TECHNICAL GUIDE
SUNLINE 2000
TM
SINGLE PACKAGE
AIR-TO-AIR
HEAT PUMPS
MODEL BQ240
20 NOMINAL TONS
(WORLD 50 HZ)

DESCRIPTION
York Sunline 2000 Heat Pumps are convertible single package
units. All models have dual refrigerant circuits for efficient part load
operation. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at ground level
or set on steel beams above a finished roof.
These heat pumps utilize a unique ambient compensated time-
temperature defrost system. The defrost module automatically
increases the time interval between defrost cycles as the outdoor
ambient temperature decreases. This helps to eliminate unneces-
sary and costly defrosts.
All units include:
Powder Paint finish that meets ASTM-B-117 750 hour salt
spray standards
Two-stage cooling provided by dual independent refrigeration
circuits with expansion valves, filter-driers, high and low pres-
sure/loss of charge switches and freezestats
Hermetically sealed compressors with crankcase heaters
Permanently lubricated motors
Bottom or side air discharge configuration capability (field con-
vertible)
Belt Drive Blower Motor
Manufactured under the quality standards of ISO9001
Twenty-four volt control circuit with compressor lock-out
Zero-25% fixed air damper with hood
Copper tube/aluminum fin coils
Easy access to all components
Rigging holes in base rails for lifting
Single point power connection
Complete factory package - tested, charged and wired
CSA agency approvals on all units
RETURN
036-21536-001-A-0403
2 Unitary Products Group
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . . . . . . 9
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . . . . . . 9
LIST OF FIGURES
Fig. # Pg. #
1 SUNLINE 2000TM HEAT PUMP . . . . . . . . . . . . . . . . 11
2 ELECTRONIC THERMOSTAT FIELD WIRING . . . . . 17
3 FIELD WIRING 24 VOLT THERMOSTAT . . . . . . . . . 17
4 FIELD WIRING DISCONNECT . . . . . . . . . . . . . . . . . . 18
5 UNIT DIMENSIONS - 20 TON . . . . . . . . . . . . . . . . . . 21
6 DETAIL X ACCY. SIDE SUPPLY & RETURN AIR
OPENINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7 DETAIL Y UNIT WITH RAIN HOODS . . . . . . . . . . . 22
8 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . 22
9 FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . . . 23
10 ROOF CURB DIMENSIONS - 20 TON . . . . . . . . . . . . 24
11 ROOF CURB BENEFITS . . . . . . . . . . . . . . . . . . . . . . 24
12 UNIT AND CURB APPLICATIONS . . . . . . . . . . . . . . . 24
13 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . 25
14 TYPICAL ROOF-TOP INSTALLATION . . . . . . . . . . . 25
15 SIMPLICITY CONTROL WIRING DIAGRAM . . . . . . . 26
LIST OF TABLES
Tbl. # Pg. #
1 CAPACITY RATINGS - COOLING . . . . . . . . . . . . . . . 11
2 CAPACITY RATINGS - HEATING . . . . . . . . . . . . . . . 11
3 COOLING CAPACITIES (M
3
/S AIRFLOW) -
240 UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4 COOLING CAPACITIES (CFM AIRFLOW) -
240 UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5 HEATING CAPACITIES (M
3
/S AIRFLOW) -
240 UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6 HEATING CAPACITIES (CFM AIRFLOW) -
240 UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7 BQ240 SUPPLY AIR WITH DOWNFLOW DUCT
APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . . 16
9 POWER EXHAUST PERFORMANCE . . . . . . . . . . . . 16
10 BLOWER MOTOR AND DRIVE DATA . . . . . . . . . . . 16
11 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . 18
12 ELECTRICAL DATA -WITHOUT POWERED
CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . . . . 19
13 ELECTRICAL DATA -WITH POWERED
CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . . . . 19
14 ELECTRIC HEAT CORRECTION FACTORS . . . . . . 19
15 PHYSICAL DATA - BASIC UNIT . . . . . . . . . . . . . . . . 20
16 OPERATING WEIGHTS (KG./LBS.) . . . . . . . . . . . . . 20
17 MINIMUM CLEARANCES (MM/IN.) . . . . . . . . . . . . . . 21
18 UTILITIES ENTRY DATA (MM/IN.) . . . . . . . . . . . . . . 21
19 FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . . . 23
036-21536-001-A-0403
Unitary Products Group 3
PRODUCT NOMENCLATURE
20T Sunline 2000 Model Number Nomenclature
B Q 240 C 00 A 7 A AA 1
Product Category
B = Heat Pump, Single Package
Product Generation
1 = First Generation
Product Identifier
Q = R-22 Standard Efficiency Heat Pump
Installation Options Additional Options
A = No Options Installed
(See Next Page)
Voltage B = Option 1
C = Option 2
7 = 380/415-3-50
D = Options 1 & 2
Nominal Cooling
Capacity - MBH
E = Option 3
F = Options 4
G = Options 1 & 3 240 = 20 Ton
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
A = Std Motor/Drive
L = Options 1,3 & 4
B = Std Mtr/Drive/Single Input Econo
M = Options 1, 2, 3, & 4
C = Std Mtr/Drive/Single Input Econo/Power Exhaust*
N = Options 2 & 3
D = Std Mtr/Drive/Motorized Damper
P = Options 2 & 4
Heat Type & Nominal Heat Capacity
F = Std Mtr/Drive/4" Filters
Q = Options 2, 3, & 4
C00 = Cooling Only. No field installed electric heat
G = Std Mtr/Drive/4" Filters/Single Input Econ
R = Options 3 & 4
H = Std Mtr/Drive/4" Filters/Single Input Econ/Power Exhaust*
S = Option 5
L = Std Mtr/Drive/BAS Ready Econ (No BAS Controller) w/2" Pleated Filters
T = Options 1 & 5
M = Std Mtr/Drive/BAS Ready Econ (No BAS Controller)/Power Exhaust w/2" Pleated Filters*
U = Options 1, 3, & 5
N = Hi Static Drive
V = Options 1, 4, & 5
P = Hi Static Drive/Single Input Econo
W = Options 1, 3, 4, & 5
Electric Heat Options
Q = Hi Static Drive/Single Input Econo/Power Exhaust*
X = Options 3 & 5
E18 = 18 KW
R = Hi Static Drive/Motorized Damper
Y = Options 4 & 5
E36 = 36 KW
T = Hi Static Drive/4" Filters
Z = Options 3, 4, & 5
E54 = 54 KW
U = Hi Static Drive/4" Filters/Single Input Econ
Options
E72 = 72 KW
V = Hi Static Drive/4" Filters/Single Input Econ/Power Exhaust*
1 = Disconnect
Y = Hi Static Drive/BAS Ready Econ (No BAS Controller) w/2" Pleated Filters
2 = Non-Pwr'd Conv Oultet
Z = Hi Static Drive/BAS Ready Econ (No BAS Controller)/Power Exhaust w/2" Pleated Filters*
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Airflow
York Brand
036-21536-001-A-0403
4 Unitary Products Group
PRODUCT NOMENCLATURE - CONTINUED
20T Sunline 2000 Model Number Nomenclature
Additional Options
AA None
AB Phase Monitor
AC Coil Guard
AD Dirty Filter Switch
AE Phase Monitor & Coil Guard
AF Phase Monitor & Dirty Filter Switch
AG Coil Guard & Dirty Filter Switch
AH Phase Monitor, Coil Guard, & Dirty Filter Switch
BA Hinged Filter Door & Tooless Access Panels
BB Phase Monitor, Hinged Filter Door & Tooless Access Panels
BC Coil Guard, Hinged Filter Door & Tooless Access Panels
BD Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
BE Phase Monitor & Coil Guard, Hinged Filter Door & Tooless Access Panels
BF Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
BG Coil Guard & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
BH Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
CA CPC Controller with Dirty Filter Switch & Air Proving Switch
CB CPC Controller, DFS, APS & Phase Monitor
CC CPC Controller, DFS, APS & Coil Guard
CD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CE CPC Controller, DFS, APS & Technicoat Cond. Coil
CF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CJ CPC Controller, DFS, APS & Technicoat Evap. Coil
CK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
DA CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Tooless Access Panels
DB CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels
DC CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels
DD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DE CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels
DF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
DG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DJ CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels
DK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
