Sunteți pe pagina 1din 53

Page 1 G&W ELECTRIC CO. 2012 PRINTED IN U.S.A.

OPERATION INSTRUCTIONS FOR


Type 7.1 Vacuum Interrupter Control
3 Phase with EZset Option

GWI 523-375
Rev. 1
July, 2012
Supersedes Rev. 0
March, 2012

Section Page
1. Introduction .................................................................. 2
1.1 General ............................................................... 2
1.2 Qualified Persons ............................................... 2
1.3 Shipment Inspection ........................................... 2
2. Safety Information & Precautions ................................ 3
2.1 Safety Alert Messages ....................................... 3
2.2 Following Safety Instructions .............................. 3
2.3 Replacement Instruction and Labels .................. 3
3. Product Description and Operations ........................... 4
3.1 General ............................................................... 4
3.2 Powering the Control .......................................... 4
3.3 External Trip Input (optional) .............................. 5
3.4 RS485 Communication ...................................... 5
4. VI Control Settings Software (VICSS) Setup .............. 6
4.1 General ............................................................... 6
4.2 Installing the Software ........................................ 6
4.3 Uninstalling the Software .................................... 6
4.4 Installing Cable Drivers for Windows XP ............ 6
4.5 Installing Cable Drivers for Windows Vista &
Windows 7 ..................................................................12
4.6 Connecting the Communication Cable .............17





5. Using the VI Control Settings Software ..................... 18
5.1 Startup .............................................................. 18
5.2 Menus ............................................................... 18
5.3 Software Settings ............................................. 24
5.4 Operation .......................................................... 25
5.5 Load Current .................................................... 27
5.6 VI Control Information ...................................... 27
5.7 Protection Setting Group .................................. 28
5.8 Sequence of Events ......................................... 29
6. Overcurrent Protection Settings ................................ 30
6.1 Trip Mode ......................................................... 31
6.2 Time/Current Characteristic Curves (TCC) ...... 32
6.3 Phase Minimum Trip ........................................ 33
6.4 Phase Instantaneous Trip Multiplier ................. 35
6.5 Phase Time Delay ............................................ 37
6.6 Phase Minimum Response Time ..................... 39
6.7 Phase Inrush Restraint ..................................... 41
6.8 Ground Fault Minimum Trip.............................. 43
7. Product Specification ................................................. 45
Appendix A: RS 485 MODBUS - RTU PROTOCOL ..... 46
Appendix B: Sequence of Events Format ..................... 51
Appendix C: Print Format .............................................. 52
Appendix D: Factory Default Settings ........................... 53












This information is transmitted by G&W Electric Co. and accepted by you subject to the following understanding and
agreement: By accepting these instructions and any included drawings you agree that all rights to the drawing and
information contained herein, as well as the proprietary and novel features of the subject matter, are reserved by G&W
Electric Co. and that devices embodying such features or information derived from these disclosures will not be
manufactured by you or disclosed to others without the expressed written consent of G&W Electric Co. These drawings
and information contained herein are and remain the property of G&W Electric Co. and are not to be copied, reproduced
or disclosed to others without the expressed written consent of G&W Electric Co.


Page 2 GWI 523-375 Rev. 1



1. Introduction

1.1 General

This document is intended to provide the user with necessary information to properly receive, operate, and
maintain the 3-phase G&W Type 7.1 VI Controls with EZset setting option. If, after reviewing the information
contained herein, you should have any questions, please contact G&W technical support.


Read these Instructions

Read and understand the contents of this document and follow all locally
approved procedures and safety practices before installing, operating or
maintaining this equipment. Be sure to read and understand the Safety
Information.

Keep these Instructions

This document is a permanent part of your G&W product. Keep it in a safe
location where it can be readily available and referred to as necessary.

How to Contact G&W

By Phone:

By Fax:
E-mail:
For Technical
Support:
Fax:
E-mail:
Mail:

Internet:

708-388-5010, Monday through Friday, 8:00 AM to 5:00 PM
Central Time
708-388-0755
webmail@gwelec.com

708-297-3835
708-389-0016
Aftermarket.support@gwelec.com
305 W. Crossroads Parkway, Bolingbrook, Illinois 60440, USA
To find your local G&W Representative visit our Web site:
www.gwelec.com


1.2 Qualified Persons


WARNING

The equipment covered by this document is intended to be installed, operated and maintained by qualified persons
who are trained in the installation, operation and maintenance of electric power distribution equipment along with the
associated hazards. A qualified person has been trained and is competent:
- To de-energize, clear and tag circuits and equipment in accordance with established safety procedures.
- To distinguish between live parts from non-live parts of the equipment.
- In the proper use of insulated tools, wears protective equipment such as rubber gloves, hard hat, safety glasses,
flash-clothes, etc. in accordance with established safety practices and is trained in the care of such equipment.
- As in certified in rendering first aid, especially in the technique of removing a person in contact with a live circuit and
in applying cardiopulmonary respiration.
These instructions are intended only for qualified persons and are not intended as a substitute for adequate training
and experience in safety procedures for this type of equipment.

1.3 Shipment Inspection

Examine the crated equipment carefully for any damage that may have occurred in transit. If damage is found,
a claim must be filed at once with the transportation company. Uncrate and remove packing as soon as
possible after receiving the equipment. Examine the equipment carefully for any hidden damage that may have
occurred in transit and was previously undetected. If damage is found, a claim should be filed at once with the
transportation company.




Page 3 GWI 523-375 Rev. 1



2. Safety Information & Precautions

2.1 Safety Alert Messages

The following is important safety information. For safe installation and operation, be sure to read and
understand all danger, warning and caution information. The various types of safety alert messages are
described below:


DANGER

DANGER - Indicates an imminently hazardous situation, which, if not avoided, will result in death or serious
injury.


WARNING

WARNING - Indicates a potentially hazardous situation, which, if not avoided, could result in death or
serious injury.


CAUTION

CAUTION - Indicates a potentially hazardous situation, which, if not avoided, may result in minor or
moderate injury. May also be used to alert against unsafe practices.

2.2 Following Safety Instructions

Carefully read all safety messages in this manual and on your equipment. Keep safety signs in good condition.
Replace missing or damaged safety signs.

Keep your equipment in proper working condition. Unauthorized modifications to the equipment may impair the
function and/or safety and effect equipment life.

If you do not understand any part of these safety instructions and need assistance, contact your G&W
representative or G&W Customer Service.

2.3 Replacement Instruction and Labels

Replacement instructions and safety labels are available from G&W. To obtain them, please contact G&W
Technical Support.
















