Fire Protection Engineering


J eff L. Harrington, P. E.
Jeff L. Harrington, P. E.
Sun, 2006-01-01 (All day)
History shows that many advances in warehouse fire protection were derived from the lessons learned
during the investigation process after catastrophic or otherwise significant fire losses.
History shows that many advances in warehouse fire protection were derived from the lessons learned
during the investigation process after catastrophic or otherwise significant fire losses. Seven key lessons
learned in this manner are discussed below.
LESSON 1 Sprinkler Design Must Match the Fire Hazard:
This lesson is illustrated by the evolution of sprinkler protection for the
storage of aerosol cans that contain combustible contents. A large
warehouse fire at Supermarket General in Edison, NJ, in 1978 was an
initial catalyst that motivated the aerosol industry to launch an extensive
research program, which culminated in a much clearer understanding of
the fire hazard of aerosols containing combustible contents, and new
protection standards for them.
1
The 1982 Kmart warehouse fire in Falls
Township, PA,
2
infused additional momentum into this process. These two
fires were convincing proof that the then-current protection approach for
aerosol storage was inadequate.
On April 16, 1996, a fire grew quickly out of control and completely destroyed the 8000 m
2
(85,000 sq ft)
single-story Lowe's bulk retail store in Albany, GA.
3
This fire grew so rapidly that it penetrated the roof
and filled the building with smoke down to the 1.5 m (5 ft) level, all within about five minutes. The fire
department was able to mount only a defensive attack from the building exterior. The fire was finally
extinguished a little over two days later, after having completely destroyed the building.
The investigation of this fire revealed that the fire started in a rack used to store calcium hypochlorite pool
chemicals, a Class lll oxidizer,
4
in plastic containers. The ceiling-only sprinkler system, designed to protect
Class III commodities stored in racks to 6 m (20 ft.) high, was not matched to the fire hazard and,
therefore, did not control the fire.
Another fire in a bulk retail warehouse occurred in Tempe, AZ, on March 19, 1998.
5
The fire hazard
consisted of rack storage of Group A plastic commodities to 4.5 m (15 ft). The sprinkler system, designed
to protect Class IV commodities stored in racks 6 m ( 20 ft) high, was not matched to the fire hazard and
Lessons Learned fromUnderstanding Warehouse Fires http://magazine.sfpe.org/print/special-hazards/lessons-learned-understand...
1 of 6 8/1/2014 6:10 PM
did not control the fire. The public fire department eventually extinguished this fire, but damage was
substantial and the total loss was approximately $6 million.
Lesson 2 Sprinklers and Sprinkler Water Supplies Must Be Maintained in Service
An automatic sprinkler system requires an adequate water supply for a sufficient duration to be successful
in controlling or suppressing a fire. A deficiency in water supply pressure, flow rate, or duration has been
a major contributing factor in numerous catastrophic warehouse fires. These fire losses serve to
emphasize what is intuitively obvious: water supplies are critical to successful fire control and
extinguishment.
A large warehouse facility in New Orleans, LA, suffered two major fire events in a single day.
6
The second
fire proved catastrophic. On March 21, 1996, an incendiary fire in portable rack storage was finally
declared extinguished at 11:54 a.m. by the fire department, 5 hours, 22 minutes after it began. Then, at
approximately 2:20 p.m., a second fire of accidental origin started and quickly grew out of control. This
fire was declared extinguished six days later, after completely destroying the 87,000 m
2
(930,000 sq ft)
general merchandise warehouse area.
After the first fire, all of the building's sprinkler systems were shut down by closing their individual control
valves in an attempt to reduce water damage. When the second fire began, all of the sprinkler systems in
the building effectively had no water supply. This allowed the fire to grow quickly beyond the capability of
the fire department to control it.
Many warehouse sprinkler systems depend on one or more automatic fire pumps for adequacy of water
supply flow and pressure. Fire pumps must operate reliably until the sprinkler system controls or
suppresses the fire. Fire pump reliability depends upon proper design, installation, inspection, testing,
and maintenance.
On October 20, 1977, almost two-thirds of the Ford Parts Depot near Cologne, Germany, was destroyed by
fire.
7
Only 10 minutes after the fire started, power to the electric fire pump failed. The power wiring for
this pump was run inside the building, across the ceiling directly over the area of fire origin. About 45
minutes after the electric fire pump lost power, it was discovered that the diesel fire pump was also not
running. It was then successfully started manually. Ultimately, 74,000 m
2
(800,000 sq ft) of warehouse
space was completely destroyed by this fire, resulting in a loss exceeding $100 million.
