Sunteți pe pagina 1din 12

DAERYUK Co., Ltd.

1
ATSAuto Transfer Switch

Automatic Transfer Switch ATS
Function of ATS Auto Changer 2
Specification of M-Type 3 ~8
Specification of T-Type 9 ~11
DAERYUK Co., Lt d.

ATSAuto Transfer Switch














Item Description
Manual select Manual select switch is used to transfer AST to the normal power on manual mode.
Timer On auto mode, Timer is used to set the transfer time from the emergency power to the normal
power, up to 30 seconds, when the normal power is recovered.
Timer lamp This time lamp is flickering when the transfer (from emergency to normal) is completed.
Also, it means the setting value of timer is passed when Timer is set.
Power Normal power indication lamp
ATS position It shows that ATS is located on the normal power position if this lamp is on.
Manual It shows the manual mode is selected. It is flickering when ATS is transferred by manual select
switch.
Auto It shows the auto mode is selected. It is flickering when it is automatically transferred after time
setting value.
ATS position It shows that ATS is located on the emergency power position if this lamp is on.
Power Emergency power indication lamp
Timer lamp It is flickering when the transfer (from normal to emergency) is completed after the time setting
value.
Timer On auto mode, Timer is used to set the transfer time from the normal power to the emergency
power, up to 30 seconds, when the normal power is off.
Manual select Manual select switch is used to transfer AST to the emergency power on manual mode.
Auto/ Manual Auto/ Manual switch is used to select Auto mode or Manual mode.








ATSAuto Transfer Switch
A1, A2: Normal power
B1, B2: Emergency power
Aa, Ba: Auxiliary contact
DAERYUK Co., Ltd. 2

ATSAuto Transfer Switch
M-Type: Specification and inner circuit


Features

1. Compact size enables to reduce the size
of control panel.
2. One-coil, one-moving contact, one-arc
chamber
>>Easy maintenance
3. First-input After-trip system enables to
protect the main contact.









Specification

DR
64/66
DR
68
DR
610
DR
612
DR
616
DR
620
DR
625
DR
632
DR
640
Rated voltage AC 690V and DC 125V
Rated current 400 600 800 1000 1200 1600 2000 2500 3200 4000
Connection (Back)
Number of poles 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P
Weight(kg) 36 41 38 50 44 52 47 57 55 68 63 73 87 105 96 120 170 210
Opening time 0.09 sec
Change-over Time 0.12 sec
AC 110V 10 10 10 12 16 20 20 20 24 24 36 40 60 60 80 80 80 80
AC 220V 5 5 5 6 8 10 10 10 12 18 20 30 30 30 40 40 40 40
Operating
current
DC 110V 10 10 10 12 16 20 20 20 24 24 36 40 60 60 80 80 80 80


Inner circuit Index












A1-A2: Power Terminal
B1-B2: Power Terminal
P: DC Power Terminal
N: DC Power Terminal
C1-C2: Input signal
D : Rectifier
Xb: Input-control swtich
Aux: Auxiliary switch
Aa : Contact of A
power input
Ba: Contact of B power
input

DAERYUK Co., Ltd. 3

ATSAuto Transfer Switch
External control circuit (AC, DC)


- Control Power AC Index











A1-A2: Power Terminal
B1-B2: Power Terminal
C1-C2: Input signal
Note : Please refer to this drawing when you configure the circuit for the stable operation.




- Control Power DC Index
27T: Relay for 27X
operation signal
delay.
27X: Relay for A power
operation.
84T: Relay for 84X
operation signal
delay.
84X: Relay for B power
operation.
C/S: Manual select switch
Auto/Manu: Auto/
Manual select switch



P, N: Power control terminal C1: Operation signal terminal for A-power C2: Operation signal terminal for B-Power
Note) Please refer to this drawing when you configure the circuit for the stable operation.








Caution
1. Please use thickness of power cable more than 2mm up to ATS 2500A
3.5mm from ATS 2500A.
And, use the cable on the power terminal for DC control power.
2. In manual operation, please select the manual mode first and use the manual operation handle.

