
95/80
105/76
407.12
170.86
409.65
171.66
412.10
172.47
414.48
173.24
416.79
173.97
419.05
174.65
421.24
175.28
423.38
175.86
427.35
169.59
427.50
176.99
429.49
177.51
431.43
178.00
433.31
178.48
437.19
171.97
439.00
172.37

406.78
174.41
409.43
175.42
412.00
176.34
414.50
177.27
416.93
178.17
419.29
179.02
421.59
179.82
423.82
180.58
426.01
181.31
430.02
175.19
430.22
182.73
432.25
183.39
434.23
184.02
436.15
184.64
440.07
178.25
441.93
178.79

401.22
155.78
403.45
156.09
405.63
156.35
407.75
156.56
409.81
156.73
411.83
156.83
415.68
150.09
415.72
157.02
417.60
157.07
419.43
157.07
421.21
157.09
425.00
150.11
426.72
150.05

105/78
398.86
159.67
401.28
160.12
403.62
160.58
405.90
161.02
408.12
161.40
410.29
161.74
412.40
162.03
414.46
162.28
418.35
155.68
418.44
162.75
420.36
162.95
422.23
163.10
424.05
163.25
427.88
156.39
429.64
156.47

105/80
396.03
162.87
398.63
163.58
401.16
164.23
403.63
164.80
406.02
165.38
408.35
165.94
410.62
166.45
412.83
166.91
414.98
167.33
417.08
167.73
421.02
161.28
421.15
168.49
423.11
168.82
425.03
169.12
426.90
169.41
430.77
162.68
432.57
162.89

115/76
392.74
143.89
394.88
143.86
396.96
143.78
398.99
143.65
400.97
143.49
402.90
143.25
406.68
136.18
406.65
142.78
408.46
142.50
410.23
142.18
411.96
141.87
415.69
134.54
417.36
134.15

115/78
390.59
148.49
392.90
148.58
395.14
148.70
397.33
148.79
399.45
148.83
401.53
148.82
403.55
148.78
405.53
148.70
409.35
141.77
409.37
148.51
411.22
148.38
413.03
148.20
414.80
148.02
418.58
140.82
420.28
140.57

115/80
388.00
152.38
390.48
152.74
392.89
153.05
395.25
153.26
397.54
153.50
399.77
153.71
401.95
153.88
404.07
154.00
406.13
154.08
408.16
154.15
412.03
147.37
412.08
154.25
413.98
154.26
415.83
154.23
417.64
154.18
421.46
147.11
423.21
146.99

Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63F. Dashed fields indicate that the unit will cycle
compressor to maintain the DP setpoint above 45F.

64

MUA-PRC004-EN

Performance
Data

unit w/TE wheel


capacity

Table PD-58. Size 051 cooling capacity with reheat installed, MBh
cfm
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100

85/76
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent

436.78
180.99
439.07
181.83
441.30
182.63
443.47
183.41
445.57
184.15
447.63
184.86
449.87
185.91
451.58
186.24
453.48
186.91

85/78
434.55
184.56
437.02
185.62
439.43
186.64
441.76
187.61
444.03
188.54
446.24
189.45
448.38
190.33
450.48
191.17
452.76
192.36
454.50
192.82
456.44
193.61

85/80
431.84
187.47
434.52
188.73
437.08
189.86
439.63
191.15
442.07
192.29
444.45
193.39
446.77
194.45
449.01
195.49
451.20
196.50
453.33
197.48
455.65
198.80
457.43
199.39
459.40
200.31

95/76
430.29
168.11
432.51
168.60
434.68
169.05
436.80
169.48
438.86
169.87
440.87
170.23
443.21
171.07
444.75
170.84
446.61
171.15

entering dry-bulb/wet-bulb F
95/78
95/80
105/76
428.20
172.43
430.60
173.10
432.93
173.76
435.20
174.38
437.42
174.96
439.57
175.52
441.67
176.04
443.72
176.54
446.10
177.51
447.67
177.42
449.57
177.85

425.64
176.06
428.24
176.96
430.72
177.74
433.20
178.62
435.58
179.42
437.89
180.16
440.15
180.87
442.35
181.56
444.48
182.22
446.57
182.84
448.99
183.96
450.60
183.99
452.53
184.56

425.96
155.38
428.07
155.47
430.13
155.54
432.14
155.58
434.11
155.59
436.56
156.23
437.92
155.44
439.75
155.39

105/78
421.84
160.31
424.17
160.58
426.44
160.89
428.65
161.16
430.80
161.38
432.90
161.58
434.95
161.76
436.96
161.90
439.44
162.67
440.84
162.01
442.71
162.10

105/80
419.45
164.64
421.95
165.18
424.37
165.62
426.77
166.10
429.09
166.54
431.34
166.94
433.53
167.29
435.68
167.62
437.77
167.93
439.81
168.21
442.33
169.11
443.76
168.59
445.67
168.80

115/76
421.45
141.89
423.46
141.61
425.43
141.30
427.35
140.96
429.90
141.38
431.09
140.04
432.88
139.64

115/78
417.75
148.06
419.95
148.02
422.09
147.93
424.18
147.80
426.24
147.65
428.24
147.47
430.20
147.26
432.78
147.83
434.01
146.61
435.84
146.34

115/80
413.25
153.23
415.67
153.40
418.02
153.49
420.35
153.58
422.59
153.67
424.78
153.71
426.92
153.71
429.01
153.69
431.05
153.65
433.05
153.57
435.67
154.27
436.93
153.19
438.80
153.04

Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63F. Dashed fields indicate that the unit will cycle
compressor to maintain the DP setpoint above 45F.

MUA-PRC004-EN

65

unit w/TE wheel


capacity

Performance
Data
Table PD-59. Size 051 reheat data, MBh

entering dry-bulb/wet-bulb F
55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

cfm
2900
3300
3700
4100
4500
4900
5100

96.9
98.5
100.0
102.1
102.5
103.5
103.9

97.5
99.1
100.6
102.6
103.1
104.0
104.5

98.2
99.8
101.3
103.2
103.7
104.6
105.0

99.7
101.6
103.2
105.3
106.1
107.3
107.9

100.4
102.2
103.9
105.9
106.7
107.9
108.4

101.0
102.9
104.5
106.5
107.3
108.5
109.0

103.2
105.3
107.2
109.2
110.4
111.8
112.4

103.8
106.0
107.8
109.8
111.0
112.3
113.0

104.4
106.6
108.5
110.3
111.6
112.9
113.5

106.6
109.1
111.1
113.0
114.6
116.2
116.9

107.2
109.7
111.8
113.6
115.2
116.8
117.5

107.9
110.4
112.4
114.2
115.8
117.3
118.0

106.9
109.5
111.8
114.0
115.9
117.8
118.7

107.6
110.2
112.4
114.6
116.5
118.4
119.2

108.2
110.8
113.1
115.1
117.1
119.0
119.8

107.3
110.0
112.5
115.0
117.2
119.5
120.5

107.9
110.6
113.1
115.5
117.7
120.0
121.0

108.5
111.3
113.8
116.1
118.3
120.6
121.6

107.6
110.4
113.2
115.9
118.4
121.1
122.2

108.2
111.1
113.8
116.5
119.0
121.7
122.8

108.8
111.8
114.5
117.1
119.6
122.2
123.3

Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63F).

Table PD-60. Size 051 condenser reheat max temperature rise, F


cfm

entering dry-bulb/wet-bulb F
55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

2900
3300
3700
4100
4500
4900
5100

32.1
28.7
26.0
24.0
22.0
20.5
19.8

32.3
28.9
26.2
24.2
22.1
20.5
19.8

32.5
29.1
26.3
24.3
22.2
20.6
19.9

32.9
29.5
26.8
24.7
22.7
21.1
20.4

33.1
29.7
27.0
24.8
22.8
21.2
20.5

33.3
29.9
27.1
25.0
22.9
21.3
20.6

34.0
30.5
27.7
25.5
23.5
21.9
21.2

34.2
30.7
27.9
25.6
23.6
22.0
21.3

34.3
30.9
28.0
25.8
23.7
22.1
21.3

35.0
31.5
28.7
26.3
24.3
22.7
21.9

35.2
31.7
28.8
26.4
24.4
22.8
22.0

35.4
31.8
29.0
26.6
24.6
22.9
22.1

35.1
31.6
28.8
26.5
24.6
23.0
22.2

35.3
31.8
29.0
26.7
24.7
23.1
22.3

35.5
32.0
29.1
26.8
24.8
23.2
22.4

35.2
31.8
29.0
26.7
24.8
23.3
22.6

35.4
31.9
29.1
26.9
25.0
23.4
22.6

35.6
32.1
29.3
27.0
25.1
23.5
22.7

35.3
31.9
29.1
27.0
25.1
23.6
22.9

35.5
32.0
29.3
27.1
25.2
23.7
23.0

35.7
32.2
29.5
27.2
25.3
23.8
23.0

Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63F).

Table PD-61. Size 051 design supply air dew point, cfm
dry-bulb
(F)

wet-bulb
(F)

46

48

58

60

62

85

76
78
80

4263
4063
3863

4701
4501
4301

4939
4739

95

76
78
80

4211
4011
3811

4649
4449
4249

5087
4887
4687

76
78
80
76
78
80

4159
3959
3759
4107
3907
3707

4597
4397
4197
4545
4345
4145

5035
4835
4635
4983
4783
4583

5073

5021

105

115

design supply air dew point (F)


50
52
54
56

Note: Dew point temps are with all compressors running, balanced supply and exhaust airflow and ARI 1060 return air conditions of 75/63F.

66

MUA-PRC004-EN

Performance
Data

unit w/TE wheel


capacity

Table PD-62. Size 066 cooling capacity without reheat, MBh


cfm
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600

85/76
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent

469.07
201.28
471.48
202.20
473.82
203.13
476.10
204.03
478.31
204.89
480.49
205.71
482.61
206.50
484.68
207.27
486.71
208.03
488.68
208.75
490.62
209.44
492.52
210.11
494.37
210.78
498.61
203.15
497.95
212.01
499.67
212.60
501.37
213.17
503.01
213.72
507.23
207.00
508.85
207.49

85/78
466.71
204.62
469.29
205.74
471.80
206.84
474.25
207.90
476.63
208.96
478.96
209.99
481.23
210.98
483.44
211.93
485.61
212.85
487.72
213.77
489.79
214.66
491.81
215.52
493.79
216.35
495.72
217.16
497.62
217.96
501.90
210.46
501.27
219.46
503.04
220.18
504.77
220.88
506.46
221.56
510.71
214.96
512.37
215.58

85/80
463.88
207.28
466.64
208.62
469.34
209.93
471.97
211.17
474.52
212.41
477.02
213.59
479.45
214.79
481.83
215.95
484.14
217.07
486.40
218.16
488.61
219.20
490.76
220.26
492.87
221.29
494.94
222.29
496.95
223.26
498.93
224.21
500.87
225.14
505.19
217.77
504.60
226.90
506.41
227.75
508.18
228.59
509.90
229.40
514.19
222.93
515.89
223.68

95/76
458.59
187.36
460.90
187.95
463.14
188.56
465.32
189.15
467.45
189.68
469.53
190.19
471.56
190.66
473.55
191.12
475.49
191.55
477.39
191.95
479.25
192.31
481.07
192.66
482.86
193.00
487.03
185.04
486.30
193.57
487.97
193.83
489.60
194.06
491.20
194.27
495.36
186.58
496.92
186.73

entering dry-bulb/wet-bulb F
95/78
95/80
105/76
453.92
190.48
456.45
191.34
458.92
192.14
461.32
192.92
463.67
193.64
465.96
194.39
468.19
195.11
470.36
195.78
472.48
196.41
474.56
197.02
476.59
197.61
478.58
198.18
480.52
198.72
482.42
199.23
484.28
199.71
486.11
200.18
490.32
192.35
489.63
201.02
491.34
201.41
493.01
201.77
494.64
202.11
498.84
194.54
500.45
194.82

451.16
193.59
453.86
194.64
456.50
195.67
459.08
196.65
461.60
197.57
464.05
198.48
466.44
199.33
468.77
200.22
471.05
201.06
473.27
201.87
475.44
202.64
477.56
203.37
479.64
204.10
481.66
204.81
483.65
205.49
485.59
206.14
487.49
206.76
489.36
207.36
493.61
199.66
492.96
208.46
494.70
208.98
496.42
209.48
498.09
209.95
502.32
202.51
503.97
202.91

448.12
173.43
450.32
173.69
452.46
173.99
454.55
174.26
456.58
174.48
458.57
174.67
460.52
174.83
462.42
174.96
464.28
175.07
466.10
175.15
467.89
175.19
469.63
175.22
471.35
175.23
475.46
166.93
474.66
175.13
476.27
175.06
477.84
174.95
479.38
174.82
483.49
166.16
485.00
165.97

105/78
443.77
177.52
446.19
178.06
448.55
178.53
450.84
179.00
453.09
179.38
455.28
179.82
457.41
180.22
459.49
180.57
461.53
180.89
463.52
181.18
465.47
181.46
467.37
181.71
469.23
181.92
471.05
182.11
472.84
182.26
474.60
182.40
478.74
174.24
477.99
182.58
479.63
182.63
481.25
182.66
482.82
182.66
486.97
174.13
488.52
174.06

105/80
441.27
181.30
443.84
182.01
446.35
182.71
448.82
183.37
451.23
183.96
453.57
184.56
455.86
185.07
458.09
185.65
460.28
186.18
462.40
186.67
464.48
187.12
466.52
187.54
468.51
187.95
470.45
188.34
472.36
188.69
474.22
189.02
476.05
189.31
477.85
189.58
482.03
181.55
481.32
190.02
483.00
190.21
484.65
190.37
486.27
190.50
490.45
182.09
492.04
182.15

115/76
437.64
159.51
439.74
159.43
441.78
159.42
443.77
159.38
445.71
159.28
447.62
159.15
449.48
158.99
451.30
158.81
453.07
158.60
454.81
158.35
456.52
158.07
458.19
157.77
459.84
157.45
463.88
148.82
463.02
156.69
464.56
156.29
466.08
155.85
467.56
155.37
471.61
145.74
473.07
145.20

115/78
433.63
164.57
435.93
164.78
438.18
164.92
440.37
165.07
442.51
165.12
444.60
165.25
446.63
165.34
448.62
165.37
450.57
165.38
452.47
165.35
454.34
165.30
456.16
165.23
457.94
165.12
459.69
164.99
461.40
164.82
463.09
164.63
467.17
156.13
466.35
164.13
467.93
163.86
469.49
163.55
471.01
163.21
475.10
153.71
476.59
153.30

115/80
431.38
169.00
433.82
169.37
436.21
169.75
438.56
170.09
440.86
170.36
443.10
170.63
445.28
170.82
447.42
171.08
449.50
171.30
451.53
171.46
453.53
171.60
455.47
171.70
457.38
171.79
459.24
171.86
461.07
171.89
462.85
171.90
464.61
171.86
466.33
171.81
470.45
163.44
469.68
171.58
471.30
171.44
472.89
171.26
474.45
171.05
478.58
161.67
480.11
161.39

Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63F. Dashed fields indicate that the unit will cycle
compressor to maintain the DP setpoint above 45F.

