SAI Active Universal for Bluetooth

Manual












Weidmller t

Bluetooth SAI Manual



2 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Contents


1. The SAIs 4
1.1. SAI 5
1.2. PROFIBUS-DP 6
1.3. Bluetooth 7
2. Project Planning and SAIs 8
2.1. Project planning 9
2.2. Power supply 10
3. Mounting the SAIs 11
3.1. Mounting dimensions and position 12
3.2. Mounting SAI distributors 13
3.3. Marking and labelling 14
3.4. Setting the PROFIBUS address 15
3.5. Setting the Bluetooth address 17
3.6. Dismounting the SAI 18
4. Connecting the SAI Distributor 19
4.1. PROFIBUS / RS-485 20
4.2. SAI-AU M12 GW PB/BT 12I 22
4.3. SAI-AU M12 BT 16DI 28
4.4. SAI-AU M12 BT 16DI/8DO 34
4.5. SAI-AU M12 BT 4AI2AO2DIO 42
5. Initial Commissioning 50
5.1. Device Data Base Files (GSD) and bitmap files 51
5.2. Copy the GSD files to the local directory 52
5.3. Install the GSD files in Step7 53
5.4. Adding a BT-GW in the hardware configurator 55
5.5. Assigning the input and output addresses 57
5.6. Configuration and setting parameters 58
5.7. SAI parameter data 59
6. Diagnosis 63
6.1. LED displays 64
6.2. Diagnostic telegrams 67
6.3. Evaluating diagnostic data in Step7 76
Appendix A: Product Overview 78
Appendix B: Drilling Templates 81
Appendix C: Converting from Hexadecimal to Decimal 82
Appendix D: Configuration of the DESINA inputs 83
Appendix E: Configuration of the digital connection points 84
Appendix G: Configuration of analogue outputs 85
Sources 86
Index 87
Glossary 90

1073380000/1.3/08.09 Weidmller t 3

Bluetooth SAI Manual

1. The SAIs

The SAIs

1.1 SAI


4

1.2 PROFIBUS-DP


6

1.3. Bluetooth


7
This chapters explains

the characteristics and operating
principle of SAIs
PROFIBUS-DP and its master/
slave structure
the Bluetooth subsystem

4 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
1073380000/1.3/08.09 Weidmller t 5
1.1. SAI
The SAI consists of the following components: The acronym SAI stands for Sensor Actuator Interface.
It is a compact-designed distributor and collector of
signal lines.
An I/O section: to connect the signal lines.
A settings section:
to set the network addresses and insert the jump-
ers for the different electric potentials.
Signals to and from the process in field installations are
often controlled from a central point, for example, by a
PLC or industrial PC. Typically, the distance between
the installation and the central controls is significant.
The resulting costs for installation and materials for the
cabling are high. This in turn increases the susceptibility
of the system to interference and errors.
A bus / power section: for the connection and loop
through for the supply voltage as well as the bus
connection.

Weidmller offers the following I/O versions:
M12 16DI with 16 digital inputs.

M12 16DI / 8DO with 8 fixed digital inputs and 8
individually configurable inputs or outputs.
The use of SAIs has proven successful under numer-
ous conditions:

The signal lines of the peripheral devices are bun-
dled together at the process in the installation and
connected to a bus.

In addition, Weidmller also offers:
Network components for the Fieldbus systems
mentioned above
Signal lines are connected simply and conveniently
by means of Plug and Play.
Sensor / valve connector cables
The controls are at a central point
Plug-in connectors and twin-plugs
The reliability of the data transfer is guaranteed by
a bus system.
Tools





I/O section
Settings section
Bus / power section
Figure 1: Basic design of an SAI distributor

Bluetooth SAI Manual

1.2. PROFIBUS-DP

PROFIBUS
PROFIBUS (PROcess Field BUS) is a part of the in-
ternational IEC 61158 and IEC 61784 standards.
Physically, PROFIBUS is either an electrical network
based on a shielded, two-conductor cable or an optical
network based on a fibre optics cable. PROFIBUS-DP
(DP =Decentralised Periphery) is a special application
for automating factory production.

System
A typical PROFIBUS-DP system is made up of:
At least one PLC or industrial PC (master) operat-
ing as a control system.
Various field devices, such as digital or analogue
I/O devices, AC or DC drives, magnetic or pneu-
matic valves, frequency converters, starters, oper-
ating and indicating devices (slaves).

Data transfer
Data exchange within the system is carried out by
means of cyclic polling. The master establishes com-
munications with one slave at a time and makes data
available and/or requests data. The slave being ad-
dressed responds immediately to the request for data.
Once completed, this procedure is repeated with the
other slave devices. This is a continuous cyclic process.
GSD files (device database files)
The GSD file is the obligatory ID card of each and
every PROFIBUS device. It contains the characteristic
data of the device, details about its communication
capabilities as well as other information, such as diag-
nostic values.
Weidmller has made available for downloading all
GSD files of the SAI distributors from the SAI Active
Universal series at: http://www.weidmueller.com.
For more information, please refer to Chapter 5 (Com-
missioning).





Figure 2: Basic PROFIBUS system configuration
6 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
1.3. Bluetooth
Bluetooth
Bluetooth defines a universal wireless interface in the
2.4 GHz ISM band. No license is required for the 2.4
GHz ISM band. Users are not required to register or
pay usage fees.

The acronym ISM stands for Industrial Scientific Medi-
cal and describes the potential scope of its use. A
range between 10 metres to 100 metres is defined
because of Bluetooth's minimal transmitting power of a
few milliwatts.

System
A Bluetooth system consists of a maximum of 255
nodes. From these however, only 8 can be simultane-
ously connected to each other.
The Weidmller Bluetooth SAIs are formed from Picon-
ets consisting of one master and six slaves. Thirty-two
of these Piconets can be operated in parallel.

The Bluetooth master, which functions as the
PROFIBUS gateways, is simultaneously a slave in the
PROFIBUS system. The PROFIBUS master views it as
a standard PROFIBUS slave with a modular I/O con-
figuration. The Bluetooth gateway can be configured
with a GSD file.

Protocol
The standard Bluetooth profile is used. The communi-
cation protocol then uses this. The implementation is
based on the CANopen / WIRELESSopen standards.






Figure 3: Basic PROFIBUS system configuration with subordinate Bluetooth
Slave (1)
Slave (6)
Bluetooth SAIs
Gateway

PLC
PROFIBUS
1073380000/1.3/08.09 Weidmller t 7

Bluetooth SAI Manual

2. Project Planning and SAIs

Project Planning and SAIs

2.1 Project planning


9


2.2 Power supply


10
8 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
2.1. Project planning
Planning the bus system

The following steps must be taken into consideration when designing an installation:

Location of the machine or facility
Assignment of the signals to the installation to a logical group
Selection of the field devices
Assignment of the signals to the field devices
Determination of where the field devices are to be installed



Criteria for determining the correct SAI distributor:


Size of the connec-
tors
Determine the size of the connectors to suit your application, the design of the sen-
sors or according to your personal preferences. Weidmller offers both M12 and M8
variants for purely digital signals
Number of poles of
the I/O connections
Please consider the sensor/actuator cable to be connected; possible options are 3
or 5 poles
Y-piece (twin) Specifically for 5-pole M12 sensor connections, you can feed two cables to a dis-
tributor input by means of a Y-piece.
Inputs / outputs Weidmller has a variety of SAI distributors on offer such as a variant with 16 digital
inputs, with mixed digital inputs/outputs as well as an analogue/digital version (for
more information please refer to Chapter 4 (Connecting SAIs).
Shielding Shielding by means of metal connectors is necessary for bus connections. We rec-
ommend the same approach for analogue signals to restrict the susceptibility to
interference.
Signals Please consider if you wish to transmit analogue or digital signals.
Table 1: Determining the SAI distributor



For more information, please refer to
Appendix A: Overview of articles to determine
correct selection of products.

1073380000/1.3/08.09 Weidmller t 9

Bluetooth SAI Manual

10 Weidmller t 1073380000/1.3/08.09
2.2. Power supply
Example calculation to determine voltage drop in
the lines:
Star or line topology wiring can be used to feed the
power supply. Only modules without digital outputs are
suitable for line topology wiring.


Power is supplied via the plug in connection AUX IN;
power is fed to the next module via the module connec-
tion AUX OUT.


Caution

The maximum current supplied to the first
module must not exceed 2.5 A per power
supply pin. The supply voltage at the last
module must not fall below 18 V DC.
When determining the maximum number of
modules in series you should take into con-
sideration the total current of all modules and
the voltage drop in the line.
Figure 4: Voltage drop

Voltage drop to module 1
(line resistance x length of line L1 x 2) x current con-
sumption
(Module 1 +Module 2+Module 3)
Voltage drop from module 1 to module 2
(line resistance x length of line L2 x 2) x current con-
sumption
Voltage drop in the lines:
(Line resistance) x (total length of line) x (2)
(Module 2 +Module 3)
Voltage drop from module 2 to module 3 Total current of the modules:
(line resistance x length of line L3 x 2) x current con-
sumption
Power consumption modules +total current of the con-
sumers
(Module 3)
Supply voltage to module 3
Input voltage voltage drop 1 voltage drop 2
voltage drop 3
Important:
The power supply to module 3 must be equal to or
greater than 18 V DC.

Calculation:
Max. current load per pin >max. number of input
modules
L1 L2 L3

Bluetooth SAI Manual
3. Mounting the SAIs

Mounting the SAIs

3.1 Mounting dimensions and position


12


3.2 Mounting SAI distributors


13


3.3 Labelling


14


3.4 Setting the PROFIBUS address


15


3.5 Setting the Bluetooth address


17


3.6 SAI disassembly


18
1073380000/1.3/08.09 Weidmller t 11

Bluetooth SAI Manual

12 Weidmller t 1073380000/1.3/08.09
3.1. Mounting dimensions and position
Note

Please observe that a given distance to the
adjacent module may be required when
using custom assembly and angled connec-
tors.


An SAI distributor can be mounted in any position.
There are no restrictions placed with regard to their
position when being mounted: vertical, horizontal, on
their side, or overhead. However, to ensure that the
LEDs can be seen, we recommend that where possi-
ble the modules are not mounted on their side or
overhead. Our SAIs can be mounted side by side.
The mounting dimensions of our SAI distributors are
210 x 54 mm.


You can find details about the mounting di-
mensions in Appendix B: Drilling Templates.












Figure 5: Mounting dimensions for the SAI Active Uni-
versal



















Bluetooth SAI Manual
3.2. Mounting SAI distributors
Mounting
To mount the SAI distributor, select a firm and level
surface. Pre-drill the bore holes (for more information,
please refer to Appendix B: Drilling Template). Hold the
distributor above the bore holes and fix it in positions
with screws. Please use a spring washer if the SAI
distributor is to be used in an environment where the
loads are subject to increased shock and vibration.
Please refer to Figure 5: Mounting dimensions for the
SAI Active Universal.

PROFIBUS guidelines
Please observe the PROFIBUS guidelines: Installation
Guideline for PROFIBUS-DP/FMS.


Figure 6: Mounting an SAI distributor
DANGER

Isolate (de-energize) the system before con-
necting the power-supply connector or insert-
ing or removing jumpers.

Torque
We recommend the following torques:
M8 connector: 0.6 Nm
M8 protective cap: 0.4 Nm
M12 connector: 0.8 Nm
M12 protective cap: 0.8 Nm
Screw for window: 0.5 Nm
Functional earth (FE)
The functional earth is the earthing (ground) of equip-
ment to its surroundings. Contrary to the protective
earth (PE) the FE does not primarily serve to protect
equipment or persons, but instead serves to discharge
electrostatic charges and shield connections.

Caution

Electromagnetic pulses affect cabling and
the distributor during operations. Flawed
signals and false data can result.
Do not use a PE conductor for the FE con-
nection.

SAI distributors from the SAI Active Universal series are
equipped with an FE connection integrated at the
mounting hole in the bus/power section. Use this con-
nection and fix the distributor directly to a conductive
surface or attach a short, low impedance FE cable to
the fixing screw by means of a cable lug. Please refer
to Figure 6: Mounting an SAI distributor.


Figure 7: Functional earth FE connection
Required accessories / DIN components
2 socket-head cap screws, M4 x 30
We recommend cylinder head studs with hexagon-
socket or Torx type.

Tools
Allen key or Torx screwdriver appropriate to the screw
you choose. For more information, please refer to Ap-
pendix A: Overview of items - Recommended tools.
1073380000/1.3/08.09 Weidmller t 13

Bluetooth SAI Manual

3.3. Marking and labelling
Twenty transparent markers in a MultiCard frame are included in the range of supply of the SAI distributors. These allow
you to individually mark the I/O connections as well as the distributor. Either two normal or one longer marker can be
used to specifically mark the distributor. Please refer to the following graphic Figure 8: Attaching the markers.

Weidmller has various printers and plotters available to achieve professional printing results. For advice and a demon-
stration, please contact your Weidmller partner.


To achieve rapid, manual on-site marking
results, we recommend our STI-S fibre pen
(please refer to Appendix A: Overview of
items).







Figure 8: Attaching markers and tags
Note

Please note that you should not stick marker
tags on top of one another. Nor should you
use coloured markers since they can cover
up the LEDs below them.






































14 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
3.4. Setting the PROFIBUS address
PROFIBUS address
The PROFIBUS address is used to determine at which
address your SAI distributor will be identified on
PROFIBUS-DP.

Setting
Set the PROFIBUS-DP address for the SAI distributor
in the settings section of the distributor. Use a flat-
bladed screwdriver to adjust the rotary switch.

Tools
Use a 2.5-mm flat-bladed screwdriver (please refer to
Appendix A: Overview of items).

Address / hexadecimal code
Please note that PROFIBUS-DP allows a maximum of
126 possible addresses. The addresses 1 to 125 are
defined. Please note that the address 126 is used for
configuration purposes and the addresses 01 and 02
are retained for the PROFIBUS master. The distributor
address is set in hexadecimal code by means of two
rotary coding switches. To do so, you will have to con-
vert the decimal address to hexadecimal or, for the
sake of simplicity, you could make use of the table
below.
Example:
To set the PROFIBUS-DP address 93, turn the left-
hand rotary coding switch to position 5 and the right-
hand rotary coding switch to position D.

Note

Each address must be allocated only once
on PROFIBUS-DP. The PROFIBUS address
that you set must match the PROFIBUS
address for this distributor set in the project
configuration software.

If you alter a PROFIBUS address during
operations you will have to disconnect the
power supply and then restart the system to
enable the master to recognise the change.








Table 2: Code conversion decimal <- >hexadecimal

1073380000/1.3/08.09 Weidmller t 15

Bluetooth SAI Manual

- Master:

The rotary switches are used for setting the Profibus
address network.


The switches are used for setting the Bluetooth network.
Set the rotary switch to position 1.

The sliding switch is used to define which networks are
to be set.
Slide the switch to position 1 in order to set the first 16
networks. Slide the switch to position ON in order to set
the next 16 networks (17 31).

- Slave:

The first rotary switch is used to set the slave's node
address. The second rotary switch is used for setting
the Bluetooth network. Set the rotary switch to position
1. The connection will be established within about 40
seconds.


Tools
Use a 2.5-mm flat-bladed screwdriver (please refer to
Appendix A: Overview of items).

Address / hexadecimal code
The distributor address is set in hexadecimal code by
means of two (or three) rotary coding switches. To do
so, you will have to convert the decimal address to
hexadecimal or, for the sake of simplicity, you could
make use of Table 2.

















































16 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
3.5. Setting the Bluetooth address
Note

Each Bluetooth address can occur only once
with a Piconet. The defined network address
must be identical with a network.

If you alter a Bluetooth address during op-
erations you will have to disconnect the
power supply and then restart the system to
enable the master to recognise the change.


Bluetooth address
The Bluetooth address is used to determine at which
address your SAI distributor will be identified from the
Bluetooth master. The Bluetooth address consists of a
node address and a network address.


Slave address
The slave address defines the location (address) of the
participant within the Piconet. Each slave address can
occur only once within a Piconet. The Bluetooth gate-
way always uses the node address 0; this cannot be
adjusted.


Network address
The network address defines the Piconet which the SAI
should be connected to. The settings on the SAI and
the Piconet gateway must be identical.




Setting
Set the address for the SAI distributor in the settings
section of the distributor. Use a flat-bladed screwdriver
to adjust the rotary switch.






















































1073380000/1.3/08.09 Weidmller t 17

Bluetooth SAI Manual

3.6. Dismounting the SAI
DANGER

Never plug in or pull out a power connector
or jumpers when the system is live (ener-
gized). Turn off the power supply to the sys-
tem first.