Page 4 GWI 523-375 Rev. 1




3. Product Description and Operations


WARNING

Before setting, operating, or maintaining this equipment, carefully read and understand the contents of this
guide. Improper installation, handling, or maintenance can result in death, severe personal injury, and/or
equipment damage.


WARNING

This equipment is not intended to protect human life. Follow all locally approved procedures and safety
practices when installing or operating this equipment. Failure to comply may result in death, severe
personal injury, and/or equipment damage.

3.1 General

Type 7.1 is designed for operation with three G&W Solid Dielectric insulated Vacuum Interrupter single phase
mechanisms or one - three phase mechanism.

The control is microprocessor based, and will trip open the Vacuum Interrupter mechanism(s) after a time delay
corresponding to the monitored current. The device monitors the current in the three phases and phase
imbalance. If any of currents exceeds the pre-selected limit for a given period of time, that phase, or all three
phases will be tripped depending on the control settings.


CAUTION

These controls are designed to work exclusively with G&W Vacuum Interrupter mechanisms. Use of these
controls for any other purpose may cause damage to the control or other equipment.

Each control is a stand-alone unit and does not require any maintenance. The unit is powered by the internal
current transformers (CTs) that measure the phase current(s). The control does not require any external power
supply or battery for normal over current detection and operation.

Type 7.1 controls are mounted inside of the Solid Dielectric mechanism cover eliminating the need for a
separate enclosure and cabling.

3.2 Powering the Control

There are two ways to power the controls primary current flowing through the current transformers or through
an external power input, which must be factory ordered.

3.2.1 Powering from Primary Current

The current levels needed to power the control are shown in the table below.



Page 5 GWI 523-375 Rev. 1


CT Ratio Primary Current Available
on Any 1 Phase
Primary Current Available
On 3 Phases
500:1

15 Amps 10 Amps per Phase
1000:1

25 Amps 15 Amps per Phase




3.2.2 External Power Input (optional)

When there is insufficient primary current on the CTs (see table 2), an external power supply can be used
to power the control. This is required when utilizing the external trip input. The external power input accepts
a DC voltage between 12 and 24VDC. The maximum current draw on this input is 1.5A when a trip is
occurring.

Type 7.1 controls must be factory ordered with this option. Access to the external power connections is
through a hardwired cable that is sealed to the switch housing to maintain submersibility.

3.3 External Trip Input (optional)

The controls can be wired to trip the Vacuum Interrupter mechanism using external trip input. The external trip
input is a dry contact and requires that the external power input be active. When a closed contact is
momentarily applied, the control sends a trip signal to all phases of the Vacuum Interrupter Mechanism. This
could be done from a source such as a relay or RTU.

Type 7.1 controls must be factory ordered with this option. Access to the external trip connections is through a
hardwired cable that is sealed to the switch housing to maintain submersibility.


3.4 RS485 Communication

The Type 7.1 control is capable of communicating through a serial line - RS485 when provided with external
power. This option must be factory ordered.

The software driver uses the MODBUS RTU protocol. This protocol is provided with sum control, timeout and
frame checking.

The following actions can be performed when the control is not performing a timing trip and if powered.
-reading of load current on all three phases
-reading cause of trip and fault current
-reading of present parameters
-setting new parameters

The default factory settings for communications are: interface RS485, address 1.

Refer to Appendix A for protocol information.

Table 1: Amount of Primary Current Necessary to power the control


Page 6 GWI 523-375 Rev. 1



4. VI Control Settings Software (VICSS) Setup
4.1 General

Type 7.1 controls are programmed using the VI control Settings Software (VICSS). The software comes with a
programming kit that includes a communication cable and a CD with software and drivers for the cable. The VI
Control Settings Software communicates via a USB cable using MODBUS protocol.

The software is available free of charge by contacting G&W technical support. A proprietary cable (ordered
separately) is needed to utilize the software to communicate with the controls.

4.2 Installing the Software

The VICSS application can be installed on a desktop or laptop PC (this software will not work on the Apple
Operating system). The minimum requirements are:
One USB port
Windows 32-bit and 64-bit based operating system (XP, Vista, 7)

To start the installation process, insert the VI Control Settings Software installation CD into the computer.
Access the folder that is named VICSS Installer. Double click the setup.exe file in the folder. Follow the
instructions on the screen to complete the installation. The installation process will overwrite any older versions
of the VICSS software but not other G&W VI control settings software such as TMC.

4.3 Uninstalling the Software

To uninstall the application, access the control panel on the PC and choose the appropriate option to uninstall
the application.

4.4 Installing Cable Drivers for Windows XP

Two drivers must be installed (both included on CD). The first driver installation is for the communication cable
protocol. Insert the CD provided with these instructions.

Connect the USB connector on the
communication cable to a USB port.














CAUTION

Do not edit ANY files in the installation folder. Editing of these files will corrupt the data for the VI Control Settings
Software and prevent reading settings or programming the control.


Page 7 GWI 523-375 Rev. 1




Navigate to the device manager.




Locate G&W TMC USB Link, right click, and
select Update Driver.



Select No, not as this time and click Next.






Page 8 GWI 523-375 Rev. 1
Select Install from a list or specific location
(Advanced) and click Next.






Check Include this location in the search: and
click Browse.






Navigate to the CD, and select
CustomCP210xDriverInstall, click OK and then
Next.










Page 9 GWI 523-375 Rev. 1
Click Continue Anyway.









Click Finish. Next install the driver for the virtual
COM port.



Navigate back to the Device Manager. Locate
G&W TMC USB Link, right click, and click
Update Driver again.























Page 10 GWI 523-375 Rev. 1


Select No, not as this time and click Next.




Select Install from a list or specific location
(Advanced) and click Next.






Check Include this location in the search: and
click Browse.























Page 11 GWI 523-375 Rev. 1
Navigate to the CD, and select
CustomCP210xDriverInstall, click OK and then
Next.








Click Continue Anyway on the next screen, and
then Finish.



Click Finish. The driver installation is now
complete and the VI Control Settings Software
can communicate with the VI Control.

















Page 12 GWI 523-375 Rev. 1
4.5 Installing Cable Drivers for Windows Vista & Windows 7

Two drivers must be installed for the cable to communicate. Insert the CD provided with these instructions and
navigate to run CP210x_VCP_Win_XP_S2K3_Vista_7.EXE.

Click Next to start the installation.



Click I Accept the terms of the license
agreement and click Next.



If it is desired to install drivers to different
location, click Browse and choose the location.
Click Next to continue.









Page 13 GWI 523-375 Rev. 1
Click Install to begin the installation.



Click Finish to begin the second part of the
driver installation.