MUA-PRC004-EN

67

unit w/TE wheel


capacity

Performance
Data
Table PD-63. Size 066 cooling capacity with reheat, MBh
cfm
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600

85/76
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent
total
latent

489.47
202.30
491.74
203.14
493.97
203.93
496.14
204.68
498.27
205.41
500.35
206.12
502.39
206.81
504.38
207.46
506.34
208.05
508.24
208.71
510.11
209.35
511.93
209.95
513.71
210.55
515.46
211.12
517.16
211.67
518.83
212.20

85/78
485.14
205.61
487.63
206.66
490.07
207.72
492.45
208.69
494.76
209.65
497.02
210.58
499.24
211.47
501.41
212.32
503.52
213.17
505.60
214.00
507.62
214.82
509.61
215.56
511.56
216.35
513.46
217.12
515.32
217.84
517.13
218.58
518.91
219.28
520.65
219.96
522.35
220.62

85/80
486.89
212.09
487.99
211.63
490.52
212.79
493.00
213.98
495.42
215.08
497.78
216.17
500.08
217.22
502.34
218.25
504.54
219.24
506.70
220.22
508.80
221.19
510.87
222.18
512.89
223.07
514.87
223.99
516.81
224.89
518.70
225.74
520.55
226.61
522.36
227.44
524.14
228.25
525.87
229.05

95/76
481.08
187.21
483.29
187.71
485.45
188.18
487.56
188.61
489.63
189.01
491.66
189.39
493.64
189.76
495.58
190.07
497.49
190.34
499.35
190.65
501.17
190.96
502.96
191.22
504.71
191.48
506.41
191.72
508.09
191.94
509.73
192.13

entering dry-bulb/wet-bulb F
95/78
95/80
105/76
479.39
192.31
481.75
192.98
484.06
193.60
486.31
194.23
488.51
194.83
490.66
195.39
492.77
195.92
494.83
196.44
496.85
196.95
498.83
197.43
500.77
197.84
502.66
198.30
504.52
198.73
506.35
199.11
508.13
199.51
509.87
199.88
511.58
200.23
513.25
200.55

478.28
197.87
479.82
197.63
482.28
198.45
484.68
199.25
487.04
199.98
489.33
200.74
491.57
201.47
493.76
202.17
495.90
202.84
498.00
203.49
500.06
204.14
502.07
204.79
504.04
205.35
505.98
205.94
507.87
206.50
509.73
207.01
511.55
207.54
513.32
208.04
515.07
208.52
516.77
208.98

474.84
172.28
476.93
172.43
478.98
172.53
480.99
172.61
482.96
172.66
484.89
172.70
486.78
172.69
488.64
172.62
490.46
172.60
492.24
172.57
493.99
172.48
495.70
172.42
497.37
172.32
499.02
172.20
500.63
172.06

105/78
471.14
177.97
473.43
178.25
475.68
178.50
477.86
178.80
479.99
179.08
482.08
179.32
484.13
179.52
486.13
179.71
488.10
179.89
490.03
180.04
491.92
180.13
493.77
180.24
495.59
180.34
497.37
180.38
499.12
180.45
500.83
180.49
502.51
180.50
504.15
180.48

105/80
469.67
183.66
471.65
183.64
474.03
184.11
476.37
184.51
478.65
184.89
480.87
185.31
483.05
185.72
485.18
186.10
487.26
186.44
489.30
186.76
491.31
187.08
493.27
187.40
495.19
187.63
497.08
187.88
498.93
188.11
500.76
188.28
502.54
188.48
504.28
188.65
505.99
188.79
507.67
188.91

115/76
468.41
156.68
470.40
156.46
472.35
156.21
474.27
155.93
476.14
155.65
477.98
155.30
479.79
154.91
481.56
154.55
483.30
154.18
485.02
153.75
486.69
153.35
488.33
152.93
489.95
152.47
491.53
151.99

115/78
462.90
163.62
465.12
163.51
467.29
163.41
469.40
163.37
471.47
163.33
473.50
163.24
475.49
163.12
477.44
162.98
479.35
162.84
481.23
162.66
483.07
162.41
484.88
162.19
486.65
161.95
488.40
161.65
490.11
161.38
491.79
161.09
493.43
160.76
495.05
160.42

115/80
461.07
169.45
463.49
169.64
465.79
169.76
468.05
169.77
470.27
169.80
472.42
169.89
474.53
169.97
476.60
170.02
478.62
170.04
480.61
170.04
482.56
170.03
484.47
170.01
486.35
169.92
488.19
169.83
490.00
169.73
491.79
169.55
493.53
169.41
495.24
169.25
496.92
169.06
498.58
168.84

Note: Capacities are with all compressors runnning, balanced supply and exhaust airflow, and ARI 1060 return air conditions of 75/63F. Dashed fields indicate that the unit will cycle
compressor to maintain the DP setpoint above 45F.

68

MUA-PRC004-EN

Performance
Data

unit w/TE wheel


capacity

Table PD-64. Size 066 reheat data, MBh


cfm
3600
4000
4400
4800
5200
5600
6000
6400
6600

entering dry-bulb/wet-bulb F
55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80
102.6
104.0
105.4
106.6
107.6
108.6
109.5
110.1
110.4

103.2
104.6
106.0
107.1
108.1
109.0
109.9
110.5
110.8

103.8
105.2
106.5
107.6
108.6
109.5
110.3
110.9
111.2

105.4
107.0
108.5
109.9
111.1
112.2
113.3
114.2
114.6

106.1
107.6
109.1
110.4
111.5
112.7
113.7
114.6
114.9

106.7
108.2
109.7
110.9
112.0
113.1
114.1
115.0
115.3

108.9
110.6
112.2
113.7
115.0
116.3
117.5
118.6
119.1

109.5
111.2
112.8
114.2
115.5
116.8
118.0
119.0
119.5

110.1
111.8
113.3
114.7
116.0
117.2
118.4
119.4
119.9

112.3
114.2
115.9
117.5
119.0
120.4
121.8
123.0
123.6

112.9
114.8
116.5
118.0
119.5
120.8
122.2
123.4
124.0

113.5
115.4
117.0
118.5
119.9
121.3
122.6
123.8
124.4

112.8
114.9
116.8
118.7
120.5
122.2
123.9
125.5
126.3

113.4
115.5
117.4
119.2
121.0
122.7
124.3
125.9
126.6

114.0
116.1
117.9
119.7
121.5
123.1
124.7
126.3
127.0

113.2
115.5
117.7
119.9
122.0
124.1
126.1
128.0
128.9

113.8
116.1
118.3
120.4
122.5
124.5
126.5
128.4
129.3

114.4
116.7
118.8
120.9
123.0
125.0
126.9
128.8
129.7

113.6
116.1
118.6
121.1
123.6
125.9
128.2
130.5
131.5

114.2
116.7
119.2
121.6
124.0
126.4
128.6
130.8
131.9

114.8
117.3
119.7
122.1
124.5
126.8
129.1
131.2
132.3

Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63F).

Table PD-65. Size 066 condenser reheat max temperature rise, F


cfm

entering dry-bulb/wet-bulb F
55/48 55/50 55/52 65/56 65/58 65/60 75/66 75/68 75/70 85/76 85/78 85/80 95/76 95/78 95/80 105/76 105/78 105/80 115/76 115/78 115/80

3600
4000
4400
4800
5200
5600
6000
6400
6600

27.3
24.9
23.0
21.3
19.9
18.7
17.6
16.6
16.1

27.4
25.0
23.1
21.4
20.0
18.7
17.6
16.6
16.2

27.5
25.2
23.2
21.5
20.0
18.8
17.7
16.7
16.2

27.9
25.6
23.6
21.9
20.5
19.2
18.1
17.1
16.7

28.1
25.7
23.7
22.0
20.5
19.3
18.2
17.2
16.7

28.2
25.8
23.8
22.1
20.6
19.3
18.2
17.2
16.8

28.8
26.3
24.3
22.6
21.1
19.8
18.7
17.7
17.2

28.9
26.5
24.4
22.7
21.2
19.9
18.8
17.8
17.3

29.1
26.6
24.5
22.8
21.3
20.0
18.8
17.8
17.3

29.6
27.1
25.0
23.3
21.7
20.4
19.3
18.3
17.8

29.7
27.2
25.1
23.3
21.8
20.5
19.4
18.3
17.9

29.9
27.4
25.2
23.4
21.9
20.6
19.4
18.4
17.9

29.7
27.2
25.2
23.5
22.0
20.7
19.6
18.6
18.2

29.8
27.4
25.3
23.6
22.1
20.8
19.7
18.7
18.2

30.0
27.5
25.4
23.7
22.2
20.9
19.7
18.7
18.3

29.8
27.4
25.4
23.7
22.3
21.0
20.0
19.0
18.6

29.9
27.5
25.5
23.8
22.4
21.1
20.0
19.0
18.6

30.1
27.6
25.6
23.9
22.4
21.2
20.1
19.1
18.6

29.9
27.5
25.6
23.9
22.6
21.3
20.3
19.4
18.9

30.0
27.7
25.7
24.0
22.6
21.4
20.3
19.4
19.0

30.2
27.8
25.8
24.1
22.7
21.5
20.4
19.4
19.0

Note: Capacities are for balanced supply and exhaust airflow with ARI 1060 return air conditions (75/63F).

Table PD-66. Size 066 design supply air dew point, cfm
dry-bulb
(F)

wet-bulb
(F)
76
78
80
76
78
80

46
5079
4809
4538
5031
4760
4489

48
5652
5381
5111
5603
5333
5062

design supply air dew point (F)


50
52
54
56
6225

5954
6527

5683
6256

6176

5905
6478

5635
6207

58

60

62

105

76
78
80

4982
4711
4440

5554
5284
5013

6127
5856
5586

6429
6158

115

76
78
80

4933
4662
4392

5505
5235
4964

6078
5807
5537

6380
6109

85

95

Note: Dew point temps are with all compressors running, balanced supply and exhaust airflow and ARI 1060 return air conditions of 75/63F.

MUA-PRC004-EN

69

TE wheel
capacity

Performance
Data
Table PD-67. Total energy wheel (only) cooling capacity
unit
size

