Sunteți pe pagina 1din 143

19.02.

14
G.F
RYC
PAH
Summer
DB WB RH GR/LB D Range C Factor Latitude Altitude Dew Point
Outside oC 43.3 25.6 24 F Deg N mtrs. F
oF 110 78 24 94.53 26 8 23.02 53
Inside oC 22.8 55.00 ft
oF 73.00 62.25 55.00 66.81 174
Diff 37 27.72
Monsoon
DB WB RH GR/LB D Range C Factor Latitude Altitude Dew Point
Outside oC 32.2 28.3 82 F Deg N mtrs. F
oF 90 83 82 162.43 26 -6 23.02 53
Inside oC 22.8 55
oF 73.00 55.00 66.81
Diff 17 95.62
Winter
DB WB RH GR/LB D Range C Factor Latitude Altitude Dew Point
Outside oC 15.6 10.6 60 F Deg N mtrs. F
oF 60 51 60 41.67 26 -30 23.02 53
Inside oC 22.8 55
oF 73.00 55.00 66.81
Diff -13 -25.1
Sensible Latent
70 deg F 365 385
71 deg F 351 399
Degree of Activity 72 deg F 337 413
73 deg F 323 427
selected 74 deg F 309 441
72 75 deg F 295 455
Sensible Load 337 337
Latent Load 413 413
0
Summer Winter
0.56 0.56
0.53 0.53
1.13 1.13
0.36 0.36
0.32 0.32
0.21 0.21
0.38 0.38
0.23 0.23
0.12 0.12
0.08 0.08
0.55 0.55
Building Constructions & "U" Factors
Internal Heat Gain from People (BTU/Hr) (Light work)
Light bench work
Parameter
DBT (F)
Item Material of Construction
U - Factor
Exposed Glass
5.5mm thk. Clear Sheet Glass
Doucble 5.5mm thk. Clear Sheet Glass
5.5mm thk. Toughened / Clear Sheet Glass
Modular Panel
80mm thk. PUF Panel + 2mm thk. GI on both sides
100mm thk. PUF Panel + 2mm thk. GI on both sides
Exposed Wall
230mm thk. Brick Wall + 15mm thk. Sand Plaster on both sides
300mm thk. Brick Wall + 15mm thk. Sand Plaster on both sides
450mm thk. Brick Wall + 15mm thk. Sand Plaster on both sides
Partition Wall
150mm thk. Brick Wall + 12mm thk. Sand Plaster on both sides
300mm thk. Brick Wall + 20mm thk. Sand Plaster on both sides
False Ceiling
15mm thk. Gypsum False ceiling
CLIENT:-
PROJECT:-
LOCATION:-
DOCUMENT NO:-
Date:
Estimated By:-
FORMULATION AREA
CHANGODAR (GUJRAT) AHU NO:-
Floor:-
Checked BY:-
CONTRACT PHARMACAL CORPORATION
0.62 0.62
0.12 0.12
0.08 0.08
0.36 0.36
0.34 0.34
Roof 0.42 0.42
North
East
South
West
NW
SW
NE
SE
Daily Range
Correction Factor
WALL
North
East
South
West
NW
SW
NE
SE
ROOF
Exposed (80lb/sqft)
Shaded (80lb/sqft)
150mm thk. RC Slab + 15mm thk. Plaster on both sides with water proofing
Flooring
150mm thk. RC Slab + 50mm thk. Kota
150mm thk. RC Slab + 50mm thk. Kota + 2mm Epoxy
False Ceiling
2mm thk. Aluminium False ceiling
80mm thk. PUF Panle + 2mm thk. GI on both sides
100mm thk. PUF Panle + 2mm thk. GI on both sides
ISHRAE
Page 1-9
Table 7
For Summer (May) -
4PM
For Monsoon (Aug) -
4PM
For Winter (Dec) - 4PM
163 165 118
Direction
Solar Gain (FPS Unit)
Peak Solar Heat Gain Through Glass (For 20
o
N Latitude)
23 11 7
12 11 74
7 12 11
Item / Direction
Solar Gain (FPS Unit)
For Summer (4Pm) For Monsoon (4Pm) For Winter (2AM)
Equivalent Temp. Diff. Through Wall & Roof
24 24 24
ISHRAE
Page 1-9
Table 9
8 -6 -30
20 6 -19
26 12 -22
12 -2 -27
24 10 -23
12
-23
22 8 -21
-21
16 2 -29
-7
-24
14
26
18 4
26
0
40
CLIENT: CONTRACT PHARMACAL CORPORATION PROJETC: FORMULATION AREA PROJECT NO: GMP/ PROJ-0579
LOCATION: CHANGODAR (GUJRAT) DOCUMENT NO: CPC/HVAC SUMMARY / R0 DATE: 19.02.14
S.N. AHU NO
ROOM
NO
ROOM NAME AREA VOL.
ROOM
TEMP.
RELATIVE
HUMIDITY
RH
CLASS
ROOM
DIFF.
PRESSURE
OCCUP
ANCY
HEAT
DISIPATION
LOAD OF
EQUIP.
MIN
FRESH AIR
MIN
SUPPLY
AIR
MIN
SUPPLY
AIR
AHU
Static
SELECTED
FRESH AIR
SELECTED
DEH AIR
QTY
COIL
BYPASS
AIR QTY
SELECTED
ROOM
SUPPLY AIR
INFIL. EXFIL.
DUST
EXH.
ROOM
EXH.
ROOM
RETURN
AIR
PURGE
AIR
SELECTED
COOLING
LOAD
HEATING
LOAD
FAN
CAPACITY
L(m) W(m) H(m) (mts2) (mts3) (C) (%) AT REST (Pa) (Nos.) (KW) (ACPH) (ACPH) (CFM) mm of Wg (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (TR) (Kw) (CFM)
A1 GF-02 AIRLOCK 3.80 2.50 2.40 9.5 22.8 NMT 25 NMT 60 NA -- 1 20 270 65 335 335
A2 GF-03 WARE HOUSE 10.50 12.78 4.20 134.2 563.6 NMT 25 NMT 60 NA -- 2.0 1 20 6630 65 6630 6630
TOTAL 143.7 586.4 2.0 355 4000 3320 6965 6965 355 9.4 12.0 7320
A3 GF-05 DISPENSING 2.00 3.12 2.40 6.2 15.0 NMT 25 NMT 60 100000 15 1.0 1.0 2 20 180 130 420 80 500
A4 GF-06 CORRIDOR (FRONT OF DISPENSING) 3.29 5.55 2.40 18.3 43.8 NMT 25 NMT 60 100000 25 2 20 520 130 520 150 370
A5 29.55 2.36 2.40 129.4 310.5 NMT 25 NMT 60 100000 35 14 20 3655 130 4690 2160 2530
14.20 2.10
14.20 2.10
A6 GF-10 AIRLOCK 1.72 2.38 2.40 4.1 9.8 NMT 25 NMT 60 100000 25 2 20 120 130 125 160 80 205
A7 GF-11 FORMULATION CHANGE ROOM 2.90 2.36 2.40 6.8 16.4 NMT 25 NMT 60 100000 15 2 20 195 130 205 205
A53 GF-12 AIRLOCK 1.70 2.38 2.40 4.0 9.7 NMT 25 NMT 60 100000 2 47 270 270 270
TOTAL 168.9 405.3 1.0 1.0 2695 6505 6230 3810 275 34.3 12.0 6505
A8 GF-14 GRANULATION DRYING 3.87 2.80 2.40 10.8 26.0 NMT 25 NMT 60 100000 25 2.0 2.40 2 20 310 130 795 120 915
A9 GF-15 COATING 3.87 2.71 2.40 10.5 25.2 NMT 25 NMT 60 100000 25 1.0 3.25 2 20 300 130 945 120 1065
A10 GF-16 MILLING SHIFTING N BLENDING 3.87 2.71 2.40 10.5 25.2 NMT 25 NMT 60 100000 25 1.0 3.25 2 20 300 130 945 120 1065
A11 GF-17 COMPRESSION 3.87 2.78 2.40 10.8 25.8 NMT 25 NMT 60 100000 25 1.0 2.39 2 20 305 130 770 120 890
A12 GF-18 PACKING 3.87 2.64 2.40 10.2 24.5 NMT 25 NMT 60 100000 25 1.0 3.67 2 20 290 130 1095 120 1215
TOTAL 52.8 126.7 6.0 15.0 210 4550 810 4550 5150 810 10.8 6.0 5360
A13 AHU 04 GF-19 INPROCESS STORAGE 6.06 2.86 2.40 17.3 41.6 NMT 25 NMT 60 100000 25 3 30 735 130 735 80 815
TOTAL 17.3 41.6 75 890 735 815 155 1.0 3.0 890
A14 GF-20 CAPSULATION 3.00 3.00 2.40 9.0 21.6 NMT 25 NMT 60 100000 25 2.0 2.39 2 20 255 130 810 80 890
A15 GF-21 PALETIZATION N COATING\ 2.98 3.00 2.40 8.9 21.5 NMT 25 NMT 60 100000 25 2.0 3.58 2 20 255 130 1100 120 1220
A16 GF-22 LIQUID PREP 3.12 2.98 2.40 9.3 22.3 NMT 25 NMT 60 100000 25 1.0 2.39 2 20 265 130 790 80 870
A17 GF-23 IPQC LAB 2.98 2.98 2.40 8.9 21.3 NMT 25 NMT 60 100000 25 1.0 1.95 2 20 255 130 680 80 760
A18 GF-24
TOOL ROOM & CLEAN EQUPMENT
ROOM
6.10 2.40 2.40 14.6 35.1 NMT 25 NMT 60 100000 25 2 20 415 130
415
80 495
A19 GF-25 WASHING AND DRYING 6.36 2.32 2.40 19.9 47.7 NMT 25 NMT 60 100000 25 1.0 3.25 2 20 565 130 1375 80 1455
2.53 2.03 5
TOTAL 70.6 169.5 7.0 13.6 5 275 5075 890 5170 5690 795 12.3 6.0 5965
A20 GF-26 GRANULATON 3.85 2.78 2.40 10.7 25.7 NMT 25 NMT 60 100000 25 1.0 5.50 2 20 305 130 1610 120 1730
A21 GF-27 COATING 3.85 2.71 2.40 10.4 25.0 NMT 25 NMT 60 100000 25 1.0 2.75 2 20 295 130 915 120 1035
A22 GF-28 DRY GRANULATION 3.85 2.71 2.40 10.4 25.0 NMT 25 NMT 60 100000 25 1.0 4.04 2 20 295 130 1225 120 1345
A23 GF-29 COMPRESSION 3.85 2.71 2.40 10.4 25.0 NMT 25 NMT 60 100000 25 2.0 3.03 2 20 295 130 1010 120 1130
A24 GF-30 COMPRESSION 3.85 2.74 2.40 10.5 25.3 NMT 25 NMT 60 100000 25 2.0 3.03 2 20 300 130 1100 120 1220
TOTAL 52.5 126.1 7.0 18.3 230 5860 830 5860 6460 830 13.6 6.0 6690
A39 GF-34 COATING 4.20 2.80 2.40 11.8 28.2 NMT 25 NMT 60 100000 25 1.0 2.25 2 20 335 130 830 120 950
A40 GF-32
MILLING SHIFTING GRANULATION
DRY COATING
4.20 6.10 2.40 25.6 61.5 NMT 25 NMT 60 100000 25 1.0 3.31 2 20 725 130
1385
120 1505
A41 GF-33 COMPRESSION 4.18 2.10 2.40 8.8 21.0 NMT 25 NMT 60 100000 25 1.0 2.48 2 20 250 130 850 80 930
A42 GF-31 CHANGE ROOM 1.77 2.10 2.40 3.7 8.9 NMT 25 NMT 60 100000 15 1.0 2 20 110 130 110 80 80 110
A43 -- PASSAGE 1.76 9.00 2.40 15.8 37.9 NMT 25 NMT 60 100000 35 2 23 520 130 520 520
A44 GF-35 DISPENSING 1.78 2.74 2.40 4.9 11.7 NMT 25 NMT 60 100000 15 1.00 2 20 140 130 400 80 320
A51 GF-36 RM STORE 4.20 2.70 2.40 11.3 27.2 NMT 25 NMT 60 100000 25 2 20 325 130 325 280 605
A52 GF-37 RM ENTRY 1.40 2.00 2.40 2.8 6.7 NMT 25 NMT 60 100000 15 2 42 170 130 170 170
TOTAL 84.7 203.3 4.0 9.0 280 4700 4590 4420 110 12.1 6.0 4700
A25 GF-38 HPLC LAB 6.00 10.50 2.40 63.0 151.2 NMT 25 NMT 60 NA -- 20.0 7.70 1 20 1780 65 3470 3470
A26 GF-39 CABIN 3.02 3.39 2.40 10.2 24.6 NMT 25 NMT 60 NA -- 1.0 0.15 1 20 290 65 315 315
A27 GF-40 CABIN 2.98 3.38 2.40 10.1 24.2 NMT 25 NMT 60 NA -- 1.0 0.15 1 20 285 65 310 310
TOTAL 83.3 199.9 22.0 8.0 495 4590 4095 4095 495 12.9 4.5 4590
A28 GF-41 ICP 4.21 2.62 2.40 11.0 26.4 NMT 25 NMT 60 NA -- 2.0 1.95 1 20 315 65 705 705
A29 GF-42 GC CABIN 4.21 2.70 2.40 11.3 27.2 NMT 25 NMT 60 NA -- 1.0 1.50 1 20 320 65 580 580
A30 GF-43 GC SAMPLE PREP 4.21 2.34 2.40 9.8 23.6 NMT 25 NMT 60 NA -- 1.0 1.14 1 20 280 65 470 470
A31 GF-44 BALANCE ROOM & WASH 4.21 6.15 2.40 25.8 62.0 NMT 25 NMT 60 NA -- 3.0 1.14 1 20 730 65 885 885
A32 GF-48 CORRIDOR 15.72 2.40 2.40 37.7 90.5 NMT 25 NMT 60 NA -- 2.0 1 20 1070 65 1080 1080
A33 GF-47 ANALYTIC CHANGE ROOM 3.04 2.39 2.40 7.3 17.4 NMT 25 NMT 60 NA -- 1 20 210 65 210 210
A34 GF-46 CORRIDOR 1.50 14.23 2.40 43.9 105.3 NMT 25 NMT 60 NA -- 1.0 1 20 1240 65 1240 1240
12.34 1.83
TOTAL 146.9 352.5 10.0 5.7 450 4810 810 5170 5170 450 12.7 6.0 5620
A35 GF-49 CABIN 3.10 2.28 2.40 7.1 17.0 NMT 25 NMT 60 NA -- 4.0 0.15 1 20 200 65 275 275
A36 GF-50 INSTRUMENT LAB 3.09 2.28 2.40 7.0 16.9 NMT 25 NMT 60 NA -- 3.0 3.20 1 20 200 65 940 940
A37 GF-51 DISSOLUTION LAB 3.25 5.53 2.40 18.0 43.1 NMT 25 NMT 60 NA -- 4.0 3.25 1 20 510 65 1180 1180
A38 GF-52 SAMPLE PREP ROOM 6.23 6.00 2.40 37.4 89.7 NMT 25 NMT 60 NA -- 6.0 3.20 1 20 1055 65 1685 1685
TOTAL 69.4 166.6 17.0 9.8 395 4475 4080 4080 395 12.3 6.0 4475
A46 AHU 10 IT SERVER ROOM 6.12 3.59 2.40 22.0 52.8 NMT 25 UNCONTROLLED NA -- 1.0 1.50 1 10 315 65 890 890
TOTAL 1.0 1.5 60 950 890 890 60 2.5 NA 950
AHU 09
AHU 01
AHU 03
AHU 4A
AHU 05
AHU 07
AHU 06
AHU 08
AHU 02
ROOM DIMENSION
PREPARED BY: RYC
CHECKED BY: PAH
HVAC SUMMARY SHEET
GF-07 /08
/09
CORRIDOR
Date: 19.02.14
Floor:- G.F
AHU NO:- AHU 01
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
18.3996
36.94 78.08 XX 27.72 Volume 805 F.A as per ACPH 13
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 20
Room Number GF-02
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.80 2.50 XX 9.50 2.40 XX 23 456
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
12.46 8.2 XX 102.22 7.872 XX 805 268
NA Coil By Pass Factor 0.10 0.00
CFM / Person 15 1
65 People 0 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0 23 11 7 0.56 0 0 0
Glass(E) 0 12 11 7 0.56 0 0 0
Glass(S) 0 12 11 74 0.56 0 0 0
Glass(W) 0 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0 40 26 -7 0.5 0 0 0
Roof insulated 0 16 2 -29 0.11 0 0 0
All glass 0 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 102 32 12 -17.92 0.55 1796 672 -1007
Floor 0 32 12 -17.92 0.5 0 0 0
Partition 173 32 12 -17.92 0.35 1932 724 -1084
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 80 37 -28
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.11 2545 273 273 273
3.41 871 871 871
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
4952 2577 -975
15% 743 387 -146
5695 2964 -1121
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 38 130 -34
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 38 130 -34
10% 4 13 -3
41 143 -38
ROOM TOTAL HEAT(RTH) 5737 3107 -1159
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 20 1.08 T 36.9 17.0 -12.9 0.9 718 330 -251
Latent 20 0.68 Gr / lb 28 95.62 -25.14 0.9 339 1170 -308
6794 4607 -1718
Safety 3% 204 138 -52
6998 4745 -1769
TR 0.58 0.40 -0.15
RSH 5695 2964 -1121
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 5737 3107 -1159
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.99 0.95 0.97
ADP 56.00 55.29 #N/A
ADP 55.5 55.5 55.5
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 16 16 16
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 335 175 -65
(From tables/chart)
SOLAR HEAT GAIN GLASS
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
INTERNAL HEAT
20
Outside air cfm
ROOM SENSIBLE HEAT SUB TOTAL
Equipement load (kW)
Lights
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TOTAL ROOM SENSIBLE HEAT (RSH)
Safety factor
HP
Watts
2
Fresh Air Selection
DESIGN CONDITIONS
Sun gain/ Temp diff
26
Winter
Summer
Monsoon
Winter
Blower Load (HP)
AIRLOCK
Equipment Load(KW)
DEHUMIDIFIER AIR CFM
DB diff
HEAT GAIN (Btu / Hour)
Fresh Air Changes/Hour
Gr/lb Difference
204.44
Supply duct heat gain + Supply duct leak loss + Safety factor
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION
HEAT LOAD CALCUALATION SHEET
PROJECT:-
LOCATION:-
DOCUMENT NO:-
CLIENT:- CONTRACT PHARMACAL CORPORATION
FORMULATION AREA
CHANGODAR (GUJRAT)
GMP TECHNICAL
SOLUTIONS PVT
LTD
Gain / People
0
ROOM DATA
PARAMETER
Outside Conditions
Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(SELECTED ADP)
Dehumidified Rise
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
Room Name
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Filtration
Static Pressure (mm of Wg)
People
TOTAL ROOM LATENT HEAT
23.02 53
Inside Conditions
Difference
Summer
Monsoon
Safety factor Supply duct leak loss + Safety factor
Selected Fresh Air (CFM)
Lighting Load
(Watts / Sq.ft.)
20
0
LATENT HEAT
335 268 268 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- AHU 01
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 2
cfm /Person
+0.18*Sq.ft
289.899192
36.94 78.08 XX 27.72 Volume 19891 F.A as per ACPH 332
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 335
Room Number GF-03
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
10.50 12.78 XX 134.19 4.20 XX 564 11272
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
34.44 41.92 XX 1443.88 13.776 XX 19891 6630
NA Coil By Pass Factor 0.10 0.0
CFM / Person 15 1
65 People 2 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0 23 11 7 0.56 0 0 0
Glass(E) 0 12 11 7 0.56 0 0 0
Glass(S) 0 12 11 74 0.56 0 0 0
Glass(W) 0 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 137 24 10 -23 0.35 1149 479 -1101
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0 40 26 -7 0.5 0 0 0
Roof insulated 0 16 2 -29 0.11 0 0 0
All glass 0 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 1444 32 12 -17.92 0.55 25365 9498 -14231
Floor 0 32 12 -17.92 0.5 0 0 0
Partition 537 32 12 -17.92 0.35 6008 2250 -3371
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 1336 614 -467
2 People Nos 337 674 674 674
0.00 0.00 2545 0 0 0
2.65 2545 6747 6747 6747
3.41 12309 12309 12309
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
53588 32570 560
15% 8038 4885 84
61626 37455 645
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 631 2178 -573
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 826 826 826
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 1457 3004 253
10% 146 300 25
1603 3305 279
ROOM TOTAL HEAT(RTH) 63229 40760 923
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 335 1.08 T 36.9 17.0 -12.9 0.9 12028 5523 -4207
Latent 335 0.68 Gr / lb 28 95.62 -25.14 0.9 5683 19604 -5154
80941 65887 -8438
Safety 3% 2428 1977 -253
83369 67863 -8691
TR 6.95 5.66 -0.72
RSH 61626 37455 645
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 63229 40760 923
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.97 0.92 0.70
ADP 55.57 54.67 #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 3340 2030 35
Sensible Heat Factor
