Sunteți pe pagina 1din 13

AST706P2 / TX1 AST 66KV / 7SJ642 V4.

8
MLFB: 7SJ 6421**B921FA0
Parameter set version: V04.81.04
Device path: \\hgfilp01
\share\ENGSERVICES\Project Filing\Secondary Systems Projects\SSPN-
00058 120523 AST Protection Upgrade\4 Technical\Calculations\Siemens 7SJ 642 fromactual
relay\TX1ASTH66KV2\P7DI\GV\ST\00000001
Author:
Creation date: 17.05.06 16:01:46
Last modified: 18.09.12 11:21:21
Operating mode: Offline
Comment:
Setting values in: Secondary value description
P R I N T - C O N T E N T S
..................... 2 1 Settings - Masking I/O (Configuration Matrix) - AST706P2 / TX1 AST 66KV / 7SJ 642 V4.8/7SJ 642
........................................................................................................................................................ 2 1.1 Matrix - printout
...................................................................................................................................................................... 2 2 Device
.............................................................................................................................................. 4 3 Power SystemData 1
................................................................................................................................... 4 4 Oscillographic Fault Records
.............................................................................................................................................. 5 5 Power SystemData 2
..................................................................................................................... 5 6 DMT / IDMT Phase/Earth Overcurrent
....................................................................................................................................... 9 7 Measurement Supervision
................................................................................................................................................................ 9 8 TX Alarms
........................................................................................................................................................ 9 9 General Alarms
........................................................................................................................................................... 11 10 LBU Intertrip
........................................................................................................................................................................ 11 11 TCS
...................................................................................................................................................... 11 12 Breaker Failure
............................................................................................................................................. 11 13 Control Authorization
....................................................................................................................................................... 12 14 Control Device
......................................................................................................................................................... 12 15 Process Data
......................................................................................................................................................... 12 16 Measurement
............................................................................................................................... 13 17 Set Points (Measured Values)
