Sunteți pe pagina 1din 11

INPE DGI

PROYECTO
CONSTRUCCION DEL NUEVO ESTABLECIMIENTO
PENITENCIARIO DE CHINCHA

MEMORIA DE CALCULO
INSTALACIONES SANITARIAS











MEMORIA DE CALCULO DE
INSTALACIONES SANITARIAS



INPE DGI
PROYECTO
CONSTRUCCION DEL NUEVO ESTABLECIMIENTO
PENITENCIARIO DE CHINCHA

MEMORIA DE CALCULO
INSTALACIONES SANITARIAS


MEMORIA DE CALCULO DE INSTALACIONES
SANITARIAS


I N D I C E

1.00 GENERALIDADES

2.00 OBJETIVOS

3.00 PARAMETROS Y CONSIDERACIONES DEL SISTEMA DE AGUA
POTABLE

4.00 CALCULO DE LA DOTACION DIARIA

5.00 CALCULO DEL VOLUMEN DE ALMACENAMIENTO

6.00 CAUDALES DE CONSUMO

7.00 SELECCIN DEL DIAMETRO DE LA TUBERIA DE ALIMENTACION

8.00 CALCULO DE LAS UNIDADES HUNTER

9.00 SISTEMA DE IMPULSION

10.00 ALTURA DINAMICA DE LA LINEA DE IMPULSION

11.00 POTENCIA APROXIMADA DE LA BOMBA

12.00 CALCULO HIDRAULICO DE LAS REDES DE DISTRIBUCION









INPE DGI
PROYECTO
CONSTRUCCION DEL NUEVO ESTABLECIMIENTO
PENITENCIARIO DE CHINCHA

MEMORIA DE CALCULO
INSTALACIONES SANITARIAS


OBRA: CONSTRUCCION DEL NUEVO ESTABLECIMIENTO PENITENCIARIO DE
CHINCHA.

MEMORIA DE CALCULO DE INSTALACIONES SANITARIAS
1.00 GENERALIDADES

La memoria de clculo de las instalaciones sanitarias se ha desarrollado para el
proyecto denominado: Construccin del Nuevo Establecimiento Penitenciario de
Chincha.

2.00 OBJETIVOS

Presentar los clculos justificativos del diseo de las instalaciones sanitarias del
presente proyecto.

3.00 PARAMETROS Y CONSIDERACIONES DEL SISTEMA DE AGUA POTABLE

Los parmetros y consideraciones del diseo de las instalaciones sanitarias, estn
basados principalmente en lo establecido en la Norma IS.010 contenido en el
Reglamento Nacional de Edificacin.

4.00 CALCULO DE LA DOTACION DIARIA

Para determinar los clculos de la Dotacin de agua se ha elaborado el siguiente
cuadro:


Descripcin Unidad N de Unidades Dotacin Diaria / Unidad Volumen diario (lt)



Internos hab 1800 150 270,000
Administrativos hab 50 25 1,250
Seguridad interna m2 160 6 960
Seguridad externa m2 90 6 540
Area del Poder Judicial m2 230 6 1,380
Taller varones m2 300 6 1,800
Cocina varones m2 60 40 2,400
Registro y clasificacion m2 160 6 960
Casa de fuerza m2 26 6 156
Areas verdes m2 400 2 800
Flotantes hab 700 15 10,500
Consultorio mdico und 10 500 5,000
Consultorio dental und 1 1000 1,000
N de camas und 5 600 3,000

TOTAL 299,746





INPE DGI
PROYECTO
CONSTRUCCION DEL NUEVO ESTABLECIMIENTO
PENITENCIARIO DE CHINCHA

MEMORIA DE CALCULO
INSTALACIONES SANITARIAS


El consumo total requerido en las instalaciones existentes y proyectadas es 299,746
lt/da. Considerando el volumen de reserva del 50 %, establecemos un
requerimiento diario de 449.62 m3/da.

Este volumen de reserva atender en caso de que el sistema sufra algn
desabastecimiento de agua potable por corte del servicio.