DL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Tooless Access Panels
DP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
DQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
036-21536-001-A-0403
Unitary Products Group 5
EA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Tooless Access Panels
EB Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels
EC Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels
ED Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
EE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels
EF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
EG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
EH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
EJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels
EK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
EL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
EM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
EN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Tooless Access Panels
EP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
EQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Tooless Access Panels
ER Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access
Panels
GA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Tooless Access Panels
GB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels
GC Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels
GD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
GE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels
GF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
GG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
GH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access
Panels
GJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels
GK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
GL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
GM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access
Panels
GN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Tooless Access Panels
GP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Tooless Access
Panels
GQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Tooless Access Panels
GR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless
Access Panels
HA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
HB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
HC Honeywell Excel 10 Controller, DFS, APS & Coil Guard
HD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
HE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
HF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
HG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
HH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
HJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
HK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
HL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
HM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
HN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
HP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
HQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
HR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
JA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
Additional Options
036-21536-001-A-0403
6 Unitary Products Group
JB Johnson UNT Controller, DFS, APS & Phase Monitor
JC Johnson UNT Controller, DFS, APS & Coil Guard
JD Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
JE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
JF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
JG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
JH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
JJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
JK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
JL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
JM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
JN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
JP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
JR Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
NA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
NB Novar ETC-3 Controller, DFS, APS & Phase Monitor
NC Novar ETC-3 Controller, DFS, APS & Coil Guard
ND Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
NE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
NF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
NG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
NH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
NJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
NK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
NL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
NM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
NN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
NP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
NQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
NR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
PA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Tooless Access Panels
PB Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels
PC Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels
PD Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels
PF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
PG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels
PK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
PL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Tooless Access Panels
PP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
PQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access
Panels
TA Technicoat Condenser Coil
TB Technicoat Condenser Coil & Phase Monitor
TC Technicoat Condenser Coil & Coil Guard
TD Technicoat Condenser Coil & Dirty Filter Switch
TE Technicoat Condenser Coil, Phase Monitor, & Coil Guard
Additional Options
036-21536-001-A-0403
Unitary Products Group 7
TF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
TH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TJ Technicoat Evaporator Coil
TK Technicoat Evaporator Coil & Phase Monitor
TL Technicoat Evaporator Coil & Coil Guard
TM Technicoat Evaporator Coil & Dirty Filter Switch
TN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
TP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
TR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TS Technicoat Evaporator & Condenser Coils
TT Technicoat Evaporator & Condenser Coils & Phase Monitor
TU Technicoat Evaporator & Condenser Coils & Coil Guard
TV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
TW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
TX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
TY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
TZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
UA Technicoat Condenser Coil, Hinged Filter Door & Tooless Access Panels
UB Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Tooless Access Panels
UC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Tooless Access Panels
UD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UE Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
UF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UJ Technicoat Evaporator Coil, Hinged Filter Door & Tooless Access Panels
UK Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Tooless Access Panels
UL Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Tooless Access Panels
UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
UP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
US Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Tooless Access Panels
UT Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Tooless Access Panels
UU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Tooless Access Panels
UV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
UX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
Additional Options
036-21536-001-A-0403
8 Unitary Products Group
FEATURES