cfm

031

1800

040

051

066

70

entering dry-bulb/wet-bulb F
95/78
95/80 105/76 105/78

85/76

85/78

85/80

95/76

105/80

115/76

115/78

115/80

total
latent

67.21
51.67

79.25
63.73

91.82
76.33

66.16
35.71

78.03
47.62

90.42
60.05

65.02
20.22

76.74
31.97

88.96
44.24

63.84
5.16

75.41
16.76

87.47
28.88

2200

total
latent

78.71
60.35

92.78
74.45

107.46
89.16

77.61
41.72

91.50
55.63

105.98
70.15

76.38
23.62

90.09
37.35

104.39
51.68

75.06
6.03

88.62
19.58

102.74
33.73

2600

total
latent

89.13
68.17

105.02
84.09

121.61
100.71

88.04
47.12

103.74
62.83

120.11
79.23

86.75
26.68

102.28
42.18

118.45
58.37

85.34
6.81

100.70
22.12

116.69
38.10

3100

total
latent

100.74
76.81

118.66
94.75

137.36
113.47

99.73
53.09

117.45
70.79

135.91
89.27

98.43
30.06

115.97
47.53

134.23
65.77

96.95
7.67

114.31
24.92

132.38
42.93

2200

total
latent

83.14
63.95

98.04
78.89

113.59
94.48

81.79
44.21

96.49
58.94

111.81
74.33

80.36
25.03

94.86
39.57

109.98
54.76

78.88
6.39

93.19
20.75

108.11
35.74

2600

total
latent

95.08
73.00

112.09
90.05

129.85
107.85

93.67
50.46

110.46
67.28

127.96
84.84

92.12
28.57

108.70
45.17

125.97
62.51

90.49
7.29

106.86
23.68

123.92
40.80

3000

total
latent

106.16
81.36

125.13
100.36

144.92
120.19

104.73
56.24

123.46
74.99

142.98
94.56

103.10
31.84

121.60
50.34

140.88
69.66

101.35
8.13

119.64
26.40

138.69
45.47

3400

total
latent

116.44
89.06

137.21
109.86

158.87
131.57

115.02
61.56

135.54
82.08

156.92
103.51

113.34
34.85

133.63
55.11

154.75
76.26

111.51
8.90

131.57
28.89

152.45
49.77

3800

total
latent

125.94
96.14

148.37
118.59

171.76
142.03

124.58
66.45

146.74
88.61

169.84
111.73

122.88
37.62

144.81
59.49

167.64
82.32

120.98
9.60

142.68
31.19

165.27
53.73

4000

total
latent

130.42
99.46

153.62
122.68

177.82
146.93

129.09
68.75

152.03
91.67

175.94
115.59

127.39
38.92

150.10
61.54

173.74
85.16

125.47
9.93

147.95
32.27

171.33
55.59

2900

total
latent

108.90
83.74

128.41
103.30

148.77
123.71

107.17
57.88

126.41
77.18

146.48
97.32

105.30
32.77

124.30
51.82

144.10
71.70

103.38
8.36

122.13
27.17

141.67
46.80

3300

total
latent

120.76
92.73

142.38
114.38

164.93
136.98

118.97
64.10

140.29
85.46

162.53
107.77

117.00
36.29

138.05
57.38

159.99
79.40

114.93
9.26

135.72
30.08

157.39
51.82

3700

total
latent

131.96
101.17

155.54
124.79

180.15
149.46

130.13
69.93

153.41
93.24

177.68
117.58

128.08
39.59

151.07
62.60

175.04
86.62

125.88
10.11

148.61
32.82

172.29
56.54

4100

total
latent

142.50
109.09

167.94
134.57

194.48
161.16

140.69
75.41

165.80
100.54

191.99
126.79

138.57
42.69

163.40
67.50

189.26
93.41

136.28
10.90

160.83
35.39

186.39
60.97

4500

total
latent

152.43
116.51

179.60
143.72

207.95
172.12

150.65
80.54

177.49
107.39

205.47
135.41

148.49
45.60

175.04
72.10

202.69
99.76

146.12
11.64

172.39
37.80

199.73
65.12

4900

total
latent

161.76
123.45

190.56
152.29

220.61
182.38

160.04
85.34

188.50
113.79

218.17
143.48

157.87
48.31

186.04
76.39

215.37
105.71

155.44
12.33

183.33
40.05

212.33
69.00

5100

total
latent

166.21
126.75

195.79
156.36

226.64
187.25

164.53
87.62

193.77
116.83

224.23
147.32

162.36
49.61

191.30
78.43

221.43
108.53

159.91
12.66

188.56
41.12

218.37
70.84

3600

total
latent

135.14
103.92

159.35
128.19

184.62
153.52

132.99
71.83

156.87
95.78

181.78
120.77

130.68
40.67

154.25
64.30

178.82
88.98

128.29
10.38

151.57
33.71

175.81
58.08

4000

total
latent

147.06
112.95

173.39
139.33

200.85
166.86

144.85
78.07

170.82
104.10

197.90
131.27

142.43
44.20

168.07
69.89

194.79
96.71

139.89
11.28

165.22
36.64

191.60
63.13

4400

total
latent

158.44
121.54

186.77
149.92

216.33
179.55

156.19
84.01

184.15
112.02

213.30
141.26

153.67
47.56

181.29
75.21

210.07
104.07

151.01
12.14

178.30
39.43

206.72
67.93

4800

total
latent

169.29
129.70

199.53
159.99

231.08
191.61

167.03
89.66

196.88
119.54

228.00
150.75

164.44
50.76

193.94
80.26

224.68
111.06

161.67
12.96

190.83
42.08

221.20
72.49

5200

total
latent

179.62
137.45

211.67
169.55

245.11
203.06

177.38
95.01

209.03
126.69

242.03
159.75

174.74
53.79

206.03
85.06

238.63
117.69

171.87
13.73

202.82
44.59

235.04
76.82

5600

total
latent

189.46
144.80

223.23
178.62

258.47
213.92

187.25
100.09

220.62
133.46

255.40
168.30

184.58
56.67

217.58
89.60

251.95
123.99

181.64
14.46

214.29
46.98

248.27
80.93

6000

total
latent

198.82
151.77

234.23
187.22

271.16
224.21

196.67
104.91

231.66
139.88

268.13
176.39

193.99
59.40

228.61
93.91

264.66
129.95

190.99
15.16

225.26
49.24

260.91
84.82

6400

total
latent

207.72
158.37

244.67
195.35

283.21
233.95

205.65
109.47

242.18
145.96

280.25
184.06

202.97
61.98

239.13
98.00

276.78
135.60

199.92
15.82

235.73
51.38

272.98
88.51

6600

total
latent

212.00
161.53

249.69
199.25

289.01
238.63

209.98
111.65

247.25
148.88

286.09
187.73

207.30
63.21

244.21
99.95

282.62
138.31

204.24
16.13

240.79
52.41

278.80
90.28

MUA-PRC004-EN

Performance
Data

TE wheel
capacity

Table PD-68. Total energy wheel (only) heating capacity, MBh


031

040

051

066

cfm
1800
2200
2600
3100
2200
2600
3000
3400
3800
4000
2900
3300
3700
4100
4500
4900
5100
3600
4000
4400
4800
5200
5600
6000
6400
6600

10
107.21
126.10
143.41
162.97
132.46
151.99
170.28
187.37
203.33
210.90
173.61
193.03
211.48
228.98
245.56
261.27
268.81
215.45
234.96
253.67
271.61
288.80
305.26
321.01
336.07
343.35

15
97.24
114.37
130.07
147.81
120.14
137.86
154.44
169.95
184.43
191.29
157.46
175.08
191.81
207.68
222.73
236.98
243.81
195.42
213.11
230.08
246.35
261.94
276.87
291.16
304.82
311.42

20
87.48
102.89
117.01
132.97
108.08
124.02
138.94
152.89
165.91
172.09
141.66
157.51
172.56
186.83
200.37
213.19
219.33
175.80
191.72
206.98
221.62
235.65
249.08
261.93
274.22
280.16

25
77.92
91.65
104.23
118.44
96.27
110.46
123.75
136.18
147.78
153.28
126.17
140.29
153.70
166.41
178.47
189.89
195.36
156.58
170.76
184.36
197.40
209.89
221.85
233.30
244.25
249.54

30
68.55
80.63
91.70
104.21
84.69
97.19
108.88
119.81
130.02
134.86
111.01
123.43
135.22
146.41
157.02
167.06
171.88
137.76
150.24
162.20
173.67
184.66
195.19
205.26
214.89
219.55

winter outdoor dry-bulb, F


35
40
45
59.38
50.39
41.57
69.84
59.26
48.89
79.42
67.40
55.61
90.26
76.59
63.19
73.36
62.25
51.36
84.18
71.43
58.93
94.31
80.02
66.02
103.77
88.06
72.65
112.61
95.56
78.84
116.81
99.12
81.78
96.15
81.59
67.32
106.91
90.72
74.85
117.12
99.39
82.00
126.81
107.61
88.78
136.00
115.40
95.22
144.70
122.79
101.31
148.87
126.33
104.23
119.32
101.25
83.54
130.13
110.42
91.10
140.49
119.21
98.36
150.43
127.65
105.32
159.95
135.72
111.98
169.06
143.46
118.36
177.78
150.86
124.47
186.13
157.94
130.31
190.16
161.36
133.13

50
32.93
38.73
44.05
50.06
40.68
46.68
52.30
57.55
62.45
64.78
53.32
59.29
64.95
70.33
75.42
80.25
82.56
66.18
72.17
77.91
83.42
88.70
93.76
98.60
103.22
105.46

55
24.46
28.77
32.71
37.18
30.22
34.67
38.84
42.74
46.38
48.11
39.60
44.03
48.24
52.23
56.02
59.60
61.32
49.15
53.60
57.87
61.96
65.88
69.63
73.23
76.66
78.32

60
16.15
18.99
21.60
24.55
19.95
22.89
25.65
28.22
30.62
31.76
26.15
29.07
31.85
34.49
36.99
39.35
40.49
32.45
35.39
38.21
40.91
43.50
45.98
48.35
50.62
51.71

65
8.00
9.41
10.70
12.16
9.88
11.34
12.70
13.98
15.17
15.73
12.95
14.40
15.77
17.08
18.32
19.49
20.05
16.07
17.52
18.92
20.26
21.54
22.77
23.94
25.07
25.61

Note: Capacities based on ARI 1060 return air conditions, 70/58F. Outdoor air is assumed to have a relative humidity of 80%. The supply and exhaust airflow are equal.

MUA-PRC004-EN

71

TE wheel
capacity

Performance
Data
Table PD-69. Total energy wheel performance
data
031

040

051

066

cfm
1800
2200
2600
3100
2200
2600
3000
3400
3800
4000
2900
3300
3700
4100
4500
4900
5100
3600
4000
4400
4800
5200
5600
6000
6400
6600

effectiveness
sensible
latent
81.6%
79.2%
78.6%
75.7%
75.6%
72.3%
72.1%
68.4%
82.5%
80.1%
80.1%
77.4%
77.8%
74.8%
75.5%
72.2%
73.3%
69.8%
72.3%
68.6%
82.0%
79.6%
80.1%
77.5%
78.3%
75.4%
76.5%
73.3%
74.8%
71.4%
73.0%
69.5%
72.2%
68.5%
82.0%
79.6%
80.5%
77.8%
79.0%
76.1%
77.5%
74.5%
76.1%
72.9%
74.7%
71.3%
73.3%
69.7%
71.9%
68.2%
71.3%
67.5%

total
80.5%
77.2%
74.1%
70.3%
81.4%
78.8%
76.3%
74.0%
71.6%
70.5%
80.9%
78.9%
76.9%
75.0%
73.1%
71.3%
70.5%
80.8%
79.2%
77.6%
76.1%
74.6%
73.1%
71.6%
70.2%
69.5%

Note: Performance based on ARI 1060 test conditions.

Table PD-70. Total energy wheel temperature rise


unit
size
031

040

051

066

cfm

10

15

1800
2200
2600
3100
2200
2600
3000
3400
3800
4000
2900
3300
3700
4100
4500
4900
5100
3600
4000
4400
4800
5200
5600
6000
6400
6600

48.96
47.11
45.34
43.21
49.49
48.05
46.65
45.30
43.98
43.34
49.21
48.08
46.98
45.90
44.85
43.83
43.32
49.19
48.28
47.39
46.51
45.65
44.81
43.98
43.16
42.76

44.88
43.19
41.56
39.61
45.36
44.05
42.77
41.52
40.32
39.73
45.11
44.07
43.07
42.08
41.12
40.18
39.71
45.09
44.26
43.44
42.64
41.85
41.07
40.31
39.57
39.20

winter outdoor dry-bulb, F


20
25
30
35
40
40.80
39.26
37.78
36.01
41.24
40.04
38.88
37.75
36.65
36.12
41.01
40.07
39.15
38.25
37.38
36.52
36.10
40.99
40.23
39.49
38.76
38.04
37.34
36.65
35.97
35.63

36.72
35.33
34.00
32.41
37.12
36.04
34.99
33.97
32.99
32.50
36.90
36.06
35.24
34.43
33.64
32.87
32.49
36.89
36.21
35.54
34.88
34.24
33.60
32.98
32.37
32.07

32.64
31.41
30.22
28.81
32.99
32.03
31.10
30.20
29.32
28.89
32.80
32.05
31.32
30.60
29.90
29.22
28.88
32.79
32.19
31.59
31.01
30.43
29.87
29.32
28.77
28.51

28.56
27.48
26.45
25.21
28.87
28.03
27.21
26.42
25.66
25.28
28.70
28.05
27.41
26.78
26.16
25.57
25.27
28.70
28.16
27.64
27.13
26.63
26.14
25.65
25.18
24.94

24.48
23.56
22.67
21.61
24.74
24.02
23.33
22.65
21.99
21.67
24.60
24.04
23.49
22.95
22.43
21.91
21.66
24.60
24.14
23.69
23.26
22.83
22.40
21.99
21.58
21.38

45

50

55

60

65

20.40
19.63
18.89
18.00
20.62
20.02
19.44
18.87
18.33
18.06
20.50
20.03
19.58
19.13
18.69
18.26
18.05
20.50
20.12
19.75
19.38
19.02
18.67
18.32
17.98
17.82

16.32
15.70
15.11
14.40
16.50
16.02
15.55
15.10
14.66
14.45
16.40
16.03
15.66
15.30
14.95
14.61
14.44
16.40
16.09
15.80
15.50
15.22
14.94
14.66
14.39
14.25

12.24
11.78
11.33
10.80
12.37
12.01
11.66
11.32
11.00
10.83
12.30
12.02
11.75
11.48
11.21
10.96
10.83
12.30
12.07
11.85
11.63
11.41
11.20
10.99
10.79
10.69

8.16
7.85
7.56
7.20
8.25
8.01
7.78
7.55
7.33
7.22
8.20
8.01
7.83
7.65
7.48
7.30
7.22
8.20
8.05
7.90
7.75
7.61
7.47
7.33
7.19
7.13

4.08
3.93
3.78
3.60
4.12
4.00
3.89
3.77
3.67
3.61
4.10
4.01
3.92
3.83
3.74
3.65
3.61
4.10
4.02
3.95
3.88
3.80
3.73
3.66
3.60
3.56

Note: Temperature rises based on ARI 1060 return air conditions, 70/58F. Outdoor air is assumed to have a relative
humidity of 80%. The supply and exhaust airflow are equal.

72

MUA-PRC004-EN

Performance
Data

electric
heat

Table PD-71. Electric heat temperature rise,F, sizes 031 & 040
unit size

cfm

20

26

32

42

heat input (kW)


56
70

84

100

122

3-stage [33,66,100%]
7-stage [14,27,41,59,68,86,100%]

031

040

1700
1800
1900
2000
2100

37
35
33
31

48
45
43
41
39

59
56
53
50
48

70
66
63

2200
2300
2400
2500
2600

37
36
34
33
31

46
44
42
40
39

60
57
55
53
51

68

2700
2800
2900
3000
3100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000

30

37
36
34
33
31
30

37
36
35
34
32
46
44
42
40
39
37
36
35
34
32
31
30

49
47
46
44
43
60
57
55
53
51
49
47
46
44
43
41
40
39
38
37
36
35
34
33

65
63
61
59
57

68
65
63
61
59
57
55
53
52
50
49
48
46
45
44

69
67
65
63
61
59
58
56
55

70
68
66

Notes:
entries with have temperature rises less than 30F or greater than 70F
low rise = 30 40F
intermediate rise = 40 60F
medium rise = 60 70F

MUA-PRC004-EN

73

Performance
Data

electric
heat

Table PD-72. Electric heat temperature rise, F, sizes 051 & 066
unit size

cfm

20

26

32

42

heat input (kW)


56

70

84

100

122

3-stage [33, 66, 100%]


7-stage [14, 27, 41, 59, 68, 86, 100%]

051

066

2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700

36
35
34
32
31
30

47
46
44
43
41
40
39
38
37
36
35
34
33
32
31
31
30

63
61
59
57
55
53
52
50
49
48
46
45
44
43
42
41
40
39
38
37

69
67
65
63
61
59
58
56
55
54
52
51
50
49
48
47

70
68
66
64
63
61
60
59
57
56

70
68
67

4800
4900
5000
5100
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000

37
36
35
34
33
32
31
31
30

37
36
35
35
49
48
46
45
44
43
42
41
40
39
38
37
37
36
35

46
45
44
43
61
59
58
56
55
54
52
51
50
49
48
47
46
45
44

55
54
53
52

70
68
66
64
63
61
60
59
57
56
55
54
53

66
64
63
62

70
68
67
66
64
63

5100
5200
5300
5400
5500

35
34
33
33
32

43
42
42
41
40

52
51
50
49
48

62
60
59
58
57

70

5600
5700
5800
5900
6000

31
31
30

39
39
38
37
37

47
46
46
45
44

56
55
54
53
52

69
67
66
65
64

6100
6200
6300
6400
6500
6600

36
36
35
34
34
33

43
43
42
41
41
40

52
51
50
49
48
48

63
62
61
60
59
58

Notes:
entries with have temperature rises less than 30F or greater than 70 F
low rise = 30 40F
intermediate rise = 40 60F
medium rise = 60 70F