Click Install to continue.




Wait while it scans for devices and click OK
when complete.

















Page 14 GWI 523-375 Rev. 1

Connect the USB connector on the communication
cable to the PCs USB port.


Navigate to the device manager.






Locate G&W TMC USB Link, right click, and
select Update Driver Software.











Page 15 GWI 523-375 Rev. 1

Select Browse my computer for driver software.



Select Let me pick from a list of device drivers on
my computer.





Locate Ports (COM & LPT), select it, and click
Next.















Page 16 GWI 523-375 Rev. 1
Under Manufacturer, locate Silicon
Laboratories and select it.







Under Model, locate Silicon Labs CP210x USB
to UART Bridge and Click Next.







Click Yes to continue.


Click Close to finish the installation. The driver
installation is now complete and the VI Control
Settings Software can communicate with the VI
Control.




Page 17 GWI 523-375 Rev. 1

4.6 Connecting the Communication Cable

The figure below shows a typical Trident Solid Dielectric fault interrupter switch with Type 7.1 control. It also
shows the location of the communication port for use with the VI Control Settings software.


Figure 4.1 Location of Communication Port

Connect the USB side of the programming cable to the PC and connect the Brad Harrison connector side of the
cable to its mating receptacle on the switch. The connector is keyed and will only go on one way. A 6ft
extension cable is available as an option. This extension cable can be permanently attached to the
communication port on the switch. A cap provided with the cable must be installed and hand-tightened when
not in use to maintain submersibility.




CAUTION

Replace the sealing cap on the programming port. Failure to replace the sealing cap may result in the loss of
sealing integrity causing damage and/or misoperation of the control.

CAUTION

Do not over tighten the sealing cap, hand tighten only. Over tightening sealing cap may damage the sealing
surface resulting in loss of sealing integrity causing damage and/or misoperation of the control.

CAUTION

Disable external trip operation while programming the control. The control will be powered up when using the
laptop programming kit. Any closure of an external trip contact will cause the control to send a trip signal to the
vacuum fault interrupters.
CAUTION

Do not attach any other equipment to the programming port. Attaching any other equipment to the programming
port may cause damage and/or misoperation of the trip module.


Page 18 GWI 523-375 Rev. 1


5. Using the VI Control Settings Software


CAUTION

Over current protection is disabled during programming. Unexpected system operations may occur as
upstream devices become responsible for over current protection.

5.1 Startup

Once the software is successfully installed, double click on the VICSS icon to start the program. The start-up
screen shown in Figure 5.1 should open.



Figure 5.1 Start-up Screen

5.2 Menus

Figure 5.2 shows the available drop down menus in the VICSS software. Each of these menus is explained in
detailed in following section.

File Operation TCC Help
New Settings
Open Settings
Save Settings
Print
Exit
Connect
Disconnect
Set Time and Date
Set Modbus
Address
Password
Upgrade Firmware
Software Version
Import from CSV File
Export to CSV File
List Selection
Retrieve from VI
Control

Figure 5.2 Software Menu Tree



Page 19 GWI 523-375 Rev. 1



5.2.1 File Menu

5.2.1.1 New Settings

Choose New Settings to open a screen with default settings.


Figure 5.3 New Settings Screen

Select 3 phase for number of protected phases, appropriate CT Ratio and EZset settings option and click
OK. Refer to the label that is installed on the outside of the switch or the customer drawing for CT ratio
information.

5.2.1.2 Open Settings

Choose Open Settings to select an existing settings file.


Figure 5.4 Open Settings Screen

Navigate to the directory of the settings file you wish to open, and click open. The settings file is saved as a
.VI file.

5.2.1.3 Save Settings

Choose Save Settings to save the settings file. This will prompt for a location in which to save the settings


Page 20 GWI 523-375 Rev. 1

file. Type a name for the file and click save.



Figure 5.5 Save Settings Screen

5.2.1.4 Print

Choose Print to print the displayed settings file. Choose the appropriate setup options and click OK. An
example for printed settings is shown in Appendix C.


Figure 5.6 Print

5.2.1.5 Exit
Choose Exit the close the program. If there are any unsaved changes, the program will prompt to save
these before closing.

5.2.2 Operation Menu

5.2.2.1 Connect

Choose Connect to set the parameters and start communication with the VI control.


Page 21 GWI 523-375 Rev. 1



Figure 5.7 Connect Window

Confirm the serial communication port and modbus address are correct before connecting. To determine
which Communication Port the USB Programming cable uses, utilize the Device Manager built into
Windows. Access to the Device Manager can vary depending on the version of Windows being used.

Once at the Device Manager, the COM port to be used is listed under Ports (COM & LPT) as G&W TMC
Link Cable for Windows XP and Silicon Labs CP210x USB to UART Bridge for Windows Vista and 7.


Figure 5.8 Device Manager

Record the COM port number (for example, COM6, as shown in Figure 5.8), listed next to Silicon Labs
CP210X USB to UART Bridge (Windows 7 & Vista) or G&W TMC Link (Windows XP) and choose this
port from the drop-down menu in the VI Control Settings Software.

The modbus address is not applicable to Type 7.1 VI Control. The factory default is 1 and must not be
changed for proper communication.

Click connect to communicate with the VI Control. When connected, the connection status in the software
will change from OFFLINE to ONLINE.

5.2.2.2 Disconnect

Choose Disconnect to disconnect the software from the VI Control. The connection status should change


Page 22 GWI 523-375 Rev. 1

from ONLINE to OFFLINE.

5.2.2.3 Set Time and Date

Choose Set Time and Date to change the current time and date on the VI Control. The VI Control is set to
Eastern Standard Time (EST) by factory default. Choose the required date and time and hit Send button
to update the time in the VI Control. The date and time in this window will automatically populate with the
time on the PC connected to the VI Control.


Figure 5.9 Set Time and Date
5.2.2.4 Set Modbus Address

The modbus address (Figure 5.7) cannot be changed in the Type 7.1 VI Control. The factory default is 1.

5.2.2.5 Password

This can be used to change or disable the password. VI Controls ship from the factory with a default
password of GWVI and the password enabled. Password is case sensitive.

To disable the password, uncheck the box in front of Enable.

To change the password, type in the old password (factory default is GWVI) and then enter the new
password.


Figure 5.10 Password Configuration

5.2.3 TCC Menu

The options under this menu are not available with the EZset settings option. If you would to upgrade the
unit to have these options, please contact local G&W representative and ask for Plus settings option.



