Sunteți pe pagina 1din 22

A 13.01.14 Issue for approval M.J .OH Y.J .SHIN M.D.

SEO
REV. DATE DESCRIPTION DSGN CHKD APPD
SUB-CONTRACTORS DOCUMENT NUMBER: MD1-0-V-111-33-00852




A 13.01.14 Issue for approval J .A.SEO M.K.LEE J .Y.KIM
REV. DATE DESCRIPTION DSGN CHKD APPD
PROJ ECT :

TWO(2) x 500 MW MONG DUONG 1 THERMAL POWER PLANT

EMPLOYER :


CONSULTANT :


CONTRACTOR :

SUB-CONTRACTOR :

DESIGNED BY DATE TITLE :
M.J .OH 13.01.14
GENERATOR PROTECTION RELAY SETTING CALCULATION CHECKED BY DATE
Y.J .SHIN
13.01.14
APPROVED BY DATE PROJ ECT NUMBER DOCUMENT NUMBER REV.
M.D.SEO
13.01.14
ADB/MD1-TPIP/EPC150911 MD1-0-V-111-33-00852 A
FOR APPROVAL



FOR INFORMATION
Issue for information

MD1-0-V-111-33-00852 2 of 22

TABLE OF CONTENT

1.0 PURPOSE ..................................................................................................................... 3


2.0 REFERENCES .................................................................................................................. 3


3.0 CONSIDERATION FOR RELAY SETTING ....................................................................... 3


4.0 COMMENTS ...................................................................................................................... 3


5.0 CALCULATIONS ............................................................................................................... 4



MD1-0-V-111-33-00852 3 of 22
1.0 PURPOSE
The purpose of this protection relay co-ordination setting study is to analyze and give the
functional settings of the protection relays necessary for the operation of the protection system
and for selective clearance of faults for Mong Duong1thermal power plant.

2.0 REFERENCES
1) IEEE Std C37.91: IEEE Guide for Protective Relay Applications to Power Transformers.
2) IEEE Std. C37.102 IEEE Guide for AC Generator Protection.
3) IEEE Std 242: IEEE Recommended Practice for Protection and Coordination of Industrial
and Commercial Power System.
4) IEC International Standard 60255-3 : Electrical Relays part3 Single input energizing
quantity measuring relays with dependent or independent time
5) IEC International Standard 60255-8 : Electrical Relays part8 Thermal electrical relays
6) IEC International Standard 60076-5 : Power Transformer part 5 Ability to withstand short
circuit
7) NEMA MG1-1998 Rev.2 2001
8) SIEMENS 7UM62XX Relay Technical Manual
9) Relay Co-ordination Guide BookKorea Electric Power Corporation

3.0 CONSIDERATION FOR RELAY SETTING
1) 27/59N (100% Stator Earth ground fault Relay) settings are applied after the actual
measurement.
2) The permissible Negative sequence constants(K) of the generator is assumed to be 10.
(K=10)

4.0 COMMENTS
1) If all of vendor technical data are provided report will be review and revised in the next
revision stage.




MD1-0-V-111-33-00852 4 of 22




















5.0 CALCULATIONS















MD1-0-V-111-33-00852 5 of 22
5.1 Generator Protection Relay
1) Basic Information and Data
1-1) Relay Data
Relay Maker SIEMENS
Relay Model 7UM6225
Function
87G Differential Protection
21G Impedance Protection
32G Reverse Power Protection
40G Under excitation (Loss-of-Field) Protection
46G Unbalanced Load (Negative Sequence) Protection
49S Thermal Overload Protection
81G Frequency Protection
27G Undervoltage Protection
59G Overvoltage Protection
50BF Breaker Failure Protection
24G Over excitation (Volt/Hertz) Protection
59GN 90-%-Stator Earth Fault Protection
27/59TN 100-%-Stator Earth Fault Protection with 3rd Harmonics
60G Fuse Failure Monitor

