Multilin
Digital Energy
Phase segregated differential protection ensures secure
high-speed single pole tripping
Complete IEC 61850 Process Bus solution providing resource
optimization and minimizing total P&C life cycle costs
Reliable and secure protection on lines equipped with series
compensation
Increased sensitivity through dynamic charging current
compensation and communication channel asymmetry
compensation
Advanced fault and disturbance recording, including internal
relay operating signals thus eliminating the need for external
recording devices
Phasor Measurement Unit - Synchronized phasor information
according to IEEEC37.118 standard
Robust network security enabling Critical Infrastructure
Protection through user command logging, and dual
permission access control
Ambient temperature monitoring with alarming when outside
temperature exceeds upper thresholds
Overhead lines including series compensated lines and
underground cables of different voltage levels
Circuits with tapped transformer feeders
Distributed busbar protection
Suitable for three terminal line configurations, with channel
redundancy and direct transfer tripping (DTT)
Wide area system monitoring and control and using
integrated protection and synchrophasor measurement
Single and dual-breaker circuits requiring single pole/three-
pole autoreclosing and independent synchrocheck supervision
Real time monitoring of remote, local and differential per
phase currents
Oscillography - 64 samples/cycle, up to 64 records
Event Recorder - 1024 time tagged events, with 0.5ms scan
of digital inputs
Data Logger - Up to 16 channels with user selectable
sampling rate
Synchronised measurement of voltage & current and
sequence component phasors - 1 to 60 phasors/sec
Multi-ended fault location consistently providing 2%
accuracy
Monitoring and Metering
Protection and Control
Phase segregated line current differential with adaptive
restraint & Ground differential
Stub bus protection
Phase Distance (three Zones) with independent compensation
settings for in-zone power transformers
Ground distance (three zones) with independent self and
mutual zero sequence compensation
Out-of-step tripping and power swing blocking
Directional overcurrent: Phase, neutral and negative sequence
Synchronism check for dual breaker applications
Communications
Networking interfaces 100Mbit Fiber Optic Ethernet, RS485,
RS232, RS422, G.703, C37.94
Multiple Protocols - IEC61850, DNP 3.0 Level 2, Modbus RTU,
Modbus TCP/IP, IEC60870-5-104, Ethernet Global Data (EGD)
Direct I/O secure, high-speed exchange of data between
L90s for Direct Transfer Trip applications
Embedded Managed Ethernet Switch with 4 - 100 Mbit Fiber
optic ports and 2 copper ports
L90
Phase segregated line current differential
and distance protection
FEATURES
APPLICATIONS
KEY BENEFITS
EnerVista Software
Graphical Logic Designer and Logic Monitor to simplify
designing and testing procedures
Document and software archiving toolset to ensure
reference material and device utilities are up-to-date
EnerVista Integrator providing easy integration of data in
the L90 into new or existing monitoring and control systems
LINE CURRENT
DIFFERENTIAL SYSTEM
Robust communications with up to 8 HardFiber Bricks
Seamless integration with existing L90 functions
Redundant architecture for dependability and security
IEC 61850 Process Bus Interface
202 202
L90 Line Differential System
T
r
a
n
s
m
i
s
s
i
o
n