74

MUA-PRC004-EN

Performance
Data

gas
heat

Table PD-73. Gas heat temperature rise, F, sizes 031 & 040

unit size

031

040

input (MBh)

125

150

200

250

300

350

400

500

output (MBh)

100

120

160

200

240

280

320

400

1700
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
2200
2300
2400
2500
2600

54
51
49
46
44
42
40
38
37
35
34
33
32
31

42
40
38
37
35

65
61
58
55
53
50
48
46
44
43
41
39
38
37
36
50
48
46
44
43

87
82
78
74
70
67
64
61
59
57
55
53
51
49
48
67
64
61
59
57

87*
84*
80*
77*
74*
71*
68*
66*
64*
61*
59*
84*
80*
77*
74*
71*

88*
85*
82*
79*
76*
74*
71*

88*
85*

89*
86*
83*

2700
2800
2900
3000
3100

34
33
32
31

41
39
38
37
36

55
53
51
49
48

68*
66*
64*
61*
59*

82*
79*
76*
74*
71*

89*
86*
83*

3200
3300
3400
3500
3600

35
34
33
32
31

46
45
43
42
41

58*
56*
54*
53*
51*

69*
67*
65*
63*
61*

81*
78*
76*
74*
72*

89*
87*
84*
82*

3700
3800
3900
4000

40
39
38
37

50*
49*
47*
46*

60*
58*
57*
55*

70*
68*
66*
65*

80*
78*
76*
74*

cfm

600

700

800

480
560
640
(dual heaters only)

Notes:
entries with have temperature rises less than 30F or greater than 90F
250/300/350/400 MBh inputs have option for dual or single heaters, except there is no 400 MBh single heater in small cabinet
* = dual (lo-rise) = 40 90F
single lo-rise = 30 75F
single hi-rise = 75 90F

MUA-PRC004-EN

75

Performance
Data

gas
heat

Table PD-74. Gas heat temperature rise F, sizes 051 & 066
input (MBh)
output (MBh)
unit size

051

066

125
100

150
120

200
160

250
200

300
240

350
280

400
320

500
400

cfm
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700

33
32
31

39
38
37
36
35
34
33
32
31

3800
3900
4000
4100
4200

4300
4400
4500
4600
4700

600
480

700
560

800
640

53
51
49
48
46
45
43
42
41
40

64*
61*
59*
58*
56*
54*
53*
51*
50*

66*
76*
74*
71*
69*
67*
65*
63*
61*
60*

79*
89*
86*
83*
81*
78*
76*
74*
72*
70*

89*
87*
84*
82*
80*

39
38
37
36
35

49*
47*
46*
45*
44*

58*
57*
55*
54*
53*

68*
66*
65*
63*
61*

78*
76*
74*
72*
70*

90*
88*

34
34
33
32
31

43*
42*
41*
40*
39

51*
50*
49*
48*
47*

60*
59*
57*
56*
55*

69*
67*
66*
64*
63*

86*
84*
82*
80*
78*

4800
4900
5000
5100
3600
3700
3800
3900
4000

31

31
30

41
40
39
38
37

38
38
37
36
51*
50*
49*
47*
46*

46*
45*
44*
43*
61*
60*
58*
57*
55*

54*
53*
52*
51*
72*
70*
68*
66*
65*

61*
60*
59*
58*
82*
80*
78*
76*
74*

77*
75*
74*
72*

88*
87*

4100
4200
4300
4400
4500

36
35
34
34
33

45*
44*
43*
42*
41*

54*
53*
51*
50*
49*

63*
61*
60*
59*
57*

72*
70*
69*
67*
66*

90*
88*
86*
84*
82*

4600
4700
4800
4900
5000

32
31
31
30

40*
39
38
38
37

48*
47*
46*
45*
44*

56*
55*
54*
53*
52*

64*
63*
61*
60*
59*

80*
78*
77*
75*
74*

88*

5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
6400
6500
6600

36
35
35
34
34
33
32
32
31
31
30

43*
43*
42*
41*
40*
39
39
38
37
37
36
36
35
35
34
34

51*
50*
49*
48*
47*
46*
45*
44*
44*
43*
42*
42*
41*
40*
40*
39

58*
57*
56*
55*
54*
53*
52*
51*
50*
49*
48*
48*
47*
46*
45*
45*

72*
71*
70*
68*
67*
66*
65*
64*
62*
61*
60*
59*
59*
58*
57*
56*

87*
85*
83*
82*
80*
79*
78*
76*
75*
74*
73*
71*
70*
69*
68*
67*

89*
87*
86*
85*
83*
82*
81*
79*
78*

89*

(dual heaters only)

Notes:
entries with have temperature rises less than 30F or greater than 90F
250/300/350/400 MBh inputs have option for dual or single heaters, except there is no 400 MBh single heater in small cabinet
* = dual (lo-rise) = 40 90F
single lo-rise = 30 75F
single hi-rise = 75 90F

76

MUA-PRC004-EN

Controls

Packaged Fresh Air Unit


with

The Intelligent Air-Cooled Chillers

Controls

We have designed the Trane Packaged


Fresh Air unit with the latest control
technology. Modular DDC controls with
human interface (HI) panel make
Packaged Fresh Air units flexible and
easy to operate.
Controls are Trane-designed to work
with Trane equipment for optimum
efficiency. The factory installs and
commissions each control component
to ensure simple and reliable operation.
Furthermore, the DDC controls modular
design allows greater application
flexibility using up to twelve different
modules, dependent upon unit options.
You can order exactly what the job
requires as options, instead of one large
control package. And since unit features
are distributed among multiple printed
circuit boards, field replacement is easy.
Depending on unit options, IntelliPak
units can operate as:
1) stand-alone
2) interface with Tranes Tracer Summit building management system
3) interface with a generic (non-Trane)
building management system (via
LCI-I using LonTalk DAC profile).
4) interface with a generic hard-wired
(non-Trane) building management
system via analog input and binary
output interface board (GBAS)
Available Input and Output Points Base
Unit (RTM module on all units)
Binary inputs
emergency stop
external auto/stop
unoccupied/occupied
dirty filter
exhaust fan air proving
Binary outputs
unoccupied mode indicator
alarm
exhaust fan enable
Analog input
OA damper minimum position heating
option
analog output (hydronic heat interface)
LonTalk communication interface
(LCI-I ) option
MUA-PRC004-EN

Binary input
enthalpy enable unoccupied economizer
Binary outputs
compressor on/off status
ventilation status
heat status
Analog outputs
supply air pressure
supply air temperature
suction temperature of each circuit
zone temperature
supply air temperature reset signal
morning warmup sensor temperature
entering air temperature
Analog inputs
cooling and heating setpoints
VAV discharge air temperature
setpoints
supply air pressure setpoint
cooling and heating enable/disable
unoccupied economizer enable/disable
economizer minimum position
unit priority shutdown
Generic BAS Option (GBAS)
Binary inputs
demand limit contacts
Binary outputs
dirty filter relay
refrigeration fail relay
heat fail relay
supply fan fail relay
active diagnostics
Analog inputs
occupied zone cooling setpoint
occupied zone heating setpoint
unoccupied zone cooling setpoint
unoccupied zone heating setpoint or
minimum outside air flow setpoint
supply air cooling setpoint
supply air heating setpoint
supply air static pressure setpoint
Zone Humidity Options (ECEM)
Analog inputs
zone relative humidity
Traq Damper Option (VCM)
Analog inputs
ventilation airflow

Ventilation Override Module (VOM)


Option
Binary inputs
VOM mode A, unit off
VOM mode B, pressurize
VOM mode C, exhaust
VOM mode D, purge
VOM mode E, purge
Binary output
V.O. relay
Standard IntelliPak Unit Control
Features
All set-up parameters are preset from
the factory, requiring less startup time
during installation.
The human interface panel is easy to
read and requires less time for building
maintenance personnel to learn to
interact with the unit. It features a clear
language display (in English, Spanish, or
French) that shows all of the Packaged
Fresh Air unit control parameters,
including system on/off, demand limiting
type, night setback setpoints, and many
other setpoints. All adjustments are
done through the human interface
keypad. Also, the human interface panel
allows you to monitor diagnostic points
such as sensor failures, supply airflow
loss, and inoperative refrigerant circuit.
No special tools are required for
servicing the unit. Diagnostics are held
in memory, even during power loss.
This allows the operator/servicer to
diagnose the failure root cause.
IntelliPak Unit Features
Unit mounted human interface panel
with a two line x 40 character display
in English, Spanish, or French language and a 16-function keypad that
includes CUSTOM, DIAGNOSTICS,
and SERVICE TEST MODE menu keys
Frostat coil frost protection on all
units
Supply air or zone dehumidification
control
Supply air or zone temperature control
Efficient condenser hot gas reheat with
modulating capacity (optional)
Morning warmup operation
unoccupied airside economizer
77

Controls
(optional) when unit has return air
damper option
supply airflow proving
supply air tempering control with
heating option
mappable sensors and setpoint
sources
occupied/unoccupied switching
timed override activation
Human Interface Panel (HI)
The human interface panel provides a
16-button keypad for monitoring,
setting, editing and controlling. The HI
panel is mounted in the units main
control panel, accessible through the
units control panel door.
The optional remote-mount version of
the human interface (RHI) panel has all
the functions of the unit-mounted
version, except for the service mode. To
use a RHI, the unit must be equipped
with the remote HI interface option,
which includes an interprocessor
communications bridge (IPCB). The RHI
can be located up to 1,000 feet (304.8
m) from the unit. A single RHI can be
used to monitor and control up to four
fresh air units, that have each been
supplied with a RHI interface option
(IPCB module).
The main menus of the human interface
panels are:
STATUS monitors temperature,
pressure, humidity, setpoints, and
input and output status.
CUSTOM key allows the user to
customize a status report - consisting
of up to four screens of the data
available in the main Status menu.
SETPOINT allows the user to edit all
factory preset default setpoints.
DIAGNOSTICS allows the user to
review active and historical lists of
diagnostic conditions. A total of 49
different diagnostics can be read at
the human interface (HI) panel and the
last 20 diagnostics can be held in an
active history buffer log at the HI
panel.
SETUP allows the user to edit control
parameters, sensor selections,
setpoint source selections, output
definitions, and numerous other points
in this menu. All points have factory
preset values to keep unnecessary
editing to a minimum.
CONFIGURATION allows changing of
factory-preset unit configuration
78

Figure C-1. The human interface panel on the Trane Packaged Fresh Air unit

information. This information can be


edited only if certain options are fieldinstalled or deleted from the unit. For
example, if a communication interface
(LCI-I) module or ventilation override
module (VOM) were field-installed, the
unit configuration will require editing
to reflect those options for proper unit
operation.
SERVICE allows servicing or troubleshooting the unit by selecting component control outputs such as compressors, fans, damper position, etc. This
menu is accessible only at the unitmounted human interface panel.

Supply Air
Dehumidification Unit
1
Occupied Sequence
During occupied mode, the primary
function of the unit is to provide ventilation air to the space. Upon entering the
occupied mode, the outside air damper
is opened and the supply air fan will
start.
Drying Mode
The unit will enter the drying mode
when the OA dew point exceeds the SA
drying setpoint (dew point). The SA
drying setpoint can be reset down

based on OA dew point conditions.


Drying functions will have priority over
cooling mode. Upon entering drying
mode, the first compressor will stage
up. While in drying mode, the first
compressor stage will always remain
active. This allows condenser reheat
(when ordered) to be available as
required during drying operation.
Additional compressors will be sequenced to match unit capacity to the
latent load.
Reheat will be controlled to meet a
supply air reheat setpoint that is a
minimum of 3F greater than the supply
air drying setpoint. The supply air reheat
setpoint can be reset up based on OA or
zone temperature conditions. When
available, condenser reheat will be
cycled to achieve a time-weighted
average of the reheat setpoint. If
primary heat reheat is user-enabled,
additional reheat capacity will be made
available to match sensible load.
Cooling Sequence
When not in drying mode, the unit will
stage cooling capacity to maintain the
supply air cooling setpoint. The supply
air cooling setpoint can be reset down
based on HI selectable parameters (OA
sensor, zone sensor if installed).

MUA-PRC004-EN

Controls
Heating Sequence
When not in drying mode, the unit will
stage heating capacity to maintain the
supply air heating setpoint. The supply
air heating setpoint can be reset up
based on HI selectable parameters (OA
sensor, zone sensor if installed). The
supply air heating setpoint must be
lower than the supply air cooling
setpoint.

additional reheat capacity will be made


available to match sensible load.

Heating Sequence
When not in drying mode, the unit will
stage heating capacity to maintain the
supply air heating setpoint. The supply
air heating setpoint can be reset up
based on HI selectable parameters (OA
sensor, zone sensor if installed). The
supply air heating setpoint must be
lower than the supply air cooling
setpoint.

Unoccupied Sequence
In unoccupied mode, the fan is stopped
and the OA damper is closed.

Supply Air
Dehumidification with Zone
RH Reference Unit
1
Occupied Sequence
During occupied mode, the primary
function of the unit is to provide ventilation air to the space. Upon entering the
occupied mode, the outside air damper
is opened and the supply air fan will
start.
Drying Mode
The unit will enter the drying mode
when the OA dew point exceeds the SA
drying setpoint (dew point). The SA
drying setpoint can be reset down
based on zone relative humidity
conditions or OA dew point conditions.
Drying functions will have priority over
cooling mode. Upon entering drying
mode, the first compressor will stage
up. While in drying mode, the first
compressor stage will always remain
active. This allows condenser reheat
(when ordered) to be available as
required during drying operation.
Additional compressors will be sequenced to match unit capacity to the
latent load.
Reheat will be controlled to meet a
supply air reheat setpoint that is a
minimum of 3F greater than the supply
air drying setpoint. The supply air reheat
setpoint can be reset up based on OA or
zone temperature conditions. When
available, condenser reheat will be
cycled to achieve a time-weighted
average of the reheat setpoint. If
primary heat reheat is user-enabled,
MUA-PRC004-EN

Cooling Sequence
When not in drying mode, the unit will
stage cooling capacity to maintain the
supply air cooling setpoint. The supply
air cooling setpoint can be reset down
based on HI selectable parameters (OA
sensor, Zone sensor if installed).