5.00 CALCULO DEL VOLUMEN DE ALMACENAMIENTO

Volumen diario: 299.8 m
3
Volumen de reserva (50%): 149.8 m
3
Volumen Total: 449.6 m
3

Volumen Calculado de Almacenamiento Cisterna 337.2 m
3

Volumen Calculado de Almacenamiento Tanque Elevado 149.9 m
3


Por tanto consideramos el siguiente dimensionamiento

Ancho (m) Largo (m) Altura (m) Volumen
(m
3
)
Cisterna 10.00 20.00 1.80 360.0
Tanque Elevado 150.0




6.00 CAUDALES DE CONSUMO

Consumo Promedio 5.204 lt/sg
Consumo Mximo Diario 6.765 lt/sg
Consumo Mximo Horario 13.53 Lt/sg



8.00 CALCULO DE LAS UNIDADES HUNTER

Servicio Cantidad Unid. Hunter Total U.H.
APARATOS SANITARIOS


Inodoro C-4

181 3 543
Lavatorio A-3

164 1 164
Ducha F-1

2 0
Urinario C-9

22 2.5 55
Lavadero B-9

17 3 51
Lavadero B-12

2 3 6
Lavadero B-16

2 3 6
Lavaollas

4 4 16
Lavadero corrido 21 5 105
Urinario Corrido

19 4 76
Turco

208 3 624



INPE DGI
PROYECTO
CONSTRUCCION DEL NUEVO ESTABLECIMIENTO
PENITENCIARIO DE CHINCHA

MEMORIA DE CALCULO
INSTALACIONES SANITARIAS


Lavadero granito 208 2 416
Salida Odontologa 1 2 2

UNIDADES HUNTER INSTALACIONES PROYECTADAS 2064

Las unidades Hunter para las instalaciones proyectadas es:

TOTAL: 2064 UH, el cual equivale a 12.40 lt/seg.

El caudal de mxima demanda simultnea es 12.40 lt/seg.



9.00 SISTEMA DE IMPULSION

CAUDAL DE BOMBEO

Caudal de Mxima Demanda Simultnea

12.400 lt/seg
Caudal de llenado de Tanque Elevado en 2 horas 4.274 lt/seg
Entonces;

Caudal de bombeo=

12.400 lt/seg

0.012 m3/seg
Nmero de horas de bombeo=

2.00 Horas

DIAMETRO DE LA LINEA DE IMPULSION

D = 1.3 x Q^( 1/2) x ( horas de bombeo / 24)^ ( 1/4)


Dimetro =

0.078 m

3.17 pulgadas
Entonces consideramos

4 pulgadas

0.102 m
PERDIDA DE CARGA EN LA LINEA DE IMPULSION

Caudal =

12.40 lt/seg
Dimetro=

0.102 m
C=

140


S (m/m)

0.0232


Longitud=

25.8 m

Perdida de carga por longitud=

0.599 m
Perdida de carga local=

0.300 m

Perdida de carga total=

0.90 m


10.00 ALTURA DINAMICA DE LA LINEA DE IMPULSION

Nivel de succin de la bomba =

161.4 m
Nivel dinmico en la cisterna

207.2 m
Altura dinmica =

28.7 m



INPE DGI
PROYECTO
CONSTRUCCION DEL NUEVO ESTABLECIMIENTO
PENITENCIARIO DE CHINCHA

MEMORIA DE CALCULO
INSTALACIONES SANITARIAS


Consideramos un factor de correccin de 25% 6.6 m

Altura dinmica Total

35.3 m



11.00 POTENCIA APROXIMADA DE LA BOMBA

Potencia Aproximada: 10 HP

12.00 CALCULO HIDRAULICO DE LAS REDES DE DISTRIBUCION
Para el clculo hidrulico de la red de distribucin se ha efectuado mediante la
frmula de Hazen & Wllians (Ver Cuadro 1).

Nivel del piso en T.E = 183.0 m
Altura del Fuste = 20.0 m
Cota Piezomtrica en T.E = 203.0 m