L
i
n
e

P
r
o
t
e
c
t
i
o
n
www.GEDigitalEnergy.com
Protection and Control
The L90 is a high-end cost effective
line current differential protection relay
intended for transmission lines and cables
of different voltages levels providing
reliable and secure operation even under
the worst case power system conditions.
The L90 provides high-speed phase-
segregated fault clearance suitable for
single and three-pole tripping applications.
Part of the Universal Relay family, the L90
comes with a variety of versatile features
truly integrating protection, monitoring,
metering, communication and control in
one easy-to-use device. The Universal Relay
family offers a high degree of modularity
in its design and functionality providing
superior performance in protection and
control meeting the toughest requirements
of the marketplace.
Segregated Current Differential
Protection
The L90 is a phase segregated current
differential protection relay, which uses
superior and patented algorithms to
address the challenges of bandwidth ,
security, dependability and sensitivity in
current differential relaying.
Bandwidth requirements are effectively
addressed by means of a patented new
data consolidation technique called
phaselets. This permits application within
a communications bandwidth of 64 Kbps,
and can detect faults within a half cycle
plus channel delay.
The L90 innovative dual slope adaptive
restraint characteristic, based on estimates
of measurement errors, allow the relay to
be secure on severe external faults while
maintaining sensitivity for internal faults.
The estimate of errors in the input currents
permits more sensitive settings than those
used in the traditional percent differential
schemes.
The L90 approach to clock synchronization
rel i es upon preci se di stri buted
synchronization. Clocks are phase
synchronized to each other and frequency
synchronized to the power system
frequency. Each relay compares its clock
to the phase of the other clocks and
makes appropriate adjustments. This
allows for greater transient ride-through
for power system and communications
disturbances.
Enhanced additional security is provided
by a sensitive current disturbance detector,
which can be used to supervise the current
differential element.
Ground Differential 87G
The Ground Differential function 87G
protects against low-current single line-
to-ground faults. It has a single slope
characteristic and uses the vectorial sum
of all in-zone phase currents to calculate
the Neutral differential current. with the
maximum value of phase current being
used as restraint. This function together
The L90 is the single point for protection, control, metering, and monitoring in one integrated device
that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint
Monitoring as shown.
831706AS.CDR
L90 Line Differential System
52
Monitoring
CLOSE TRIP
Data From/To Remote End
(via Dedicated Communications)
Metering FlexElement
TM Transducer
Inputs
50DD 51N 50N 67P 87L 21P 68 78 50BF 51_2 51P 50_2
79
50P 21G 67N/G
27P
27X
59N
59X
59P
25
51G 50G
DEVICE
NUMBER
21G
21P
25
27P
27X
50BF
50DD
50G
50N
50P
50_2
51G
51N
51P
51_2
52
59N
59P
59X
67N
67P
67_2
68
78
79
87L
Ground Distance
Phase Distance
Synchrocheck
Phase Undervoltage
Auxiliary Undervoltage
Breaker Failure
Adaptive Fault Detector
Ground Instantaneous Overcurrent
Neutral Instantaneous Overcurrent
Phase Instantaneous Overcurrent
Negative Sequence Instantaneous Overcurrent
Ground Time Overcurrent
Neutral Time Overcurrent
Phase Time Overcurrent
Negative Sequence Time Overcurrent
AC Circuit Breaker
Neutral Overvoltage
Phase Overvoltage
Auxiliary Overvoltage
Neutral Directional Overcurrent
Phase Directional Overcurrent
Negative Sequence Directional Overcurrent
Power Swing Blocking
Out-of-Step Tripping
Automatic Recloser
Segregated Line Current Differential
FUNCTION
ANSI DEVICE NUMBERS AND FUNCTIONS
(senstive current disturbance detector)
Functional Block Diagram
L90 - Protection, Metering, Monitoring and Control
Device
Number
Function
21G Ground Distance
21P Phase Distance
25 Synchronism Check
27P Phase Undervoltage
27X Auxiliary Undervoltage
50BF Breaker Failure
50DD Current Disturbance Detector
50G Ground Instantaneous Overcurrent
50N Neutral Instantaneous Overcurrent
50P Phase Instantaneous Overcurrent
50_2 Negative Sequence Instantaneous Overcurrent
51G Ground Time Overcurrent
51N Neutral Time Overcurrent
51P Phase Time Overcurrent
51_2 Negative Sequence Time Overcurrent
52 AC Circuit Breaker
59N Neutral Overvoltage
59P Phase Overvoltage
59X Auxiliary Overvoltage
67_2 Negative Sequence Directional Overcurrent
67N Neutral Directional Overcurrent
67P Phase Directional Overcurrent
68 Power Swing Blocking
78 Out-of-step Tripping
79 Automatic Recloser
87L Segregated Line Current Differential
ANSI Device Numbers & Functions
203 203
L90 Line Differential System
T
r
a
n
s
m
i
s
s
i
o
n

