GE Energy Generator Protection These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes the matter should be referred to the GE Company. 2006 General Electric Company GEK 75512k Generator Protection TABLE OF CONTENTS I. INTRODUCTION.......................................................................................................................... 3 A. Standards .................................................................................................................................. 3 B. Protection Responsibility ......................................................................................................... 3 C. Protection Equipment............................................................................................................... 4 II. RELATIONSHIP BETWEEN OPERATION, PROTECTION AND ALARMS .................... 5 A. Operation and Protection.......................................................................................................... 5 B. Protection and Alarms.............................................................................................................. 5 III. ALARMS ........................................................................................................................................ 5 IV. PROTECTION WHEN GENERATOR IS OFF LINE.............................................................. 6 V. TRIPPING METHODS................................................................................................................. 9 A. Protective Actions for Generator Faults................................................................................... 9 VI. PROTECTION RECOMMENDATIONS ................................................................................... 11 A. Discussion and Recommendations for Generator Faults ......................................................... 11 LIST OF FIGURES Figure 1. ................................................................................................................................................ 16 LIST OF TABLES Table 1. ALARMS................................................................................................................................. 6 Table2.SUMMARYOFGENERATORPROTECTIONRECOMMENDATIONS........................... 32 2 Generator Protection GEK 75512k I. INTRODUCTION This instruction book insert was prepared to provide a summary of General Electric's recommendations for protection of its cylindrical rotor synchronous generators. Since a wide variety of technology is applied to machines of various size and rating, not all of the alarm and protection recommendations are applicable for a given generator design. For example, references to hydrogen and stator water cooling systems are not applicable to air cooled machines. The alarm and protection sections are sequenced so that recommenda- tions which are generally applicable appear first, ones related to hydrogen systems next, and finally stator water cooling system alarms and protection. Recommendations for excitation system protection are not included, but are covered in separate instructions. This instruction book discusses the kinds of protection that are desirable, and the action that is believed to be best for the needed protection. Specific relays and relay circuits are not discussed. A. Standards General Electric turbine-generators are designed and built to meet or surpass applicable industry ac- cepted standards. For the cylindrical rotor synchronous generators covered by these instructions, these standards are: 1. ANSI C50.10 General Requirements for Synchronous Machines 2. ANSI C50.13 Requirements for Cylindrical Rotor Synchronous Generator 3. ANSI C50.14 Requirements for Cylindrical Rotor Synchronous Generators 4. ANSI C50.15 Requirements for Gas Turbine Driven Synchronous Machines 5. CEI/IEC 34-1 Rotating Electrical Machines - Rating and Performance 6. CEI/IEC 34-3 Rotating Electrical Machines - Specific requirements for turbine-type synchronous machines B. Protection Responsibility There are IEEE Standards covering generator protection which provide guidance material on generator protective relaying. These include: 1. ANSI/IEEE C37.101 IEEE Guide for Generator Ground Protection 2. ANSI/IEEE C37.102 IEEE Guide for AC Generator Protection 3. ANSI/IEEE C37.106 IEEE Guide for Abnormal Frequency Protection for Power Generating Plants 3 GEK 75512k Generator Protection There are two IEEE Press Books which provide a useful anthology of the background material related to generator protection. These are: 1. IEEE Press Book - Protective Relaying for Power Systems: Volume 1, 1980 2. IEEE Press Book - Protective Relaying for Power Systems: Volume 2, 1992. Another useful reference is the IEEE Buff Book from the color series - ANSI/IEEE Std 242 - Protection and Coordination of Industrial and Commercial Power Systems. The operating limits specified by the manufacturer may be inadvertently exceeded for a number of reasons. These include, among others: internal generator failure auxiliary equipment failure operator error abnormal system conditions The protection methods and equipment in place should be able to safely protect the generator no matter which of these circumstances, or combination of them, causes the abnormal operation. Since protective relays and other devices are not immune to failure, it is recommended that considera- tion be given to providing back-up protection for those faults where a device failure could subject the generator to serious damage. Generator protection is a large and complex subject. These instructions were written to provide infor- mation on protection, based on our experience as designers and manufacturers, that may not always be readily available in other forms. The recommendations contained in these instructions are based on the best available information at the time of publication. Changes in the state of the art may result in modification of these recommenda- tions. Such modifications will usually be communicated to all owners of affected turbine-generators throughGeneralElectric,TechnicalInformationLetter(TIL)series. These modifications will be incorporatedinperiodicrevisionstotheseinstructions. C. Protection Equipment It should not be assumed that any required hardware is part of the turbine-generator supplied, although in certain cases some protection is due to special requirements or it is integrated into the excitation or control system. In either case, it is the owner's or his designate's responsibility to check, adjust, calibrate and connect all protective equipment to suitable tripping relays or circuits in order to provide the intended protection. The manufacture should be consulted for specific protection application issues or concerns. 4 Generator Protection GEK 75512k II. RELATIONSHIP BETWEEN OPERATION, PROTECTION AND ALARMS A. Operation and Protection The line between generator operation and protection is not always clear and there is inevitably an area of overlap. These instructions cover those functions that are mainly performed by protective relaying or similar devices or functions. A companion instruction (Ref. 1) covers those aspects of generator operation that are mainly under control of an operator and/or electronic turbine-generator controller. Both of these publications should be consulted during plant design and should be used in conjunction with other parts of the instruction book for proper operation of the turbine-generator. B. Protection and Alarms Those protective relays or devices that trip the generator should alert an operator as to the cause of any trip, and be able to take direct action if this should prove necessary. In addition to the tripping relays there are other relays or devices that initiate only an alarm or data logging. In these cases it becomes an operator's responsibility to decide what corrective action is required and to take it. III. ALARMS Many of the alarm only devices are for temperature measurement. These are Resistance Temperature Detectors (RTDs) and Thermocouples (TCs). Some measure other variables such as hydrogen pressure and purity, and stator cooling water pressure, flow and conductivity (if applicable). A typical list of alarm devices furnished with the generator is given in Table 1, including recommended alarm points and signal ranges. If additional special instrumentation is supplied, alarm settings will be specified in the appropriate section of the instruction book. Table 1 contains information which may be useful when specifying signal monitoring or recording equip- ment. The table also includes typical ranges of the variable for each of the devices shown. These ranges do not represent the actual capabilities of the generator or its auxiliary equipment and should not be used in any way as a guide for operation. When a protective device or function signals a trip, or when the operator trips the unit because of an alarm or other indication of malfunction, it is most important that the cause of the problem be determined and corrected before attempting to restart or resynchronize. Failure to do so may lead to more serious troubles. IV. PROTECTION WHEN GENERATOR IS OFF LINE The need for protecting a generator while on line is well known, but the need when off line may not be as well understood. Nevertheless, there are circumstances under which a generator could be damaged while off line. For this reason, it is recommended that, as a general rule, all alarms and protections be kept operative at all times. Exceptions to this rule are those protections which would mis-operate or give false signals when the unit is below rated speed, not excited, or not synchronized. Relaying and interlocking circuitry that operates when the unit is off line should be reviewed to make certain it does not inadvertently incapacitate any essential protection. 