Caution

No immediate damage will occur to the de-
vice if you dismount an SAI distributor when
the system is operating.

However, the disruption to PROFIBUS will
place the rest of the plant in an uncontrolled
state. This can lead to indirect damage.
Disconnect the power to the system before
you mount or take off the distributor.


Dismounting
Turn off the power supply to the system.
Disconnect the connections to the power supply on
the SAI distributor.
Disconnect the PROFIBUS connections on the SAI
distributor.
Disconnect the I/O connections.
Dismount the distributor by undoing the mounting
screws.

Tools
Use an Allen key or Torx screwdriver appropriate to the
screw you choose. For more information, please refer
to Appendix A: Overview of items - Recommended
tools.

18 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
4. Connecting the SAI Distributor

Connecting the SAI Distributor

4.1 PROFIBUS / RS-485


20


4.2 SAI SAI-AU M12 GW PB/BT 12I


22


4.3 SAI SAI-AU M12 BT 16DI


28


4.4 SAI SAI-AU M12 BT 16 DI/8DO


34


4.4 SAI SAI-AU M12 BT 4AI2AO2DIO


42

1071640000/1.3/08.09 Weidmller t 19

Bluetooth SAI Manual

4.1. PROFIBUS / RS-485
PROFIBUS is a universal, open, digital communication
system providing solutions for a wide spectrum of appli-
cations first and foremost in production and process
automation. PROFIBUS is a suitable solution for fast,
time-critical applications, as well as for complex com-
munications tasks. PROFIBUS communication is an-
chored in the international standards IEC 61158 and
IEC 61784.61158.

The criteria for its use and planning are defined in the
openly accessible guidelines available from the
PROFIBUS Users Organisation (PUO). These guide-
lines fulfil the demands on the part of the users for
multi-vendor and open solutions. That guarantees the
communication between devices of differing manufac-
tures without having to make prior adjustments.

Additional information is available under
www.profibus.com.

Connection
The following section pertains only to the SAI-AU M12
GW PB/BT 12I Bluetooth gateway.




Module connection from BUS IN
Contact system M12 male connector, 5-pole
Coding B
Pin assignment Pin 1: +5 V DC
Pin 2: Data A (green wire)
connected with
BUS-OUT Pin 2
Pin 3: GND
Pin 4: Data B (red wire)
connected with
BUS-OUT Pin 4


Pin 5: Shield
Table 3: Contact assignment (pin out) of the
PROFIBUS connector

Select the bus cable as cable type A in accordance with
IEC 61158. The PROFIBUS connection is made via a
5-pole M12 male connector (Bus IN) and a 5-pole M12
female connector (Bus OUT). Both connections are B-
coded. Use the "Bus In" connection to feed in signals
and "Bus Out" to route these forward.

In the SAI, male and female connectors are conduc-
tively connected. That enables the PROFIBUS to be
routed from SAI to SAI without the need for spur lines.

Note

It is possible to connect the SAI distributors
by means of a spur line for low transmission
rates up to 1500 Kbit/s. The total length of
the spur line must not exceed 6.6 meters.
The spur lines should be kept as short as
possible. Avoid the use of spur lines for baud
rates greater than 1500 Kbit/s.




Module connection from Bus OUT
Contact system M12 female connector, 5-pole
Coding B
Pin assignment Pin 1: +5 V DC
Pin 2: Data A (green wire)
connected with
BUS-OUT Pin 2
Pin 3: GND
Pin 4: Data B (red wire)
connected with
BUS-OUT Pin 4


Pin 5: Shield
Table 4: Contact assignment (pin out) of the
PROFIBUS female contact socket


20 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Bus termination
A reference voltage of 5 V DC is applied to both bus
connections. This voltage is isolated from the internal
system voltage and is applied exclusively to supply an
external bus connection with power. Install the termina-
tions at the physical beginning and end according to the
PROFIBUS standard EN 50170 using the following
values:


Figure 9: Bus termination wiring


Accessories:
Terminating resistor connector, PROFIBUS-DP in M12
connector
Type: SAIEND PM M12 5P B-COD
QTY.: 1
Order No.: 1784770000

Setting the transmission rate
The SAI recognises and adopts the transmission speed
which is being used on the bus. Any change to the
transmission speed on the bus will also be recognised
and adopted.
SAI distributors support all conventional baud rates.
Technical specifications
Fieldbus interface PROFIBUS-DP V0 according
to DIN EN 61158 certified by
the PUO
Protocol PROFIBUS IEC 61158
GSD file (Device
Data Base File)
Device-specific for each mod-
ule
Transmission RS485
Transmission me-
dium
Twisted pair
Separation of poten-
tials
Yes, to module electronics
Dielectric strength 500 V DC
Baud rates 9.6, 19.2, 45.45, 93.75, 187.5,
500, 1500, 3000, 6000, 12000
Kbit/s set automatically
Number of nodes Max. 32 in one segment; max.
127 with repeater
Range of bus ad-
dresses
0 to 126; recommended 2 to
125
Setting the bus ad-
dress
By means of two rotary coding
switches; Coding hexadecimal
Table 5: Technical data, PROFIBUS
1073380000/1.3/08.09 Weidmller t 21

Bluetooth SAI Manual

4.2. SAI-AU M12 GW PB/BT 12I
The SAI distributor Active Universal has the functions of
a decentralized I/O system. Each distributor is equipped
with module-specific actuator/sensor functions and a
Fieldbus interface.
The module combines the complete electronics in a
water- and dust-proof protected housing. This enables it
to be used in harsh environments.

The module SAI-AU M12 GW PB/BT 12I is designed to
connect 12 digital sensors with 6 M12 connectors.


Figure 10: SAI-AU M12 GW PB/BT 12I
LEDs:
BF PROFIBUS status indicator
BT Bluetooth communication
LQ Link quality (displays field
strength)
UI1 Supply voltage UI1
Supplies the module and the DI1,
DI3 and DI5 slots
UI2 Supply voltage UI2
Supplies the D12, DI4 and DI6
slots
UL Power supply to module Address
area illumination
DI1 to DI12 Digital inputs
Connections:
AUX IN Supply voltage UI1 and UI2
AUX OUT Feed through supply voltage UI1
and UI2
BUS IN PROFIBUS input
BUS OUT PROFIBUS output
1 to 6 Two digital inputs each
Rotary switch:
X1 PROFIBUS address low byte
X10 PROFIBUS address high byte
NA Bluetooth network address
Jumper field:
J 1 Switch/jumper for network ad-
dresses
Table 6: SAI-AU M12 GW PB/BT 12I


BF BT LQ UI1 UI2 - -
LED BF
LED BT
LED LQ
LED UI1
LED UI2
Unoccupied
Unoccupied
LED UL
(Illuminated
address area)


LED DI13 (PIN 2)



LED DI5 (PIN 4)



LED DI11 (PIN 2)



LED DI3 (PIN 4)



LED DI9 (PIN 2)



LED DI1 (PIN 4)

LED DI13 (PIN 2)



LED DI5 (PIN 4)



LED DI11 (PIN 2)



LED DI3 (PIN 4)



LED DI9 (PIN 2)



LED DI1 (PIN 4)

22 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual

PROFIBUS addressing
Two rotary switches in the address section of the SAI
are used to make the necessary bus address settings.
The setting is made in hexadecimal code from 00H to
7EH which corresponds to the decimal values from 0 to
126 (see also Appendix C: Converting decimal to hexa-
decimal, page 82).

Note
It is only possible to set the bus address in the address
section of the SAI. Any alterations made to the bus
address during operations will be recognised and
adopted following the next reset (turning off the power
supply).
The factory-set default bus address on the SAI is 03.




A table is available in the Appendix C to aid
conversion of decimal to hexadecimal ad-
dresses.


Figure 11: PROFIBUS address switch



1073380000/1.3/08.09 Weidmller t 23

Bluetooth SAI Manual

Setting the Bluetooth gateway address
The Bluetooth side of the gateway only needs to have a
network address specified. The node address at the
gateway is always 0 and cannot be changed. The rotary
switch NA and jumper J 1 are used to establish the
address and SAI address range.

The table on the right lists the exact functioning of the
net-selection switch (NA). Network addresses from 1 to
31 can be assigned.



Figure 12: Bluetooth address switch


Piconets Net-selection
switch (NA)
Jumper (J1)
1 1 1 (OFF)
2 2 1 (OFF)
3 3 1 (OFF)
4 4 1 (OFF)
5 5 1 (OFF)
6 6 1 (OFF)
7 7 1 (OFF)
8 8 1 (OFF)
9 9 1 (OFF)
10 A 1 (OFF)
11 B 1 (OFF)
12 C 1 (OFF)
13 D 1 (OFF)
14 E 1 (OFF)
15 F 1 (OFF)
16 0 ON
17 1 ON
18 2 ON
19 3 ON
20 4 ON
21 5 ON
22 6 ON
23 7 ON
24 8 ON
25 9 ON
26 A ON
27 B ON
28 C ON
29 D ON
30 E ON
31 F ON
Table 7: Bluetooth gateway addresses

Any combination not listed here will lead to an address
error and will be indicated by a continual red status LED.
Position 0 on the net-selection switch is never allowed
when you are working with the lower address range.

24 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Connection of supply voltage
The power supply is 24 V DC in accordance with EN
611312; the permissible range is 18 to 30 V DC. The
distributor is designed to offer protection against polar-
ity reversal.

Note

The power supply is connected via a 5-pole
A-coded M12 male connector and a 5-pole,
A-coded M12 female connector. Both power
supplies share a common earth and are not
electrically isolated.
Use the AUX In connection to feed in the
power supply and Bus Out to feed it for-
ward.


Module connection from AUX-IN
Contact system M12 male connector, 5-pole
Coding A
Pin assignment Pin 1: +24 V DC UI1
connected with
AUX-OUT Pin 1
Pin 2: +24 V DC UI2
connected with
AUX-OUT Pin 2
Pin 3: GND
Pin 4: GND

Pin 5: PE
Table 8: Contact assignment (pin out) of the power
supply connector


















Module connection from AUX OUT
Contact system M12 female connector, 5-pole
Coding A
Pin assignment Pin 1: +24 V DC UI1
connected with
AUX-IN Pin 1
Pin 2: +24 V DC UI2
connected with
AUX-IN Pin 2
Pin 3: GND
Pin 4: GND

Pin 5: PE
Table 9: Contact assignment (pin out) of the female
power supply connector


The power rating per pin is max. 2.5 A. Both circuits supply the plug-in stations DI1 to DI6 and the module electronics as
follows:
UI1: supply voltage for one sensor at pin 1 from the plug-in slots 1, 3, 5 and 7 and the module electronics
UI2: supply voltage for one sensor at pin 1 from the plug-in slots 2, 4 and 6

1073380000/1.3/08.09 Weidmller t 25

Bluetooth SAI Manual

Connection of the digital inputs

Connection for two digital inputs
Contact system M12 female connector, 5-pole
Coding A
Pin 1: +24 V DC sensor volta-
ge
Pin 2: Input 2 or
diagnostics input
Pin 3: GND
Pin 4: Input 1
Pin assignment


Pin 5: PE
Table 10: Contact assignment of the digital inputs

Block diagram of the digital input
Input configuration, pins 2 and 4 from each M12 female
connector:


Figure 13: Block diagram of the digital input
Optical displays
The status of a digital input is shown with a yellow/red
LED.

LED IN: 0.0, 0.1, 0.2, 0.3, 0.4, 0.5, 1.1, 1.2, 1.3, 1.4,
1.5:
yellow: status of digital input from pin 4
red: short-circuit at 24 V DC sensor voltage pin 1

LED UI1:

green: Voltage 1 >18 V DC
red: Voltage 1 <18 V DC

LED UI2:
green: Voltage 2 >18 V DC
red: Voltage 2 <18 V DC

LED BT: Bluetooth communication
Flashing green: Search for SAIs
green: All configured SAIs found, communication
established
red: No SAIs found, no communication established

LED LQ: Link quality (displays field strength)
green: good reception
red: poor reception
Off: no connection

26 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Technical specifications
Power supply 24 V DC
Limit values 18 V DC to 30 V DC
Contact load 2.5 A per pin
Reverse polarity protection Yes
Current consumption Module: approx. 70 mA
Digital inputs 16 channels
Plug-in slots DI1, DI2, DI3, DI4, DI5 and DI6
Grouping Two groups per six channels, with common earth
Permissible input voltage 30 V DC to +30 V DC (protected against polarity reversal)
Input level Low <5 V DC, acc. to EN 61131-2 Type 1
Input level High >15 V DC acc. to EN 61131-2 Type 1
Input current Low <15 mA acc. to EN 61131-2 Type 1
Input current High 2 mA to 15 mA acc. to EN 61131-2 Type 1
Input filter 3 ms
Separation of potentials (electrical isola-
tion) to the module electronics
None
Display elements One yellow/red error/status LED per channel
General technical data:
Ambient temperature during operation 0 to +60 C, acc. to EN 61131-2
Ambient temperature during storage 25 to +85 C, acc. to EN 61131-2
Protection class IP65 / IP67
GSD file (Device Data Base File) WIAU0A75.GSD
Dimensions L x W x H, 210 x 54 x 52 mm
Weight 340 g
Article order number 1006980000
Article designation SAI-AU M12 GW PB/BT 12I
Table 11: Technical data for the SAI-AU M12 GW PB/BT 12I

1073380000/1.3/08.09 Weidmller t 27

Bluetooth SAI Manual

28 Weidmller t 1073380000/1.3/08.09
4.3. SAI-AU M12 BT 16DI
The SAI distributor Active Universal has the functions of
a decentralized I/O system. Each distributor is equipped
with module-specific actuator/sensor functions and a
wireless interface.
LEDs:
BT Bluetooth communication
LQ Link quality (displays field
strength)
UI1 Supply voltage UI1
Supplies the module and the plug-
in stations DI1, DI3, DI5 and DI7
UI2 Supply voltage UI2
Supplies the D12, DI4, DI6 and
DI8 slots
UL Power supply to module Address
area illumination
DI1 to DI16 Digital inputs
Connections:
AUX IN Supply voltage UI1 and UI2
AUX OUT Feed through supply voltage UI1
and UI2
1 to 8 Two digital inputs each
Rotary switch:
KA Bluetooth node address
NA Bluetooth network address
Jumper field:
J 1 J umper for the voltages UI1 and
UI2

The module combines the complete electronics in a
water- and dust-proof protected housing. This enables it
to be used in harsh environments.

The SAI-AU M12 BT 16DI module is designed to con-
nect 16 digital sensors with 8 M12 male connectors.




- BT LQ UI1 UI2 - -
Unoccupied
LED BT
LED LQ
LED UI1
LED UI2
Unoccupied
Unoccupied
LED DI15 (PIN 2)



LED DI7 (PIN 4)



LED DI13 (PIN 2)



LED DI5 (PIN 4)



LED DI11 (PIN 2)



LED DI3 (PIN 4)



LED DI9 (PIN 2)



LED DI1 (PIN 4)

LED DI15 (PIN 2)



LED DI7 (PIN 4)



LED DI13 (PIN 2)



LED DI5 (PIN 4)



LED DI11 (PIN 2)



LED DI3 (PIN 4)



LED DI9 (PIN 2)



LED DI1 (PIN 4)

LED UL
(Illuminated
address area)


Table 12: SAI-AU M12 BT 16DI


Figure 14: SAI-AU M12 BT 16DI

Bluetooth SAI Manual
Setting the Bluetooth address
Two rotary switches in the address section of the SAI
are used to make appropriate network address settings.

The table on the right lists the exact functioning of the
slave-selection switch (SA) and the net-selection switch
(NA). Node addresses ranging from 1 to 6 and network
addresses ranging from 1 to 31 can be specified.