L
i
n
e

P
r
o
t
e
c
t
i
o
n
www.GEDigitalEnergy.com
with the phase differential delivers
enhanced sensibility and selectivity to the
protection scheme.
Charging Current Compensation
For l ong transmi ssi on l i nes and
underground cables, the charging current
may be large and result in excessively high
pickup settings. The L90 can dynamically
compensate the charging current thus
increasing its sensitivity to the fault current
on long transmission lines.
Enhanced Monitoring Features
The L90 uses an advanced error detection
and supervising functions to secure the
L90 against misoperation due to erroneous
data. High bit errors are addressed by
means of computing a 32 bit CRC check
sums effectively addressing the concerns
of multiple bit errors due to high channel
noise.
On mul ti pl exed channel s, channel
asymmetry may be expected due to path
switching spurious differential currents,
which can endanger the security of the
differential system. By using GPS time
synchronization, up to 10ms of channel
asymmetry can be compensated for. Extra
security has been implemented in the L90
to ensure proper operation on the event of
IRIG-B signal failure.
Integrated channel monitoring provides
real-time diagnostic data on the health
of the L90. Communications channel
deterioration or failure will activate an
alarm, and can be used to enable backup
protection. Channel propagation delay
is monitored and adjusted according to
variations in communication paths.
Communication Topologies
Relays can communicate through direct
fiber, RS422, G.703, IEEE C37.94 interfaces
at 64Kbps, with extensive channel
monitoring and diagnostics are included.
In a current differential scheme, the L90s
exchange data via the communication
link, acting either as master collecting
data, making calculations and making
all relevant trip and restraint decisions,
or as slave only transmitting current
data to the one acting as master. For two
terminal applications, use the redundant
communications capability of the L90 for
optimal reliability of the current differential
line protection. For this scheme, data
is continuously transmitted over both
Overvoltage and undervoltage
protection
Long lines under lightly loaded conditions
or no-load may experience voltages
exceeding rated per unit voltage level
of the line. Use the phase overvoltage
element of the L90 to initiate a local trip as
well as a remote trip using direct transfer
trip.
Overcurrent Functions
The L90 provides overcurrent functions
for phase, neutral and ground which can
run parallel with the primary differential
element or can be programmed to provide
primary protection under conditions the
differential element is not available.
Single-Pole Tripping
The L90 relay uses a state-of- the-art dual
phase selection algorithm that provides
fast and accurate fault type identification
even under weak-infeed conditions.
Typical two and three terminal application of L90. L90 supports a variety of media cards for signalling
between L90s including direct multimode or single mode fibre, RS422, G.703 and IEEE C37.94.
Typical Applications
channels, so if a failure occurs, the L90
will continue to provide current differential
protection.
For three terminal applications, advanced
inter-relay communication features
eliminate the need for redundant
communication channels due to the ability
of the L90 to automatically switch between
master and slave mode, maintaining a
dependable system even with a failure of
one of the communication channels.
Distance
Separate high-speed phase and ground
distance elements are provided for optional
supervision with tapped transformers and
as a back-up during channel failures or
unavailability. The back-up distance the
functions in L90 come with three zones
of phase and ground distance (mho or
quad). The phase distance elements
come with built-in in-zone transformer
compensation. The L90 also provides
a load encroachment element , which
supervises the distance elements under
heavy line loading conditions.
204 204
L90 Line Differential System
T
r
a
n
s
m
i
s
s
i
o
n