5 GEK 75512k Generator Protection Table 1. ALARMS SIGNAL DEVICE RANGE SETTING NOTES MACHINE TEMPERATURES GENERATOR WITH BRUSHLESS EXCITER BRUSHLESS EXCITER RTD -20 to 80C Generator Cold Gas +40C Check Ventilation GENERATOR WITH STATIC EXCITATION COLLECTOR AIR IN RTD or TC -30 to 70C 45C In: Check Filters COLLECTOR AIR OUT RTD or TC -20 to 80C AIR IN + 20C Out: Check Ventilation GENERATOR FIELD TRANSDUCER 0 to 150C Reduce field current by adj. MVAR load. STATOR COIL (SLOT) RTD 0 to 100C for H 2 O See Ref. 2 0 to 150C for H 2 and Air OTHER ALARMS BEARING VIBRATION VIBRATION DETECTOR --- --- See Recommendation in this publication. BEARING OIL TEMP HIGH - --- --- See Turbine Section of Instruction Book NEGATIVE SEQUENCE CURRENT RELAY --- --- Balance or reduce load. See Recommendation for Unbalanced Armature Currents. GENERATOR OVERVOLTAGE RELAY --- Over 1.05 pu voltage Reduce machine voltage. AIR COOLING (if applicable) COLD AIR RTD -30 to 70C HOT AIR RTD -10 to 90C LOCAL OVERHEATING (if applicable) CORE MONITOR LEVEL (if applicable) CORE MONITOR --- --- See Recommend. for Local Overheating. MACHINE HEATING (if applicable) SIGNAL VALIDATION DEVICE --- --- See Recommend. for Local Overheating. @From operating pressure Two switches 6 Generator Protection GEK 75512k Table 1. ALARMS (Cont'd) SIGNAL DEVICE RANGE SETTING NOTES SEAL OIL SYSTEM (if applic.) DIFF SEAL OIL PRESSURE LOW DIFF. PRESSURE SWITCH --- 3 psid [20.7 kPa] [211 g/cm 2 ] See Ref. 3 DRAIN ENLARGEMENT LIQUID DETECTOR FULL LIQUID LEVEL DETECTOR --- See Ref. 3 EMERGENCY PUMP RUNNING RELAY --- See Ref. 3 FILTER DIFF. PRESSURE HIGH (if applicable) DIFF. PRESSURE SWITCH 10 psid [69 kPa (differential)] [703 g/cm 2 (diff.)] See Ref. 3 VACUUM TANK OIL LEVEL HIGH/LOW (if applicable) FLOAT SWITCH --- +4/-6 in [+102/-152 mm] See Ref. 3 MAIN PUMP MOTOR OVERLOAD (if applicable) THERMOSTAT --- See Ref. 2 EMERGENCY PUMP MOTOR OVERLOAD (if applicable) THERMOSTAT --- See Ref 2 HYDROGEN GAS SYSTEM COOLER HOT GAS TEMP HIGH RTD or TC 0100C COOLER COLD GAS TEMP HIGH/LOW RTD or TC 070C COMMON COLD GAS TEMP HIGH (if applicable) RTD 070C MACHINE GAS TEMP HIGH METER RELAY 0100C See Ref. 4 MACHINE GAS PRESSURE HIGH/LOW PRESSURE SWITCH --- +4/-2 psi @ [+27.6/-13.8 kPa] [+281/-14.1 g/cm 2 ] See Ref. 4 MACHINE GAS PURITY LOW METER RELAY or TRANSMITTER 50100C 0100C 90% See Ref. 4 GENERATOR CASING LIQUID DETECTOR FULL LIQUID DETECTOR --- See Ref. 4 Two switches @From operating pressure 7 GEK 75512k Generator Protection Table 1. ALARMS (Cont'd) SIGNAL DEVICE RANGE SETTING NOTES STATOR COOLING WATER SYSTEM (if applicable) INLET TEMP HIGH RTD or TC 070C 2C OVER MAX. See Ref. 2 INLET FLOW LOW FLOW SWITCH See Ref. 3 INLET PRESSURE LOW PRESSURE SWITCH See Ref. 3 LIQUID HEADER OUTLET TEMP HIGH TC 0100C See Ref. 3 BULK WATER OUTLET TEMP HIGH RTD 0100C See Ref. 2 CONN RING TEMP HIGH (if separately cooled) TC 0100C See Ref. 2 CONN RING FLOW LOW (if separately cooled) FLOWMETER See Ref. 3 HV BUSHING OUTLET TEMP HIGH TC 0100C See Ref. 2 HV BUSHING FLOW LOW FLOWMETER 3 gpm LOW [189 ml/s] See Ref. 3 MAIN FILTER DIFF PRESSURE HIGH DIFF PRESSURE SWITCH 015 psid [0103 kPa (differential)] [01.05 kg/cm 2 (diff.)] 8 psid [55 kPa (differential)] [562 g/cm 2 (diff.)] Change filter before 7 psid [48 kPa (diff.)] [492 g/cm 2 (diff.)] CONDUCTIVITY HIGH TRANSDUCER 010 mho/cm [010 S/cm] 0.5 & 9.9 mho/cm [0.5 & 9.9 S/cm] Change resin on first alarm. Trip manually on second alarm TANK LEVEL HIGH/LOW FLOAT SWITCH --- +4/-4 inches [+102/-102 mm] Check main pump RESERVE PUMP RUNNING PRESSURE SWITCH 0150 psi [01.03 MPa] [010.5 kg/cm 2 ] 10 & 20 psi below normal [69 & 138 kPa][0.7 & 1.41 kg/cm 2 ] Check cause and correct RUNBACK INITIATED RELAY NONE PRESET Two switches @From operating pressure 8 Generator Protection GEK 75512k V. TRIPPING METHODS There are a number of ways a turbine-generator, or a generator alone, may be tripped, i.e., disconnected from the system or shut down. Some of the factors that should be considered in determining what type of trip to use for each fault requiring one are: severity of fault to generator probability of fault spreading amount of overspeed resulting probability of high overspeed importance of removing excitation need for maintaining auxiliary power need for shutting down the unit time required to resynchronize effect on the power system In recognition of the factors above, the manufacturer recommends an action that insures protection of the generator. Unless otherwise noted, a protective action with a lower number than the recommended action is allowable (see Table II). Although the lower number protective action may provide faster protection, addi- tional danger to the turbine is incurred. These dangers include higher overspeed and worse turbine thermal shock duty. The recommended protective actions are selected based on the manufactures judgement with regard to providing acceptable generator protection, while minimizing unnecessarily harsh turbine duty. The owner should select the action to be used based on the importance of the applicable factors in his case. A. Protective Actions for Generator Faults 1. Simultaneous trip - trips the turbine valves closed, opens generator line breakers and removes excitation simultaneously, as with a lock-out relay. A simultaneous trip is acceptable for all gen- erator faults, and generally provides the highest degree of protection for the turbine-generator although it does permit a small overspeed and there is a slight probability of high overspeed. 2. Generator trip - opens the generator line breakers and removes excitation simultaneously, but leaves the turbine running near rated speed. Where maintaining speed is not harmful, this provides as high a degree of protection for the generator as a simultaneous trip (Type 1). If the plant can operate following a full load rejection, and if the cause of the trip can be identified and rectified quickly, it may make resynchronization possible in a shorter time than Type 1. Since it does result in a higher overspeed than Type 1, it should only be used when there is an advantage in not tripping the turbine. 3. Breaker trip - trips all generator line breakers but not the excitation or the turbine. This trip has advantages similar to the generator trip when the fault permits excitation to remain applied. Its advantage over Type 2 is that it provides auxiliary power in cases where this cannot be switched to another bus. If this is not an advantage, Types 2 or 1 should be used. 9 GEK 75512k Generator Protection 4. Sequential trip - trips the turbine first. When the turbine inlet valve limit switches indicate the valves are closed, and the recommended reverse power relay (or function) operates, normally after a three-second delay, the generator line breakers are tripped. Opening of the breakers then trips excitation. This trip should prevent any overspeed and thus is preferred whenever the risk from a three-second delay in tripping the generator is slight. It is also preferred for most faults in the turbine or steam generator. Its disadvantage is that certain multiple limit-switch failures, or a reverse power relay failure, would prevent completing the trip. Although this probability is small, a second reverse power relay, with a 10 to 30 second time delay, connected to produce a Type 1 simultaneous trip, is recommended as a back-up. This back-up relay also serves as the primary protection for motoring which does not occur as part of a sequential trip. 5. Manual trip - turbine is tripped manually. When generator power reverses, reverse power relay trips generator line breakers. Breaker opening trips excitation. This trip is recommended when- ever an operator sees the need for a fault trip and is not certain that a runback and trip (Type 6) will be fast enough. Note that Type 5 is actually a manually initiated sequential trip. NOTE There are no cases for which manually tripping the generator breakers is recom- mended. This is because the generator breakers should not normally be tripped until after the turbine has been tripped and power has reversed. Then the gener- ator breakers should be automatically tripped by the reverse power relay. A pro- tected bypass switch may be used to permit manually tripping the generator alone in case of limit-switch or reverse power relay failure. A manual generator breaker trip should only be used with full recognition of the risk involved. 6. Manual runback and trip - manually decreases turbine output to low level or to zero, followed by the turbine (sequential) trip. This is the normal trip, which is preferred for all normal shut- downs. It is also recommended for trips required by alarms when the operator judges a Type 5 manual trip is not essential. 7. Automatic runback - reduces load (via turbine control) at a preset rate to a preset load. It is recommended here only for loss of stator coolant (if required). It is an alternative to tripping the unit, and permits continuing on line at a very low load. When it can be used, it has the advantage of enabling earlier return to full load if the trouble can be quickly corrected. 