All models are available with a wide variety of factory-
mounted options such as phase monitor, dirty filter switch,
and coil guard to make them suitable for almost every appli-
cation.
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at
the factory to simplify the field installation and to provide
years of dependable operation.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. Models with
factory installed power exhaust are suitable for bottom
duct connections only. For bottom duct, you remove the
sheet metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, you replace
the supply and return air panels on the rear of the unit with a
side duct flange accessory.
All models are available with these factory mounted outdoor
air damper options:
Single enthalpy economizer
Single enthalpy economizer with power exhaust
Motorized outdoor air damper
A fixed outdoor air intake assembly will be shipped in the
return air compartment of all units ordered without an econo-
mizer or motorized outdoor air damper option. The assembly
includes a rain hood with a damper that can be set for 10, 15
or 25% outdoor air. With bottom duct connections, the intake
damper assembly should be mounted over the opening in the
return air panel. With horizontal ductwork, it should be
mounted on the return air duct.
All supply air blowers are equipped with a belt drive that can
be adjusted to meet the exact requirements of the job. A high
static drive option is available for applications with a higher
CFM and/or static pressure requirement.
All compressors have internal pressure relief. Every refriger-
ant circuit includes an expansion valve, a liquid line filter-
drier, a discharge line high pressure switch and a suction line
with a freezestat and low pressure/loss of charge switch to
protect all system components.
Simplicity Controls - Simplicity control boards
have standardized a number of features previously avail-
able only as options or by utilizing additional controls.
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0F outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling
fan delay times are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas and electric heat units. The unit con-
trol board will alarm on ignition failures, compressor
lockouts and repeated limit switch trips.
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a
three times, youre out philosophy. The high and
low-pressure switches and the freezestats must trip
three times within two hours before the unit control
board will lock out the associated compressor.
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
All units have long lasting powder paint cabinets with 750
hour salt spray test approval under ASTM-B117 procedures.
All models are CSA approved.
Electric Heat Operation - All electric heat models (fac-
tory installed only) are wired for a single power source
and include a bank of nickel chromium elements
mounted at the discharge of the supply air blower to pro-
vide a high velocity and uniform distribution of air across
the heating elements. Every element is fully protected
against excessive current and temperature by fuses and
two thermal limit switches.
The power supply wiring can be routed into the control
box through a threaded pipe connection in the base pan
of the unit or through a knockout in the wiring panel on
the front of the unit.
BAS Controls - Yorks Sunline series units offer fac-
tory mounted BAS controls such as Novar, Honeywell,
Johnson, and CPC.
036-21536-001-A-0403
Unitary Products Group 9
FACTORY-INSTALLED OPTIONS
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
Power exhaust is not available as a field installed
option.
POWER EXHAUST - Our single economizer options are
available with power exhaust. Whenever the outdoor air
intake dampers are opened for free cooling, the exhaust
fan will be energized to prevent the conditioned space
from being over-pressurized during economizer opera-
tion.
The exhaust fan, motor and controls are installed and
wired at the factory. The rain hood and the back-draft
damper need to be assembled and installed in the field.
The power exhaust option can only be used on bot-
tom duct configurations.
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is oper-
ating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
PHENOLIC COATED EVAPORATOR AND CON-
DENSER COILS - Special coating process that utilizes
Technicoat 10-1" processes. Coating is applied by total
immersion of the complete coil for maximum protection.
ELECTRIC HEATERS wired for single point power sup-
ply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent
operation at excessive temperatures.
FILTER OPTIONS - Standard units are shipped with 2
throw-away filters installed. 2 pleated and 4 pleated fil-
ters are offered as a factory installed option.
CONVENIENCE OUTLET - This 110 volt outlet can be
powered by the unit with a stepdown transformer or
you may order the unit with a non-powered conve-
nience outlet that can be wired in the field.
DISCONNECT SWITCH - For heat pump units, a HACR
breaker sized to the name plate max fuse size for the
particular unit is provided. Factory installed option only.
BAS - See Additional Options section in the product
nomenclature.
SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of-
phase condition.
HIGH SPEED DRIVE - Includes a belt and blower pulley
upgrade to enhance blower performance.
DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
HINGED FILTER DOOR/TOOLESS BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
NOTE: Knobs are shipped separately within the unit to
prevent shipping damage. These must be field
installed for tool-less operation.
FIELD-INSTALLED ACCESSORIES
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
Power exhaust is not available as a field installed option.
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
Power exhaust is not available as a field installed option.
ROOF CURBS - Fourteen-inch high roof curbs provide a
water-tight seal between the unit and the finished roof.
036-21536-001-A-0403
10 Unitary Products Group
These full perimeter curbs meet the requirements of the
National Roofing Contractors Association (NRCA) and
are shipped knocked-down for field assembly.
They're designed to fit inside the base rails of the unit
and include both a wood nailing strip and duct hanger
supports.
SIDE DUCT FLANGES - One-inch flanges replace the
supply and return air panels on the rear of the unit to
accommodate horizontal duct connections. These
flanges can also be used individually for bottom supply/
horizontal return or horizontal supply/bottom return. They
cannot be used on units with power exhaust.
BAROMETRIC RELIEF DAMPER - This damper acces-
sory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
HIGH SPEED DRIVE - A smaller blower pulley and a
shorter belt increase the speed of the supply air blower
for applications with a higher CFM and/or static pressure
requirements.
ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
WOOD SKID - Allows unit to be handled with 90 forks.
CO
2
SENSOR - Senses CO
2
levels and automatically
overrides the economizer when levels rise above the
present limits.
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of-
phase condition.
036-21536-001-A-0403
Unitary Products Group 11
FIGURE 1 - SUNLINE 2000
TM
HEAT PUMP
HIGH EFFICIENCY COMPRESSORS
WITH CRANKCASE HEATERS
COPPER TUBE/ALUMINUM FIN
OUTDOOR COILS
LOW VOLTAGE RELAY BOARD
AND TERMINAL STRIP
ELECTRICAL DISCONNECT
MOUNTING LOCATION
(Field Installed)
TERMINAL BLOCK
(For Single Point Power Supply
With Electirc Heat)
KNOCKOUT FOR
SIDE CONTROL WIRING AND
SIDE POWER WIRING ENTRY
BOTTOM & CONTROL
WIRING ENTRY
ELECTRIC HEATER LOCATION
(OPTION)
BELT-DRIVE
BLOWER MOTOR
FULL PERIMTER 14 GUAGE BASE
RAILS WITH LIFTING HOLES
NPT FEMALE
CONDENSATE DRAIN
SIDE AND BOTTOM
SUPPLY & RETURN AIR