L
i
n
e

P
r
o
t
e
c
t
i
o
n
www.GEDigitalEnergy.com
Direct transfer trip (DTT)
Use the direct transfer trip feature of L90
to trip remote breaker. Both single pole
and three pole direct transfer trips are
supported. Up to eight signals can be
sent over pilot communications channels
selectable through user configurable
logic.
Autoreclosing
The L90 provides multi-shot auto reclosing
for single pole or three pole auto relcose
on all types of faults with independently
settable dead time for each shot . Auto-
reclose can be dynamically blocked by
user programmable logic. Four different
auto-relcose modes are available enabling
the users to select the reclosing mode to
suit specific applications.
Synchronism Check
The L90 monitors voltage difference,
phase angle difference and slip frequency
to ensure proper breaker closure as per
user requirements. The L90 provides
additional enhancements in synchronizing
by checking dead source conditions
for synchronism bypass under these
conditions.
Breaker Failure
The L90 is able to provide fully independent
breaker failure protection for the breakers
associated to the line when connected to
a substation with a breaker-and-a-half or
ring bus arrangement. The L90 provides
the required elements to perform two
independent breaker failure functions.
Multiple Breaker Configurations
The L90 supports multi-breaker busbar
configurations such as breaker-and-a-half
or ring bus arrangements, providing dual
breaker auto reclose, dual synch-check
elements, and dual independent Breaker
Failure elements. The design provides
secure operation during external faults
with possible CT saturation
Special Applications - Distributed
Busbar
Use the L90s capability of supporting
up to 4 directly connected CTs for
applications where the use of conventional
bus differential relaying is not practical
or economically feasible. The L90 can
be used to protect both line and buses
by measuring currents from the feeder
CTs as shown. The L90 provides primary
protection for both the buses and the
circuit connecting them.
IEC 61850 Process Bus
The IEC 61850 Process Bus module is
designed to interface with the GE Multilin
HardFiber System, allowing bi-directional
IEC 61850 fiber optic communications.
The HardFiber System is designed to
integrate seamlessly with the existing
Universal Relay applications, including
protection functions, FlexLogic, metering
and communications.
The GE Multilin HardFiber System offers
the following benefits:
Communicates using open standard
IEC 61850 messaging
Drastically reduces P&C design,
installation and testing labor by
eliminating individual copper
terminations
Integrates with existing C70s by
replacing traditional CT/VT inputs with
IEC 61850 Process Bus module
Does not introduce new Cyber Security
concerns
Visit the HardFiber System product page on
the GE Multilin web site for more details.
Advanced Automation
The L90 incorporates advanced automation
features including powerful FlexLogic
programmable logic, communication, and
SCADA capabilities that far surpass what
is found in the average line relay. The L90
integrates seamlessly with other UR relays
for complete system protection.
FlexLogic
FlexLogic is the powerful UR-platform
programming logic engine that provides
the ability of creating customized
protection and control schemes thereby
minimizing the need, and the associated
costs, of auxiliary components and wiring.
Using FlexLogic, the L90 can be
programmed to provide required tripping
logic along with custom scheme logic for
line breaker control and interlocking and
dynamic setting group changes.
Scalable Hardware
The L90 is available with a multitude of I/O
configurations to suit the most demanding
application needs. The expandable modular
design allows for easy configuration and
future upgrades.
Flexible, modular I/O covering a broad
range of input signals and tripping
schemes
Mechanically latching outputs
can be used to develop secure
interlocking applications and replace
electromechanical lockout relays
FlexLogic
TM

Designer
Flexlogic allows for customizing the L90 to operate and control the breakers and other auxiliary
devices needed to fit most line protection schemes and applications.
205 205
L90 Line Differential System
T
r
a
n
s
m
i
s
s
i
o
n