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
(From tables/chart)
CALCUALTION Room Sensible Heat
Room Total Heat
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
TOTAL ROOM LATENT HEAT
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
Safety factor Supply duct leak loss + Safety factor
335
2
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
Lights 2887.77 Watts
INTERNAL HEAT
People Gain / People
Equipement load (kW) HP
Outside air cfm DB diff
335
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Unit in Meters. :
Unit in Ft. :
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Fresh Air Selection
Room Name WARE HOUSE
26 Monsoon
Difference
Blower Load (HP)
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
Summer
DESIGN CONDITIONS
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Inside Conditions
DOCUMENT NO:- 0
PARAMETER
Outside Conditions
Summer
23.02 53
Winter
6630 6630 6630 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- AHU 01
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
27.0778848
36.94 78.08 XX 27.72 Volume 528 F.A as per ACPH 18
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 30
Room Number GF-05
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
2.00 3.12 XX 6.24 2.40 XX 15 299
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
6.56 10.23 XX 67.10 7.872 XX 528 176
100000 Coil By Pass Factor 0.10 0.98
CFM / Person 15 2
130 People 1 Pressure 15 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 67.10 32 12 -17.92 0.55 1179 441 -661
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 72.50 32 12 -17.92 0.35 810 303 -455
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 120 55 -42
1 People Nos 337 337 337 337
0.98 1.31 2545 3328 3328 3328
0.14 2545 358 358 358
3.41 572 572 572
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
6704 5395 3437
15% 1006 809 516
7709 6204 3953
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 57 195 -51
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 470 608 362
10% 47 61 36
517 669 398
ROOM TOTAL HEAT(RTH) 8226 6873 4350
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 30 1.08 T 36.9 17.0 -12.9 0.9 1077 495 -377
Latent 30 0.68 Gr / lb 28 95.62 -25.14 0.9 509 1756 -462
9812 9123 3512
Safety 3% 294 274 105
10106 9397 3617
TR 0.84 0.78 0.30
RSH 7709 6204 3953
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 8226 6873 4350
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.94 0.90 0.91
ADP 55.00 54.50 54.50
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 420 340 215
Sensible Heat Factor
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
(From tables/chart)
CALCUALTION Room Sensible Heat
Room Total Heat
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
TOTAL ROOM LATENT HEAT
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
Safety factor Supply duct leak loss + Safety factor
30
1
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
Lights 134.20 Watts
INTERNAL HEAT
People Gain / People
Equipement load (kW) HP
Outside air cfm DB diff
30
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Unit in Meters. :
Unit in Ft. :
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Fresh Air Selection
Room Name DISPENSING
26 Monsoon
Difference
Blower Load (HP)
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
Summer
DESIGN CONDITIONS
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Inside Conditions
DOCUMENT NO:- 0
PARAMETER
Outside Conditions
Summer
23.02 53
Winter
420 340 215 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
35.3649996
36.94 78.08 XX 27.72 Volume 1547 F.A as per ACPH 52
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 55
Room Number GF-06
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.29 5.55 XX 18.26 2.40 XX 44 876
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
10.79 18.20 XX 196.47 7.872 XX 1547 516
100000 Coil By Pass Factor 0.10 0.0
CFM / Person 15 2
130 People 0 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 196.47 32 12 -17.92 0.55 3451 1292 -1936
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 149.64 32 12 -17.92 0.35 1673 626 -939
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 219 101 -77
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.41 2545 1049 1049 1049
3.41 1675 1675 1675
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
8068 4744 -228
15% 1210 712 -34
9278 5455 -262
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 104 358 -94
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 104 358 -94
10% 10 36 -9
114 393 -103
ROOM TOTAL HEAT(RTH) 9392 5849 -365
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 55 1.08 T 36.9 17.0 -12.9 0.9 1975 907 -691
Latent 55 0.68 Gr / lb 28 95.62 -25.14 0.9 933 3219 -846
12300 9974 -1902
Safety 3% 369 299 -57
12669 10273 -1959
TR 1.06 0.86 -0.16
RSH 9278 5455 -262
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 9392 5849 -365
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.99 0.93 0.72
ADP 56.00 55.00 49.00
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 505 300 -10
Sensible Heat Factor
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
(From tables/chart)
CALCUALTION Room Sensible Heat
Room Total Heat
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
TOTAL ROOM LATENT HEAT
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
Safety factor Supply duct leak loss + Safety factor
55
0
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
Lights 392.94 Watts
INTERNAL HEAT
People Gain / People
Equipement load (kW) HP
Outside air cfm DB diff
55
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Unit in Meters. :
Unit in Ft. :
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Fresh Air Selection
Room Name CORRIDOR (FRONT OF DISPENSING)
26 Monsoon
Difference
Blower Load (HP)
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
Summer
DESIGN CONDITIONS
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Inside Conditions
DOCUMENT NO:- 0
PARAMETER
Outside Conditions
Summer
23.02 53
Winter
516 516 516 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
250.5793104
36.94 78.08 XX 27.72 Volume 10959 F.A as per ACPH 2557
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 2560
Room Number GF-07 /08 /09
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
29.55 2.36 XX 129.38 2.40 XX 311 6210
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
96.92 7.74 XX 1392.11 7.872 XX 10959 3653
100000 Coil By Pass Factor 0.10 0.0
CFM / Person 15 14
130 People 0 Pressure 35 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 1392.11 32 12 -17.92 0.55 24455 9157 -13721
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 819.92 32 12 -17.92 0.35 9166 3432 -5143
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 10213 4689 -3572
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
7.68 2545 19538 19538 19538
3.41 11868 11868 11868
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
75240 48685 8971
15% 11286 7303 1346
86526 55987 10316
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 4825 16646 -4376
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 4825 16646 -4376
10% 483 1665 -438
5308 18310 -4814
ROOM TOTAL HEAT(RTH) 91834 74297 5502
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 2560 1.08 T 36.9 17.0 -12.9 0.9 91919 42202 -32149
Latent 2560 0.68 Gr / lb 28 95.62 -25.14 0.9 43429 149810 -39387
227182 266309 -66034
Safety 3% 6815 7989 -1981
233998 274298 -68015
TR 19.50 22.86 -5.67
RSH 86526 55987 10316
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 91834 74297 5502
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.94 0.75 1.87
ADP 55.14 50.83 56.00
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 4690 3035 560
Sensible Heat Factor
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
(From tables/chart)
CALCUALTION Room Sensible Heat
Room Total Heat
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
TOTAL ROOM LATENT HEAT
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
Safety factor Supply duct leak loss + Safety factor
2560
0
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
Lights 2784.21 Watts
INTERNAL HEAT
People Gain / People
Equipement load (kW) HP
Outside air cfm DB diff
2560
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Unit in Meters. :
Unit in Ft. :
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Fresh Air Selection
Room Name CORRIDOR
26 Monsoon
Difference
Blower Load (HP)
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
Summer
DESIGN CONDITIONS
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Inside Conditions
DOCUMENT NO:- 0
PARAMETER
Outside Conditions
Summer
23.02 53
Winter
4690 3653 3653 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
7.946922816
36.94 78.08 XX 27.72 Volume 348 F.A as per ACPH 12
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 15
Room Number GF-10
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
1.72 2.38 XX 4.10 2.40 XX 10 197
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
5.65 7.81 XX 44.15 7.872 XX 348 116
100000 Coil By Pass Factor 0.10 0.00
CFM / Person 15 2
130 People 0 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 44.15 32 12 -17.92 0.55 776 290 -435
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 44.89 32 12 -17.92 0.35 502 188 -282
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 60 27 -21
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.09 2545 236 236 236
3.41 376 376 376
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
1949 1118 -125
15% 292 168 -19
2242 1286 -144
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 28 98 -26
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 28 98 -26
10% 3 10 -3
31 107 -28
ROOM TOTAL HEAT(RTH) 2273 1393 -173
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 15 1.08 T 36.9 17.0 -12.9 0.9 539 247 -188
Latent 15 0.68 Gr / lb 28 95.62 -25.14 0.9 254 878 -231
3066 2518 -592
Safety 3% 92 76 -18
3158 2594 -609
TR 0.26 0.22 -0.05
RSH 2242 1286 -144
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 2273 1393 -173
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.99 0.92 0.84
ADP 56.00 54.83 53.20
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 125 70 -5
Sensible Heat Factor
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
(From tables/chart)
CALCUALTION Room Sensible Heat
Room Total Heat
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
TOTAL ROOM LATENT HEAT
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
Safety factor Supply duct leak loss + Safety factor
15
0
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
Lights 88.30 Watts
INTERNAL HEAT
People Gain / People
Equipement load (kW) HP
Outside air cfm DB diff
15
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Unit in Meters. :
Unit in Ft. :
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Fresh Air Selection
Room Name AIRLOCK
26 Monsoon
Difference
Blower Load (HP)
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
Summer
DESIGN CONDITIONS
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Inside Conditions
DOCUMENT NO:- 0
PARAMETER
Outside Conditions
Summer
23.02 53
Winter
125 116 116 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
13.2554592
36.94 78.08 XX 27.72 Volume 580 F.A as per ACPH 19
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 20
Room Number GF-02
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
2.90 2.36 XX 6.84 2.40 XX 16 329
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
9.51 7.74 XX 73.64 7.872 XX 580 193
100000 Coil By Pass Factor 0.10 0.0
CFM / Person 15 2
130 People 0 Pressure 15 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 73.64 32 12 -17.92 0.55 1294 484 -726
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 74.05 32 12 -17.92 0.35 828 310 -464
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 80 37 -28
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.15 2545 393 393 393
3.41 628 628 628
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
3222 1852 -197
15% 483 278 -30
3706 2130 -227
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 38 130 -34
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 38 130 -34
10% 4 13 -3
41 143 -38
ROOM TOTAL HEAT(RTH) 3747 2273 -264
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 20 1.08 T 36.9 17.0 -12.9 0.9 718 330 -251
Latent 20 0.68 Gr / lb 28 95.62 -25.14 0.9 339 1170 -308
4805 3773 -823
Safety 3% 144 113 -25
4949 3886 -848
TR 0.41 0.32 -0.07
RSH 3706 2130 -227
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 3747 2273 -264
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.99 0.94 0.86
ADP 56.00 55.00 53.60
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 205 120 -10
Sensible Heat Factor
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
(From tables/chart)
CALCUALTION Room Sensible Heat
Room Total Heat
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
TOTAL ROOM LATENT HEAT
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
0
Safety factor Supply duct leak loss + Safety factor
20
0
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
Lights 147.28 Watts
INTERNAL HEAT
People Gain / People
Equipement load (kW) HP
Outside air cfm DB diff
20
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Unit in Meters. :
Unit in Ft. :
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Fresh Air Selection
Room Name FORMULATION CHANGE ROOM
26 Monsoon
Difference
Blower Load (HP)
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
Summer
DESIGN CONDITIONS
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Inside Conditions
DOCUMENT NO:- 0
PARAMETER
Outside Conditions
Summer
23.02 53
Winter
205 193 193 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- AHU 03
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 2
cfm /Person
+0.18*Sq.ft
50.9871648
36.94 78.08 XX 27.72 Volume 918 F.A as per ACPH 31
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 55
Room Number GF-14
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.87 2.80 XX 10.84 2.40 XX 26 520
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
12.69 9.18 XX 116.60 7.872 XX 918 306
100000 Coil By Pass Factor 0.10 2.4
CFM / Person 15 2
130 People 2 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 116.60 32 12 -17.92 0.55 2048 767 -1149
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 219 101 -77
2 People Nos 337 674 674 674
2.40 3.22 2545 8191 8191 8191
0.24 2545 623 623 623
3.41 994 994 994
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
12749 11349 9256
15% 1912 1702 1388
14662 13052 10644
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 104 358 -94
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 826 826 826
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 930 1184 732
10% 93 118 73
1023 1302 805