OUTDOOR AIR OPENING
FOR INTERNAL ECONOMIZER
2" DISPOSABLE
FILTERS
ECONOMIZER HOOD
LONG LASTING POWDER PAINT FINISH
TABLE 1: CAPACITY RATINGS - COOLING
MODEL
DESIGN TEMPERATURES (C)
TOTAL OUTPUT
kW / MBH
TOTAL INPUT
kW
COP
1
EER
2
SENSIBLE
OUTPUT
kW / MBH
LATENT OUTPUT
kW / MBH
RATING
3
POINT
INDOOR
DB / WB
OUTDOOR
DB / WB
BQ240
T1 27 / 19 35 / 24 60.2 / 205 22.8 2.65 9.00 50.3 / 172 9.9 / 34
T2 29 / 19 46 / 24 52.0 / 177 26.2 2.00 6.75 52.0 / 177 0.0 / 0
T3 21 / 15 27 / 19 52.7 / 180 20.8 2.55 8.65 42.6 / 145 10.1 / 34
1. COP = Coefficient of Performance - total output kW divided by the total input kW.
2. EER = Energy Efficiency Ratio - total output Mbh divided by the total input kW.
3. T1 = Moderate Climates, T2 = Hot Climates, T3 = Cool Climates.
TABLE 2: CAPACITY RATINGS - HEATING
MODEL
DESIGN TEMPERATURES (C)
TOTAL OUTPUT
kW / MBH
TOTAL INPUT
kW
COP
1
EER
2
ELECTRIC HEAT
3
NOMINAL CAPACITY
kW
RATING
POINT
INDOOR
DB / WB
OUTDOOR
DB / WB
BQ240
High 20 / 12 7 / 6 63.9 / 218 20.2 3.15 10.80
15, 27, 40, 54 Low 20 / 12 2 / 1 34.9 / 119 17.3 2.00 6.85
X-Low 20 / 12 -7 / -8 23.5 / 80 15.5 1.50 5.20
1. COP = Coefficient of Performance - total output kW divided by the total input kW.
2. EER = Energy Efficiency Ratio - total output Mbh divided by the total input kW.
3. Heaters available as factory-installed options - all with single point power supply.
036-21536-001-A-0403
12 Unitary Products Group
TABLE 3: COOLING CAPACITIES (M
3
/S AIRFLOW) - 240 UNIT
AIR ON
INDOOR COIL
TOTAL
1
CAP.
kW
POWER
2
INPUT
KW
SENSIBLE CAPACITY
1
, kW
ENTERING DRY BULB TEMPERATURE, C
m
3
/s WB C 32 30 28 26 24 22
@ 27C AIR TEMPERATURE ON OUTDOOR COIL
4.44
23 76.0 20.5 64 56 47 39 31 -
21 71.8 20.2 72 64 55 47 39 31
19 67.5 19.9 68 68 63 55 47 39
17 65.3 19.7 65 65 65 60 52 44
15 63.1 19.4 63 63 63 59 51 42
3.78
23 73.7 20.3 56 49 41 34 26 -
21 69.6 20.1 63 56 48 41 33 26
19 65.5 19.8 65 63 55 48 40 33
17 63.3 19.6 63 63 60 52 45 38
15 61.2 19.3 61 61 61 57 50 42
2.83
23 67.7 19.8 47 41 36 30 24 -
21 63.9 19.6 53 47 42 36 30 24
19 60.1 19.3 59 54 48 42 36 30
17 58.2 19.1 58 58 52 46 40 34
15 56.2 18.9 56 56 56 50 44 39
@ 35C AIR TEMPERATURE ON OUTDOOR COIL
4.44
23 67.2 25.5 55 47 39 30 22 -
21 65.0 23.6 65 57 49 41 33 24
19 62.7 21.7 63 63 59 51 43 35
17 59.3 22.8 59 59 59 52 44 36
15 55.9 23.9 56 56 56 52 43 35
3.78
23 68.4 22.5 52 45 37 30 22 -
21 66.1 20.8 62 55 47 40 33 25
19 63.8 19.2 64 64 58 50 43 35
17 60.3 20.1 60 60 59 51 44 36
15 56.8 21.1 57 57 57 52 45 38
2.83
23 59.1 24.9 40 34 29 23 17 -
21 57.1 23.1 48 42 36 31 25 19
19 55.2 21.2 55 50 44 38 33 27
17 52.1 22.3 52 51 45 39 33 28
15 49.1 23.4 49 49 46 40 34 28
@ 46C AIR TEMPERATURE ON OUTDOOR COIL
4.44
23 62.7 25.6 56 47 39 31 23 -
21 59.1 25.0 59 55 47 39 31 22
19 55.5 24.3 56 56 55 47 39 30
17 54.2 24.2 54 54 54 49 41 33
15 52.9 24.1 53 53 53 49 40 32
3.78
23 60.1 25.3 50 42 35 27 20 -
21 56.6 24.6 57 49 42 35 27 20
19 53.2 24.0 53 53 49 42 34 27
17 51.9 23.9 52 52 51 44 36 29
15 50.7 23.8 51 51 51 46 39 31
2.83
23 56.0 24.5 41 35 29 23 18 -
21 52.8 23.9 47 41 35 29 24 18
19 49.6 23.3 50 47 41 35 30 24
17 48.4 23.2 48 48 43 37 31 26
15 47.3 23.1 47 47 45 39 33 27
1. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance
Table for the kW of the supply air blower motor.
2. These ratings include the outdoor fan motors (Total 1.5 kW) and the compressor motors but not the supply air blower motor.
036-21536-001-A-0403
Unitary Products Group 13
TABLE 4: COOLING CAPACITIES (CFM AIRFLOW) - 240 UNIT
AIR ON
INDOOR COIL
TOTAL
1
CAP.
MBH
POWER
2
INPUT
KW
SENSIBLE CAPACITY
1
, MBH
ENTERING DRY BULB TEMPERATURE, F
CFM WB F 90 86 82 79 75 72
@ 80F AIR TEMPERATURE ON OUTDOOR COIL
9400
73 259 20.5 218 190 161 133 105 -
70 245 20.2 245 217 189 161 132 104
66 230 19.9 230 230 216 188 160 132
63 223 19.7 223 223 223 206 178 150
59 215 19.4 215 215 215 201 173 145
8000
73 252 20.3 191 166 141 115 90 -
70 237 20.1 215 190 165 139 114 89
66 223 19.8 223 214 188 163 138 112
63 216 19.6 216 216 204 179 154 128
59 209 19.3 209 209 209 195 169 144
6000
73 231 19.8 161 141 121 102 82 -
70 218 19.6 181 162 142 122 103 83
66 205 19.3 202 183 163 143 124 104
63 198 19.1 198 196 177 157 137 118
59 192 18.9 192 192 191 171 151 132
@ 95F AIR TEMPERATURE ON OUTDOOR COIL
9400
73 229 25.5 188 160 132 104 75 -
70 222 23.6 222 196 167 139 111 83
66 214 21.7 214 214 203 175 146 118
63 202 22.8 202 202 202 178 150 122
59 191 23.9 191 191 191 177 148 120
8000
73 233 22.5 178 153 127 102 77 -
70 225 20.8 213 187 162 137 111 86
66 218 19.2 218 218 197 171 146 120
63 206 20.1 206 206 200 175 150 124
59 194 21.1 194 194 194 179 153 128
6000
73 202 24.9 137 117 98 78 58 -
70 195 23.1 163 144 124 104 85 65
66 188 21.2 188 170 150 131 111 91
63 178 22.3 178 173 153 134 114 94
59 168 23.4 168 168 156 137 117 97
@ 115F AIR TEMPERATURE ON OUTDOOR COIL
9400
73 214 25.6 190 162 134 105 77 -
70 202 25.0 202 189 161 133 104 76
66 189 24.3 189 189 188 160 132 103
63 185 24.2 185 185 185 168 140 112
59 180 24.1 180 180 180 166 138 110
8000
73 205 25.3 170 145 119 94 68 -
70 193 24.6 193 169 143 118 93 67
66 181 24.0 181 181 168 142 117 92
63 177 23.9 177 177 175 150 124 99
59 173 23.8 173 173 173 157 132 107
6000
73 191 24.5 139 119 99 80 60 -
70 180 23.9 159 139 120 100 80 61
66 169 23.3 169 160 140 121 101 81
63 165 23.2 165 165 147 127 107 88
59 161 23.1 161 161 153 133 113 94
1. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance
Table for the kW of the supply air blower motor.
2. These ratings include the outdoor fan motors (Total 1.5 kW) and the compressor motors but not the supply air blower motor.
036-21536-001-A-0403
14 Unitary Products Group