L
i
n
e

P
r
o
t
e
c
t
i
o
n
www.GEDigitalEnergy.com
Monitoring and Metering
The L90 includes high accuracy metering
and recording for all AC signals. Voltage,
current, and power metering are built into
the relay as a standard feature. Current
and voltage parameters are available as
total RMS magnitude, and as fundamental
frequency magnitude and angle.
Fault and Disturbance Recording
The advanced disturbance and event
recording features within the L90 can
significantly reduce the time needed for
postmortem analysis of power system
events and creation of regulatory reports.
Recording functions include:
Sequence of Event (SOE)
- 1024 time stamped events
Oscillography,
- 64 digital & up to 40 Analog channels
Data Logger, disturbance recording
16 channels up to 1 sample / cycle /
channel
Fault Reports
- Powerful summary report of pre-fault
and fault values
Multi-ended fault location
- calculating fault location on two or
three terminal lines with 2% accuracy
The very high sampling rate and large
amount of storage space available for
data recording in the L90 can eliminate
the need for installing costly standalone
recording equipment.
CB1
CT1
CB2
CT2
CB3
CT3
CB4
BUS1
CT4
L90-2
C
o
m
m
u
n
i
c
a
t
i
o
n

c
h
a
n
n
e
l
CB5
CT5
CB6
CT6
CB7
CT7
BUS2
L90-1
831783A1.CDR
PROTECTED
LINE
VT3
VT2
1PH
CT2
CB2 CB1
CT1
VT1
1PH
L90
Example of Distributed Bus Differential Protection Application.
L90 Breaker-and-a-Half Application example.
Advanced Device Health
Diagnostics
The L90 performs comprehensive device
health diagnostic tests during startup
and continuously at runtime to test
its own major functions and critical
hardware. These diagnostic tests monitor
for conditions that could impact security
and availability of protection, and present
device status via SCADA communications
and front panel display. Providing
continuous monitoring and early detection
of possible issues helps improve system
uptime.
Comprehensive device health
diagnostic performed during startup
Monitors the CT/VT input circuitry to
validate the integrity of all signals
Communications
The L90 provides for secure remote data
and engineering access, making it easy
and flexible to use and integrate into
new and existing infrastructures. Fiber
optic Ethernet provides high-bandwidth
communications allowing for low-latency
controls and high-speed file transfers of
relay fault and event record information.
The available redundant Ethernet option
and the embedded managed Ethernet
switch provide the means of creating fault
tolerant communication architectures in
an easy, cost-effective manner.
The L90 supports the most popular industry
standard protocols enabling easy, direct
integration into monitoring and SCADA
systems.
IEC61850
DNP3.0
IEC60870-5-104
Modbus RTU, Modbus TCP/IP
Interoperability with Embedded
IEC61850
The L90 with integrated IEC61850 can be
used to lower costs associated with line
protection, control and automation. GE
Multilins leadership in IEC61850 comes from
thousands of installed devices and follows on
Multilins extensive development experience
with UCA 2.0.
Replace expensive copper wiring
between devices with direct transfer of
data using GOOSE messaging
Configure systems based on IEC61850
and also monitor and troubleshoot
them in real-time with EnerVista


Viewpoint Engineer
Integrate GE Multilin IEDs and generic
IEC61850-compliant devices seamlessly
in EnerVista

Viewpoint Monitoring
Multi-Language
The L90 supports English, French, Russian,
and Chinese languages on the front panel,
EnerVista setup software, and product
manual. Easily switch between English
and an additional language on the local
displays without uploading new firmware.
206 206
L90 Line Differential System
T
r
a
n
s
m
i
s
s
i
o
n