CUADRO 1: Cuadro de Prdidas de Carga y Presin

Cota de Coeficiente Cota
Tramo U.H Terreno Caudal Longitud Diametro de rugosidad S Hf Piezometrica Velocidad Presin
m l/s (m) pulg m Hazen-W. (m/m) m m m/s m
1-2 2065 183 12.40 20.0 4.00 0.102 140 0.02323 0.46 202.54 1.53 19.5
2-3 2065 180.5 12.40 65.0 4.00 0.102 140 0.02323 1.51 201.03 1.53 20.5
3-4 1600 184 10.40 60.0 4.00 0.102 140 0.01678 1.01 200.02 1.28 16.0
4-5 1600 184 10.40 2.0 4.00 0.102 140 0.01678 0.03 199.99 1.28 16.0
5-6 1200 184 8.70 35.0 4.00 0.102 140 0.01206 0.42 199.56 1.07 15.6
6-7 950 184 7.53 30.0 3.00 0.076 140 0.03747 1.12 198.44 1.65 14.4
7-8 760 184 6.30 25.0 3.00 0.076 140 0.02694 0.67 197.77 1.38 13.8
8-9 760 184 6.30 42.0 3.00 0.076 140 0.02694 1.13 196.63 1.38 12.6
9-10 700 184 5.95 20.0 3.00 0.076 140 0.02424 0.48 196.15 1.30 12.1
10-11 360 184 3.50 6.0 2.50 0.064 140 0.02207 0.13 196.02 1.11 12.0
11-12 360 184 3.50 2.0 2.50 0.064 140 0.02207 0.04 195.97 1.11 12.0
12-13 240 184 2.75 40.0 2.50 0.064 140 0.01412 0.56 195.41 0.87 11.4
13-14 240 184 2.75 2.0 2.50 0.064 140 0.01412 0.03 195.38 0.87 11.4
14-15 120 184 1.83 40.0 2.00 0.051 140 0.01971 0.79 194.59 0.90 10.6
15-16 120 184 1.83 2.0 2.00 0.051 140 0.01971 0.04 194.55 0.90 10.6
16-17 60 184 1.25 20.0 1.50 0.038 140 0.03953 0.79 193.76 1.10 9.8
17-18 40 184 0.91 8.0 1.50 0.038 140 0.02197 0.18 193.59 0.80 9.6
18-19 10 184 0.43 6.0 1.00 0.025 140 0.03955 0.24 193.35 0.85 9.3
19-20 5 188.5 0.23 3.5 0.75 0.019 140 0.05045 0.18 193.17 0.81 4.7
9.83



Pto desfavorable: Nudo 20


Turco Lavadero: h= 0.6 m

Presin mnima de flujo: 2 mca
3 Codo 1/2" 0.5 1.5 m
1 Tee 1/2" 0.15 0.15 m

Longitud equivalente= 1.65 m



INPE DGI
PROYECTO
CONSTRUCCION DEL NUEVO ESTABLECIMIENTO
PENITENCIARIO DE CHINCHA

MEMORIA DE CALCULO
INSTALACIONES SANITARIAS



Longitud del Tramo= 1 m

Longitud total= 2.65 m

Q= 0.23 lt/seg

D= 0.019 m

C= 140


Sf= 0.050447


Hf= 0.1336845



Presin= 3.94 m

P > 2.0m ==> OK

Se ha considerado una presin remanente de 1.94 m para satisfacer la presin en la zona
de ampliacin.




INPE DGI
PROYECTO
CONSTRUCCION DEL NUEVO ESTABLECIMIENTO
PENITENCIARIO DE CHINCHA

MEMORIA DE CALCULO
INSTALACIONES SANITARIAS



DIMENSIONAMIENTO DE SISTEMAS DE TRATAMIENTO DE AGUAS RESIDUALES

MEDIANTE LAGUNAS DE ESTABILIZACION ANAEROBIAS PRIMARIAS Y FACULTATIVAS SECUNDARIAS


DISEO DE LAGUNAS ANAEROBIAS
PROYECTO: CONSTRUCCION DE NUEVO ESTABLECIMIENTO PENITENCIARIO DE CHINCHA


POBLACION DE DISEO===============>

2200 Habitantes

DOTACION==========================>

150 lt/hab/dia

CONTRIBUCIONES:

DESAGE===========================>

80 %

DBO5==============================>

50 grDBO/hab/dia

TEMPERATURA DEL AGUA

DEL MES MAS FRIO==================>

20 C


Caudal de Aguas residuales (Q):

Poblacin x Dotacin x %Contribucin

264.00 m3/dia


11.00 m3/hora


3.06 lps

Carga de DBO5 (C):

Poblacin x Contribucin percapita

110 KgDBO5/dia


CARGA ORGANICA VOLUMETRICA (CV)=============>

200 grDBO/m3.dia


Volumen de laguna requerido sin acumulacin de lodo (V1)

Carga DBO5/Carga volumetrica

550 m3


TASA DE ACUMULACION DE LODOS (ta)==>

0.04 m3/hab/ao

PERIODO DE LIMPIEZA (pl)===========>

1 aos


Volumen de acumulacion de lodos (V2)

Poblacin x ta x pl

88 m3


NUMERO DE LAGUNAS EN PARALELO (N)==>

2 unidades (2 mnimo)


Volmenes unitarios

(v1) Sin lodos (V1/N)