Figure 15: Address switch


Network Slave-
selection
switch (SA)
Net-selection
switch (NA)
1 1..6 1
2 1..6 2
3 1..6 3
4 1..6 4
5 1..6 5
6 1..6 6
7 1..6 7
8 1..6 8
9 1..6 9
10 1..6 A (10)
11 1..6 B (11)
12 1..6 C (12)
13 1..6 D (13)
14 1..6 E (14)
15 1..6 F (15)
16 A..F (10..15) 0 +16
17 A..F (10..15) 1 +16
18 A..F (10..15) 2 +16
19 A..F (10..15) 3 +16
20 A..F (10..15) 4 +16
21 A..F (10..15) 5 +16
22 A..F (10..15) 6 +16
23 A..F (10..15) 7 +16
24 A..F (10..15) 8 +16
25 A..F (10..15) 9 +16
26 A..F (10..15) A (10) +16
27 A..F (10..15) B (11) +16
28 A..F (10..15) C( 12) +16
29 A..F (10..15) D (13) +16
30 A..F (10..15) E (14) +16
31 A..F (10..15) F (15) +16
BT LQ UI1 UI2
SA NA UL J 1
Table 13: Setting the Bluetooth address, SAI


Any combination not listed here will lead to an address
error and will be indicated by a continual red status LED.
Forbidden settings are: node numbers 0, 7, 8, 9 and the
position 0 on the net-selection switch when you are
working with the lower address range.
1073380000/1.3/08.09 Weidmller t 29

Bluetooth SAI Manual

Connection of supply voltage
The power supply is 24 V DC in accordance with EN
611312; the permissible range is 18 to 30 V DC. The
distributor is designed to offer protection against polar-
ity reversal.









Module connection from AUX-IN
Contact system M12 male connector, 5-pole
Coding A
Pin assignment Pin 1: +24 V DC UI1
connected with
AUX-OUT Pin 1
Pin 2: +24 V DC UI2
connected with
AUX-OUT Pin 2
Pin 3: GND
Pin 4: GND

Pin 5: PE
Table 14: Contact assignment (pin out) of the power
supply connector





Note

The power supply is connected via a 5-pole
A-coded M12 male connector and a 5-pole,
A-coded M12 female connector. Both power
supplies share a common earth and are not
electrically isolated.
Use the AUX In connection to feed in the
power supply and Bus Out to feed it for-
ward.


Module connection from AUX OUT
Contact system M12 female connector, 5-pole
Coding A
Pin assignment Pin 1: +24 V DC UI1
connected with
AUX-IN Pin 1
Pin 2: +24 V DC UI2
connected with
AUX-IN Pin 2
Pin 3: GND
Pin 4: GND

Pin 5: PE
Table 15: Contact assignment (pin out) of the female
power supply connector
The power rating per pin is max. 2.5 A. Both circuits
supply the plug-in stations DI1 to DI8 and the module
electronics as follows:

UI1: supply voltage for one sensor at pin 1 from the plug-in slots 1, 3, 5 and 7 and the module electronics
UI2: supply voltage for one sensor at pin 1 from the plug-in slots 2, 4 6 and 8

Both voltages can be bridged at the plug-in jumper position using a jumper. The module will then be supplied from only
one voltage source.

Jumper field J1, jumper options
2 1* bridge voltage
UI2 and UI1


* Factory default
setting

1 1 parked jumper position

All other combinations are not
possible as pin 3 of this mod-
ule has no function.

Table 16: Plug-in jumper positions for the SAI-AU M12 BT 16DI
30 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Connection of the digital inputs


Connection for two digital inputs
Contact system M12 female connector, 5-pole
Coding A
Pin 1: +24 V DC sensor volta-
ge
Pin 2: Input 2 or
diagnostics input
Pin 3: GND
Pin 4: Input 1
Pin assignment


Pin 5: PE
Table 17: Contact assignment (pin out) of the digital
input




Block diagram of the digital input

Input wiring of pins 4 and 2 for each M12 female con-
nector:


Figure 16: Block diagram of the digital input

DESINA
DESINA is an abbreviation for DistributEd and Stan-
dardised INstAllation technology for machine tools and
manufacturing systems. DESINA describes the stan-
dardised process for electrical, hydraulic and pneumatic
installations for automatic machine tools and production
systems.
For further information, please visit www.desina.de.

Note

It is possible to monitor the sensor cable for
breakage by bridging the 24 V DC power
supply and the DESINA diagnostics input
with an adapter.
Optical displays
The status of a digital input is shown with a yellow/red
LED.













Figure 17: View of M12 16DI

LED IN1: 0.0, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7:
yellow: status of digital input from pin 4
red: Short-circuit at 24 V DC sensor voltage pin 1


LED IN2: 1.0, 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7:
yellow: status of digital input or DESINA input from
Pin 2
red: short-circuit at 24 V DC of the sensor voltage
Pin 1 or error message at DESINA input

LED UI1:
green: Voltage 1 >18 V DC
red: Voltage 1 <18 V DC

LED UI2:
green: Voltage 2 >18 V DC
red: Voltage 2 <18 V DC

LED BT: Bluetooth communication
Flashing blue: detectable for all masters
blue: not detectable, connection already estab-
lished
Flashing green: Comm. stopped, no answer to
polling
green: Operation, BT connection established

LED LQ: Link quality (displays field strength)
green: good reception
red: poor reception
Off: no connection






1073380000/1.3/08.09 Weidmller t 31

Bluetooth SAI Manual




Connection of sensors with diagnostics outputs in accordance with DESINA specifications













Figure 18: Sensors with DESINA


Depending on the type of sensor, the DESINA diagnostics functionality senses and reports wire breaks, connector inter-
face damage and defects in the electronics.

Connection of sensors with monitoring for wire breakage















Figure 19: Sensor without DESINA




32 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Technical specifications
Power supply 24 V DC
Limit values 18 V DC to 30 V DC
Contact load 2.5 A per pin
Reverse polarity protection Yes
Current consumption Module: approx. 70 mA
Digital inputs 16 channels
Plug-in slots DI1, DI2, DI3, DI4, DI5, DI6, DI7 and DI8
Grouping Two groups for each eight channels, with common earth
Permissible input voltage 30 V DC to +30 V DC (protected against polarity reversal)
Input level Low <5 V DC, acc. to EN 61131-2 Type 1
Input level High >15 V DC acc. to EN 61131-2 Type 1
Input current Low <15 mA acc. to EN 61131-2 Type 1
Input current High 2 mA to 15 mA acc. to EN 61131-2 Type 1
Input filter 3 ms
Separation of potentials (electrical isola-
tion) to the module electronics
None
Display elements One yellow/red error/status LED per channel
General technical data:
Ambient temperature during operation 0 to +60 C, acc. to EN 61131-2
Ambient temperature during storage 25 to +85 C, acc. to EN 61131-2
Protection class IP65 / IP67
Dimensions L x W x H, 210 x 54 x 52 mm
Weight 340 g
Article order number 1006940000
Article designation SAI-AU M12 BT 16DI
Table 18: Technical data for the SAI-AU M12 BT 16DI

1073380000/1.3/08.09 Weidmller t 33

Bluetooth SAI Manual

34 Weidmller t 1073380000/1.3/08.09
4.4. SAI-AU M12 BT 16DI/8DO
The SAI distributor Active Universal has the functions of a
decentralized I/O system. Each distributor is equipped with
module-specific actuator/sensor functions and a wireless
interface. The module combines the complete electronics in a
water- and dust-proof protected housing. This enables it to be
used in harsh environments.
LEDs:
BT Bluetooth communication
LQ

Link quality (displays field
strength)
UI Supply voltage UI
Supplies the module and the in-
puts
UQ1 Supply voltage UQ1
Power supply to the outputs 0.0
and 0.1
UQ2 Supply voltage UQ2
Power supply to the outputs 0.2
and 0.3
UQ3 Supply voltage UQ3
Power supply to the outputs 0.4 to
0.7
UL Power supply to module Address
area illumination
IO1 to IO16 Digital inputs
Connections:
AUX IN1 Supply voltage UI and UQ1
AUX IN2 Supply voltage UQ2 and UQ3
1 to 8 Two digital inputs each, or one
digital input and one DESINA
diagnostic input, or one digital
output and one digital input
Rotary switch:
KA Bluetooth node address
NA Bluetooth network address
Jumper field:
J 1 J umper for the voltages UQ1,
UQ2 and UQ3

The SAI-AU M12 BT 16DI/8DO module is designed to connect
16 digital sensors. Alternatively, up to eight channels can be
used as outputs. Of these, six outputs are designed for a load
current of 0.5A and two outputs for a load current of 2A.
The signals are connected via eight M12 plug-in connectors.




Figure 20: SAI-AU M12 BT 16DI/8DO

Table 19: SAI-AU M12 BT 16DI/8DO
Unoccupied
LED BT
LED LQ
LED UI
LED UQ1
LED UQ2
LED UQ3
LED DI15 (PIN 2)



LED DI7 (PIN 4)



LED DI13 (PIN 2)



LED DI5 (PIN 4)



LED DI11 (PIN 2)



LED DI3 (PIN 4)



LED DI9 (PIN 2)



LED DI15 (PIN 2)



LED DI7 (PIN 4)



LED DI13 (PIN 2)



LED DI5 (PIN 4)



LED DI11 (PIN 2)



LED DI3 (PIN 4)



LED DI9 (PIN 2)



LED DI1 (PIN 4)

LED DI1 (PIN 4)

- BT LQ UI UQ1 UQ2 UQ3
LED UL
(Illuminated
address area)



Bluetooth SAI Manual
Setting the Bluetooth slave address
Two rotary switches in the address section of the SAI
are used to make appropriate network address settings.

The table on the right lists the exact functioning of the
slave-selection switch (SA) and the net-selection switch
(NA). Node addresses ranging from 1 to 6 and network
addresses ranging from 1 to 31 can be specified.


Figure 21: Address switch

Note

The specified nodes correspond to the as-
signed plug-in slot on the slave.

Example:
Assigned slot 2
Address to be set: 27

Gateway setting:
J 1 =ON
NA =B
Slave setting:
SA =B
NA =B










Caution

Any combination not listed here will lead to
an address error and will be indicated by a
continual red status LED.
Forbidden settings are: node numbers 0, 7,
8, 9 and the position 0 on the slave-selection
switch when you are working with the lower
address range.

Piconets Slave-
selection
switch (SA)
Net-selection
switch (NA)
1 1..6 1
2 1..6 2
3 1..6 3
4 1..6 4
5 1..6 5
6 1..6 6
7 1..6 7
8 1..6 8
9 1..6 9
10 1..6 A
11 1..6 B
12 1..6 C
13 1..6 D
14 1..6 E
15 1..6 F
16 A..F 0
17 A..F 1
18 A..F 2
19 A..F 3
20 A..F 4
21 A..F 5
22 A..F 6
23 A..F 7
24 A..F 8
25 A..F 9
26 A..F A
27 A..F B
28 A..F C
29 A..F D
30 A..F E
31 A..F F
BT LQ UI UQ1 UQ2 UQ3
SA NA UL J 1
Table 20: Setting the Bluetooth address, SAI









1073380000/1.3/08.09 Weidmller t 35

Bluetooth SAI Manual

Connection of supply voltage
The power supply is 24 V DC in accordance with EN
611312; the permissible range is 18 to 30 V DC. The
distributor is designed to offer protection against polar-
ity reversal.










Module connection from AUX IN1
Contact system M12 male connector, 5-pole
Coding A
Pin assignment Pin 1: +24 V DC UI
Pin 2: +24 V DC UQ1
Pin 3: GND
Pin 4: GND

Pin 5: PE
Table 21: Contact assignment (pin out) of the power
supply connector
Note

The power supply is connected via a 5-pole
A-coded M12 male connector and a 5-pole,
A-coded M12 female connector.
Use the AUX In connection to feed in the
power supply and Bus Out to feed it for-
ward. Both power supplies share a common
earth and are not electrically isolated.





Module connection from AUX IN2
Contact system M12 male connector, 5-pole
Coding A
Pin assignment Pin 1: +24 V DC UQ2
Pin 2: +24 V DC UQ3
Pin 3: GND
Pin 4: GND

Pin 5: PE
Table 22: Contact assignment (pin out) of the power
supply connector

The current load per pin is a maximum of 2.5 A. The total current per module is 8A. The four circuits supply the three
output circuits, the sensor supplies and the module electronics as described below:
Voltage UI: 16 sensors at pin 1 from plug-in stations 1 to 8 and module supply
Voltage UQ1: one output driver with 0.5 A to 0.0 and one output driver with 2.0 A to 0.1
Voltage UQ2: one output driver with 0.5 A to 0.2 and one output driver with 2.0 A to 0.3
Voltage UQ3: four output drivers with 0.5 to 0.4, 0.5, 0.6 and 0.7

The three voltages for the output drivers can be connected together using jumpers at a plug-in jumper position.


Jumper field J1, jumper options
2 1 Bridge voltage
UQ1 and UQ2
3 1 Bridge voltage
UQ1 and UQ3
2 1 and
3 1*
Bridge voltage
UQ1, UQ2 and UQ3
2 3 Bridge voltage
UQ2 and UQ3

* Factory default
setting


Table 23: Plug-in jumper positions for the SAI-AU M12 BT 16DI/8DO
36 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Connection of the digital input


Connection for a digital input
Contact system M12 female connector, 5-pole
Coding A
Pin 1: +24 V DC sensor volta-
ge
Pin 2: Input 2 or
diagnostics input
Pin 3: GND
Pin 4: Input 1
Pin assignment


Pin 5: PE
Table 24: Contact assignment (pin out) of the digital
input


Block diagram of the digital input

Input wiring of pins 4 and 2 for each M12 female con-
nector:


Figure 22: Block diagram of the digital input

DESINA
DESINA is an abbreviation for DistributEd and Stan-
dardised INstAllation technology for machine tools and
manufacturing systems. DESINA describes the stan-
dardised process for electrical, hydraulic and pneumatic
installations for automatic machine tools and production
systems. For further information, please visit
www.desina.de.


Note

It is possible to monitor the sensor cable for
breakage by bridging the 24 V DC power
supply and the DESINA diagnostics input
with an adapter.



Optical displays
The status of a digital input is shown with a yellow/red
LED.













Figure 23: /A view of M12 16DI

LED IN1: 0.0, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7:
yellow: status of digital input from pin 4
red: Short-circuit at 24 V DC sensor voltage pin 1


LED IN2: 1.0, 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7:
yellow: status of digital input or DESINA input from
Pin 2
red: short-circuit at 24 V DC of the sensor voltage
Pin 1 or error message at DESINA input

LED UI1:
green: Voltage 1 >18 V DC
red: Voltage 1 <18 V DC

LED UI2:
green: Voltage 2 >18 V DC
red: Voltage 2 <18 V DC

LED BT: Bluetooth communication
Flashing blue: detectable for all masters
blue: not detectable, connection already estab-
lished
Flashing green: Comm. stopped, no answer to
polling
green: Operation, BT connection established

LED LQ: Link quality (displays field strength)
green: good reception
red: poor reception
Off: no connection
1073380000/1.3/08.09 Weidmller t 37

Bluetooth SAI Manual



Connection of sensors with diagnostics outputs in accordance with DESINA specifications













Figure 24: Sensor with DESINA

Depending on the type of sensor, the DESINA diagnostics functionality senses and reports wire breaks, connector inter-
face damage and defects in the electronics.

Connection of sensors with monitoring for wire breakage















Figure 25: Sensor without DESINA


38 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Block diagram of digital output















Figure 26: Block diagram of the digital outputs

















Figure 27: Assignment of the 0.5 A and 2 A outputs



Optical displays
The status of each connection group with two digital
inputs or with a digital input and a diagnostics input to
DESINA specifications is indicated by means of two
dual-coloured yellow/red LEDs.

