Analysisanddesignofreinforcedconcretereservoir

foracapacityof115m
3

Translated and Presented By: Civilax.com




Analysis and design of reinforced concrete reservoir
for a capacity of 115 m
3

DESIGNOFASUPPORTEDFORRESERVOIRCAPACITY115m
3

1. General
Information.

1.1. Geometry.

Type: a reservoir for storing water for human consumption shall be deemed,
under section 2.1.1 ACI 350.3-01 circular tank
is classified as reinforced concrete slab with
free wall-no-Flexible 2.2 (1).
Volume : Storage equal to 115 cubic meters.

Radio : Interior (D) of 7.00 m.

Alturas : Effective water storage height (Hl) equal to


3.00 m.
Depth buried (He) equal to 1.00

meters.

Height Total of wall (HW) equal to 4.00


m.
Arrow design for the dome (Fc) equal to

Light over 10 thus 7.00 / 10 =

0.70 meters.
Thickness of walls : tw = 0.20 meters.

Thickness of the Dome : Ce = 0.10 meters with a widening 0.15

meters at 1 meter from the dome-wall junction.


Thickness of Foundation : Hz = 0.25 meters.

Flown Foundation : v = 0.50 meters.


Analysis and design of reinforced concrete reservoir
for a capacity of 115 m
3

1.2. Materials.
Strength of Concrete : f'c = 210 Kg / cm
2
at 28 days.

It's Concrete : According to ACI 350M-01 section 8.5.1 =


15100 f
'
c= 218819.79 Kg / cm
2
.
steel fy : 4200 Kg / cm
2
.

1.3. Used regulations.

Code Requirements for Environmental Engineering Concrete Structures (ACI


350M-01) And Commentary (ACI 350RM-01), ACI Committee 350 Reported By.
Seismic Design of Liquid-Containing Concrete Structures (ACI 350.3-01)
and Commentary (350.3R-01), Reported by ACI Committee 350.
Design Considerations for Environmental Engineering Concrete Structures
(ACI 350.4R-04), Reported by ACI Committee 350.
Concrete Structures for Containment of Hazardous Materials (ACI 350.2R-
04), Reported by ACI Committee 350.
Tightness Testing of Environmental Engineering Concrete Structures (ACI
350.1-01) and Commentary (350.1R-01), Reported by ACI Committee 350.
Environmental Engineering Concrete Structures (ACI 350.R-89), Reported
by ACI Committee 350.
Building Code Requirements for Structural Concrete (ACI 318M-08) and
Commentary, ACI Committee 318 Reported by.
Technical Standard for Buildings "Earthquake-resistant Design" E-030.

2. Analysis (according Methodology Appendix A of ACI 350.3-01).

2.1. Static Seismic Analysis.

The results presented were evaluated in Excel spreadsheets and Sap2000


program.

Calculation of Effective Mass, according to ACI 350.3-01 Section 9.5.2:



M uro weight (W w) + Domeweight (W r) 5466.34kg
M uro weight (W w) 4330.55kg
Dome wei ght (W r) 1135.79kg
Interiordiameter(D) 7.00m
Effecti ve Li qui d hei ght (Hl ) 3.00m
Effecti ve l oop coeffi ci ent M () (for Dead Wei ght) 0.66
EffectiveloopM(We)(byDeadWeight) 3985.34kg
Analysis and design of reinforced concrete reservoir
for a capacity of 115 m
3

Calculation of Effective Mass of the stored liquid, impulsive component


(Wi) and convective component (Wc) as ACI 350.3-01 Section 9.3.1:


MTotalLiquidhandleacenadoAlm(Wl) 115000.00kg
D/Hl 2.33
Wi/Wl 0.48
Wc/Wl 0.49
Equi val ent Wei ght rapporteur Com I m pul si va W i 54946.11kg
Equi val ent Wei ght rapporteur Com Convecti ve W c 56665.44kg

Calculating the combined natural vibration frequency (wi) of the structure


and the liquid stored impulsive component as ACI 350.3-01 section 9.3.4

Analysis and design of reinforced concrete reservoir
for a capacity of 115 m
3


Hl /D 0.43
Coef. For det. Frequency Fund. Tankl i qui d (Cw) 0.156
Murothickness(tw) 0.20m
Innerrimradius R 3.50m
Coef. For det. Frequency Fund. Tankl i qui d (Cl ) 0.373
ResistancetopressureComConcrete(f'c) 210.00kg/cm
Moduleofelasticityofconcrete(Ec) 21458.90MPa
Concretedensity(c) 2.40kN.S2/m
Freq. Ci rc. The m ode vibration compul si ve i m (wi ) 371.92rad/
Fund period. Rocki ng Tank + Com p. Im compulsive (Ti) 0.0169s

Calculate the frequency of vibration of the convective component (wc) as


ACI 350.3-01 Section 9.3.4:


Analysis and design of reinforced concrete reservoir
for a capacity of 115 m
3

Accel erati on due to gravi ty (g) 9.81m/s2


10,426
Freq. ci rcular vi brati on pri m er m convecti ve peri od (wc) 3.94rad/s
N atural peri od of pri m er m convecti ve peri od (Tc) 1.59s

Parameters for Calculating Seismic Force as ACI 350.3-01 NTE section 4.2
and E-030:
The area factor corresponding to the Seismic Zone ACI 350.3 is similar to
the values specified in the NTE E-030 Section 2.1. Being in the high hazard
area shall be taken as Zone 3 with an acceleration of 0.30 g (NTE as E-
030), which is equivalent to Zone 4 ACI 350.3-01.