Lesson 3 Fire Detection and Notification Must Not Be Delayed
Automatic fire detection in a warehouse environment is most often provided by the sprinkler system via a
water flow switch. Normally, the water flow switch is connected to the building's local fire alarm control
panel, providing local notification. The fire alarm control panel may be monitored by a remote Central
Station service, which calls the fire department immediately upon receipt of a fire alarm signal, such as
sprinkler water flow activation.
Notification of the local and public emergency response personnel by means of the sprinkler water flow
switch is sufficient, assuming that the sprinkler system will be successful in controlling or suppressing the
fire. This is a valid assumption if the sprinkler system was properly designed to match the fire hazards
present; was properly installed; is properly inspected, tested, and maintained; and has an adequate,
reliable water supply.
Lessons Learned fromUnderstanding Warehouse Fires http://magazine.sfpe.org/print/special-hazards/lessons-learned-understand...
2 of 6 8/1/2014 6:10 PM
In many instances, a fire is discovered by a building occupant prior to the activation of the first sprinkler
and therefore prior to the activation of the water flow switch. Such early fire discovery can capture
valuable time that can be used to provide early warning of the fire to the other building occupants and to
the local and public emergency responders.
Shortening the time lapse between detection and notification is very important, and can be accomplished
by careful design of equipment, through written emergency procedures, and by effective training of
building occupants.
For example, all regular building occupants should be trained to immediately notify a designated
individual of the fire by prearranged means, such as by house phone, manual pull station, two-way radio,
pager, etc. Second, the occupant should evacuate the building, initiate incipientstage firefighting, or take
other action as determined by the written emergency response plan. If an employee's first action after
discovering the fire is something other than notifying someone else, unnecessary time delay will occur. If,
at the same time, there is a problem with the sprinkler system or water supply, the time delay could be
disastrous.
The first action of the employees who initially discovered the Ford Parts Depot fire was an attempt to fight
the fire themselves with small hose lines. They did not notify the on-site fire brigade or anyone else. The
Ford fire brigade was eventually notified approximately 15 minutes later by water flow alarm from the
first sprinkler activation. The initial fire hose attack by the regular employees was unsuccessful in
controlling the fire, even after persisting in the attempt until the first sprinkler actuated. This, in turn, led
to a substantial delay in notifying the other building occupants and the formally trained fire brigade.
On March 11, 1970, an employee discovered a fire in a furniture distribution warehouse
8
and attempted to
extinguish it using one, and then another, portable fire extinguisher. This effort at manual fire
extinguishment was unsuccessful. Then, another employee attempted to connect a garden hose to a water
source to spray water on the fire. Before the garden hose was connected and deployed to the fire area, the
fire had spread to adjacent piles of furniture in cardboard boxes and was growing rapidly. The fire
department was finally notified by telephone approximately 20 minutes after the initial fire discovery. But
it was too late and the fire destroyed the facility, resulting in a loss of approximately $8 million.
LESSON 4 Occupant Fire Suppression Attempts Often Fail
Combustible storage, vertically stacked, leads to rapid initial fire growth. A fire in rack storage of
combustible commodities has been shown by full-scale experiment to have a power-law dependence on
time to the third power during the initial growth period.
9
A fire can therefore quickly grow beyond the
capability of portable fire extinguishers and small fire hoses.
This may explain why the initial attempts of building occupants to manually suppress fires in warehouses
in their incipient stage so often fail. During the time it takes for an occupant to take notice of a fire and
begin to apply extinguishant to the fire, the fire has been growing exponentially and has already reached a
size that cannot be extinguished by portable extinguishers or a single small fire hose.
During the Ford Parts Depot and Furniture Transport Terminal fire incidents,building occupants
discovered the fire prior to the activation of the first sprinkler. Their first action was to attempt manual
fire suppression using portable fire extinguishers, which eventually failed.
Lessons Learned fromUnderstanding Warehouse Fires http://magazine.sfpe.org/print/special-hazards/lessons-learned-understand...
3 of 6 8/1/2014 6:10 PM
After discovering the first New Orleans warehouse fire, building occupants attempted manual suppression
with portable fire extinguishers. This attempt failed. Next, they wasted more time by retrieving a portable
hose reel cart and connected it to a nearby fire hose connection. After unreeling the hose, they discovered
that is it was not equipped with a nozzle. Next, they retrieved a second hose cart that was equipped with a
nozzle and used it to spray water on the fire, but this was unsuccessful because the fire had grown too
large. The public fire department, having been notified by a water flow signal, eventually suppressed this
fire 5 hours, 22 minutes after it began. The delay in notifying the fire department caused by the failed
occupant suppression attempts was a contributing factor in this large loss.