L
i
n
e

P
r
o
t
e
c
t
i
o
n
www.GEDigitalEnergy.com
EnerVista
TM
Software
The EnerVista Suite is an industry-
leading set of software programs that
simplifies every aspect of using the L90
relay. The EnerVista suite provides all the
tools to monitor the status of the protected
asset, maintain the relay, and integrate
information measured by the L90 into
DCS or SCADA monitoring systems.
Convenient COMTRADE and Sequence
of Events viewers are an integral part
of the UR Setup software included with
every UR relay, to carry out postmortem
event analysis to ensure proper protection
system operation.
EnerVista Launchpad
EnerVista Launchpad is a powerful
software package that provides users with
all of the setup and support tools needed
for configuring and maintaining GE Multilin
products. The setup software within
Launchpad allows configuring devices in
real-time by communicating using serial,
Ethernet , or modem connections, or
offline by creating setting files to be sent
to devices at a later time.
Included in Launchpad is a document
archiving and management system
that ensures critical documentation is
up-to-date and available when needed.
Documents made available include:
Manuals & Brochures
Application Notes
Guideform Specifications
Wiring Diagrams
FAQs
Service Bulletins
Viewpoint Monitoring
Viewpoint Monitoring is a simple-to-use
and full-featured monitoring and data
recording software package for small
systems. Viewpoint Monitoring provides a
complete HMI package with the following
functionality:
Plug-&-Play Device Monitoring
System Single-Line Monitoring & Control
Annunciator Alarm Screens
Trending Reports
Automatic Event Retrieval
Automatic Waveform Retrieval
Viewpoint Engineer
Viewpoint Engineer is a set of powerful tools
that will allow the configuration and testing
of UR relays at a system level in an easy-to-
use graphical drag-and-drop environment.
Viewpoint Engineer provides the following
configuration and commissioning utilities:
Graphical Logic Designer
Graphical System Designer
Graphical Logic Monitor
Graphical System Monitor
Viewpoint Maintenance
Viewpoint Maintenance provides tools that
will create reports on the operating status
of the relay, simplify the steps to download
fault and event data, and reduce the work
required for cyber-security compliance
audits. Tools available in Viewpoint
Maintenance include:
Settings Security Audit Report
Device Health Report
Single Click Fault Data Retrieval
EnerVista Integrator
EnerVista Integrator is a toolkit that allows
seamless integration of GE Multilin devices
into new or existing automation systems.
Included in EnerVista Integrator is:
OPC/DDE Server
GE Multilin Drivers
Automatic Event Retrieval
Automatic Waveform Retrieval
User Interface
The L90 front panel provides extensive
local HMI capabilities. The local display
is used for monitoring, status messaging,
fault diagnosis, and device configuration.
User configurable messages that combine
text with live data, can be displayed when
user-defined conditions are met.

Record the operation of the internal L90
elements and external connected devices
with 1ms time-stamped accuracy to identify
the Sequence of Operation of station devices
during line faults and disturbances.
Power System Troubleshooting
Graphically view zone settings for
ground phase distance elements for
the selected zones and the power swing
detection element.
Analyze line faults using both analog and digital power system quantities
that are measured and recorded up to a rate of 64 samples per cycle.
207 207
L90 Line Differential System
T
r
a
n
s
m
i
s
s
i
o
n

