RHOSS S.p.A. FanCoils Versione 1.

1
CASSETTE AIR HANDLING UNITS
Capacity
RANGE UTC VERSION ----- MODEL 40
10.84 [kW] Total Capacity
3007
6.35
8.41
[g/h]
[kW]
[kW]
Condensed Water
Sensible Capacity
Total Capacity
CooIing Heating
Number [n] 6 6 [n] Number
Rows
nlet DBT
WBT
RH
DBT
WBT
RH
Outlet
[C]
[C]
[%]
[C]
[C]
[%]
26.0
50
18.6
13.9
13.2
91
nlet DBT [C] 22
Outlet DBT [C] 42.6
[m/h] 1650 Flow rate
Med Speed
Flow rate
Speed
[m/h] 1650
Med
FIuid
Flow rate
Pressure drop
[l/h]
[kPa]
1441
14
Temperature nlet
Outlet
[C]
[C]
7.0
12.0
Fluid Water
Flow rate
Pressure drop
Temperature
Fluid
nlet
Outlet
[l/h]
[kPa]
[C]
[C]
1441
13
50.0
43.4
Water
Dimensions and Weight
[A]
[B]
[C]
Weight
[mm]
[mm]
[mm]
[kg]
1175
295
575
62
Other Data
Max. absorbed power [W]
[A]
Sound power level
Sound pressure level [dB(A)]
[dB(A)] 54
46
0 [Pa] Static Pressure
Sound pressure level measured at 1 meter distance from air outlet
Air
[V-ph-Hz] 230-1-50 Power supply
Max. absorbed current
Tel. 0432.911611 - Fax 0432.911600 E-mail. rhoss@rhoss.it - http: www.rhoss.it
RHOSS S.p.A.
Via Oltre Ferrovia - 33033 CODROPO (UD) - TALA
RHOSS S.p.A. FanCoils Versione 1.1
CASSETTE AIR HANDLING UNITS
Air handIing units UTC
Features
- Air handling unit: Cassette type for false ceiling installation, with direct air supply and intake.
- Heat exchanger: water finned coil.
- Fan: 3-speeds.
- Structure: self-bearing, of galvanized steel complete with: built-in condensate drain device to pump condensate
water from the drain pan to the natural discharge level, air supply panel with adjustable air diffusers, air intake grille
and cleanable filter.
- Standard version: 2-pipe systems.
Accessories suppIied Ioose
- KV3 - 3-way electrovalve for 2-pipe installations with auxiliary condensate drain pan.
- KV3B4 - 3-way electrovalve for 4-pipe installations with auxiliary condensate drain pan.
- KMC - Micropump for forced discharge of condensate water.
- KVA - Auxiliary condensate drain pan.
Standard controIs
KCV2 (supplied loose) Panel with 3-speed switch complete with summer/off/winter switch, with possibility to connect
the minimum temperature thermostat externally. Wall-mounted.
KTCV2 (supplied loose) Control and regulation panel comprising: off/continuous ventilation/thermostat-controlled
ventilation switch; ambient thermostat; summer/winter switch; speed switch; auxiliary contacts (230 Vac) for
controlling ON/OFF valves in 2-pipe, 2-pipe with heater (KRER) or 4-pipe systems, with possibility to connect the
minimum temperature thermostat externally. Wall-mounted
KTCVA (supplied loose) Electronic control panel comprising: continuous ventilation/off/thermostat-controlled
ventilation switch; three-speed switch; ambient thermostat; automatic summer/winter switch; red/green
heating/cooling LED; auxiliary contact (230 Vac) for controlling the ON/OFF valve for 2-pipe systems. Wall-mounted.
KTCVR (supplied loose) Electronic control panel comprising: on/off/heater switch; automatic summer/winter switch;
automatic speed/minimum speed switch; comfort adjustment knob 5C; auxiliary contacts (230 Vac) for controlling
the ON/OFF valve for 2-pipe, 2-pipe with heater (KRER) or 4-pipe systems. Wall-mounted.
EvoIuted controIs
KPCM (supplied loose) Electronic control panel with LCD display and 11 keys, for the manual or automatic
regulation of all the machine functions on the basis of the chosen ambient temperature. The panel is designed to be
wall-mounted.
KCMS (supplied loose) Electronic card, which can be configured as a master of slave card, for the manual or
automatic regulation of all the machine functions, complete with container for any additional KMVR and KMRR
modules.
KMVR (supplied loose) Module for managing ON/OFF valves in 2 or 4-pipe systems and for switching the relative
central units (cooler/heat pump/boiler) on and off, to be used in combination with the KCMS, KCMS/PCM, CMS,
CMS/PCM electronic card.
Tel. 0432.911611 - Fax 0432.911600 E-mail. rhoss@rhoss.it - http: www.rhoss.it
RHOSS S.p.A.
Via Oltre Ferrovia - 33033 CODROPO (UD) - TALA
RHOSS S.p.A. FanCoils Versione 1.1
CASSETTE AIR HANDLING UNITS
KST (supplied loose) Temperature sensor for additional water heating coil, to be used in combination with the
KCMS, KCMS/PCM, CMS, CMS/PCM electronic card.
SeriaI converters (suppIied Ioose)
KRS485 (supplied loose) RS485 serial interface for logical dialogue with building automation and supervision
systems, for use with the KCMS, KCMS/PCM, CMS, CMS/PCM electronic card (Supported protocols: proprietor
protocol; ModBus RTU).
KS (supplied loose) CAN-bus (Controller Area Network) serial interface for systems iDRHOSS, indispensable for
networking the units and serial addresses, for use with the KCMS, KCMS/PCM, CMS, CMS/PCM electronic card
(Can-Open protocol).
KRS232 (supplied loose) RS485/RS232 serial converter for connection to supervision systems, for use with one or
more KRS485 serial interface systems in the event of centralised unit management.
KRS232 (supplied loose) RS485/RS232 serial converter for connection to supervision systems, for use with one or
more KRS485 serial interface systems in the event of centralised unit management.