LESSON 5 Fire Defense Strategies Must Consider the Environment
Several catastrophic warehouse fires have shown that, for certain commodities, the fire defense strategies
should include the potential impact on the exterior environment. These potential impacts include the
effects of liquid runoff on nearby streams, rivers and lakes, and below-ground drinking water aquifers.
Also, the effects of prevailing winds on the fire plume on nearby residential and business centers should be
considered.
In November 1986, 30 tons of toxic material was washed into the Rhine River by water used by the public
fire department to extinguish a fire at the Sandoz chemical plant and storage facility near Basel,
Switzerland.
10
A toxic chemical slick 40 km (25 miles) long was created, resulting in widespread
destruction of aquatic life, which only began recovering more than a year following the incident. The fire
occurred in an unsprinklered warehouse storing chemicals in a high-piled configuration. Massive
amounts of water were poured onto this fire for about 24 hours to effect complete extinguishment as
quickly as possible. It was later discovered that nearly all of the water used in fire suppression flowed
through storm drains directly into the Rhine.
In stark contrast to the Sandoz fire incident, the fire suppression strategies employed during the Sherwin-
Williams warehouse fire in Dayton, OH, were an environmental success story. A fire started accidentally
in this fully sprinklered, 18,000 m
2
(190,000 sq ft) warehouse on May 27, 1987, and quickly overpowered
the building's sprinkler systems.
11
The warehouse contained over 5,700,000 liters (1.5 million gallons) of
paint and paint-related products, and was sitting directly above a water aquifer that provided drinking
water to about one-third of the area's population.
The fire department, public officials, and Sherwin-Williams representatives collaborated in developing the
fire suppression strategy for this fire while the incident was unfolding. The impacts of air, ground, and
surface water pollution were considered carefully. The decision was made to let the fire burn itself out and
cease pouring water onto the fire. The risk of contaminating the underground drinking water supply was
deemed higher than that associated with the smoke plume. Efforts to let the fire safely burn itself out,
while catching all water runoff, were highly successful in preventing contamination of the aquifer.
12
LESSON 6 Fire Prevention Efforts Can Be Focused NFPA has compiled statistics on structure fires
in storage properties.13 There was an average of 22,900 fires per year in storage occupancies for the
period 19941998. The leading cause of these fires was intentional fire-setting (arson). Other top fire
causes include open flame, embers, or torches, which includes hot work activities such as welding and
Lessons Learned fromUnderstanding Warehouse Fires http://magazine.sfpe.org/print/special-hazards/lessons-learned-understand...
4 of 6 8/1/2014 6:10 PM
cutting; electrical distribution equipment such as fixed wiring, transformers, and circuit breakers; other
equipment such as fuel-powered and electric-powered equipment. Chemical reactions between
incompatible chemicals have also been known to ignite warehouse fires. These top fire causes in
warehouse environments consistently remain near the top of the list year after year. Therefore, specifically
targeting them can have a significant impact in reducing the probability of fire.
For example, improving internal and external security can reduce the chance of intentionally set fires.
Lack of security is an invitation to criminals or disgruntled employees. The first fire at the warehouse in
New Orleans was intentionally set within a 21-foot high storage rack that was not equipped with in-rack
sprinklers, leading to a major fire loss. The bulk retail warehouse fire in Tempe, AZ, was started
intentionally in a 4.5 m (15 ft) high storage rack containing lawn furniture seat cushions, also resulting in
a major loss.
Strict adherence to a hot work safety management program by welltrained personnel can reduce the
chance of ignition by hot work. Guidance is available in NFPA 51B.
14
Effective preventive maintenance on industrial trucks coupled with proper training and certification of
operators can minimize the probability of a fire. Both the Kmart2 and Sherwin-Williams11 fires were
started when flammable vapors came into contact with hot forklift truck engine components. A propane-
powered lift truck operating in a warehouse for a flock manufacturing plant caught fire when a fuel system
fitting came loose.
15
The operator jumped off of the truck and watched it roll into a storage array
containing baled flock and rags, which then ignited.
Careful planning for the storage of incompatible chemicals can minimize the probability of these
chemicals accidentally coming into contact with one another leading to ignition. The fires at Albany, GA
(1996), Quincy, MA ( 1995),
16
and Phoenix, AZ ( 2000),
17
were each apparently started when
incompatible materials contaminated pool chemicals. The contamination resulted in an exothermic
chemical reaction, which in turn ignited the immediately adjacent combustibles.