8. Manual runback - manually reduces load at a rate and to a level determined by operator. This is useful for some faults which may be load sensitive, such as local overheating, and where there is no need to trip immediately. It also allows the generator to continue to supply reactive power to the system. The recommendations in these instructions are intended to provide the best balanced protection for the turbine-generator for generator faults. Unusual circumstances or other plant limitations must be considered by the owner, and may require different actions. Turbine problems should be handled in accordance with applicable turbine instructions. 10 Generator Protection GEK 75512k VI. PROTECTION RECOMMENDATIONS The remainder of this instruction book comprises discussions of, and detailed recommendations for, each of the faults listed in the table of contents, and summarized in Table II. References are listed at the end of the book. A. Discussion and Recommendations for Generator Faults 1. Stator Overcurrent 1. Description Generators are designed to operate continuously at rated kVA, frequency and power factor over a range of 95 to 105% of rated voltage. Operation beyond rated kVA may result in harmful stator overcurrent. Note that at rated kVA, 95% voltage, stator current will be 105%. This is permissible. Normally, generator load is under the control of an operator. Situations can arise during sys- tem disturbances, such as accompanying generator or line tripouts, which can result in an overcurrent condition. For short times, it is permissible to exceed the current corresponding to rated kVA. This ca- pability is specified in ANSI Standard C50.13 as follows: Time (seconds) 10 30 60 120 Armature current (percent) 226 154 130 116 2. Detection Stator current should be monitored by an operator, and kept within rated value by adjustment of the turbine-generator controls. A consequence of overcurrent is stator winding overheating, which should be detected by winding temperature detectors, usually TCs measuring stator cooling water temperature, and/or RTD's in slots with the stator winding (if applicable). All functioning TCs and RTDs should be continuously monitored and alarmed (see Ref. 1, and 2&3 for H 2 0 cooled machines). However, even though it may not result in excessive stator winding temperatures, operating above specified currents is not an acceptable practice since unmonitored phe- nomena, such as temperatures in other parts of the stator circuit, winding forces, abnormal magnetic fields, etc., may become excessive. 3. Recommendation Automatic tripping is not provided for protection against stator overcurrent. However, all operators should be made aware of the importance of operating the generator within its rated capability. In cases when a generator will operate in an unattended station, some form of overcurrent (overload) protection should be provided. An alternative is stator overtempera- ture which provides similar protection. For additional information, see Ref. 1. 11 GEK 75512k Generator Protection 2. Stator Ground Fault 1. Description The generator stator neutral normally operates at a potential close to ground, generally through a high impedance grounding transformer/resistor. In some cases a reactor is used in a resonant grounding arrangement. Should a phase winding or any equipment connected to it fault to ground, the normally low neutral voltage could rise as high as line-to-neutral voltage, depending on fault location. Although a single ground fault will not necessarily cause immediate damage, the presence of one increases the probability of a second. This is because the occurrence of such a fault is probably the result of damage which is not confined to one spot. In fact, the existence of a ground fault through tough, high-voltage insulation is usually a result of another, potentially catastrophic, trouble. Asecond fault, even if detected by differential relays, may cause serious damage. Asecond fault in the same phase will not be detected by differential relays, and could cause serious damage as a result. 2. Detection The usual method of detection is by a voltage relay across the grounding resistor. A current relay is sometimes used in place of a voltage relay or as a back-up. The relay should be insensitive to third harmonic voltage, but should have as low a pick-up level at line frequency as is practical to reduce the unprotected zone at the neutral end of the windings. Methods are available which are designed to protect the entire winding. These schemes make use of the relationship of third harmonic voltages at the line and neutral terminals of the generator. These schemes supplement the fundamental frequency protection. 3. Recommendations The grounding impedance should limit the ground fault current to less than 25 amperes. The usual criterion based on circuit capacitance will normally result in less than 10 amperes. The stator ground fault relay should be connected to trip the unit within several seconds, using a simultaneous trip, Type 1. For further information, see Ref. 5. 3. Stator Phase-to-Phase Fault 1. Description A stator phase-to-phase fault is any electrical fault between two phases of the armature wind- ing. This type of fault is very serious because very large currents can flow and produce large amounts of damage to the winding if allowed to persist. Because of the nature of the con- struction of the armature it is very likely that this type of fault will grow to include ground, thereby causing significant damage to the stator core. 12 Generator Protection GEK 75512k 2. Detection It is possible to detect a phase-to-phase fault in the winding by means of a differential relay. This method provides protection for the entire winding, and its sensitivity is limited mainly by the degree to which the various current transformers are matched. The differential relay method cannot protect against a fault within one phase of the winding. Such a turn-to-turn fault can only be detected by the resulting armature current unbalance. However, such faults are rare and will usually include ground, in which case they will be detected by the stator ground fault relay. 3. Recommendations Upon detection of a phase-to-phase fault in the winding, it is imperative that the unit be tripped without delay, using a simultaneous (Type 1) trip. 4. Over-Voltage 1. Description Permissible voltage limits under various operating conditions are given in the Generator Op- eration instructions (Ref. 1). It is normally an operator's responsibility to maintain voltage (and the corresponding kVA) within specified limits. With turbine-generators it is unlikely that voltage will depart significantly from the preset value. If it does, due to a regulator failure or a system disturbance, a trip signal will usually be produced by one of the protective relays, such as volts/Hertz or maximum excitation limit. 2. Recommended Action Therefore, specific over-voltage protection is generally not required for the generator. De- pending on the circumstances, it may be desirable to protect other equipment connected to the generator. For unmanned generating stations, consideration should by given to implementing automatic overvoltage protection. For additional information, see Ref. 1. 5. Volts Per Hertz 1. Description Per unit voltage divided by per unit frequency, commonly called volts/Hertz, is a readily measurable quantity that is proportional to flux in the generator and step-up transformer cores. Moderate overfluxing (105%110%) increases core loss, elevating core temperatures for all generator designs and armature temperatures for generators with conventionally cooled stator windings. Long term operation at elevated temperatures can shorten the life of the stator insulation systems. More severe overfluxing (above 110%) further increases core loss, and saturates portions of the core to the point that flux flows out into adjacent structures. The resulting induced voltages can be coupled to stator punchings due to the manner in which cores are assembled and clamped. Severe overfluxing can breakdown interlaminar insulation, followed by rapid local core melting. 13 GEK 75512k Generator Protection Over-volts/Hertz can be caused by regulator failure, load rejection while under control of the dc regulator, or excessive excitation with the generator off line. It can also result from decreasing speed while the ac regulator or the operator attempts to maintain rated stator voltage. 2. Detection Volts per Hertz is calculated in a static circuit incorporated in a volts/Hertz relay or sensor. Timing circuits are also incorporated. The volts/Hertz sensor is normally included as part of the excitation system. 3. Recommendation Even though over-volts/Hertz is more likely to occur when off line, it can also occur when on line. For this reason the volts/Hertz protection should be in operation whenever excitation is applied. Refer to Figure 1 for a graphical representation of the recommended V/Hz protection. In view of the potential consequences it is prudent to provide as conservative protection as possible consistent with security from false tripping. Selection of a modest maximum trip level of above 118%, coupled with a 2 second time delay satisfies these objectives. A load rejection from full rated KVA, rated power factor and 105% of rated voltage will not result in tripping if an automatic voltage regulator is in service. Operation at 118% should be lim- ited not to exceed 45 seconds. The curve shape from 118 to 110% V/Hz approximates the overexcitation capability of many transformers (for stepup and station service power applica- tions). However if the transformers require lower values, the protective relays should be set accordingly. Continuous operation above 105% V/Hz is not sanctioned and an alarm func- tion should be provided to alert the operator that corrective action is needed. The excitation control limiter (if applicable) should be set to prevent continuous operation above 109%. The trip signal should produce a simultaneous trip, Type 1, or a generator trip, Type 2. 