* The MBH and kW values do not include the supply air blower motor.

TABLE 5: HEATING CAPACITIES (M
3
/S AIRFLOW) - 240 UNIT
m
3
/s
RETURN AIR
C
CAP. (C)
PWR. (P)
(KW)
OUTDOOR AIR TEMPERATURE, C (72% RH)
-20 -15 -10 -5 0 5 10 15 20
2.83
13
C 16.9 21.8 27.7 34.8 42.9 52.1 62.5 73.9 86.5
P 11.4 12.1 13.0 13.9 14.8 15.9 17.0 18.2 19.5
20
C 16.2 20.6 26.0 32.4 39.9 49.1 58.5 68.8 80.1
P 11.6 12.5 13.7 14.7 15.7 16.8 17.9 19.2 20.5
27
C 15.4 19.4 24.3 30.2 37.0 44.6 53.1 62.4 72.5
P 11.9 12.8 13.8 14.8 15.9 17.0 18.2 19.4 20.7
3.78
13
C 17.4 22.3 28.4 35.7 44.0 53.5 64.1 75.8 88.7
P 10.7 11.4 12.2 13.0 13.9 14.9 16.0 17.1 18.3
20
C 16.8 21.5 27.3 34.2 42.3 52.3 62.6 74.0 86.6
P 11.5 12.3 13.2 14.2 15.3 16.4 17.5 18.8 20.1
27
C 16.3 20.7 26.2 32.8 40.6 49.5 59.5 70.6 82.9
P 11.7 12.7 13.7 14.8 16.0 17.2 18.5 19.9 21.3
4.44
13
C 17.8 22.9 29.2 36.6 45.1 54.9 65.8 77.8 91.0
P 10.0 10.7 11.4 12.2 13.1 14.0 15.0 16.0 17.2
20
C 17.5 22.5 28.7 36.1 44.8 55.7 67.0 79.7 93.6
P 11.1 11.9 12.8 13.8 14.8 15.9 17.1 18.4 19.7
27
C 17.2 22.0 28.1 35.6 44.5 54.8 66.6 79.9 94.8
P 11.6 12.6 13.7 14.9 16.1 17.4 18.8 20.3 21.9
TABLE 6: HEATING CAPACITIES (CFM AIRFLOW) - 240 UNIT
CFM
RETURN AIR
F
CAP. (MBH)
PWR. (kW)
OUTDOOR AIR TEMPERATURE, F (72% RH)
-4 5 14 23 32 41 50 59 68
6000
55
MBH 58 74 95 119 146 178 213 252 295
kW 11.4 12.1 13.0 13.9 14.8 15.9 17.0 18.2 19.5
68
MBH 55 70 89 111 136 167 199 235 273
kW 11.6 12.5 13.7 14.7 15.7 16.8 17.9 19.2 20.5
80
MBH 53 66 83 103 126 152 181 213 248
kW 11.9 12.8 13.8 14.8 15.9 17.0 18.2 19.4 20.7
8000
55
MBH 59 76 97 122 150 182 219 259 303
kW 10.7 11.4 12.2 13.0 13.9 14.9 16.0 17.1 18.3
68
MBH 57 73 93 117 144 178 214 253 296
kW 11.5 12.3 13.2 14.2 15.3 16.4 17.5 18.8 20.1
80
MBH 56 70 89 112 138 169 203 241 283
kW 11.7 12.7 13.7 14.8 16.0 17.2 18.5 19.9 21.3
9400
55
MBH 61 78 99 125 154 187 224 265 310
kW 10.0 10.7 11.4 12.2 13.1 14.0 15.0 16.0 17.2
68
MBH 60 77 98 123 153 190 229 272 320
kW 11.1 11.9 12.8 13.8 14.8 15.9 17.1 18.4 19.7
80
MBH 59 75 96 122 152 187 227 273 323
kW 11.6 12.6 13.7 14.9 16.1 17.4 18.8 20.3 21.9
036-21536-001-A-0403
Unitary Products Group 15
NOTES: 1.Blower performance includes fixed outdoor air, 2 T/A filters, a dry evaporator coil and no electric heat.
2.Refer to Table 8 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
TABLE 7: BQ240 SUPPLY AIR WITH DOWNFLOW DUCT APPLICATIONS
BLOWER
SPEED,
(RPM)
MOTOR
PULLEY
(TURNS
OPEN)*
AIRFLOW
2.80 m
3
/s 3.30 m
3
/s 3.80 m
3
/s 4.10 m
3
/s 4.40 m
3
/s
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
STANDARD DRIVE (m
3
/s)
765 6.0 137 2.9 3.3 93 2.9 3.3 23 3.2 3.7 - - - - - -
795 5.0 176 3.0 3.4 132 3.1 3.5 62 3.4 3.9 - - - - - -
820 4.0 209 3.1 3.6 165 3.2 3.7 95 3.6 4.1 40 4.0 4.5 - - -
850 3.0 250 3.3 3.8 206 3.4 3.9 136 3.8 4.4 81 4.2 4.8 16 4.7 5.3
875 2.0 284 3.4 3.9 240 3.6 4.1 170 4.0 4.6 115 4.4 5.0 51 4.9 5.6
905 1.0 327 3.6 4.1 283 3.8 4.3 212 4.3 4.9 157 4.7 5.3 93 5.2 5.9
HIGH SPEED DRIVE (m
3
/s)
895 6.0 312 3.5 4.0 268 3.7 4.3 198 4.2 4.8 143 4.6 5.2 79 5.1 5.8
930 5.0 362 3.7 4.3 318 4.0 4.5 248 4.5 5.1 193 4.9 5.6 129 5.4 6.2
970 4.0 421 4.0 4.5 377 4.2 4.9 306 4.8 5.5 252 5.2 6.0 187 5.8 6.6