ROOM TOTAL HEAT(RTH) 15684 14354 11449
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 55 1.08 T 36.9 17.0 -12.9 0.9 1975 907 -691
Latent 55 0.68 Gr / lb 28 95.62 -25.14 0.9 933 3219 -846
18592 18479 9912
Safety 3% 558 554 297
19150 19033 10210
TR 1.60 1.59 0.85
RSH 14662 13052 10644
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 15684 14354 11449
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.93 0.91 0.93
ADP 55.00 54.50 54.83
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 795 710 580
Sensible Heat Factor
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
(From tables/chart)
CALCUALTION Room Sensible Heat
Room Total Heat
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
TOTAL ROOM LATENT HEAT
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
0
Safety factor Supply duct leak loss + Safety factor
55
2
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
Lights 233.19 Watts
INTERNAL HEAT
People Gain / People
Equipement load (kW) HP
Outside air cfm DB diff
55
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Unit in Meters. :
Unit in Ft. :
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Fresh Air Selection
Room Name GRANULATION DRYING
26 Monsoon
Difference
Blower Load (HP)
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
Summer
DESIGN CONDITIONS
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Inside Conditions
DOCUMENT NO:- 0
PARAMETER
Outside Conditions
Summer
23.02 53
Winter
795 710 580 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
35.31257736
36.94 78.08 XX 27.72 Volume 888 F.A as per ACPH 30
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 40
Room Number GF-15
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.87 2.71 XX 10.49 2.40 XX 25 503
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
12.69 8.89 XX 112.85 7.872 XX 888 296
100000 Coil By Pass Factor 0.10 3.25
CFM / Person 15 2
130 People 1 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 112.85 32 12 -17.92 0.55 1982 742 -1112
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 160 73 -56
1 People Nos 337 337 337 337
3.25 4.36 2545 11092 11092 11092
0.24 2545 603 603 603
3.41 962 962 962
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
15135 13809 11825
15% 2270 2071 1774
17406 15880 13599
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 75 260 -68
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 488 673 345
10% 49 67 34
537 740 379
ROOM TOTAL HEAT(RTH) 17943 16621 13978
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 40 1.08 T 36.9 17.0 -12.9 0.9 1436 659 -502
Latent 40 0.68 Gr / lb 28 95.62 -25.14 0.9 679 2341 -615
20058 19621 12861
Safety 3% 602 589 386
20660 20210 13246
TR 1.72 1.68 1.10
RSH 17406 15880 13599
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 17943 16621 13978
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.97 0.96 0.97
ADP 55.57 55.29 55.57
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 945 860 740
Sensible Heat Factor
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
(From tables/chart)
CALCUALTION Room Sensible Heat
Room Total Heat
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
TOTAL ROOM LATENT HEAT
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
0
Safety factor Supply duct leak loss + Safety factor
40
1
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
Lights 225.70 Watts
INTERNAL HEAT
People Gain / People
Equipement load (kW) HP
Outside air cfm DB diff
40
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Unit in Meters. :
Unit in Ft. :
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Fresh Air Selection
Room Name COATING
26 Monsoon
Difference
Blower Load (HP)
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
Summer
DESIGN CONDITIONS
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Inside Conditions
DOCUMENT NO:- 0
PARAMETER
Outside Conditions
Summer
23.02 53
Winter
945 860 740 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
35.31257736
36.94 78.08 XX 27.72 Volume 888 F.A as per ACPH 30
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 40
Room Number GF-16
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.87 2.71 XX 10.49 2.40 XX 25 503
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
12.69 8.89 XX 112.85 7.872 XX 888 296
100000 Coil By Pass Factor 0.10 3.3
CFM / Person 15 2
130 People 1 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 112.85 32 12 -17.92 0.55 1982 742 -1112
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 160 73 -56
1 People Nos 337 337 337 337
3.25 4.36 2545 11092 11092 11092
0.24 2545 603 603 603
3.41 962 962 962
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
15135 13809 11825
15% 2270 2071 1774
17406 15880 13599
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 75 260 -68
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 488 673 345
10% 49 67 34
537 740 379
ROOM TOTAL HEAT(RTH) 17943 16621 13978
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 40 1.08 T 36.9 17.0 -12.9 0.9 1436 659 -502
Latent 40 0.68 Gr / lb 28 95.62 -25.14 0.9 679 2341 -615
20058 19621 12861
Safety 3% 602 589 386
20660 20210 13246
TR 1.72 1.68 1.10
RSH 17406 15880 13599
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 17943 16621 13978
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.97 0.96 0.97
ADP 55.57 55.29 55.57
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 945 860 740
Sensible Heat Factor
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
(From tables/chart)
CALCUALTION Room Sensible Heat
Room Total Heat
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
TOTAL ROOM LATENT HEAT
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
0
Safety factor Supply duct leak loss + Safety factor
40
1
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
Lights 225.70 Watts
INTERNAL HEAT
People Gain / People
Equipement load (kW) HP
Outside air cfm DB diff
40
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Unit in Meters. :
Unit in Ft. :
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Fresh Air Selection
Room Name MILLING SHIFTING N BLENDING
26 Monsoon
Difference
Blower Load (HP)
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
Summer
DESIGN CONDITIONS
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Inside Conditions
DOCUMENT NO:- 0
PARAMETER
Outside Conditions
Summer
23.02 53
Winter
945 860 740 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
35.83725648
36.94 78.08 XX 27.72 Volume 911 F.A as per ACPH 30
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 40
Room Number GF-17
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.87 2.78 XX 10.76 2.40 XX 26 516
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
12.69 9.12 XX 115.76 7.872 XX 911 304
100000 Coil By Pass Factor 0.10 2.4
CFM / Person 15 2
130 People 1 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 115.76 32 12 -17.92 0.55 2034 761 -1141
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 160 73 -56
1 People Nos 337 337 337 337
2.39 3.20 2545 8152 8152 8152
0.24 2545 618 618 618
3.41 987 987 987
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
12288 10929 8898
15% 1843 1639 1335
14131 12569 10232
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 75 260 -68
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 488 673 345
10% 49 67 34
537 740 379
ROOM TOTAL HEAT(RTH) 14668 13309 10612
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 40 1.08 T 36.9 17.0 -12.9 0.9 1436 659 -502
Latent 40 0.68 Gr / lb 28 95.62 -25.14 0.9 679 2341 -615
16783 16309 9494
Safety 3% 503 489 285
17286 16799 9779
TR 1.44 1.40 0.81
RSH 14131 12569 10232
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 14668 13309 10612
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.96 0.94 0.96
ADP 55.43 55.14 55.43
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 770 685 555
Sensible Heat Factor
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
(From tables/chart)
CALCUALTION Room Sensible Heat
Room Total Heat
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
TOTAL ROOM LATENT HEAT
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
0
Safety factor Supply duct leak loss + Safety factor
40
1
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
Lights 231.53 Watts
INTERNAL HEAT
People Gain / People
Equipement load (kW) HP
Outside air cfm DB diff
40
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Unit in Meters. :
Unit in Ft. :
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Fresh Air Selection
Room Name COMPRESSION
26 Monsoon
Difference
Blower Load (HP)
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
Summer
DESIGN CONDITIONS
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Inside Conditions
DOCUMENT NO:- 0
PARAMETER
Outside Conditions
Summer
23.02 53
Winter
770 685 555 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
34.78789824
36.94 78.08 XX 27.72 Volume 865 F.A as per ACPH 29
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 35
Room Number GF-02
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.87 2.64 XX 10.2168 2.40 XX 25 490
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
12.69 8.6592 XX 109.93 7.872 XX 865 288
100000 Coil By Pass Factor 0.10 3.67
CFM / Person 15 2
130 People 1 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 109.93 32 12 -17.92 0.55 1931 723 -1083
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 99.85 32 12 -17.92 0.35 1116 418 -626
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 140 64 -49
1 People Nos 337 337 337 337
3.67 4.92 2545 12534 12534 12534
0.23 2545 587 587 587
3.41 937 937 937
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
17582 15600 12636
15% 2637 2340 1895
20219 17940 14532
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 66 228 -60
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 479 641 353
10% 48 64 35
527 705 388
ROOM TOTAL HEAT(RTH) 20746 18645 14920
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 35 1.08 T 36.9 17.0 -12.9 0.9 1257 577 -440
Latent 35 0.68 Gr / lb 28 95.62 -25.14 0.9 594 2048 -538
22597 21270 13942
Safety 3% 678 638 418
23274 21908 14361
TR 1.94 1.83 1.20
RSH 20219 17940 14532
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 20746 18645 14920
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.97 0.96 0.97
ADP 55.57 55.43 55.57
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 1095 975 790
Sensible Heat Factor
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
(From tables/chart)
CALCUALTION Room Sensible Heat
Room Total Heat
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
TOTAL ROOM LATENT HEAT
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
0
Safety factor Supply duct leak loss + Safety factor
35
1
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
Lights 219.87 Watts
INTERNAL HEAT
People Gain / People
Equipement load (kW) HP
Outside air cfm DB diff
35
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Unit in Meters. :
Unit in Ft. :
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Fresh Air Selection
Room Name PACKING
26 Monsoon
Difference
Blower Load (HP)
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
Summer
DESIGN CONDITIONS
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Inside Conditions
DOCUMENT NO:- 0
PARAMETER
Outside Conditions
Summer
23.02 53
Winter
1095 975 790 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- AHU 04
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
33.56784288
36.94 78.08 XX 27.72 Volume 1468 F.A as per ACPH 73
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 75
Room Number GF-19
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
6.06 2.86 XX 17.3316 2.40 XX 42 1248
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
19.88 9.3808 XX 186.49 7.872 XX 1468 734
100000 Coil By Pass Factor 0.10 0.00
CFM / Person 15 3
130 People 0 Pressure 25 Room Air Changes/Hour 30
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 186.49 32 12 -17.92 0.55 3276 1227 -1838
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 299 137 -105
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.59 2545 1494 1494 1494
3.41 1590 1590 1590
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
6659 4448 1141
15% 999 667 171
7658 5115 1312
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 141 488 -128
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 141 488 -128
10% 14 49 -13
156 536 -141
ROOM TOTAL HEAT(RTH) 7813 5651 1171
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 75 1.08 T 36.9 17.0 -12.9 0.9 2693 1236 -942
Latent 75 0.68 Gr / lb 28 95.62 -25.14 0.9 1272 4389 -1154
11779 11277 -925
Safety 3% 353 338 -28
12132 11615 -952
TR 1.01 0.97 -0.08
RSH 7658 5115 1312
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 7813 5651 1171
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.98 0.91 1.12
ADP 56.00 54.50 56.00
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 415 280 75
Sensible Heat Factor
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
(From tables/chart)
CALCUALTION Room Sensible Heat
Room Total Heat
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
TOTAL ROOM LATENT HEAT
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
0
Safety factor Supply duct leak loss + Safety factor
75
0
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
Lights 372.98 Watts
INTERNAL HEAT
People Gain / People
Equipement load (kW) HP
Outside air cfm DB diff
75
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Unit in Meters. :
Unit in Ft. :
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Fresh Air Selection
Room Name INPROCESS STORAGE
26 Monsoon
Difference
Blower Load (HP)
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
Summer
DESIGN CONDITIONS
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Inside Conditions
DOCUMENT NO:- 0
PARAMETER
Outside Conditions
Summer
23.02 53
Winter
734 734 734 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- AHU 4A
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 2
cfm /Person
+0.18*Sq.ft
47.4312
36.94 78.08 XX 27.72 Volume 762 F.A as per ACPH 25
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 50
Room Number GF-20
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.00 3.00 XX 9 2.40 XX 22 432
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
9.84 9.84 XX 96.84 7.872 XX 762 254
100000 Coil By Pass Factor 0.10 2.39
CFM / Person 15 2
130 People 2 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 96.84 32 12 -17.92 0.55 1701 637 -954
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 199 92 -70
2 People Nos 337 674 674 674
2.39 3.20 2545 8152 8152 8152
0.56 2545 1425 1425 1425
3.41 826 826 826
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
12977 11805 10052
15% 1947 1771 1508
14924 13576 11560
