YORK Refrigeration, Controls

Jens Juuls Vej 28, 8260 Viby J, Denmark


Phone +45 86 28 79 11, Fax +45 86 28 71 44
CVR No 10301491 F:\SABROE CONTROLS GROUP\IVH\COMSAB II PLC DRIVER DOKUMENTATION KOPI AF\SIEMENS S5.DOC
1
Comsab Driver for Siemens PLC Type S5
1 Hardware
Siemens PLC 115U, CPU 941, 942, 943
CP 523 card, 6ES5 523-3UA11
Please note:
- for 135U the CPU 928B is used + RS232 insert module
- for 115U the CP 523 card is used
2 Function
In DB100 is keyed in how many values that are wanted read/written in the connected
compressors. The compressors are keyed in succession: 1-2-3-4 etc. and no holes
must occur. Each compressor has its own DB (DB70 DB83). Here is keyed in the
wanted values to be read/written (HEX-number, see York Comsab II manual).
Further, the values that are wanted transferred to the compressor are keyed in.
Max 14 compressors
Max 29 reading points per compressor
Max 10 writing points per compressor
3 DBes for compressors
DB 70 (compressor 1)
DB 71 (compressor 2)
DB 72 (compressor 3)
DB 73 (compressor 4)
-
-
-
-
-
DB 83 (compressor 14)
4 Grouping of the DBes for the compressors
DW 1: Hex. number for the wanted points in Comsab to be read (see
Comsab II manual read list)
DW 2:
-:
-:
-:
DW 29:
DW 50: Answer from Comsab (integer KF)
Answer is multiplied by a factor 10.
DW 51:
-:
-:
DW78:
YORK Refrigeration, Controls
Jens Juuls Vej 28, 8260 Viby J, Denmark
Phone +45 86 28 79 11, Fax +45 86 28 71 44
CVR No 10301491 F:\SABROE CONTROLS GROUP\IVH\COMSAB II PLC DRIVER DOKUMENTATION KOPI AF\SIEMENS S5.DOC
2
Answer from question in DW 1 is read in DW 50.
Answer from question in DW 2 is read in DW 51 etc.
DW 100: Hex number for the wanted points in Comsab to be written to.
DW 101:
-:
-:
DW 109:
DW 150: Value for Comsab (Integer KF)
Value must be multiplied by a factor 10.
DW 151:
-:
-:
DW 159:
Value in DW 150 belongs to DW 100.
Value in DW 151 belongs to DW 101 etc.
5 Example of keying into DB100
5.1
DW 1: KF +10 (read 10 points in compressor 1)
DW 31: KF +3 (write 3 points in compressor 1)
DW 2: KF +12 (read 12 points in compressor 2)
DW 32: KF +2 (write 2 points in compressor 2)
etc.
In general
DW 1 DW 14 reading point number for compr. 1
14
DW 31 DW 44 writing point number for compr. 1
14
If the contents in one of these data words = 0, then the driver restarts from 1.
5.2 Example for compressor 2
Number of values that is to be read/keyed into DW 2 and number of values
that is to be written/keyed into DW 32.
Read 5 values + write 2 values in compressor 2:
DW 2: KF + 5, DW 32: KF + 2
Example for compressor 4
Read 4 values in compressor 4:
DW 4: KF + 4, DW 34: KF + 0
5.3 If a compressor is not connected to the system
then write KF + 0 in the belonging DW
YORK Refrigeration, Controls
Jens Juuls Vej 28, 8260 Viby J, Denmark
Phone +45 86 28 79 11, Fax +45 86 28 71 44
CVR No 10301491 F:\SABROE CONTROLS GROUP\IVH\COMSAB II PLC DRIVER DOKUMENTATION KOPI AF\SIEMENS S5.DOC
3
6. Examples of keying into DB for compressor
6.1 Compressor 7
wants to read A: Oil temperature (22 H)
B: Suction temperature (20 H)
To Comsab
DB 76 DW 1 KH 26 22
DW 2 KH 26 20
From Comsab
DB 76 DW 50 KF value (oil temperature)
DW 51 KF value (suction temperature)
6.2 Compressor 3
Wants to write A: set point 1 Suction pressure (2FH)
B set point 2 Suction pressure (3OH)
To Comsab
DB 72 DW 100 KH 22 2F
DW 101 KH 22 30
DW 150 KF 234 (-23.4 C)
DW 151 KF 325 (- 32.5 C)
The values in DW 150 and DW 151 are transferred to Comsab.
7. Cable
Comsab II Siemens PLC (CP 523)
No connec. Screen 1
Pin no. 8 (Rx) - 11
Pin no. 2(Tx) - 5
Pin no. 1(Gnd) - 21
-
Plug (9 pole) (25 pole)