1005 3.0 473 4.2 4.8 429 4.5 5.1 359 5.1 5.8 304 5.6 6.4 240 6.1 7.0
1045 2.0 535 4.4 5.0 491 4.8 5.5 420 5.4 6.2 365 5.9 6.8 - - -
1080 1.0 590 4.6 5.3 546 5.0 5.8 475 5.7 6.5 420 6.2 7.1 - - -
BLOWER
SPEED,
(RPM)
MOTOR
PULLEY
(TURNS
OPEN)*
AIRFLOW
5930 CFM 6990 CFM 8050 CFM 8685 CFM 9320 CFM
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
STANDARD DRIVE (CFM)
765 6.0 0.6 3.8 3.3 0.4 3.9 3.3 0.1 4.3 3.7 - - - - - -
795 5.0 0.7 4.0 3.4 0.5 4.1 3.5 0.2 4.6 3.9 - - - - - -
820 4.0 0.8 4.2 3.6 0.7 4.4 3.7 0.4 4.8 4.1 0.2 5.3 4.5 - - -
850 3.0 1.0 4.4 3.8 0.8 4.6 3.9 0.5 5.1 4.4 0.3 5.6 4.8 0.1 6.2 5.3
875 2.0 1.1 4.6 3.9 1.0 4.8 4.1 0.7 5.4 4.6 0.5 5.9 5.0 0.2 6.6 5.6
905 1.0 1.3 4.8 4.1 1.1 5.1 4.3 0.9 5.7 4.9 0.6 6.3 5.3 0.4 6.9 5.9
HIGH SPEED DRIVE (CFM)
895 6.0 1.3 4.7 4.0 1.1 5.0 4.3 0.8 5.6 4.8 0.6 6.1 5.2 0.3 6.8 5.8
930 5.0 1.5 5.0 4.3 1.3 5.3 4.5 1.0 6.0 5.1 0.8 6.6 5.6 0.5 7.2 6.2
970 4.0 1.7 5.3 4.5 1.5 5.7 4.9 1.2 6.4 5.5 1.0 7.0 6.0 0.8 7.8 6.6
1005 3.0 1.9 5.6 4.8 1.7 6.0 5.1 1.4 6.8 5.8 1.2 7.4 6.4 1.0 8.2 7.0
1045 2.0 2.1 5.9 5.0 2.0 6.4 5.5 1.7 7.3 6.2 1.5 7.9 6.8 - - -
1080 1.0 2.4 6.2 5.3 2.2 6.8 5.8 1.9 7.7 6.5 1.7 8.4 7.1 - - -
036-21536-001-A-0403
16 Unitary Products Group
* Factory Setting
Power Exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.
TABLE 8: STATIC RESISTANCES
1
DESCRIPTION
RESISTANCE, IWG/Pa
m
3
/s (CFM)
20 TON
2.9 (6000) 3.8 (8000) 4.5 (9400)
WET INDOOR COIL 0.1/25 0.1/25 0.1/25
ELECTRIC HEAT OPTIONS
18 KW 0.1/25 0.1/25 0.1/25
36 KW 0.1/25 0.2/50 0.3/75
54 KW 0.2/50 0.3/75 0.4/100
72 KW 0.2/50 0.4/100 0.6/150
ECONOMIZER OPTION 0.1/25 0.1/75 0.1/25
HORIZONTAL DUCT CONNECTIONS
2
0.2/50 0.3/75 0.5/125
1. Deduct these resistance values from the available external static pressures shown in the respective Blower Performance Table (See Note 2 for
exception.)
2. Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures to the ESP values
on the respective units blower performance table.
TABLE 9: POWER EXHAUST PERFORMANCE
MOTOR
SPEED
STATIC RESISTANCE OF RETURN DUCTWORK, IWG/Pa
0.2/50 0.3/75 0.4/100 0.5/125 0.6/150
m
3
/s (CFM)
KW
m
3
/s (CFM)
KW
m
3
/s (CFM)
KW
m
3
/s (CFM)
KW
m
3
/s (CFM)
KW
HIGH* 2.47 (5250) 0.83 2.12 (4500) 0.85 1.98 (4200) 0.88 1.77 (3750) 0.93 1.41 (3000) 0.99
MEDIUM 2.31 (4900) 0.77 1.84 (3900) 0.79 1.65 (3500) 0.82 1.37 (2900) 0.85 - -
LOW 2.07 (4400) 0.72 1.74 (3700) 0.74 1.41 (3000) 0.78 - - - -
TABLE 10: BLOWER MOTOR AND DRIVE DATA
UNIT
SIZE
(MBH)
BLOWER
RANGE
(RPM)
MOTOR
1
ADJUSTABLE MOTOR PULLEY
2
FIXED BLOWER PULLEY
BELT
(NOTCHED)
kW/HP
FRAME
SIZE
EFF.
(%)
PITCH DIA.
(mm / in.)
BORE
(mm / in.)
DESIG-
NATION
PITCH DIA.
(mm / in.)
BORE
(mm / in.)
DESIG-
NATION
PITCH
LENGTH
(mm/in.)
DESIG-
NATION
QTY.
240
STD
DRIVE
765 - 905 5.6/7.5 213T 89
140 - 165
5.5 - 6.5
35 / 1-3/8 1VP68 264 / 10.4 30 / 1-3/16 BK110 2078 / 81.8 BX80 1
HIGH
SPEED
DRIVE
895-1080 5.6/7.5 213T 87
147-178
5.8-7.0
35 / 1-3/8 1VP75 239 / 9.4 30 / 1-3/16 BK100 2103 / 82.8 BX81 1
1. All motors are 1450 RPM, have solid bases and a 1.10 service factor.
2. Do NOT close this pulley below 1 turn open.
036-21536-001-A-0403
Unitary Products Group 17