As for the parameter value of the soil, according to NTE 030 E-Type S3
corresponds to a value of 1.4, this time also the value is very similar to
that proposed by ACI 350.3-01.

The NTE E-030, ranks as reservoirs Essential Building (A) that corresponds
to the factor 1.5. NTE is seen that the E-030 does not have categories for
major reservoirs such as ACI 350.3-01, which categorizaramos this model in
the second type corresponding to reservoirs intended to remain in use for
emergency purposes in seismic events. For this model we use the highest
value of 1.5.
Analysis and design of reinforced concrete reservoir
for a capacity of 115 m
3

The Sharpe ratio Response Modification or seismic force reduction if we


used the NTE E-030 would have a value of 6, as in the previous parameter,
we see that the ACI 350.3-01 delivery values for different types of
reservoirs, and more NTE restrictive than the E-030. AL factors needed for
impulsive and convective components will use the values Rwi Rwc = 2.75 and
= 1.00 (type b).
Analysis and design of reinforced concrete reservoir
for a capacity of 115 m
3

Calculating spectral amplification factors Ci and Cc, as ACI 350.3-01


section 4.2:


Coeff i ci ent represent i ng t he char acteri sti cs of t he soi l ( S) 1.40
Spectral ampl i fi cati on factor Am for m ov. Hori zontal Ci 1.96
Spectral ampl i fi cati on factor Am for m ov. Hori zontal Cc 1.37

Calculation of the maximum displacement of the liquid contents (dmax) as


ACI 350.3-01 Section 7.1:


Analysis and design of reinforced concrete reservoir
for a capacity of 115 m
3

Factor zone (Z) 0.40


I m i mportance factor (I ) 1.50
Margin Shift M axim umentV erticalliquid content(dm ax) 4.04m

Calculate the height of the center of gravity location of impulsive and


convective components as ACI 350.3-01 Section 9.3.2:

hi / Hl 0.375
Hei ght at center of G ravedad of Com p. I m pul si va (hi ) 1.13m
hc / Hl 0.58
Hei ght at center of G ravedad of Com p. Convecti ve (hc) 1.75m

Calculation of dynamic lateral forces, according to ACI 350.3-01 Section


4.1.1:

Analysis and design of reinforced concrete reservoir
for a capacity of 115 m
3



Factorzone (Z) 0.40
Imimportance factor(I) 1.50
Coeffi ci ent representi ng the characteri sti cs of the soi l (S) 1.40
Coef. From MENDMENT I m pul si vas Response Forces (Rwi ) 2.75
Coef. From MENDMENT Convecti ve Response Forces (Rwc) 1.00
Effecti ve Wei ght Tank M uro (.W w) 2849.55kg
Dome Tankwei ght (W r) 1135.79kg
Equi val ent Wei ght rapporteur Com Im pul si va W i 54946.11kg
Equi val ent Wei ght rapporteur Com Convecti ve W c 56665.44kg
Spectralampli fi cationfactor Am formov.Horizontal Ci 1.96
Spectralampli fi cationfactor Am formov.Horizontal Cc 1.37
Inertial ForceLateral Accelerationof Muro(Pw) 1709.73
Lateral AccelerationInertialForce Dome(Pr) 681.47
Lateral Forcepul sivaIm(Pi) 32967.67kg
Convecti ve LateralForce (Pc) 65390.96kg

2.2. Horizontal Dynamic Spectral Analysis.

Initial Parameters and Formulation of Inelastic Spectra:

The following values specified in the static analysis will be taken:

Factorzone (Z) 0.40


Imimportancefactor(I) 1.50
Coeffi ci ent representi ng the characteri sti cs of the soi l (S) 1.40
Coef. From MENDMENT I m pul si vas Response Forces (Rwi ) 2.75
Coef. From MENDMENT Convecti ve Response Forces ( Rwc) 1.00
Spectralampli fi cationfactor Am formov. Horizontal Ci 1.96
Spectralampli fi cationfactor Am formov. Horizontal Cc 1.37

The Design Spectrum for assessing inertial forces produced by the wall +
dome + impulsive component, will be as follows.
ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3


ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3

The Spectrum Design for Convective Component shall:

For both parameters records were taken Static Analysis.


ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3

Modeling the Impulsive and convective mass:

Criteria developed by Housner, GW which can be found in "Dynamic Pressure


on Fluid Containers", Technical Information (TID) Document 7024, Chapter 6,
and Appendix F, U.S. Atomic Energy Commission, 1963. This model gives good
approximation take compared to more sophisticated models such as that
presented Graham and Rodriguez (1952).