6. Field Overexcitation 1. Description The generator field winding is designed to operate continuously at a current equal to that required to produce rated kVA at rated conditions. In addition, higher currents are permitted for short times, to permit field forcing during transient conditions. These limits are specified in terms of a curve of field voltage vs. time defined by the following points in ANSI Standard C50.13-1977: Time (seconds) 10 30 60 120 Field voltage (percent) 208 146 125 112 14 Generator Protection GEK 75512k 2. Detection Most excitation systems now being furnished include a Maximum Excitation Limit function. Its purpose is to prevent prolonged field overcurrent by recalibrating the current regulator, transferring to another regulator, and, finally, producing a trip signal, as required. 3. Recommendation The owner's responsibility with respect to this function is to see that the Maximum Excitation Limit is properly adjusted and maintained, and properly connected to trip the unit when re- quired. Protection Type 4, sequential trip, or Type 1, simultaneous trip, is recommended. For high response exciters, a Type 1 trip may be required to avoid rapid overheating of the field should the exciter stay at ceiling for an extended period of time. In such cases a sequential trip would take too long. Since loss of potential transformer signal to the voltage regulator is one cause of field overcur- rent, relaying to detect this situation and automatic transfer to another regulator is suggested. Sensing and transfer functions are part of most modern excitation systems. 7. Field Ground 1. Description The generator field winding is electrically isolated from ground. Therefore the existence of one ground fault in the winding will usually not damage the rotor. However, the presence of two or more grounds in the winding will cause magnetic and thermal imbalances plus lo- calized heating and damage to the rotor forging or other metallic parts. Unfortunately, the presence of the first ground fault makes detection of a second fault difficult, if not impossi- ble. In addition, modern rotor winding insulation systems have achieved a level of quality that reduces the likelihood of a field ground except under unusual circumstances where the probability of occurrence of a second ground or other serious problem is high. 15 GEK 75512k Generator Protection Figure 1. 2. Detection The relay necessary to detect a field ground is normally supplied with the excitation system. 3. Recommendation It is recommended that the field ground detector be connected to produce a sequential trip, Type 4. Alternatively, a runback, Type 6, or simultaneous trip, Type 1, may be used. 8. Loss of Excitation 1. Description Loss of excitation (or loss of field) results in loss of synchronism and operation of the gen- erator as an induction machine. This will result in the flow of slip frequency currents in the rotor body, wedges, and amortisseur windings (if so equipped), as well as severe torque oscillations in the rotor shaft. The rotor is not designed to sustain such currents, nor is the turbine-generator shaft designed to long withstand the alternating torques. The result can be rotor overheating, coupling slippage and even rotor failure. The length of time before serious damage occurs depends on the generator load at the time of the incident, slip frequency, and whether the field winding is open circuited or shorted, and may be a matter of seconds. 16 Generator Protection GEK 75512k Aloss of excitation normally indicates a problemwith the excitation systemwhich, depending on its nature, could be serious (e.g., collector ring flashover, if so equipped). Because of the VARs absorbed to make up for the low or lost excitation, some systems cannot tolerate the continued operation of a generator without excitation. Consequently, if the generator is not disconnected immediately when it loses excitation, widespread instability may very quickly develop, and major system shut-down may occur. 2. Detection Since loss of excitation results in a marked change in reactive kVA, a loss of excitation relay of the impedance or mho type is usually used (Ref. 6). 3. Recommendation The generator should be tripped from the power system, using a simultaneous trip (Type 1), or a generator trip (Type 2). It is important that all excitation power be removed. It should not be assumed that, since there is loss of excitation, the exciter is not supplying power to an internal fault. 9. Unbalanced Armature Currents 1. Description When the generator is supplying an unbalanced load, the phase currents and terminal volt- ages deviate from the ideal balanced relationship, and a negative phase sequence armature current (I 2 ) is imposed on the generator. The negative sequence current in the armature wind- ing creates a magnetic flux wave in the air gap which rotates in opposition to the rotor at synchronous speed. This flux induces currents in the rotor body iron, wedges, retaining rings and amortisseur windings, if so equipped, at twice the line frequency. Heating occurs in these areas and the resulting temperatures depend upon the level and duration of the unbalanced currents. Under some conditions, it is possible to reach temperatures at which the rotor ma- terials no longer contain the centrifugal forces imposed on them, resulting in serious damage to the turbine-generator set (Ref. 11). There is always some low level unbalance in any power system and therefore limits on the continuous unbalance have been established. For currents above the permissible continuous levels, a limit on the time-integral of I 2 2 has been established for times up to 120 seconds. Such levels will often result from faults, open lines or breaker failures. Unless otherwise specified by the manufacturer as part of the generator design data informa- tion, the negative sequence current limits are given in the applicable standards (Ref 31 or Ref 32), where I 2 is the per unit negative sequence current on the generator base and t is the time in seconds. See Ref 1 for further comments on unbalanced loading capability. 2. Detection The protection scheme should be designed such that it will permit negative sequence currents up to the continuous limit, but produce a trip signal if the level exceeds this value long enough to reach the permissible I 2 2 t limit (Ref 13). 17 GEK 75512k Generator Protection It is also desirable to alert an operator when I 2 exceeds a normal level, which may be lower than the permissible continuous negative sequence current. This enables him to adjust load in order to prevent a trip. Ref. 1 describes in more detail the actions an operator may take. 3. Recommendations A negative sequence relay, similar to that described above, should be used on all units. It should be arranged to cause a breaker trip, Type 3, generator trip, Type 2, or a simultaneous trip, Type 1. 10. Loss of Synchronism 1. Description Loss of synchronism, also referred to as out-of-step operation or pole slipping, can occur as a result of steady-state transient or dynamic instability. It also may occur as a result of loss of excitation or synchronizing errors. 2. Detection The majority of users do not apply specific loss-of-synchronization relaying. However, a skilled relay engineer can adjust impedance relaying to reliably detect loss of synchronism. Loss of excitation relays may provide detection, but cannot be relied upon under all condi- tions. If the electrical center during loss of synchronism is in the transmission system, line relays may detect it. If they do not, specific relaying should be provided. 3. Recommendation Out-of-step operation can result in pulsating torques and winding stresses and high rotor iron currents that are potentially damaging to the generator. Excessive stator winding and core end heating can also result if the out-of-step operation is caused by reduced or lost excitation. Therefore, it is recommended that the generator be separated from the system without delay, preferably during the first slip cycle (Ref. 14, 26, 27.). A breaker trip, Type 3, is recom- mended, and permits the fastest resynchronization after conditions have stabilized. 11. Abnormal Frequency Operation 1. Description For a generator connected to a power system, abnormal frequency operation is a result of a severe system disturbance. An isolated or unconnected unit could operate at low or high frequency due to improper speed control adjustment or misoperation of the speed control. There are two effects to be considered. The generator can tolerate underfrequency operation for long periods, provided load and voltage are sufficiently reduced, as explained in Generator Operation instructions (Ref. 1). The generator can also tolerate overfrequency operation provided voltage is within an accept- able range. 18 Generator Protection GEK 75512k 2. Recommendation For the generator, specific protection for abnormal frequency operation is not required. How- ever, the turbine is very sensitive to abnormal frequencies and recommendations given for it should be carefully studied and followed (Ref. 24, 25). Detection of abnormal frequency operation may also be used to identify system problems. Refer unusual frequency operation questions to the GE company for recommendations. 