Page 23 GWI 523-375 Rev. 1




5.2.4 Help Menu
5.2.4.1 Upgrade Firmware


Figure 5.11 Firmware Upgrade

The VI Control includes the ability to upgrade to the control firmware using this menu. G&W will notify
users when firmware upgrade options are available. Contact G&W technical support for information about
firmware upgrades.

5.2.4.2 Software Version


Figure 5.12 Software Version

The software version is available from this screen.



Page 24 GWI 523-375 Rev. 1

5.3 Software Settings

5.3.1 Device Information



Figure 5.13 Device Information

The VI Control Settings Software allows the user to enter control specific identification information which
will appear while communicating with, retrieving settings from, and downloading events from specific VI
Controls. Each field is stored in the non-volatile memory of the control for future use.

5.3.1.1 Device ID

This parameter can be 15 characters long.

5.3.1.2 Feeder Name

This parameter can be 15 characters long.

5.3.1.3 Other

This parameter can be 15 characters long.

5.3.2 Connection Status

This field is used to display the status of the connection between VI Control Settings Software and the VI
control. The status will be displayed as either ONLINE or OFFLINE.

ONLINE indicates that the VI Control Settings Software is currently communicating with the VI Control.

OFFLINE indicates that communication has not been established between the VI Control Settings Software
and the control.

5.3.3 Settings

This parameter displays the status of settings currently displayed in the software. Options include:

New - settings have been created and have not yet been sent to the VI Control or saved
Modified - the displayed settings have been modified and have not been saved
From File the displayed settings were opened from a file stored on the PC
From VI Control the displayed settings were read from a VI control and have not yet been saved OR
modified

Note: When the VI Control Settings Software is displaying From File in the settings field, the settings
shown may or may not be different than the settings stored in the VI Control.





Page 25 GWI 523-375 Rev. 1


5.4 Operation

Figure 5.14 Operation section

5.4.1 Retrieve

Pressing the Retrieve button will retrieve all overcurrent protection settings and control status information
from the VI Control and will populate the VI Control Settings Software fields. Checking the Auto button will
automatically retrieve the Block GF Trip handle status (optional), load current and VI Control Information
every 15 seconds.

5.4.2 Send

Pressing the Send button, sends all overcurrent protections setting and the Device Information fields to the
VI control. If the password is enabled, a pop-up window will appear to prompt for the password to be
entered before continuing.


Figure 5.15 Password prompt for sending settings

Type in the password and click Ok. Refer to password section for more information.

5.4.3 Auto

Checking the Auto button will automatically retrieve the Block GF Trip handle status (optional), load current
and VI Control Information every 15 seconds.

5.4.4 Block All Trips (Optional)

When the VI Control is factory ordered with this option, the text will show in Black. If the VI control is not
equipped with this option, the text will be grayed out and the box cannot be checked. Checking this box
turns off the VI Controls setting group and overcurrent protective functions. If the VI Control experiences
an overcurrent condition while this box is checked, this event will not be recorded.

When this box is checked, a window will appear with the following message WARNING: You are about to
DISABLE ALL PROTECTION. Press OK to confirm the selection.



Page 26 GWI 523-375 Rev. 1


Figure 5.16 Enable Block All Trips Warning

Unchecking the box will put the control in normal operation mode. When this box is unchecked, a window
showing WARNING: You are about to ENABLE ALL PROTECTION will ask to confirm the selection.
Press OK to continue.


Figure 5.17 Disable Block All Trips Warning

5.4.5 Block GF Trip (Optional)

The manual Block Ground Fault Trip feature allows the user to enable or disable the Ground Fault settings
in the control through an external handle located on the switch mechanism housing.

Figure 5.18 Block GF Trip Handle Location and Label


Page 27 GWI 523-375 Rev. 1

Figure 5.18 shows a typical Trident Solid Dielectric fault interrupter switch with Type 7.1 control and the
optional manual Block Ground Fault Trip handle.

This parameter shows the position of the Block Ground Fault Trip handle on the switch or VI Control.

When the parameter shows ENABLED, the Block Ground Fault Trip handle has been engaged and the VI
Control will not initiate a trip based on the Ground Fault Settings. If the VI Control experiences an
overcurrent Ground Fault condition while this is checked, this event will not be recorded.

When the parameter shows DISABLED, the handle is in the normal operation position and the VI Control
will respond to the settings stored within the control.

5.5 Load Current


Figure 5.19 Load Current Fields

The Load Current fields will be populated when the VI Control Settings Software is connected to the VI
Control and the Communication Status shows ONLINE. When the Auto box next to Retrieve is checked,
the load currents get updated every 15 seconds. The primary current flowing through the switch will be
shown in the A-phase, B-phase, C-phase fields. The calculated phase imbalance will be shown in the N
(Neutral) field.

5.6 VI Control Information


Figure 5.20 VI Control Information

The VI control information will populate when the PC is connected to a VI Control and the Connection
Status shows ONLINE. The VI Control Time field in the software gets updated every minute when
connected to the control. The following information is displayed:
Type - Settings option that is available on this control
CT ratio Ratio of the current transformers in the switch
Firmware Version of firmware on the control
VI Control Time The current time on the VI control
Last Configuration The time that the VI control was last configured

Last configuration is updated when the send button is pressed or when the enable/disable button is
pressed under Alternate tab with New or Modified in the settings field and communication status is
ONLINE.


Page 28 GWI 523-375 Rev. 1


5.7 Protection Setting Group

The VI control allows for one set of protection settings. For explanation of these settings, please refer to
Section 6.


Figure 5.21 Protection Settings Tab



Page 29 GWI 523-375 Rev. 1

5.8 Sequence of Events

The sequence of events tab shows the 16 most recent events recorded in the VI control when the
connection status shows ONLINE. The most recent event is recorded as E1 and the oldest event is
recorded as E16.

To view specific events, check the box next to the event and the detailed description of these events will be
displayed in the box to the right. Multiple events can be checked and viewed at one time. Click the
Refresh button to view any recent events.


Figure 5.22 Sequence of Events

Click the Download button to download all 16 events in the VI control as a .txt onto your PC. The format
and explanation of one event is shown in Appendix B.




Page 30 GWI 523-375 Rev. 1


6. Overcurrent Protection Settings

This section covers different settings and selections available for each setting for EZset option. Each control is
factory set to the lowest setting or to customer provided settings after testing. Refer to Appendix D for the factory
default settings.


CAUTION

Improper setting selections can result in miscoordination with other devices on the system. Check
coordination of settings with other system devices before applying.


CAUTION

Curve selection and trip settings must be selected so as not to exceed the ratings of equipment on the
system. Improper settings can cause damage to equipment on the system.