1-2) Generator Data
Parameter Data Unit Remark
Rated MVA 650.52 MVA
Power Factor (Overexcited) 0.85 -
Direct axis synchronous reactance (Xd) 2.10 PU Saturation
Direct axis transient reactance (Xd) 0.225 PU Saturation
Direct axis sub-transient reactance (Xd) 0.160 PU Saturation
Negative sequence reactance (X2) 0.160 PU -
Zero sequence reactance (Xo) 0.140 PU -
Rated voltage 21 kV
Rated current 17884.7 A Calculation a.
a. Rated current
] [ 7 . 17884
21 3
650520
A I
NS
=

=



MD1-0-V-111-33-00852 6 of 22
2) Protection Diagram

2-1) Device Configuration Parameters address blocks 1
a. Setting group change option
Setting group change option is Enabled
Address Parameter Setting Value Remark
0103
0104
0112
0113
0114
0116
0117
0120
0130
0131
Setting Group Change Option
Fault values
50/51 Overcurrent Protection I>
50/51/67 Overcurrent Protection I>>
51V Inverse O/C Time Protection
49 Thermal Overload Protection
46 Negative Sequence Protection
87G/87TDifferential Protection
40 Under excitation Protection
32R Reverse Power Protection
Disabled
Instantaneous values
Disabled
Disabled
Disabled
Enabled
Enabled
Generator/Motor
Enabled
Enabled

0132
0133
0140
0141
32F Forward Power Supervision
21 Impedance Protection
27 Undervoltage Protection
59 Overvoltage Protection
Disabled
Enabled
Enabled
Enabled


MD1-0-V-111-33-00852 7 of 22
Address Parameter Setting Value Remark
0142
0143
0144
0150
0151
0152
0154
0155
0160
0165
0166
0170
0171
0180
0181
0182
0185
0186
0187
0188
0189
0190
0191
81 Over / Under frequency Protection
24 Over excitation Protection (U/f)
27 Inverse Undervoltage Protection Up<
59N/67GN Stator Ground Fault Protection
50N/51G Sensitive Ground Current Protection
27/59TN Ground Fault Prot. 3
rd
Harm.
50N/51G Sensitive Earth Current Protection B
Interturn Protection
64 Rotor Ground Fault Protection (R, fn)
48 Motor Starting Time Supervision
66 Restart Inhibit for Motors
50BF Breaker Failure Protection
50/27 Inadvertent Energisation
60FL Fuse Failure Monitor
Measured Values Supervision
74TC Trip Circuit Supervision
Threshold Supervision
External Trip Function 1
External Trip Function 2
External Trip Function 3
External Trip Function 4
External Temperature Input
Ext. Temperature Input Connection Type
Enabled
Enabled
Disabled
Non-directional only V0
Disabled
Enabled
Disabled
Disabled
Disabled
Disabled
Disabled
Side 2
Disabled
Enabled
Enabled
Disabled
Enabled
Disabled
Disabled
Disabled
Disabled
Disabled
6 RTD simplex
operation
2-2) Power System Data address blocks 2
Address Parameter Setting Value Remark

0242
0244
0270
0271
0272
0274A
0276
- Group Power System -
Starpoint of Side 1 is
Starpoint of Side 2 is
Rated Frequency
Phase Sequence
Scheme Configuration
Storage of th. Replicas w/o Power Supply
Unit of temperature measurement

Isolated
Isolated
50 Hz
A B C
Direct connected to
busbar
NO
Degree Celsius









0251
0252

0201
0202
0203
0204
0205
0210
211
212
213

221
222
223

224
- Group Generator/Motor
Rated Primary Voltage Generator/Motor
Rated Apparent Power of the Generator
- Group CTs
CT-Strpnt. Side1 in Direct. of Object
CT Rated Primary Current Side 1
CT Rated Secondary Current Side 1
Correction Angle CT W0
CT Ratio Prim./Sec. Iee1
CT-Strpnt. Side2 in Direct. of Object
CT Rated Primary Current Side 2
CT Rated Secondary Current Side 2
CT Ratio Prim./Sec. Iee2
- Group VTs
Rated Primary Voltage
Rated Secondary Voltage (Ph-Ph)
UE Connection