.................................................................................................................................................................... 13 18 Energy
................................................................................................................................................................. 13 19 Statistics
............................................................................................................................................... 13 20 Set Points (Statistic)
................................................................................................................................................... 13 21 Threshold-Switch
7SJ642 V4_8_prn
SIMATIC Matrix - short view 18.09.12 11:25:03
Page 1 of 13
1
Setti ngs - Maski ng I/O (Confi gurati on Matri x) - AST706P2 / TX1 AST 66KV / 7SJ642 V4.
8/7SJ642
1.1 Matri x - printout
Information: Indications and commands only
Filter: No filter
2 Device
Device
No. D L T BI F S C BO LEDs O S
00003 >Time Synch >Synchronize Internal Real Time Clock SP_Ev
00005 >Reset LED >Reset LED SP
>Light on >Back Light on SP IO
00051 Device OK Device is Operational and Protecting OUT IO
00052 ProtActive At Least 1 Protection Funct. is Active IntSP IO
00055 Reset Device Reset Device OUT I
00056 Initial Start Initial Start of Device OUT I
Reset LED Reset LED IntSP I
00067 Resume Resume OUT I
00068 Clock SyncError Clock Synchronization Error OUT IO
00069 DayLightSavTime Daylight Saving Time OUT IO
00110 Event Lost Event lost OUT_Ev I
00113 Flag Lost Flag Lost OUT I
00125 Chatter ON Chatter ON OUT IO
00140 Error SumAlarm Error with a summary alarm OUT IO
00160 AlarmSumEvent AlarmSummary Event OUT IO
00144 Error 5V Error 5V OUT IO
00145 Error 0V Error 0V OUT IO
00146 Error -5V Error -5V OUT IO
00147 Error PwrSupply Error Power Supply OUT IO
00177 Fail Battery Failure: Battery empty OUT IO
00070 Settings Calc. Setting calculation is running OUT IO
00071 Settings Check Settings Check OUT
00072 Level-2 change Level-2 change OUT IO
00183 Error Board 1 Error Board 1 OUT IO
00184 Error Board 2 Error Board 2 OUT IO
00185 Error Board 3 Error Board 3 OUT IO
00186 Error Board 4 Error Board 4 OUT IO
00187 Error Board 5 Error Board 5 OUT IO
00188 Error Board 6 Error Board 6 OUT IO
00189 Error Board 7 Error Board 7 OUT IO
DataStop Stop data transmission IntSP IO
00016 >DataStop >Stop data transmission SP
Test mode Test mode IntSP IO
00015 >Test mode >Test mode SP
7SJ642 V4_8_prn
Settings - Masking I/O (Configuration Matrix) - AST706P2 / TX1 AST 66KV / 7SJ642 V4.8/7SJ642
SIMATIC Matrix - short view 18.09.12 11:25:03
Page 2 of 13
Device(2)
T S C C D CM
X X
X
X
7SJ642 V4_8_prn
Device
SIMATIC Matrix - short view 18.09.12 11:25:03
Page 3 of 13
Device(3)
No. D L T BI F S C BO LEDs O S
FdrEARTHED Feeder EARTHED IntSP
Brk OPENED Breaker OPENED IntSP
HWTestMod Hardware Test Mode IntSP IO
SynchClock Clock Synchronization IntSP_Ev
00193 AlarmNO calibr Alarm: NO calibration data available OUT IO
17565 >Blk.offset s. >Blocking of the offset supervision SP IO
00191 Error Offset Error: Offset OUT IO
00320 Warn Mem. Data Warn: Limit of Memory Data exceeded OUT IO
00321 Warn Mem. Para. Warn: Limit of Memory Parameter exceeded OUT IO
00322 Warn Mem. Oper. Warn: Limit of Memory Operation exceeded OUT IO
00323 Warn Mem. New Warn: Limit of Memory Newexceeded OUT IO
Distur.CFC Disturbance CFC OUT IO
17566 Dist.CFC Src Disturbance CFC Source VI IO
00545 PU Time Time fromPickup to drop out VI