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 94 325 -85
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 826 826 826
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 920 1151 741
10% 92 115 74
1012 1266 815
ROOM TOTAL HEAT(RTH) 15936 14842 12375
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 50 1.08 T 36.9 17.0 -12.9 0.9 1795 824 -628
Latent 50 0.68 Gr / lb 28 95.62 -25.14 0.9 848 2926 -769
18580 18593 10978
Safety 3% 557 558 329
19137 19150 11307
TR 1.59 1.60 0.94
RSH 14924 13576 11560
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 15936 14842 12375
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.94 0.91 0.93
ADP 55.00 54.67 55.00
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 810 740 630
Sensible Heat Factor
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
(From tables/chart)
CALCUALTION Room Sensible Heat
Room Total Heat
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
TOTAL ROOM LATENT HEAT
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
0
Safety factor Supply duct leak loss + Safety factor
50
2
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
Lights 193.68 Watts
INTERNAL HEAT
People Gain / People
Equipement load (kW) HP
Outside air cfm DB diff
50
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Unit in Meters. :
Unit in Ft. :
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Fresh Air Selection
Room Name CAPSULATION
26 Monsoon
Difference
Blower Load (HP)
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
Summer
DESIGN CONDITIONS
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Inside Conditions
DOCUMENT NO:- 0
PARAMETER
Outside Conditions
Summer
23.02 53
Winter
810 740 630 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 2
cfm /Person
+0.18*Sq.ft
47.314992
36.94 78.08 XX 27.72 Volume 757 F.A as per ACPH 25
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 50
Room Number GF-21
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
2.98 3.00 XX 8.94 2.40 XX 21 429
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
9.77 9.84 XX 96.19 7.872 XX 757 252
100000 Coil By Pass Factor 0.10 3.58
CFM / Person 15 2
130 People 2 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 96.19 32 12 -17.92 0.55 1690 633 -948
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 199 92 -70
2 People Nos 337 674 674 674
3.58 4.79 2545 12201 12201 12201
0.80 2545 2035 2035 2035
3.41 820 820 820
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
17620 16455 14712
15% 2643 2468 2207
20262 18923 16919
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 94 325 -85
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 826 826 826
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 920 1151 741
10% 92 115 74
1012 1266 815
ROOM TOTAL HEAT(RTH) 21275 20189 17734
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 50 1.08 T 36.9 17.0 -12.9 0.9 1795 824 -628
Latent 50 0.68 Gr / lb 28 95.62 -25.14 0.9 848 2926 -769
23918 23939 16337
Safety 3% 718 718 490
24636 24657 16827
TR 2.05 2.05 1.40
RSH 20262 18923 16919
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 21275 20189 17734
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.95 0.94 0.95
ADP 55.29 55.00 55.29
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 1100 1025 920
Sensible Heat Factor
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
(From tables/chart)
CALCUALTION Room Sensible Heat
Room Total Heat
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
TOTAL ROOM LATENT HEAT
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
0
Safety factor Supply duct leak loss + Safety factor
50
2
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
Lights 192.39 Watts
INTERNAL HEAT
People Gain / People
Equipement load (kW) HP
Outside air cfm DB diff
50
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Unit in Meters. :
Unit in Ft. :
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Fresh Air Selection
Room Name PALETIZATION N COATING\
26 Monsoon
Difference
Blower Load (HP)
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
Summer
DESIGN CONDITIONS
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Inside Conditions
DOCUMENT NO:- 0
PARAMETER
Outside Conditions
Summer
23.02 53
Winter
1100 1025 920 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
33.00759168
36.94 78.08 XX 27.72 Volume 788 F.A as per ACPH 26
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 35
Room Number GF-22
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.12 2.98 XX 9.2976 2.40 XX 22 446
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
10.23 9.7744 XX 100.04 7.872 XX 788 263
100000 Coil By Pass Factor 0.10 2.39
CFM / Person 15 2
130 People 1 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 100.04 32 12 -17.92 0.55 1757 658 -986
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 140 64 -49
1 People Nos 337 337 337 337
2.39 3.20 2545 8152 8152 8152
0.56 2545 1425 1425 1425
3.41 853 853 853
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
12664 11489 9732
15% 1900 1723 1460
14564 13213 11192
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 66 228 -60
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 479 641 353
10% 48 64 35
527 705 388
ROOM TOTAL HEAT(RTH) 15091 13917 11580
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 35 1.08 T 36.9 17.0 -12.9 0.9 1257 577 -440
Latent 35 0.68 Gr / lb 28 95.62 -25.14 0.9 594 2048 -538
16941 16542 10602
Safety 3% 508 496 318
17449 17039 10920
TR 1.45 1.42 0.91
RSH 14564 13213 11192
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 15091 13917 11580
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.97 0.95 0.97
ADP 55.43 55.14 55.43
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 790 720 610
(From tables/chart)
DOCUMENT NO:- 0
Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26
Inside Conditions Fresh Air Selection
Difference
Summer
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
ROOM DATA
Room Name LIQUID PREP
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
HP
INTERNAL HEAT
Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Filtration
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TOTAL ROOM SENSIBLE HEAT (RSH)
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
200.08 Watts
People
(SELECTED ADP)
Sensible Heat Factor
CALCUALTION
Gain / People
1
0
Room Total Heat
35
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
ROOM SENSIBLE HEAT SUB TOTAL
Equipement load (kW)
Lights
35
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
Blower Load (HP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
Safety factor Supply duct leak loss + Safety factor
GRAND TOTAL HEAT
Room Sensible Heat
790 720 610 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
32.1707004
36.94 78.08 XX 27.72 Volume 751 F.A as per ACPH 25
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 35
Room Number GF-23
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
2.98 2.98 XX 8.8655 2.40 XX 21 426
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
9.76 9.7744 XX 95.39 7.872 XX 751 250
100000 Coil By Pass Factor 0.10 1.95
CFM / Person 15 2
130 People 1 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 95.39 32 12 -17.92 0.55 1676 627 -940
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 140 64 -49
1 People Nos 337 337 337 337
1.95 2.61 2545 6655 6655 6655
0.48 2545 1221 1221 1221
3.41 813 813 813
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
10842 9718 8037
15% 1626 1458 1206
12468 11176 9243
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 66 228 -60
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 479 641 353
10% 48 64 35
527 705 388
ROOM TOTAL HEAT(RTH) 12995 11880 9631
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 35 1.08 T 36.9 17.0 -12.9 0.9 1257 577 -440
Latent 35 0.68 Gr / lb 28 95.62 -25.14 0.9 594 2048 -538
14845 14506 8653
Safety 3% 445 435 260
15291 14941 8913
TR 1.27 1.25 0.74
RSH 12468 11176 9243
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 12995 11880 9631
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.96 0.94 0.96
ADP 55.29 55.14 55.29
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 680 610 505
(From tables/chart)
DOCUMENT NO:- 0
Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26
Inside Conditions Fresh Air Selection
Difference
Summer
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
ROOM DATA
Room Name IPQC LAB
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
HP
INTERNAL HEAT
Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Filtration
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TOTAL ROOM SENSIBLE HEAT (RSH)
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
190.79 Watts
People
(SELECTED ADP)
Sensible Heat Factor
CALCUALTION
Gain / People
1
0
Room Total Heat
35
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
ROOM SENSIBLE HEAT SUB TOTAL
Equipement load (kW)
Lights
35
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
Blower Load (HP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
Safety factor Supply duct leak loss + Safety factor
GRAND TOTAL HEAT
Room Sensible Heat
680 610 505 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
28.354752
36.94 78.08 XX 27.72 Volume 1240 F.A as per ACPH 41
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 45
Room Number GF-24
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
6.10 2.40 XX 14.6 2.40 XX 35 703
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
20.01 7.872 XX 157.53 7.872 XX 1240 413
100000 Coil By Pass Factor 0.10 0.00
CFM / Person 15 2
130 People 0 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 157.53 32 12 -17.92 0.55 2767 1036 -1553
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 180 82 -63
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.33 2545 841 841 841
3.41 1343 1343 1343
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
5131 3303 569
15% 770 495 85
5901 3798 654
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 85 293 -77
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 85 293 -77
10% 8 29 -8
93 322 -85
ROOM TOTAL HEAT(RTH) 5994 4120 570
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 45 1.08 T 36.9 17.0 -12.9 0.9 1616 742 -565
Latent 45 0.68 Gr / lb 28 95.62 -25.14 0.9 763 2633 -692
8373 7495 -688
Safety 3% 251 225 -21
8624 7720 -709
TR 0.72 0.64 -0.06
RSH 5901 3798 654
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 5994 4120 570
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.98 0.92 1.15
ADP 56.00 54.83 56.00
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 320 210 40
(From tables/chart)
DOCUMENT NO:- 0
Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26
Inside Conditions Fresh Air Selection
Difference
Summer
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
ROOM DATA
Room Name TOOL ROOM & CLEAN EQUPMENT ROOM
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
HP
INTERNAL HEAT
Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Filtration
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TOTAL ROOM SENSIBLE HEAT (RSH)
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
315.05 Watts
People
(SELECTED ADP)
Sensible Heat Factor
CALCUALTION
Gain / People
0
0
Room Total Heat
45
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
ROOM SENSIBLE HEAT SUB TOTAL
Equipement load (kW)
Lights
45
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
Blower Load (HP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
Safety factor Supply duct leak loss + Safety factor
GRAND TOTAL HEAT
Room Sensible Heat
413 413 413 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
53.52508248
36.94 78.08 XX 27.72 Volume 1685 F.A as per ACPH 56
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 60
Room Number GF-25
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
6.36 2.32 XX 19.8911 2.40 XX 48 955
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
20.86 7.6096 XX 214.03 7.872 XX 1685 562
100000 Coil By Pass Factor 0.10 3.25
CFM / Person 15 2
130 People 1 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 214.03 32 12 -17.92 0.55 3760 1408 -2109
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 206.40 32 12 -17.92 0.35 2307 864 -1295
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 239 110 -84
1 People Nos 337 337 337 337
3.25 4.36 2545 11092 11092 11092
0.96 2545 2442 2442 2442
3.41 1825 1825 1825
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
22002 18077 12208
15% 3300 2712 1831
25303 20789 14039
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 113 390 -103
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 526 803 310
10% 53 80 31
579 883 341
ROOM TOTAL HEAT(RTH) 25881 21672 14381
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 60 1.08 T 36.9 17.0 -12.9 0.9 2154 989 -753
Latent 60 0.68 Gr / lb 28 95.62 -25.14 0.9 1018 3511 -923
29053 26173 12704
Safety 3% 872 785 381
29925 26958 13085
TR 2.49 2.25 1.09
RSH 25303 20789 14039
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 25881 21672 14381
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.98 0.96 0.98
ADP 55.57 55.29 55.57
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 1375 1130 765
(From tables/chart)
DOCUMENT NO:- 0
Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26
Inside Conditions Fresh Air Selection
Difference
Summer
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
ROOM DATA
Room Name WASHING AND DRYING
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
HP
INTERNAL HEAT
Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
Filtration
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TOTAL ROOM SENSIBLE HEAT (RSH)
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
428.06 Watts
People
(SELECTED ADP)
Sensible Heat Factor
CALCUALTION
Gain / People
1
0
Room Total Heat
60
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
ROOM SENSIBLE HEAT SUB TOTAL
Equipement load (kW)
Lights
60
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
Blower Load (HP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
Safety factor Supply duct leak loss + Safety factor
GRAND TOTAL HEAT
Room Sensible Heat
1375 1130 765 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- AHU 05
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
35.71880179
36.94 78.08 XX 27.72 Volume 906 F.A as per ACPH 30
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 40
Room Number GF-26
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
6.00 10.50 XX 10.7 2.40 XX 26 513
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
19.68 34.44 XX 115.10 7.872 XX 906 302
100000 Coil By Pass Factor 0.10 5.50
CFM / Person 15 2
130 People 1 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 115.10 32 12 -17.92 0.55 2022 757 -1134
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 160 73 -56