VT Ratio Prim./Sec. Neutral VT

21.00 kV
650.52 MVA

YES
21000 A
5 A
0.00
60.0
YES
21000 A
5 A
1.0

21.00 kV
110 V
VN connected to
neutral transformer
87.5








Not relevant











MD1-0-V-111-33-00852 8 of 22
Address Parameter Setting Value Remark
225

280
281

295
296
297
Matching Ratio Ph.-VT to Broken-Delta-VT
- Group Breaker
Minimum TRIP Command Duration
Closed Breaker Min. Current Threshold
- Group Transducer
Transducer 1
Transducer 2
Transducer 3
1.73

0.15 sec
0.20 A

10V
10V
with filter


Not relevant
Not relevant

Not relevant
Not relevant
Not relevant

2-3) Settings for Power system data 2 address blocks 11
Address Parameter Setting Value Remark
1108 Measurement of Active Power for Generator



MD1-0-V-111-33-00852 9 of 22
2-4) Settings for Unbalance load Protection(46G) address blocks 17
a. Setting continuously permissible current calculation
- Setting criterion : Pickup value shall be set at I2 = 8% and K = 10, because generator is
cylindrical-rotor generator.
81 . 6
21,000
17,884.7
8
I
I
I
I
I2
prim CT N
Nmach
mach N
mach max 2
= = = > [%]
Continuously Permissible current setting is 6.8 [%]
b. Setting warning stage time delay(Alarm)
- Setting criterion : Setting value shall be set at 3sec for Alarm
Warning stage time delay is 3 [sec]
c. Setting negative sequence factor K calculation
- Setting criterion : Setting value K shall be set at 8, Considering 20% margin .
[s] 5.80 )
21,000
17884.7
( 8 )
I
I
( K K
2 2
prim CT N
Nmach
prim sec
= = =
Negative sequence factor K setting is5.8 [s]
d. Setting time for cooling down calculation
- Setting criterion :
downc Cool
t ' value shall be set at according to the manufacturer's
recommended formula.
[s] 1,562
0.08
10
) /I (I
K
t
2 2
N perm 2
prim
downc Cool
= = =

Time for cooling down is 1,562 [s]
e. Setting 46-2 pickup calculation
- Setting criterion : Pickup value shall be set at 60% of rated current for operating for line-to-line
short-circuit fault.
[%] 51.10
21,000
17,884.7
60%
I
I
I
I
I2
prim CT N
mach N
mach N
mach max 2
= = = >>

Continuously Permissible current setting is 51 [%]
f. Setting 46-2 time delay
-Setting value shall be set at 3sec.
46-2 time delay setting is 3.00 [sec]







MD1-0-V-111-33-00852 10 of 22
g. Setting Table
Address Parameter Setting Value Remark
1701
1702
1703
1704
1705
1706
1707
46 Negative Sequence Protection
46 Continuously Permissible Current 12
46 Warning Stage Time Delay
46 Permissible Negative Sequence Time K
46 Time for Cooling Down
46-2 Pickup
46-2 Time Delay
ON
6.8 %
3.00 sec
5.8sec
1,562 sec
51%
3.00 sec


2-5) Settings for Differential Protection (87G-1,2) address blocks 20
a. Setting I-Diff> calculation
- Setting criterion
Setting value shall be set at a range that does not operation by the differential current with
CT error and relay error.
CT error : The current of minimum operating current side is very small, so ct error is
ignore.
Relays error : Errors guaranteed by Publisher 5%(Reference by SIEMENS 7UM62 Manual)
Margin : 5%
Relays error + margin = 5.0% + 5.0% = 10.0 [%]
87-1pick-up setting is 0.1I/InO
b. Setting I-DIFF> time
- Setting criterion : Correct setting of the minimum possible.
87-1 time delay is 0.00 [sec]
c. Setting I-DIFF>> calculation
- Setting criterion :Setting value shall be set at greater than 1/Xd(Transient reactance) of
generator.
777 . 5 13 . 0
225 . 0
1
2 - 7 8 = = I/InO
87-2pick-up setting is 5.8I/InO

MD1-0-V-111-33-00852 11 of 22
d. Setting table
Address Parameter Setting Value Remark

2001
2005
- Group General -
87G/87T Differential Protection
87 Increase of Trip Char. During Start