12. Breaker Failure 1. Description Since most faults involving the generator require tripping of the generator/line breakers, fail- ure of any of them to open properly results in loss of protection and/or other problems, such as motoring. If one or two poles of a generator line breaker fail to open, the result can be a single-phase load on the generator and negative sequence currents on the rotor. 2. Detection Both types of failure described above will cause conditions that may be detected by other pro- tective devices, e.g., reverse power, loss of synchronism or negative sequence relays. How- ever, a more direct method is the use of Breaker Failure Protection (BFP) which is energized when the breaker trip is initiated. After a suitable time interval, if confirmation of breaker tripping in all three lines is not received, a signal is generated. 3. Recommendation Industry past practice has not always recognized the need for breaker failure protection be- cause of the reliability of line breakers. However, it is recommended that BFP be used with all tripping relays that can trip a generator line breaker. The BFP signal should trip all line breakers that can feed current to the generator through the failed breaker (Ref. 15). 13. System Back-Up 1. Description System back-up protection is also known as external fault back-up protection. As this name implies, it is used to protect the generator from supplying short circuit current to a fault in an adjacent system element because of a primary relaying failure (Ref. 15, 16). 2. Detection Either voltage restrained or current restrained inverse-time overcurrent or distance relays may be used, depending on the kind of relaying with which the back-up relays must be selective. Negative sequence relays, in addition to their primary protective role, are sometimes con- sidered for system back-up protection. However, these will not provide protection against balanced faults. 19 GEK 75512k Generator Protection 3. Recommendation System back-up protection is recommended. A breaker trip Type 3 is recommended, which permits the fastest resynchronization after the system fault has been cleared. In Steam tur- bines, if immediate resynchronization is not a priority, a type 1 trip may be considered to trip the turbine, exciter and generator breaker simultaneously. 14. Voltage Surges 1. Description Certain abnormal conditions could occur which might subject the generator to high voltages surges. Among these are: Switching surges from circuit breakers at generator voltage Positive and negative surges arriving simultaneously on two phases Ineffective direct stroke shielding Failure of high side surge protective equipment Accidental connection between high and low side transformer windings, due to internal failure, external flashover or other cause The latter category is not a normal protective function of lowvoltage arrestors and would sub- ject them to excessive duty which could cause their failure. In view of the potential personnel hazard in the event of surge arrestor failure, the user should consider physically isolating the surge arrestor cubicles and limiting access to them. 2. Recommendation To provide protection for these and similar situations, surge arrestors are recommended for all units. Surge capacitors are generally not required for machines with single-turn coils. They are provided on some packaged generators where optional installation of surge capacitors close to the surge arrestors would not be convenient. Application of LCI (load commutated inverters) for turbine-generator starting may also obviate the use of surge capacitors on multi- turn coil machines. Optimal protection requires surge protection be located in close proximity to the generator terminals. 15. Transmission Line Switching 1. Description The switching of transmission lines at or near generating stations for maintenance purposes, or simply restoring a line to service after a relayed tripout, are recognized as normal functions in the course of operating a power system. In some cases these line switching operations can subject nearby generating units to excessive duty. The effect on the generator in severe cases 20 Generator Protection GEK 75512k is the same as for poor synchronizing in causing possible stator winding and shaft fatigue damage (Ref. 7). 2. Detection A measure of the severity of a switching event is the sudden step change in power (P) seen by the generator at the instant of switching. As a general guide, studies have shown that where P does not exceed 0.5 per unit on the generator kVA base the duty will be negligible (Ref. 17, 18). Values of P greater than 0.5 per unit may be determined to be non-harmful to the generator, for specific units and system switching events, but these cases should be carefully studied and identified. Predetermination of duties associated with line-switching operations and operating proce- dures which limit these duties to acceptable values can be found from simulating these op- erations, using a computer program such as that normally used for stability studies (Ref. 17, 18). 3. Recommendation The recommended procedure for avoiding excessive duty for the normal planned line-switch- ing operation is to establish, where necessary, operating procedures which limit the machine P to either the general 0.5 per unit level or an individually determined level for that unit. As an adjunct to established operating procedures, phase angle check relays at key breaker locations can prevent line closings under circumstances predetermined to be excessive. Note, however, that such check relays should not be applied without reliable means of overriding which would permit necessary line closing operations under emergency circumstances. 16. High Speed Reclosing 1. Description High speed reclosing of transmission circuits directly out of generating stations or electrically close to the station may cause significant shaft fatigue damage to the turbine-generator unit, particularly where high speed reclosing following severe multi-phase faults is permitted (Ref. 7, 19). The actual fatigue duty which a unit may experience during its lifetime from this cause depends on many factors, including both the unit's and the system's characteristics, the frequency of fault occurrence, etc. Studies substantiate that significant shaft damage could occur with unsuccessful reclosing for close-in three-phase faults. 2. Recommendation In order to eliminate or reduce the potential effects of unrestricted high speed reclosing of lines near generating stations, an alternative reclosing practice such as one of the following is recommended: Delayed reclosing, with a delay of 10 seconds or longer. Sequential reclosing, i.e., reclose initially only from the remote end of the line and block closing at the station if the fault persists. This is recommended only if the remote end of the line is not electrically near other turbine-generator units. 21 GEK 75512k Generator Protection Selective reclosing, i.e., high speed reclosing only for the less severe faults such as single line-to-ground; delayed reclosing on others. Other relaying practices providing selectiv- ity on the basis of fault severity would also be effective in reducing shaft fatigue duty. Where such alternative reclosing practices are not considered acceptable to the user, it is recommended that either: a. Detailed studies be performed to determine the probable lifetime fatigue damage which might be experienced for the reclosing practice contemplated, or b. Torsional monitoring equipment be installed to determine the accumulated fatigue dam- age being incurred. 17. Subsynchronous Resonance (SSR) 1. Description When a turbine-generator is connected to a transmission network that has series capacitor compensation or a high voltage dc (HVDC) transmission system, it is possible to develop subsynchronous (under line frequency) current oscillations in the lines and in the genera- tor armature. In the case of series compensated ac systems, these currents interact with the synchronously rotating flux to produce torque pulsation on the generator rotor. If these pul- sations are at a frequency close to one of the torsional natural frequencies of the turbine-gen- erator, high levels of torsional vibration can be induced in the shafts. Torsional instability of the turbine-generator shaft system has the potential for being extremely damaging to the turbine-generator shafts, and resulted in two shaft failures in the early 1970s. A more re- cently observed phenomenon involves interaction between torsional modes and HVDC con- trols (Ref. 28). This could lead to an unstable situation, resulting in spontaneous growth of torsional vibrations and potential damage to the shaft. 2. Detection Unstable or high levels of torsional vibration may be detected by observing the variations in angular velocity of the turbine-generator. A common measuring system involves a toothed wheel, a magnetic pickup and a frequency demodulator. Strain gauge telemetry systems have also been utilized in short-term tests to detect shaft torsional oscillations. Indirect methods of identifying subsynchronous resonance steady-state instability problems involve monitor- ing generator electrical terminal quantities. The armature current relay described in Ref. 20 utilizes this approach. 