1 People Nos 337 337 337 337
5.50 7.38 2545 18771 18771 18771
1.40 2545 3562 3562 3562
3.41 981 981 981
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
25832 24481 22460
15% 3875 3672 3369
29707 28153 25829
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 75 260 -68
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 488 673 345
10% 49 67 34
537 740 379
ROOM TOTAL HEAT(RTH) 30244 28894 26208
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 40 1.08 T 36.9 17.0 -12.9 0.9 1436 659 -502
Latent 40 0.68 Gr / lb 28 95.62 -25.14 0.9 679 2341 -615
32359 31894 25091
Safety 3% 971 957 753
33330 32851 25843
TR 2.78 2.74 2.15
RSH 29707 28153 25829
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 30244 28894 26208
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.98 0.97 0.99
ADP 56.00 55.57 56.00
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 1610 1525 1400
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
1
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
40
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 230.21 Watts
Blower Load (HP)
Outside air cfm DB diff
40
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name GRANULATON
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
1610 1525 1400 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
35.19710534
36.94 78.08 XX 27.72 Volume 883 F.A as per ACPH 29
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 40
Room Number GF-27
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.02 3.39 XX 10.42808 2.40 XX 25 501
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
9.91 11.1192 XX 112.21 7.872 XX 883 294
100000 Coil By Pass Factor 0.10 2.75
CFM / Person 15 2
130 People 1 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 112.21 32 12 -17.92 0.55 1971 738 -1106
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 160 73 -56
1 People Nos 337 337 337 337
2.75 3.69 2545 9385 9385 9385
0.72 2545 1832 1832 1832
3.41 957 957 957
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
14641 13322 11349
15% 2196 1998 1702
16838 15320 13051
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 75 260 -68
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 488 673 345
10% 49 67 34
537 740 379
ROOM TOTAL HEAT(RTH) 17375 16061 13430
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 40 1.08 T 36.9 17.0 -12.9 0.9 1436 659 -502
Latent 40 0.68 Gr / lb 28 95.62 -25.14 0.9 679 2341 -615
19490 19061 12313
Safety 3% 585 572 369
20074 19633 12682
TR 1.67 1.64 1.06
RSH 16838 15320 13051
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 17375 16061 13430
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.97 0.95 0.97
ADP 55.43 55.29 55.57
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 915 830 710
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
1
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
40
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 224.41 Watts
Blower Load (HP)
Outside air cfm DB diff
40
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name COATING
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
915 830 710 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
35.19710534
36.94 78.08 XX 27.72 Volume 883 F.A as per ACPH 29
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 40
Room Number GF-28
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
2.98 3.38 XX 10.4 2.40 XX 25 501
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
9.77 11.0864 XX 112.21 7.872 XX 883 294
100000 Coil By Pass Factor 0.10 4.04
CFM / Person 15 2.0
130 People 1 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 112.21 32 12 -17.92 0.55 1971 738 -1106
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 160 73 -56
1 People Nos 337 337 337 337
4.04 5.42 2545 13796 13796 13796
0.96 2545 2442 2442 2442
3.41 957 957 957
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
19663 18344 16371
15% 2949 2752 2456
22612 21095 18826
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 75 260 -68
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 488 673 345
10% 49 67 34
537 740 379
ROOM TOTAL HEAT(RTH) 23150 21836 19205
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 40 1.08 T 36.9 17.0 -12.9 0.9 1436 659 -502
Latent 40 0.68 Gr / lb 28 95.62 -25.14 0.9 679 2341 -615
25264 24836 18087
Safety 3% 758 745 543
26022 25581 18630
TR 2.17 2.13 1.55
RSH 22612 21095 18826
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 23150 21836 19205
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.98 0.97 0.98
ADP 55.57 55.43 56.00
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 1225 1145 1020
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
1
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
40
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 224.41 Watts
Blower Load (HP)
Outside air cfm DB diff
40
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name DRY GRANULATION
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
1225 1145 1020 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 2
cfm /Person
+0.18*Sq.ft
50.19710534
36.94 78.08 XX 27.72 Volume 883 F.A as per ACPH 29
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 55
Room Number GF-29
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.85 2.71 XX 10.42808 2.40 XX 25 501
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
12.62 8.8888 XX 112.21 7.872 XX 883 294
100000 Coil By Pass Factor 0.10 3.03
CFM / Person 15 2
130 People 2 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 112.21 32 12 -17.92 0.55 1971 738 -1106
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 219 101 -77
2 People Nos 337 674 674 674
3.03 4.06 2545 10324 10324 10324
0.80 2545 2035 2035 2035
3.41 957 957 957
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
16180 14828 12807
15% 2427 2224 1921
18607 17053 14728
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 104 358 -94
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 826 826 826
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 930 1184 732
10% 93 118 73
1023 1302 805
ROOM TOTAL HEAT(RTH) 19630 18355 15533
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 55 1.08 T 36.9 17.0 -12.9 0.9 1975 907 -691
Latent 55 0.68 Gr / lb 28 95.62 -25.14 0.9 933 3219 -846
22538 22480 13996
Safety 3% 676 674 420
23214 23154 14416
TR 1.93 1.93 1.20
RSH 18607 17053 14728
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 19630 18355 15533
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.95 0.93 0.95
ADP 55.14 54.83 55.14
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 1010 925 800
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
2
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
55
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 224.41 Watts
Blower Load (HP)
Outside air cfm DB diff
55
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name COMPRESSION
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
1010 925 800 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 2
cfm /Person
+0.18*Sq.ft
50.42068954
36.94 78.08 XX 27.72 Volume 893 F.A as per ACPH 30
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 55
Room Number GF-30
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.85 2.74 XX 10.5 2.40 XX 25 506
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
12.62 8.9872 XX 113.45 7.872 XX 893 298
100000 Coil By Pass Factor 0.10 3.03
CFM / Person 15 2.0
130 People 2 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 113.45 32 12 -17.92 0.55 1993 746 -1118
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 106.17 32 12 -17.92 0.35 1187 444 -666
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 219 101 -77
2 People Nos 337 674 674 674
3.03 4.06 2545 10324 10324 10324
0.88 2545 2239 2239 2239
3.41 967 967 967
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
17603 15495 12343
15% 2640 2324 1851
20243 17819 14194
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 104 358 -94
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 826 826 826
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 930 1184 732
10% 93 118 73
1023 1302 805
ROOM TOTAL HEAT(RTH) 21266 19121 15000
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 55 1.08 T 36.9 17.0 -12.9 0.9 1975 907 -691
Latent 55 0.68 Gr / lb 28 95.62 -25.14 0.9 933 3219 -846
24174 23247 13463
Safety 3% 725 697 404
24899 23944 13867
TR 2.07 2.00 1.16
RSH 20243 17819 14194
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 21266 19121 15000
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.95 0.93 0.95
ADP 55.29 55.00 55.14
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 1100 965 770
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
2
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
55
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 226.90 Watts
Blower Load (HP)
Outside air cfm DB diff
55
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name COMPRESSION
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
1100 965 770 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- AHU 07
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 20
cfm /Person
+0.18*Sq.ft
422.0184
36.94 78.08 XX 27.72 Volume 5336 F.A as per ACPH 89
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 425
Room Number GF-38
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
#REF! #REF! XX 63 2.40 XX 151 3024
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
#REF! #REF! XX 677.88 7.872 XX 5336 1779
NA Coil By Pass Factor 0.10 7.70
CFM / Person 15 1
65 People 20 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 677.88 32 12 -17.92 0.55 11908 4459 -6681
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 1696 778 -593
20 People Nos 337 6740 6740 6740
7.70 10.33 2545 26279 26279 26279
1.28 2545 3256 3256 3256
3.41 5779 5779 5779
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
55658 47292 34780
15% 8349 7094 5217
64007 54386 39997
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 801 2763 -727
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 8260 8260 8260
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9061 11023 7533
10% 906 1102 753
9967 12126 8287
ROOM TOTAL HEAT(RTH) 73974 66511 48284
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 425 1.08 T 36.9 17.0 -12.9 0.9 15260 7006 -5337
Latent 425 0.68 Gr / lb 28 95.62 -25.14 0.9 7210 24871 -6539
96444 98388 36408
Safety 3% 2893 2952 1092
99337 101340 37500
TR 8.28 8.44 3.12
RSH 64007 54386 39997
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 73974 66511 48284
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.87 0.82 0.83
ADP 53.80 52.67 53.00
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 3470 2945 2170
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
20
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
425
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 1355.76 Watts
Blower Load (HP)
Outside air cfm DB diff
425
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name #REF!
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
3470 2945 2170 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
34.82857104
36.94 78.08 XX 27.72 Volume 867 F.A as per ACPH 14
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 35
Room Number GF-39
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
#REF! #REF! XX 10.2 2.40 XX 25 491
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
#REF! #REF! XX 110.16 7.872 XX 867 289
NA Coil By Pass Factor 0.10 0.15
CFM / Person 15 1.0
65 People 1 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 110.16 32 12 -17.92 0.55 1935 725 -1086
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 77.40 32 12 -17.92 0.35 865 324 -485
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 140 64 -49
1 People Nos 337 337 337 337
0.15 0.20 2545 512 512 512
0.12 2545 294 294 294
3.41 939 939 939
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
5022 3195 462
15% 753 479 69
5776 3674 531
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 66 228 -60
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 479 641 353
10% 48 64 35
527 705 388
ROOM TOTAL HEAT(RTH) 6302 4379 920
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 35 1.08 T 36.9 17.0 -12.9 0.9 1257 577 -440
Latent 35 0.68 Gr / lb 28 95.62 -25.14 0.9 594 2048 -538
8153 7004 -58
Safety 3% 245 210 -2
8397 7214 -60
TR 0.70 0.60 0.00
RSH 5776 3674 531
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 6302 4379 920
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.92 0.84 0.58
ADP 54.67 53.20 #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 315 200 30
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
1
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
35
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 220.32 Watts
Blower Load (HP)
Outside air cfm DB diff
35
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name #REF!
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
315 289 289 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
34.50822432
36.94 78.08 XX 27.72 Volume 853 F.A as per ACPH 14
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 35
Room Number GF-40
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
#REF! #REF! XX 10.0724 2.40 XX 24 483
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
#REF! #REF! XX 108.38 7.872 XX 853 284
NA Coil By Pass Factor 0.10 0.15
CFM / Person 15 1
65 People 1 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 108.38 32 12 -17.92 0.55 1904 713 -1068
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 77.40 32 12 -17.92 0.35 865 324 -485
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 140 64 -49
1 People Nos 337 337 337 337
0.15 0.20 2545 512 512 512
0.11 2545 289 289 289
3.41 924 924 924
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
4971 3163 460
15% 746 474 69
5717 3638 529
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 66 228 -60
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 479 641 353
10% 48 64 35
527 705 388
ROOM TOTAL HEAT(RTH) 6244 4342 917
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 35 1.08 T 36.9 17.0 -12.9 0.9 1257 577 -440
Latent 35 0.68 Gr / lb 28 95.62 -25.14 0.9 594 2048 -538
8094 6968 -61
Safety 3% 243 209 -2
8337 7177 -63
TR 0.69 0.60 -0.01
RSH 5717 3638 529
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 6244 4342 917
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.92 0.84 0.58
ADP 54.67 53.20 #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 310 200 30
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
1
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
35
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 216.76 Watts
Blower Load (HP)
Outside air cfm DB diff
35
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name #REF!