ON
OFF




2021
2026A
2031
2036A

2041A
2042A
2043A
2044A
2051A
2052A
2053
2061A
2062A
2063A
- Group I-Diff -
87-1 Pickup Value of Differential Curr
87-1 T I-DIFF> Time Delay
87-2 Pickup Value of High Set Trip
87-2 T I-DIFF>> Time Delay
- Group Characteristic -
87 Slope 1 of Tripping Characteristic
87 Slope 1 of Tripping Characteristic
87 Slope 2 of Tripping Characteristic
87 Base Point for Slope 2 of Charac.
87 I-RESTRAINT for Start Detection
87 Factor for Increasing of Char. At Start
87 Maximum Permissible Starting Time
87 Pickup for Add-on Stabilization
87 Duration of Add-on Stabilization
87 Time for Cross-blocking Add-on Stabiliz.

0.10I/InO
0.00sec
5.8I/InO
0.00sec

0.25
0.00I/InO
0.50
2.50 I/InO
0.10I/InO
1.0
5.0sec
4.00I/InO
15Cycle
15 Cycle








2-6) Settings for Underexcitation (Loss-of-Field) Protection (40) address blocks 30
a. Setting 1/xd CHAR.1 pickup calculation
- Setting criterion :Setting value shall be set at 105% of 1/xd.
Char.1 ] . [ 43 . 0
000 , 21
7 . 884 , 17
05 . 1
10 . 2
1
/ 1 U P X
d
= = =

Susceptance Intersect characteristic 1 is 0.43
b. Setting Angle 1
- Setting criterion :Setting angle shall be set at 60~80.
Inclination angle of characteristic 1 is 80 []
c. Setting CHAR.1 time delay
- Setting criterion :Setting time shall be set at 2~10 sec.
Characteristic 1 time delay is 5.00 [sec]


MD1-0-V-111-33-00852 12 of 22
d. Setting 1/xd CHAR.2 pickup calculation
- Setting criterion :Setting value shall be set at 90% of CHAR.1.
Char. 2 = ] . [ 387 . 0 9 . 0 43 . 0 9 . 0 1 . U P Char = =

Susceptance Intersect characteristic 2 is 0.39[P.U]
e. Setting Angle 2
- Setting criterion :Setting angle shall be set at 90.
Inclination angle of characteristic 2 is 90 []
f. Setting CHAR.2 time delay
- Setting criterion :Setting time shall be set at 2~10 sec.
Characteristic 2 time delay is 5.0 [sec]
g. Setting 1/xd CHAR.3 pickup calculation
- Setting criterion :According to manufacturer recommendations, Setting value shall be set at
greater than
1.0[[P.U] and smaller than 1/Xd(Transient reactance) of generator.
] . [ 79 . 3
A 000 , 21
V 000 , 21
V 000 , 21
A 7,884.7 1
225 . 0
1
'
1
sec
U P
X
d
= =

Susceptance Intersect characteristic 3is 3.79[P.U]
h. Setting Angle 3
- Setting criterion :Setting angle shall be set at 80~110.
Inclination angle of characteristic 3 is 110 []
i. Setting CHAR.3 time delay
- Setting criterion :Setting time shall be set at manufacturer recommendations.
Characteristic 3 time delay is 0.50 [sec]
j. Setting table
Address Parameter Setting Value Remark

3001
3011
3012
3013
3014A

3002
3003
3004
3005
3006
3007
3008
3009
3010
- Group 40 Underexcit. -
40 Underexcitation Protection
40 T-Short Time Delay (Char.&Uexc)
40 State of Excitation Volt. Supervision
Excitation Voltage Superv. Pickup
Undervoltage blocking pickup
- Group Characteristics -
40 Susceptance Intersect Characteristic 1
40 Inclination Angle of Characteristic 1
40 Characteristic 1 Time Delay
40 Susceptance Intersect Characteristic 2
40 Inclination Angle of Characteristic 2
40 Characteristic 2 Time Delay
40 Susceptance Intersect Characteristic 3
40 Inclination Angle of Characteristic 3
40 Characteristic 3 Time Delay