L
i
n
e

P
r
o
t
e
c
t
i
o
n
www.GEDigitalEnergy.com
Typical Wiring
L90-H00-HCL-F8F-H6G-L6D-N6K-S6C-U6H-W7A
L90
A B C
52
1
Power
supply
9
CPU
7
COM
8
CT/VT
6
Inputs/
outputs
*
6
Inputs/
outputs
*
6
Inputs/
outputs
*
6
Inputs/
outputs
6
Inputs/
outputs
*
J U M X L W K V B H T D N G S F P R
RS-232
DB-9
(front)
UR COMPUTER
1
TXD RXD
RXD TXD
SGND SGND
1 8
3
2
20
7
6
4
5
22
CONNECTOR
PERSONAL
COMPUTER
CONNECTOR
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
DC
TO
REMOTE
L90
OPTIONAL
TC
TC
N
2
1 H1a
H2b
H1c
H1b
H2c
H2a
H4a
H4c
H3b
H3a
H4b
H3c
SURGE
H6a
H8a
H5b
H7b
H8b
H5a
H7a
H6c
H8c
H5c
H7c
H1
H2
H3
H4
I
V
I
V
I
V
I
V
6G
U8a
U7b
U7a
U8c
U7c U1b
U2b
U3b
U4b
U5b
U6b
U1a
U2a
U3a
U4a
U5a
U6a
U1c
U2c
U3c
U4c
U5c
U6c
SURGE U8b
U1
U5
U2
U6
U3
U4
6H I
V
I
V
I
V
I
V
I
V
I
V
N7a
N1a
N2b
N7c
N1c
N7b
N1b
N8c
N8b
N2c
N8a
N2a
N4a
N5b
N4c
N6b
N3b
N3a
N6a
N4b
N5c
N5a
N3c
N6c
6
K
N1
N5
N2
N6
N3
N7
N4
N8
CRITICAL
FAILURE
OUTPUT
CONTROL
POWER
HI
LO
1
FILTER
SURGE
B3a
B1b
B8a
B6b
B8b
B6a
B3b
B1a
B2b
B5b
Tx1 Rx1
Tx2 Rx2
IN
T
E
R
-
R
E
L
A
Y
C
O
M
M
S
.
W
7
A
FIBER
FIBER
6
C
S1
S5
S2
S6
S3
S7
S4
S8
S7a
S1a
S2b
S7c
S1c
S7b
S1b
S8c
S8b
S2c
S8a
S2a
S4a
S5b
S4c
S6b
S3b
S3a
S6a
S4b
S5c
S5a
S3c
S6c
L6a
L8a
L5b
L7b
L5a
L7a
L6c
L8c
L5c
L7c
SURGE
L1a
L8b
L4c
L2c
L3a
L3c
L1c
L3b
L1b
L4a
L2a
6
D
minimum
PROVIDED
8L
F
1
c
F
4
a
F
3
c
F
2
c
F
4
c
F
1
a
F
4
b
F
1
b
F
2
a
F
3
a
F
2
b
F
3
b
IA IB IC IG
IA
5
IA
1
IB
5
IC
5
IG
5
IB
1
IC
1
IG
1
F
8
c
F
8
a
F
5
a
F
5
c
F
7
c
F
6
a
F
7
a
F
6
c
V
X
V
A
V
B
V
C
V
X
V
A
V
B
V
C
Multilin
com
10BaseFL
10BaseFL
10BaseT
D1a
D2a
D4b
D3a
D4a IRIG-B
Input
IRIG-B
Output
COM
1
RS485
ALTERNATE
NORMAL
Tx2
Rx2
Tx1
Rx1
BNC
BNC
Fibre
Optic
*
Remote
Device
Shielded
Co-axial
Co-axial
com
10BaseFL
10BaseFL
10BaseT
D1a
D2a
D4b
D3a
D4a IRIG-B
Input
IRIG-B
Output
COM
1
RS485
ALTERNATE
NORMAL
Tx2
Rx2
Tx1
Rx1
BNC
BNC
Fibre
Optic
*
Remote
Device
Shielded
Co-axial
Co-axial
208 208
L90 Line Differential System
T
r
a
n
s
m
i
s
s
i
o
n