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
310 284 284 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- AHU 08
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 2
cfm /Person
+0.18*Sq.ft
51.29719806
36.94 78.08 XX 27.72 Volume 931 F.A as per ACPH 16
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 55
Room Number GF-41
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
4.21 2.62 XX 11.0 2.40 XX 26 528
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
13.79 8.5772 XX 118.32 7.872 XX 931 310
NA Coil By Pass Factor 0.10 1.95
CFM / Person 15 1.0
65 People 2 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.11 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 118.32 32 12 -17.92 0.55 2078 778 -1166
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 219 101 -77
2 People Nos 337 674 674 674
1.95 2.61 2545 6655 6655 6655
0.24 2545 611 611 611
3.41 1009 1009 1009
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
11246 9827 7705
15% 1687 1474 1156
12933 11301 8861
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 104 358 -94
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 826 826 826
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 930 1184 732
10% 93 118 73
1023 1302 805
ROOM TOTAL HEAT(RTH) 13956 12603 9666
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 55 1.08 T 36.9 17.0 -12.9 0.9 1975 907 -691
Latent 55 0.68 Gr / lb 28 95.62 -25.14 0.9 933 3219 -846
16864 16729 8129
Safety 3% 506 502 244
17370 17231 8373
TR 1.45 1.44 0.70
RSH 12933 11301 8861
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 13956 12603 9666
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.93 0.90 0.92
ADP 54.83 54.33 54.67
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 705 615 480
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
2
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
55
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 236.64 Watts
Blower Load (HP)
Outside air cfm DB diff
55
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name ICP
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
705 615 480 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
36.94873758
36.94 78.08 XX 27.72 Volume 960 F.A as per ACPH 16
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 40
Room Number GF-42
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
4.21 2.70 XX 11.332475 2.40 XX 27 544
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
13.79 8.8396 XX 121.94 7.872 XX 960 320
NA Coil By Pass Factor 0.10 1.50
CFM / Person 15 1
65 People 1 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 121.94 32 12 -17.92 0.55 2142 802 -1202
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 160 73 -56
1 People Nos 337 337 337 337
1.50 2.00 2545 5102 5102 5102
0.18 2545 458 458 458
3.41 1040 1040 1040
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
9238 7812 5679
15% 1386 1172 852
10624 8984 6531
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 75 260 -68
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 488 673 345
10% 49 67 34
537 740 379
ROOM TOTAL HEAT(RTH) 11161 9724 6910
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 40 1.08 T 36.9 17.0 -12.9 0.9 1436 659 -502
Latent 40 0.68 Gr / lb 28 95.62 -25.14 0.9 679 2341 -615
13276 12724 5792
Safety 3% 398 382 174
13674 13106 5966
TR 1.14 1.09 0.50
RSH 10624 8984 6531
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 11161 9724 6910
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.95 0.92 0.95
ADP 55.29 54.83 55.14
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 580 490 355
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
1
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
40
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 243.87 Watts
Blower Load (HP)
Outside air cfm DB diff
40
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name GC CABIN
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
580 490 355 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
34.05753096
36.94 78.08 XX 27.72 Volume 833 F.A as per ACPH 14
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 35
Room Number GF-43
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
4.21 2.34 XX 9.8 2.40 XX 24 472
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
13.79 7.6752 XX 105.88 7.872 XX 833 278
NA Coil By Pass Factor 0.10 1.14
CFM / Person 15 1.0
65 People 1 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 105.88 32 12 -17.92 0.55 1860 696 -1044
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 140 64 -49
1 People Nos 337 337 337 337
1.14 1.53 2545 3882 3882 3882
0.16 2545 407 407 407
3.41 903 903 903
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
7528 6289 4436
15% 1129 943 665
8658 7233 5102
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 66 228 -60
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 479 641 353
10% 48 64 35
527 705 388
ROOM TOTAL HEAT(RTH) 9184 7937 5490
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 35 1.08 T 36.9 17.0 -12.9 0.9 1257 577 -440
Latent 35 0.68 Gr / lb 28 95.62 -25.14 0.9 594 2048 -538
11035 10562 4512
Safety 3% 331 317 135
11366 10879 4648
TR 0.95 0.91 0.39
RSH 8658 7233 5102
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 9184 7937 5490
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.94 0.91 0.93
ADP 55.14 54.67 54.83
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 470 395 280
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
1
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
35
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 211.75 Watts
Blower Load (HP)
Outside air cfm DB diff
35
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name GC SAMPLE PREP
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
470 395 280 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 3
cfm /Person
+0.18*Sq.ft
95.06266787
36.94 78.08 XX 27.72 Volume 2189 F.A as per ACPH 36
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 100
Room Number GF-44
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
4.21 6.15 XX 25.85 2.40 XX 62 1241
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
13.79 20.16 XX 278.13 7.872 XX 2189 730
NA Coil By Pass Factor 0.10 1.14
CFM / Person 15 1
65 People 3 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 278.13 32 12 -17.92 0.55 4886 1830 -2741
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 110.94 32 12 -17.92 0.35 1240 464 -696
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 399 183 -140
3 People Nos 337 1011 1011 1011
1.14 1.53 2545 3882 3882 3882
0.16 2545 407 407 407
3.41 2371 2371 2371
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
14196 10148 4095
15% 2129 1522 614
16326 11670 4709
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 188 650 -171
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 1239 1239 1239
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 1427 1889 1068
10% 143 189 107
1570 2078 1175
ROOM TOTAL HEAT(RTH) 17896 13749 5884
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 100 1.08 T 36.9 17.0 -12.9 0.9 3591 1649 -1256
Latent 100 0.68 Gr / lb 28 95.62 -25.14 0.9 1696 5852 -1539
23183 21249 3089
Safety 3% 695 637 93
23878 21887 3182
TR 1.99 1.82 0.27
RSH 16326 11670 4709
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 17896 13749 5884
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.91 0.85 0.80
ADP 54.67 53.40 52.33
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 885 635 255
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
3
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
100
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 556.25 Watts
Blower Load (HP)
Outside air cfm DB diff
100
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name BALANCE ROOM & WASH
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
885 730 730 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 2
cfm /Person
+0.18*Sq.ft
103.0715904
36.94 78.08 XX 27.72 Volume 3196 F.A as per ACPH 53
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 105
Room Number GF-48
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
15.72 2.40 XX 37.73 2.40 XX 91 1811
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
51.56 7.87 XX 405.95 7.872 XX 3196 1065
NA Coil By Pass Factor 0.10 0.0
CFM / Person 15 1
65 People 2 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 405.95 32 12 -17.92 0.55 7131 2670 -4001
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 458.21 32 12 -17.92 0.35 5122 1918 -2874
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 419 192 -147
2 People Nos 337 674 674 674
0.00 0.00 2545 0 0 0
0.20 2545 509 509 509
3.41 3461 3461 3461
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
17316 9424 -2378
15% 2597 1414 -357
19914 10838 -2735
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 198 683 -179
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 826 826 826
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 1024 1509 647
10% 102 151 65
1126 1660 711
ROOM TOTAL HEAT(RTH) 21040 12498 -2023
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 105 1.08 T 36.9 17.0 -12.9 0.9 3770 1731 -1319
Latent 105 0.68 Gr / lb 28 95.62 -25.14 0.9 1781 6145 -1615
26591 20373 -4958
Safety 3% 798 611 -149
27389 20984 -5106
TR 2.28 1.75 -0.43
RSH 19914 10838 -2735
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 21040 12498 -2023
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.95 0.87 1.35
ADP 55.14 53.80 56.00
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 1080 590 -145
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
2
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
105
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 811.91 Watts
Blower Load (HP)
Outside air cfm DB diff
105
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name CORRIDOR
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
1080 1065 1065 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
14.07201408
36.94 78.08 XX 27.72 Volume 615 F.A as per ACPH 10
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 15
Room Number GF-47
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.04 2.39 XX 7.27 2.40 XX 17 349
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
9.97 7.84 XX 78.18 7.872 XX 615 205
NA Coil By Pass Factor 0.10 0.0
CFM / Person 15 1
65 People 0 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 78.18 32 12 -17.92 0.55 1373 514 -771
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 85.14 32 12 -17.92 0.35 952 356 -534
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 60 27 -21
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.08 2545 209 209 209
3.41 666 666 666
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
3260 1773 -450
15% 489 266 -68
3749 2039 -518
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 28 98 -26
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 28 98 -26
10% 3 10 -3
31 107 -28
ROOM TOTAL HEAT(RTH) 3780 2147 -546
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 15 1.08 T 36.9 17.0 -12.9 0.9 539 247 -188
Latent 15 0.68 Gr / lb 28 95.62 -25.14 0.9 254 878 -231
4573 3272 -965
Safety 3% 137 98 -29
4711 3370 -994
TR 0.39 0.28 -0.08
RSH 3749 2039 -518
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 3780 2147 -546
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.99 0.95 0.95
ADP 56.00 55.29 55.14
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 205 115 -25
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
15
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 156.36 Watts
Blower Load (HP)
Outside air cfm DB diff
15
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name ANALYTIC CHANGE ROOM
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
205 205 205 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
99.94039764
36.94 78.08 XX 27.72 Volume 3715 F.A as per ACPH 62
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 100
Room Number GF-46
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
1.50 14.23 XX 43.86 2.40 XX 105 2105
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
4.90 46.67 XX 471.89 7.872 XX 3715 1238
NA Coil By Pass Factor 0.10 0.00
CFM / Person 15 1
65 People 1 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 85 12 -2 -27 0.35 358 -60 -805
wall (E) 32 26 12 -22 0.35 290 134 -246
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 471.89 32 12 -17.92 0.55 8290 3104 -4651
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 399 183 -140
1 People Nos 337 337 337 337
0.00 0.00 2545 0 0 0
0.20 2545 509 509 509
3.41 4023 4023 4023
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
14205 8230 -972
15% 2131 1235 -146
16336 9465 -1118
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 188 650 -171
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 601 1063 242
10% 60 106 24
662 1170 266
ROOM TOTAL HEAT(RTH) 16998 10634 -852
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 100 1.08 T 36.9 17.0 -12.9 0.9 3591 1649 -1256
Latent 100 0.68 Gr / lb 28 95.62 -25.14 0.9 1696 5852 -1539
22285 18135 -3646
Safety 3% 669 544 -109
22953 18679 -3755
TR 1.91 1.56 -0.31
RSH 16336 9465 -1118
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 16998 10634 -852
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.96 0.89 1.31
ADP 55.43 54.33 56.00
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 885 515 -60
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
1
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
100
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 943.78 Watts
Blower Load (HP)
Outside air cfm DB diff
100
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name CORRIDOR
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
1238 1238 1238 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- AHU 09
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 4
cfm /Person
+0.18*Sq.ft
73.68329832
36.94 78.08 XX 27.72 Volume 598 F.A as per ACPH 10
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 75
Room Number GF-49
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.10 2.28 XX 7.06 2.40 XX 17 339
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
10.17 7.48 XX 76.02 7.872 XX 598 199
NA Coil By Pass Factor 0.10 0.2
CFM / Person 15 1
65 People 4 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 76.02 32 12 -17.92 0.55 1335 500 -749
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 299 137 -105
4 People Nos 337 1348 1348 1348
0.15 0.20 2545 512 512 512
0.08 2545 203 203 203
3.41 648 648 648
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
4346 3348 1857
15% 652 502 279
4997 3851 2136
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 141 488 -128
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 1652 1652 1652
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 1793 2140 1524
10% 179 214 152
1973 2354 1676
ROOM TOTAL HEAT(RTH) 6970 6204 3812
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 75 1.08 T 36.9 17.0 -12.9 0.9 2693 1236 -942
Latent 75 0.68 Gr / lb 28 95.62 -25.14 0.9 1272 4389 -1154
10935 11830 1716
Safety 3% 328 355 51
11263 12185 1767
TR 0.94 1.02 0.15
RSH 4997 3851 2136
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 6970 6204 3812
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.72 0.62 0.56
ADP 49.00 #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 275 210 120
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
4
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
75
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 152.04 Watts
Blower Load (HP)
Outside air cfm DB diff
75
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name CABIN
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
275 210 199 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 3
cfm /Person
+0.18*Sq.ft
58.62150278
36.94 78.08 XX 27.72 Volume 596 F.A as per ACPH 10
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 60
Room Number GF-50
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.09 2.28 XX 7.03 2.40 XX 17 338
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
10.12 7.48 XX 75.68 7.872 XX 596 199
NA Coil By Pass Factor 0.10 3.2
CFM / Person 15 1
65 People 3 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 75.68 32 12 -17.92 0.55 1329 498 -746
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 239 110 -84
3 People Nos 337 1011 1011 1011
3.20 4.29 2545 10921 10921 10921
0.36 2545 916 916 916
3.41 645 645 645
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
15062 14101 12664
15% 2259 2115 1900
17321 16216 14563
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 113 390 -103
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 1239 1239 1239
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 1352 1629 1136
10% 135 163 114
1487 1792 1250
ROOM TOTAL HEAT(RTH) 18808 18008 15813
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 60 1.08 T 36.9 17.0 -12.9 0.9 2154 989 -753
Latent 60 0.68 Gr / lb 28 95.62 -25.14 0.9 1018 3511 -923
21981 22508 14136
Safety 3% 659 675 424
22640 23183 14561
TR 1.89 1.93 1.21
RSH 17321 16216 14563
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 18808 18008 15813
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.92 0.90 0.92
ADP 54.83 54.50 54.83
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 940 880 790
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
3
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
60
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 151.35 Watts
Blower Load (HP)
Outside air cfm DB diff
60
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name INSTRUMENT LAB
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
940 880 790 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 4
cfm /Person
+0.18*Sq.ft
94.809138
36.94 78.08 XX 27.72 Volume 1522 F.A as per ACPH 25
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 95
Room Number GF-51