ON
oo sec
OFF
2.00 V
25.00 V

0.43
80.0
5.00 sec
0.39
90.0
5.0 sec
3.79
110.0
0.50 sec


Not relevant

Not relevant
Not relevant

MD1-0-V-111-33-00852 13 of 22

2-7) Settings for Reverse power Protection (32-1G) address blocks 31
a. Setting P> Reverse Pick-up calculation (After obtain data, the recalculation is needed.)
- Setting criterion: Setting value shall be set at less than 50% of the Motoring Power that
required for the synchronous speed.
] [% 425 . 0
21,000
17884.7
21.0
21.0
% 5 . 0
I
I
U
U
% 5 . 0
S
P
pri N
mach N
pri N
mach N
SEC N
sec
= = =

32R P> Reverse pick-up setting is -0.42 [%]
b. Setting time delay
- Setting criterion: Setting time shall be set at 10 sec.
32R Trip delay long is 10.00 [sec]
c. Setting table
Address Parameter Setting Value Remark
3101
3102
3103
3104
3105A
32R Reverse power protection
32R P>Pickup
32R Time delay long(without stop valve)
32R Time delay short(with stop valve)
32R Pickup holding time
ON
-0.42%
10.00 sec
oo sec
0.00 sec



Not active




MD1-0-V-111-33-00852 14 of 22
2-8) Settings for Impedance Protection (21) address blocks 33

<CT Connection Example & Zone Reach>

a. Setting fault detection I> pickup calculation
- Setting criterion :Setting value shall be set at 125% of the rated current of generator.
] [ 32 . 5
000 , 21
5
25 . 1 7 . 884 , 17 A I = >=

Fault detection I>is 5.32[A]
b. Setting undervoltage seal-in pickup calculation
- Setting criterion: Setting value shall be set at 80% of the rated voltage of generator.
] [ 0 . 88 8 . 0 110 V V = <=

Undervoltage seal-in pickup is 88.0 [V]
c. Setting duration of undervoltage seal-in
- Setting criterion: Setting time shall be set at 4.0 sec. (Z2 operating time + 1.5sec)
Duration of undervoltage seal-in is 4.00 [sec]
d. Setting impedance zone Z1 calculation
- Setting criterion: Setting value shall be set at 75% of step-up Tr. impedance.
] [ 0.060
720
21
100
13
100
75
MVA
kV
100
u
100
k
Z
2 2
k R
PRI
O = = =

K
R
: Zone reach of zone Z1 in %
Uk : percent impedance voltage of the unit transformer


MD1-0-V-111-33-00852 15 of 22
] [ 1.32
190.90
4,200
0.060
Ratio VT
Ratio CT
Z Z
PRI SEC
O = = =
Impedance zone Z1 is 1.32 []
e. Setting impedance zone Z1 time delay
- Setting criterion: Setting time shall be set at 0.5 sec for back up protection of step up Tr.
Impedance zone Z1 time delay is 0.50 [sec]
f. Setting impedance zone Z2 calculation
- Setting criterion:
1) Setting value shall be set at 150% of impedance for rated power of generator.
2) Step-up Tr. Impedance + (Next transmission line impedance

Apparent Factor)
3) Set as a small value of 1) and 2), but Step-up Tr. Data is not received.
So setting value is1).
] [ 02 . 1 5 . 1
52 . 650
21
5 . 1
2 2
O = = =
MVA
kV
Z
PRI

Impedance zone Z2 is 1.02 []
g. Setting impedance zone Z2 time delay
- Setting criterion: Setting time shall be set at 0.5 sec for back up protection of step up Tr..
Impedance zone Z2 time delay is 2.50 [sec]
h. Setting table
Address Parameter Setting Value Remark

3301
3302
3303
3304
3305
3312


3306
3307
3308
3309
3310
3311
- Group General -
21 Impedance Protection
21 Fault Detection I> Pickup
21 State of Undervoltage Seal-in
21 Undervoltage Seal-in Pickup
21 Duration of Undervoltage Seal-in
21 T END: Final Time Delay