Lesson 7 Provide and Maintain Effective Compartmentation
Today, the building codes and insurance underwriters allow warehouse facilities to contain very large
undivided areas, exceeding 90,000 m
2
(1 million sq ft) in some cases. However, where fire walls or
barriers are required, or provided, they can be very effective in stopping the spread of fire and the
combustion byproducts of heat and smoke. Therefore, care should be taken to maintain these fire barriers
in good condition, including opening protective devices, such as fire doors or fire shutters.
The New Orleans, LA, warehouse was constructed with two fire compartments. The fire started in the
largest compartment, which covered 86,000 m
2
(930,000 sq ft) This compartment was separated from
the adjacent 19,000 m
2
(200,000 sq ft) compartment by a fire barrier wall. Eventually, the second fire at
this facility on March 21, 1996, completely destroyed the largest compartment, including collapse of
major portions of the roof. The fire barrier protected the small compartment well, which sustained only
minor damage from smoke and heat.
Jeff Harrington is with Harrington Group, Inc.
References
Lessons Learned fromUnderstanding Warehouse Fires http://magazine.sfpe.org/print/special-hazards/lessons-learned-understand...
5 of 6 8/1/2014 6:10 PM
Chemical Times & Trends, The Journal of the Chemical Specialties Manufacturers Association
(CSMA), An Industry Responds: "A Technical History of the CSMA Aerosol Warehouse Storage Fire
Protection Research Program," January 1988 and April 1988.
1.
NFPA Fire Investigations Report, "Storage Fire (Kmart), Fall Township, PA, June 21, 1982,"
National Fire Protection Association, Quincy, MA.
2.
NFPA Fire Investigations Report, "Bulk Retail Store Fire, Albany, GA, April 16, 1996," National
Fire Protection Association, Quincy, MA.
3.
NFPA 430, Code for the Storage of Liquid and Solid Oxidizers, National Fire Protection
Association, Quincy, MA, 2004 Edition.
4.
NFPA Fire Investigations Report, "Bulk Retail Store Fire, Tempe, AZ, March 19, 1998," National
Fire Protection Association, Quincy, MA.
5.
NFPA Fire Investigations Report, "Warehouse Fire, New Orleans, LA, March 21, 1996," National
Fire Protection Association, Quincy, MA.
6.
"Ford Warehouse Fire Offers No Fire Protection Surprises," Fire Journal, January, 1979. 7.
Watrous, L., "Large Undivided Areas, High Fire Load, No Sprinkler Protection, Strong Winds,
Congestion, Delayed Reporting," Fire Journal, July, 1970.
8.
Yu, H-Z, "The Transient Ceiling Flows of Growing Rack Storage Fires," Fire Safety Science,
Proceedings of the Third International Symposium, 1991, p. 281-290.
9.
United States Fire Administration, Federal Emergency Management Agency, Technical Report
Series, "Sherwin-Williams Paint Warehouse Fire, Dayton, Ohio (May 27, 1987) With Supplement
on Sandoz Chemical Plant Fire, Basel, Switzerland," 1987.
10.
NFPA Fire Investigations Report, "Flammable Liquid Warehouse Fire, Dayton, Ohio, May 27,
1987," National Fire Protection Association, Quincy, MA.
11.
United States Fire Administration, Federal Emergency Management Agency, Technical Report
Series, "Sherwin-Williams Paint Warehouse Fire, Dayton, Ohio (May 27, 1987) With Supplement
on Sandoz Chemical Plant Fire, Basel, Switzerland," 1987.
12.
Ahrens, M., "Selections From The U.S. Fire Problem Overview Report Leading Causes and Other
Patterns and Trends Storage Properties Excluding Dwelling Garage," National Fire Protection
Association, Quincy, MA, June 2003.
13.
NFPA 51B, Standard for Fire Prevention During Welding, Cutting and other Hot Work, National
Fire Protection Association, Quincy, MA, 2003 Edition.
14.
"Textile Storage," Fire Journal, March/April, 1989, p. 23. 15.
NFPA Fire Investigations Report, "Bulk Retail Store Fire, Quincy, MA, May 23, 1995," National
Fire Protection Association, Quincy, MA.
16.
NFPA Fire Investigations Report, "Storage Warehouse, Phoenix, AZ, August 2, 2000," National
Fire Protection Association, Quincy, MA.