3. Responsibility for Detection It should be understood by those utilities that utilize series capacitor compensation, or have HVDC transmission in their system, that the potential for damaging torsional vibrations is a consequence of the special electrical characteristics of the transmission network. It is, there- fore, the owner's responsibility to implement devices to detect, and protect the machine from, the influences of subsynchronous torsional interaction. In the case of HVDC transmission lines, the potential for interaction between the HVDC controls and the turbine-generator ro- tor system needs to be accounted for in HVDC control design. General Electric has worked closely with many utilities on system studies to define the requirements for protective devices 22 Generator Protection GEK 75512k on particular systems. The company has also manufactured and has in service protective de- vices. This equipment includes (Ref. 20): a. A static subsynchronous resonance filter (static blocking filter) b. A supplementary excitation damping control (excitation system damper) c. A machine frequency relay (armature current frequency relay) (Ref. 21) d. A torsional vibration monitor (Ref. 22) In addition, generators that are applied for use in series capacitor compensated systems or systems containing HVDC transmission are sometimes furnished with pole-face amortisseur windings. The addition of pole-face amortisseur windings does not necessarily enhance neg- ative sequence capability. The function of amortisseur windings is to reduce the machine electrical resistance in the subsynchronous frequency range, which reduces the potential for torsional interaction at subsynchronous frequencies. 4. Recommendation It is vital that the electric utility work closely with the manufacturer at the planning stage to define the need for auxiliary equipment to protect the machine. This equipment, if required, needs to be operational when the machine is first connected to the network containing series capacitor compensated and/or HVDC transmission lines. It needs to be highly reliable, as misoperation could result in major machine failure. 18. Inadvertent Energization 1. Description When a generator is energized three-phase while at standstill or reduced speed, it will behave and accelerate as an induction motor. The equivalent machine impedance during the high slip interval can be represented by negative sequence reactance (X 2 ) in series with negative sequence resistance (R 2 ). The machine terminal voltage and current during this interval will be a function of generator, transformer and system impedances. If the generator-transformer is connected to an infinite system, the machine currents will be high (several per unit), and conversely, if the unit is connected to a weak system, the machine current could be low (12 per unit). During the period the machine is accelerating, high currents will be induced in the rotor and the time to damage may be on the order of a few seconds. NOTE Negative sequence reactance of a steam turbine-generator is approximately equal to the subtransient reactance X" dv . Anumber of generators have been accidentally energized while at standstill or very lowspeed. While many have survived the experience with minor damage, others have not. 23 GEK 75512k Generator Protection 2. Detection While there are several generator zone relays that may detect this contingency, their perfor- mance may be marginal. Therefore, the preferred approach is to provide detection means specifically designed for this purpose. One such method is to use overcurrent relays that are armed by a speed relay when the gen- erator is off line. 3. Recommendation It is recommended that the detection scheme described above be used to protect every gen- erator. To prevent damage to the rotor, stator bearings, etc., it is desirable that high speed protection be provided for this contingency. The relaying should be connected to trip the main generator breaker, trip any breakers which could feed current to the generator if breaker failure is detected, and be so implemented that it is never taken out of service when the unit is shut down for any purpose, even with the rotor removed. 19. Bearing Vibration 1. Description High vibration (as defined below) on a generator is a symptom of a problem. There are many possible causes of vibration, including: Unbalance Misalignment Thermal sensitivity Damaged bearings Oil whip Rubbing Bent overhangs Out-of-round journals or collectors Stiffness dissymmetry. 2. Detection All bearings are normally provided with vibration detectors and recorders. Either velocity probes, proximity probes, or both are used. These permit recording and monitoring of vi- bration, and alarming and/or tripping at predetermined levels of vibration. The vibration recorders do not provide the frequency spectrum information which could be useful in deter- mining the cause of the vibration. This information must be obtained with a portable vibration analyzer. 24 Generator Protection GEK 75512k 3. Recommendation For both generator and alternator bearings provided with proximity probes, the table below summarizes recommendations for various levels of shaft vibration. The vibration levels are given in mils [m], peak-to-peak, unfiltered. For Vibration Level Exceeding 2 Poles 4 Poles (mils) (m) (mils) (m) Recommendations 10 254 12 305 Sequential trip (Type 4) 7 178 10 254 Runback and trip within 15 minutes (Type 6) 6 152 8 203 Correct at first opportunity 3 76 5 127 Correct when convenient For generators provided with velocity probes which monitor endshield or pedestal deflection in the vicinity of the bearing, the alarm level is 0.5 in/sec, and the trip level is 1 in/sec. 4. Reference For more detailed information on vibration, refer to the turbine section of the instruction book (Ref. 24). 20. Synchronizing Errors 1. Description Improper synchronizing of units to the line may occur for a number of reasons. The most severe of these results from incorrect connection of potential transformer or synchronizing aids such that gross out-of-phase synchronizing, such as a 120 error, may occur. A failure of automatic synchronizing equipment may also result in large synchronizing errors. While tur- bine-generators are designed to withstand these rare occurrences without catastrophic results, provided stator current does not exceed the three-phase short circuit value, they can result in damage, such as slipped couplings, with resulting high vibration, loosened stator windings, and fatigue damage to the shaft and other mechanical parts (Ref. 7). Careless synchronizing, while generally a less severe incident, may, on an accumulated basis, have the same result. The following synchronizing limits are recommended to avoid damaging effects: Breaker closing within 10 (electrical angle) Voltage matching within 0 to +5% Slip slower than 10 seconds per slip cycle for manual synchronization. Slip slower than 6 seconds per slip cycle for automatic synchronization. 25 GEK 75512k Generator Protection 2. Detection A severe out-of-phase synchronizing incident will be evident from the physical effects of noise and turbine-generator foundation vibration. In addition, a tripout may result from the vibration trips or from electrical protective relays. Poor synchronizing routine is less evi- dent but would be observable by the synchroscope and an oscillation of electrical quantities (power, VARs) subsequent to the synchronizing. 3. Recommendations Careful checking of circuits during initial installation or equipment changeout and the estab- lishment of well-adhered-to procedures for manual synchronizing are key elements in mini- mizing out-of-phase synchronizing incidents. A Synch Check function should monitor manual synchronizing to prevent large errors (Ref. 8). Automatic synchronizing relays can provide very high accuracy. Where such relays are used, however, it is important that a check function be applied to provide an independent back-up. Failure of the primary relays to perform should be alarmed, since this might otherwise not be noticed. 21. Motoring 1. Description Motoring of a generator will occur when turbine output is reduced such that it develops less than no-load losses while the generator is still on line. Assuming excitation is sufficient, the generator will operate as a synchronous motor driving the turbine. The generator will not be harmed by synchronous motoring, but, if it occurs as a result of failure to complete a sequential trip, protection for the fault originating that trip is lost. In addition, a steam turbine can be harmed through overheating during synchronous motoring. If field excitation is lost, along with turbine output, the generator will run as an induction motor, driving the turbine. In addition to possible harm to the turbine, this will produce slip- frequency currents in the rotor and could cause it to overheat if continued long enough. A third type of motoring occurs when the generator is accidentally energized when at low speed. This is discussed separately under Accidental Energization. 2. Detection Motoring following loss of turbine output can be detected with a reverse power relay. To avoid false trips due to power swings, a time-delay pick-up of 10 to 30 seconds is suggested. This is the backup relay suggested in the description of Trip 4 - sequential trip. Measurement of very low power levels at very low power factors will require relatively high precision. Re- duction in reactive power flowin the generator will reduce the requirement for high precision. This may be accomplished through control action of the excitation system or by operator ac- tion. 26 Generator Protection GEK 75512k 3. Recommendation It is recommended that the reverse power relay referred to above be used and connected to produce a Type 1, simultaneous trip. Alternatively, a Type 2 generator trip or Type 3 breaker trip could be used. Breaker Failure Protection (see page 23) should be initiated, since line breaker failure may be the cause of the motoring. In addition, the turbine section of the in- struction book (Ref. 9) should be consulted and followed. 