Sunteți pe pagina 1din 2

S900

Remote Terminal Unit (RTU) / Sequence of Events Recorder (SER)


Applications
Low to high voltage subsations
Refurbishment or new
substations
Medium to large capacity
Protective relay supervision
Automatic functions integrated
Capacity
Up to 3 SCADA links
Up to 256 relays or IEDs
supervised
Up to 32 serial link
Via I/Os boards :
- DIs : up to 4032
- DOs : up to 1024
- AIs : up to 480
Up to 2 printers
Performances
DIs :
- 1ms time tagging
AIs :
- Up to 1s refresh rate
- 0.1% precision full scale
Sequence control :
- From 10 ms time cycle
Time accuracy :
- 1 ms for centralised I/O
- Implementation dependant for
connected relays
The S900 has been developed for
use in distributed environments such
as power generation, transmission
and distribution substations and
industrial sites.
Substation control operations are
realised by data capture and output
controls via dedicated I/O boards
or by communication links with
protective relays and IEDs. The
controls can be executed with
immediate operate or in select
before operate mode.
Modules and racks feature high
modular design. Racks can be
geographically distributed in a site
(substation, power plant) to optimise
wiring. Racks are linked through the
FIP Bus (1 Mbits/sec) and
synchronised.
The S900 can communicate with
three master stations using a
partitioned database and different
communication protocols.
The S900 can managed up to
256 protective relays or data from
Intelligent Electronic Devices (IEDs)
connected on serial ports (up to
32). The S900 supports multiple
protocols: Modbus, K-Bus Courier,
IEC 60870-5-101, IEC 60870-5-103.
Performing automatic controls
described using IEC 61131-3
standards can be implemented to
define interlock functions and
automatic sequences such as
automatic reclosure and busbar
transfer.
A user-friendly Human Machine
Interface (HMI) can be used with
the S900 to control and supervise
the entire plant and system.
The S900 can communicate with
three master stations using
IEC 60870-5-101, DNP3,
HNZ 66S15, HNZ ELENAS.
The S900 is a set of hardware and software designed to be
used in Remote Terminal Unit (RTU) or Sequence of Events
Recorder (SER). The S900 is designed to the highest standards
of performance, safety and reliability to meet the requirements
of the ELECTRICAL Power industry.
Technical specifications
Power supply
24 Vdc 20%
48/60 Vdc 20%
110/125 Vdc 20%
220 Vdc 20%
250 Vdc -20%, +10%
DI ratings
Opto isolated inputs
10 mA for 24 Vdc
5 mA for 48 Vdc
3 mA for 60 Vdc
3 mA for 110/125 Vdc
1 mA for 220/250 Vdc
Dielectric insulation
2.8 kV peak at 50 Hz
DO ratings
Breaking capacity for signaling
2A at 250 Vdc, 250 Vac
Breaking capacity for command
Continuous current : 5 A
Surge current : 30 A / 500 ms
Power : 1000 VA and L/R=40 ms
AI ratings
Range
5, 10, 20, 4-20 mA
1.25, 2.5, 5 V
Input impedance
250 for current
> 10 M for voltage
AO ratings
Range
5, 10, 20, 4-20 mA
Load impedance
6 k at 5 mA, 3 k at 10 mA,
1.5 k at 20 mA
Relay interfaces
Up to 256 protective relays
K-Bus Courier
RS232 connection through KITZ
101/201
115 Kbaud
Up to 32 protections per serial links
Modbus
RS232 connection through
RS232/RS485 converter
Up to 19200 baud
IEC 60870-5-103 (VDEW)
RS232 connection through
RS232/optical converter
9600 or 19200 baud
IEC 60870-5-101
RS232 connection
Up to 19200 baud
SCADA interfaces
Up to 3 master stations
IEC 60870-5-101 / DNP3 /
HNZ 66S15-ELENAS
RS232 connection through external
modem
Single or double link
Up to 19200 baud
Hardware
Rack
6U, 19
Up to 32 racks
O
u
r

p
o
l
i
c
y

i
s

o
n
e

o
f

c
o
n
t
i
n
u
o
u
s

d
e
v
e
l
o
p
m
e
n
t

a
n
d

t
h
e

r
i
g
h
t

i
s

r
e
s
e
r
v
e
d

t
o

s
u
p
p
l
y

e
q
u
i
p
m
e
n
t

w
h
i
c
h

m
a
y

v
e
r
y

f
r
o
m

t
h
a
t

d
e
s
c
r
i
b
e
d
.
Protection & Control, HQ, 60 Route de Sartrouville, BP58, 78230 Le Pecq Cedex. France
Tl: +33 (0) 134 80 79 00 Fax: +33 (0) 134 80 79 13 Email: protection.control@tde.alstom.com Internet: www.tde.alstom.com
Publication: L1 6366 A 2000 ALSTOM 080002 - ARCEAUX 49 Imp. - Printed in France
TRANSMI SSI ON & DI STRI BUTI ON
Master station 1
Printer 1
Alphanumeric control
E/S
E/S
Protective
relays
or IEDs
FIP Bus
S900 main
S900 extended
Protective
relays
or IEDs
Printer 2
External clock
Master station 2
Master station 3
OPN A9311 OPN A9311 OPN A9311
OPN A9311
Rear I/O connectors
Front face communication
connectors
Enclosure
1 rack standard box
42U standard cubicle
1 rack shielded box, IP55
42U shielded cubicle, IP55
Electrical safety
Dielectric voltage withstand
2.8 kV peak at 50 Hz for 1 minute
on I/O according to
IEC 60870-2-1 and IEC 60060-1
Surge dielectric withstand
5 kV peak, 1.2/50 ms on I/O
according to IEC 60255-5
and IEC 60060-1
Immunity to HF disturbances
1 MHz 2.5 KV peak on I/O,
according to IEC 61000-4-12,
IEEE 472 and ANSI C37-90
Electrostatic discharge
8 kV in air, 6 kV points contact
according to IEC 61000-4-2
Electromagnetic disturbance
10 V/m according to
IEC 61000-4-3
Environment withstand
0C to +60C according to
IEC 60068-2-1 and -2-2
5% to 95% humidity according to
IEC 60068-2-3

S-ar putea să vă placă și