LED I/O1: 0.0, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7:
yellow: status of digital input or digital output
from pin 4
red: short-circuit of 24 V DC sensor voltage pin 1
or short-circuit at the output on pin 4

LED DI2: 1.0, 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7:
yellow: status of digital input or DESINA input
from pin 2
red: short-circuit of 24 V DC sensor voltage pin 1
or error message at DESINA input

LED UI:
green: Voltage 1 >18 V DC
red: Voltage 1 <18 V DC

LEDs UQ1, UQ2, UQ3:
green: Voltage >18 V DC or
red: Voltage <18 V DC























Figure 28: I/O housing M12 16DI/8DO

















1073380000/1.3/08.09 Weidmller t 39

Bluetooth SAI Manual

Technical specifications
Power supply 24 V DC
Limit values 18 V DC to 30 V DC
Contact load 2.5 A per pin
Reverse polarity protection Yes
Current consumption Module: approx. 70 mA
Digital inputs 16 channels
Plug-in slots DI1, DI2, DI3, DI4, DI5, DI6, DI7 and DI8
Grouping Two groups for each eight channels, with common earth
Permissible input voltage 30 V DC to +30 V DC (protected against polarity reversal)
Input level Low <5 V DC, acc. to EN 61131-2 Type 1
Input level High >15 V DC acc. to EN 61131-2 Type 1
Input current Low <15 mA acc. to EN 61131-2 Type 1
Input current High 2 mA to 15 mA acc. to EN 61131-2 Type 1
Input filter 3 ms
Separation of potentials (electrical isolation) to
the module electronics
None
Display elements One yellow/red error/status LED per channel
Digital outputs 8 channels, 2 channels 2 A, 6 channels 0.5
Plug-in stations with 0.5 A I/O1, I/O3, I/O5, I/O6, I/O7, I/O8
Plug-in stations with 2 A I/O2, I/O4
Grouping One group for 8 channels with common earth
Driver type Highside
Total current UQ1, I/O1 and I/O2 2,5 A
Total current UQ2, I/O3 and I/O4 2,5 A
Total current UQ3, I/O5, I/O6, I/O7 and I/O8 2,5 A
Total current, module 8 A
Output voltage Low 0 V
Output voltage: UQ minus the on-state voltage of the damping diode
Switching capacity, resistive load Max. 100 Hz
Switching capacity, inductive load Max. 1 Hz
Switching capacity, lamp load: Max. 8 Hz
Short-circuit proof Yes, switch-off in case of short-circuit and error message
Short-circuit current at 25 C 1.4 A at 0.5 A outputs
Short-circuit current at 25 C 5.6 A at 2.0 A outputs
Separation of potentials (electrical isolation) to None
40 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
1073380000/1.3/08.09 Weidmller t 41
the module electronics
Display elements One yellow/red error/status LED per channel
General technical specifications
Ambient temperature during operation 0 to +60 C, acc. to EN 61131-2
Ambient temperature during storage 25 to +85 C, acc. to EN 61131-2
Protection class IP65 / IP67
Dimensions L x W x H, 210 x 54 x 52 mm
Weight 340 g
Article order number 1006930000
Article designation SAI-AU M12 BT 16DI/8DO
Table 25: Technical data for the SAI-AU M12 BT 16DI/8DO

Bluetooth SAI Manual
4.5. SAI-AU M12 BT
4AI2AO2DIO
The SAI distributor Active Universal has the functions of
a decentralized I/O system. Each distributor is equipped
with module-specific actuator/sensor functions and a
wireless interface. The module combines the complete
electronics in a water- and dust-proof protected housing.
This enables it to be used in harsh environments.
The SAI-AU M12 BT 4AI2AO2DIO module is used for
connecting four inputs with four M12 connectors; where
two each can be used as outputs.
Figure 29: SAI-AU M12 BT 4AI2AO2DIO
LEDs:
BT Bluetooth communication
LQ Link quality (displays field
strength)
UI1 Supply voltage UI1
Supplies the module and the plug-
in stations DI1, DI3, DI5 and DI7
UI2 Supply voltage UI2
Supplies the D12, DI4, DI6 and
DI8 slots
UL Power supply to module
Address area illumination
DIO0 to DIO1 Digital inputs / outputs
DI2 to DI3 Digital inputs
AI0 to AI3 Fault-LED for analogue inputs
AO0 to AO1 Fault-LED for analogue outputs
Connections:
AUX IN Supply voltage UI1 and UI2
AUX OUT Feed through supply voltage UI1
and UI2
1 to 8 Two digital inputs each
Rotary switch:
KA Bluetooth node address
NA Bluetooth network address
Jumper field:
J1 Jumper for the voltages
UI1 and UI2
Table 26: SAI-AU M12 BT 4AI2AO2DIO
42 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Setting the Bluetooth address
Two rotary switches in the address section of the SAI
are used to make appropriate network address settings.

The table on the right lists the exact functioning of the
slave-selection switch (SA) and the net-selection switch
(NA). Node addresses ranging from 1 to 6 and network
addresses ranging from 1 to 31 can be specified.



Figure 30: Address switch

















Caution

Any combination not listed here will lead to
an address error and will be indicated by a
continual red status LED.
Forbidden settings are: node numbers 0, 7,
8, 9 and the position 0 on the net-selection
switch when you are working with the lower
address range.


Networks Slave-
selection
switch
Net-selection
switch
1 1..6 1
2 1..6 2
3 1..6 3
4 1..6 4
5 1..6 5
6 1..6 6
7 1..6 7
8 1..6 8
9 1..6 9
10 1..6 A (10)
11 1..6 B (11)
12 1..6 C (12)
13 1..6 D (13)
14 1..6 E (14)
15 1..6 F (15)
16 A..F (10..15) 0 +16
17 A..F (10..15) 1 +16
18 A..F (10..15) 2 +16
19 A..F (10..15) 3 +16
20 A..F (10..15) 4 +16
21 A..F (10..15) 5 +16
22 A..F (10..15) 6 +16
23 A..F (10..15) 7 +16
24 A..F (10..15) 8 +16
25 A..F (10..15) 9 +16
26 A..F (10..15) A (10) +16
27 A..F (10..15) B (11) +16
28 A..F (10..15) C( 12) +16
29 A..F (10..15) D (13) +16
30 A..F (10..15) E (14) +16
31 A..F (10..15) F (15) +16
BT LQ UI1 UI2
SA NA UL J 1
Table 27: Setting the Bluetooth address, SAI

1073380000/1.3/08.09 Weidmller t 43

Bluetooth SAI Manual

Connection of supply voltage
The power supply is 24 V DC in accordance with EN
611312; the permissible range is 18 to 30 V DC. The
distributor is designed to offer protection against polarity
reversal.

Note

The power supply is connected via a 5-pole,
A-coded M12 male connector and a 5-pole,
A-coded M12 female connector.
Use the AUX In connection to feed in the
power supply and Bus Out to feed it for-
ward. Both power supplies share a common
earth and are not electrically isolated.


Module connection from AUX IN1
Contact system M12 male connector, 5-pole
Coding A
Pin assignment Pin 1: +24 V DC UI1 con-
nected to AUX OUT,
pin 1
Pin 2: +24 V DC UI2 con-
nected to AUX OUT,
pin 2
Pin 3: GND
Pin 4: GND

Pin 5: PE
Table 28: Contact assignment (pin out) of the power
supply connector


















Module connection from AUX OUT
Contact system M12 female connector, 5-pole
Coding A
Pin assignment Pin 1: +24 V DC UI
Pin 2: +24 V DC UQ1
Pin 3: GND
Pin 4: GND

Pin 5: PE
Table 29: Contact assignment (pin out) of the female
power supply connector

Power supply:
The power rating per pin is max. 2.5 A. Both circuits supply the plug-in stations DI1 to DI6 and the module electronics as
follows:
UI1: supply voltage for two sensors each, at pin 1 from the plug-in stations: 1, 3, 5, 7, 9, 11, 13, 15, and the module
electronics.
UI2: supply voltage for one sensor at pin 1 from the plug-in stations 2, 4, 6, 8, 10, 12, 14 and 16
Both voltages can be bridged at the plug-in jumper position using a jumper. The module will then be supplied from only
one voltage source.

Jumper field J1, jumper options
2 1* bridge voltage
UI2 and UI1


* Factory default
setting

1 1 parked jumper position

All other combinations are not
possible as pin 3 of this mod-
ule has no function.

Table 30: Plug-in jumper positions for the SAI-AU M12 BT 4AI2AO2DIO


44 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Connection for an analogue input
Contact system M12 male connector, 5-
pole
Coding A
Pin 1: +24 V DC
Sensor voltage
Pin 2: Analogue input
+
Pin 3: GND
Pin 4: Analogue output
current
Pin assignment


Pin 5: PE
Housing Shield
Table 31: Contact assignment (pin out) of the ana-
logue input


Connection for an analogue output
Contact system M12 female connector, 5-
pole
Coding A
Pin 1: +24 V DC, actuator
voltage
Pin 2: Analogue output
voltage
Pin 3: GND
Pin 4: Analogue output
current
Pin assignment



Pin 5: PE
Housing Shield
Table 32: Contact assignment (pin out) of an ana-
logue output


Block diagram of the analogue input



Figure 31: Block diagram of the analogue input

Block diagram of the analogue output



Figure 32: Block diagram of the analogue output


Connection for two digital inputs or for a digital
input with diagnostics input to DESINA specifica-
tions.
Contact system M12 female connector, 5-pole
Coding A
Pin assignment

PIN 1: +24 V DC sensor voltage
PIN 2: Input 2 or diagnostics
input
PIN 3: GND
PIN 4: Input 1 / output
PIN 5: E
Table 33: Contact assignment of the digital inputs

DESINA (www.desina.de)
DESINA is an abbreviation for DistributEd and Stan-
dardised INstAllation technology for machine tools and
manufacturing systems. DESINA describes the stan-
dardised process for electrical, hydraulic and pneumatic
installations for automatic machine tools and production
systems.
Block diagram of the digital input

Input wiring of pins 4 and 2 for each M12 female con-
nector:


Figure 33: Block diagram of the digital input

Note

It is possible to monitor the sensor cable for
breakage by bridging the 24 V DC power
supply and the DESINA diagnostics input
with an adapter.


1073380000/1.3/08.09 Weidmller t 45

Bluetooth SAI Manual

Optical displays
The status of a digital input is shown with a yellow/red
LED.


Figure 34: /A view of M12 4AI


















LED IN: DIO0 / DIO1
yellow: status of digital input from Pin 4
red: Short-circuit at 24 V DC sensor voltage pin 1


LED IN: DI2 / DI3
yellow: status of digital input or DESINA input from
Pin 2
red: short-circuit at 24 V DC of the sensor voltage
Pin 1 or error message at DESINA input

LED AI0, AI1, AI2, AI3:
red: Range Fault

LED AO0, AO1:
red: Range Fault

LED UI1:
green: Voltage 1 >18 V DC
red: Voltage 1 <18 V DC

LED UI2:
green: Voltage 2 >18 V DC
red: Voltage 2 <18 V DC

LED BT: Bluetooth communication
Flashing blue: detectable for all masters
blue: not detectable, connection already estab-
lished
Flashing green: Comm. stopped, no answer to
polling
green: Operation, BT connection established

LED LQ: Link quality (displays field strength)
green: good reception
red: poor reception
Off: no connection
46 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Connection of sensors with diagnostics outputs in
accordance with DESINA specifications













Figure 35: Sensors with DESINA


Depending on the type of sensor, the DESINA diagnos-
tics functionality senses and reports wire breaks, con-
nector interface damage and defects in the electronics.

Connection of sensors with monitoring for wire
breakage















Figure 36: Sensors without DESINA



1073380000/1.3/08.09 Weidmller t 47

Bluetooth SAI Manual

48 Weidmller t 1073380000/1.3/08.09
Technical specifications
Power supply 24 V DC
Limit values 18 V DC to 30 V DC
Contact load 2.5 A per pin
Reverse polarity protection Yes
Current consumption Module: approx. 70 mA
Digital inputs
Plug-in slots DI1, DI1, DI2, DI3,
Grouping One groups for each two channels, with common earth
Permissible input voltage 30 V DC to +30 V DC (protected against polarity reversal)
Input level Low <5 V DC, acc. to EN 61131-2 Type 1
Input level High >15 V DC acc. to EN 61131-2 Type 1
Input current Low <15 mA acc. to EN 61131-2 Type 1
Input current High 2 mA to 15 mA acc. to EN 61131-2 Type 1
Input filter 3 ms
Separation of potentials (electrical isola-
tion) to the module electronics
None
Display elements One yellow/red error/status LED per channel
Digital outputs
Plug-in slots DO0, DO1
Grouping 1 Gruppe fr 2 Kanle mit gemeinsamer Masse
Driver type Highside
Total current UI1 2,5 A
Total current module 2,5 A
Output voltage Low 0 V
Output voltage High UQ minus the on-state voltage of the damping diode
Switching capacity, resistive load max. 100 Hz
Switching capacity, inductive load max. 1 Hz
Switching capacity, lamp load max. 8 Hz
Short-circuit proof Yes, switch-off in case of short-circuit and error message
Short-circuit current at 25 C 1,4 A bei 0,5 A Ausgngen
Short-circuit current at 25 C 5,6 A bei 2,0 A Ausgngen
Separation of potentials to the module
electronics
none
Indication elements One yellow/red error/status LED per channel
Analogue inputs

Bluetooth SAI Manual
Plug-in slots AI0, AI1, AI2, AI3
Limit values -10 V +10 V
Input type Differential measurement between pins 2 and 4
Sampling period 10 250 ms adjustable per analogue input
Accuracy <0.2 % of the upper limit of effective range
Offset error <0.1 % of the upper limit of effective range
Linearity <0,05 % of upper limit of effective range
Temperature coefficient <300 ppm/K of upper limit of effective range
Analogue outputs
Steckpltze AO0, AO1
Limit values - 10 V +10 V (PIN 2/3)
0 V +10 V (PIN 2/3)
4 20 mA (PIN 4/3)
0 20 mA (PIN 4/3)
Sampling period 5 250 ms adjustable per analogue input
Accuracy <0.2 % of the upper limit of effective range
Offset error <0.1 % of the upper limit of effective range
Linearity <0,05 % of upper limit of effective range
Temperature coefficient <300 ppm/K of upper limit of effective range
General technical specifications
Ambient temperature during operation 0 to +60 C, acc. to EN 61131-2
Ambient temperature during storage 25 to +85 C, acc. to EN 61131-2
Protection class IP65 / IP67
Dimensions L x W x H 210 x 54 x 52 mm
Weight 340 g
Article order number 1006920000
Article designation SAI-AU M12 BT 4AI2AO2DIO
Table 34: Technical data for the SAI-AU M12 BT 4AI2AO2DIO







1073380000/1.3/08.09 Weidmller t 49

Bluetooth SAI Manual

5. Initial Commissioning

Initial commissioning

5.1 Device Data Base Files (GSD) and bitmap files


51


5.2 Copy the GSD files to the local directory


52


5.3 Install the GSD files in Step7


53


5.4 Adding an SAI module in the hardware configurator


55


5.5 Assigning the input and output addresses


57


5.6 Configuring and setting parameters


58


5.7 SAI parameter data


59


50 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
5.1. Device Data Base Files (GSD) and bitmap files
GSD files (device database files)

GSD files are the electronic data sheets of a device that
provide a PROFIBUS master with straightforward in-
formation about the characteristics of the PROFIBUS
DP field device.

The information in these files includes:
The supported transmission rates
The length of the input and output data to be ex-
changed
The meaning of the diagnostics parameters and
the application parameters
The field device type
The supported services


The files are provided with the file extension gsd.

The following data is valid for the SAI-AU BT GW 12DI
PROFIBUS gateway:

ID number: 0A75
GSD file (device database file): WIAU0A75.GSD
Version: 14






Bitmap files
Symbols are made available for display in the hardware configurator. The name of the bitmap file for normal operations is
WIAU_BTN.DIB. The name of the bitmap file for diagnostics is WIAU_BTS.DIB.


WIAU_BTN.DIB WIAU_BTS.DIB
Figure 37: Bitmaps for hardware configurator


How the GSD and bitmap files are used and their memory location depends on the con-
figuration tool being used. Hardware configuration is explained below, based on an ex-
ample using the programming software Simatic

Step7.

Registered trademark of Siemens AG



1073380000/1.3/08.09 Weidmller t 51

Bluetooth SAI Manual

5.2. Copy the GSD files to the local directory
The GSD files are available for downloading free of
charge from Weidmllers homepage,
http://www.weidmueller.com/54266/Downloads/Softwar
e/SAI-Active-Data/cw_index.aspx?newsid=

The memory location of the GSD files is determined by
the installation routine of the Step7 programme. Usually,
this is below the installation directory
\Step7\S7DATA\GSD.

The necessary bitmap files are copied into the
\Step7\S7DATA\NSBMP directory.


52 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
5.3. Install the GSD files in Step7
Open the proper project in the programme Step7 and select the hardware configuration.


Figure 38: Installing the GSD file: step 1

Note

Close all Step7 applications before continu-
ing with the following commands.


Select the command Extras >Update Catalogue to update the contents of the catalogue in the hardware configurator.


Figure 39: Installing the GSD file: step 2


1073380000/1.3/08.09 Weidmller t 53

Bluetooth SAI Manual

When selecting the PROFIBUS-DB device, look under
PROFIBUS-DP => Additional field devices => Gateway => Bluetooth-Gateway for the Weidmller Bluetooth SAI modules.