00546 TRIP Time Time fromPickup to TRIP VI
236.2127.01 BLK. Flex.Fct. BLOCK Flexible Function IntSP IO
3 Power System Data 1
Power System Data 1
No. D L T BI F S C BO LEDs O S T S C C D CM
05145 >Reverse Rot. >Reverse Phase Rotation SP IO
05147 Rotation L1L2L3 Phase Rotation L1L2L3 OUT IO
05148 Rotation L1L3L2 Phase Rotation L1L3L2 OUT IO
4 Osci l l ographi c Faul t Records
Oscillographic Fault Records
No. D L T BI F S C BO LEDs O S T S C C D CM
00004 >Trig.Wave.Cap. >Trigger WaveformCapture SP
00203 Wave. deleted Waveformdata deleted OUT_Ev I
FltRecSta Fault Recording Start IntSP X IO
30053 Fault rec. run. Fault recording is running OUT
7SJ642 V4_8_prn
Device
SIMATIC Matrix - short view 18.09.12 11:25:03
Page 4 of 13
5 Power System Data 2
Power System Data 2
No. D L T BI F S C BO LEDs O S T S C C D
00356 >Manual Close >Manual close signal SP
02720 >Enable ANSI#-2 >Enable 50/67-(N)-2 (override 79 blk) SP IO
00533 IL1 = Primary fault current IL1 VI IO
00534 IL2 = Primary fault current IL2 VI IO
00535 IL3 = Primary fault current IL3 VI IO
00501 Relay PICKUP Relay PICKUP OUT I
00511 Relay TRIP Relay GENERAL TRIP command OUT I X
00561 Man.Clos.Detect Manual close signal detected OUT IO
04601 >Brk Aux NO >Breaker contact (OPEN, if bkr is open) SP IO
04602 >Brk Aux NC >Breaker contact(OPEN, if bkr is closed) SP IO
00126 ProtON/OFF Protection ON/OFF (via systemport) IntSP IO
6 DMT / IDMT Phase/Earth Overcurrent
DMT / IDMT Phase/Earth Overcurrent
No. D L T BI F S C BO LEDs O S T S C C D
01761 Overcurrent PU Time Overcurrent picked up OUT IO
01791 OvercurrentTRIP Time Overcurrent TRIP OUT U4 I
01704 >BLK Phase O/C >BLOCK Phase time overcurrent SP
01718 >BLOCK I>>> >BLOCK I>>> SP
01721 >BLOCK I>> >BLOCK I>> SP
01722 >BLOCK I> >BLOCK I> SP
01723 >BLOCK Ip >BLOCK Ip SP
01751 O/C Phase OFF Time Overcurrent Phase is OFF OUT IO
01752 O/C Phase BLK Time Overcurrent Phase is BLOCKED OUT IO IO
01753 O/C Phase ACT Time Overcurrent Phase is ACTIVE OUT IO
01762 O/C Ph L1 PU Time Overcurrent Phase L1 picked up OUT IO X
01763 O/C Ph L2 PU Time Overcurrent Phase L2 picked up OUT IO X
01764 O/C Ph L3 PU Time Overcurrent Phase L3 picked up OUT IO X
01767 I>>>picked up I>>>picked up OUT IO
01769 I>>>TRIP I>>>TRIP OUT I
01800 I>>picked up I>>picked up OUT IO
01805 I>>TRIP I>>TRIP OUT I X
01810 I>picked up I>picked up OUT IO
01815 I>TRIP I>TRIP OUT I
01820 Ip picked up Ip picked up OUT IO
01825 Ip TRIP Ip TRIP OUT I X
01787 I>>>Time Out I>>>Time Out OUT
01804 I>>Time Out I>>Time Out OUT
01814 I>Time Out I>Time Out OUT
01824 Ip Time Out Ip Time Out OUT
10034 I>>>BLOCKED I>>>BLOCKED OUT IO IO
01852 I>>BLOCKED I>>BLOCKED OUT IO IO
01851 I>BLOCKED I>BLOCKED OUT IO IO
7SJ642 V4_8_prn
Power System Data 2
SIMATIC Matrix - short view 18.09.12 11:25:03
Page 5 of 13
Power System Data 2(2)
CM
7SJ642 V4_8_prn
DMT / IDMT Phase/Earth Overcurrent
SIMATIC Matrix - short view 18.09.12 11:25:03
Page 6 of 13
DMT / IDMT Phase/Earth Overcurrent(3)
CM
7SJ642 V4_8_prn
DMT / IDMT Phase/Earth Overcurrent
SIMATIC Matrix - short view 18.09.12 11:25:03
Page 7 of 13
DMT / IDMT Phase/Earth Overcurrent(4)
No. D L T BI F S C BO LEDs O S T S C C D
01855 Ip BLOCKED Ip BLOCKED OUT IO IO
01714 >BLK Earth O/C >BLOCK Earth time overcurrent SP
01719 >BLOCK IE>>> >BLOCK IE>>> SP
01724 >BLOCK IE>> >BLOCK IE>> SP
01725 >BLOCK IE> >BLOCK IE> SP
01726 >BLOCK IEp >BLOCK IEp SP
01756 O/C Earth OFF Time Overcurrent Earth is OFF OUT IO
01757 O/C Earth BLK Time Overcurrent Earth is BLOCKED OUT IO IO
01758 O/C Earth ACT Time Overcurrent Earth is ACTIVE OUT IO
