LOCATION : BONIFACIO EXTENSION, AGUADA, OZAMIS CITY
STRUCTURAL ANALYSIS AND DESIGN CRITERIA DESIGN CRITERIA:
Live Load : Floor Load : 1920 Pa (Residential Occupancy) Table 205-1, NSCP2010 : 4800 Pa (Stair Loading) Dead Load : : 4000 N/m (Wall dead weight with opening) : 6500 N/m (Wall dead weight without opening) 2943 N/m 2 (Floor Dead weight plus floor finishes) Self weight : 23540 N/m 3 (Concrete) Fc : 20.7 MPa (3.0 ksi) Class A
Steel Modulus: 200GPa Fy : 276 MPa Main Reinforcements Grade 40 : 228 MPa Secondary Reinforcements Grade 33 Min. ReBar : 10 mm diameter Max ReBar : 16 mm diameter
Seismic Zone Factor, Z: 0.40 Section 208.4.4.1 of NSCP 2010
Importance Factor, I: 1.00 Standard Occupancy. Section 208.4.2 of NSCP 2010 Pension House Building
Rw : 8.5 Structural system numerical coefficient representative of the inherent over-strength and global ductility capacity for Concrete Moment Resisting Space Frame system.
Na : 1.0 Near source factor near Western Mindanao Fault Nv : 1.0 Near source factor near Western Mindanao Fault
Soil Type, S : 4.0 Soil Profile Silt Medium Dense/ Clay Med Stiff
Soil Bearing Cap: 100 kPa Maximum Soil Bearing Capacity, from table 7.7 See Soil Testing Result.
Max. EQ Mag: 7 & up Maximum Earthquake Magnitude consideration
Load Combination : As per Section 409.3 of the NSCP2010 6 th Edition 1.4 Dead Load (409-1)
1.2 Dead Load +1.6 Live Load +0.5 Roof Live Load (409-2)
1.2 Dead Load +1.0 Live Load +1.6 Roof Live Load (409-3)
1.508 Dead Load +1.4 Earthquake +Live Load (409-5)
1.208 Dead Load +1.4 Earthquake Load (409-7)
As per Section 426.409.2 of the NSCP2010 6 th Edition
1.358 Dead Load +1.275 Live Load +1.4 Earthquake (426-2)