Figure 40: GSD file catalogue




54 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
1073380000/1.3/08.09 Weidmller t 55
5.4. Adding a BT-GW in the hardware configurator
The hardware configuration with a PROFIBUS DP-
enabled central processing unit (CPU 315-2 DP) has
been launched and a PROFIBUS DP master system
has been defined for this CPU.
You can now add individual devices to the PROFIBUS
DP master system. A pop-up window opens in which
the PROFIBUS address can be assigned. You can set
parameters on the Parameter tabbed page.

Note

Assign each PROFIBUS address only once.



Figure 41: Hardware configurator

Bluetooth SAI Manual

The gateway which has been inserted now has slots
available for modules. Up to seven modules can be
added to these slots. A maximum of six devices can be
connected with Bluetooth. The seventh device or the
first device depicts 12 digital gateway inputs (digital
input: DI).

On PROFIBUS, these 12 DIs are connected via a 16-DI
identifier, since only a byte-by-byte assignment is pos-
sible.

An excerpt from a gateway is shown in the figure below.
In this example, all available module types are listed
once.
Note

According to the definition, the Gateway IOs
must occupy the first slot. No "holes" are
allowed in the slot list. The SAIs must be
listed in the proper order according to their
identifiers (node numbers).








Figure 42: The gateway slot list



These modules are stored in the GSD file. They are
assigned the application parameters in this file. There
are a total of four modules in the selection list: the
Gateway-IOs 12DI, a SAI 16DI, a SAI 16DI/8DO and a
SAI 4AI/2AO/4DI.

Note

The Universal Module is a Step7 attachment
and cannot be deleted.


Figure 43: Module types
56 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
5.5. Assigning the input and output addresses
Each PROFIBUS DP device is already automatically
assigned an address, with which data is exchanged
with the PLC programme.
You can accept or alter these addresses. The quickest
method is to double-click the address bar of the se-
lected device. Then it is possible to select the starting
address.




Figure 44: Assigning input / output addresses

1073380000/1.3/08.09 Weidmller t 57

Bluetooth SAI Manual

5.6. Configuration and setting parameters
The functionality for all modules is defined via one or several configuration bytes in the configuration menu. To access
this menu click Edit =>Object properties =>Configure properties.



Figure 45: Parameter

Refer to the following sub-section for details about module parameterization methods.



An overview of the diagnostics of the SAIs the
meaning of the diagnostics bytes is available in
Chapter 6.

58 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
5.7. SAI parameter data
Each SAI module is associated with specific parameters in the GSD file. The operator may alter these parameters.

SAI-AU M12 GW PB/BT 12I

With these module types, the user can activate the
DESINA configuration for each digital input. More on
the DESINA configuration can be found under [2].

SAI: SAI-AU M12 GW PB/BT
12I
Number of parameter
bytes:
5
First byte: 0xAA (frame separator)
Second byte: 0x0D (the number of pa-
rameter bytes which follow)
Third byte: 0x00 Activates the DESINA
function
Fourth byte: 0x14 Configuration of the
maximum transmit power
Fifth byte: 0x00 Activation of the
channel-specific diagnos-
tics, configuration of the
behaviour of the input data
in event of module loss
6 15 bytes: 0xFF Configuration of the
use for the Bluetooth chan-
nels
Table 35: Overview of the SAI parameters GW 12I

SAI-AU M12 BT 16DI
DESINA configuration is also available for this module.

SAI: SAI-AU M12 BT 16DI
Number of parameter
bytes:
5
First byte: 0xAA (frame separator)
Second byte: 0x03 (the number of pa-
rameter bytes which follow)
Third byte: Activates the DESINA
function
Fourth byte: 0x14 Configuration of the
maximum transmit power
Fifth byte: 0x00 reserved
Table 36: Overview of SAI parameters, 16DI

SAI-AU M12 BT 16DI/8DO
With this module type, the user also has the possibility
for DESINA configuration. In addition, the user can
specify the type (output or input) and specify a safe
status for each output.

SAI: SAI-AU M12 BT 16DI/8DO
Number of parameter
bytes:
8
First byte: 0xAA (frame separator)
Second byte: 0x06 (the number of pa-
rameter bytes which follow)
Third byte: 0x00 Activates the DESINA
function
Fourth byte: 0x00 Defines the function
of the connection points as
input or output
Fifth byte: 0x00 Defines how the out-
puts react when there is a
bus malfunction.
Sixth byte: 0x00 Defines the safe
status of outputs
Seventh byte: 0x14 Configuration of the
maximum transmit power
Eighth byte: reserved
Table 37: Overview of SAI parameters, 16DI/8DO





























1073380000/1.3/08.09 Weidmller t 59

Bluetooth SAI Manual

SAI-AU M12 BT 4AI2AO2DIO
With this module type, the user also has the possibility
for DESINA configuration. In addition, the user can
specify the type (output or input) for each digital input
and specify a safe status for each output.

SAI: SAI-AU M12 BT
4AI2AO2DIO
Number of parameter
bytes:
10
First byte: 0xAA (frame separator)
Second byte: 0x13 (the number of pa-
rameter bytes which follow)
Third byte: 0x00 Defines the meas-
urement range for the ana-
logue inputs
Fourth byte: 0x00 Defines the output
range for the analogue
inputs
Fifth byte: 0xFA Defines the conver-
sion time for the analogue
input channel 1
Sixth byte: 0xFA Defines the conver-
sion time for the analogue
input channel 2
Seventh byte: 0xFA Defines the conver-
sion time for the analogue
input channel 3
Eighth byte: 0xFA Defines the conver-
sion time for the analogue
input channel 4
Ninth byte: 0x00 reserved
Tenth byte: 0x00 reserved
Eleventh byte: 0x00 Defines how the ana-
logue outputs react when
there is a bus malfunction.
12th and 13th bytes: 0x00 Defines the safe
status of the analogue
output 1
14th and 15th bytes: 0x00 Defines the safe
status of the analogue
output 2
Sixteenth byte: 0x00 Activates the DESINA
function
Seventeenth byte: 0x00 Defines the function
of the connection point as
input or output
Eighteenth byte: 0x00 Defines how the digi-
tal outputs react when there
is a bus malfunction.
Nineteenth byte: 0x00 Defines the safe
status of the digital outputs
Twentieth byte: 0x14 Configuration of the
maximum transmit power
Twenty-first byte: 0x00 reserved
Table 38: Overview of SAI parameters, 4AI2AO2DIO




























































60 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Acti vates the DESINA function
Bits 0 to 7 set the DESINA diagnostics of the connec-
tions 1 to 8. The DESINA diagnostics functionality is
activated if the corresponding bit is set to 1. If the
DESINA diagnostic functionality is activated, the con-
nection at pin 4 acts as a DESINA diagnostics input.
The connection at pin 2 is then the switch input to be
monitored.

Bits 0 to 7 1 =DESINA functionality ON
Bits 0 to 7 0 =DESINA functionality OFF
Table 39: DESINA parameters




Defines the function of the connection point as
input or output
The input of bit 0 to bit 7 sets the functionality of pin 2 of
the connections 1 to 8 as well as 1 to 16 of the M8
connection. Setting this bit to 1 activates the output.
Set to this status, short-circuits to earth and +24 V DC
will be recognised and reported in the diagnostics.

Bits 0 to 7 1=connection pin 2 is INPUT
Bits 0 to 7 0=connection pin 2 is OUTPUT
Table 40: Reversal of input and output

Defines how the outputs react when there is a bus
malfunction.
The entries for Bit 0 to Bit 7 determine for each output if
it enters a safe status or if it retains the last status. If
this bit is set to 1, the output retains the last status that
prevailed before the bus error occurred. The safe status
is defined in byte 5

Bits 0 to 7 1 =OUTPUT goes into safe
status
Bits 0 to 7 0 =OUTPUT retains most recent
status
Table 41: Behaviour when bus malfunction occurs



Defines the safe status of outputs
The entries for Bit 0 to Bit 7 determine for each output if
it is ON or OFF when in the safe status.

Bits 0 to 7 1 =OUTPUT switches ON
Bits 0 to 7 0 =OUTPUT switches OFF
Table 42: Behaviour when bus malfunction occurs

1073380000/1.3/08.09 Weidmller t 61

Bluetooth SAI Manual

Configuration of the analogue inputs

The four analogue inputs are set with two bits respec-
tively.
The first bit defines the type of measurement as voltage
or current measurement; the second bit sets the meas-
urement range in accordance with the selected meas-
urement.

Bit 0 0 =analogue input 0 VOLTAGE measurement
1 =analogue input 0 CURRENT measurement
Bit 1 0 =analogue input 0 measurement range 0 to
10 V or 0 to 20 mA
1 =analogue input 0 measurement range
10 V to +10 V or 4 to 20 mA
Bit 2 0 =analogue input 1 VOLTAGE measurement
1 =analogue input 1 CURRENT measurement
Bit 3 0 =analogue input 1 measurement range 0 to
10 V or 0 to 20 mA
1 =analogue input 1 measurement range
10 V to +10 V or 4 to 20 mA
Bit 4 0 =analogue input 2 VOLTAGE measurement
1 =analogue input 2 CURRENT measurement
Bit 5 0 =analogue input 2 measurement range 0 to
10 V or 0 to 20 mA
1 =analogue input 2 measurement range
10 V to +10 V or 4 to 20 mA
Bit 6 0 =analogue input 3 VOLTAGE measurement
1 =analogue input 3 CURRENT measurement
Bit 7 0 =analogue input 3 measurement range 0 to
10 V or 0 to 20 mA
1 =analogue input 3 measurement range
10 V to +10 V or 4 to 20 mA
Table 43: Configuration of the analogue inputs


Configuration of the analogue outputs

The type of signals of the two analogue outputs (as
current or voltage output) is determined by the selection
of the connection pin and the configuration. The meas-
urement range is configured in accordance with the
selected output type.

Bit 0 0 =analogue output 0 VOLTAGE measure-
ment
1 =analogue output 0 CURRENT measure-
ment
Bit 1 0 =analogue output 0 measurement range 0
to 10 V or 0 to 20 mA
1 =analogue output 0 measurement range
10 V to +10 V or 4 to 20 mA
Bit 2 0 =analogue output 1 VOLTAGE measure-
ment
1 =analogue output 1 CURRENT measure-
ment
Bit 3 0 =analogue output 1 measurement range 0
to 10 V or 0 to 20 mA
1 =analogue output 1 measurement range
10 V to +10 V or 4 to 20 mA
Bit 4 Not used
Bit 5 Not used
Bit 6 Not used
Bit 7 Not used
Table 44: Configuration of the analogue outputs

62 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
6. Diagnosis

Diagnosis

6.1 LED displays


64


6.2 Diagnostic telegrams


67


6.3 Evaluating diagnostic data in Step7


76


1073380000/1.3/08.09 Weidmller t 63

Bluetooth SAI Manual

6.1. LED displays
Assignment of the PROFIBUS, Bluetooth and supply voltage LEDs


SAI-AU M12 GW PB/BT 12I




SAI-AU M12 BT 16DI
SAI-AU M12 BT AI/AO/DI



SAI-AU M12 BT 16DI/8DO


BF BT LQ UI1 UI2 - -



- BT LQ UI1 UI2 - -



- BT LQ UI UQ1 UQ2 UQ3
Figure 46: Status LEDs



LED displays of PROFIBUS, Bluetooth and supply voltages

ON =slave exchanging data LED BF
PROFIBUS
green
flashing =transition after SAI is turned on
red ON =error, no data is being exchanged
LED BT blue Flashing: - detectable for all masters
Illuminated: - not detectable, connection already exists
green Flashing: - communication stopped, no answer to polling
Illuminated: - operation, BT connection established
LED LQ green - good reception
red - poor reception
Off - no connection
green ON =UI1 >18 V DC OFF =UI1 <18 V DC LED UI1
Power supply red ON =UI1 <18 V DC OFF =UI1 >18 V DC
green ON =UI2 >18 V DC OFF =UI2 <18 V DC LED UI2
Power supply red ON =UI2 <18 V DC OFF =UI2 >18 V DC
green ON =UI >18 V DC OFF =UI <18 V DC LED UI
Power supply red ON =UI <18 V DC OFF =UI >18 V DC
LED UQ1 green ON =UQ1 >18 V DC OFF =UQ1 <18 V DC
64 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Power supply red ON =UQ1 <18 V DC OFF =UQ1 >18 V DC
green ON =UQ2 >18 V DC OFF =UQ2 <18 V DC LED UQ2
Power supply red ON =UQ2 <18 V DC OFF =UQ2 >18 V DC
green ON =UQ3 >18 V DC OFF =UQ3 <18 V DC LED UQ3
Power supply red ON =UQ3 <18 V DC OFF =UQ3 >18 V DC
Table 45: LED displays for PROFIBUS and supply voltages

1073380000/1.3/08.09 Weidmller t 65

Bluetooth SAI Manual

66 Weidmller t 1073380000/1.3/08.09
The assigned LEDs can be used to detect the status/diagnostics of the digital inputs and digital outputs and the DESINA
information.


Example of LED assignments based on the SAI-AU M12 BT 16DI



- BT LQ UI1 UI2 - -
Unoccupied
LED BT
LED LQ
LED UI1
LED UI2
Unoccupied
Unoccupied
Figure 47: LED assignments for SAI-AU M12 BT 16DI


LED display of the digital input

yellow Status of the digital input ON OFF
Short-circuit at pin 1, sensor voltage
Pin 4 Digital Input
red

Pin 2 Digital input 2 yellow Status of digital input or DESINA diagnostics input ON OFF
DESINA diagnostics red Short-circuit at pin 2, sensor voltage (together with LED pin 4)
Table 46: LED display of the digital inputs

Bluetooth SAI Manual
6.2. Diagnostic telegrams
The diagnostic telegram consists of six bytes of standard diagnostic information and manufacturer diagnostic information.

The number of bytes required for the manufacturers diagnostics varies from module to module.

Standard diagnostics information

Byte 0, station status 1
Bit 0 station_non_exist 1 =station cannot be reached; always "0"
Bit 1 station_not_ready 1 =station is not ready for data exchange
Bit 2 cfg_fault 1 =configuration error with the master
Bit 3 ext_diag 1 =extended diagnostics data is available
Bit 4 not_supported 1 =a requested function is not supported
Bit 5 invalid_slave_response 1 =the slave response was not valid
Bit 6 prm_fault 1 =false or incomplete parameter data
Bit 7 master_lock 1 =parameters are from another master set - access is locked
Byte 1, station status 2
Bit 0 Prm_req 1 =parameter must be transmitted again
Bit 1 Stat_diag 1 =diagnostic data is present
Bit 2 1 Slave always sets "1"
Bit 3 WD_ON 1 =The slave has activated the watchdog
Bit 4 freeze_mode 1 =The slave has received the "freeze" control command
Bit 5 sync_mode 1 =The slave has received the "sync" control command
Bit 6 reserved Slave always sets "0"
Bit 7 deactivated 1 =set from master, slave is inactive, slave always sets "0"
Byte 2, station status 3
Bit 0 reserved Slave always sets "0"
Bit 1 reserved Slave always sets "0"
Bit 2 reserved Slave always sets "0"
Bit 3 reserved Slave always sets "0"
Bit 4 reserved Slave always sets "0"
Bit 5 reserved Slave always sets "0"
Bit 6 reserved Slave always sets "0"
Bit 7 ext_overflow 1 =Diagnostic data overflow
1073380000/1.3/08.09 Weidmller t 67

Bluetooth SAI Manual

Byte 3, Diag. master address
FFH PB address of master FF =Parameter has still not been received from master
02H or the address of the master, which the parameter has set
Byte 4, Ident Number (high byte)
08H High byte of the ident number The ID number of the PROFIBUS device high byte
Byte 5, ident number (low byte)
15H Low byte of the ident number The ID number of the PROFIBUS device low byte
Table 47: Standard diagnostics information


68 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
1073380000/1.3/08.09 Weidmller t 69
Manufacturer diagnostics information
The manufacturers diagnostics information can be
composed of one or more bytes. The manufacturer
determines the amount and their content.
For SAI modules, these include various diagnostic
information depending on the type of module; a part of
this information has to be activated by parameterisation.
An overview of the diagnostic bytes is given below;
these bytes are counted after the standard diagnostics
information byte 6.

The gateway is structured modularly with up to seven
modules. Seven universal modules are established in
the diagnostics data so that each module can be added
to each gateway position.