CAUTION

Switch bushing selection or cable size may limit acceptable trip setting selection. Trip setting must be
selected so as not to exceed ratings of bushings or cable. Improper settings can cause damage to
equipment on the system.




Page 31 GWI 523-375 Rev. 1

6.1 Trip Mode

The VI Control Settings Software is designed to work with both single phase tripping and three phase
tripping mechanisms. The Trip Mode dial allows for this selection.

When the 1 Phase mode is selected, the control will only trip the phase where the input current exceeds
the phase minimum trip, if the switch is equipped with single phase tripping mechanisms.

When the 3 Phase mode is selected, the control will trip all three phases when the input current exceeds
the lowest pre-selected limit. Figure 6.1 shows where to set the Trip mode.



Figure 6.1



Page 32 GWI 523-375 Rev. 1

6.2 Time/Current Characteristic Curves (TCC)

There are 30 built-in curves available for selection. The built-in curves include fuse and relay curves. The
relay curves have multiple time dials which are displayed when the relay curve is selected in the software.
Each TCC curve is stored in non-volatile memory as a series of 489 data points in a tabular format. A TCC
curve is a table that provides different time delays for different current values.

The G&W TCCs form two groups, emulation curves and standard relay curves. All curves are generated
from emulations of actual curves. None of the emulations is meant to represent one specific manufacturer;
instead, data was used from multiple manufacturers. All emulations meet ANSI standards. Different TCC
curves can be selected for Phase and Ground Settings. Figure 6.2 shows where to set the Phase and
Ground TCC curves.


Note: For Time Current Curves, reference G&W website at www.gwelec.com.



Figure 6.2



Page 33 GWI 523-375 Rev. 1

6.3 Phase Minimum Trip

General:





The VI controls operate off of a Phase Minimum Trip setting. All Phase trip time calculations
are made using this value as a point of reference. If the current, on A, B, or C phases, is above
the phase minimum trip threshold, then timing begins by comparing the primary current to the
values stored in the TCC table. A trip command is sent when the time exceeds the TCC time
associated with the measured primary current level.

Settings:




The range for the Phase Minimum Trip setting is 15 300 Amps for 500:1 CTs and 30 600
Amps for 1000:1 CTs. The user may select between 12 settings. Controls with 500:1 CTs can
choose from 15A, 20A, 25A, 35A, 45A, 60A, 75A, 100A, 125A, 175A, 225A and 300A. Controls
with 1000:1 CTs can choose from 30A, 40A, 50A, 70A, 90A, 120A, 150A, 200A, 250A, 350A,
450A, and 600A.

Example:

































Figure 6.3

Figure 6.3 depicts how the trip timing is determined based on the measured input current.
Variations in the primary current during the timing phase will also affect the final trip time. If
during the timing phase the primary current falls below 85% of the Phase Minimum Trip setting
the timing is reset to zero. If the primary current is between 85% and 100% of the Phase
Minimum Trip setting, a reverse timing algorithm is employed until the timing is reset to zero.

The accuracy of the timing is dependent on the slope of the TCC. The steeper the slope the
greater the error band due to the accuracy of the current measurement. If the primary current is
greater than 250 Amps, the typical current measurement accuracy is +/-2%. If the primary
current is less than 250 Amps, the typical current measurement accuracy is +/-5 Amps.

The TCC table has a dynamic range for currents ranging from the Phase Minimum Trip to 20
times the Phase Minimum Trip. The control will still issue a trip command if the current level
0.010
0.100
1.000
10.000
100.000
10 100 1000
T
r
i
p

T
i
m
e

(
S
e
c
)
Primary Current (Amps)
E-spd Slow Curve with
Phase Minimum Trip of
25 Amps


Page 34 GWI 523-375 Rev. 1















exceeds 20 times the Phase Minimum Trip value. In these scenarios, the control uses the
fastest trip time on the selected TCC curve. For example, a Phase Minimum Trip of 15 Amps
has a TCC maximum current of 300 Amps and a Phase Minimum Trip of 100 Amps has a TCC
maximum current of 2000 Amps.

The control can measure up to 6000 Amps for 500:1 CTs and 12,000 Amps for 1000:1 CTs.
These are the maximum currents that will be recorded under Sequence of Events.


Where to set
Phase Minimum
Trip in
Software:






























Figure 6.4

If 1 phase trip mode is selected, separate minimum trip values can be selected for each phase.
If 3 phase trip mode is selected, changing any minimum trip value will update all the minimum
trips. Please see trip mode section for more information.



Page 35 GWI 523-375 Rev. 1
6.4 Phase Instantaneous Trip Multiplier

General:





The Phase Instantaneous Trip Multiplier aids in customizing the protection capabilities of the
control by providing a separate trip time for higher fault currents. When any phase exceeds the
current value defined by the Phase Minimum Trip times the Phase Instant Multiplier, the control
will initiate a trip command to all three phases within half a cycle, 8.3 msec at 60 Hz (10 msec
at 50 Hz).

Settings:


The user may select between 9 settings. The settings available are OFF, x1, x3, x5, x7, x9,
x11, x13, x15. Selecting OFF disables this feature.

Example:





































E Speed Slow selected for Phase TCC, 60 Hz system, Phase Minimum Trip set to 25 Amps,
Phase Instantaneous Trip Multiplier set to x3 Amps and all other settings inactive:



Figure 6.5

If the primary current on A phase is 60 Amps, the control will trip as defined by the TCC and
Phase Minimum Trip setting in 2.085 seconds. If the current is 80 Amps, which is above the
Phase Instantaneous Trip setting of 75 Amps (25 x 3), the control will initiate a trip command in
8.3 msec instead of the typical Phase TCC time of 1.117 seconds




















0.010
0.100
1.000
10.000
100.000
10 100 1000
T
r
i
p

T
i
m
e

(
S
e
c
)
Primary Current (Amps)
Standard
Curve
Modified Curve
with
Instantaneous
Trip setting of 75
Amps


Page 36 GWI 523-375 Rev. 1


Where to set
Phase
Instantaneous
Trip Multiplier in
software:














Figure 6.6




Page 37 GWI 523-375 Rev. 1
6.5 Phase Time Delay

General:






This feature may be helpful when coordinating the VI Control with other protection devices.
When the measured current level exceeds the Phase Minimum Trip value, the control will add
the selected Phase Time Delay to the phase TCC time. After both the phase TCC time and
Phase Time Delay have elapsed, the control will initiate a trip command to one phase or three
phases based on the trip mode selection.
Settings:


The user may select between 12 settings. The settings available are 0.000s, 0.030s, 0.060s,
0.100s, 0.150s, 0.200s, 0.250s, 0.300s, 0.350s, 0.400s, 0.450s, and 0.500s. Selecting 0.000s
disables this feature.