2
Unoccupied Sequence
When the return air damper option is
installed and a request for unoccupied
operation is received, the fan, cooling,
and heating capacity will be cycled in a
recirculating mode to maintain zone
requirements. See below for a detailed
description of the operating modes.
If no return air damper is installed, the
fan is stopped and the OA damper is
closed in unoccupied mode.
Drying Mode
During unoccupied mode (with return
air damper option installed), the unit will
enter the drying mode when the zone
RH exceeds the unoccupied zone RH
setpoint. In the drying mode, capacity
will be cycled to maintain the supply air
drying (dew point) setpoint. The SA
drying setpoint can be reset down
based on zone relative humidity
conditions and will be based on the
unoccupied zone RH setpoint.
Supply air reheat functions will be active
to maintain the supply air reheat
setpoint. Supply air reheat reset
functions will be active and reset based
on unoccupied zone setpoints. Exhaust
fan operation control will be cycled off
during unoccupied modes unless
unoccupied economizer operations are
active.
Cooling Mode
During unoccupied cooling mode, the
fan, economizer and mechanical cooling

Sequence of
Operation
cycle to control zone temperature.
Economizer functions will be enabled
when the difference in the enthalpy of
the OA and zone is adequate. Mechanical cooling will supplement economizer
capacity as required.
Heating Mode
During unoccupied heating mode, fan
and heating capacity are cycled to
maintain the unoccupied zone heating
setpoint.

Zone Dehumidification Unit


Sequence of Operation
1
Occupied Sequence
During occupied mode, the primary
function of the unit is to provide ventilation air to the space. Upon entering the
occupied mode, the outside air damper
is opened and the supply air fan will
start.
Drying Mode
The unit enters the drying mode when
the zone relative humidity exceeds the
zone relative humidity setpoint (%RH).
In the drying mode, the capacity is
controlled to meet the default supply air
drying setpoint (dewpoint). The SA
drying setpoint can be reset down
based on zone relative humidity
conditions. Drying functions have
priority over cooling mode. Upon
entering drying mode, the first compressor stages up. While in drying mode, the
first compressor stage always remains
active. This allows condenser reheat
option (if ordered) to be available as
required during the drying operation.
Additional compressors will sequence
to match unit capacity to the latent load.
Reheat is controlled to meet a supply air
reheat setpoint that is a minimum of 3F
greater than the supply air drying
setpoint. The supply air reheat setpoint
can be reset up based on OA or zone
temperature conditions. When available, condenser reheat will cycle to
achieve a time-weighted average of the
reheat setpoint. If primary heat reheat is
user-enabled, additional reheat capacity
is made available to match the sensible
load.

79

Controls
Drying mode stops when the zone
relative humidity falls below the
operator adjustable setpoint for leaving
drying mode.

Heating Mode
During unoccupied heating mode, fan
and heating capacity cycle to maintain
the unoccupied zone heating setpoint.

Cooling Sequence
When not in drying mode, the unit
stages cooling capacity to maintain the
supply air cooling setpoint. The supply
air cooling setpoint can be reset down
based on HI selectable parameters (OA
sensor, zone sensor if installed).

Zone Dehumidification with


Outside Air RH Reference
Unit

Heating Sequence
When not in drying mode, the unit will
stage heating capacity to maintain the
supply air heating setpoint. The supply
air heating setpoint can be reset up
based on HI selectable parameters (OA
sensor, zone sensor if installed). The
supply air heating setpoint must be
lower than the supply air cooling
setpoint.
2
Unoccupied Sequence
In unoccupied mode, the fan is stopped
and the OA damper is closed.
Drying Mode
During unoccupied mode (with return
air damper option installed), the unit
enters the drying mode when the zone
RH exceeds the unoccupied zone RH
setpoint. In the drying mode, capacity
cycles to maintain the supply air drying
(dew point) setpoint. The SA drying
setpoint can be reset down based on
zone relative humidity conditions and
will be based on the unoccupied zone
RH setpoint.
Supply air reheat functions are active to
maintain the supply air reheat setpoint.
Supply air reheat reset functions are
active and reset based on unoccupied
zone setpoints. Exhaust fan operation
control cycles off during unoccupied
modes unless unoccupied economizer
operations are active.
Cooling Mode
During unoccupied cooling mode, the
fan, economizer, and mechanical cooling
cycle to control zone temperature.
Economizer functions enable when the
difference in the enthalpy of the OA and
zone is adequate. Mechanical cooling
supplements economizer capacity as
required.

80

1
Occupied Sequence
During occupied mode, the primary
function of the unit is to provide ventilation air to the space. Upon entering the
occupied mode, the outside air damper
opens and the supply air fan starts.
Drying Mode
The unit enters the drying mode when
the zone relatiave humidity exceeds the
zone relative humidity setpoint (%RH).
In the drying mode, capacity is controlled to meet the default supply air
drying setpoint (dew point). The SA
drying setpoint can be reset down
based on zone relative humidity
conditions or OA dew point conditions.
Drying functions will have priority over
cooling mode. Upon entering drying
mode, the first compressor stages up.
While in drying mode, the first compressor stage always remains active. This
allows condenser reheat (when
ordered) to be available as required
during drying operation. Additional
compressors will sequence to match
unit capacity to the latent load.
Reheat is controlled to meet a supply air
reheat setpoint that is a minimum of 3F
greater than the supply air drying
setpoint. The supply air reheat setpoint
can be reset up based on OA or zone
temperature conditions. When available, condenser reheat will cycle to
achieve a time-weighted average of the
reheat setpoint. If primary heat reheat is
user-enabled, additional reheat capacity
is made available to match sensible
load.
Drying mode stops when the zone
relative humidity falls below the
operator-adjustable setpoint for leaving
drying mode.

Sequence of
Operation
Cooling Sequence
When not in drying mode, the unit
stages cooling capacity to maintain the
supply air cooling setpoint. The supply
air cooling setpoint can be reset down
based on HI selectable parameters (OA
sensor, zone sensor if installed).
Heating Sequence
When not in drying mode, the unit
stages heating capacity to maintain the
supply air heating setpoint. The supply
air heating setpoint can be reset up
based on HI selectable parameters (OA
sensor, zone sensor if installed). The
supply air heating setpoint must be
lower than the supply air cooling
setpoint.
2
Unoccupied Sequence
When the return air damper option is
installed and a request for unoccupied
operation is received, the fan and
cooling/heating capacity cycle in a
recirculating mode to maintain zone
requirements. See below for a detailed
description of the operating modes.
If no return air damper is installed, the
fan stops and the OA damper closes in
unoccupied mode.
Drying Mode
During unoccupied mode (with return
air damper option installed), the unit
enters the drying mode when the zone
RH exceeds the unoccupied zone RH
setpoint. In the drying mode, capacity
cycles to maintain the supply air drying
(dew point) setpoint. The SA drying
setpoint can be reset down based on
zone relative humidity conditions and
will be based on the unoccupied zone
RH setpoint.
Supply air reheat functions are active to
maintain the supply air reheat setpoint.
Supply air reheat reset functions are
active and reset based on unoccupied
zone setpoints. Exhaust fan operation
control will cycle off during unoccupied
modes unless unoccupied economizer
operations are active.
Cooling Mode
During unoccupied cooling mode, the
fan, economizer, and mechanical cooling
cycle to control zone temperature.
Economizer functions will enable when
the difference in the enthalpy of the OA
MUA-PRC004-EN

and zone is adequate. Mechanical


cooling supplements economizer
capacity as required.
Heating Mode
During unoccupied heating mode, fan
and heating capacity cycle to maintain
the unoccupied zone heating setpoint.

Supply Air Temp Control


(No Dehumidification) Unit
1
Occupied Sequence
During occupied mode, the primary
function of the unit is to provide ventilation air to the space. Upon entering the
occupied mode, the outside air damper
opens and the supply air fan starts.
Cooling Sequence
The unit stages cooling capacity to
maintain the supply air cooling setpoint.
The supply air cooling setpoint can be
reset down based on HI selectable
parameters (OA sensor, zone sensor if
installed).
Heating Sequence
The unit stages heating capacity to
maintain the supply air heating setpoint.
The supply air heating setpoint can be
reset up based on HI selectable parameters (OA sensor, zone sensor if
installed). The supply air heating
setpoint must be lower than the supply
air cooling setpoint.
2
Unoccupied Sequence
In unoccupied mode, the fan stops and
the OA damper closes.

Zone Temp Control (No


Dehumidification) Unit
1
Occupied Sequence
During occupied mode, the primary
function of the unit is to provide ventilation air to the space. Upon entering the
occupied mode, the outside air damper
opens and the supply air fan starts.
Cooling Sequence
The unit stages cooling capacity to
maintain the supply air cooling setpoint.
MUA-PRC004-EN

Controls

Sequence of
Operation

The supply air cooling setpoint can be


reset down based on HI selectable
parameters (OA sensor, zone sensor if
installed).

switches to occupied mode. Cooling will


suspend until building load conditions
exceed the MWU setpoint of 3F (1.7C),
which is field adjustable.

Heating Sequence
The unit stages heating capacity to
maintain the supply air heating setpoint.
The supply air heating setpoint can be
reset up based on HI selectable parameters (OA sensor, zone sensor if
installed). The supply air heating
setpoint must be lower than the supply
air cooling setpoint.

Ventilation Override (VOM) Option


The user can customize up to five
different override sequences for
purposes of ventilation override control.
If more than one VOM sequence is
requested, the sequence with the
highest priority initiates first. Priority
schedule is that sequence A (unit off)
is first, with sequence E (purge
sequence) last.

2
Unoccupied Sequence
In unoccupied mode, the fan stops and
the OA damper closes.

Control Sequences of
Operation
Morning Warmup
This feature is available on all types of
factory-installed heat units and on units
with no heat. This function may still be
selected to support systems with heat
sources not provided by the fresh air
unit. At the conclusion of unoccupied
mode, the selected zone is heated to the
user-defined morning warmup setpoint.
The unit is then released to occupied
mode. There are two types of morning
warmup: full capacity or cycling
capacity.

UNIT OFF sequence A


When complete system shut down is
required, the following sequence is
used.
supply fan off
outside air dampers closed
heat all stages off, modulating heat
output at 0 vdc
occupied/unoccupied output
deenergized
VO relay energized
exhaust fan (field-installed) off
exhaust damper (field-installed)
closed

Full capacity morning warmup (MWU)


Full capacity morning warmup uses full
heating capacity to heat the zone as
quickly as possible. Full heating capacity
is provided until the morning warmup
setpoint is met. At this point, the unit is
released to daytime mode.

PRESSURIZE sequence B
This override sequence is for use when
a positively pressured space is desired
instead of a negatively pressurized
space.
supply fan on
outside air dampers open
heat all stages off, modulating heat
output at 0 vdc
occupied/ unoccupied output energized
VO relay energized
exhaust fan (field-installed) Off
exhaust damper (field-installed)
closed

Cycling capacity morning warmup


(MWU)
Cycling capacity morning warmup
provides gradual heating to overcome
building sink as the zone is heated.
Normal zone temperature control with
varying capacity raises the zone
temperature to the MWU zone temperature setpoint. Cycling capacity
MWU will operate until MWU setpoint is
reached or for 60 minutes. Then the unit

EXHAUST sequence C
With the buildings exhaust fans running
and the units supply fan off, the conditioned space becomes negatively
pressurized. This is desirable for
clearing the area of smoke when
necessary (i.e., from an extinguished
fire, to keep smoke out of areas that
were not damaged).
supply fan off
outside air dampers closed

81

Controls
heat all stages off, modulating heat
output at 0 vdc
occupied/unoccupied output
deenergized
VO relay energized
exhaust fan (field-installed) on
exhaust damper (field-installed) open
PURGE sequence D
This sequence is for purging air out of a
building before coming out of unoccupied mode of operation. Also, it can
purge smoke or stale air.
supply fan on
outside air damper open
heat: all stages off, modulating heat
output at 0 vdc
occupied/unoccupied output energized
VO relay energized
exhaust fan (field-installed) on
exhaust damper (field-installed) open
PURGE sequence E
This sequence uses supply air control
for smoke control.
supply fan on
outside air dampers open
heat: all stages off, modulating heat
output at 0 vdc
occupied/unoccupied output energized
VO relay energized
exhaust fan (field-installed) on
exhaust damper (field-installed) open
Note: Each system (cooling, exhaust,
supply air, etc.) within the unit can be
redefined in the field for each of the five
sequences, if required. Also the definitions of any or all of the five sequences
may be locked into the software by
simple key strokes at the human
interface panel.
Generic Building Automation System
Module (GBAS) Option
The generic building automation system
module (GBAS) provides broad control
capabilities for building automation
systems other than a Tracer Summit
system. Use a field provided potentiometer or a 0-5 vdc signal to any of the
GBAS inputs, to access the following
inputs and outputs listed in the paragraphs below.

82

GBAS analog inputs


These four analog inputs can be
configured to any of the following:
(1) occupied zone cooling
(2) unoccupied zone cooling
(3) uccupied zone heating
(4) unoccupied zone heating
(5) SA cooling setpoint
(6) SA heating setpoint
(7) space static pressure setpoint
(8) SA static pressure setpoint
GBAS binary outputs
Each of the five (5) relay outputs can be
mapped to any/all of the available
diagnostics.
Demand limiting binary input
This function is operational on units with
a GBAS and reduces electrical consumption at peak load times. There are
two types of demand limiting, 50% and
100%. When demand limiting is needed,
mechanical cooling and heating
operation are either partially (50%), or
completely disabled (100%) to save
energy. The demand limit definition is
user definable at the human interface
panel. Demand limit binary input
accepts a field supplied switch or
contact closure. When the need for
demand limiting discontinues, the units
cooling/heating functions will (again)
fully enable.
Evaporator Coil Frost Protection
Frostat
A temperature sensor on the evaporator determines if the coil is getting close
to a freezing condition. Mechanical
cooling capacity is shed as necessary to
prevent icing.
The Frostat system eliminates the
need for hot gas bypass and adds a
suction line surface temperature sensor
mounted near the TXV bulb location to
shut off cooling when coil frosting
conditions occur. The supply fan does
not shut off and will de-ice the coil.
Timers prevent the compressors from
rapid cycling.