Byte 6 Extended diagnostic data: Header

The number of bytes of the manufacturers diagnostics,
including this byte.
Bits 6+7 0= Device-specific diagnostic
Byte 7 Software version, high byte
High byte, SW version SW version of the PB device, high byte
Byte 8 Software version, low byte
Low byte, SW version SW version of the PB device, low byte
Byte 9 Doubled address on sub-bus module
Bit 0 1= Doubled address, module 1
Bit 1 1= Doubled address, module 2
Bit 2 1= Doubled address, module 3
Bit 3 1= Doubled address, module 4
Bit 4 1= Doubled address, module 5
Bit 5 1= Doubled address, module 6
Bit 6 1= The sub-bus module is detected too much
Bit 7 reserved
Byte 10 Missing sub-bus module
Bit 0 1= Missing module 1
Bit 1 1= Missing module 2
Bit 2 1= Missing module 3
Bit 3 1= Missing module 4
Bit 4 1= Missing module 5
Bit 5 1= Missing module 6
Bit 6 reserved
Bit 7 reserved
Byte 11 Configuration error, QoS

Bluetooth SAI Manual

Bit 0 1= Configuration error, module 1
Bit 1 1= Configuration error, module 2
Bit 2 1= Configuration error, module 3
Bit 3 1= Configuration error, module 4
Bit 4 1= Configuration error, module 5
Bit 5 1= Configuration error, module 6
Bit 6 reserved
Bit 7 reserved
Table 48: Manufacturer's diagnostic information, bytes 6 11

Byte 12 Wrong sub-bus module detected
Bit 0 1= Wrong module 1 detected
Bit 1 1= Wrong module 2 detected
Bit 2 1= Wrong module 3 detected
Bit 3 1= Wrong module 4 detected
Bit 4 1= Wrong module 5 detected
Bit 5 1= Wrong module 6 detected
Bit 6 1= Wrong GW module detected
Bit 7 reserved
Byte 13 Poor wireless connection to sub-bus system
Bit 0 1= Poor connection, module 1
Bit 1 1= Poor connection, module 2
Bit 2 1= Poor connection, module 3
Bit 3 1= Poor connection, module 4
Bit 4 1= Poor connection, module 5
Bit 5 1= Poor connection, module 6
Bit 6 1= Communication error, gateway
Bit 7 reserved
Byte 14 LQI sub-bus module 1
LQI Byte Quality of wireless connection, module 1
Byte 15 LQI sub-bus module 2
LQI Byte Quality of wireless connection, module 2
Byte 16 LQI sub-bus module 3
LQI Byte Quality of wireless connection, module 3
Byte 17 LQI sub-bus module 4
70 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
LQI Byte Quality of wireless connection, module 4
Byte 18 LQI sub-bus module 5
LQI Byte Quality of wireless connection, module 5
Byte 19 LQI sub-bus module 6
LQI Byte Quality of wireless connection, module 6
Byte 20 Voltage monitoring, part 1
Bit 0 1= No voltage UI module 1
Bit 1 1= No voltage UQ1 module 1
Bit 2 1= No voltage UQ2 module 1
Bit 3 1= No voltage UQ3 module 1
Bit 4 1= No voltage, UI module 2
Bit 5 1= No voltage UQ1 module 2
Bit 6 1= No voltage UQ2 module 2
Bit 7 1= No voltage UQ3 module 2
Byte 21 Voltage monitoring, part 2
Bit 0 1= No voltage, UI module 3
Bit 1 1= No voltage UQ1 module 3
Bit 2 1= No voltage UQ2 module 3
Bit 3 1= No voltage UQ3 module 3
Bit 4 1= No voltage UI module 4
Bit 5 1= No voltage UQ1 module 4
Bit 6 1= No voltage UQ2 module 4
Bit 7 1= No voltage UQ3 module 4
Table 49: Manufacturer's diagnostic information, bytes 12 21

Byte 22 Voltage monitoring, part 3
Bit 0 1= No voltage UI module 5
Bit 1 1= No voltage UQ1 module 5
Bit 2 1= No voltage UQ2 module 5
Bit 3 1= No voltage UQ3 module 5
Bit 4 1= No voltage UI module 6
Bit 5 1= No voltage UQ1 module 6
Bit 6 1= No voltage UQ2 module 6
Bit 7 1= No voltage UQ3 module 6
Byte 23 Voltage monitoring, part 4
1073380000/1.3/08.09 Weidmller t 71

Bluetooth SAI Manual

Bit 0 1= No voltage, UI gateway
Bit 1 1= No voltage, UQ1 gateway
Bit 2 1= No voltage, UQ2 gateway
Bit 3 1= No voltage, UQ3 gateway
Bit 4 reserved
Bit 5 reserved
Bit 6 reserved
Bit 7 reserved
Table 50: Manufacturer's diagnostic information, bytes 22 23

Byte 24 Short circuit on sensor voltage
Bit 0 1= Short circuit on sensor slot 1
Bit 1 1= Short circuit on sensor slot 2
Bit 2 1= Short circuit on sensor slot 3
Bit 3 1= Short circuit on sensor slot 4
Bit 4 1= Short circuit on sensor slot 5
Bit 5 1= Short circuit on sensor slot 6
Bit 6 1= Short circuit on sensor slot 7
Bit 7 1= Short circuit on sensor slot 8
Byte 25 Error message for DESINA characteristic
Bit 0 1= Desina diagnostic on slot 1
Bit 1 1= Desina diagnostic on slot 2
Bit 2 1= Desina diagnostic on slot 3
Bit 3 1= Desina diagnostic on slot 4
Bit 4 1= Desina diagnostic on slot 5
Bit 5 1= Desina diagnostic on slot 6
Bit 6 1= Desina diagnostic on slot 7
Bit 7 1= Desina diagnostic on slot 8
Byte 26 Short circuit on digital output to earth GND
Bit 0 1= Short circuit to earth on slot 1
Bit 1 1= Short circuit to earth on slot 2
Bit 2 1= Short circuit to earth on slot 3
Bit 3 1= Short circuit to earth on slot 4
Bit 4 1= Short circuit to earth on slot 5
Bit 5 1= Short circuit to earth on slot 6
72 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Bit 6 1= Short circuit to earth on slot 7
Bit 7 1= Short circuit to earth on slot 8
Byte 27 Short circuit on digital output to +24 V DC
Bit 0 1= Short circuit to +24V DC on slot 1
Bit 1 1= Short circuit to +24V DC on slot 2
Bit 2 1= Short circuit to +24V DC on slot 3
Bit 3 1= Short circuit to +24V DC on slot 4
Bit 4 1= Short circuit to +24V DC on slot 5
Bit 5 1= Short circuit to +24V DC on slot 6
Bit 6 1= Short circuit to +24V DC on slot 7
Bit 7 1= Short circuit to +24V DC on slot 8
Byte 28 reserved

Byte 29 reserved

Table 51: Manufacturer's diagnostic information, bytes 24 29
1073380000/1.3/08.09 Weidmller t 73

Bluetooth SAI Manual

After the gateway's device-specific diagnostic bytes, the module-specific diagnostic bytes are then added. In order to
save space, one module is detailed as an example. This module would be executed up to seven times for a diagnostic
telegram.
Byte x Short-circuit on sensor voltage
Bit 0 1= Short circuit on sensor slot 1
Bit 1 1= Short circuit on sensor slot 2
Bit 2 1= Short circuit on sensor slot 3
Bit 3 1= Short circuit on sensor slot 4
Bit 4 1= Short circuit on sensor slot 5
Bit 5 1= Short circuit on sensor slot 6
Bit 6 1= Short circuit on sensor slot 7
Bit 7 1= Short circuit on sensor slot 8
Byte x+1 Error message for DESINA characteristic
Bit 0 1= Desina diagnostic on slot 1
Bit 1 1= Desina diagnostic on slot 2
Bit 2 1= Desina diagnostic on slot 3
Bit 3 1= Desina diagnostic on slot 4
Bit 4 1= Desina diagnostic on slot 5
Bit 5 1= Desina diagnostic on slot 6
Bit 6 1= Desina diagnostic on slot 7
Bit 7 1= Desina diagnostic on slot 8
Byte x+2 Short circuit on digital output to earth GND
Bit 0 1= Short circuit to earth on slot 1
Bit 1 1= Short circuit to earth on slot 2
Bit 2 1= Short circuit to earth on slot 3
Bit 3 1= Short circuit to earth on slot 4
Bit 4 1= Short circuit to earth on slot 5
Bit 5 1= Short circuit to earth on slot 6
Bit 6 1= Short circuit to earth on slot 7
Bit 7 1= Short circuit to earth on slot 8
Byte x+3 Short circuit on digital output to +24 V DC
Bit 0 1= Short circuit to +24V DC on slot 1
Bit 1 1= Short circuit to +24V DC on slot 2
Bit 2 1= Short circuit to +24V DC on slot 3
Bit 3 1= Short circuit to +24V DC on slot 4
74 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Bit 4 1= Short circuit to +24V DC on slot 5
Bit 5 1= Short circuit to +24V DC on slot 6
Bit 6 1= Short circuit to +24V DC on slot 7
Bit 7 1= Short circuit to +24V DC on slot 8
Byte x+4 Analogue input range 420 mA, 4 mA below
Bit 0 1= 4 mA too low out of range at analogue input 0
Bit 1 1= 4 mA too low out of range at analogue input 1
Bit 2 1= 4 mA too low out of range at analogue input 2
Bit 3 1= 4 mA too low out of range at analogue input 3
Bit 4 7 reserved
Byte x+5 Reserved for expansions
reserved
Table 52: Module-specific diagnostic bytes
1073380000/1.3/08.09 Weidmller t 75

Bluetooth SAI Manual

76 Weidmller t 1073380000/1.3/08.09
6.3. Evaluating diagnostic data in Step7
Whereas the data for inputs and outputs can be ex-
changed and processed directly in Step7 with
PROFIBUS via the input and output image, diagnostic
data must be read into the application programme with
an SFC.


Diagnostics data (slave diagnostics) of a DP slave is
read with the SFC 13 "DPNRM_DG".

Figure 48: Diagnostics function block

Input variables:
REQ =1: Request to read
LADDR: Planned diagnostics address of the DP slave; this can be read in the hardware con-
figurator.
Note: The address must be entered in hexadecimal, for example, the diagnostic
address 1022 (3FEH) means: LADDR: =W#16#3FE
Output variables:
RET_VAL RET_VAL contains the length of the actual transmitted data.
If an error occurs when the function is being processed, the return value contains an
error code.
RECORD Target range for the read diagnostic data.
The minimum length of the data record to be read or the target range is 6.
BUSY =1 The read operation has not been completed
Table 53: Diagnostics function block

In the example above, 10 bytes following the flag byte M 120.0 are reserved as target range of the diagnostics data for
an SAI-AU M12 PB 16DI. These are divided up as follows:
Standard diagnostics information
MB 120 Byte 0 Station status 1
MB 121 Byte 1 Station status 2
MB 122 Byte 2 Station status 3
MB 123 Byte 3 Diag. master address
MB 124 Byte 4 Ident number (high byte)
MB 125 Byte 5 Ident number (low byte)

Bluetooth SAI Manual
Manufacturer diagnostics information
MB 126 Byte 6 The number of bytes of the manufacturers diagnostics, in-
cluding this byte.
MB 127 Byte 7 MSB software version (high byte)
MB 128 Byte 8 LSB software version (low byte)
MB 129 Byte 9 Short-circuit at +24 V DC sensor voltage
MB 130 Byte 10 Error message for DESINA diagnostics
Table 54: Diagnostics information


Please refer to the Siemens Step7 programming manual as well as the Online Help file for further
information.
1073380000/1.3/08.09 Weidmller t 77

Bluetooth SAI Manual


78 Weidmller t 1073380000/1.3/08.09
Appendix A: Product Overview
Modules
Modules
SAI-AU M12 GW PB/BT 12I in M12 with 12 digital inputs 1006980000
SAI-AU M12 BT 16DI in M12 with 16 digital inputs 1006940000
SAI-AU M12 BT 16DI/8DO in M12 with 16 digital inputs / 8 digital outputs 1006930000
SAI-AU M12 BT 4AI2AO2DIO in M12 with analogue I/Os and digital I/Os 1006920000


Connector
I/O and AUX connectors
SAIS-4/7 M12 male connector, 4-pole, straight 9457550000
SAISW-4/7 M12 male connector, 4-pole, angled 9457290000
SAIB-4/7 M12 female connector, 4-pole, straight 9457240000
SAIBW-4/7 M12 female connector, 4-pole, angled 9457700000
PROFIBUS connectors
SAISM 5/8S M12 5P B-COD PROFIBUS male connector, straight, B-coded 1784790000
SAIBM 5/8S M12 5P B-COD PROFIBUS female connector, straight, B-coded 1784780000
PROFIBUS terminating resistor
SAIEND PB M12 5P B-COD M12, 5-pole, B-coded 1784770000


Twin plug
Twin plug
SAI-Y-5S- M12/M12 M12 on 2 x M12, with connection for two sensors 1826880000
SAI-Y-4-4/2-4 M12/8 M12 on 2 x M8, with connection for two sensors 1783420000
Table 55: Connectors product overview



Bluetooth SAI Manual
Cables
General cables Example: Cable length: 3 m
SAIL-M12G-4-3.0U M12 male connector, 4-pole, straight, PUR, 3 m cable 9456100300
SAIL-M12BG-4-3.0U M12 female connector, 4-pole, straight, PUR, 3 m ca-
ble
9457730300
SAIL-M12GM12G-4-1.5U M12 male connector, 4-pole, straight on female,
M12 straight, PUR, 1.5 m cable
9457190000
SAIL-M12W-4-3.0U M12 male connector, 4-pole, angled, PUR, 3 m cable 1906260300
SAIL-M12BW-4-3.0U M12 female connector, 4-pole, angled, PUR, 3 m cable 9457740300
SAIL-M12GM12G-4-3.0U M12 male connector, 4-pole, straight on female,
M12 straight, PUR, 3 m cable
1906300300
SAIL-M8GS-3-3.0U M8 male connector, 3-pole, straight, shielded,
PUR, 3 m cable
1824590300
SAIL-M8WS-3-3.0U M8 male connector, 3-pole, angled, shielded,
PUR, 3 m cable
1857550300
SAIL-M8GBS-3-3.0U M8 female connector, 3-pole, straight, shielded,
PUR, 3 m cable
9457450300
SAIL-M8WBS-3-3.0U M8 female connector, 3-pole, angled, shielded,
PUR, 3 m cable
9457380300
SAIL-M8GSM8GS-3-3.0U M8 male connector, straight, on female, M8, straight,
3-pole, shielded, PUR, 3m cable
1824570300
PROFIBUS cables Example: Cable length: 3 m
SAIL-M12G-PB-3.0U M12 male connector, straight, PUR, 3 m cable 1873300300
SAIL-M12GM12G-PB-3.0U M12 male connector, straight on female, M12, straight,
PUR, 3 m cable
1873310300
SAIL-M12BG-PB-3.0U M12 female connector, straight, PUR, 3 m cable 1873320300

Table 56: Cables product overview



Please observe that we are only able to print a small selection of all of our cables


We have a wide variety on offer:
Various lengths: 1.5 m; 3.0 m; 5.0 m; 10,0 m; with more custom lengths on request
Shielded or unshielded
With/without LEDs
Straight/angled
A variety of pole counts
1073380000/1.3/08.09 Weidmller t 79

Bluetooth SAI Manual


80 Weidmller t 1073380000/1.3/08.09
Different cable materials
With/without valve connectors

For more detailed information, please refer to our SAI section catalogue.
Tools
Cutting
KT 8 Cable Cutter 9002650000
Unsheathing/stripping
CST VARIO Stripping tool 9005700000
STRIPAX for cable stripping 9005000000
MULTI-STRIPAX 6-16 for cable stripping and wire-end ferrule crimping 9202210000
Crimping
PZ 6 Roto for crimping in all positions 9014350000
H-BOX 0.14-0.75QMM Box with wire-end ferrules 0.14 0.75 mm
2
9025410000
Screwdriver, flat-blade
SD 0.6 x 3.5 x 100 for setting the address range 9008330000
Fastening and screwing
Screwty set For tightening and loosening knurled nuts on con-
nectors
1910000000
Screwty set - DM see above, but with torque 1920000000


Accessories
Protective caps
SAI-SK-M12-UNI M12, in black plastic 2330260000
SAI-SK M8 M12, in black plastic 1802760000
Marking tags
ESG 8/13,5/43,3 SAI AU MultiCard labelling sets 1912130000


Testing
Simulation plug
SAIS-T-2/1-K Bridge between pin 1 and pin 2 8569100000
SAIS-T-4/1-K Bridge between pin 1 and pin 4 8726310000
Table 57: Tools and accessories product overview