22. Stator Overtemperature 1. Description Stator overheating may result from overcurrent operation, improper gas pressure or purity (if applicable), gas or water cooling system malfunction, internal cooling passage blockage, etc. 2. Detection Armature bar temperatures are monitored by either TCs measuring stator cooling water tem- perature and/or RTD's in the stator slots (if applicable). All functioning RTDs and TCs should be constantly monitored and alarmed (see Ref 1, and 2&3 for H 2 0 cooled machines). As pointed out in the stator overcurrent section, these temperature detectors do not provide com- plete protection against damage due to overcurrent operation, because temperatures in other parts of the winding, winding forces, abnormal magnetic fields, etc. may become excessive. 3. Recommendation Automatic shutdown is not always provided for protection against stator overheating on gen- erators with conventionally cooled stator windings. Section 26 describes automatic protection recommended for liquid cooled armature windings. All operators should be made aware of the importance of operating the generator within its rated capability. In cases where a gen- erator will operate in an unattended station, some form of overtemperature protection should be provided. Implementation of an automatic stator overtemperature protection scheme also provides some overcurrent protection, and is generally easier to implement than overcurrent relaying. 23. Loss of Coolant to Gas Coolers (if applicable) 1. Description Serious overheating of all generator components will occur if coolant flow to the gas coolers is lost. Various machine temperature alarms will detect the overheating condition prior to any damaging overtemperatures. However, without human monitoring and intervention, the condition will persist. 2. Detection The RTD's monitoring the hot and cold gas temperatures may be used as the basis for estab- lishing protection against the loss of gas coolant. Refer to Table 1 for Alarm information. 27 GEK 75512k Generator Protection 3. Recommendation For machines which run unattended, consideration should be given to implementing an auto- matic runback (trip 6) or trip 4 (sequential trip), based on the cold and hot gas RTD's. 24. Reduced Seal Oil Pressure (if applicable) 1. Description A floating, radial ring-type seal is used to prevent hydrogen leakage from the generator along the shaft. Oil is supplied to the seals at a pressure slightly higher than that of the hydrogen in the generator. For large, liquid cooled generators, the oil is supplied by a seal oil pumping unit. The main pump is driven by an ac motor. An emergency back-up pump is driven by a dc motor. This pump will start automatically if the oil discharge pressure of the main pump decreases or if ac power is lost. In addition to the main and emergency pumps, bearing header pressure is available to maintain hydrogen pressure in the generator at a maximum of approximately 8 psig or 5 psid less than the available bearing header pressure, whichever is lower. For most conventionally cooled hydrogen generators, seal oil is supplied from the lube oil tank by the same pump supplying bearing oil. The main pump is driven by an ac motor. An emergency lube oil back-up pump is driven by a dc motor. This pump will start automatically if the seal oil differential pressure decreases or if ac power is lost. Some machines are pro- vided with a specific DC seal oil emergency backup pump in addition to the lube oil backup pump. Higher pressure (greater than 30 psig) conventionally cooled machines are provided with separate seal oil pumps. See Ref. 10 for details on the seal oil system provided. 2. Detection Alarms indicate low differential seal oil pressure, main pump motor overload, and emergency pump running (see Table 1). 3. Recommendation If the main pump is lost an operator should take immediate action to determine the cause. If the problem requires more than a few hours to correct, gas pressure should be reduced to the lowest value required for the generator load, as determined from the reactive capability curves. This procedure is recommended because the emergency pump has only the bearing header pressure as back-up on liquid cooled machines, and no additional backup is provided on conventionally cooled generators. Careful consideration of the DC supply capacity and the purge cycle time is required to decide how long it is safe operate on the backup DC pump. If this gas pressure cannot be maintained, additional reductions in both gas pressure and load will be required. Operation for long periods with the emergency pump or the bearing header supply only will result in a reduction of hydrogen purity. For most generators under these con- ditions, gas must be scavenged from the generator to maintain hydrogen purity as described in Ref. 4. Some conventionally cooled machines will automatically increase the scavenge gas rate in an attempt to maintain purity. Again, see Ref. 4 for details. 28 Generator Protection GEK 75512k 25. Local Overheating (if applicable) 1. Description Before synchronization, there are at least two areas of possible overheating in the generator which are a function of field excitation: Stator core heating, which is related to the stator flux (volts/Hertz). Generator field heating, which is related to field current. After synchronization, in addition to these two, there is also the possibility of stator winding heating (including end windings, connection rings, leads, and high voltage bushings), which is related to armature current. Local overheating can be caused in a number of ways. One is damage to the laminations at the inner diameter of the stator core. This might cause electrical contact between laminations leading to a flow of current and therefore heating. This type of damage may be caused by a foreign object striking the core under the influence of electromagnetic forces in the machine. Overheating may also be caused by improper cooling or by faulty or damaged insulation, allowing excessive leakage current to flow. It can also be caused by operating outside the capability limits, especially in underexcited regions. 2. Detection On hydrogen-cooled steam turbine-generators, overheating can be detected by the use of the Generator Gas Monitoring System (GGMS). The GGMS consists of a generator Core Moni- tor, a Signal Validation Control and a Pyrolysate Collector. The generator Core Monitor is an ionization-type particulate detector that is connected to the generator so that a constant flow of cooling gas passes through it. The cooling gas is monitored for the presence of submicron particles (particulates). Under normal conditions, the gas coolant contains no particulates that can be detected by the monitor. When overheating occurs, the thermal decomposition of organic material, epoxy paint, core lamination enamel or other insulating materials produces a large number of particulates which can be detected by the monitor to produce an alarm. The particulates can be collected by the Pyrolysate Collector which is designed to operate when a generator Core Monitor alarm occurs. Confirmation of overheating may be accomplished by laboratory analysis of the particulates. The Validation Control is used to automatically discriminate between a Core Monitor alarm caused by an instrument malfunction and one caused by local overheating. When the alarm is verified, the Validation Control actuates a machine heating alarm. 3. Recommendation When a machine heating alarm occurs, load should be reduced by manual runback (Type 8) until the alarm signal clears. If the alarm signal does not clear within five minutes the generator should be tripped manually (Type 5). Contacts are provided in the Validation Control which can be used to actuate runback or trip circuits if this feature is desired. 29 GEK 75512k Generator Protection Additional information may be found in specific Generator Gas Monitoring System publica- tions in the Operation and Maintenance Manual (O&M Manual). 