Sequence of
Operation
Occupied/Unoccupied Switching
There are four ways to switch occupied/
unoccupied:
(1) programmable night setback sensor
(2) field-supplied contact closure
(hardwired binary input to RTM)
(3) Tracer Summit or other BAS (via LCI
with LonTalk DAC profile)
(4) factory-mounted time clock
Field supplied occupied/unoccupied
input on the RTM
This input accepts a field supplied switch
or contacts closure such as a time clock.
Tracer system
The Tracer system can control the
occupied/unoccupied status of the fresh
air unit.
Factory mounted time cock
A time clock can control the
occupied/unoccupied status of the
fresh air unit.
Timed Override Activation - ICS
This function is operational whenever
the units RTM module board is used as
the zone temperature sensor source,
which can be set at the human interface
panel. Initiate this function by pressing
the override button on the zone sensor,
to switch the unit to the occupied mode.
Unit operation (occupied mode) during
timed override will terminate by a signal
from Tracer.
Timed Override Activation - Non-ICS
This function is active whenever the
user selects the units RTM module
board as the zone temperature source
(can be set at the human interface
panel). Initiate this function by pressing
the override button on the zone sensor,
which will switch the unit to the occupied
mode. Automatic cancellation of the
timed override mode occurs after three
hours of operation.
Low Ambient Compressor Lockout
This function will lock out the compressor if the outdoor air temperature is
below the low ambient compressor
lock-out temperature setpoint when
using a field-installed outside air sensor.
This setpoint is adjustable at the human
interface panel. Compressors will lock

MUA-PRC004-EN

Controls
out when outdoor air temperature falls
below that selected temperature and
will start again when the temperature
rises 5F above the setpoint.
Comparative Enthalpy Control of
Unoccupied Economizer Operation
An optional comparative enthalpy
system controls the economizer
operation and measures the temperature and humidity of both return air and
outside air to determine which source
has lower enthalpy. This system allows
true comparison of outdoor air and
return air enthalpy by measurement of
outdoor and return air temperature and
humidity. The comparative enthalpy
option should always be ordered with a
return air damper.
Note: If the unit does not have comparative enthalpy, the Packaged Fresh Air
unit compares outdoor air enthalpy with
a fixed reference enthalpy, set through
the human interface panel. If ordering
the reference enthalpy option, you
should also order a return air damper.
Also, either supply air dehumidification
with zone RH reference or zone dehumidification with OA RH reference must
be ordered to utilize either comparative
enthalpy or reference enthalpy control.
Emergency Stop Input
A binary input is provided on the units
RTM module board for installation of a
field-provided switch or contacts to
immediately shutdown all unit functions.
Total Energy Wheel with Occupancy
Control
The optional total energy wheel
recovers energy from the exhaust
airstream and preconditions the
outdoor air. The total energy wheel
enables when the unit is in occupied

MUA-PRC004-EN

Sequence of
Operation
mode and the exhaust fan is running.
The wheel disables during unoccupied
mode or any time that the exhaust fan is
not running. This includes the unoccupied economizer mode when the wheel
disables, but the exhaust fan enables.
The wheel also disables via a factoryinstalled thermostat at any time a frost
condition occurs (default setpoint 12F).
This frost protection thermostat utilizes
a setpoint range of -30 to 100F.
Total Energy Wheel with Dry-Bulb
Control
The optional total energy wheel
recovers energy from the exhaust
airstream and preconditions the
outdoor air. The total energy wheel
enables when all of the following are
true:
unit is in occupied mode
exhaust fan is enabled
outside air temperature is above the
upper limit setpoint (default setpoint
80F) or below the lower limit setpoint
(default setpoint 45F)
outside air temperature is above the
frost protection setpoint (default
setpoint 12F)
Always set the upper limit setpoint to
the anticipated return air dry-bulb
temperature. Set the lower limit
setpoint to 10F less than the unit supply
air dry-bulb setpoint. The wheel will
disable during unoccupied mode or
when the exhaust fan is not running.
This includes the unoccupied economizer mode when the wheel will
disable, but the exhaust fan will enable.
The wheel also disables via a factory
installed thermostat when a frost
condition occurs. This frost protection
thermostat utilizes a setpoint range of
-30 to 100F.

83

Controls
Standard With All Units

Optional Zone Sensors

Zone temperature sensor, accessory


model number digit 16 = A, BAYSENS017

Dual setpoint, manual/automatic


changeover sensor, accessory model
number digit 20 = A

This wall-mounted zone sensor ships


with every Packaged Fresh Air unit.
Additional sensors are also available for
order using the accessory model
number. This zone sensor includes an
internal thermistor and should be
mounted in the zone. This sensor is
available for use with all zone sensor
options to provide remote sensing
capabilities.

Standard with All Units if Supply Air


Dehumidification w/Zone Reference or
Zone Dehumidification

This zone sensor module is for use with


cooling/heating applications. It provides
the following features and system
control functions:

Zone Sensor
Options
System control switch to select AUTO
mode for automatic selection of
heating or cooling as required, or OFF
to turn the system off.
Dual temperature setpoint levers for
setting cooling (blue lever) or heating
(red lever).
Thermometer to indicate temperature
in the zone.
Function status indicator lights:
SYS ON glows continuously during
normal operation, or blinks if system is
in test mode.
COOL glows continuously during cooling
cycles or blinks to indicate a cooling
system failure.
HEAT glows continuously during heating
cycles or blinks to indicate a heating
system failure.
SERVICE blinks or glows to indicate a
problem. These signals vary depending on the particular equipment used.

System control switch (auto/off):


Allows you to automatically select
heating or cooling as required, or turn
the system off.
Dual temperature setpoint levers allow
you to set different cooling (blue lever)
and heating setpoints (red lever).
Thermometer to indicate temperature
in the zone.

Carbon dioxide zone sensor, accessory


model number digit 23 = A

This zone sensor is for use with Packaged Fresh Air units to monitor CO2
levels in the space.

Zone relative humidity sensor

This wall-mounted zone sensor ships


with every Packaged Fresh Air unit
when the system control options above
are ordered. Additional sensors are also
available for order using the accessory
model number and ordering the space
relative humidity kit.
84

Dual setpoint, manual/automatic


changeover sensor with system function
lights, accessory model number
digit 21 = A

This zone sensor is for use with cooling/


heating applications. It provides the
following features and system control
functions:
MUA-PRC004-EN

Controls

Zone Sensor
Options

Integrated Comfort
Systems Sensors for FAU
Applications

MUA-PRC004-EN

Zone temperature sensor w/timed


override buttons and local setpoint
adjustment, accessory model number
digit 18 = A, BAYSENS014

Zone temperature sensor w/timed


override buttons, accessory model
number digit 17 = A, BAYSENS013

This zone sensor is for use with cooling/


heating ICS. It provides the following
features and system control functions:
Remote temperature sensing in the
zone
A timed override button to move an
Integrated Comfort System or a
building management system from
unoccupied to occupied mode.
Setpoint thumbwheel for local setpoint
adjustment
Cancel button to cancel the unoccupied
override command.

This zone sensor is for use with cooling/


heating Integrated Comfort Systems
(ICS). It provides the following features
and system control functions:
Remote temperature sensing in the
zone
A timed override button to move an
ICS or building management system
from it unoccupied to occupied mode.
Cancel button to cancel the unoccupied
override command.

85

Electrical
Data
Power Wire Sizing and
Protection Device
Equations
Each type of unit has its own set of
calculations for MCA (minimum circuit
ampacity) and MOP (maximum
overcurrent protection. For units with
multiple modes of operation, you must
consider each individual field-wired
hazardous voltage circuit. Use the load
that provides the highest value in the
applicable circuit. To correctly size the
units electrical service wiring, read the
load definitions that follow and then find
the appropriate set of calculations
based on your unit type.
Load Definitions
Load 1 = current of the largest motor
(compressor or fan motor)
Load 2 = sum of the currents of all
remaining motors
Load 3 = current of electric heaters
Load 4 = control power transformer
= any other load rated at one amp or
more (gas heat, factory-wired
convenience outlet)
Set #1: Cooling Only Units and Cooling
with Gas Heat, All Single Source Power
MCA = (1.25 x load 1) + load 2 + load 4
MOP = (2.25 x load 1) + load 2 + load 4
Select an overcurrent protective device
rating equal to the MOP value. If the
MOP value does not equal a standard
device size as listed in NEC 240-6, select
the next lower standard device rating. If
the selected MOP is less than the MCA,
then reselect the lowest standard
maximum overcurrent protective
device size that is equal to or larger than
the MCA, provided the reselected
device size does not exceed 800 amps.
Disconnect Switch Sizing (DSS) if field
provided and installed
If the unit has a factory-installed, nonfused disconnect switch, this sizing
equation is not necessary. If the disconnect is field-provided and installed, use
the following equation to determine its
rating:
DSS = 1.15 x (load 1 + load 2 + load 4)
Select a disconnect switch (DSS) size
equal to or larger than the DSS value
calculated.
86

Set #2: Units with Electric Heat, Single


Source Power, Non-Concurrent Load
To arrive at the correct MCA and MOP
values, you must perform two sets of
calculations: one for cooling only (set #1)
and one for electric heat only (set #2).
Calculate the MCA and MOP values as if
the unit were in the cooling mode (use
the equations given in set #1). Then
repeat the calculations for MCA and
MOP for the unit in the heating mode
using set #2. When determining loads,
keep in mind that the compressors and
condenser fans do not run while the unit
is in the heating mode.
For units using heaters:
less than 50 kW, use the formula,
MCA = 1.25 x (load 1 + load 2 + load 4)
+ (1.25 x load 3)
equal to or greater than 50 kW, use
the formula, MCA = 1.25 x (load 1 +
load 2 + load 4) + load 3
Select the nameplate MCA value that is
the larger of the cooling (set #1) or the
heating mode MCA calculated above.
MOP = (2.25 x load 1) + load 2 + load 3 +
load 4
Select an overcurrent protective device
rating equal to the MOP value. If the
MOP value does not equal a standard
device size as listed in NEC 240-6, select
the next lower standard device rating. If
the next lower standard rating is less
than 125% of the current rating of the
electric heater load, select the next
higher standard device rating. If the
selected MOP is less than the MCA, then
reselect the lowest standard device size
which is equal to or larger than the
MCA, provided the reselected device
size does not exceed 800 amps.
Select the MOP value that is the larger
of the cooling (set #1) mode MOP value
or the heating MOP value calculated
above.
Disconnect Switch Sizing (DSS) if field
provided and installed
If the unit is ordered with a factoryinstalled non-fused disconnect switch,
this sizing equation is not necessary. If
the disconnect is to be field-provided
and installed, use the following equation
to determine its rating:
DSS = 1.15 x (load 1 + load 2 + load 3 +
load 4)

Select the DSS value that is the larger of


the cooling (set #1) mode DSS or the
heating mode DSS value calculated
above. Select a disconnect switch size
equal to or greater than the DSS value
calculated.
Set #3: Units with Electric Heat, Single
Source Power, Concurrent Load
Concurrent load = 2 compressors and
first stage electric heat
Primary Heat Reheat Selection
You may enable primary heat reheat to
take advantage of the primary heat
source as supplemental reheat for the
condenser reheat. Although in most
cases, the MCA and MOP values are
unaffected by the concurrent loads of
compressors, condenser fans, and first
stage of electric heat, there are a few
circumstances where the MCA and
MOP are increased when this sequence
is employed.
You must perform three sets of calculations to obtain the correct MCA and
MOP values: one for cooling (set #1)
only, one for electric heat (set #2) only,
and one for when the unit is in the
cooling mode with compressors and
electric heat on concurrently (set #3).
For size 031 and 040 units, compressors
A (1K1) and B (1K2) can run concurrently with 1/3 of three-stage electric
heat or 1/7 of seven-stage electric heat.
For size 051 and 066 size units, compressors A (1K1) and D (1K4) can run
concurrently with 1/3 of three-stage
electric heat or 1/7 of seven-stage
electric heat.
For units using heaters less than 50 kW:
MCA = (1.25 x load 1) + load 2 + load 4 +
(1.25 x load 3)
For unit using heaters equal to or
greater than 50 kW:
MCA = (1.25 X load 1) + load 2 + load 3 +
load 4
Select the nameplate MCA value that is
the largest of the three sets of MCA
calculations.
MOP = (2.25 x load 1) + load 2 + load 3 +
load 4
Select an overcurrent protective device
rating equal to the MOP value. If the
MOP value does not equal a standard
device size as listed in NEC 240-6, select
MUA-PRC004-EN

Electrical
Data
the next lower standard device rating. If
the next lower standard rating is less
than 125% of the current rating of the
electric heater load, select the next
higher standard device rating. If the
selected MOP is less than the MCA, then
reselect the lowest standard device size
which is equal to or larger than the
MCA, provided the reselected device
size does not exceed 800 amps.

Dual Source Power


For units with dual source power, use
two different sets or MCA and MOP
calculations, one for each power
connection. MCA1 and MOP1 represent
the values calculated for the operation
of the compressors and condenser fans.
For the calculations of MCA1 and MOP1,
use the instructions from set #1 previously in this section.

The MOP value selected should be the


largest of the three sets of MOP value
calculations.

MCA2 and MOP2 represent the values


calculated for the operation of the unit in
heating mode:

Disconnect Switch Sizing (DSS) if field


provided and installed
If the unit is ordered with a factoryinstalled non-fused disconnect switch,
this sizing equation is not necessary. If
the disconnect is to be field-provided
and installed, use the following equation
to determine its rating:

MCA2 = (1.25 x load 3) if heater kW is


less than 50kW

DSS = 1.15 x (load 1 + load 2 + load 3 +


load 4)
Select the DSS that is the largest of the
three sets of DSS calculations. Select a
disconnect switch size equal to or
greater than the DSS value calculated.
Set #4: Units with Electric Heat, Dual
Source Power
Dual source power is required only on
some 208V and 230V units when
provided with electric heat. Those units
are:
size

voltage

elec ht kW

031

208V or 230V

42 kW or
larger

040

208V or 230V

42 kW or
larger

051

208V or 230V

70 kW or
larger

066

208V or 230V

70 kW or
larger

MUA-PRC004-EN

Load Definitions
Load 1
Supply Fan

Exhaust Fan

Reheat Comp (A) Condenser Fan 1 (A)


Main Comp 1 (B) Condenser Fan 2 (B)
Main Comp 2 (C) Condenser Fan 3 (C)
Main Comp 3 (D) [5100/6600]
total Energy Wheel
Load 3
Electric Heat

or

kW < 50

(1.0 x load 3) if heater kW is 50kW or


greater, MOP2 = (1.25 x load 3)

kW > 50

Select an overcurrent protective device


rating for the heating circuit equal to the
MOP2 value. If the MOP2 value does not
equal a standard device size as listed in
NEC 240-6, select the next lower
standard device rating. If the selected
MOP2 is less than the MCA2, then
reselect the lowest standard device size
that is equal to or larger than the MCA2,
provided the reselected device size
does not exceed 800 amps.