Bluetooth SAI Manual
Appendix B: Drilling Templates

Figure 49: Drilling Templates
1073380000/1.3/08.09 Weidmller t 81

Bluetooth SAI Manual


Appendix C: Converting fromHexadecimal to Decimal
Dec. Hex. Dec. Hex. Dec. Hex. Dec. Hex.
0 00 32 20 64 40 96 60
1 01 33 21 65 41 97 61
2 02 34 22 66 42 98 62
3 03 35 23 67 43 99 63
4 04 36 24 68 44 100 64
5 05 37 25 69 45 101 65
6 06 38 26 70 46 102 66
7 07 39 27 71 47 103 67
8 08 40 28 72 48 104 68
9 09 41 29 73 49 105 69
10 0A 42 2A 74 4A 106 6A
11 0B 43 2B 75 4B 107 6B
12 0C 44 2C 76 4C 108 6C
13 0D 45 2D 77 4D 109 6D
14 0E 46 2E 78 4E 110 6E
15 0F 47 2F 79 4F 111 6F
16 10 48 30 80 50 112 70
17 11 49 31 81 51 113 71
18 12 50 32 82 52 114 72
19 13 51 33 83 53 115 73
20 14 52 34 84 54 116 74
21 15 53 35 85 55 117 75
22 16 54 36 86 56 118 76
23 17 55 37 87 57 119 77
24 18 56 38 88 58 120 78
25 19 57 39 89 59 121 79
26 1A 58 3A 90 5A 122 7A
27 1B 59 3B 91 5B 123 7B
28 1C 60 3C 92 5C 124 7C
29 1D 61 3D 93 5D 125 7D
30 1E 62 3E 94 5E 126 7E
31 1F 63 3F 95 5F 127 7F
Table 58: Converting from Hexadecimal to Decimal

82 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Appendix D: Configuration of the DESINA inputs
Modules SAI-AU M12 GW PB/BT 12I, SAI-AU M12 BT 16 DI, SAI-AU M12 BT 16DI/8DO

First byte in the configuration: Activates the DESINA function

Bit 0 with bit 7 OFF =DESINA function deactivated
ON =DESINA function activated



OFF OFF OFF OFF .. .. .. .. 0..
OFF OFF OFF ON .. .. .. .. 1..
OFF OFF ON OFF .. .. .. .. 2..
OFF OFF ON ON .. .. .. .. 3..
OFF ON OFF OFF .. .. .. .. 4..
OFF ON OFF ON .. .. .. .. 5..
OFF ON ON OFF .. .. .. .. 6..
OFF ON ON ON .. .. .. .. 7..
ON OFF OFF OFF .. .. .. .. 8..
ON OFF OFF ON .. .. .. .. 9..
ON OFF ON OFF .. .. .. .. A..
ON OFF ON ON .. .. .. .. B..
ON ON OFF OFF .. .. .. .. C..
ON ON OFF ON .. .. .. .. D..
ON ON ON OFF .. .. .. .. E..
ON ON ON ON .. .. .. .. F..
.. .. .. .. OFF OFF OFF OFF ..0
.. .. .. .. OFF OFF OFF ON ..1
.. .. .. .. OFF OFF ON OFF ..2
.. .. .. .. OFF OFF ON ON ..3
.. .. .. .. OFF ON OFF OFF ..4
.. .. .. .. OFF ON OFF ON ..5
.. .. .. .. OFF ON ON OFF ..6
.. .. .. .. OFF ON ON ON ..7
.. .. .. .. ON OFF OFF OFF ..8
.. .. .. .. ON OFF OFF ON ..9
.. .. .. .. ON OFF ON OFF ..A
.. .. .. .. ON OFF ON ON ..B
.. .. .. .. ON ON OFF OFF ..C
.. .. .. .. ON ON OFF ON ..D
.. .. .. .. ON ON ON OFF ..E
.. .. .. .. ON ON ON ON ..F


0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0
1.7 1.6 1.5 1.4 1.3 1.2 1.1 1.0
input 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0
DESINA 1.7 1.6 1.5 1.4 1.3 1.2 1.1 1.0


Example:

ON OFF OFF OFF .. .. .. .. 8..
.. .. .. .. ON ON OFF OFF ..C


Table 59: Configuration of a DESINA function: 0x8C



1073380000/1.3/08.09 Weidmller t 83

Bluetooth SAI Manual


Appendix E: Configuration of the digital connection points
Modules SAI-AU M12 PB 16DI/8DO
Second byte in the configuration: Defines the function of the connection points as input or output

Bit 0 with bit 7 OUT =connection to pin 2 is output
IN =connection to pin 2 is input


OUT OUT OUT OUT .. .. .. .. 0..
OUT OUT OUT IN .. .. .. .. 1..
OUT OUT IN OUT .. .. .. .. 2..
OUT OUT IN IN .. .. .. .. 3..
OUT IN OUT OUT .. .. .. .. 4..
OUT IN OUT IN .. .. .. .. 5..
OUT IN IN OUT .. .. .. .. 6..
OUT IN IN IN .. .. .. .. 7..
IN OUT OUT OUT .. .. .. .. 8..
IN OUT OUT IN .. .. .. .. 9..
IN OUT IN OUT .. .. .. .. A..
IN OUT IN IN .. .. .. .. B..
IN IN OUT OUT .. .. .. .. C..
IN IN OUT IN .. .. .. .. D..
IN IN IN OUT .. .. .. .. E..
IN IN IN IN .. .. .. .. F..
.. .. .. .. OUT OUT OUT OUT ..0
.. .. .. .. OUT OUT OUT IN ..1
.. .. .. .. OUT OUT IN OUT ..2
.. .. .. .. OUT OUT IN IN ..3
.. .. .. .. OUT IN OUT OUT ..4
.. .. .. .. OUT IN OUT IN ..5
.. .. .. .. OUT IN IN OUT ..6
.. .. .. .. OUT IN IN IN ..7
.. .. .. .. IN OUT OUT OUT ..8
.. .. .. .. IN OUT OUT IN ..9
.. .. .. .. IN OUT IN OUT ..A
.. .. .. .. IN OUT IN IN ..B
.. .. .. .. IN IN OUT OUT ..C
.. .. .. .. IN IN OUT IN ..D
.. .. .. .. IN IN IN OUT ..E
.. .. .. .. IN IN IN IN ..F


Connection 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0


Example:

IN IN IN OUT .. .. .. .. E..
.. .. .. .. OUT OUT OUT OUT ..0


Table 60: Establishing the configuration for the digital connection points: 0xE0



84 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Appendix G: Configuration of analogue outputs
7 6 5 4 3 2 1 0 Measurement range Value range
.. .. .. .. .. ..
0 0 Analogue output 0: 0 to 10 V 0 to 2047
.. .. .. .. .. ..
0 1 Analogue output 0: 0 to 20 mA 0 to 4095
.. .. .. .. .. ..
1 0 Analogue output 0: -10 V to +10 V 0 to 4095
.. .. .. .. .. ..
1 1 Analogue output 0: 4 to 20 mA 819 to 4095
.. .. .. ..
0 0
.. ..
Analogue output1: 0 to 10 V 0 to 2047
.. .. .. ..
0 1
.. ..
Analogue output 1: 0 to 20 mA 0 to 4095
.. .. .. ..
1 0
.. ..
Analogue output 1: -10 V to +10 V 0 to 4095
.. .. .. ..
1 1
.. ..
Analogue output 1: 4 vbis 20 mA 819 to 4095
Table 61: Configuration of the analogue output

1073380000/1.3/08.09 Weidmller t 85

Bluetooth SAI Manual


Sources
Web addresses
www.weidmueller.com
www.profibus.com


Standards

IEC 61158-x: Digital data communications for measurement and control Fieldbus for use in industrial control sys-
tems.

IEC 61784-1: Digital Data Communications for Measurement and Control Part1: Profile Sets for continuous and
discrete Manufacturing relative to Fieldbus Use in Industrial Control Systems

EN 50170: Universal Field Communication System, Revision A2



86 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Index
Figure 1: Basic design of an SAI distributor 5
Figure 2: Basic PROFIBUS system configuration 6
Figure 3: Basic PROFIBUS system configuration with subordinate Bluetooth 7
Figure 4: Voltage drop 10
Figure 5: Mounting dimensions for the SAI Active Universal 12
Figure 6: Mounting an SAI distributor 13
Figure 7: Functional earth FE connection 13
Figure 8: Attaching markers and tags 14
Figure 9: Bus termination wiring 21
Figure 10: SAI-AU M12 GW PB/BT 12I 22
Figure 11: PROFIBUS address switch 23
Figure 12: Bluetooth address switch 24
Figure 13: Block diagram of the digital input 26
Figure 14: SAI-AU M12 BT 16DI 28
Figure 15: Address switch 29
Figure 16: Block diagram of the digital input 31
Figure 17: View of M12 16DI 31
Figure 18: Sensors with DESINA 32
Figure 19: Sensor without DESINA 32
Figure 20: SAI-AU M12 BT 16DI/8DO 34
Figure 21: Address switch 35
Figure 22: Block diagram of the digital input 37
Figure 23: /A view of M12 16DI 37
Figure 24: Sensor with DESINA 38
Figure 25: Sensor without DESINA 38
Figure 26: Block diagram of the digital outputs 39
Figure 27: Assignment of the 0.5 A and 2 A outputs 39
Figure 28: I/O housing M12 16DI/8DO 39
Figure 29: SAI-AU M12 BT 4AI2AO2DIO 42
Figure 30: Address switch 43
Figure 31: Block diagram of the analogue input 45
Figure 32: Block diagram of the analogue output 45
Figure 31: Block diagram of the digital input 45
Figure 34: /A view of M12 4AI 46
Figure 35: Sensors with DESINA 47
Figure 36: Sensors without DESINA 47
Figure 37: Bitmaps for hardware configurator 51
Figure 38: Installing the GSD file: step 1 53
Figure 39: Installing the GSD file: step 2 53
Figure 40: GSD file catalogue 54
Figure 41: Hardware configurator 55
Figure 42: The gateway slot list 56
Figure 43: Module types 56
Figure 44: Assigning input / output addresses 57
Figure 45: Parameter 58
Figure 46: Status LEDs 64
Figure 47: LED assignments for SAI-AU M12 BT 16DI 66
Figure 48: Diagnostics function block 76
Figure 49: Drilling Templates 81




1073380000/1.3/08.09 Weidmller t 87
Index
Table 1: Determining the SAI distributor 9
Table 2: Code conversion decimal <- >hexadecimal 15
Table 3: Contact assignment (pin out) of the PROFIBUS connector 20
Table 4: Contact assignment (pin out) of the PROFIBUS female contact socket 20
Table 5: Technical data, PROFIBUS 21
Table 6: SAI-AU M12 GW PB/BT 12I 22
Table 7: Bluetooth gateway addresses 24
Table 8: Contact assignment (pin out) of the power supply connector 25
Table 9: Contact assignment (pin out) of the female power supply connector 25
Table 10: Contact assignment of the digital inputs 26
Table 11: Technical data for the SAI-AU M12 GW PB/BT 12I 27
Table 12: SAI-AU M12 BT 16DI 28
Table 13: Setting the Bluetooth address, SAI 29
Table 14: Contact assignment (pin out) of the power supply connector 30
Table 15: Contact assignment (pin out) of the female power supply connector 30
Table 16: Plug-in jumper positions for the SAI-AU M12 BT 16DI 30
Table 17: Contact assignment (pin out) of the digital input 31
Table 18: Technical data for the SAI-AU M12 BT 16DI 33
Table 19: SAI-AU M12 BT 16DI/8DO 34
Table 20: Setting the Bluetooth address, SAI 35
Table 21: Contact assignment (pin out) of the power supply connector 36
Table 22: Contact assignment (pin out) of the power supply connector 36
Table 23: Plug-in jumper positions for the SAI-AU M12 BT 16DI/8DO 36
Table 24: Contact assignment (pin out) of the digital input 37
Table 25: Technical data for the SAI-AU M12 BT 16DI/8DO 41
Table 26: SAI-AU M12 BT 4AI2AO2DIO 42
Table 27: Setting the Bluetooth address, SAI 43
Table 28: Contact assignment (pin out) of the power supply connector 44
Table 29: Contact assignment (pin out) of the female power supply connector 44
Table 30: Plug-in jumper positions for the SAI-AU M12 BT 4AI2AO2DIO 44
Table 31: Contact assignment (pin out) of the analogue input 45
Table 32: Contact assignment (pin out) of an analogue output 45
Table 33: Contact assignment of the digital inputs 45
Table 34: Technical data for the SAI-AU M12 BT 4AI2AO2DIO 49
Table 35: Overview of the SAI parameters GW 12I 59
Table 36: Overview of SAI parameters, 16DI 59
Table 37: Overview of SAI parameters, 16DI/8DO 59
Table 38: Overview of SAI parameters, 4AI2AO2DIO 60
Table 39: DESINA parameters 61
Table 40: Reversal of input and output 61
Table 41: Behaviour when bus malfunction occurs 61
Table 42: Behaviour when bus malfunction occurs 61
Table 43: Configuration of the analogue inputs 62
Table 44: Configuration of the analogue outputs 62
Table 45: LED displays for PROFIBUS and supply voltages 65
Table 45: LED display of the digital inputs 66
Table 47: Standard diagnostics information 68
Table 48: Manufacturer's diagnostic information, bytes 6 11 70
Table 49: Manufacturer's diagnostic information, bytes 12 21 71
Table 50: Manufacturer's diagnostic information, bytes 22 23 72
Table 51: Manufacturer's diagnostic information, bytes 24 29 73
Table 52: Module-specific diagnostic bytes 75
Table 53: Diagnostics function block 76
Table 54: Diagnostics information 77
Table 54: Connectors product overview 78
Table 55: Cables product overview 79
Table 56: Tools and accessories product overview 80
Table 58: Converting from Hexadecimal to Decimal 82
Table 59: Configuration of a DESINA function: 0x8C 83
Table 60: Establishing the configuration for the digital connection points: 0xE0 84
88 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
1073380000/1.3/08.09 Weidmller t 89
Table 61: Configuration of the analogue output 85