L
i
n
e

P
r
o
t
e
c
t
i
o
n
www.GEDigitalEnergy.com
Ordering Notes:
1 - For vertical mounting order codes, please visit our online store
2 - To view the latest options available for the L90, or to order the UR Classic Front Panel, please visit our online store for more details.
UR Applications I Learning CD TRCD-URA1-C-S-1
Multilink Ethernet Switch ML2400-F-HI-HI-A2-A2-A6-G1
Viewpoint Engineer VPE-1
Viewpoint Maintenance VPM-1
Viewpoint Monitoring IEC61850 VP-1-61850
Accessories for the L90
View Guideform specifications
Download the instruction manual
Review applications notes and support documents
Buy a L90 online
View the UR Family brochure
Visit www.GEMultilin.com/L90 to:
Ordering
L90 - * 00 - H * * - F ** - H ** - L ** - N ** - S ** - U ** - W/X ** For Horizontal Mount
Base Unit L90 Base Unit
CPU E RS485 + RS485 (IEC61850 option not available)
G RS485 + Multi-mode ST 10BaseF
H RS485 + Mutli-mode ST Redundant 10BaseF
J RS485 + Multi-mode ST 100BaseFX
K RS485 + Multi-mode ST Redundant 100BaseFX
N RS485 + 10/100 BaseT
S RS485 + 6 port, 100 Mbps, Managed Ethernet Switch
Software 00 No Software Options
02 Breaker and Half software
03 IEC61850
05 Breaker and Half + IEC61850
06 Phasor Measurement Unit (PMU)
07 IEC61850 + Phasor Measurement Unit (PMU)
08 Breaker & Half + Phasor Measurement Unit (PMU)
09 Breaker & Half + IEC61850 + Phasor Measurement Unit (PMU)
Mount / Coating H Horizontal (19" rack) - Standard
A Horizontal (19" rack) - Harsh Chemical Environment Option
V Vertical (3/4 size) - Standard
B Vertical (3/4 size) - Harsh Chemical Environment Option
User Interface K Enhanced English Front Panel
L Enhanced English Front Panel with User-Programmable Pushbuttons
M Enhanced French Front Panel
N Enhanced French Front Panel with User-Programmable Pushbuttons
Q Enhanced Russian Front Panel
T Enhanced Russian Front Panel with User-Programmable Pushbuttons
U Enhanced Chinese Front Panel
V Enhanced Chinese Front Panel with User-Programmable Pushbuttons
F Vertical Front Panel with English display
Power Supply H 125 / 250 V AC/DC
H RH 125/250 V AC/DC with redundant 125/250 V AC/DC
L 24 - 48 V (DC only)
CT/VT DSP 8L 8L Standard 4CT/4VT w/ enhanced diagnostics
8N 8N Standard 8CT w/ enhanced diagnostics
IEC 61850 Process Bus 81 8 Port IEC 61850 Process Bus Module
Digital I/O XX XX XX XX XX No Module
4A 4A 4A 4A 4A 4 Solid State (No Monitoring) MOSFET Outputs
4C 4C 4C 4C 4C 4 Solid State (Current w/opt Voltage) MOSFET Outputs
4D 4D 4D 4D 4D 16 Digital Inputs with Auto-Burnish
4L 4L 4L 4L 4L 14 Form-A (No Monitoring) Latchable Outputs
67 67 67 67 67 8 Form-A (No Monitoring) Outputs
6C 6C 6C 6C 6C 8 Form-C Outputs
6D 6D 6D 6D 6D 16 Digital Inputs
6E 6E 6E 6E 6E 4 Form-C Outputs, 8 Digital Inputs
6F 6F 6F 6F 6F 8 Fast Form-C Outputs
6K 6K 6K 6K 6K 4 Form-C & 4 Fast Form-C Outputs
6L 6L 6L 6L 6L 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs
6M 6M 6M 6M 6M 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs
6N 6N 6N 6N 6N 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs
6P 6P 6P 6P 6P 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs
6R 6R 6R 6R 6R 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs
6S 6S 6S 6S 6S 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs
6T 6T 6T 6T 6T 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs
6U 6U 6U 6U 6U 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs
6V 6V 6V 6V 6V 2 Form-A (Cur w/ opt Volt) 1 Form-C Output, 2 Latching Outputs, 8 Digital Inputs
Transducer I/O 5A 5A 5A 5A 5A 4 dcmA Inputs, 4 dcmA Outputs
5F 5F 5F 5F 5F 8 dcmA Inputs
Inter-Relay Communications 7A 820 nm, multi-mode, LED, 1 Channel
7B 1300 nm, multi-mode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7H 820 nm, multi-mode, LED, 2 Channels
7I 1300 nm, multi-mode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7S G.703, 2 Channels
7W RS422, 2 Channels
7V RS422, 2 Channels, Dual Clock
73 1550 nm, single-mode, LASER, 2 Channel
76 IEEE C37.94, 820 nm, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, multimode, LED, 2 Channel
2B C37.94SM, 1300nm Singlemode, ELED, 2 Channel Single mode
2S 6 port, 100 Mbps, Managed Ethernet Switch, HI (125/250V AC/DC)
2T 6 port, 100 Mbps, Managed Ethernet Switch, LO (24-48 Vdc)
090914-v4