Load 4
Control Power Transformer (Loads > 1
Amp [1T1 - 208/230])
Gas Heat
Factory-Wired Convenience Outlet

Disconnect Switch Sizing (DSS) if field


provided and installed:
If the unit is ordered with a factoryinstalled non-fused disconnect switch,
this sizing equation is not necessary. If
the disconnect is to be field-provided
and installed, use the following equation
to determine its rating:
DSS2 = 1.15 x (load 3)
Select the DSS2 value that is the largest
of the three sets of DSS2 calculations.
Select a disconnect switch size equal to
or greater than the DSS2 value calculated.

87

Electrical
Data
Table ED-1. Electrical Service Sizing Data
unit
size
031

voltage
208/60/3
230/60/3
460/60/3
208/60/3
230/60/3
460/60/3
208/60/3
230/60/3
460/60/3
208/60/3
230/60/3
460/60/3

040

056

066

reheat comp (A)


tons* rla
lra
4.5 15
124
4.5 15
124
4.5
8 59.6
6.75 23
164
6.75 23
164
6.75 11
100
9.0 35
222
9.0 31
251
9.0 16
117
9.0 35
222
9.0 31
251
9.0 16
117

main comp 1 (B)


tons* rla
lra
9.0
35
222
9.0
31
251
9.0
16
117
10.0
35
222
10.0
31
251
10.0
16
117
14.0
48
337
14.0
43
376
14.0
23
178
15.0
51
337
15.0
46
376
15.0
23
178

main comp 2 (C)


main comp 3 (D)
tons* rla
lra tons* rla
lra
14.0
48
337

14.0
43
376

14.0
23
178

15.0
51
337

15.0
46
376

15.0
23
178

9.0
35
222
9.0
35
222
9.0
31
251
9.0
31
251
9.0
16
117
9.0
16
117
15.0
51
337 15.0
51
337
15.0
46
376 15.0
46
376
15.0
23
178 15.0
23
178

*tons refers to nominal R22 tons


electric heat FLA is determined at 208, 240, & 480 volts

Table ED-2. Supply fan motor fla


Voltage
208/60/3
230/60/3
460/60/3

standard efficiency
1 hp 2 hp 3 hp 5 hp 7.5 hp 10 hp 15 hp
3.1
2.8
1.4

5.9
5.6
2.8

8.7 14.0
8.0 13.2
4.0
6.6

22.2 28.2
21.6 28.0
10.8 14.0

40.7
40.6
20.3

high efficiency
1 hp 2 hp 3 hp 5 hp 7.5 hp 10 hp 15 hp
3.1
2.8
1.4

6.1
5.4
2.7

9.3 14.9
8.2 12.8
4.1
6.4

21.3
20.0
10.0

29.0
25.8
12.9

40.7
35.4
17.7

Table ED-3. Exhaust fan motor fla


Voltage
208/60/3
230/60/3
460/60/3

standard efficiency
1 hp 2 hp 3 hp 5 hp 7.5 hp 10 hp 15 hp
3.1
2.8
1.4

5.9
5.6
2.8

8.7 14.0
8.0 13.2
4.0
6.6

22.2 28.2
21.6 28.0
10.8 14.0

40.7

Table ED-4. Energy wheel motor fla


unit size

031

040

051

066

voltage
208/60/3
230/60/3
460/60/3

1/2 hp
2.7
2.4
1.2

1/2
2.7
2.4
1.2

3/4
3.6
3.0
1.5

3/4
3.6
3.0
1.5

high efficiency
1 hp 2 hp 3 hp 5 hp 7.5 hp 10 hp 15 hp
3.1
2.8
1.4

6.1
5.4
2.7

9.3 14.9
8.2 12.8
4.1
6.4

21.3
20.0
10.0

29.0
25.8
12.9

Table ED-5. Condenser fan motors


voltage
208/60/3
230/60/3
460/60/3

fla
3.8
3.6
1.8

Table ED-6. Factory-wired convenience outlet


voltage

amps

208/60/3
230/60/3
460/60/3

7.21
6.52
3.26

Table ED-7. total gas heat amps with combustion blower


voltage
208/60/3
230/60/3
460/60/3

amps
2.54
2.30
1.15

Table ED-8. Control power transformer (loads greater than 1 amp)

88

voltage

amps

208/60/3
230/60/3

1.20
1.09

MUA-PRC004-EN

Electrical
Data
Table ED-9. Electric heat FLA
unit
size

voltage

kW
20

kW
26

kW
32

kW
42

kW
56

kW
70

kW
84

kW
100

kW
122

031

208/60/3
230/60/3
460/60/3

55.5 72.2
48.1 62.5
24.1 31.3

88.8
77.0
38.5

116.6
101.0
50.5

155.4
134.7
67.4

040

208/60/3
230/60/3
460/60/3

72.2
62.5
31.3

88.8
77.0
38.5

116.6
101.0
50.5

155.4 194.3 233.2


134.7 168.4 202.1
67.4 84.2 101.0

051

208/60/3
230/60/3
460/60/3

88.8
77.0
38.5

116.6
101.0
50.5

155.4 194.3 233.2 277.6


134.7 168.4 202.1 240.6
67.4 84.2 101.0 120.3

066

208/60/3
230/60/3
460/60/3

116.6
101.0
50.5

155.4 194.3 233.2 277.6 338.6


134.7 168.4 202.1 240.6 293.5
67.4 84.2 101.0 120.3 146.7

Note: Electric heat FLA is determined at 208, 240 & 480 volts.

Table ED-10. Dual source electric heat - customer wire gauge, AWG
unit
size

voltage

kW
42

kW
56

kW
70

kW
84

kW
100

kW
122

031

208/60/3
230/60/3

1/0
1

2/0
1/0

040

208/60/3
230/60/3

1/0
1

2/0
1/0

3/0
2/0

250
4/0

051

208/60/3
230/60/3

3/0
2/0

250
4/0

300
250

066

208/60/3
230/60/3

3/0
2/0

250
4/0

300
250

500
350

Table ED-11. Voltage utilization range

MUA-PRC004-EN

voltage

utilization
range

208/60/3
230/60/3
460/60/3

187-220
208-254
416-508

89

Dimensions &
Weights
Typical exterior dimensions

outdoor side view, unit without total energy wheel


OUTDOOR SIDE VIEW

outdoor side view, unit with total energy wheel

DETAIL B
LIFTING HOLE
DETAIL A

detail B
lifting hole detail A
INLET HOOD
END VIEW

CONTROL PANEL
END VIEW

inlet hood end view


control panel end view

unit
size

without TE wheel
031, 041
18' - 10"
051, 066
19' - 3"
with TE wheel
031, 041
24' - 2"
051, 066
24' - 7"
90

dimensions (ft and in)


F
G
H

2' - 7"
3'

4' - 2"
5' - 10"

3' - 10"
4' - 1"

3' - 2"
3' - 6"

10"
1' - 3"

2' - 7"
3'

4' - 2"
5' - 10"

3' - 10"
4' - 1"

9 1/4"
8"

3' - 2"
3' - 6"

10"
1' - 3"

9"
10 14"

1' - 11 1/2"
2' - 4 1/2"

1 1/4"
1 1/4"

1' - 6 14"
3' - 6 3/4"

2 1/2"
3"

1' 6"
1' 8"

1' - 6 14"
3' - 6 3/4"

2 1/2"
3"

7"
7"

1' - 3/4"
11"

9"
1' - 11 1/2"
10 - 14" 2' - 4 1/2"

MUA-PRC004-EN

Dimensions &
Weights
Typical exterior
dimensions

unit without TE wheel - indoor side view (electric heat version shown)

unit with TE wheel - indoor side view (electric heat version shown)

single & dual gas heater options

MUA-PRC004-EN

91

Dimensions & unit without TE


Weights
wheel
Unit base plan view, duct openings and thru-base power
openings, unit sizes 031 & 040
unit without TE wheel

unit with TE wheel

92

MUA-PRC004-EN

Dimensions &
Weights
Unit base plan view, duct openings and thru-base power
openings, unit sizes 051 &066
unit without TE wheel

unit with TE wheel

MUA-PRC004-EN

93

Dimensions &
Weights
Fresh air unit control panel detail, all unit sizes

detail A

3x

THRU-BASE MAIN POWER WIRING ENTRANCE


HOLE 3.000
NOTE: DRILL OR PUNCH HOLE IN COVER PLATE FOR
SMALLER CONDUIT CONNECTION

94

MUA-PRC004-EN

Dimensions &
Weights
Exterior features for unit sizes 031 & 040,
without TE wheel
CONDENSER FANS

CONVENIENCE OUTLET (OPTION)


LIFTING HOLES
MAIN COMPRESSOR ACCESS PANEL
(40x35)
REHEAT COMPRESSOR/COIL ACCESS PANEL
(34x36)

HORIZONTAL DISCHARGE
(OPTION)
MAIN CONDENSER
COIL ACCESS PANEL
(68x36)

HUMAN INTERFACE
ACCESS DOOR
UNIT CONTROL PANEL

MAIN POWER WIRING ENTRANCE


(CAN ALSO BE RUN THRU-BASE)

24 VOLT CONTROL CIRCUIT WIRING ENTRANCE


(CAN ALSO BE RUN THRU-BASE)

DUAL GAS HEAT ACCESS PANEL


(EACH HEATER HAS SEPARATE PANEL)
(16x23)

INLET HOOD
GAS CONNECTIONDUAL GAS HEAT
(EACH HEATER HAS SEPARATE GAS CONNECTIONS)
NATURAL GAS 250400 MBH: .500 NPT INTERNAL

CONDENSATE
DRAIN CONNECTION
ELECTRIC HEAT POWER WIRING ENTRANCE
(ALSO CAN BE RUN THRU-BASE)
ELECTRIC HEATER ELECTRICAL PANEL (24x30)
-ORGAS HEAT PANEL (16x23)
-ORFIXED PANEL FOR NO-HEAT OPTION
OR HYDRONIC HEAT INTERFACE OPTION (24x47)

FILTER AND DAMPER ACCESS DOOR


(25x39)
EVAP COIL AND
CONDENSATE DRAIN PAN
ACCESS DOOR (18x34)

SUPPLY FAN ACCESS DOOR


(33X34)

MUA-PRC004-EN

95

Dimensions &
Weights
Exterior features, unit sizes 031 & 040
with TE wheel

96

MUA-PRC004-EN

Dimensions &
Weights
Exterior features for unit sizes 051 & 066,
without TE wheel
CONDENSER FANS

LIFTING HOLES
REHEAT COMPRESSOR/
COIL ACCESS PANEL (40x52)

MAIN COMPRESSOR/
COIL ACCESS PANEL (34x52)
CONVENIENCE OUTLET
(OPTION)

HORIZONTAL DISCHARGE
(OPTION)
MAIN COMPRESSOR/
COIL ACCESS PANEL
(68x52)
MAIN POWER WIRING ENTRANCE
(CAN ALSO BE RUN THRU-BASE)

HUMAN INTERFACE
ACCESS DOOR
UNIT CONTROL PANEL
24 VOLT CONTROL CIRCUIT WIRING ENTRANCE
(CAN ALSO BE RUN THRU-BASE)

DUAL GAS HEAT ACCESS PANEL


(EACH HEATER HAS SEPARATE PANEL)
(16x23)
GAS CONNECTIONDUAL GAS HEAT
(EACH HEATER HAS SEPARATE GAS CONNECTIONS)
ELECTRIC HEAT POWER WIRING ENTRANCE
FOR 208/230 V: 70, 84, 100, 122 kW
(CAN ALSO BE RUN THRU-BASE)

CONDENSATE DRAIN
CONNECTION
INLET HOOD

ELECTRIC HEATER ELECTRICAL PANEL (24x49)


-ORSINGLE GAS HEAT ACCESS PANEL (16x23)
-ORFIXED PANEL FOR NO-HEAT OPTION
OR HYDRONIC HEAT INTERFACE OPTION (24x67)

SUPPLY FAN ACCESS DOOR


(33x54)
FILTER AND DAMPER ACCESS DOOR
(25x59)

GAS CONNECTIONSINGLE GAS HEATER

MUA-PRC004-EN

97

Dimensions &
Weights
Exterior features for unit sizes 051 & 066
with TE wheel

98

MUA-PRC004-EN

Dimensions &
Weights
Standard curb, unit sizes 031 & 040
without TE wheel

6 WOOD NAILER

MUA-PRC004-EN

99

Dimensions &
Weights
Standard roof curb, unit sizes 031 & 040
with TE wheel

6" WOOD NAILER

100

MUA-PRC004-EN

Dimensions &
Weights
Standard curb, unit sizes 051 & 66 without TE wheel

6 WOOD NAILER

MUA-PRC004-EN

101

Dimensions &
Weights
Standard roof curb, unit sizes 051 & 066
with total energy wheel

6" WOOD NAILER

102

MUA-PRC004-EN

Dimensions &
Weights
Extended height curb, unit sizes 031 & 040
without TE wheel

6 WOOD NAILER

MUA-PRC004-EN

103

Dimensions &
Weights
Extended height roof curb , unit sizes 031 & 040
with TE wheel

6" WOOD NAILER

104

MUA-PRC004-EN

Dimensions &
Weights
Extended height curb, unit sizes 051 & 066
without TE wheel

6 WOOD NAILER

MUA-PRC004-EN

105

Dimensions &
Weights
Extended height roof curb, unit sizes 051 & 066
with TE wheel

6" WOOD NAILER

106

MUA-PRC004-EN

Dimensions &
Weights
Unit and accessory weights
Table I-DW-1. Typical unit, unit with total energy wheel, and roof curb weights
unit
size

base unit
weight 1

total energy wheel unit


base weight 1

031
040
051
066

4600
4700
5600
6000

1460
1520
1920
1970

roof curb for unit w/o TE wheel


low
high acoustic
282
282
282
282

613
613
613
613

roof curb for unit with TE wheel


low
high

1500
1500
1500
1500

350
350
350
350

766
766
766
766

1. Base unit operating weight is for units with the condenser hot gas reheat option, return air, and no heat. Subtract condenser hot gas reheat weight for cooling only units. See Table
I-DW-2 for weight.