Example:






































E Speed Slow selected for Phase TCC, 60 Hz system, Phase Minimum Trip value set for 25
Amps, Phase Time Delay set for 0.30 seconds, and all other settings inactive:



Figure 6.7

If the primary current on A phase is 60 Amps, the control will time for the phase TCC time of
2.085 seconds and then for the Phase Time Delay of 0.30 seconds. It will initiate a trip
command in 2.385 (2.085 + 0.30) seconds.


















0.010
0.100
1.000
10.000
100.000
10 100 1000
T
r
i
p

T
i
m
e

(
S
e
c
)
Primary Current (Amps)
Standard
Curve
Modified Curve
with Phase Time
Delay of 0.3 secs


Page 38 GWI 523-375 Rev. 1


Where to set
Phase Time
Delay in
software:















Figure 6.8



Page 39 GWI 523-375 Rev. 1
6.6 Phase Minimum Response Time

General:



The Phase Minimum Response Time feature allows the user to ensure that the Vacuum
Interrupter will not trip open before a specific time. This feature will work in conjunction will all
other features of the control except the Ground Fault (Phase Imbalance Feature).

Settings:



The user may select between 10 settings. The settings available are OFF, 0.050s, 0.100s,
0.145s, 0.205s, 0.260s, 0.335s, 0.405s, 0.495s and 0.580s. Selecting OFF disables this
feature.

Example:









































E Speed Slow selected for phase TCC, 60 Hz system, Phase Minimum Trip value set to 25
Amps, Phase Minimum Response Time set to 0.58 seconds, and all other settings inactive:



Figure 6.9

If the primary current on A phase is 60 Amps, the normal phase trip time would be 2.085
seconds as defined by the Phase TCC. Because this is above the Phase Minimum Response
Time of 0.58 seconds, the VI Control uses the phase TCC time. If the primary current is 120
Amps, the Phase TCC time would be 0.465 seconds. Because the Phase Minimum Response
Time is set for 0.58 seconds, the control will wait and not initiate a trip command until 0.58
seconds.














0.010
0.100
1.000
10.000
100.000
10 100 1000
T
r
i
p

T
i
m
e

(
S
e
c
)
Primary Current (Amps)
Modified Curve with
Phase Minimum
Response of 0.58
secs
Standard
Curve


Page 40 GWI 523-375 Rev. 1


Where to set
Phase Minimum
Response in
software:














Figure 6.10



Page 41 GWI 523-375 Rev. 1
6.7 Phase Inrush Restraint

General:










The Phase Inrush Restraint function consists of two settable parameters, the Phase Inrush Trip
Multiplier and the Phase Inrush Active Timer. This function is helpful for preventing nuisance
trips due to cold load pickup. At the initial start-up of the control, Phase Minimum Trip value is
temporarily changed to the Phase Minimum Trip times the Phase Inrush Trip Multiplier. This
value is active for the duration of the Phase Inrush Active Timer. The Phase Inrush Restraint
Function is disabled after the Phase Inrush Active Timer expires, or any phase exceeds the
Phase Inrush Trip Multiplier times the Phase Minimum Trip.

Once disabled, the Phase Inrush Restraint Function will not be reactivated unless the average
three phase primary current drops below 7.5 Amps (500:1 CTs) or 15 Amps (1000:1 CTs).

Settings:





The user may select between 12 settings for Phase Inrush Multiplier and 12 settings for Phase
Inrush Active Timer. The settings available for the multiplier are x1, x2, x3, x4, x5, x6, x7, x8,
x9, x11, x13, x15 and the settings available for the active timer are 0.00s, 1.75s, 3.25s, 5.25s,
and 7.00s. Selecting 1 for the Phase Inrush multiplier or entering 0.00s for the Phase Inrush
Active timer will disable this feature.

Example:







































E Speed Slow selected for phase TCC, Phase Minimum Trip value set to 25 Amps, Phase
Inrush multiplier set to 3, Phase Inrush Active Timer set to 5.25 seconds, and all other settings
inactive:


Figure 6.11

If the primary current on A phase is 60 Amps, the TCC time would be 2.085 seconds without
inrush functionality. Because inrush function is activated, the Phase Minimum Trip is
temporarily changed to 75Amps (25 x 3) for 5.25 seconds. If the primary current remains at 60
Amps after 5.25 seconds, the control will begin timing per the TCC and then initiate a trip
command. The total time will be 7.335 (5.25 + 2.085) seconds.
0.010
0.100
1.000
10.000
100.000
10 100 1000
T
r
i
p

T
i
m
e

(
S
e
c
)
Primary Current (Amps)
Modified Curve
with Inrush
multiplier of 3
and Inrush delay
of 5.2 seconds
Standard
Curve


Page 42 GWI 523-375 Rev. 1









If the current on phase A goes above 75 Amps, the Inrush Restraint function will be disabled,
and the control will initiate a trip command using the Phase TCC with a Phase Minimum Trip of
25 Amps.




Where to set
Phase Inrush
Modifiers in
Software:




















Figure 6.12






Page 43 GWI 523-375 Rev. 1
6.8 Ground Fault Minimum Trip

General:














The Ground Fault Minimum Trip feature can be used to protect against excessive phase
imbalances that may result in damage to equipment. This feature is only available when 3
phase Trip Mode is selected.

The control performs an analog sum of the three individual phase currents. The analog sum
takes the current amplitude as well as the phase angle into account. If the sum is not zero,
there is a phase imbalance present. The Ground Fault feature is set as a percentage of the
minimum trip. If the phase imbalance is more than the selection Ground Fault Minimum Trip
setting, the VI Control will begin to time using the TCC chosen for ground fault settings. A
separate TCC must be selected for Ground Fault settings. This TCC can be different from the
Phase TCC. Refer to section 6.2 on how to choose a different Ground Fault TCC.

The control can measure up to 3000 Amps for 500:1 CTs and 6000 Amps for 1000:1 CTs. This
represents the maximum current that will be recorded for phase imbalance under Sequence of
Events.

Settings:

The user may select between 10 settings. The settings available are OFF, 10%, 15%, 20%,
25%, 30%, 35%, 40%, 45%, and 50%. Selecting OFF disables this feature.

Example:







































E Speed Slow selected for both phase and ground TCC, Phase Minimum Trip value set for 100
Amps, Ground Minimum Trip for 10%, and all other settings inactive:


Figure 6.13

If the phase imbalance is 30 Amps, the VI control will initiate a trip command after a Ground
TCC trip time of 1.283 seconds.