NOTE: This unit does NOT REQUIRE a heat pump
thermostat. It is designed to work with a stan-
dard two-stage cool, two-stage heat thermo-
stat; however, the thermostat must provide a
G signal when there is a call for W1.

FIGURE 2 - ELECTRONIC THERMOSTAT FIELD WIRING
W2
RC
RH
Y1
Y2
W1
G
C
X1
X3
X4
A1
|
A2
|
T
T
THERMOSTAT*
TERM NALS
UN T TERM NALS
STR P TB1
* El ectroni c programmabl e Thermostat 2ET077001 0024 (i ncl udes subbase).
|
Termi nal s A1 and A2 provi de a rel ay output to cl ose the outdoor
economi zer dampers when the thermostat swi tches to the set-back posi ti on.
24 Vol t
Transformer
TO REMOTE SENSOR
2ET04701 324 F USED
OCC
W1
W2
Y1
G
Y2
X
R
SD
C
R
E
M
O
T
E
M

N

P
O
S
FIGURE 3 - FIELD WIRING 24 VOLT THERMOSTAT
OCC
W1
W2
Y1
G
Y2
X
R
SD
C
R
E
M
O
T
E
M

N

P
O
S
W1
W2
Y1
G
Y2
C
UN T CONTROL
BOARD
T-STAT
RH
RC
The thermostat must provide a G signal
when there is a call for W1.The unit control
board will energize the indoor blower when
the compressors are energized; however, if
the thermostat calls for W2 during the anti-
short-cycle delay, the electric heat (when
installed) will be energized immediately
upon the call for W2.
The thermostat must provide a G signal
when there is a call for W1.The unit control
board will energize the indoor blower when
the compressors are energized; however, if
the thermostat calls for W2 during the anti-
short-cycle delay, the electric heat (when
installed) will be energized immediately
upon the call for W2.
036-21536-001-A-0403
18 Unitary Products Group

FIGURE 4 - FIELD WIRING DISCONNECT
TERM NAL BLOCK TB1
GROUND
LUG
THREE
PHASE
POWER
SUPPLY
FACTORY OR F ELD
SUPPL ED D SCONNECT
TABLE 11: VOLTAGE LIMITATIONS
POWER SUPPLY
VOLTAGE
MIN. MAX.
380/415-3-50 342 456
036-21536-001-A-0403
Unitary Products Group 19

Note 1: Maximum HACR breaker of the same amp size is acceptable.
Note 2: Only 18kW of the 36 or 54kW, or only 36kW of the 72kW electric heat can be simultaneously energized with the mechanical
heating. The full heater kW operates only if both compressors are locked out.

Note 1: Maximum HACR breaker of the same amp size is acceptable.
Note 2: Only 18kW of the 36 or 54kW, or only 36kW of the 72kW electric heat can be simultaneously energized with the mechanical
heating. The full heater kW operates only if both compressors are locked out.
TABLE 12: ELECTRICAL DATA -WITHOUT POWERED CONVENIENCE OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL
KW
2
STAGES AMPS
BQ240
380 9.6 66 2.1 11.7 0.0
- 0.0 - - 57.2 60
E18 11.3 1 17.1 78.7 80
E36 22.6 2 34.3 78.7 80
E54 33.8 2 51.4 78.8 80
E72 45.1 2 68.6 100.3 110
415 9.6 66 2.1 11.7 0.0
- 0.0 - - 57.2 60
E18 13.5 1 18.7 80.7 90
E36 26.9 2 37.4 80.7 90
E54 40.4 2 56.2 84.9 90
E72 53.8 2 74.9 104.0 110
TABLE 13: ELECTRICAL DATA -WITH POWERED CONVENIENCE OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL KW
2
STAGES AMPS
BQ240
380 9.6 66 2.1 11.7 6.3
- 0.0 - - 63.5 70
E18 11.3 1 17.1 85.0 90
E36 22.6 2 34.3 85.0 90
E54 33.8 2 51.4 86.7 90
E72 45.1 2 68.6 108.2 110
415 9.6 66 2.1 11.7 6.3
- 0.0 - - 63.5 70
E18 13.5 1 18.7 87.0 90
E36 26.9 2 37.4 87.0 90
E54 40.4 2 56.2 92.8 100
E72 53.8 2 74.9 110.3 125
TABLE 14: ELECTRIC HEAT CORRECTION FACTORS
NOMINAL VOLTAGE VOLTAGE KW CAP. MULTIPLIER
380 380 0.627
415 415 0.75
036-21536-001-A-0403
20 Unitary Products Group
TABLE 15: PHYSICAL DATA - BASIC UNIT
MODEL BQ240
SUPPLY AIR
BLOWER
CENTRIFUGAL BLOWER
(Dia. x Wd. mm.)
(Dia. x Wd. in.)
457 x 381
18 x 15
FAN MOTOR (KW/HP) 5.6/7.5
INDOOR COIL
ROWS DEEP 4
FINS PER INCH 13
FACE AREA (Sq. M./Sq. Ft.) 1.92 x 20.5
OUTDOOR
FAN
(Two Per Unit)
PROPELLER DIA. (mm/in.) (Each) 762/30
FAN MOTOR (KW/HP) (Each) .8/1.25
NOM. M
3
/S/CFM TOTAL (Each) 3.4/7200
OUTDOOR COIL
ROWS DEEP 3
FINS PER INCH 15
FACE AREA (Sq. M./Sq. Ft.) 4.02/43.3
COMPRESSOR
(Qty. Per Unit)
10 TON TANDEM 2
AIR
FILTERS
QUANTITY PER UNIT (406 X 508 X 51 mm) / (16" X 20" X 2") 4
QUANTITY PER UNIT (406 X 635 X 51 mm) / (16" X 25" X 2") 4
TOTAL FACE AREA (sq. ft.) 20.0
CHARGE REFRIGERANT 22
SYSTEM NO. 1 (Kg./Lbs.) 10.88/24.0
SYSTEM NO. 2 (Kg./Lbs.) 11.3/25.0
TABLE 16: OPERATING WEIGHTS (KG./LBS.)
MODEL BQ240
Basic Unit BQ (Heat Pump) 998/2200
Options
Economizer 73/160
Economizer with Power Exhaust 111/245
Motorized Damper 68/150
Electric Heater
18 KW 11/25
36 KW 14/30
54 KW 16/35
72 KW 18/40
Accessories
Roof Curb 79/185
Barometric Damper 20/45
Wood Skid 91/220
036-21536-001-A-0403
Unitary Products Group 21

