Knee Point Voltage and Current Transformers
09/23/2009 10:22 AM
dear friend,
kindly any one explaine me what is the effect of knee point voltage in CT.
If one PX Class CT having Vk>300V, Ia<30 mA how i calculate this CT BURDEN also what is the primary current when
th ct is satsurated,
thanking you,
yours ,
B.JEYACHANDRAN
Interested in this topic? By joining CR4 you can "subscribe" to
this discussion and receive notification when new comments are added.
Join CR4, The Engineer's Place for News and Discussion!
Manimaran
Vasan
Member
Join Date: Sep 2009
Location: ABB Limited,
Nashik
Posts: 9
Re: Knee Point Voltage and Current Transformers
09/26/2009 2:26 AM
Dear friend,
Knee Point voltage is nothing but a point at which the CT saturates. Thatsy its always better to design the CTs which
can operate without saturation even at a voltage appears in the CT during fault condition. Pls find below the following
formula for calculating the Knee point voltage.
Vk=2If(Rct+2Rl).
where, If is the current refected to the CT secondary during fault condition,
Rct is the resistance of the CT which can be adopted by means of a thumb rule considering the CT ratio,
Rl is the lead resistance i.e. sum of the resistance of the wire connected between the relay & CT and Impedance
offered by the internal circuitary of the relay
For PS class CT's designed considering the above,burden is not applicable.
Pls revert back if you have any further queries.
Regards,
Manimaran.V
B.JEYACHANDRAN
Active Contributor
Join Date: Apr 2009
Location: Madurai
Posts: 22
Re: Knee Point Voltage and Current Transformers
09/26/2009 2:42 AM
dear friend,
thank you for your guidence, how i calculate the fault current limit in primary side with knee point voltage
Manimaran
Vasan
Member
Join Date: Sep 2009
Location: ABB Limited,
Nashik
Posts: 9
Re: Knee Point Voltage and Current Transformers
09/26/2009 7:44 AM
Dear Friend,
Pls find below the formula for calculating the fault current,
Fault current(in KA) = Rated Curent/(% Impedance*1000)
% Impedence shall be calculated for the system from the point of source to the point of occurence of the fault.
The Engineer's Place for News and Discussion
Login | Register
5/19/2014 CR4 - Thread: Knee Point Voltage and Current Transformers
http://cr4.globalspec.com/thread/43832/Knee-Point-Voltage-and-Current-Transformers 2/3
#4
In reply to #3
#5
In reply to #3
#12
In reply to #1
#6
#7
In reply to #6
#8
In reply to #7
#9
In reply to #8
#11
In reply to #9
#10
Regards,
Manimaran.V
shock007
Active Contributor
Join Date: Jun 2008
Posts: 10
Re: Knee Point Voltage and Current Transformers
09/28/2009 4:12 AM
Dear Manimaran,
Can you please explain, how to calculate Ia and what is its significance?
Anonymous
Poster
Re: Knee Point Voltage and Current Transformers
09/28/2009 11:19 AM
dear friend,
thankyou friend
Anonymous
Poster #1
Re: Knee Point Voltage and Current Transformers
05/29/2012 1:48 AM
ayubkseb
Member
Join Date: Apr 2008
Location: Doha Qatar
Posts: 8
Re: Knee Point Voltage and Current Transformers
09/30/2009 12:38 PM
Dear member
For PX class CTs , the burden is not normally mentioned . There the CT is defiened based on the CT kneepoint voltage ,
magnetising current etc . The burden is mentioned in class P CTs
In PX class CTs the kneepoint voltage is normally based on the max fault current and a diamensioning factor based on
system X/R ratio
Ayub
shock007
Active Contributor
Join Date: Jun 2008
Posts: 10
Re: Knee Point Voltage and Current Transformers
09/30/2009 9:06 PM
Understand from above formula to calculate knee point voltage. Can you please explain how to calculate magnetising
current.
ayubkseb
Member
Join Date: Apr 2008
Location: Doha Qatar
Posts: 8
Re: Knee Point Voltage and Current Transformers
10/01/2009 12:24 AM
There is no formulae as such for calculating the magnetising current . However some a application demands minimum
value of mag current for relay setting ( eg; REF protection ). Iin any case a magnetising current of less than 30 mA
would be sufficient for most of the application
Manimaran
Vasan
Member
Join Date: Sep 2009
Location: ABB Limited,
Nashik
Posts: 9
Re: Knee Point Voltage and Current Transformers
10/01/2009 3:31 AM
ya.. thats right.. there is no formula for calculating magnetising current. however, lesser the magnetising current,
better is your CT performance.
Regards,
Manimaran.V
Govindarul
Participant
Join Date: May 2012
Posts: 2
Re: Knee Point Voltage and Current Transformers
05/07/2012 7:57 AM
The formula for calulating the required magnetising current for the CT =
[(IOP / CT Ratio) - IR] / n
Where,
IOP = Relay operating current (absolute current value in terms of CT primary)
IR = Relay setting current (in terms of CT secondary)
n = Number of parallel CTs forming (87) protected zone
Anonymous
Re: Knee Point Voltage and Current Transformers
06/20/2010 6:35 AM
5/19/2014 CR4 - Thread: Knee Point Voltage and Current Transformers
http://cr4.globalspec.com/thread/43832/Knee-Point-Voltage-and-Current-Transformers 3/3
#13
In reply to #10
Copy to Clipboard
Poster
Govindarul
Re: Knee Point Voltage and Current Transformers
05/29/2012 2:01 AM
Register to Reply
13 comments
Back to top
Interested in this topic? By joining CR4 you can "subscribe" to
this discussion and receive notification when new comments are added.
Join CR4, The Engineer's Place for News and Discussion!
Users who posted comments:
Anonymous Poster (3); ayubkseb (2); B.JEYACHANDRAN (1); Govindarul (2); Manimaran Vasan (3); shock007 (2)
Previous in Forum: UPS Rating and Capacity Next in Forum: Generator Life Expectancy
You might be interested in: Voltage Dividers and Voltage References, Display and Point of Purchase Services (POP), Voltage Converters and
Voltage Inverters
"Twenty years from now you will be more disappointed by the things that you didn't do than by the ones you did do. So throw off the
bowlines. Sail away from the safe harbor. Catch the trade winds in your sails. Explore. Dream. Discover." -- Mark Twain
All times are displayed in US/Eastern (EDT) (Register to change time zone)
2014 IHS.
No part of this site may be copied, transmitted or stored, in any form or by any means, without prior written permission of
IHS. The information contained on this site is by users for users and is provided for information purposes only and does not
constitute advice. Any views or opinions expressed by users are personal to them and do not represent the views or
opinions of IHS. You should check any information and use your own judgment or seek expert advice before doing or not
doing anything on the basis of what you read here. IHS does not verify or warrant the accuracy or completeness of any
information on this site and, to the extent permitted by law, IHS shall not be liable for any loss, damage or expense incurred
by reliance on it or for any dealings you have with users or other third parties that take place using or facilitated by this site.