0.001
0.010
0.100
1.000
10.000
100.000
1 10 100 1000 10000
T
r
i
p

T
i
m
e

(
S
e
c
)
Primary Current (Amps)
10 Amp TCC Curve
used for Ground
Fault Calculations
100 Amp TCC
Curve used for
phase calculations


Page 44 GWI 523-375 Rev. 1



Where to set
Ground Fault
Minimum Trip in
Software:























Figure 6.14














Page 45 GWI 523-375 Rev. 1

7. Product Specification

Power Requirements Powered by current from the current transformers
External Power
Requirements (optional)
12-24 VDC through the External Power Input (Section 3)
Minimum Trip Setting
Options (500:1 CT)
15A, 20A, 25A, 35A, 45A, 60A, 75A,
100A, 125A, 175A, 225A, 300A

Minimum Trip Setting
Options (1000:1 CT)
30A, 40A, 50A, 70A, 90A, 120A, 150A,
200A, 250A, 350A, 450A, 600A

Enclosure IP68 (20ft 20 days)
Frequency 60 Hz (Standard)
50 Hz (Optional)
Environment Operating Temperature: -40C to +65C
Storage Temperature: -50C to +85C
Humidity: 10% to 95%

Type Tests:


Electrostatic Discharge test

IEC 60255-22-2 Level 4 contact discharge on conductive user interface

Radiated Electromagnetic
Field Disturbance test &
Radiated Electromagnetic
Interference


IEEE C37.90.2-2004 - 35V/m
Surge Withstand ANSI/IEEE C37.60

Vibration

IEC 60255-21-1 First Edition 1988 (EN 60255-21-1 First Edition 1995)
Electrical relays, Part 21: Vibration, shock, bump, and seismic tests on
measuring relays and protection equipment; Section One Vibration tests
(sinusoidal); Severity: Class 1 Endurance; Class 2 Response.

IEC 60255-21-2 First Edition 1988 (EN 60255-21-2 First Edition 1995)
Electrical relays, Part 21: Vibration, shock, bump, and seismic tests on
measuring relays and protection equipment; Section Two Shock and Bump
tests. Severity Level: Class 1 Shock withstand, Bump; Class 1 Shock
Response
















Page 46 GWI 523-375 Rev. 1
Appendix A: RS 485 MODBUS - RTU PROTOCOL


A.1 Communication Settings

Baud rate 1200
Parity Odd
Error check CRC - 16
Hardware RS 485

A.2 Modbus Functions Supported

The communication driver has implemented the following functions:

1. Function Code 03 - Read one or more Holding Registers.
Refer to section A.3 for more information.

2. Function Code 04 - Read one or more Input Registers.
Refer to section A.4 for more information.

A.3 Function Code 03 Parameters

Function Code: 03
Start address: 0000
Number of registers: 15



















A3.1 Interpretation of Parameters

Registers 0000, 0001, 0002 - Phase Minimum Trip A / B / C
Register Parameter
0000 Minimum Trip Phase C
0001 Minimum Trip Phase B
0002 Minimum Trip Phase A
0003 Phase Instant Trip Multiplier
0004 Ground Fault Minimum Trip Multiplier
0005 The Ground Fault TCC
0006 Phase Time Delay Adder
0007 Phase Minimum Response Time
0008 Phase Inrush Restraint Multiplier
0009 Phase Inrush Restraint Time Adder
0010 The Phase TCC
0011 Single or Three Phase Trip Settings
0012 Transformer ratio and option flags
0013 Reserved
0014 Unit Address
Value (CT 500 : 1) (CT 1000 : 1)
0 15 A 30 A
1 20 A 40 A
2 25 A 50 A
3 35 A 70 A
4 45 A 90 A
5 60 A 120 A
6 75 A 150 A
7 100 A 200 A


Page 47 GWI 523-375 Rev. 1






Register 0003 Phase Instant Trip Multiplier
Value Multiplier
0 OFF
1 1
2 3
3 5
4 7
5 9
6 11
7 13
8 15

Register 0004 Ground Fault Minimum Trip Multiplier (Percentage of Phase Minimum Trip)
Value Setting
0 OFF
1 10 %
2 15 %
3 20 %
4 25 %
5 30 %
6 35 %
7 40 %
8 45 %
9 50 %

Registers 0005, 0010 Ground Fault and Phase Time Current Curve
Value TCC
0 E-SLOW (E Speed Slow)
1 E-STD (E Speed Standard)
2 OFC (Oil Fuse Cut Out)
3 K (K Speed)
4 KEAR Q (Kearney QA Speed)
5 EF (EF Speed)
6 NX-C (NC35-C)
7 CO11-1 (CO11 Time Dial 1)
8 CO11-2 (CO11 Time Dial 2)
9 T LINK (T Speed Slow/ T Link)
10 CO9-1 (CO9 Time Dial 1)
11 CO9-2 (CO9 Time Dial 2)
12 280ARX (280 ARC Recloser Curve)
13 CO9-4.5 (CO9 Time Dial 4.5)
14 CENT A (Centerior A)
15 KEARKS (Kearney KS Speed)
16 IAC53 (GE IAC53 Relay)
17 F (F Speed)
18 CO8-.5 (CO8 Time Dial 0.5)
19 CO8-1 (CO8 Time Dial 1)
20 CO8-2 (CO8 Time Dial 2)
21 CO8-3 (CO8 Time Dial 3)
22 CO8-4 (CO8 Time Dial 4)
8 125 A 250 A
9 175 A 350 A
10 225 A 450 A
11 300 A 600 A


Page 48 GWI 523-375 Rev. 1
23 CO8-5 (CO8 Time Dial 5)
24 CO8-6 (CO8 Time Dial 6)
25 CO8-7 (CO8 Time Dial 7)
26 CO8-8 (CO8 Time Dial 8)
27 CO8-9 (CO8 Time Dial 9)
28 CO8-10 (CO8 Time Dial 10)
29 CO8-11 (CO8 Time Dial 11)
30 Effuse (EF Fuse Equivalent)

Register 0006 Phase Time Delay adder
Value Time Delay
0 0.00 Seconds
1 0.03 Seconds
2 0.06 Seconds
3 0.10 Seconds
4 0.15 Seconds
5 0.20 Seconds
6 0.25 Seconds
7 0.30 Seconds
8 0.35 Seconds
9 0.40 Seconds
10 0.45 Seconds
11 0.50 Seconds


Register 0007 Phase Minimum Response time
Value Minimum Response Time
0 OFF
1 0.050 Seconds
2 0.100 Seconds
3 0.145 Seconds
4 0.205 Seconds
5 0.260 Seconds
6 0.335 Seconds
7 0.405 Seconds
8 0.495 Seconds
9 0.580 Seconds


Register 0008 Phase Inrush Restraint multiplier
Value Inrush Multiplier
0 x1
1 x2
2 x3
3 x4
4 x5
5 x6
6 x7
7 x8
8 x9
9 x11
10 x13
11 x15

Register 0009 Phase Inrush Restraint Time Adder
Value Time Adder


Page 49 GWI 523-375 Rev. 1
0 0.00 Seconds
1 1.75 Seconds
2 3.50 Seconds
3 5.25 Seconds
4 7.00 Seconds

Register 0011 Single or Three Phase trip
Value Trip Setting
0 Single Phase Trip
Any other Three Phase Trip


Register 0012 Transformer ratio and option flags:
Most significant byte reads 0x00, low significant byte according to table below.