DAERYUK Co., Ltd. 4

ATSAuto Transfer Switch
Parts & Dimensions






































Type 64M 66M 68M 610M 612M 616M 620M 625M
X1 465 510 540 620 695 760
X2 425 470 500 580 655 720
X3 235 242.5 250 257.5 270 284
Y1 260 270
Y2 220 230
Y3 74.5 73.5 78
H 260
T 15 20 25
P 75 90 100 130 155 175
mm
Type Wa Wb Wc Wn L T Y
64M 30 10 75 11
66M 30 10 75 11
68M 40 10 75 11
610M 45 12 75 13
612M 55 12 75 13
616M 75 40 12 75 13
620M 100 53 12 75 13
625M 120 40 15 75 14
- 3P 64M ~ 625M
- Dimensions
Unit: mm
Control circuit terminal
Insert hall for Manual
handle
A power indication
B power indication
Aux switch
Input terminal of A power
Output terminal of load
Input terminal of B power
- Bus bar
DAERYUK Co., Ltd. 5

ATSAuto Transfer Switch







































Type 64M 66M 68M 610M 612M 616M 620M 625M
X1 540 585 620 705 785 860
X2 500 545 580 665 745 820
X3 235 242.5 250 257.5 270 284
Y1 260 270
Y2 220 230
Y3 74.5 73.5 78
H 260
T 15 20 25
P1 75 90 100 130 155 175
P2 75 82 87 102 117 132
Type Wa Wb Wc Wn L T Y
64M 30 30 10 75 11
66M 30 30 10 75 11
68M 40 30 10 75 11
610M 45 30 12 75 13
612M 55 30 12 75 13
616M 75 40 40 12 75 13
620M 100 45 53 12 75 13
625M 120 55 40 15 75 14
- 4P 64M ~ 625M
Unit: mm
Control circuit terminal
Insert hall for Manual
handle
A power indication
B power indication
Aux switch
Input terminal of A power
Output terminal of load
Input terminal of B power
- 4P 64M ~ 625M: Dimension
Unit: mm
- Bus bar
Unit: mm
DAERYUK Co., Ltd. 6

ATSAuto Transfer Switch


- 3P 632M

















Unit: mm

- 4P 632M


















Unit: mm
DAERYUK Co., Ltd. 7

ATSAuto Transfer Switch


- 3P 640M

















Unit: mm


- 4P 640M


















Unit: mm
DAERYUK Co., Ltd. 8

ATSAuto Transfer Switch
T-Type: Specification and inner circuit



















DR 61T DR 62T DR 64T
Rated voltage AC 690V and DC 125V
Rated current 100 200 400
Connection Front, Back
Number of poles 2P 3P 4P 2P 3P 4P 2P 3P 4P
Weight(kg) 5 6 7.5 6 8 10 11 14 17
Opening time 0.06 sec
Change-over Time 0.08 sec
AC 110V/ 220V 16
AC 220V/ 220V 8
Operati
ng
current
DC 110V 16
Features
1. The protection function of wrong
operation.
- designed to move the center of control
part automatically.
2. Excellent open-close performance.
- minimizes the arc generation.
- Increases the life cycle.
3. Easy use and maintenance
4. Compact and light design
- Easy to maintenance and installation.

Specification
DAERYUK Co., Ltd. 9

ATSAuto Transfer Switch
External control circuit (AC, DC)

































X1 X2

2P 3P 4P 2P 3P 4P
X3 X4 X5 Y1 Y2 Y3 Y4 Y5 W1 W1-T W2 W2-T 1 2
DR 61T
DR 62T
250 290 330 230 270 310 160 40 40 250 305 330 20 5 5
DR 64T 270 320 360 250 300 340 165 50 45
220 185
260 315 340 30 7
20 5
7
9
- Inner circuit
- Index
Control circuit terminal
Insert hall for Manual handle
A power indication
B power indication
Aux switch
Input terminal of A power
Output terminal of load
Input terminal of B power
- Dimensions
A power indication B power indication
Insert hall for manual handle
Control terminal Input terminal of A power
Input terminal of B power Load terminal(output)
DAERYUK Co., Ltd. 10

ATSAuto Transfer Switch


- Control power: AC

















- Control power: DC




















- Index
A2: Control terminal of A power A1: Operation signal terminal of A power
B2: Control terminal of B power B1: Operation signal terminal of B power
27T: Relay for 27X operation signal delay 27X: Relay for A power operation
84T: Relay for 84X operation signal delay 84X: Relay for B power operation
C/ S: Manual select switch Auto/ Manu: Auto/ Manual select switch
DAERYUK Co., Ltd. 11

DAERYUK Co., Ltd. 12
ATSAuto Transfer Switch

MEMO


Head Office:
#530 Samkye-Ri, Phokog-Eup, Cheoin-Gu, Yongin-City, Gyeonggi-Do, Korea
Tel: +82-31-334-3371 Fax: +82-31-334-3374
Sales Office:
#430-4 Ohsung Bldg. 1F, Bangae2-Dong Seocho-Ku Seoul, Korea
Tel: +82-2-588-7154 Fax: +82-2-588-7159
Website: www.e-daco.net