Table I-DW-2. Typical component weights


unit
size

125

150

single gas (MBh)


200
250
300

350

400

250

300

dual gas (MBh)


400
500
600

700

800

031
040
051
066

201
201
201
201

217
217
217
217

247
247
247
247

333
333
333
333

361
361

402
402
402
402

434
434
434
434

494
494
494

666

722

295
295
295
295

295
295
295
295

590
590

590
590

electric heaters
20-84 kW 100,122 kW
60
60
60
60

100
100

150
150
270
270

condenser hot
gas reheat 2

Figure I-DW-1. Fresh air unit weight and center of gravity


unit
size

center of gravity
X (in)
Y (in)

units without total energy wheel


031
90
50
040
90
50
051
100
51
066
100
51
units with total energy wheel
031
123
50
040
123
50
051
130
51
066
130
51

MUA-PRC004-EN

max operational
weight (lbs)

typical point loading% of unit weight


B
C
D
E

4934
5194
6190
6722

16
16
19
19

18
18
18
18

19
19
17
17

18
18
15
15

16
16
15
15

14
14
16
16

6394
6718
8081
8663

16
16
13
13

16
16
15
15

17
16
17
17

18
17
20
21

17
17
18
18

16
17
16
16

107

Dimensions &
Weights
Component arrangement
unit size 031 & 040
unit without TE wheel

unit sizes 031 & 040

unit with TE wheel

108

MUA-PRC004-EN

Dimensions &
Weights
Component arrangement
unit size 051 & 066
unit withouth TE wheel

unit with TE wheel

MUA-PRC004-EN

109

Dimensions &
Weights
Total energy wheel cassette locations, typical indoor
side views

unit size 031

unit size 040

unit size 051

unit size 066

110

MUA-PRC004-EN

Dimensions & unit without TE


Weights
wheel
Minimum operating & service
clearances
unit without TE wheel

TOP: CLEAR OF ALL OBSTACLES OR OVERHANGS

unit with TE wheel

TOP: CLEAR OF ALL OBSTACLES OR OVERHANGS


MUA-PRC004-EN

111

Mechanical
Specifications
Fan Motors
The supply and exhast fan motors are
either standard-efficiency open dripproof or high-efficiency open drip-proof.
All supply fan motors meet the U.S.
Energy Policy Act of 1992 (EPACT).

Dampers Low Leak


The outside air damper has a unitcontrolled actuator with parallel-blades.
The blade construction is a 14-gage
galvanized steel, roll-formed airfoil-type.

Exhaust Backdraft Damper


A backdraft damper prevents outside
air entry into the building through the
exhaust fan. Damper frame is extruded
aluminum with mitered corners. Blades
are formed aluminum with extruded
vinyl edge seals that mechanically lock
into the blade edge. Bearings are
corrosion resistant synthetic and the
linkage is concealed in frame for low
pressure drop and noise.
Condenser Fan and Motors
The unit condenser fans are vertical
discharge, direct-drive fans. They are
statically and dynamically balanced. The
blades and spider are constructed of
zinc-plated steel. Condenser fan motors
are three-phase motors with permanently lubricated ball bearings, built-in
current and thermal overload protection, and weather-tight slingers over the
motor bearings.

Figure MS-5. Traq Damper

building comfort. A centralized microprocessor provides anti-short cycle


timing and time delay between compressors to provide a higher level of
machine protection. The unit controls
can function as a stand-alone controller
ling. The character font is 5 x 7 dot
matrix plus cursor. The display is a
supertwist liquid crystal display (LCD)
with blue characters on a gray/green
background, which provides high
visibility and interface ease. Meaningful
diagnostics are also reported and
displayed at the HI panel display.
The HI keypad is equipped with 16
individual touch-sensitive membrane
key switches. The switches are divided
into four separate sections and password protected to prevent tampering by
unauthorized personnel. The six main
menus are STATUS, SETPOINTS,
DIAGNOSTICS, SETUP, CONFIGURATION, and SERVICE MODE.

Options
Electric Heating Option
High nickel chrome alloy resistance wire
is mechanically staked and welded to
corrosion-resistant terminals. Heaters
are provided with both manual and
automatic temperature control devices.
See Figure MS-4.

Filters
The filter racks (see Figure MS-4)
accommodate 2 filter media and are
field convertible to allow 4 filter media.

3-Stage Electric Heat


These electric heaters have three
balanced stages with heating steps of
33, 66, and 100%.
Figure MS-6. Return air damper

7-Stage Electric Heat


These heaters have three unbalanced
stages, resulting in seven steps of 14,
27, 41, 59, 68, 86, and 100%.

Electrical and Controls

Figure MS-4. Filter racks


112

Controls
The Trane Packaged Fresh Air unit is
completely factory-wired with necessary controls and terminal block for
power wiring. Microprocessor controls
are provided for all 24-volt and 115-volt
control functions. The resident control
algorithms make all heating, cooling,
drying, and/or ventilating decisions in
response to electronic signals from
sensors measuring indoor temperature,
outdoor temperature, and humidity.
The control algorithm maintains
accurate temperature, dew point, and/
or humidity control. It also minimizes
setpoint drift and provides better

Figure MS-7. Electric heat option


MUA-PRC004-EN

Mechanical
Specifications
Gas-Fired Heating Option
The Packaged Fresh Air units furnaces
are certified for 80% thermal efficiency.
The heaters include an integral power
vent system. All natural gas-fired units
are completely assembled and wired at
the factory. The burner and bottom pans
are type 409 stainless steel.
409 Stainless Steel Heat Exchanger
Heat exchanger headers and tubing are
type 409 stainless steel.
321 Stainless Steel Heat Exchanger
Heat exchanger headers and tubing are
type 321 stainless steel.
Single Bank Staged
A single heater unit with a two-stage
gas valve provides two steps of heat.
Single Bank Modulated
A single heater unit with solid state
controls provides close temperature
control through regulating manifold
pressure. The controls modulate
between 50 and 100%.
Dual Bank Staged
The heater bank contains a single-stage
and a two-stage unit. This combination
results in steps of 25, 50, 75, and 100%.
Dual Bank Modulated
The heater bank contains a single-stage
and a modulating unit. The microprocessor sequences the single stage bank
with the modulating bank to provide
capacity control between 25-100%
heating capacity. This combination
results in 25 to 50% modulation, a 25%
step, and 75 to 100% modulation.
Hydronic Heat Interface
A bulkhead and coil support is provided
downstream of the fan to accept a fieldinstalled one or two-row hydronic
heating coil. The unit controller provides
a modulating output to control a fieldinstalled water valve and accepts a low
temperature limit input signal. The coil
supports accept a standard Trane
33X36 heating coil for the small
cabinet and 33X48 coil for the large
cabinet. Large cabinets may require
field-provided blockoffs. Also, if fieldinstalling smaller coils than recommended, additional field modifications
or blockoffs must be made. Openings in
the unit side panels for piping must also
be field constructed.

MUA-PRC004-EN

Condenser Hot Gas Reheat


An indoor reheat condenser is mounted
downstream of the evaporator coils.
The indoor and outdoor reheat condenser has parallel circuits. A liquid
solenoid valve controls where refrigerant condensation occurs.

Dirty Filter Switch


This option indicates when there is a
dirty filter. The dirty filter switch triggers
an information-only diagnostic message
on the human interface or lights the
service LED on the zone sensor, and will
allow continued unit operation.

Traq Damper
Traq outdoor air dampers with flow
measurement rings and a ventilation
control module are available for airflow
measurement and verification. Each
damper has a unit-controlled actuator.
See Figure MS-5.

Non-Fused Disconnect Switch


A through-the-door, non-fused disconnect switch with external handle is
factory-installed. See Figure MS-7.

Return Air/Reference Enthalpy


Air returns vertically through the unit
base. Dampers are low-leak. Each
damper has a unit-controlled actuator.
Inputs are provided for unoccupied
economizer control, based upon a
comparison of the outside air stream to
a definable enthalpy reference point.
See Figure MS-6.
Return Air/Comparative Enthalpy
Air returns vertically through the unit
base. Dampers are low-leak. Each
damper has a unit-controlled actuator.
Inputs are provided for unoccupied
economizer control, based upon a
comparison of enthalpies of the return
and outdoor air streams.
External Exhaust Interface
The exhaust plenum is internal to the
unit cabinet and has one-inch, doublewall, foamed construction. The unit
controller provides a binary exhaust fan
signal and accepts a binary fan airflow
proving input signal from a fieldinstalled exhaust fan.

Figure MS-8. Non-fused disconnect


switch

Convenience Outlet
A convenience outlet is provided on the
condenser side of the unit. The GFI
outlet is 115 volt, and capable of manual
resetting.

Corrosion-Inhibiting Coil Coating


The indoor and outdoor coils have a four
to six mil protective coating applied by a
multiple dip and bake process.
Corrosion-Inhibiting Cabinet Coating
The units interior and exterior surfaces
have a four to six mil spray-on protective coating applied with an air-dry
process.
Two-Inch Throwaway Filter
The Fresh Air Units filters are UL class
2. Filters are 30% efficient based on
ASHRAE test standard 52-76 with an
arrestance of 90-92%.

Figure MS-9. Convenience outlet

Extended Grease Lines


Factory installed extended grease lines
provide a common location for
regreasing the supply and exhaust fan
bearings. The grease fittings are easily
accessible within the fan compartment.

113

Mechanical
Specifications
LonTalk Communications Interface
(LCI-I)
The LCI-I provides an interface to a
Tracer Summit system or other control
system that supports LonTalk and the
DAC profile. The LCI-I is a factoryinstalled device and provides a Comm5
interface to a Trane Integrated Comfort
System (ICS). The LCI-I allows control
and monitoring of the unit via a twowire communication link.
Generic Building Automation
System (GBAS)
The GBAS module is for use with a nonTrane building management system.
The module provides a binary input for
demand limiting, four analog inputs for
setpoint adjustment, and five relay
outputs for diagnostic reporting. Inputs
can use a potentiometer or 0-5 VDC
signal.
Ventilation Override Module (VOM)
The VOM allows programming of the
unit with up to five ventilation sequences: smoke purge, evacuation,
pressurization, purge, and purge with
duct control. Typically a hard-wire short
from a smoke detector or fire control
panel will cause a binary input on the
VOM to close, thus causing the programmed sequence to occur. These
points can be permanently locked to
prevent tampering.
Interface for Remote Human
Interface (RHI)
This interface consists of an
interprocesor communication board
(IPCB) and is factory-installed in the unit
control panel. This component provides
a communication bridge for the RHI to
up to four units. This option must be
installed in the unit to communicate with
a remote HI.

Accessories
Roof Mounting Curb
The roof mounting curb is fabricated of
14-gage galvanized steel with a nominal
two x two-inch nailer setup. The curb
ships knocked down with a curb gasket.
Curb height options are 14 or 24-inches.
Acoustical Roof Curb
The acoustical roof curb ships fully
assembled and has prefabricated,
noncombustible construction with
114

sealing gasket around perimeter


members to ensure air/water tight
integrity. The curb construction is a
minimum 14 gage galvanized steel
structural members with minimum 20
gage galvanized steel flashing with
overlapping continuous rubber counter
flashing. Curbs have a 2x2 nailer strip
for attaching roof felts. The base
contains acoustically nonconductive
floor pans with the supply and return
openings framed for duct attachment.
The roof curb incorporates an integral
spring-vibration isolation rail with
adjustable 1 deflection isolators, and is
properly sized and selected for unit
point loading. Spring isolators have a
minimum 90% isolation efficiency.
Permanent Filters
Permanent filters are provided with a
2 metal frame and permanent wire
mesh media. The filter media is cleanable.
LonTalk Communications Interface
(LCI-I) Kit
A field-installed LCI-I kit is provided to
interface with a Tracer Summit system
or other control system that supports
LonTalk and the DAC (discharge air
control) profile. The LCI-I kit provides a
Comm5 interface to control and monitor
the unit via a two-wire communication
link.
Generic BAS (GBAS) Interface Kit
A field-installed GBAS kit is provided for
use with a non-Trane building management system. The GBAS module
provides a binary input for demand
limiting, four analog inputs for setpoint
adjustment, and five relay outputs for
diagnostic reporting. Inputs use a
potentiometer or a 0-5VDC signal.
Ventilation Override Module (VOM)
Kit
This field kit allows ventilation override
capability. The VOM module allows
programming of the unit with up to five
ventilation sequences: smoke purge,
evacuation, pressurization, purge and
purge with duct control. Typically a
hard-wire short from a smoke detector
or fire control panel will cause a binary
input on the VOM to close, thus causing
the programmed sequence to occur.
These points can be permanently
locked to prevent tampering.
MUA-PRC004-EN

Mechanical
Specifications
Electronic Time Clock
The electronic time clock is fieldinstalled. It allows night setback and
unoccupied functions when using a
standard (dual setpoint) zone sensor
module.
Remote Human Interface
The remote human interface (RHI) panel
can perform all the same functions as
the unit mounted human interface,
except for the service mode. It uses the
same two line x 40-character display
and keypad as the HI. Also, the RHI can
monitor up to four units.
Zone Temperature Sensor
A remote zone temperature sensor is
available for use when using zone
sensors for morning warmup (with all
units or as a zone sensor with the Tracer
Integrated Comfort system).
Zone Sensor with Timed Override
A zone temperature sensor with timed
override buttons is available for use
with the Tracer Integrated Comfort
system.
Zone Sensor with Local Setpoints
A zone temperature sensor with local
temperature adjustment control and
timed override buttons is available for
use with the Tracer Integrated Comfort
system or for use as a morning warmup
setpoint and sensor.

Dual Setpoint Sensor


The dual setpoint sensor is for use with
zone heating and cooling setpoints, and
supply air cooling and heating resets.
The zone sensor has two temperature
setpoint levers and an auto-off system
switch.
Dual Setpoint Sensor with System
Function Lights
The dual setpoint sensor is for use with
zone heating and cooling setpoints, as
well as supply air cooling and heating
resets. The zone sensor has two
temperature setpoint levers, an auto-off
system switch, and status indication
LED lights for: system on, heat, cool, and
service.
Space Relative Humidity Kit
The zone relative humidity sensor
initiates the dehumidification mode for
zone dehumidification units. It can also
reset the supply air-drying or zone
relative humidity setpoints.
Carbon Dioxide Sensor
The carbon dioxide sensor is fieldinstalled. It monitors carbon dioxide
concentrations and displays on the
human interface panel.
Dry-bulb Duct Sensor
This field-installed bullet-type sensor
option is for use as a temperature input
from a location such as a return air duct.

Remote Minimum Position


Potentiometer Control
A remote minimum position potentiometer allows remote control of the
minimum outside air damper position.

MUA-PRC004-EN

115

Literature Order Number

MUA-PRC004-EN

File Number

PL-AH-MUA-PRC004-EN 1202

Supersedes

MUA-PRC004-EN 0402

A business of American Standard Inc. Stocking Location


www.trane.com
For more information contact
your local Trane office or