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.25 5.53 XX 17.97 2.40 XX 43 863
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
10.66 18.14 XX 193.38 7.872 XX 1522 507
NA Coil By Pass Factor 0.10 3.25
CFM / Person 15 1
65 People 4 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 193.38 32 12 -17.92 0.55 3397 1272 -1906
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 379 174 -133
4 People Nos 337 1348 1348 1348
3.25 4.36 2545 11092 11092 11092
0.40 2545 1018 1018 1018
3.41 1649 1649 1649
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
18882 16552 13067
15% 2832 2483 1960
21714 19035 15028
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 179 618 -162
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 1652 1652 1652
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 1831 2270 1490
10% 183 227 149
2014 2497 1639
ROOM TOTAL HEAT(RTH) 23729 21532 16666
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 95 1.08 T 36.9 17.0 -12.9 0.9 3411 1566 -1193
Latent 95 0.68 Gr / lb 28 95.62 -25.14 0.9 1612 5559 -1462
28751 28657 14011
Safety 3% 863 860 420
29614 29517 14432
TR 2.47 2.46 1.20
RSH 21714 19035 15028
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 23729 21532 16666
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.92 0.88 0.90
ADP 54.67 54.17 54.50
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 1180 1035 815
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
4
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
95
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 386.77 Watts
Blower Load (HP)
Outside air cfm DB diff
95
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name DISSOLUTION LAB
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
1180 1035 815 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 6
cfm /Person
+0.18*Sq.ft
162.3627216
36.94 78.08 XX 27.72 Volume 3165 F.A as per ACPH 53
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 165
Room Number GF-52
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
6.23 6.00 XX 37.36 2.40 XX 90 1793
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
20.42 19.68 XX 402.02 7.872 XX 3165 1055
NA Coil By Pass Factor 0.10 3.2
CFM / Person 15 1
65 People 6 Pressure -- Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 402.02 32 12 -17.92 0.55 7062 2644 -3962
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 154.80 32 12 -17.92 0.35 1731 648 -971
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 658 302 -230
6 People Nos 337 2022 2022 2022
3.20 4.29 2545 10921 10921 10921
0.48 2545 1221 1221 1221
3.41 3427 3427 3427
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
27042 21186 12428
15% 4056 3178 1864
31099 24364 14292
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 311 1073 -282
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 2478 2478 2478
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 2789 3551 2196
10% 279 355 220
3068 3906 2416
ROOM TOTAL HEAT(RTH) 34167 28270 16708
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 165 1.08 T 36.9 17.0 -12.9 0.9 5924 2720 -2072
Latent 165 0.68 Gr / lb 28 95.62 -25.14 0.9 2799 9656 -2539
42890 40646 12097
Safety 3% 1287 1219 363
44177 41865 12460
TR 3.68 3.49 1.04
RSH 31099 24364 14292
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 34167 28270 16708
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.91 0.86 0.86
ADP 54.67 53.80 53.60
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 1685 1320 775
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
6
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
165
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 804.03 Watts
Blower Load (HP)
Outside air cfm DB diff
165
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name SAMPLE PREP ROOM
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
1685 1320 1055 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- AHU 06
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
37.776768
36.94 78.08 XX 27.72 Volume 996 F.A as per ACPH 33
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 40
Room Number GF-34
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
4.20 2.80 XX 11.76 2.40 XX 28 564
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
13.78 9.18 XX 126.54 7.872 XX 996 332
100000 Coil By Pass Factor 0.10 2.3
CFM / Person 15 2
130 People 1 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 126.54 32 12 -17.92 0.55 2223 832 -1247
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 160 73 -56
1 People Nos 337 337 337 337
2.25 3.02 2545 7679 7679 7679
0.72 2545 1832 1832 1832
3.41 1079 1079 1079
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
13309 11832 9623
15% 1996 1775 1444
15305 13607 11067
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 75 260 -68
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 488 673 345
10% 49 67 34
537 740 379
ROOM TOTAL HEAT(RTH) 15842 14347 11446
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 40 1.08 T 36.9 17.0 -12.9 0.9 1436 659 -502
Latent 40 0.68 Gr / lb 28 95.62 -25.14 0.9 679 2341 -615
17957 17347 10328
Safety 3% 539 520 310
18496 17868 10638
TR 1.54 1.49 0.89
RSH 15305 13607 11067
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 15842 14347 11446
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.97 0.95 0.97
ADP 55.43 55.14 55.43
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 830 740 600
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
1
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
40
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 253.08 Watts
Blower Load (HP)
Outside air cfm DB diff
40
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name COATING
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
830 740 600 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
64.620816
36.94 78.08 XX 27.72 Volume 2170 F.A as per ACPH 72
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 75
Room Number GF-32
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
4.20 6.10 XX 25.62 2.40 XX 61 1230
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
13.78 20.01 XX 275.67 7.872 XX 2170 723
100000 Coil By Pass Factor 0.10 3.31
CFM / Person 15 2
130 People 1 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 275.67 32 12 -17.92 0.55 4843 1813 -2717
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 299 137 -105
1 People Nos 337 337 337 337
3.31 4.44 2545 11288 11288 11288
1.20 2545 3053 3053 3053
3.41 2350 2350 2350
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
22170 18979 14206
15% 3325 2847 2131
25495 21826 16337
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 141 488 -128
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 554 901 285
10% 55 90 28
610 991 313
ROOM TOTAL HEAT(RTH) 26105 22816 16650
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 75 1.08 T 36.9 17.0 -12.9 0.9 2693 1236 -942
Latent 75 0.68 Gr / lb 28 95.62 -25.14 0.9 1272 4389 -1154
30070 28442 14555
Safety 3% 902 853 437
30973 29295 14991
TR 2.58 2.44 1.25
RSH 25495 21826 16337
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 26105 22816 16650
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.98 0.96 0.98
ADP 55.57 55.29 56.00
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 1385 1185 885
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
1
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
75
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 551.34 Watts
Blower Load (HP)
Outside air cfm DB diff
75
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name MILLING SHIFTING GRANULATION DRY COATING
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
1385 1185 885 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
31.980894
36.94 78.08 XX 27.72 Volume 743 F.A as per ACPH 25
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 35
Room Number GF-33
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
4.18 2.10 XX 8.77 2.40 XX 21 421
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
13.69 6.89 XX 94.34 7.872 XX 743 248
100000 Coil By Pass Factor 0.10 2.48
CFM / Person 15 2
130 People 1 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 94.34 32 12 -17.92 0.55 1657 621 -930
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 140 64 -49
1 People Nos 337 337 337 337
2.48 3.32 2545 8447 8447 8447
0.88 2545 2239 2239 2239
3.41 804 804 804
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
13624 12511 10848
15% 2044 1877 1627
15667 14388 12475
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 66 228 -60
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 479 641 353
10% 48 64 35
527 705 388
ROOM TOTAL HEAT(RTH) 16194 15093 12864
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 35 1.08 T 36.9 17.0 -12.9 0.9 1257 577 -440
Latent 35 0.68 Gr / lb 28 95.62 -25.14 0.9 594 2048 -538
18045 17718 11886
Safety 3% 541 532 357
18586 18250 12242
TR 1.55 1.52 1.02
RSH 15667 14388 12475
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 16194 15093 12864
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.97 0.95 0.97
ADP 55.43 55.29 55.43
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 850 780 680
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
1
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
35
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 188.68 Watts
Blower Load (HP)
Outside air cfm DB diff
35
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name COMPRESSION
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
850 780 680 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
22.21535472
36.94 78.08 XX 27.72 Volume 316 F.A as per ACPH 11
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 25
Room Number GF-31
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
1.77 2.10 XX 3.73 2.40 XX 9 179
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
5.82 6.89 XX 40.09 7.872 XX 316 105
100000 Coil By Pass Factor 0.10 0.00
CFM / Person 15 2
130 People 1 Pressure 15 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 40.09 32 12 -17.92 0.55 704 264 -395
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 100 46 -35
1 People Nos 337 337 337 337
0.00 0.00 2545 0 0 0
0.08 2545 214 214 214
3.41 342 342 342
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
1697 1202 463
15% 255 180 69
1951 1383 532
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 47 163 -43
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 460 576 370
10% 46 58 37
506 633 407
ROOM TOTAL HEAT(RTH) 2457 2016 940
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 25 1.08 T 36.9 17.0 -12.9 0.9 898 412 -314
Latent 25 0.68 Gr / lb 28 95.62 -25.14 0.9 424 1463 -385
3779 3891 241
Safety 3% 113 117 7
3892 4008 248
TR 0.32 0.33 0.02
RSH 1951 1383 532
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 2457 2016 940
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.79 0.69 0.57
ADP 52.00 #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 110 75 30
(From tables/chart)
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
1
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
LATENT HEAT
Gr/lb Difference
25
ROOM SENSIBLE HEAT SUB TOTAL
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
Equipement load (kW) HP
Lights 80.17 Watts
Blower Load (HP)
Outside air cfm DB diff
25
INTERNAL HEAT
People Gain / People
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
ROOM DATA
Room Name CHANGE ROOM
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
110 105 105 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
30.591756
36.94 78.08 XX 27.72 Volume 1338 F.A as per ACPH 45
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 45
Room Number --
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
1.76 9.00 XX 15.8 2.40 XX 38 883
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
5.76 29.52 XX 169.95 7.872 XX 1338 520
100000 Coil By Pass Factor 0.10 0.00
CFM / Person 15 2.0
130 People 0 Pressure 35 Room Air Changes/Hour 23
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 169.95 32 12 -17.92 0.55 2986 1118 -1675
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 180 82 -63
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.42 2545 1057 1057 1057
3.41 1449 1449 1449
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
5671 3707 768
15% 851 556 115
6522 4263 884
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 85 293 -77
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 85 293 -77
10% 8 29 -8
93 322 -85
ROOM TOTAL HEAT(RTH) 6615 4584 799
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 45 1.08 T 36.9 17.0 -12.9 0.9 1616 742 -565
Latent 45 0.68 Gr / lb 28 95.62 -25.14 0.9 763 2633 -692
8995 7960 -458
Safety 3% 270 239 -14
9264 8198 -472
TR 0.77 0.68 -0.04
RSH 6522 4263 884
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 6615 4584 799
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.99 0.93 1.11
ADP 56.00 54.83 56.00
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 355 235 50
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name PASSAGE
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 339.91 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
45
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
45
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
520 520 520 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
9.457022534
36.94 78.08 XX 27.72 Volume 414 F.A as per ACPH 14
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 15
Room Number GF-35
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
1.78 2.74 XX 4.88 2.40 XX 12 234
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
5.85 8.98 XX 52.54 7.872 XX 414 138
100000 Coil By Pass Factor 0.10 1.0
CFM / Person 15 2
130 People 0 Pressure 15 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 52.54 32 12 -17.92 0.55 923 346 -518
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 48.12 32 12 -17.92 0.35 538 201 -302
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 60 27 -21
0 People Nos 337 0 0 0
1.00 1.34 2545 3413 3413 3413
0.40 2545 1018 1018 1018
3.41 448 448 448
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
6399 5453 4038
15% 960 818 606
7359 6271 4643
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 28 98 -26
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 28 98 -26
10% 3 10 -3
31 107 -28
ROOM TOTAL HEAT(RTH) 7390 6378 4615
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 15 1.08 T 36.9 17.0 -12.9 0.9 539 247 -188
Latent 15 0.68 Gr / lb 28 95.62 -25.14 0.9 254 878 -231
8183 7503 4196
Safety 3% 245 225 126
8429 7728 4322
TR 0.70 0.64 0.36
RSH 7359 6271 4643
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 7390 6378 4615
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 1.00 0.98 1.01
ADP 56.00 56.00 56.00
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 400 340 255
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name DISPENSING
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 105.08 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
15
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
15
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
400 340 255 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- #REF!
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People #REF!
cfm /Person
+0.18*Sq.ft
#REF!
36.94 78.08 XX 27.72 Volume #REF! F.A as per ACPH #REF!
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 #REF!
Room Number #REF!
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
#REF! #REF! XX #REF! #REF! XX #REF! #REF!
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
#REF! #REF! XX #REF! #REF! XX #REF! #REF!
#REF! Coil By Pass Factor 0.10 #REF!
CFM / Person 15 #REF!
#REF! People #REF! Pressure #REF! Room Air Changes/Hour #REF!
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) #REF! 23 11 7 0.56 #REF! #REF! #REF!
Glass(E) #REF! 12 11 7 0.56 #REF! #REF! #REF!
Glass(S) #REF! 12 11 74 0.56 #REF! #REF! #REF!
Glass(W) #REF! 163 165 118 0.56 #REF! #REF! #REF!
wall (N) #REF! 12 -2 -27 0.35 #REF! #REF! #REF!
wall (E) #REF! 26 12 -22 0.35 #REF! #REF! #REF!
wall (S) #REF! 24 10 -23 0.35 #REF! #REF! #REF!
wall (W) #REF! 20 6 -19 0.35 #REF! #REF! #REF!
Roof sun #REF! 40 26 -7 0.5 #REF! #REF! #REF!
Roof insulated #REF! 16 2 -29 0.11 #REF! #REF! #REF!
All glass #REF! 37 17 -12.92 1.13 #REF! #REF! #REF!
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling #REF! 32 12 -17.92 0.55 #REF! #REF! #REF!
Floor #REF! 32 12 -17.92 0.5 #REF! #REF! #REF!
Partition #REF! 32 12 -17.92 0.35 #REF! #REF! #REF!
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 #REF! #REF! #REF!
#REF! People Nos 337 #REF! #REF! #REF!
#REF! #REF! 2545 #REF! #REF! #REF!
#REF! 2545 #REF! #REF! #REF!
3.41 #REF! #REF! #REF!
Reheat SUM #REF! Monsoon #REF! Winter #REF! 3.41 #REF! #REF! #REF!
#REF! #REF! #REF!
15% #REF! #REF! #REF!
#REF! #REF! #REF!
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 #REF! #REF! #REF!
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 #REF! #REF! #REF!
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL #REF! #REF! #REF!
10% #REF! #REF! #REF!
#REF! #REF! #REF!
ROOM TOTAL HEAT(RTH) #REF! #REF! #REF!
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible #REF! 1.08 T 36.9 17.0 -12.9 0.9 #REF! #REF! #REF!
Latent #REF! 0.68 Gr / lb 28 95.62 -25.14 0.9 #REF! #REF! #REF!
#REF! #REF! #REF!
Safety 3% #REF! #REF! #REF!
#REF! #REF! #REF!
TR #REF! #REF! #REF!
RSH #REF! #REF! #REF!
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH #REF! #REF! #REF!
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF #REF! #REF! #REF!
ADP #REF! #REF! #REF!
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) #REF! #REF! #REF!
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name #REF!
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights #REF! Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
#REF!
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
#REF!
#REF!