Glossary
Glossary
AC or DC drives
AC or DC motors
Accuracy
Bit accuracy is a measure of the exactness of digital
measurement and calculation operations. With an accu-
racy of 8 bit, for example, 1 byte corresponds to an accu-
racy of 1/(2^8) =1/256 or 0.390625% steps. This is par-
ticularly important when converting from an analogue
signal to a digital value if the measurement value of a
sensor (temperature, pressure or similar) is to undergo
further digital processing.
AI
Please see Analogue input
Analogue input
Analogue input detects analogue signals as voltage sig-
nals from 0 to 10 V or as current signals from 0 to 20 mA
or 4 to 20 mA; resolution is generally 10 or 12 bit, 16 bit
representation.
Analogue output
Analogue input control variable as analogue signal; volt-
age signals from 0 to 10 V or -10 V to +10 V or as current
signals from 0 to 20 mA or 4 to 20 mA; resolution is gen-
erally 10 or 12 bit, representation 16 bit representation.
AO
Please see Analogue output
AUX IN
Power supply, 24 VDC feed in
AUX OUT
Power supply, 24 VDC feed out
Baud rate
The baud rate describes the number of signal codes
(symbol) that can be transmitted per second.
Bitmap file
This is an image file or graphic consisting of pixels; with
black and white information. Each bit corresponds to an
information unit and can consequently code a pixel. For
display purposes in the hardware configurator, bitmap
files in DIB format with 70 x 40 pixels are recommended.
Bus / power section
This is the section on the SAI to which the Fieldbus and
the supply voltage are connected.
BUS IN
PROFIBUS connection module, feed in. It is fully con-
nected to Bus OUT.
BUS OUT
PROFIBUS connection, bus feed out. It is fully connected
to Bus IN.
Bus termination
Install the bus terminations at the physical beginning and
physical end, according to the PROFIBUS standard, with
one bus termination each.
Bus termination
An active bus termination must be fitted at the beginning
and end of each PROFIBUS segment. The termination
consists of a combination of resistances. To function cor-
rectly, it requires a 5-V supply voltage that is normally
made available by each PROFIBUS device.
Coding A
Special coding for male or female M12 connectors for
purposes of recognition and non-reversal. On SAI mod-
ules, coding A is utilised for the power supply as well as
inputs and outputs. B-coding is specified for the
PROFIBUS Fieldbus.
Coding B
Special coding for male or female M12 connectors for
purposes of recognition and non-reversal. Coding B is
used for the PROFIBUS-DP Fieldbus.
90 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Configuration
Please see Hardware configuration.
Configuration menu
This is used to enter and configure the hardware of a
controller system.
Please also see Hardware configuration.
Connector
A plug-in connector connects lines carrying electrical
power or signals. The standards regulate the form and
the contact assignment of the connector and the corre-
sponding mating connector. They also define the electri-
cal signals to be transmitted.
DATA A
Data from PROFIBUS is transmitted via a two-core,
shielded twisted-pair cable with RS485 characteristics
(differential signal transmission). The two wires are des-
ignated as DATA A (green wire) and DATA B (red wire).
DATA B
Data from PROFIBUS is transmitted via a two-core,
shielded twisted-pair cable with RS485 characteristics
(differential signal transmission). The two wires are des-
ignated as DATA A (green wire) and DATA B (red wire).
DESINA
Please see Diagnostics input DESINA
DI
Please see Digital input.
Diagnostic telegram
Diagnostic telegrams indicate the status of the
PROFIBUS-DP slave. A diagnostic telegram is composed
of six bytes of standard diagnostics information as well as
the manufacturers diagnostics information. The number
of bytes required for the manufacturers diagnostics var-
ies from module to module.
Diagnostics data
Diagnostics data is transmitted in a diagnostics telegram.
This information is differentiated between standard diag-
nostics information (6 bytes) and vendor diagnostics in-
formation, the length of which depends on the vendor.
Diagnostics input DESINA
DESINA is an abbreviation for DistributEd and Standard-
ised INstAllation technology for machine tools and manu-
facturing systems. DESINA describes the specification for
standardising the electric, hydraulic and pneumatic instal-
lation of automated machine tools and manufacturing
systems. DESINA diagnostics input supplies diagnostic
information in addition to the digital input signal.
See also http://www.desina.de.
DIN
German acronym: German Institute for Standardization
DO
Please see Digital output.
DP
Please see PROFIBUS-DP.
EMC
Electromagnetic compatibility describes the freedom from
interference of electrical devices with regard to their envi-
ronment.
FE
Please see Functional Earth.
Field devices
Field device is a term used to describe all of the devices
operated on a Fieldbus. Field devices can be input and
output modules (SAIs) as well as drives, controls and
human-machine interfaces.
FMS
Please see PROFIBUS FMS
Frequency converter
A frequency converter generates an alternating current of
a certain frequency from an alternating current of a differ-
ent frequency and may also alter the voltage; it makes it
possible to adjust rotational speeds. In particular for
three-phase motors, frequency converters are an eco-
nomic form of control.
Functional earth
The functional earth serves to discharge compensating
and interference currents in order to guarantee EMC
characteristics. According to VDE 0100, the functional
earth is not the same as the protective earth; it is forbid-
den to use it as the protective earth.
GSD file (Device Data Base File)
A GSD file (Device Data Base File) contains a description
of all of the DP slave-specific characteristics.
1073380000/1.3/08.09 Weidmller t 91

The format of GSD files is defined in the standard IEC
61784-1:2002 Ed1 CP 3/1.
Hardware configuration
All devices and parameters of a control system are de-
fined in a hardware configuration.
Hardware configurator
Special software that is normally manufacturer-specific
and used for creating and downloading a hardware con-
figuration.
Hexadecimal code
Numeric code that represents information from 1 digit, 4
bit, decimal numbers 0 to 15 using digits 0 to 9 together in
conjunction with the letters A to F.
High byte
The high byte is the most-significant byte of a term con-
sisting of two or more bytes, for example, a software ver-
sion number.
Please see Low byte.
I/O section
This is the section of the SAI where the digital or ana-
logue sensors and actuators are connected.
Ident. number
Identification of a PROFIBUS-DP device. Assigned by the
PROFIBUS User Organisation (PUO).
IEC
International Electro-technical Commission
IEC 61158
Digital Data Communications for Measurement and Con-
trol Field bus for use in industrial control systems.
Part 1: Overview and guidance for the IEC 61158 series
Part 2: Physical layer specification and service definition
Part 3: Data link service definition
Part 4: Data link protocol specification
Part 5: Application layer service definition
Part 6: Application layer protocol specification
Industry PC
A standard PC adapted to suit harsh production environ-
ments.
Input addresses
External signals in a PLC are exchanged via digital or
analogue inputs or outputs. These are controlled by the
PLC programme via the addresses. The addresses can
be a combination of station address, module address and
connection address. It is possible that the addresses can
only be accessed byte for byte or word for word.
ISO
International Standard Organization
J1
Designation for a special jumper field used to link supply
voltages.
Jumpers
J umpers are used to configure electronic sub-assemblies
or set operating parameters that are carried out either
rarely or only once during initial commissioning proce-
dures.
The jumper is usually made of a small metal plate and a
plastic housing. It is plugged into two pins which results in
an electrical contact being created via the metal plates.
Generally, that results in the function of the hardware com-
ponent being activated, deactivated or configured.
LED
Light Emitting Diode used to indicate signal status of
the digital inputs and outputs as well as the status of the
voltage supply and Fieldbus.
LED BF
Red/green LED for indicating status on PROFIBUS
Green ON =slave exchanging data
Green flashing =transition after SAI is turned on
Red =error, no data is being exchanged
LED UI
Red/green LED for indicating the status of supply voltage
UQ1
Functions as LED U1
LED UI1
Red/green LED for indicating the status of supply voltage
U1
Green ON =UI1 >18 V DC
Green OFF =UI1 <18 V DC
Red ON =UI1 <18 V DC
Red OFF =UI1 >18 V DC
92 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
LED UI2
Red/green LED for indicating the status of supply voltage
U2
Functions as LED U1
LED UL
Two green LEDs for indicating module power supply; also
serve to illuminate the address section.
LED UQ1
Red/green LED for indicating the status of supply voltage
UQ1
Functions as LED U1
LED UQ2
Red/green LED for indicating the status of supply voltage
UQ2
Functions as LED U1
LED UQ3
Red/green LED for indicating the status of supply voltage
UQ3
Functions as LED U1
Low byte
Least-significant byte of a term consisting of two or more
bytes, for example, a software version number.
Please see High byte.
M12
Metric thread with a thread diameter of 12 mm.
M12 socket (female connector)
A socket with cavities containing contacts for creating an
electrical connection. Sockets are also referred to as fe-
male connectors. The mating partner of a socket is re-
ferred to as the plug or male connector. The socket outlet
can be described as a special form of socket.
M8
Metric thread with a thread diameter of 8 mm.
Output addresses
External signals in a PLC are exchanged via digital or
analogue inputs or outputs. These are controlled by the
PLC programme via the addresses. The addresses can
be a combination of station address, module address and
connection address. It sometimes possible that the ad-
dresses can only be accessed byte for byte or word for
word.
Output interval
Please see sampling period.
Parameter
Parameters describe the technical characteristics of tech-
nical devices. Weidmller SAI parameters serve to acti-
vate the DESINA diagnostic input, to define plug-in con-
nectors as inputs or outputs, as well as define the ana-
logue measurement ranges as a current or voltage input.
Parameterisation
Term used to describe assigning parameters with a
parameterisation or programming tool.
PE
Please see Protective earth.
Peripheral devices
These are devices outside of a central processing unit;
with Fieldbus systems, this also applies to all devices in
the Fieldbus.
PLC
PLC is the acronym for Programmable Logic Controller
Plug and Play
Sometimes written as Plug 'n' Play or Plug & Play; it de-
scribes the characteristics of modern, mostly peripheral
devices that are immediately available for use without
having to first install a programme.
Polling
The generally recognised term for "to poll" or query. The
poll function is an operating mode of Fieldbus devices in
a Fieldbus system.
Power supply
Electrical loads require a voltage supply to provide the
power. In control systems, the supply voltage used is 24
VDC.
Please see voltage range.
Power supply
Voltage with which the device is supplied. The power
supply in automation engineering is usually 18 to 24 VDC.
PROFIBUS
(PROcess FIeld BUS) is a part of the international stan-
dards IEC 61158 and IEC 61784. Physically, PROFIBUS
is either an electrical network based on a shielded, two-
1073380000/1.3/08.09 Weidmller t 93

conductor cable or an optical network based on a fibre
optics cable.
PROFIBUS guidelines
Vendor-independent compatibility is guaranteed by tech-
nical guidelines to ensure implementation of PROFIBUS
technology. The technical guidelines are published and
distributed centrally by the PROFIBUS User Organisation
(PUO) to underline the fact that these are effectively a
standard. Diverse PROFIBUS guidelines are available,
for example: the "Optical transfer technology for
PROFIBUS".
PROFIBUS slave
PROFIBUS slaves exchange data cyclically with a
PROFIBUS master. In addition, parameterization, con-
figuration and, in the case of a malfunction, diagnostic
data is transmitted. Typical PROFIBUS slaves include
connection terminals, repeaters, gateways, communica-
tion terminals, valve blocks and others.
PROFIBUS User Organisation
More than 260 vendors and users of the standardised
communication system PROFIBUS have come together
in the registered association PROFIBUS User Organisa-
tion (PUO) to jointly support further technical improve-
ments and establish the use of the technology interna-
tionally. The PROFIBUS User Organisation is a regis-
tered association. Membership is open to any company or
research facility anywhere in the world.
PROFIBUS-DP
This is a special application for automating factory pro-
duction. DP =Decentralised Periphery
PROFIBUS-DP address
With the PROFIBUS address you determine at which
address your SAI distributor will be identified on
PROFIBUS-DP.
PROFIBUS-FMS
This is utilised for the universal, object-oriented, cyclic
and acyclic exchange of data at a medium speed. FMS is
particularly suitable for exchanging data between intelli-
gent slaves such as PCs and PLCs. PROFIBUS-DP and
PROFIBUS-PA are special variants.
FMS =Fieldbus Message Specification
PROFIBUS-Master
PROFIBUS-DP differentiates between Class 1 and Class
2 masters. The Class 2 master is utilised for parameteri-
zation of PROFIBUS slaves by means of software; it is
mainly used to set the PROFIBUS address. As well as
exchanging data with the slave, the Class 1 master sup-
plies the PROFIBUS slave with configuration and pa-
rameter data.
PROFIBUS-PA
This is used to control field devices by means of a proc-
ess control system in the processing industry. This variant
of PROFIBUS is used in hazardous areas (Ex-Zone 0 &
1). Low currents only are used so that no sparks flash-
over in the case of a malfunction; it uses a slower data
transmission rate.
PA=Process Automation
Protecti ve earth
Protective earth conductors are often used in electrical
equipment and cable lines. This is also known as the pro-
tective lead, earth, earth connection or PE (protective
earth).
The task of the protective earth conductor in electrical
systems is to protect human beings from dangerous
touch voltages as well as to protect the system from
damage. The PE conductor is fitted in such a manner that
there is an electrical connection between the outer metal
housing of the electrical equipment (for example lamps,
fridges, motors).
Should a fault occur and the electrical supply voltage
comes into contact with the exterior of a piece of electrical
equipment, the short-circuit to ground via the PE conduc-
tor should ensure that the voltage between the housing of
the respective electrical equipment and the ground (with
which humans and animals are generally in contact) is
reduced to a harmless level.
At the same time, the high short-circuit currents trip the
fuse. That ensures that the electrical equipment with the
fault is disconnected extremely quickly from the supply
voltage.
German regulations stipulate that the PE conductor must
be identifiable by the colour combination green/yellow.
Repeater
Repeaters are necessary in order to create a CAN net-
work with more than 32 stations or establish a larger net-
work extension. The repeater represents the beginning of
a new segment in which the maximum number of stations
can be used or the maximum extension is defined.
Rotary coding switch
94 Weidmller t 1073380000/1.3/08.09

Bluetooth SAI Manual
Requiring a minimum of space, rotary coding switches
are used to make settings. These settings are usually
coded in decimal or hexadecimal formats.
RS-485
As a so-called differential voltage interface, the RS-485
interface operates with +5V (high) and 0V (low) by which
the non-inverted signal is transmitted via one wire and the
inverted (or negative) signal via the other wire. As distor-
tions have the same effect on both signals, the difference
between both signals remains (virtually) the same and
can be used for evaluation purposes.
An RS-485 connection constitutes a serial data transmis-
sion, which means the bits are transmitted one after the
other on a line.
SAI
The acronym SAI stands for Sensor Actuator Inter-
face. It is a compact-designed distributor or collector of
signal lines.
SAI distributor
Please see SAI.
Sampling period
The sampling period determines in which time interval an
analogue input is converted. The sampling period for the
SAI-AU AI/AO/DI can be set between 5 ms and 250 ms.
Segment
The PROFIBUS network consists of one or more seg-
ments. The maximum extension of a segment depends
on the baud rate being used. Up to 32 PROFIBUS sta-
tions can be connected in each segment.
Settings section
Range on the SAI in which the configuration of the hard-
ware is carried out; for example, the module address.
Shielding
Shielding is necessary to protect cables from radiated
noise disturbances.
Simatic Step7
STEP 7 is the current programming software used for the
Simatic S7 PLC family of products from Siemens; this is a
family of controls for PLC based automation systems.
In accordance with IEC 61131-3, the basic version of
STEP 7 includes the programming languages:
CFS - Continuous Function Chart
LD Ladder Diagram
STL Statement List
Slave
Please see PROFIBUS slave.
Temperature coefficient
The temperature coefficient is a relative change to a
physical variable resulting from a change in temperature
of 1 K (Kelvin).
Torx screwdriver
Torx is an improvement to the cross-head screw and
hexagon-socket (Allen) as a tool receiving socket, for
example in counter-sunk screws.
The profile is similar to a six-pointed star with rounded off
points and corners more or less a wave form. The com-
pany Camcar belongs to the Textron Group and is the
inventor and patent holder. In the meantime, the Torx
patent has run out and the hexalobular internal drive fea-
ture has been incorporated in international standards.
T-piece
A t-piece is used to provide uninterrupted feed of the
supply voltage and the Fieldbus.
T-pieces are connected straight onto the consumer load
and interconnected with the supply voltage or Fieldbus by
means of male and female connectors.
Transmission rate
Please see Baud rate.
Voltage range
The voltage range of the 24 VDC supply voltage is 18
VDC to 30 VDC.
X1
Rotary switch for setting the CAN address, in hexadeci-
mal format, low byte from 01H to 0FH.
X10
Rotary switch for setting the CAN address, in hexadeci-
mal format, high byte from 10H to F0H.
Y-Plugs
Y-plugs separate two digital signals, inputs or outputs
applied to an M12 connector in two digital signals.
1073380000/1.3/08.09 Weidmller t 95

96 Weidmller t 1073380000/1.3/08.09



www.weidmueller.com





gypten
Argentinien
Aserbeidschan
Australien
Kanada
Kasachstan
Katar
Kolumbien
Kroatien
Kuwait
Lettland
Libanon
Litauen
Luxemburg
Malaysia
Mazedonien
Mexiko
Montenegro
Neuseeland
Niederlande
Norwegen
sterreich
Oman
Paraguay
Peru
Philippinen
Polen
Portugal
Rumnien
Russland
Saudi-Arabien
Schweden
Schweiz
Serbien
Singapur
Slowakei
Slowenien
Spanien
Sdafrika
Sdkorea
Syrien
Taiwan
Thailand
Tschechien
Trkei
Ukraine
Ungarn
Uruguay
USA
VAE
Venezuela
Vietnam
Weirussland


Weidmller is the leading manufacturer of electrical con-
nection components for data and power transmissions.

We develop, produce and sell customer-oriented solutions
which cover the full scope of the Weidmller product line.
As an OEM supplier, our company sets standards world-
wide for electrical connection technology and systems.

The product portfolio includes terminal blocks, PCB and
plug-in connectors, protected component assemblies,
Industrial Ethernet components as well as relay couplers
through to power supplies and surge protection modules
that can be supplied with all types of connections. The
programme is rounded off with materials for installation
and marking of electrical equipment, basic I/O compo-
nents as well as tools. Weidmller products are used
chiefly in the electrical cabinet and in field wiring. Our
comprehensive service offering makes Weidmller even
more attractive for our customer.













Weidmller Interface GmbH & Co. KG
Postfach 3030
32720 Detmold
Klingenbergstrae 16
32758 Detmold, Germany
Telephone +49 (0) 5231 14-0
Fax +49 (0) 5231 14-2083
E-mail info@weidmuller.com Order number: