Sunteți pe pagina 1din 28

Engineered for flexibility and performance.

TM
Technical Manual MAC - 2011(60Hz)
Modular Air Cooled Chiller
Models: MAC160A-960A
MAC210A-1260A
Refrigerant Type: R22
Cooling Capacity: 56/70kW
1
Nomenclature..............................................................................................................................2
Features.......................................................................................................................................3
Specifcations .............................................................................................................................4
Sound Data ..................................................................................................................................7
Operating Limit ...........................................................................................................................8
Performance Data .......................................................................................................................8
Outlines and Dimensions ........................................................................................................10
Wiring Diagrams .......................................................................................................................12
Refrigerant Circuit ....................................................................................................................15
Equipment Options ..................................................................................................................16
Troubleshooting .......................................................................................................................20
Exploded view & Part list .........................................................................................................21
Contents
McQuay is a registered trademark of McQuay International. All rights reserved throughout the world.
2011 McQuay International. 2011 McQuay International.
Bulletin illustrations cover the general appearance of McQuay International products at the time of publication. We reserve the right to change
design and construction specifcations at any time without notice.
Note: Installation and maintenance are to be performed only by qualifed personnel who are familiar with
local codes and regulations, and experienced with this type of equipment.
Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
Warning: Moving machinery and electrical power hazard may cause severe personal injury or death.
Disconnect and lock off power before servicing equipment.
Literature No.: TM-MAC-1101A(60Hz)
Supersedes: TM-MAC-1001A(60Hz)
Part No.: M08039110006
2
Nomenclature
M AC 160 A ---P XX U
Export
Description
Power Supply
P: 208~230/3/60
Q: 460/3/60
Series
Nominal Cooling Capacity
Air Cooled Chiller
McQuay
3
MAC units are high thermodynamic engineering products, studied with high accuracy in balancing compressors,
condensers and evaporators in order to offer high performances and wide safety margins. The choice of the
materials and the equipment adopted for the products has been made without any compromis, for the purpose
of high quality and long service life. The products meet ISO 9001 and ISO 14001 requirements, and assurance
beyond any doubts of the high producing standards followed by McQuay.
Modular Design
MAC160A, MAC210A, designed as the 2 basic modules, can be combined with freedom to satisfy different load.
The maximum number of combination is 10 modules, however it
,
s still very convenient to transport and install these
units by separating them into single ones.
High Flexiblity
The MAC units are available in sizes covering a range of nominal cooling capacity from 56 to 420 kW. And with
availability of many accessories, including advanced control and safety devices, the mac units are of high fexibility
for their installation in commercial, residential and industrial buildings. They can couple with different types of fan
coil or AHU, proving themselves to be ideal for various kinds of areas by modular combination.
Low Installation Cost
The units are completely assembled at factory, reducing the cost of installation on site. A frm steel base evenly
distributes the weight of the unit to the support points and allows simple installation by an easy access to the lifting
points.
Compressor
McQuay Modular Air Cooled Chiller is equipped with highly effcient, reliable and silent scroll compressor which
features an internal overload protection. The compressor adopts hermetic type to further eliminate operating noise
and vibration.
Air-cooled Condenser
The two air cooled condenser coils with V-shaped are made of staggered rows of 3/8
"
OD seamless copper tube,
mechanically expanded into slit aluminum fns to ensure optimum heat exchange capability.
Condenser Fan Motor
To achieve the high air charge requirement, the unit is equipped with the high airfow propeller fan which is made
of acryl styrene resin. The fan is direct driven by weatherproof three-phase motor to ensure a reliable continuous
operation.
Evaporator
The heat exchanger is made of stainless steel plates closely arranged and brazed together to ensure high heat
exchange effciency. The complete heat exchanger is insulated with thermal closed cell nitric rubber foam to give
optimum thermal insulation.
Refrigerant Circuit
The refrigerant circuit is factory brazed and evacuated before accurately charged with R22 or R407C (optional)
to ensure optimum operating requirement. To ensure fawless continuous operation, each refrigerant circuit is
equipped with a carefully sized thermostatic expansion valve, or a capillary tube.
Additional Safety Protection
The modular air-cooled chillers are equipped with intelligently designed safety control to ensure continuous
safe operation. High and low pressure switch is provided to prevent the compressor damage resulting from both
abnormal high discharge head pressure and low pressure due to insuffcient gas.
In addition, thermal and current overload protector are supplied with the units as well as phase sequencer protector.
Features
4
Specifcations
MODEL MAC160A MAC320A MAC480A MAC640A MAC800A MAC960A
NOMINAL CAPACITY
Btu/h 191126 382253 573379 764505 955631 1146758
kW 56 112 168 224 280 336
NOMINAL TOTAL INPUT POWER kW 22 44 66 88 110 132
NOMINAL RUNNING CURRENT A 70 140 210 280 350 420
POWER SOURCE V/Ph/Hz 208~230/3/60,460/3/60
REFRIGERANT TYPE R22
CASING
MATERIAL ELECTRO-GALVANIZED MILD STEEL
FINISH EPOXY POLYESTER POWER
THICKNESS mm/inch 1.2/0.047
UNIT
DIMENSION
HEIGHT mm/inch 1785/70
WIDTH mm/inch 1820/72
DEPTH mm/inch 1000/40 2000/80 3000/120 4000/160 5000/200 6000/240
PACKING
DIMENSION
HEIGHT mm/inch 1940/76
WIDTH mm/inch 1930/76
DEPTH mm/inch 1150/44 2300/88 3450/132 4600/176 5750/220 6900/264
NET WEIGHT kg/lb 620/1366 1240/2732 1860/4098 2480/5464 3100/6830 3720/8196
GROSS WEIGHT kg/lb 670/1476 1340/2952 2010/4428 2680/5904 3350/7380 4020/8856
RUNNING WEIGHT kg/lb 640/1410 1280/2820 1920/4230 2560/5640 3200/7050 3840/8460
NOTES:
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING CAPACITY IS BASED ON LEAVING WATER TEMPERATURE 6.7C, AMBIENT TEMPERATURE 35C AND 0.043 L/S
PER kW WATER FLOW.
4) RECOMMENDED NUMBER OF THE UNITS CONNECTED IS 6. IF YOU HAVE TO CONNECT MORE UNITS, PLEASE CONTACT
SHENZHEN MCQUAY.
General Data
MODEL MAC210A MAC420A MAC630A MAC840A MAC1050A MAC1260A
NOMINAL CAPACITY
Btu/h 238908 477816 716724 955631 1194539 1433447
kW 70 140 210 280 350 420
NOMINAL TOTAL INPUT POWER kW 24.5 49 73.5 98 122.5 147
NOMINAL RUNNING CURRENT A 79 158 237 316 395 474
POWER SOURCE V/Ph/Hz 208~230/3/60,460/3/60
REFRIGERANT TYPE R22
CASING
MATERIAL ELECTRO-GALVANIZED MILD STEEL
FINISH EPOXY POLYESTER POWER
THICKNESS mm/inch 1.2/0.047
UNIT
DIMENSION
HEIGHT mm/inch 1940/76
WIDTH mm/inch 1940/76
DEPTH mm/inch 1140/45 2280/90 3420/135 4560/180 5700/225 6840/270
PACKING
DIMENSION
HEIGHT mm/inch 2250/92
WIDTH mm/inch 2140/46
DEPTH mm/inch 1200/85 2400/170 3600/255 4800/340 6000/425 7200/510
NET WEIGHT kg/lb 730/1609 1460/3218 2190/4827 2920/6436 3650/8045 4380/9654
GROSS WEIGHT kg/lb 780/1718 1560/3436 2340/5154 3120/6872 3900/8590 4680/10308
RUNNING WEIGHT kg/lb 750/1653 1500/3306 2250/4959 3000/6612 3750/8265 4500/9918
5
MODEL MAC160A MAC320A MAC480A MAC640A MAC800A MAC960A
EVAPORATOR
TYPE BRAZED PLATE HEAT EXCHANGER
PLATE MATERIAL STAINLESS STEEL
MODEL NAME V25*40*40
WATER VOLUME m
3
/ft
3
0.078/2.76 0.156/5.52 0.243/8.28 0.312/10.4 0.39/13.8 4.68/16.56
NOMINAL WATER FLOW
m/h/US
GPM
9.61/0.71 19.22/1.42 28.84/2.13 38.448/2.84 48.06/3.55 57.67/4.26
WATER LINE (HYDRAULIC KIT)
PIPING
INSTALLATION PIPE
CONNECTION
mm/inch 32/1-1/4
HEAD m 3
PIPE SIZE mm/inch 73.6/3
BPHE WPD kPa/psi 142/20.6 145/21.0 148/21.5 151/21.9 154/22.3 157/22.8
CONDENSER COIL
TYPE TUBE+FIN
TUBE
MATERIAL COPPER
TYPE INNER GROOVE
WALL THICKNESS mm/inch 0.36/0.01417
OUTER DIAMETER mm/inch 9.52/ 3/8
TUBE HEIGHT TH 36
FIN
MATERIAL ALUMINUM
THICKNESS mm/inch 0.11/0.00433
ROWS 3
FIN PER INCH 14
TOTAL FACE AREA m
2
/ft
2
2.75/29.6 5.5/59.2 8.25/88.8 11/118.4 13.75/148 16.5/177.6
CONDENSER FAN
TYPE/DRIVE AXIAL BIG VANE AND LOW NOISE BLOWER/DIRECT
QUANTITY 2 4 6 8 10 12
BLADE MATERIAL GALVANIZED STEEL
BLADE DIAMETER mm/inch 711.2/28
POWER SUPPLY V/Ph/Hz 208~230/3/60;460/3/60
RATED RUNNING
CURRENT
208~230V
A 4.5
460V
A 2.2
RATED INPUT POWER W 1000
RATED OUTPUT POWER W 850
MOTOR POLES 6
AIR VOLUME
CMH/
CFM
26000/15058 52000/30116 78000/45174 104000/60232 13000/75290 156000/90348
COMPRESSOR
TYPE SCROLL
QUANTITY 2 4 6 8 10 12
NOS OF CIRCUITS 2 4 6 8 10 12
POWER SUPPLY V/Ph/Hz 208~230/3/60;460/3/60
RATED RUNNING
CURRENT
208~230V
A 27
460V
A 13
RATED INPUT POWER W 7400
MAXIMUM STARTING
CURRENT
208~230V
A 148
460V
A 72
PROTECTION DEVICES H/L PRESSURE SWITCH/THERMAL AND CURRENT OVERLOAD PROTECTOR
STAGE OF CAPCITY CONTROL 2 4 6 8 10 12
INSULATION GRADE
E
LOCKED ROTOR AMP
208~230V A 248
460V A 120
REFRIGERANT
TYPE R22
CONTROL THERMOSTATIC EXPANSION VALVE AND CAPILLARY
REFRIGERANT CHARGE kg/lb 13.1/28.9 26.2/57.8 39.3/86.7 52.4/115.6 65.5/144.5 78.6/173.4
Components Data
6
MODEL MAC210A MAC420A MA C630A MAC840A MAC1050A MAC1260A
EVAPORATOR
TYPE BRAZED PLATE HEAT EXCHANGER
PLATE MATERIAL STAINLESS STEEL
MODEL NAME
208~230V B3-095-84
460V B3-095-96
WATER VOLUME
208~230V m
3
/ft
3
0.102/3.60 0.204/7.2 0.306/10.8 0.408/14.4 0.51/18 0.612/21.6
460V m
3
/ft
3
0.108/3.81 0.216/7.62 0.324/11.43 0.432/15.24 0.54/19.05 0.648/22.86
NOMINAL WATER FLOW
m/h/US
GPM
11.88/0.87 23.76/1.74 35.64/2.61 47.52/3.48 59.4/4.35 71.28/5.22
WATER LINE (HYDRAULIC KIT)
PIPING
INSTALLATION
PIPE
CONNECTION
mm/inch 38/1 1/2"
HEAD m 5
PIPE SIZE mm/inch 125/5"
BPHE WPD
208-230V
kPa/psi
72/10.4 75/10.9 78/11.3 81/11.7 84/12.2 87/12.6
460V 87/12.6 90/13.1 93/13.5 96/13.9 99/14.4 102/14.8
CONDENSER COIL
TYPE TUBE+FIN
TUBE
MATERIAL COPPER
TYPE INNER GROOVE
WALL THICKNESS mm/inch 0.36/0.01417
OUTER
DIAMETER
mm/inch 9.52/3/8
TUBE HEIGHT TH 40
FIN
MATERIAL ALUMINUM
THICKNESS mm/inch 0.11/0.00433
ROWS 3
FIN PER INCH 16
TOTAL FACE AREA m
2
/ft
2
3.50/37.6 7/15.2 10.5 14 17.5 21
CONDENSER FAN
TYPE/DRIVE AXIAL BIG VANE AND LOW NOISE BLOWER/DIRECT
QUANTITY 2 4 6 8 10 12
BLADE MATERIAL GALVANIZED STEEL
BLADE DIAMETER mm/inch 711.2/28
POWER SUPPLY V/Ph/Hz 208~230/3/60;460/3/60
RATED RUNNING
CURRENT
208~230V A 5.2
460V A 2.6
RATED INPUT POWER W 1150
RATED OUTPUT POWER W 840
MOTOR POLES 8
AIR VOLUME
CMH/
CFM
26000/15058 52000/30116 78000/45174 104000/60232 13000/75290 156000/90348
COMPRESSOR
TYPE SCROLL
QUANTITY 2 4 6 8 10 12
NOS OF CIRCUITS 2 4 6 8 10 12
POWER SUPPLY V/Ph/Hz 208~230/3/60;460/3/60
RATED RUNNING
CURRENT
208~230V A 31
460V A 15
RATED INPUT POWER W 8500
MAXIMUM
STARTING
CURRENT
208~230V A 172
460V A 84
PROTECTION DEVICES H/L PRESSURE SWITCH/THERMAL AND CURRENT OVERLOAD PROTECTOR
STAGE OF CAPCITY CONTROL 2 4 6 8 10 12
INSULATION GRADE E
LOCKED ROTOR
AMP
208~230V A 260
460V A 125
REFRIGERANT
TYPE R22
CONTROL THERMOSTATIC EXPANSION VALVE AND CAPILLARY
REFRIGERANT CHARGE kg/lb 13.1/28.9 26.2/57.8 39.3/86.7 52.4/115.6 65.5/144.5 78.6/173.4
7
Electric Data
MODEL MAC160A-PAAU MAC160A-QAAU MAC210A-PABU MAC210A-QABU
RATED TOTAL INPUT POWER (COOLING) W 22000 22000 24500 24500
RATED RUNNING CURRENT (COOLING) A 70 34 79 38
POWER SOURCE V/Ph/Hz 208~230/3/60 460/3/60 208~230/3/60 460/3/60
POWER
SOURCE
WIRE
MAIN WIRE SECTION AREA mm
2
25 10 25 10
(R/S/T) QTY 3
NETURAL SECTION AREA mm
2
6 4 6 4
WIRE QTY 1 1 1 1
EARTH SECTION AREA mm
2
25 10 25 10
WIRE QTY 1
CONTROL WIRE RVVP21mm
2
NOTES:
1) The above data are based on unit electronic parameter.
2) The wires should be well connected.
3) Every wire can not contact pipes, compressor, fan motor or other movable parts.
Safety Devices
HIGH PRESSURE SWITCH
OPEN Pa / psi 3000000/406
CLOSE Pa / psi 2400000/348
LOW PRESSURE SWITCH
OPEN Pa / psi 50000/7.25
CLOSE Pa / psi 150000/21.76
PHASE SEQUENCER Y
DISCHARGE THERMOSTAT SETTING C / F 1255/257.49
Sound Data
ACCORDING TO :ISO3744:1994 "ACOUSTICS--DETERMINATION OF SOUND POWER LEVELS OF NOISE SOURCES USING SOUND
PRESSURE--ENGINEERING METHOD IN AN ESSENTIALLY FREE FIELD OVER A REFLECTING PLANE".
Type
1/1 Octave Sound Pressure Level (dB,ref 20uPa)
dB(A)
63HZ 125HZ 250HZ 500HZ 1000HZ 2000HZ 4000HZ 8000HZ
MAC160A (208~230V/3Ph/60Hz) 49.0 54.6 58.9 66.2 68.4 63.6 58.5 54.6 71.90
MAC160A (460V/3Ph/60Hz) 49.3 54.2 57.9 65.6 67.9 63.7 57.3 52.9 71.40
MAC210A (208~230V/3Ph/60Hz) 50.8 52.7 58.0 64.3 66.4 62.5 57.3 51.0 70.20
MAC210A (460V/3Ph/60Hz) 49.4 53.4 57.4 64.4 66.6 61.9 56.8 49.1 70.00
8
Performance Data
COOLING CAPACITY
Cooling Performance Chart
0.80
25 28 30 35 40 43
0.82
0.84
0.86
0.88
0.90
0.92
0.94
0.96
0.98
1.00
1.02
1.04
1.06
1.08
1.10
1.12
1.14
1.16
1.18
Ambient Temperature ()
C
r
r
e
c
t
i
o
n

F
a
c
t
o
r

o
f

C
a
p
a
c
i
t
y
O
u
t
p
u
t

T
e
m
p
e
r
a
t
u
r
e

o
f

C
o
o
l
e
d

W
a
t
e
r

(

)
9
8
7
6
5
4
Operating Limit
15 15
leaving water temperature ()
5 7.5 10 12.5 15
40 40
A
m
b
i
e
n
t

t
e
m
p
e
r
a
t
u
r
e

(

)
20
25
35
30
operating limit
20
25
35
30
Cooling mode
5
48
10 7.5 15 12.5
48
9
Water Pressure Drop Chart
Water Pressure Drop Chart
0
40
80
120
160
200
240
280
320
Water Flowm
3
/h
P
r
e
s
s
u
r
e

D
r
o
p

k
P
a

6 7 8 9 10 11 12 13 14 15 5
MAC160A-PAA/QAA-E
COOLING POWER INPUT
Cooling Power Input Chart
0.84
0.86
0.88
0.90
0.92
0.94
0.96
0.98
1.00
1.02
1.04
1.06
1.08
1.10
Ambient Temperature ()
C
o
r
r
e
c
t
i
o
n

F
a
c
t
o
r

o
f

P
o
w
e
r
O
u
t
p
u
t

T
e
m
p
e
r
a
t
u
r
e

o
f

C
o
o
l
e
d

W
a
t
e
r

(

)
9
8
7
6
5
4
25 28 30 35 40 43
Correction Factors With Glycol Use
GLYCOL% COOLING CAPACITY WATER FLOW PRESSURE DROP
10 0.99 1.015 1.06
20 0.98 1.04 1.12
30 0.97 1.08 1.18
40 0.965 1.135 1.24
10
Water Out
Water In
Outlines and Dimensions
Model: MAC160A
Model: MAC210A
Water Out
Water In
Water Pressure Drop Chart
0
20
40
60
80
100
120
140
160
6 17 18 7 8 9 10 11 12 13 14 15 16
180
Water Flowm
3
/h
P
r
e
s
s
u
r
e

D
r
o
p

k
P
a

MAC210A-PAB/QAB-E
11
Models: MAC960A
91
3
3
AxN=L
A A A A A A
2
3
2
.
5
3
4
3
1820
335
1
7
2
4
1
7
8
5
Intel
Outel
Models: MAC1260A
A A A A A A
2
0
8
9
2
1
9
3
2056
303
AxN=L 110
3
3
3
3
5
4
5
6
.
5
Intel
Outel
Unit: mm mm
Unit: mm mm
MODEL NUMBER Single unit size (A) units size (L)
MAC160A 1 1000 1000
MAC320A 2 1000 2000
MAC480A 3 1000 3000
MAC640A 4 1000 4000
MAC800A 5 1000 5000
MAC960A 6 1000 6000
n (n10) 1000 1000 x n
MODEL NUMBER Single unit size (A) units size (L)
MAC210A 1 1030 1030
MAC420A 2 1030 2060
MAC630A 3 1030 3090
MAC840A 4 1030 4120
MAC1050A 5 1030 5150
MAC1260A 6 1030 6180
n (n10) 1030 1030 x n
12
Wiring Diagrams
Ensure that the rated voltage of the unit corresponds to that of the name plate before general precautions.
Provide a power outlet to be used exclusively for each unit. A power supply disconnects and a circuit breaker for
over-current protection should be provided in the exclusive line.
The modular air-cooled chillers must be well grounded. It absolutely cannot be connected with gas-pipe, water pipe
and telephone line.
With MCH03B Controller
208-230V/3Ph/60Hz
HEATER
24 25
T
KM1
S
R
KM2
FAN2 FAN1
OL3 OL4
L1
2. 1A
OL3
2. 1A
OL4
PCB
MCH03B
CN6
A B
CN4
H
T
/E
V
1
LIVE
NEUTRAL
C
O
M
P
1
L2
TH1
C
O
M
P
2
TH2 TH3
E
V
2
4
W
V
-1
TH5 TH4
4
W
V
-2
A
-H
A
T
KM3 KM4
1 2
KM1 KM2
A
L
-O
U
T
M
/F
A
N
2
HP2
HP1
OL3
B A JP5
CN5
JP8
JP4
JP3
SET/SF
JP1
JP2
LP1
HP1
23
22
A
L
-IN
P
U
M
P
H
/F
A
N
1
JP6
L
/H
E
A
T
OV-COMP2
OV-COMP1
OV-FAN
OV-PUMP
16
FLOW
FREZ/LP2
OVHT/HP2
EN-SAVE
N-COM
13
14
12
L2
LP1
OL4 17
DPS
LP2
5 6 7
KM5 KM3 KM4
19
21
TC1
TC2
SYMBOL
OL3- 4
HP1- 2
LP1- 2
CRANKCASE HEATER
HEATER
CRANKCASE
DESCRI PTI ON
COMPRESSOR
DESCRI PTI ON:
COMP1- 2
KM1- 4
FAN1- 2
SYMBOL
SYMBOL
FAN MOTOR
CONTACTOR
TEMPERATURE SWI TCH
DI SCHARGE
OVERLOAD PROTECTOR
TC1- 2
DESCRI PTI ON
LOW PRESSURE SWI TCH
HI GH PRESSURE SWI TCH
PHASE PROTECTOR
DESCRI PTI ON
FU
SYMBOL
FUSE
OVERLOAD PROTECTOR SETTI NG:
E
N
V
IR
O
N
M
E
N
T
T
H
E
R
M
O
S
T
A
T
L
E
A
V
IN
G
W
A
T
E
R
T
H
E
R
M
O
S
T
A
T
E
N
T
E
R
IN
G
W
A
T
E
R
T
H
E
R
M
O
S
T
A
T
25
15
18
L2
L3
28
RM4-TG20
L1
JP3
OPEN CLOSE
JP1 JP2 JP7 JP5 JP4 JP6 JP8
CLOSE OPEN CLOSE OPEN OPEN OPEN
JUMPPER SETTI NG:
COMP1
CRANKCASE
~
COMP2
~
CRANKCASE
HEATER
M M
~ ~
M M
JP7
MODEL: MAC160/210A(SLAVE UNIT)
PRESSURE SWI TCH DPS
FU1
FU2
208~230V/3~/60Hz
RM4- TG20
TO LAST SLAVE UNIT TO NEXT SLAVE UNIT
I F UNI T I S FI NAL SLAVE UNI T, JP8 JUMPER I S CLOSE
FACTORY WI RI NG
FI ELD WI RI NG 1:
3:
2:
NOTE:
JP3
OPEN CLOSE
JP1 JP2 JP7 JP5 JP4 JP6 JP8
HEATER
24 25
T
KM1
S
R
KM2
FAN2 FAN1
OL3 OL4
L1
2.1A
OL3
2.1A
OL4
PCB
MCH03B
CN6
A B
CN4
H
T
/E
V
1
LIVE
NEUTRAL
C
O
M
P
1
L2
TH1
C
O
M
P
2
TH2 TH3
E
V
2
4
W
V
-1
TH5 TH4
4
W
V
-2
A
-H
A
T
KM3 KM4
1 2
KM1 KM2
A
L
-O
U
T
M
/F
A
N
2
HP2
HP1
OL3
B A JP5
CN5
JP8
JP4
JP3
SET/SF
JP1
JP2
LP1
HP1
23
22
POWER
CN4
A
L
-IN
CN3
CN2
CN1
P
U
M
P
H
/F
A
N
1
JP6
LCD DISP WINDOW
L
/H
E
A
T
OV-COMP2
OV-COMP1
OV-FAN
OV-PUMP
16
15
FLOW
FREZ/LP2
OVHT/HP2
EN-SAVE
N-COM
13
14
12
11
L2
LP1
OL4 17
DPS
LP2
5 6 7
KM5 KM3 KM4
10 9
19
21
TC1
TC2
SYMBOL
OL3-4
HP1-2
LP1-2
CRANKCASE HEATER
HEATER
CRANKCASE
DESCRIPTION
COMPRESSOR
DESCRIPTION:
COMP1-2
KM1-4
FAN1-2
SYMBOL
SYMBOL
FAN MOTOR
CONTACTOR
TEMPERATURE SWITCH
DISCHARGE
OVERLOAD PROTECTOR
TC1-2
DESCRIPTION
LOWPRESSURE SWITCH
HIGH PRESSURE SWITCH
PHASE PROTECTOR
DESCRIPTION
FU
SYMBOL
FUSE
CLOSE CLOSE CLOSE CLOSE OPEN OPEN
JUMPPER SETTING:
OVERLOAD PROTECTOR SETTING:
E
N
V
IR
O
N
M
E
N
T
T
H
E
R
M
O
S
T
A
T
L
E
A
V
IN
G
W
A
T
E
R
T
H
E
R
M
O
S
T
A
T
E
N
T
E
R
IN
G
W
A
T
E
R
T
H
E
R
M
O
S
T
A
T
25
15
18
L2
L3
28
RM4-TG20
L1
COMP1
CRANKCASE
~
COMP2
~
CRANKCASE
HEATER
M M
~ ~
M M
JP7
AC/DC
ALARM INDICATOR LIGHT AC/DC POWER
2-WAY VALVE INTERLOCKING
PUMP OVERLOAD PROTECTOR SC302B CONTROLLER
POWER
ADAPTER
PUMP CONTACTOR
NOTE:
4:
1:
3:
2:
FIELD WIRING
FACTORY WIRING
KM5
IF 2-WAY VALVE INTERLOCKING FUNCTION IS PERMITED ,
JP6 JUMPER IS OPEN .OTHERWISE IS CLOSE(FACTORY SETTING)
TO SLAVE UNIT
PRESSURE SWITCH DPS
FU1
FU2
208~230V/3~/60Hz
RM4-TG20
MODEL: MAC160/210A(MASTER UNIT)
13
460V/3Ph/60Hz
JP3
OPEN CLOSE
JP1 JP2 JP7 JP5 JP4 JP6 JP8
HEATER
24 25
T
KM1
S
R
KM2
FAN2 FAN1
OL3 OL4
L1
2.1A
OL3
2.1A
OL4
PCB
MCH03B
CN6
A B
CN4
H
T
/E
V
1
LIVE
NEUTRAL
C
O
M
P
1
L2
TH1
C
O
M
P
2
TH2 TH3
E
V
2
4
W
V
-1
TH5 TH4
4
W
V
-2
A
-H
A
T
KM3 KM4
1 2
KM1 KM2
A
L
-O
U
T
M
/F
A
N
2
HP2
HP1
OL3
B A JP5
CN5
JP8
JP4
JP3
SET/SF
JP1
JP2
LP1
HP1
23
22
POWER
CN4
A
L
-IN
CN3
CN2
CN1
P
U
M
P
H
/F
A
N
1
JP6
LCD DISP WINDOW
L
/H
E
A
T
OV-COMP2
OV-COMP1
OV-FAN
OV-PUMP
16
15
FLOW
FREZ/LP2
OVHT/HP2
EN-SAVE
N-COM
13
14
12
11
L2
LP1
OL4 17
DPS
LP2
5 6 7
KM5 KM3 KM4
10 9
19
21
TC1
TC2
SYMBOL
OL3-4
HP1-2
LP1-2
CRANKCASE HEATER
HEATER
CRANKCASE
DESCRIPTION
COMPRESSOR
DESCRIPTION:
COMP1-2
KM1-4
FAN1-2
SYMBOL
SYMBOL
FAN MOTOR
CONTACTOR
TEMPERATURE SWITCH
DISCHARGE
OVERLOAD PROTECTOR
TC1-2
DESCRIPTION
LOWPRESSURE SWITCH
HIGH PRESSURE SWITCH
PHASE PROTECTOR
DESCRIPTION
FU
SYMBOL
FUSE
CLOSE CLOSE CLOSE CLOSE OPEN OPEN
JUMPPER SETTING:
OVERLOAD PROTECTOR SETTING:
E
N
V
IR
O
N
M
E
N
T
T
H
E
R
M
O
S
T
A
T
L
E
A
V
IN
G
W
A
T
E
R
T
H
E
R
M
O
S
T
A
T
E
N
T
E
R
IN
G
W
A
T
E
R
T
H
E
R
M
O
S
T
A
T
PUMP CONTACTOR
NOTE:
4:
1:
3:
2:
FIELD WIRING
FACTORY WIRING
KM5
IF 2-WAY VALVE INTERLOCKING FUNCTION IS PERMITED ,
JP6 JUMPER IS OPEN .OTHERWISE IS CLOSE(FACTORY SETTING)
25
15
18
L2
L3
28
RM4-TG20
L1
COMP1
CRANKCASE
~
COMP2
~
CRANKCASE
HEATER
M M
~ ~
M M
JP7
AC/DC
MODEL: MAC160/210A(MASTER UNIT)
ALARM INDICATOR LIGHT AC/DC POWER
2-WAY VALVE INTERLOCKING
PUMP OVERLOAD PROTECTOR SC302B CONTROLLER
POWER
ADAPTER
TO SLAVE UNIT
PRESSURE SWITCH DPS
RM4-TG20
460V
230V
FU1
TF
FU2
460V/3~/60Hz
TRANSFORMER TR
JP3
OPEN CLOSE
JP1 JP2 JP7 JP5 JP4 JP6 JP8
HEATER
24 25
T
KM1
S
R
KM2
FAN2 FAN1
OL3 OL4
L1
2.1A
OL3
2.1A
OL4
PCB
MCH03B
CN6
A B
CN4
H
T
/E
V
1
LIVE
NEUTRAL
C
O
M
P
1
L2
TH1
C
O
M
P
2
TH2 TH3
E
V
2
4
W
V
-1
TH5 TH4
4
W
V
-2
A
-H
A
T
KM3 KM4
1 2
KM1 KM2
A
L
-O
U
T
M
/F
A
N
2
HP2
HP1
OL3
B A JP5
CN5
JP8
JP4
JP3
SET/SF
JP1
JP2
LP1
HP1
23
22
A
L
-IN
P
U
M
P
H
/F
A
N
1
JP6
L
/H
E
A
T
OV-COMP2
OV-COMP1
OV-FAN
OV-PUMP
16
FLOW
FREZ/LP2
OVHT/HP2
EN-SAVE
N-COM
13
14
12
L2
LP1
OL4 17
DPS
LP2
5 6 7
KM5 KM3 KM4
19
21
TC1
TC2
SYMBOL
OL3-4
HP1-2
LP1-2
CRANKCASE HEATER
HEATER
CRANKCASE
DESCRIPTION
COMPRESSOR
DESCRIPTION:
COMP1-2
KM1-4
FAN1-2
SYMBOL
SYMBOL
FAN MOTOR
CONTACTOR
TEMPERATURE SWITCH
DISCHARGE
OVERLOAD PROTECTOR
TC1-2
DESCRIPTION
LOWPRESSURE SWITCH
HIGH PRESSURE SWITCH
PHASE PROTECTOR
DESCRIPTION
FU
SYMBOL
FUSE
CLOSE OPEN CLOSE OPEN OPEN OPEN
JUMPPER SETTING:
OVERLOAD PROTECTOR SETTING:
E
N
V
IR
O
N
M
E
N
T
T
H
E
R
M
O
S
T
A
T
L
E
A
V
IN
G
W
A
T
E
R
T
H
E
R
M
O
S
T
A
T
E
N
T
E
R
IN
G
W
A
T
E
R
T
H
E
R
M
O
S
T
A
T
L3 15
RM4-TG20
L1
L2
25
18
28
TR TRANSFORMER
COMP1
CRANKCASE
~
COMP2
~
CRANKCASE
HEATER
M M
~ ~
M M
JP7
MODEL: MAC160/210A(SLAVE UNIT)
PRESSURE SWITCH DPS
RM4-TG20
TO LAST SLAVE UNIT TO NEXT SLAVE UNIT
IF UNIT IS FINAL SLAVE UNIT, JP8 JUMPER IS CLOSE
FACTORY WIRING
FIELD WIRING 1:
3:
2:
NOTE:
TF
230V
460V
FU1 FU2
460V/3~/60Hz
14
With MC01 (OYLM) Chiller Panel Controller
208-230V/3Ph/60Hz
JH1
JUMPPER SETTING:
OPEN
OL4
DESCRIPTION
LOWPRESSURE SWITCH
HIGH PRESSURE SWITCH PHASE PROTECTOR
DESCRIPTION
NOTE:
CONTACTOR
COMPRESSOR COMP
KM
SYMBOL
RM4-TG20 HP
LP
SYMBOL
HEATER
DESCRIPTION
FUSE OVERLOAD PROTECTOR FU OL
SYMBOL
FAN1 FAN2
208-230V/3~/60Hz
KM1
25
T
R
S
26
KM2 KM4
CLOSE
JH2
2:
NOTE:
1:
FACTORY WIRING.
FIELD INSTALLATION.
ENTERING WATER TEMPERATURE
OUTDOOR AMBENT SENSOR
LEAVING WATER TEMPERATURE
N
L
IV
E
C
O
M
2
1 2
C
O
M
1
B
O
IL
E
R
KM1 KM2
W
-P
U
M
P
O
U
T
-F
A
N
2
O
U
T
-F
A
N
1
4
W
V
1
4
W
V
2
5 7
A
-F
R
E
E
Z
E
A
L
M
-O
U
T
11
KM3 KM4
AC/DC SUPPLY
A
L
M
-IN
12
ALARM
MAC160A
TOLERANCE SETTING:
MODEL
5.3A
OL3
5.3A
OL4
LCD DISP WINDOW
1
2
V
L
P
2
F
0
2
F
0
1
L
P
1
H
P
2
H
P
1
C
O
2
C
O
1
F
L
O
W
P
O
A
L
-M
D
E
2
D
E
1
C
/H
O
N
/O
F
F
W
I
W
O
O
A
C
D
1
C
D
2
D
F
1
D
F
2
O
L
5
O
L
3
O
L
4
JH1
JH2
3
18 13 14 15 16 17 19 22
COMPRESSOR DISCHARGE SENSOR 1
COMPRESSOR DISCHARGE SENSOR 2
USER PANEL
N
FAN FAN MOTOR
24
OL3
KM3
DPS QS SWITCH
KM6 KM7
27 28
WATER PUMP, BOILER AND ANTIFREEZE CONTROL CONTACTOR . KM5, KM6, KM7 3:
KM5
4
D
P
S
23
QS
18
L3 15
RM4-TG20
28
25
L1
L2
7.2A 7.2A MAC210A
OL1 OL2
OL2 OL1
42.0A
47.0A 47.0A
42.0A
O
L
1
O
L
2
20 21
CRANKCASE
COMP1
~
M
COMP2
CRANKCASE
HEATER
~
M
~
M
MODEL: MAC160/210A
L
P
2
L
P
1
H
P
2
H
P
1
PCB BOARD
M
~
FU2
FU1
DIFFERENTIAL PRESSURE SWITCH
JH1
JUMPPER SETTING:
OPEN
OL4
DESCRIPTION
LOWPRESSURE SWITCH
HIGH PRESSURE SWITCH PHASE PROTECTOR
DESCRIPTION
NOTE:
CONTACTOR
COMPRESSOR COMP
KM
SYMBOL
RM4-TG20 HP
LP
SYMBOL
HEATER
DESCRIPTION
FUSE
OVERLOAD PROTECTOR FU OL
SYMBOL
FAN1 FAN2
460V/3~/60Hz
KM1
25
T
R
S
26
KM2 KM4
CLOSE
JH2
2:
NOTE:
1:
FACTORY WIRING.
FIELD INSTALLATION.
ENTERING WATER TEMPERATURE
OUTDOOR AMBENT SENSOR
LEAVING WATER TEMPERATURE
N
L
IV
E
C
O
M
2
1 2
C
O
M
1
B
O
IL
E
R
KM1 KM2
W
-P
U
M
P
O
U
T
-F
A
N
2
O
U
T
-F
A
N
1
4
W
V
1
4
W
V
2
5 7
A
-F
R
E
E
Z
E
A
L
M
-O
U
T
11
KM3 KM4
AC/DC SUPPLY
A
L
M
-IN
12
ALARM
MAC160A
TOLERANCE SETTING:
MODEL
2.5A
OL3
2.5A
OL4
LCD DISP WINDOW
1
2
V
L
P
2
F
0
2
F
0
1
L
P
1
H
P
2
H
P
1
C
O
2
C
O
1
F
L
O
W
P
O
A
L
-M
D
E
2
D
E
1
C
/H
O
N
/O
F
F
W
I
W
O
O
A
C
D
1
C
D
2
D
F
1
D
F
2
O
L
5
O
L
3
O
L
4
JH1
JH2
3
18 13 14 15 16 17 19 22
COMPRESSOR DISCHARGE SENSOR 1
COMPRESSOR DISCHARGE SENSOR 2
USER PANEL
N
FAN FAN MOTOR
24
OL3
KM3
DPS QS SWITCH
KM6 KM7
27 28
WATER PUMP, BOILER AND ANTIFREEZE CONTROL CONTACTOR. KM5, KM6, KM7 3:
KM5
4
D
P
S
23
QS
L3
RM4-TG20
L2
L1
15
18
28
25
TF TRANSFORMER
2.9A 2.9A MAC210A
OL2 OL1
20.0A
23.0A 23.0A
20.0A
OL2 OL1
CRANKCASE
COMP1
~
M
COMP2
CRANKCASE
HEATER
~
M
~
M
MODEL: MAC160/210A
L
P
2
L
P
1
H
P
2
H
P
1
PCB BOARD
M
~
FU2
230V
TF
460V
FU1
21 20
O
L
1
O
L
2
DIFFERENTIAL PRESSURE SWITCH
460V/3Ph/60Hz
15
Refrigerant Circuit
Model: MAC160A
REFRIGERANT FLOW
WATER IN
2
3
4
5
4
3
WATER
OUT
6 ACCUMULATOR
1 COMPRESSOR
4 CAPILLARY 5 BPHE
2 HEAT EXCHANGER 3 LIQUID RECEIVER
2
1
6
1
6
Model: MAC210A
WATER INLET
WATER OUTLET
REFRIGERANT FLOW
1 COMPRESSOR 2 HEAT EXCHARGER 3 DRY-FILTER
4 TXV 5 BPHE 6 ACCUMULATOR
2
3
4
2
3
4
5
1
1
6
NOTE: THE PICTURE ABOVE IS FOR REFERENCE ONLY
16
Equipment Options
1. INSPECTION
All modular air cooled chillers are transported with pallet. and fully charged with refrigerant. Additional refrigerant
charge at site is not necessary.
All units should be visually inspected and make sure all accessories delivered together with units.
2. STORAGE
All units shall be stored at appropriate storage conditions. DO NOT stack the units.
3. INSTALLATION LOCATION
3.1 All units shall be installed at appropriate locations. Improperly installed units may lead to failure and void of
warranty.
3.2 Suffcient clearance in between units and walls shall be provided for easy maintenance and air circulation.
3.3 Short cycle of hot condenser air shall be avoid at all time. Adequate space and minimum height clearance
shall be provided. Short condenser air cycle may shorten equipment life span, frequent system failure or
equipment unable to start up.
3.4 All obstacles surrounding the unit shall be removed to ensure proper air circulation.
3.5 Installation environment shall be non-hazardous and non-explosive. Highly acidic and highly polluted
environment may affect system performance and lead to condenser coil choke, system failure and shorter
equipment life.
Space between units
should be at least 1.5m
Space between units and the wall
should be at least 1.8m
Space between units and the wall
should be at least 1.8m
The hight of the unit
3m high space
for ventilation
OBSTACLE
OBSTACLE BLOCKING
AIR INLET
MODULAR AIR COOLED CHILLERS
OBSTACLE BLOCKING
AIR OUTLET
OBSTACLE BLOCK AIR INTAKE
17

T|l C|Tlk
b^ClT\0 ^\0l
lOkl TlTlk
Ck^Ml b^k
C^bl Ck^\l
1.8m
Min 3m
AIR DISCHARGE
4. HANDLING
Each modular air cooled chiller is skidded at the factory. Care should be taken during handing to avoid damage
to the unit and internal components. Fork lifter or cable crane should be used for easy erection.

5. LIFTING METHOD
Lifting ropes shall be used on the suspension plates on top of the unit.
During lifting, special attention should be pay to the center of gravity of the unit.
Special care should be pay to lifting ropes during lifting of the unit. Lifting tools such as cramp bar shall be used
to protect the unit.
18
T|l OC^TTO\ Ol T|l
lOOT bOkl
FOUNDATION BOLT

M20(M10)x300

Notes:
1. The foundation should be mattess or channel structure which can support at least 400kg/m2.
2. 20mm thickness rubber shock pad is needed between the unit and the foundation.
3. n is the total number of the module.

6. INSTALLATION BASE
6.1 The unit must be installed on a fat and level concrete foundation. It can be conveniently installed on rooftop,
terrace and other proper places.
6.2 Drain pipe
6.3 Strong enough

19
1
2
T
l
k
M
T
\
^


D
l
\
T
C
l
4
3
5
13
14
3
15
12
11
11
10
WATER INLET
7
8
9
8
WATER OUTLET
OVERFLOW OUTLET
6
7.INSTALLATION
system 1
T
l
k
M
T
\
^


D
l
\
T
C
l

!
WATER INLET
^
|
\
T
T
^
k
Y

l

l
C
Tk
T
C
^


|
l
^
T
lk
OVERFLOW OUTLET
2
4
1
3
8
12
13
11
10
14
8
9
WATER OUTLET
6
system 2
1 Pressure Gauge (0-1MPa) 7 Auto air vent valve 13 Check Valve
2 Flexible Joint 9 Expansion Tank 14 Bypass Valve
3,5,8 Gate Valve 10 Y-strainer 15 Thermometer (0-100)
4 Drain Valve 11 Reducer
6 Expansion Tank 12 Pump
Note: Both system 1 and system 2 are used on less than 6 units connection (Inc. 6 units). System 2 is most used on more than 6 units connection.
This is helpful for balance of the hydraulic system.
Prior to starting up the unit, fushing of the water system is required:
1. Shut off the inlet and outlet valves and turn on the bypass valve.
2. Run the pump to circulate the water in the system for a while.
3. Open up the strainer to inspect the flter.
4. Clean the flter if necessary to ensure no debris trap in the piping system.
5. Shut off the bypass valve and turn on inlet and outlet valves
6. System is ready for operation.
20

Caution
Clean water has to be used to avoid corrosion and damage of the system. If the system is operating under harsh atmospheric or water conditions
(acidic, corrosive etc.), system is expected to face drop in capacity and might eventually lead to failure.
Troubleshooting
SYMPTOMS POSSIBLE CAUSES REMEDIAL ACTION
Compressor stops wi thout
reason. (alarm lamp is on)
1. Control system faulty.
2. Compressor faulty.
Contact local dealer.
Noisy and vibrancy
1. Dirt or dust in fan motor.
2. Compressor noisy.
3. Vibrancy noise caused by foor or wall.
1. Clean away dirt or dust.
2. Contact local dealer.
3. Check the installation.
Fan motor cease running.
1. Circuit faulty.
2. Overheat relay starting.
1. Check the circuit and repair when necessary.
2. Contact local dealer.
Insuffcient cooling/heating.
1. Compressor faulty.
2. Contamination in hydraulic system.
3. Clogged condenser coil.
4. Low refrigerant charge.
1. Contact local dealer.
2. Clean hydraulic system.
3. Clean the coil.
4. Add refrigerant.
Cycling water pump does not
start.
1. No power supply.
2. Water pump motor faulty.
3. water pump
1. Check power system.
2. Check water pump or change if necessary.
3. Try to run the water vane or change water pump it
necessary.
Water cycling faulty.
1. Gas in cycling system.
2. Deposit or dirt in the heat exchanger.
1. Discharge the gas.
2. Backwash heat exchanger.
Unit does not start.
1. Water fow switch faulty.
2. Pressure switch faulty.
1. Check water fow.
2. Check system pressure.
21
Exploded view & Part list
22
NO. Part Number Description Quantity
1 M01014300958 FAN GUARD 2
2 M03019000807 FAN BLADE,89MM TFE710C-89 XINCHANG 2
3 M50014300883 PANEL,OUTFLOW 2
4 M03039001528 MOTOR,YDK1000-6BCYONGAN 2
5 M50014300882 FAN SUPPORT 2
6 M50024301859 ASSY,RIGHT COIL 2
7 M50024301858 ASSY,LEFT COIL 2
8 ASSY,METAL STRUCTURE 1
9 M01014300932 PANEL,LEFT SURFACE 2
10 M04109010636 PRESSURE SWITCH 2.4/2.8MPa 1
11 A50054009748 ASSY,ACCESS VALVE 1/4 SP2200 4
12 M04109010637 PRESSURE SWITCH 0.05/0.15MPa 1
13 M50049305803 CONTROL BOX ASSY 1
14 A02169000502 FILTER DRIER,BFK-085S ALCO 2
15 M02089321002 CAPILLARY 4
16 M01014300930 PANEL,FRONT SURFACE A 1
17 M01014300931 PANEL,FRONT SURFACE B 1
18 M0419010625 COMPRESSOR,ZR125KC-TF5-522 (WITH HEATER) 2
19 M02119012953 ACCUMULATOR,QFQ5.2-A-01 6.0L TONGLI 2
20 ASSY,COPPER TUBE 1
21 M01014300929 PANEL,FRONT AND BACK SURFACE 3
22 have no this part
23 M04064305407 DIFFERENCE PRESSURE 5/9KPa 1
24 M02209000726 HEAT EXCHANGER,BRAZED PLATE V25*40*40 SWEP 1
25 M02069005115 STRIANER,WATER CU PN25(1 1/4") ITALY OR
26 M50104303801 WATER PIPE ,INLET(PPR) 1
27 M50104303806 WATER PIPE ,OUTLET(PPR) 1
28 M50014300880 ASSY,BASE PAN 1
TERMINAL BOX M50044304010
1 A04119003779 TERMINAL BLOCK ,ET3501-3P-1 1
2 M04119003708 TERMINAL BLOCK ,HP-T3021-18P
3 M04039003178 CONTACTOR,LC1-D6511MTC T.E. 2
4 M04039003169 CONTACTOR,LC1-D0910M7C T.E. 2
5 M04169003904 FUSE LINK RT14-4A WITH BASE DELIXI 1
6 M04199011980 PHASE PROTECTOR DB3A01A 1
7 M04089011195 CONTROL MODULE,MCH03B EC (B4.3) 1
8 M04089900249 CONTROLLER SC302B(MCQUAY,CHINESE) 1
9 M04179003990 OVERLOAD PROTECTOR,LR2-D1307N1.6-2.5A) 2
MAC160A-PAA-E
23
NO. Part Number Description Quantity
1 M01014300958 FAN GUARD 2
2 M03019000807 FAN BLADE,89MM TFE710C-89 XINCHANG 2
3 M50014300883 PANEL,OUTFLOW 2
4 M03039001527 MOTOR,YDK1000-6AC YONGAN 2
5 M50014300882 FAN SUPPORT 2
6 M50024301859 ASSY,RIGHT COIL 2
7 M50024301858 ASSY,LEFT COIL 2
8 ASSY,METAL STRUCTURE 1
9 M01014300932 PANEL,LEFT SURFACE 2
10 M04109010636 PRESSURE SWITCH 2.4/2.8MPa 1
11 A50054009748 ASSY,ACCESS VALVE 1/4 SP2200 4
12 M04109010637 PRESSURE SWITCH 0.05/0.15MPa 1
13 M50049305803 CONTROL BOX ASSY 1
14 A02169000502 FILTER DRIER,BFK-085S ALCO 2
15 M02089321002 CAPILLARY 4
16 M01014300930 PANEL,FRONT SURFACE A 1
17 M01014300931 PANEL,FRONT SURFACE B 1
18 A050049004677 COMPRESSOR,ZR125KC-TFD-522(WITH HEATER) 2
19 M02119012953 ACCUMULATOR,QFQ5.2-A-01 6.0L TONGLI 2
20 ASSY,COPPER TUBE 1
21 M01014300929 PANEL,FRONT AND BACK SURFACE 3
22 have no this part
23 M04064305407 DIFFERENCE PRESSURE 5/9KPa 1
24 M02209000726 HEAT EXCHANGER,BRAZED PLATE V25*40*40 SWEP 1
25 M02069005115 STRIANER,WATER CU PN25(1 1/4"ITALY OR
26 M50104303801 WATER PIPE ,INLET(PPR) 1
27 M50104303806 WATER PIPE ,OUTLET(PPR) 1
28 M50014300880 ASSY,BASE PAN 1
TERMINAL BOX M50044304010
1 A04119003779 TERMINAL BLOCK ,ET2501-3P-1 1
2 M04119003708 TERMINAL BLOCK ,HP-T3021-18P
3 M04039003178 CONTACTOR,LC1-D6511MTC T.E. 2
4 M04039003151 CONTACTOR,LC1-2501M7C 2
5 M04169003904 FUSE LINK RT14-4A WITH BASE DELIXI 1
6 M04199362000 PHASE PROTECTOR RM4-TG20 T.E. 1
7 M04089012294 CONTROL MODULE,MC01 EC MC2.0 2CP 1
8 M04089900249 CONTROLLER SC302B(MCQUAY,CHINESE) 1
9 M04179003990 OVERLOAD PROTECTOR,LR2-D1307N1.6-2.5A) 2
MAC160A-QAA-E
24
25
MAC210A-PAB-E
NO. Part Number Description Quantity
1 M01014302202 OUTER NOZZLE 810mm 2
2 M03019000809 FAN BLADE,240MM DBF7A-240 XINCHANG 2
3 M01014303266 PANEL,OUTFLOW 2
4 M03039001148 MOTOR,YDK1000-8A9, YONGAN 2
5 M01014300567 SUPPORT MOTOR 2
6 M50024304050 ASSY, RIGHE COIL 2
7 M50024304049 ASSY, LEFT COIL 2
8 ASSY,METAL STRUCTURE 1
9 M01014300103 PANEL,UNDERSURFACE 4
10 M04109003655 PRESSURE SWITCH H20PS 3.0/2.4MPa 1
11 A50054009748 ASSY,ACCESS VALVE 1/4 SP2200 4
12 M04109010639 LOW PRESSURE SWITCH 0.05/0.15MPa 1
13 M50049304037 TERMINAL BOX 1
14 A02169000508 FILTER DRIER,EK-085S ALCO 2
15 M05019010949 VALVE,TXV TDEBX11 5/8*7/8 DANFOSS 2
16 M01014300104 PANEL,UNDERSURFACE5 1
17 M01014300105 PANEL,UNDERSURFACE5 1
18 M04019002899
COMPRESSOR,ZR144KC-TF5(WITH
HEATER)COPELAND
2
19 M02119012953 ACCUMULATOR,QFQ5.2-A-01 6.0L TONGLI 2
20 ASSY,COPPER TUBE 1
21 M01014300106 PANEL,UNDERSURFACE 1
22 M05014302007 VALVE,CONNECT SENSOR 2
23 M04064305407 SWITCH,DIFFERENCE PRESSURE 5/9KPa 1
24 M02204302010 BPHE,B3-095-84 QINBAO 1
25 M05029004269 JOINT,FLEXIBLE RUBBER KST-40 2
26 M05014013017 VALVE,BALL Q11F-20T 2
27 M02069005116 STRAINER,WATER CU PN25(1 1/2)ITALY OR 1
28 M50104303215 ASSY,WATER PIPE(INLET) 1
29 M50104303216 ASSY,WATER PIPE(OUTLET) 1
30 M50014303234 ASSY BASE PAN 1
TERMINAL BOX
1 M04119003708 TERMINAL BLOCK ,HP-T3021-18P 1
2 M04119003779 TERMINAL BLOCK ,ET3501-3P-1 1
3 M04039003178 CONTACTOR,LC1-D6511MTC T.E. 2
4 M04039003169 CONTACTOR,LC1-D0910M7C T.E. 2
5 M04169003904 FUSE LINK RT14-4A WITH BASE DELIXI 1
6 M04199362000 PHASE PROTECTOR ,RM4-TG20 T.E. 1
7 M04089012294 CONTROL MODULE,MC01 EC MC2.0 1
8 M04089900247 CONTROLLER SC302B(MCQUAY,ENGLISH) 1
9 M04179003986 OVERLOAD PROTECTOR,LR2-D3357C 2
26
NO. Part Number Description Quantity
1 M01014302202 OUTER NOZZLE 810mm 2
2 M03019000809 FAN BLADE,240MM DBF7A-240 XINCHANG 2
3 M01014303266 PANEL,OUTFLOW 2
4 M03039013480 MOTOR,YT160-1000-8A4 2
5 M01014300567 SUPPORT MOTOR 2
6 M50024304050 ASSY, RIGHE COIL 2
7 M50024304049 ASSY, LEFT COIL 2
8 ASSY,METAL STRUCTURE 1
9 M01014300103 PANEL,UNDERSURFACE 4
10 M04109003655 PRESSURE SWITCH H20PS 3.0/2.4MPa 1
11 A50054009748 ASSY,ACCESS VALVE 1/4 SP2200 4
12 M04109010639 LOW PRESSURE SWITCH 0.05/0.15MPa 1
13 M50049304038 TERMINAL BOX 1
14 A02169000508 FILTER DRIER,EK-085S ALCO 2
15 M05019010949 VALVE,TXV TDEBX11 5/8*7/8 DANFOSS 2
16 M01014300104 PANEL,UNDERSURFACE5 1
17 M01014300105 PANEL,UNDERSURFACE5 1
18 M04019002837
COMPRESSOR,ZR144KC-TFD-522(WITH
HEATER)COPELAND
2
19 M02119012953 ACCUMULATOR,QFQ5.2-A-01 6.0L TONGLI 2
20 ASSY,COPPER TUBE 1
21 M01014300106 PANEL,UNDERSURFACE 1
22 M05014302007 VALVE,CONNECT SENSOR 2
23 M04064305407 SWITCH,DIFFERENCE PRESSURE 5/9KPa 1
24 M02204302010 BPHE,B3-095-84 QINBAO 1
25 M05029004269 JOINT,FLEXIBLE RUBBER KST-40 2
26 M05014013017 VALVE,BALL Q11F-20T 2
27 M02069005116 STRAINER,WATER CU PN25(1 1/2)ITALY OR 1
28 M50104303215 ASSY,WATER PIPE(INLET) 1
29 M50104303216 ASSY,WATER PIPE(OUTLET) 1
30 M50014303234 ASSY BASE PAN 1
TERMINAL BOX
1 M041190026708 TERMINAL BLOCK ,HP-T24021-18P 1
2 M04119003777 TERMINAL BLOCK ,ET2501-3P-1 1
3 M04039003168 CONTACTOR,LC1-3201M7C T.E. 2
4 M04039003169 CONTACTOR,LC1-D0910M7C T.E. 2
5 M04169003901 FUSE,RT 14-10A,BOLT IN 10A 022M04010-001 1
6 M041992662000 PHASE PROTECTOR ,RM4-TG20 T.E. 1
7 M04089012294 CONTROL MODULE,MC01 EC MC2.0 1
8 M04089900247 CONTROLLER SC302B(MCQUAY,ENGLISH) 1
9 M0417003957 OVERLOAD PROTECTOR,LRD22KN(16-24A) T.E. 2
MAC210A-QAB-E
2011 McQuay International +1 (800) 432-1342 www.mcquay.com
We do our utmost efforts to ensure all details are correct and accurate during the time of publication.
However, McQuay reserves the right to discontinue and/or alter the specifcations and designs any time
without notice and incurring obligations.
Specifcations may change to suit local conditions and some models are not available for certain countries.
ISO 9001
Certifcate No.: 9601019
BS-OHSAS 18001
Certifcate No.: 7644
ISO 14001
Certifcate No.: EMS 80362

S-ar putea să vă placă și