- Group Zones -
21 Impedance Zone Z1
21 Impedance Zone Z1 Time Delay
21 Impedance Zone Z1B
21 Impedance Zone Z1B Time Delay
21 Impedance Zone Z2
21 Impedance Zone Z2 Time Delay

ON
5.32 A
ON
88.0 V
4.00 sec
oo sec


1.32 Ohm
0.50 sec
0.99 Ohm
oo sec
1.02 Ohm
2.50 sec






Not active





Not active



3313
3314
3315
3316A
3317A
- Group Power swing -
Power Swing Blocking
Distance betw. Power Swing Trip-Pol.
Rate of Change of dZ/dt
Power Swing Blocking locks out
Power Swing Action Time

OFF
1.60 Ohm
60.0 Ohm/s
Zone Z1
3.00 sec










MD1-0-V-111-33-00852 16 of 22
2-9) Settings for Overvoltage Protection (59G) address blocks 41
a. Setting V> Pick-up calculation
- Setting criterion: Setting value shall be set at 120% of the rated voltage of generator.
] [ 0 . 132 20 . 1
000 , 21
110
000 , 21 V V = >=

V> pick-up setting is 132[V]
b. Setting V> time delay
- Setting criterion: Setting operating time shall be set coordination with operating time of
24G function.
V> Time delay is 1.80 [sec]
c. Setting table
Address Parameter Setting Value Remark
4101
4102
4103
4104
4105
4106A
4107A


59 Overvoltage Protection
59-1 Pickup
59-1 Time Delay
59-2 Pickup
59-2 Pickup
59 V>, V>> Drop out ratio
59 Measurement values
ON
132V
1.80 sec
140.0 V
oo sec
0.95
Voltage
protection
with
V-Phase-
Phase




Not active







MD1-0-V-111-33-00852 17 of 22
2-10) Settings frequency Protection (81G) address blocks 42(Requires consultation with
the Client)
a. Setting 81-1 Pick-up calculation
- Setting criterion: Setting value shall be set at 49Hz of under frequency function.
81-1 pick-up setting is 49.00 [Hz]
b. Setting 81-1 time delay
- Setting criterion: Setting operating time delay shall be set at 1.0sec.
81-1 time delay is 1.00 [sec]
c. Setting 81-2 Pick-up calculation
- Setting criterion: Setting value shall be set at 48Hz of under frequency function.
81-2 pick-up setting is 48.00 [Hz]
d. Setting 81-2 time delay
- Setting criterion: Setting operating time delay shall be set at 20sec.
81-2 time delay is 20.00 [sec]
e. Setting 81-3 Pick-up calculation
- Setting criterion: Setting value shall be set at 47Hz of under frequency function.
81-3 pick-up setting is 47.00 [Hz]
f. Setting 81-3 time delay
- Setting criterion: Setting operating time delay shall be set at 1.0sec.
81-3 time delay is 1.00 [sec]
g. Setting 81-4 Pick-up calculation
- Setting criterion: Setting value shall be set at 53Hz of over frequency function.
81-4 pick-up setting is 53.00 [Hz]
h. Setting 81-4 time delay
- Setting criterion: Setting operating time delay shall be set at 1.0sec.
81-4 time delay is 1.00 [sec]
i. Setting minimum required voltage calculation
- Setting criterion: Setting value shall be set at 65% of the rated voltage for operating minimum
voltage to frequency protection function.
[V] 71.5 0.65
21,000
110
0 00 , 21 V
min
= =

Minimum required voltage is 71.5 [V]






MD1-0-V-111-33-00852 18 of 22
j. Setting table
Address Parameter Setting Value Remark
4201
4203
4204
4206
4207
4209
4210
4212
4213
4214

4215
81Over/Under frequency protection
81-1 Pickup
81-1 Time delay
81-2 Pickup
81-2 Time delay
81-3 Pickup
81-3 Time delay
81-4 Pickup
81-4 Pickup Time delay
81 Handling of Threshold stage f4

81 Minimum required voltage for operation
ON
49.00 Hz
1.00 sec
48.00 Hz
20.00 sec
47.00 Hz
1.00 sec
53.00 Hz
1.00 sec
Freq.prot.stage
automatic
71.5 V