26. Loss of Stator Coolant (if applicable) 1. Description Stator winding cooling water is supplied by one of two identical pumps. The pump not run- ning is in a standby mode and is connected to start automatically if the discharge pressure of the operating pump falls. Cooling flow may be reduced or lost because of: a. System restrictions such as plugged filters or strainer, or a buildup of material such as copper oxide in the stator winding strands b. Localized restriction in a single bar or group of bars in the winding c. Pipe break d. Loss of pumps e. Misadjustment of the control valve f. Control valve failure g. Freeze-up of the system or instrument lines containing moisture 2. Detection a. System restrictions downstream of the control valve sensing point will be signaled by the low flow alarm. System restrictions upstream of the sensing point will be compensated for by the control valve. If the limits of control valve operation are reached, a restriction will be signalled by the low pressure and low flow alarms. A high differential pressure will occur across the component containing the restriction, and the most likely place for this is the main filter. On newer units, filter pressure is monitored by a differential pres- sure alarm. System restrictions can also be signalled by the bulk water outlet temperature sensor which provides an alarm function, and by the individual liquid header outlet TCs and slot RTDs. b. Localized restrictions in a single bar or group of bars might be detected by the individual liquid header outlet TCs and the slot RTDs. c. A pipe break will be detected by a rise in the bulk outlet temperature and the individual liquid heater TCs, or by the low pressure alarm and a temperature rise indicated by the slot RTDs. d. Loss of both pumps will be detected by low pressure and low flow alarms and by a tem- perature rise signalled by all of the slot RTDs. 30 Generator Protection GEK 75512k e. Misadjustment of the control valve, which causes a flow restriction, will be detected by low pressure, low flow, and high bulk outlet temperature alarms. The individual outlet TCs and slot RTDs will also be affected. f. Control valve failure is likely to cause higher flow than required. There are no alarms to detect this, but the situation will, in time, be apparent to an operator when higher than normal flows and pressures are observed. g. Freezing temperatures in the station are particularly dangerous because some of the pro- tective devices may freeze and either fail to operate or operate incorrectly. The generator should not be operated above its no-liquid capability when station temperatures are be- low freezing unless provisions are made to protect vital parts of the system from the low temperature. 3. Recommendation Most serious faults will initiate an alarm. These are listed in Table 1. Appropriate operator action should be taken at the time of the alarm (Ref. 2, 3). The nature of the problem dictates the action required, as discussed below. Abnormal temperatures in the stator require that a check be made of the cooling flow. If a pumping unit abnormality is not apparent, a local restriction in the stator winding may be the cause. Temperature limits are outlined in the generator instruction book (Tab 30). Load reduction may be necessary to prevent exceeding limits. Problems with the cooling system should be corrected at the time of the alarm. If they are not, and the condition (flow, pressure, etc.) becomes more abnormal, a second contact will operate. This should be used to initiate either a runback or a trip, as selected by the owner during the design stage. If tripping was selected, a sequential trip, Type 4, may be used. Operators should be advised, however, not to wait for automatic protection to operate but to take corrective action immediately. This is the reason for the alarm. If runback, rather than trip, was selected, but the runback fails to occur, a trip signal will be produced. In many cases a load reduction to the no-liquid capability of the generator is required before maintenance can be performed, such as adjustment of the control valve, changing filters or calibrating sensors. These tasks should be performed periodically as recommended in the applicable instruction (Tab 33 of Generator Instruction Book). 27. High Water Conductivity (if applicable) 1. Description High purity water is required to cool the stator winding conductors safely. The water purity is maintained by fine filtration and a deionizer. A reduction in deionizer resin capacity will result in an increase in water conductivity. 31 GEK 75512k Generator Protection 2. Detection Water conductivity is continuously monitored at both inlet and outlet of the stator. A conduc- tivity above 0.5 mhos/cm [0.5 S/cm] will initiate an alarm. A second alarm will register when conductivity rises to 9.9 mhos/cm [9.9 S/cm]. 3. Recommendation The operator should replace the deionizer resin after the first alarm at 0.5 mhos/cm [0.5 S/cm], and before the second alarm. The unit should not be operated with water conductivity above the second alarm point, which is 9.9 mhos/cm [9.9 S/cm]. If this alarm sounds, the unit should be removed from service, using manual runback and trip (Type 6). Table2.SUMMARYOFGENERATORPROTECTIONRECOMMENDATIONS Fault Type Recommendation Page Electrical Faults Stator overcurrent Stator ground fault Stator phase-to-phase fault Over-voltage Over-volts/Hertz Field overexcitation Field ground Loss Of excitation Runback 8 or 7 Trip 1 Trip 1 Restore normal voltage 13 Trip 1 (or 2) Trip 4 Trip 4 (or 6) Trip 1 (or 2) 11 11 12 13 13 14 14 16 System Faults Unbalanced armature currents Loss of synchronism Abnormal frequency operation Breaker failure System Back-up Voltage surges Trip 3 Trip 3 See Turbine Instructions Use Breaker Failure Protection Trip 3 Use surge arrestors 17 17 18 18 19 19 System Operations Transmission line switching High speed reclosing Subsynchronous resonance Inadvertent energization Limit magnitude of power step See detailed recommendations See detailed recommendations See detailed recommendations 20 21 21 22 Mechanical or Thermal Faults 32 Generator Protection GEK 75512k Fault Type Recommendation Page Bearing vibration Synchronizing errors Motoring Stator Overtemperature Loss coolant to gas coolers Reduced seal oil pressure Local Overheating Loss of stator coolant High water conductivity Trip 4 Use check relays Trip 1 (or 2 or 3) Aarm (Trip 6 or 4) Trip 6 (or 4) Reduce H 2 pressure & load Runback 8(or 7) or Trip 5 Runback 7 or Trip 4 Trip 6 23 24 25 26 26 27 28 29 30 Protective Actions Key 1 Simultaneous trip 2 Generator trip 3 Breaker trip 4 Sequential trip 5 Manual trip 6 Manual Runback and trip 7 Automatic runback 8 Manual runback This table does not purport to summarize all the descriptive material contained in the referenced pages. These must be read and understood when using this summary. REFERENCES 1. GeneratorTabinO&MManual. 2. OperatorActiononHighTemperatureAlarms,GeneratorSectionofO&MManual. 3. OperatorActiononLowFlowandLowPressureAlarms,GeneratorSectionofO&MManual. 4. GasControlSystem,GeneratorSectionofO&MManual. 5. Brown,P.G.,Johnson,I.B.andStevenson,J.R.,GeneratorNeutralGrounding,IEEETrans., Vol.PAS-97,No.3,1978,pp.683694. 6. Berdy,J.,LossofExcitationProtectionforModernSynchronousGenerators,IEEETrans., Vol.PAS-94,1975,pp.14571463;availableasGEPublicationGER3183. 7. Brown,P.G.andQuay,R.,TransmissionLineReclosing-Turbine-GeneratorDutiesand StabilityConsiderations,TexasA&MRelayConference,April1976. 8. Winick,Kenneth,RelaySupervisionofManualSynchronizing,availableasGEPublication GER2624. 9. SequentialTrippingandPreventionofMotoring,TurbinesectionofO&MManual. 10. ShaftSealingSystem,GeneratorSectionofO&MManual. 33 GEK 75512k Generator Protection 11. Linkinhoker,C.L.,Schmitt,N.andWinchester,R.L.,InfluenceofUnbalancedCurrentson theDesignandOperationofLargeTurbine-Generators,IEEETrans.,Vol.PAS-92,1973, pp.15971604;availableasGEPublicationGER2874. 12. ANSIStd.C50.13-1977,Sections6.3and6.5. 13. Graham,P.J.,Brown,P.G.andWinchester,R.L.,GeneratorProtectionwithNewStaticNeg- ativeSequenceRelays,IEEETrans.,Vol.PAS-94,1974,pp.12081223. 14. WorkingGroupReport,OutofStepRelayingforGenerators,IEEETrans.,Vol.PAS-96, No.5,1977,pp.15561564. 15. IEEECommitteeReport,LocalBack-upRelayingProtection,IEEETrans.,Vol.PAS-89, No.6,1970,pp.10611608. 16. Hoffman,D.C.,Back-upProtectionforSystemFaultsattheGenerator,GeneralElectric Review,February1950. 17. Walker,D.N.,Adams,S.L.andPlacaek,R.J.,TorsionalVibrationandFatigueofTurbine- GeneratorShafts,IEEEPowerEngineeringSociety1978IEEE/ASME/ASCEJointPower GenerationConference;DigestStateoftheArtSymposium,Turbine-GeneratorShaftTor- sionals. 18. IEEEWorkingGroupoftheSubsynchronousMachineCommittee,SteadyStateSwitching Guide. 19. Joyce,J.S.andLambrecht,D.,StatusofEvaluatingtheFatigueofLargeSteamTur- bine-GeneratorsCausedbyElectricalDisturbances,IEEEPowerEngineeringSociety1978 IEEE/ASME/ASCEJointPowerGeneratorConference;DigestStateoftheArtSymposium, Turbine-GeneratorShaftTorsionals. 20. Counter-measurestoSubsynchronousResonanceProblems,IEEESubsynchronousRes- onanceWorkingGroupoftheSystemDynamicPerformanceSubcommittee;IEEETrans., Vol.PAS-99,No.5,1980,pp.18101818. 21. Bowler,C.E.J.,etal.,TheNavajoSMFTypeSSRRelay,IEEETrans.,Vol.PAS-97,No. 5,1978,pp.14891495. 22. Farmer,R.G.,et.al.,NavajoProjectReportonSSRAnalysisandSolution,IEEETrans., Vol.PAS-96,No.1,1977,pp.12261232. 23. ResistanceTemperatureDetectorspublication,GeneratorSectionofO&MManual. 24. StartingandLoading,publication,TurbinesectionofO&MManual. 25. Smaha,D.W.,Rowland,C.R.andPope,J.W.,CoordinationofLoadConservationwithTur- bine-GeneratorUnderfrequencyProtection,IEEETrans.,Vol.PAS-99,No.3,1980,pp. 11371150. 26. Berdy,J.,Out-of-StepProtectionforGenerators,availableasGEPublicationGER3179. 34 Generator Protection GEK 75512k 27. Berdy,J.,ApplicationofOut-of-StepBlockingandTrippingRelays,availableasGEPub- licationGER3180. 28. Piwko,R.J.andLarsen,E.V.,HVDCSystemControlforDampingofSubsynchronousOs- cillations,IEEEPaperNo.81-TD660-0(presentedSeptember1981atIEEETransmission andDistributionConference). 29. ANSI/IEEEC37-101IEEEGuideforGeneratorGroundProtection. 30. ANSI/IEEEC37-102IEEEGuideforACGeneratorProtection. 31. CEI/IECstandard34-3RotatingElectricalMachines-Specificrequirementsforturbine-type synchronousmachines. 32. ANSIC50.13RequirementsforCylindricalRotorSynchronousGenerator. GERsareGeneralElectricCompanypublicationswhichmaybeobtainedthroughthenear- estGESalesOffice. 35 GEK 75512k Generator Protection GE Energy General Electric Company www.gepower.com 36