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
#REF! #REF! #REF! SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- AHU 10
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 1
cfm /Person
+0.18*Sq.ft
57.57390478
36.94 78.08 XX 27.72 Volume 1862 F.A as per ACPH 31
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 60
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
6.12 3.59 XX 21.98 2.40 XX 53 528
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
20.08 11.78 XX 236.52 7.872 XX 1862 310
NA Coil By Pass Factor 0.10 1.5
CFM / Person 15 1
65 People 1 Pressure -- Room Air Changes/Hour 10
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 236.52 32 12 -17.92 0.55 4155 1556 -2331
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 159.96 32 12 -17.92 0.35 1788 670 -1003
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 239 110 -84
1 People Nos 337 337 337 337
1.50 2.01 2545 5119 5119 5119
0.24 2545 611 611 611
3.41 2016 2016 2016
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
14266 10419 4665
15% 2140 1563 700
16406 11981 5365
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 113 390 -103
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 413 413 413
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 526 803 310
10% 53 80 31
579 883 341
ROOM TOTAL HEAT(RTH) 16984 12865 5706
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 60 1.08 T 36.9 17.0 -12.9 0.9 2154 989 -753
Latent 60 0.68 Gr / lb 28 95.62 -25.14 0.9 1018 3511 -923
20157 17365 4030
Safety 3% 605 521 121
20761 17886 4151
TR 1.73 1.49 0.35
RSH 16406 11981 5365
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 16984 12865 5706
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.97 0.93 0.94
ADP 55.43 55.00 55.14
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 890 650 295
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name IT SERVER ROOM
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 473.04 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
60
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
60
1
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
890 650 310 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- DU
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 60
cfm /Person
+0.18*Sq.ft
1020.60841
36.94 78.08 XX 27.72 Volume 5275 F.A as per ACPH 176
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 1025
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
4.45 14.00 XX 62.27 2.40 XX 149 2242
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
14.59 45.92 XX 670.05 7.872 XX 5275 1319
NA Coil By Pass Factor 0.10 2.0
CFM / Person 15 2
65 People 60 Pressure 0 Room Air Changes/Hour 15
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 670.05 32 12 -17.92 0.55 11771 4408 -6604
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 117.39 32 12 -17.92 0.35 1312 491 -736
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 4089 1877 -1430
60 People Nos 337 20220 20220 20220
2.00 2.68 2545 6826 6826 6826
1.04 2545 2646 2646 2646
3.41 5712 5712 5712
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
52576 42180 26633
15% 7886 6327 3995
60462 48507 30628
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 1932 6665 -1752
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 24780 24780 24780
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 26712 31445 23028
10% 2671 3144 2303
29383 34589 25331
ROOM TOTAL HEAT(RTH) 89846 83096 55959
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 1025 1.08 T 36.9 17.0 -12.9 0.9 36803 16897 -12872
Latent 1025 0.68 Gr / lb 28 95.62 -25.14 0.9 17389 59982 -15770
144038 159976 27316
Safety 3% 4321 4799 819
148359 164775 28136
TR 12.36 13.73 2.34
RSH 60462 48507 30628
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 89846 83096 55959
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.67 0.58 0.55
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 3275 2630 1660
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name DINING HALL
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 1340.09 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
1025
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
1025
60
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
3275 2630 1660 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- AHU 13
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 10
cfm /Person
+0.18*Sq.ft
192.99696
36.94 78.08 XX 27.72 Volume 1880 F.A as per ACPH 31
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 195
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.70 6.00 XX 22.20 2.40 XX 53 533
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
12.14 19.68 XX 238.87 7.872 XX 1880 313
NA Coil By Pass Factor 0.10 1.50
CFM / Person 15 1
50 People 10 Pressure 15 Room Air Changes/Hour 10
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 238.87 32 12 -17.92 0.55 4196 1571 -2354
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 778 357 -272
10 People Nos 337 3370 3370 3370
1.50 2.01 2545 5119 5119 5119
0.10 2545 245 245 245
3.41 2036 2036 2036
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
15745 12699 8145
15% 2362 1905 1222
18107 14604 9366
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 368 1268 -333
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 4130 4130 4130
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 4498 5398 3797
10% 450 540 380
4947 5938 4176
ROOM TOTAL HEAT(RTH) 23054 20542 13543
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 195 1.08 T 36.9 17.0 -12.9 0.9 7002 3215 -2449
Latent 195 0.68 Gr / lb 28 95.62 -25.14 0.9 3308 11411 -3000
33364 35168 8093
Safety 3% 1001 1055 243
34365 36223 8336
TR 2.86 3.02 0.69
RSH 18107 14604 9366
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 23054 20542 13543
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.79 0.71 0.69
ADP 51.67 49.00 #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 985 795 510
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name STAFF ROOM
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 477.74 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
195
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
195
10
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
985 795 510 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 2
cfm /Person
+0.18*Sq.ft
39.9783936
36.94 78.08 XX 27.72 Volume 436 F.A as per ACPH 7
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 40
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
2.30 2.24 XX 5.15 2.40 XX 12 124
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
7.54 7.35 XX 55.44 7.872 XX 436 73
NA Coil By Pass Factor 0.10 0.0
CFM / Person 15 1
50 People 2 Pressure 0 Room Air Changes/Hour 10
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 55.44 32 12 -17.92 0.55 974 365 -546
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 160 73 -56
2 People Nos 337 674 674 674
0.00 0.00 2545 0 0 0
0.02 2545 57 57 57
3.41 473 473 473
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
2337 1641 601
15% 351 246 90
2687 1888 692
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 75 260 -68
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 826 826 826
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 901 1086 758
10% 90 109 76
992 1195 833
ROOM TOTAL HEAT(RTH) 3679 3082 1525
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 40 1.08 T 36.9 17.0 -12.9 0.9 1436 659 -502
Latent 40 0.68 Gr / lb 28 95.62 -25.14 0.9 679 2341 -615
5794 6083 407
Safety 3% 174 182 12
5968 6265 419
TR 0.50 0.52 0.03
RSH 2687 1888 692
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 3679 3082 1525
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.73 0.61 0.45
ADP 50.00 #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 150 105 40
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name MEETING ROOM
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 110.87 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
40
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
40
2
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
150 105 73 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 3
cfm /Person
+0.18*Sq.ft
99.87665206
36.94 78.08 XX 27.72 Volume 2400 F.A as per ACPH 40
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 100
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
3.65 1.57 XX 28.33 2.40 XX 68 680
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
11.96 5.15 XX 304.87 7.872 XX 2400 400
NA Coil By Pass Factor 0.10 0.20
CFM / Person 15 1
50 People 3 Pressure 0 Room Air Changes/Hour 10
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 304.87 32 12 -17.92 0.55 5356 2005 -3005
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 157.38 32 12 -17.92 0.35 1759 659 -987
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 399 183 -140
3 People Nos 337 1011 1011 1011
0.20 0.27 2545 683 683 683
0.12 2545 313 313 313
3.41 2599 2599 2599
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
12120 7453 474
15% 1818 1118 71
13938 8571 545
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 188 650 -171
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 1239 1239 1239
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 1427 1889 1068
10% 143 189 107
1570 2078 1175
ROOM TOTAL HEAT(RTH) 15508 10649 1720
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 100 1.08 T 36.9 17.0 -12.9 0.9 3591 1649 -1256
Latent 100 0.68 Gr / lb 28 95.62 -25.14 0.9 1696 5852 -1539
20795 18150 -1074
Safety 3% 624 544 -32
21419 18694 -1106
TR 1.78 1.56 -0.09
RSH 13938 8571 545
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 15508 10649 1720
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.90 0.80 0.32
ADP 54.33 52.33 #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 755 465 30
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name WAITING AND RECEPTION
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 609.74 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
100
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
100
3
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
755 465 400 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
21.963312
36.94 78.08 XX 27.72 Volume 961 F.A as per ACPH 32
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 35
Room Number GF-36
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
4.20 2.70 XX 11.34 2.40 XX 27 544
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
13.78 8.86 XX 122.02 7.872 XX 961 320
100000 Coil By Pass Factor 0.10 0.0
CFM / Person 15 2
130 People 0 Pressure 25 Room Air Changes/Hour 20
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 122.02 32 12 -17.92 0.55 2143 803 -1203
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 140 64 -49
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.26 2545 652 652 652
3.41 1040 1040 1040
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
3975 2559 440
15% 596 384 66
4571 2942 506
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 66 228 -60
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 66 228 -60
10% 7 23 -6
73 250 -66
ROOM TOTAL HEAT(RTH) 4644 3193 441
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 35 1.08 T 36.9 17.0 -12.9 0.9 1257 577 -440
Latent 35 0.68 Gr / lb 28 95.62 -25.14 0.9 594 2048 -538
6494 5818 -537
Safety 3% 195 175 -16
6689 5992 -554
TR 0.56 0.50 -0.05
RSH 4571 2942 506
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 4644 3193 441
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.98 0.92 1.15
ADP 56.00 54.83 56.00
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 250 160 30
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name RM STORE
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 244.04 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
35
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
35
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
320 320 320 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
5.42304
36.94 78.08 XX 27.72 Volume 237 F.A as per ACPH 8
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 10
Room Number GF-37
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
1.40 2.00 XX 2.80 2.40 XX 7 282
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
4.59 6.56 XX 30.13 7.872 XX 237 166
100000 Coil By Pass Factor 0.10 0.00
CFM / Person 15 2
130 People 0 Pressure 15 Room Air Changes/Hour 42
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 30.13 32 12 -17.92 0.55 529 198 -297
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 40 18 -14
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.13 2545 338 338 338
3.41 257 257 257
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
1164 811 284
15% 175 122 43
1338 933 326
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 19 65 -17
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 19 65 -17
10% 2 7 -2
21 72 -19
ROOM TOTAL HEAT(RTH) 1359 1004 308
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 10 1.08 T 36.9 17.0 -12.9 0.9 359 165 -126
Latent 10 0.68 Gr / lb 28 95.62 -25.14 0.9 170 585 -154
1888 1754 28
Safety 3% 57 53 1
1945 1807 29
TR 0.16 0.15 0.00
RSH 1338 933 326
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 1359 1004 308
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.98 0.93 1.06
ADP 56.00 54.83 56.00
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 75 55 20
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name RM ENTRY
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 60.26 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
10
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
10
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
166 166 166 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
7.8362928
36.94 78.08 XX 27.72 Volume 343 F.A as per ACPH 11
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 15
Room Number GF-12
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
1.70 2.38 XX 4.05 2.40 XX 10 456
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
5.58 7.81 XX 43.53 7.872 XX 343 268
100000 Coil By Pass Factor 0.10 0.0
CFM / Person 15 2
0 People 0 Pressure 0 Room Air Changes/Hour 47
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 60 27 -21
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 371 371 371
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
431 399 350
15% 65 60 53
496 458 403
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 28 98 -26
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 28 98 -26
10% 3 10 -3
31 107 -28
ROOM TOTAL HEAT(RTH) 527 566 375
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 15 1.08 T 36.9 17.0 -12.9 0.9 539 247 -188
Latent 15 0.68 Gr / lb 28 95.62 -25.14 0.9 254 878 -231
1320 1691 -45
Safety 3% 40 51 -1
1359 1741 -46
TR 0.11 0.15 0.00
RSH 496 458 403
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 527 566 375
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.94 0.81 1.08
ADP 55.14 52.67 56.00
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 30 25 25
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name AIRLOCK
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 87.07 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
15
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
15
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
268 268 268 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.00 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0.00 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.00
CFM / Person 15 0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
5 5 0 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.00 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0.00 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.0
CFM / Person 15 0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
5 5 0 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.0 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.00
CFM / Person 15 0.0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
5 5 0 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.00 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0.00 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.00
CFM / Person 15 0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
5 5 0 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.00 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0.00 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.0
CFM / Person 15 0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
5 5 0 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.00 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0.00 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.0
CFM / Person 15 0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
5 5 0 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.00 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0.00 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.00
CFM / Person 15 0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
5 5 0 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.00 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0.00 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.0
CFM / Person 15 0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
5 5 0 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.00 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0.00 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.00
CFM / Person 15 0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
5 5 0 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.00 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0.00 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.0
CFM / Person 15 0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
5 5 0 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.00 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0.00 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.00
CFM / Person 15 0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
5 5 0 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.00 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0.00 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.0
CFM / Person 15 0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
5 5 0 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162 0.0
60 51 60.00 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.0 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.00
CFM / Person 15 0.0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
5 5 0 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.00 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0.00 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.00
CFM / Person 15 0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
5 5 0 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.00 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0.00 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.0
CFM / Person 15 0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
5 5 0 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.00 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0.00 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.0
CFM / Person 15 0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor
(From tables/chart)
5 5 0 SELECTED SUPPLY AIR CFM
Date: 19.02.14
Floor:- G.F
AHU NO:- 0
Estimated By:- RYC
Checked BY:- PAH
DB (F) WB (F) %RH Gr/lb Lattitude Attitude (ft) Daily Range (F) Dew Point (F)
110 78 24 94.5 0.0
90 83 82 162.4 0.0
60 51 60 41.67 0.0
73.0 55 66.81 CFM
People 0
cfm /Person
+0.18*Sq.ft
0
36.94 78.08 XX 27.72 Volume 0 F.A as per ACPH 0
16.96 82.94 XX 95.62 Exfilteration DUST EXHAUST
-12.92 51.08 XX -25.14 5
Room Number 0
W L XX Area (sq.mtr) Height (mtr) XX Volume (cu.mt) CMH
0.00 0.00 XX 0.00 0.00 XX 0 0
W L XX Area (sq.ft) Height (ft) XX Volume (cu.ft) CFM
0.00 0.00 XX 0.00 0 XX 0 0
0 Coil By Pass Factor 0.10 0.00
CFM / Person 15 0
0 People 0 Pressure 0 Room Air Changes/Hour 0
Item L (mtrs) W (mtrs)
Area or Qty
(Sq.ft)
Factor
Summer Monsoon Winter 'U'Factor Summer Monsoon Winter
Glass(N) 0.00 23 11 7 0.56 0 0 0
Glass(E) 0.00 12 11 7 0.56 0 0 0
Glass(S) 0.00 12 11 74 0.56 0 0 0
Glass(W) 0.00 163 165 118 0.56 0 0 0
wall (N) 0 12 -2 -27 0.35 0 0 0
wall (E) 0 26 12 -22 0.35 0 0 0
wall (S) 0 24 10 -23 0.35 0 0 0
wall (W) 0 20 6 -19 0.35 0 0 0
Roof sun 0.00 40 26 -7 0.5 0 0 0
Roof insulated 0.00 16 2 -29 0.11 0 0 0
All glass 0.00 37 17 -12.92 1.13 0 0 0
Partition glass 0 31.94 11.96 -17.92 0.8 0 0 0
Ceiling 0.00 32 12 -17.92 0.55 0 0 0
Floor 0.00 32 12 -17.92 0.5 0 0 0
Partition 0.00 32 12 -17.92 0.35 0 0 0
BF 1.08
summer monsoon winter
36.9 16.96 -12.92 0.10 1.08 20 9 -7
0 People Nos 337 0 0 0
0.00 0.00 2545 0 0 0
0.00 2545 0 0 0
3.41 0 0 0
Reheat SUM 0.00 Monsoon 0.00 Winter 0.00 3.41 0 0 0
20 9 -7
15% 3 1 -1
23 11 -8
BF
summer Monsoon Winter
Outside air cfm 28 95.62 -25.14 0.1 0.68 9 33 -9
Vap.Trans. 27.72 95.62 -25.14 0.01 XXX 0 0 0
People XX Nos XX Gain / People 413 0 0 0
Steam XX XX XX lb/hr X 1080 0 0 0
Permeation
ROOM LATENT HEAT SUB TOTAL 9 33 -9
10% 1 3 -1
10 36 -9
ROOM TOTAL HEAT(RTH) 33 46 -17
Cfm Factor Summer Monsoon Winter (1 - B.F.)
Sensible 5 1.08 T 36.9 17.0 -12.9 0.9 180 82 -63
Latent 5 0.68 Gr / lb 28 95.62 -25.14 0.9 85 293 -77
298 421 -157
Safety 3% 9 13 -5
307 434 -162
TR 0.03 0.04 -0.01
RSH 23 11 -8
Room Total Heat = Room Sensible Heat + Room Latent Heat RTH 33 46 -17
Sensible Heat Factor = Room Sensible Heat / Room Total Heat SHF 0.69 0.23 0.46
ADP #N/A #N/A #N/A
ADP 54 54 54
Dehumidified Rise = (1-B.F.) x (RM.TEMP-A.D.P.) 17 17 17
Dehumidified CFM = RSH / (1.08 x Dehumidified Rise) 5 5 0
GMP TECHNICAL
SOLUTIONS PVT
LTD
HEAT LOAD CALCUALATION SHEET
CLIENT:- CONTRACT PHARMACAL CORPORATION
PROJECT:- FORMULATION AREA
LOCATION:- CHANGODAR (GUJRAT)
DOCUMENT NO:- 0
DESIGN CONDITIONS
PARAMETER
Outside Conditions
Summer
23.02 53 26 Monsoon
Winter
Inside Conditions Fresh Air Selection
Difference
Summer
Monsoon
Winter Selected Fresh Air (CFM)
ROOM DATA
Room Name 0
Unit in Meters. :
Unit in Ft. :
Clean Room Class
Lighting Load
(Watts / Sq.ft.)
2
Equipment Load(KW)
Filtration Fresh Air Changes/Hour
Static Pressure (mm of Wg)
Sun gain/ Temp diff HEAT GAIN (Btu / Hour)
SOLAR HEAT GAIN GLASS
HP
SOLAR & TRANS. HEAT GAIN-WALLS & ROOF
TRANS HEAT GAIN EXCEPT WALLS & ROOFS
INFILTRATION & OUTSIDE AIR
Outside air cfm DB diff
Lights 0.00 Watts
Blower Load (HP)
ROOM SENSIBLE HEAT SUB TOTAL
5
INTERNAL HEAT
People Gain / People
Equipement load (kW)
Safety factor
Supply duct heat gain + Supply duct leak loss + Safety factor
TOTAL ROOM SENSIBLE HEAT (RSH)
LATENT HEAT
Gr/lb Difference
5
0
0
Safety factor Supply duct leak loss + Safety factor
TOTAL ROOM LATENT HEAT
(SELECTED ADP)
Dehumidified Rise
DEHUMIDIFIER AIR CFM
OUTDOOR AIR HEAT = Outside Air CFM x x (1 - B.F.) x Factor = BTU / Hr.
GRAND TOTAL HEAT SUB TOTAL
GRAND TOTAL HEAT
CALCUALTION Room Sensible Heat
Room Total Heat
Sensible Heat Factor