Alarm





2-11) Settings for Over excitation(volt/hertz) Protection (24G) address blocks 43
a. Setting 24-1 V/f Pick-up calculation
- Setting criterion: Setting value shall be set at 108% of the rated voltage/hertz for minimum
operating .
24-1 V/f pick-up setting is 1.08
b. Setting 24-1 V/f time delay
- Setting criterion: Setting time shall be set at 10secforoperating time in warm stage.
24-1 V/f time delay is 10.00 [sec]
c. Setting 24-2 V/f Pick-up calculation
- Setting criterion: Setting value shall be set at 118% of the rated voltage/hertz.
24-2 V/f pick-up setting is 1.18
d. Setting 24-2 V/f time delay
- Setting criterion: Setting time shall be set at 2.0sec.
24-2 V/f time delay is 2.00 [sec]
e. Setting V/f time characteristic
- Setting criterion: Setting value shall be set by reference to the short-time over-excitation
curve of manufacturer.
24 V/f=1.15Time delay is 82[sec]
24 V/f=1.20Time delay is 36 [sec]
24 V/f=1.25Time delay is 26 [sec]
24 V/f=1.30Time delay is 18 [sec]
24 V/f=1.35Time delay is 5 [sec]
24 V/f=1.40Time delay is 5 [sec]




MD1-0-V-111-33-00852 19 of 22
f. Setting table
Address Parameter Setting Value Remark

4301
4302
4303
4304
4305

4306
4307
4308
4309
4310
4311
4312
4313
4314
- Group Over excitation -
24 Over excitation protection(U/F)
24-1 V/f> Pickup
24-1 V/f Time delay
24-2 V/f Pickup
24-2 V/f Time delay
- Group Characteristics -
24 V/f = 1.05 Time delay
24 V/f = 1.10 Time delay
24 V/f = 1.15 Time delay
24 V/f = 1.20 Time delay
24 V/f = 1.25 Time delay
24 V/f = 1.30 Time delay
24 V/f = 1.35 Time delay
24 V/f = 1.40 Time delay
24 Time for cooling down

ON
1.08
10.00 sec
1.18
2.00 sec

20000 sec
6000 sec
82 sec
36sec
26sec
18sec
5 sec
5 sec
3600 sec


2-12) Settings for Ground fault Protection (27/59TN) address blocks 60
" Address. 6006-6009 " function must be reset to the final correction for elements
measured during the field test.
Address Parameter Setting Value Remark
5201
5202
5204
5205
5206
27/59TN Ground Fault Prot. 3
rd
Harm.
27TN 3
rd
Hamonic Pickup <
27/59TN 3
rd
H Release Threshould
27/59TN 3.H Release Threshold Pmin>
27/59TN 3.H Release Threshold V 1min >
ON
1.0V
2.0sec
20%
80V


2-13) Settings for Breaker failure Protection (50BF) address blocks 70
a. Setting supervision current pickup calculation
- Setting criterion: Setting value shall be set at 10% of the rated current of generator.
] [ 425 . 0
000 , 21
5
7 . 17884 1 . 0 Pickup 0BF 5 A = =

Supervision current pickup setting is 0.43 [A]
b. Setting trip-timer
- Setting criterion: GCB operating time + Lock out relay reset time + margin
Trip-timer is 0.15 [sec]







MD1-0-V-111-33-00852 20 of 22
c. Setting table
Address Parameter Setting Value Remark
7001
7002


7003
7004
50BF Breaker Failure Protection
50BF Start with Internal TRIP command


50BF Supervision Current Pickup
50BF TRIP-Timer
ON
Start Breaker
Failure with
Bin.Outp.12
0.43 A
0.15 sec


2-14) Settings for Measurement Supervision address blocks 81
Address Parameter Setting Value Remark
8101
8102
8103
8104
8105
8104
8105
8108
8109
8110
8111
8112
8113
Measurement Supervision
Voltage Threshold for Balance Monitoring
Balance Factor for Voltage Monitor
Current Balance Monitor Side 1
Balance Factor for Current Monitor S1
Current Balance Monitor Side 2
Balance Factor for Current Monitor S2
Summation Thes. forVolt. Monitoring
Factor for Volt. Sum. Monitoring
Summated Cur. Mon. Threshold Side1
Summated Current Mon. Factor Side 1
Summated Cur. Mon. Threshold Side 2
Summated Current Mon. Factor Side 2
OFF
50 V
0.75
2.50 A
0.50
2.50 A
0.50
10 V
0.75
0.50 A
0.10
0.50 A
0.10