NOTE: Units and ductwork are approved for zero clearance to
combustible materials when equipped with electric
heaters.
NOTE: All entry holes should be field sealed to prevent rain
water entry into building.
FIGURE 5 - UNIT DIMENSIONS - 20 TON
All dimensions are in millimeters and
inches. They are subject to change with-
out notice. Certified dimensions will be
provided upon request.
TABLE 17: MINIMUM CLEARANCES (MM/IN.)
LOCATION CLEARANCE
Front 914 mm/36
Back
610 mm/24 (Less Economizer)
1245 mm/49 (With Economizer)
Left Side (Filter Access)
610 mm/24 (Less Economizer)
914 mm/36 (With Economizer)
Right Side (Cond. Coil) 914 mm/36
Below Unit
1
1. Units (applicable in U.S.A. only) may be installed on
combustible floors made from wood or class A, B or C
roof covering material.
0 mm/0
Above Unit
2
2. Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct outdoor air dis-
charge outlet.
1829 mm/72 With 914 mm/36
Maximum Horizontal Overhang
(For Condenser Air Discharge)
TABLE 18: UTILITIES ENTRY DATA (MM/IN.)
HOLE OPENING SIZE (DIA.) USED FOR
A
28.6 mm/1-1/8 KO
Control Wiring
Front
19.1 mm/3/4 NPS (Fem.) Bottom
B
92.1 mm/3-5/8 KO
Power Wiring
Front
76.2 mm/3 NPS (Fem.) Bottom
036-21536-001-A-0403
22 Unitary Products Group



DUCT COVERS - Units are shipped with the bottom
duct openings covered. An accessory flange kit is available for con-
necting side ducts.
For bottom duct applications:
1. Remove the side panels from the supply and return
air compartments to gain access to the bottom
supply and return air duct covers.
2. Remove and discard the bottom duct covers. (Duct
openings are closed with sheet metal covers except
when the unit includes a power exhaust option. The
covering consists of a heavy black paper composition.)
3. Replace the side supply and return air compartment
panels.
For side duct applications;
1. Replace the side panels on the supply and return air
compartments with the accessory flange kit panels.
2. Connect ductwork to the duct flanges on the rear of
the unit.
OUTDOOR AIR PANEL SIZE
20 TON UNITS 32-1/2" X 43"
FIGURE 6 - DETAIL X ACCY. SIDE SUPPLY & RETURN AIR OPENINGS
FIGURE 7 - DETAIL Y UNIT WITH RAIN HOODS
FIGURE 8 - CENTER OF GRAVITY
036-21536-001-A-0403
Unitary Products Group 23


FIGURE 9 - FOUR AND SIX POINT LOADS
A
E
D
B
F
C
FRONT
A
B
C
D
FRONT
TABLE 19: FOUR AND SIX POINT LOADS
UNIT
4 - POINT LOADS (Kg. / Lbs)
TOTAL A B C D
240 1084/2390 233/514 244/538 310/684 297/654
NOTE: These weights are with economizer and 36 kW electric heat.
UNIT
6 - POINT LOADS (Kg. / Lbs)
TOTAL A B C D E F
240 1084/2390 156/343 163/359 185/407 207/456 198/436 176/389
NOTE: These weights are with economizer and 36 kW electric heat.
4 Point Loads 6 Point Loads
036-21536-001-A-0403
24 Unitary Products Group


FIGURE 10 - ROOF CURB DIMENSIONS - 20 TON
FIGURE 11 - ROOF CURB BENEFITS
FIGURE 12 - UNIT AND CURB APPLICATIONS
036-21536-001-A-0403
Unitary Products Group 25

FIGURE 13 - TYPICAL APPLICATIONS
FIGURE 14 - TYPICAL ROOF-TOP INSTALLATION
036-21536-001-A-0403
26 Unitary Products Group
FIGURE 15: SIMPLICITY CONTROL WIRING DIAGRAM
W1
W2
Y1
G
OCC
P
P1
Y2
X
R
SD
C
C
SD
SD
R
OCC
C
RC
G
Y2
Y1
W2
W1
Jumper
Smoke
Detector
24 VAC
Class 2
X
R
THERMOSTAT
TERMINALS
CONTROL
TERMINAL
BLOCK
TERMINALS ON
A LIMITED
NUMBER OF
THERMOSTATS
3
1
2
4
3
1
2
4
Second stage heating not required on single stage heating units.
Second stage cooling not required on single stage cooling units.
Jumper is required if there is no Smoke Detector circuit.
Jumper is required for any combination of R, RC, or RH.
6
5
5
6
OCC is an output from the thermostat to indicate the Occupied condition.
X is an input to the thermostat to display Error Status conditions.