275.00 m3

(v2) De acumulacin de lodos (V2/N)

44.00 m3


=

Volumen total unitario (vu=v1+v2)

319.00 m3


Caudal afluente unitario (Qu = Q/N)

132.00 m3/dia

Periodo de Retencin (PR), sin lodo

PR = v1/Qu

2.08 das





INPE DGI
PROYECTO
CONSTRUCCION DEL NUEVO ESTABLECIMIENTO
PENITENCIARIO DE CHINCHA

MEMORIA DE CALCULO
INSTALACIONES SANITARIAS


PROFUNDIDAD (Z)====================>

2 m

Inclinacin de taludes [V:1 ; H: ]===========>

2.5

Longitud del espejo de agua:

20

Volumen Total Unitario: 466.67 m3



Dimensiones (Laguna cuadrada) Seccin Superficial


Longitud

20 m


Ancho

20 m


AREA SUPERFICIAL (As)

0.04 Ha

Carga unitaria: Cu= C/N

55.00 KgDBO/da


Carga Superficial aplicada:

CSa = Cu/As

1375 Kg/Ha.dia


Condiciones finales de las lagunas primarias anaerobias


Dimensiones del espejo de agua:


Longitud 20 m


Ancho 20 m


Area: 0.04 Ha


Borde Libre:

0.5 m


Altura Total Util:

2 m


Inclinacion de taludes


[V:1 ; H: 2.5


Area Acumulada: 0.08 Ha


Dimensiones en la coronacion:


Longitud 22.5 m


Ancho 22.5 m


Dimensiones del fondo de la laguna


Longitud 10 m


Ancho 10 m


Eficiencia de remocion de DBO estimada:

50 %

Carga Remanente:

55 Kg DBO/dia

Caudal efluente:

264 m3/dia (Se desprecian las

perdidas)



Altura de lodos

1.84 m


largo de base 1

19.2


ancho de base 1

19.2


Largo de base 2

10


Ancho de base 2 10


Volumen de lodos 405.19




INPE DGI
PROYECTO
CONSTRUCCION DEL NUEVO ESTABLECIMIENTO
PENITENCIARIO DE CHINCHA

MEMORIA DE CALCULO
INSTALACIONES SANITARIAS



Concentracon DBO afluente

416.67 mg/lt

Concentracin del BDO efluente

208.33 mg/lt

Eficiencia Total DBO

50.00 %



DISEO DE LAGUNAS FACULTATIVAS
PROYECTO: CONSTRUCCION DE NUEVO ESTABLECIMIENTO PENITENCIARIO DE CHINCHA



Carga Superficial de diseo (CSdis)

CS = 250 x 1.05^(T - 20)

250.00 KgDBO5/Ha.dia


Area Superficial requerida para lagunas secundarias facultativas (At)

At = Cremanente/CSdis

0.22 Ha

Nmero de lagunas en paralelo seleccionado==>

1 Unidades

AREA UNITARIA (Au)

0.22 Ha

CAUDAL UNITARIO AFLUENTE (Qu)

264.00 m3/dia


Perdida:infiltracin - evaporacin=>

0.5 cm/dia

Coliformes fecales en el crudo==>

1.00E+06 NMP/100 ml


Dimensiones lagunas secundarias facultativas

RELACION Largo/Ancho (L/W) Secd.======>

3


ANCHO APROXIMADO (W):

27

LONGITUD APROXIMADA (L):



81


Tasas netas de mortalidad

Kb SECUNDARIAS Kb(S) = 0.6 x 1.05^(T-20)

0.600 (1/dias)

Longitud Secundarias (Ls)

102 m

Ancho Primarias (Ws) ================>

34 m

Profd. secundarias (Zs)================>

1.5 m

P.R. Teorico (Sec.)

21.1 dias

Factor de Correcc (HCF)==>

0.6

P.R. Corregido (Sec.)

12.7 dias

Nmero de dispersin

d= 0.130

Factor adimensional

a= 2.221

Factor intrinseco de algas (Fia)

0.1

Factor de caractersticas de sedimentacin (Fcs)

0.7


Caudal efluente unitario

246.66 m3/dia

Caudal efluente total

246.66 m3/dia




INPE DGI
PROYECTO
CONSTRUCCION DEL NUEVO ESTABLECIMIENTO
PENITENCIARIO DE CHINCHA

MEMORIA DE CALCULO
INSTALACIONES SANITARIAS


Nmero de coliformes en el efluente

7.68E+03 NMP/100ml