2-15) Settings for Ground Fault Prot. 59GN address blocks 50
a. Setting Stator Ground Fault Prot pickup calculation
- Setting criterion: Setting value shall be set at 8% of maximum zero Phase voltage,
because 59GN is detection 90% or more of the generator ground fault.
] [ 2 . 19 08 . 0 240 V V
oper
= =

Ground Fault Prot pickup current pickup setting is 19.2 [V]
b. Setting trip-timer
- Setting criterion: Setting time shall be set at 1.5sec.
Trip-timer is 1.5 [sec]


MD1-0-V-111-33-00852 21 of 22
c. Setting table
Address Parameter Setting Value Remark
5001
5002
5005
59G/67GN Stator Ground Fault Prot.
59N V0 Pickup
59N/67GN Time delay
ON
9.6V
1.5sec




2-16) Settings for Thermal Overload Protection (49M) address blocks 16
a. Setting K-Factor calculation
- Setting criterion :Setting value shall be set at 105% of the rated current of motor.
8942 . 0
000 , 21
7 . 17884
05 . 1 = = K
49 K-Factor is 0.89
b. Setting Time constant
- Setting criterion: protection coordination with Stator overload curve.
1) Setting value shall be set at 115% of the rated current and operating time is 89sec.
[SEC] 5 . 38
]
1
000 , 21 93 . 0
15 . 1 7 . 884 , 17
)
000 , 21 93 . 0
15 . 1 7 . 884 , 17
(
ln[
89
]
1
) (
ln[
2
2
2
2
=
|
.
|

\
|

|
|
.
|

\
|

=
N
N
I k
I
I k
I
t
t

2) Setting value shall be set at 125% of the rated current and operating time is 54sec.
[SEC] 5 . 7 3
]
1
000 , 21 93 . 0
25 . 1 7 . 884 , 17
)
000 , 21 93 . 0
25 . 1 7 . 884 , 17
(
ln[
54
]
1
) (
ln[
2
2
2
2
=
|
.
|

\
|

|
|
.
|

\
|

=
N
N
I k
I
I k
I
t
t

3)Set as a small value of 1) and 2).So setting value is1).
Time constant is 37.5 sec


MD1-0-V-111-33-00852 22 of 22
c. Setting 49 thermal alarm stage
- Setting criterion: Setting value shall be set at 125% of the rated current and operating time
is 54sec.
% 70 . 90 9070 . 0 )
05 . 1
1
( )
1
(
2 2
= = =

=
Factor k
u
49 Thermal alarm stage is 90%
d. Setting Maximum Current for Thermal calculation
- Setting criterion :Setting value shall be set at 3 times of the rated current of generator by
reference to the recommendation value of relay manufacturer.
[A] 77 . 12
000 , 21
5
0 . 3 7 . 884 , 17 THERM. MAX I = =
49 K-Factor is 12.77 [A]
e. Setting table
Address Parameter Setting Value Remark

1601
1602
1603
1604
1610A
1612A
1615A
1616A

1605
1607
1608
- Group 49 -
49 Thermal overload protection
49 K-Factor
49 Time Constant
49 Thermal Alarm Stage
49 Current Overload Alarm Setpoint
49 Kt-FACTOR when motor stops
49 Maximum Current for Thermal Replica
49 Emergency time
- Group Temp. Input -
49 Temperature Rise at Rated Sec. Curr.
49 Temperature Input
49 Temperature for Scaling

ON
0.89
37.5 sec
90 %
5.00 A
1.0
12.77 A
100 sec

100
Disabled
100










Not relevant

Not relevant

2-17) Settings for Supervision Functions(60G) address blocks 81
Address Parameter Setting Value Remark
8001 Fuse Fail Mon ON
Fuse Failure