01765 O/C Earth PU Time Overcurrent Earth picked up OUT IO
01768 IE>>>picked up IE>>>picked up OUT IO
01770 IE>>>TRIP IE>>>TRIP OUT I
01831 IE>>picked up IE>>picked up OUT IO
01833 IE>>TRIP IE>>TRIP OUT I
01834 IE>picked up IE>picked up OUT IO
01836 IE>TRIP IE>TRIP OUT I
01837 IEp picked up IEp picked up OUT IO
01839 IEp TRIP IEp TRIP OUT L7 I X X
01788 IE>>>Time Out IE>>>Time Out OUT
01832 IE>>Time Out IE>>Time Out OUT
01835 IE>Time Out IE>Time Out OUT
01838 IEp TimeOut IEp Time Out OUT
10035 IE>>>BLOCKED IE>>>BLOCKED OUT IO IO
01854 IE>>BLOCKED IE>>BLOCKED OUT IO IO
01853 IE>BLOCKED IE>BLOCKED OUT IO IO
01856 IEp BLOCKED IEp BLOCKED OUT IO IO
IDMT O/C Rph IDMT O/C Rph Alarm OUT X L1 IO X X
IDMT O/C Wph IDMT O/C Wph Alarm OUT X L2 IO X X
IDMT O/C Bph IDMT O/C Bph Alarm OUT X L3 IO X X
IDMT Rph LED IDMT O/C Rph LED OUT X U1 IO
IDMT Wph LED IDMT O/C Wph LED OUT X U2 IO
IDMT Bph LED IDMT O/C Bph LED OUT X U3 IO
E/F IDMT LED E/F IDMT LED OUT X U7 IO
H/S O/C Rph H/S O/C Rph Alarm OUT X L4 IO X X
H/S O/C Wph H/S O/C Wph Alarm OUT X L5 IO X X
H/S O/C Bph H/S O/C Bph Alarm OUT X L6 IO X X
H/S Rph LED H/S O/C Rph LED OUT X U4 IO
H/S Wph LED H/S O/C Wph LED OUT X U5 IO
H/S Bph LED H/S O/C Bph LED OUT X U6 IO
7SJ642 V4_8_prn
DMT / IDMT Phase/Earth Overcurrent
SIMATIC Matrix - short view 18.09.12 11:25:03
Page 8 of 13
7 Measurement Supervision
Measurement Supervision
No. D L T BI F S C BO LEDs O S T S C C
00253 VT brk. wire Failure VT circuit: broken wire OUT IO X
00255 Fail VT circuit Failure VT circuit OUT IO X
00256 VT b.w. 1 pole Failure VT circuit: 1 pole broken wire OUT IO X
00257 VT b.w. 2 pole Failure VT circuit: 2 pole broken wire OUT IO X
00258 VT b.w. 3 pole Failure VT circuit: 3 pole broken wire OUT IO X
00169 VT FuseFail>10s VT Fuse Failure (alarm>10s) OUT IO
00170 VT FuseFail VT Fuse Failure (alarminstantaneous) OUT IO
00162 Failure SumI Failure: Current Summation OUT IO
00163 Fail I balance Failure: Current Balance OUT IO
00167 Fail U balance Failure: Voltage Balance OUT IO
00161 Fail I Superv. Failure: General Current Supervision OUT IO
00171 Fail Ph. Seq. Failure: Phase Sequence OUT IO
00176 Fail Ph. Seq. U Failure: Phase Sequence Voltage OUT IO
00175 Fail Ph. Seq. I Failure: Phase Sequence Current OUT IO
00197 MeasSup OFF Measurement Supervision is switched OFF OUT IO
06509 >FAIL:FEEDER VT >Failure: Feeder VT SP IO
06510 >FAIL: BUS VT >Failure: Busbar VT SP IO
8 TX Alarms
TX Alarms
No. D L T BI F S C BO LEDs O S T S C C D CM
TX Buchhol TX Buchholz Trip SP H2 U4 IO X X
TX NEC TX NEC Pressure Trip SP IO X
TX TCH TX Tap Changer Trip SP H3 U4 IO X X
TX WindTem TX Oil Temperature Trip SP IO X
TX Buch Al TX Buchholz Alarm SP H8 IO X X
TX Wind Al TX Winding Temperature Alarm SP H9 IO X X
TX TCH Oil TX Tap Changer Oil Level Alarm SP IO X
TX BuchholzL TX Buchholz Trip Latch OUT X IO X
TX NECL TX NEC Pressure Trip Latch OUT X IO
TX TCHL TX Tap Changer Trip Latch OUT X IO X
TX WTITempL TX Oil Temperature Trip Latch OUT X IO
TX Buch AlL TX Buchholz AlarmLatch OUT X IO X
TX Wind AlL TX Winding Temperature AlarmLatch OUT X IO X
TX Oil levelL TX Oil Level AlarmLatch OUT X IO
9 General Alarms
General Alarms
No. D L T BI F S C BO LEDs O S T S C C D CM
Trip Relay Trip Relay Alarm SP H5 IO X
7SJ642 V4_8_prn
Measurement Supervision
SIMATIC Matrix - short view 18.09.12 11:25:03
Page 9 of 13
Measurement Supervision(2)
D CM
7SJ642 V4_8_prn
General Alarms
SIMATIC Matrix - short view 18.09.12 11:25:03
Page 10 of 13
10 LBU Intertrip
LBU Intertrip
No. D L T BI F S C BO LEDs O S T S C C D CM