Bit Interpretation
1 0 CT ratio 500:1 Read only
2 0 CT ratio 1000:1 Read only
3 1 Block All Trips/ 0 Enable All Trips Read / Write
4 0 Enable Block all trips Read only
5 0 CT Correction Old Read only
6 0 CT Correction New Read only
7 Read 1 Read only
8 0 Block Ground Fault trip Read only

Register 0014 The Unit Address
Most significant byte is reserved, low significant byte according to table below.





































































Value Address
0 1
1 2
2 3
3 4
4 5
5 6
6 7
7 8
8 9
9 10
10 11
11 12
12 13
13 14
14 15
15 16


Page 50 GWI 523-375 Rev. 1
A.4 Modbus Function Code 04 Load Currents and Cause of Trip

Function Code: 04
Start address: 0000
Number of registers: 6










A.4.1 Interpretation of Load Currents and Cause of Trip

Registers 0000, 0001, 0002, 0003, 0005 Load Currents
The binary values of currents (fault/load) represent the current in Amps in the primary circuit. The
value is scaled according to the Min Trip setting and ratio of the transformer.

Register 0004 Cause of the Last Trip

Value Cause
0x00 Ground Fault
0x01 Phase C
0x02 Phase B
0x03 Phase A
0x05 Phase C - instantaneous
0x06 Phase B - instantaneous
0x07 Phase A - instantaneous
0x21 Phase C Current over the dynamic range of 20
0x22 Phase B Current over the dynamic range of 20
0x23 Phase A Current over the dynamic range of 20
0x08 Manual/Remote
0xFF Memory clear

A.5 Exception Definitions

The control has implemented the following exception codes:

1. Illegal function - code 01. The message function received is not an allowable action.
This message is sent if the Type 3 received any request other than implemented functions (code 3,
code 4, and code6).

2. Illegal data address - code 02. The address referenced in the address field is not valid.
The control will respond with this message if the register address is not implemented.

3. Illegal data value - code 03. The value referenced in the data field is not valid.
If a CRC error is detecting, the control will not respond.

The implementation of the communication driver does not support parity bit checking.
If the waiting time between two characters is longer than 32.5 milliseconds the message will be ignored
and no response will be send.

Register Parameter
0000 Neutral Current
0001 Load Current Phase C
0002 Load Current Phase B
0003 Load Current Phase A
0004 Cause of the Last Trip
0005 Fault Current of the Last Trip


Page 51 GWI 523-375 Rev. 1
Appendix B: Sequence of Events Format

Event Number: 01-16
Date and Time of Trip: (yyyy-mm-dd hh:mm:ss)
Cause of Trip: Phase A Minimum Trip, Phase B Minimum Trip, Phase C Minimum Trip, Phase N Minimum Trip,
Remote Trip, Phase A Instant, Phase B Instant, Phase C Instant
Amount of Fault Current:
A Phase = XX Amps, B Phase = XX Amps, C Phase = XX Amps, Calculated Neutral = XX Amps
Elapsed Fault Current Time: XX msec
A Phase = 0 msec, B Phase = 0 msec, C Phase = 0 msec, Calculated Neutral = 0 msec
Time Control Powered prior to trip: XX Days, YY Hours, ZZ Minutes, AA Seconds, BB msec
Last recorded Load Current prior to Fault Condition:
A Phase = XX Amps, B Phase = XX Amps, C Phase = XX Amps, Calculated Neutral = XX Amps
Setting at time of Trip:
Minimum Trip Phase A: X A (13A Fuse)
Minimum Trip Phase B: X A (13A Fuse)
Minimum Trip Phase C: X A (13A Fuse)
Phase Instant: x X
Phase Time Delay: X sec
Phase Minimum Response: X sec
Phase Inrush Multiplier: X
Phase Inrush Time Delay: X sec
Ground Fault Minimum Trip: x X

Control Specific Information
Device ID: XXXXXXXXXXXXXX
Feeder Name: XXXXXXXXXXX
Other: XXXXXXXXXXXX
Active Group: Protection
Settings Type: 3-Phase EZset
Firmware-01 v1.08

Trip Solenoid Activated
1
: A=X.X V B=X.X V C=X.X V
Trip Capacitor Voltage
2
: A=X.X V B=X.X V C=X.X V
Control Power Status
3
: X.X V
Temperature of Control at time of Trip: X C











1
If Trip Solenoid Activated is 6.5V or above, the trip signal was properly activated and sent to the switch. If the
value is below 6.5V, the trip signal was not properly activated. Contact G&W Technical Support for assistance.
2
If Trip Capacitor Voltage is 6.5V or above, the trip capacitor was fully charged and able to send a trip signal to the
switch. If this value is below 6.5V, contact G&W Technical Support for assistance
3
If the control power status is greater than or equal to 6.8V, the control is fully powered.


Page 52 GWI 523-375 Rev. 1
Appendix C: Print Format



























Page 53 GWI 523-375 Rev. 1
Appendix D: Factory Default Settings



Device ID: Blank Feeder Name: Blank Other: Blank
Protection Settings:
Trip Mode: 3 Phase
Phase TCC Selection: Fuse, E Speed Slow, Time Dial: None
Phase Minimum Trip: 500:1 CTs: 15 Amps (7A Fuse)
1000:1 CTs: 30 Amps (13A Fuse)
Phase Time Modifiers:
Phase Instant: OFF
Time Delay: 0.0 Seconds
Minimum Response: OFF
Phase Inrush Modifiers:
Inrush Multiplier: x1
Inrush Active Timer: 0.00 Seconds
Ground Fault Settings:
Ground Fault TCC Selection: Fuse, E Speed Slow, Time Dial: None
GF Minimum Trip: OFF

S-ar putea să vă placă și