M.K. Ince and Associates Ltd. Appendix APPENDIX A TRANSFORMER SPECIFICATIONS s Transformer Specification 34.5 kV, BIL 150 kV, Loop Feed for SWT 2.3 MW ____________________________________________________________________________
Wind Turbine Transformer Specification 34.5 kV, BIL 150 kV Pad-Mounted Loop Feed, Dead Front, ANSI/IEEE C57.12
Three phase Pad-Mounted transformer Type Liquid filled Nominal Power . 2600 kVA Wind. Temperature rise . 65 K High voltage . 34.5 kV High voltage DETC . +/- 2 x 2.5% High voltage BIL Accessories150 kV Low voltage .. .0.69 kV Frequency .... .60 Hz Enclosure protection NEMA 3R Transformer impedance .. 6% Load Current Harmonic Factor.5% max Over-excitation . volts/Hz 5% No load loss .. 2.46 kW Load loss .. 15.63 kW Manufacturer Siemens
Transformer monitoring Top oil temperature . dial type without contacts
Oil level indicator . dial type without contacts Pressure relive valve .. without contacts
Transformer cooling Cooling system ONAN Liquid . Mineral oil ASTM D3487 - Type II
Weights and dimensions (approximate) Oil ... 1100 l (290 Gal) Total weight .. 6760 kg (14903 lb) Height .1900 mm (75 in) Length ... 2600 mm (102 in) Width 2600 mm (102 in)
Service conditions Max. ambient temperature40C Average temperature.30C Lower ambient temperature.-40C Altitude.1000 m (3300 ft) Outdoor operation Step-up operation Seismic conditions zone III
Transformer grounding Star point solidly grounded
Angular displacement Vector group . Dyn11 ANSI/IEEE angular displacement is 30 with the LV lagging the HV.
Transformer disconnection Under oil two position load break switch, manually operated. Current rating (continuous) 300 A BIL 150 kV.
HV Protection Partial Range Current Limiting Fuse in series with oil immersed Weak Link Expulsion Fuse on the HV side.
Interface HV grid Feeder arrangement Loop Feed Point of connection .. 600A, 35kV integral loadbreak bushing type (elbows not included)
Interface LV LV connector . NEMA 6H spade type
Surface protection Protection epoxy primer+ coating + finish (total > 155 microns) Color .... pad-mount green RAL6002 (similar to Munsell olive green, 7GY 3.29/1.5) 1 s Transformer Specification 34.5 kV, BIL 150 kV, Loop Feed for SWT 2.3 MW ____________________________________________________________________________
Standard accessories 1. De-energized Tap Changer 2. Loadbreak switch_two positions 3. Integral Dead Break Bushing Type 4. Low Voltage Bushing 5. Oil Level Indicator 6. Oil temperature indicator 7. Pressure Relief Valve 8 Drain Valve with Sampler
Optional Features: Cooling . KNAN cooling (high fire point silicone or ester fluid) Vector group Dyn11 or other Frequency ... 50 Hz Paint . special colors Service conditions . special ambient temperature Service conditions . altitude > 1000 m Service conditions.. seismic zone IV Special accessories please contact Siemens