LBU ITrip LBU Intertrip Received SP H6 U13 IO X X
11 TCS
TCS
No. D L T BI F S C BO LEDs O S T S C C D CM
TCS In TCS Input SP L20 IO X
TCS Al TCS Alarm OUT X L14 IO X X
TCS LED TCS LED OUT X U14 IO
12 Breaker Failure
Breaker Failure
No. D L T BI F S C BO LEDs O S T S C C D
01403 >BLOCK BkrFail >BLOCK Breaker failure SP IO
01431 >BrkFail extSRC >Breaker failure initiated externally SP H6 IO
01451 BkrFail OFF Breaker failure is switched OFF OUT IO
01452 BkrFail BLOCK Breaker failure is BLOCKED OUT IO IO
01453 BkrFail ACTIVE Breaker failure is ACTIVE OUT IO
01456 BkrFail int PU Breaker failure (internal) PICKUP OUT IO
01457 BkrFail ext PU Breaker failure (external) PICKUP OUT IO
01471 BrkFailure TRIP Breaker failure TRIP OUT I
01480 BkrFail intTRIP Breaker failure (internal) TRIP OUT I
01481 BkrFail extTRIP Breaker failure (external) TRIP OUT U5,U12 I X
01494 BkrFail TRIP 2 Breaker failure TRIP 2 OUT
LBU LED LBU LED OUT X U10 IO X X
13 Control Authorization
Control Authorization
No. D L T BI F S C BO LEDs O S T S C C D CM
Cntrl Auth Control Authority DP IO
ModeLOCAL Controlmode LOCAL DP IO
ModeREMOTE Controlmode REMOTE IntSP IO
7SJ642 V4_8_prn
LBU Intertrip
SIMATIC Matrix - short view 18.09.12 11:25:03
Page 11 of 13
14 Control Device
Control Device
No. D L T BI F S C BO LEDs O S T S C C D CM
Breaker Breaker CF_D12
Breaker Breaker DP IO
Disc.Swit. Disconnect Switch CF_D2
Disc.Swit. Disconnect Switch DP IO
EarthSwit Earth Switch CF_D2
EarthSwit Earth Switch DP IO
Brk Open Interlocking: Breaker Open IntSP
Brk Close Interlocking: Breaker Close IntSP
Disc.Open Interlocking: Disconnect switch Open IntSP
Disc.Close Interlocking: Disconnect switch Close IntSP
E SwOpen Interlocking: Earth switch Open IntSP
E SwCl. Interlocking: Earth switch Close IntSP
UnlockDT Unlock data transmission via BI IntSP
Q2 Op/Cl Q2 Open/Close CF_D2
Q2 Op/Cl Q2 Open/Close DP IO
Q9 Op/Cl Q9 Open/Close CF_D2
Q9 Op/Cl Q9 Open/Close DP IO
Fan ON/OFF Fan ON/OFF CF_D2
Fan ON/OFF Fan ON/OFF DP IO
15 Process Data
Process Data
No. D L T BI F S C BO LEDs O S T S C C D CM
>CB ready >CB ready Spring is charged SP
>DoorClose >Door closed SP
>Door open >Cabinet door open SP IO
>CB wait >CB waiting for Spring charged SP IO
>No Volt. >No Voltage (Fuse blown) SP IO
>Err Mot U >Error Motor Voltage SP IO
>ErrCntrlU >Error Control Voltage SP IO
>SF6-Loss >SF6-Loss SP IO
>Err Meter >Error Meter SP IO
>Tx Temp. >Transformer Temperature SP IO
>Tx Danger >Transformer Danger SP IO
16 Measurement
No information available
7SJ642 V4_8_prn
Control Device
SIMATIC Matrix - short view 18.09.12 11:25:03
Page 12 of 13
17 Set Poi nts (Measured Values)
Set Points (Measured Values)
No. D L T BI F S C BO LEDs O S T S C C D CM
00284 SP. I< Set Point I<alarm OUT IO
00285 SP. PF(55)alarm Set Point 55 Power factor alarm OUT IO
18 Energy
No information available
19 Statistics
Statistics
No. D L T BI F S C BO LEDs O S T S C C D CM
01020 Op.Hours= Counter of operating hours VI
00409 >BLOCK Op Count >BLOCK Op Counter SP IO
01021 SumL1 = Accumulation of interrupted current L1 VI
01022 SumL2 = Accumulation of interrupted current L2 VI
01023 SumL3 = Accumulation of interrupted current L3 VI
20 Set Poi nts (Statistic)
Set Points (Statistic)
No. D L T BI F S C BO LEDs O S T S C C D CM
00272 SP. Op Hours> Set Point Operating Hours OUT IO
21 Threshold-Switch
Threshold-Switch
No. D L T BI F S C BO LEDs O S T S C C D CM
ThreshVal1 Threshold Value 1 IntSP IO X
7SJ642 V4_8_prn
Set Points (Measured Values)
SIMATIC Matrix - short view 18.09.12 11:25:03
Page 13 of 13