A three dimensional model is built and a hub are assigned to map the
impulsive component weight (W = 54.95 Tn) to a hi (1.13 m) tall. Knots hi
level were modeled to have the same displacement and Wi simulate the mass
moving with the tank walls. The first mode of vibration obtained was
0.1955s, 0.0169s compared to that obtained in the calculation of Ti.
The convective component was modeled with Wc = 56.67 tons weight, a

height hc (1.75 m). This weight will be attached to the walls of tank

24 springs, which have a stiffness of 11.35 t / m; This causes the weight


to interact with the walls of the tank. The first vibration mode which is
obtained without considering the contribution of the tank walls, was 1.29s
1.59s compared to that obtained in the Tc calculation.

2.3. Push Soil Dynamics.

The soil mass involved in an earthquake is calculated by the method of


Pseudo force. The weight for the calculation of the mass of soil is
considered acting for a length equal to the diameter divided by the
reservoir area of each tributary of the wall section. Will be modeled to a
height of 0.3 H of the base of the wall.
ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3



According Monobe-Okabe:



Densi ty of Soi l () 1100.00kg/m
Depth of the reservoi r i s buri ed (hz) 1.00m
Muroinclination() 0.00
Soi l Fri cti on Angl e () 17.00
Fri cti on angl e between M uro and Soi l () 12.75
Incl i ne Soi l Sl ope () 0.00
tomax 0.20g
11.31
Kae 0.73
Wei ght per m handl e soi l 2804.49kg
Wei ght interacting ZI SCi / Rwi (Pb) 1682.69kg

2.4. Uploads Dead Weight, Live Loads, Pressure Water and Soil Active Push.
The loads by weight own be the that provide the walls the
reservoir and the roof.
As overhead design for minimum of 50 kg/m2 on the dome of the reservoir
will be assigned.
Water pressure is modeled using all the contour of the walls of the
reservoir as the thrust forces from
ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3

active soil. Ture in both until they are, 3.00 m for water and 1.00 m to
the ground.

2.5. Summary of Structural Analysis

Calculation of Total Shear and Moment in the Base, as ACI 350.3-01 Section
4.1.2 and 4.1.3:
The base shear is equal to the sum of the inertial forces of the reservoir,
plus the forces promoting convective impulsive components, plus the force
produced by the mass of soil; the combination of these forces will be in
the discretion of the square root of the sum of squares.

A L I S A N I S A T E S T I CO
Total i n base shear (V) 75153.54kg
Hei ght to center of M uro ravedad G (hw) 2.00m
Hei ght to center of the Dome ravedad G (hr) 4.31m
Hei ght at center of G ravedad of Com p. Im pul si va (hi ) 1.13m
Hei ght at center of G ravedad of Com p. Convecti ve (hc) 1.75m
Hei ght at the l ocati on of the thrust force em soi l (hz / 3) 0.33m
MomentbyMuroacceleration(Pw) 3419.46kgm
MomentbyacceleratingtheDome(Pr) 2933.81kgm
MomentbyLateralForcepulsivaIm(Pi) 37088.63kgm
MomentbyLateralForceConvective(Pc) 114377.44kgm
MomentbyLateralForceGroundloopM(Pb) 560.90kgm
TotalMomentatthebase(Mb) 122549.76kgm

A L I S I S A N DI N M I CO
Total shear at the base to 80% of Stati c Anal ysi s 60122.83kg
Total shear at the base to Dynami c Anal ysi s i co (V) 77938.30kg
Factor to scal e the desi gn spectrum 9.81
De s p z t o m e n t M a x i m o r
Rightshifttowardentanalysis 0.0083cm
Hei ght at whi ch the poi nt i s l ocated 4.00m
Drift 0.0000571
Driftmaximum 0.007
ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3

3. Design Parties Reservoir.

3.1. Majorization Load Factors and Strength Reduction. According to ACI 350M-01
and ACI 318M-08.
In both codes are working with the recently published ACI 318M-

. 08 The following load combinations are indicated by the load factors


majorization:
U = 1.4 (D + F)

U = 1.2 (D + F) + 1.6 (L + H) + Lr 0.5 U


= 1.2 D + 1.6 L + Lr
U = 1.2 D + E + L
U = 0.9 D + E
D = Dead Weight uploads, Dead Loads. L =
Loads Vivas.
Lr = Roof Loads.

H = Soil Pressure Loads.

F = Fluid Pressure Loads.

The reduction factors of resistance to:


Controlled Voltage = 0.9

Controlled compression spiral wire members = 0.75 Compression


Controlled, other types of reinforcement = 0.65
Shear and Torsion = 0.75

Seismic shear zones = 0.60

Boards and diagonal reinforcement beams = 0.85


ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3

3.2. Design Dome Reservoir.

Shells and Folded Plates ACI 318M-08: the considerations listed in Chapter
19 shall take.
According to section 9.2.11, the design strength will be equal to 0.40 f'c.

The minimum amount to be provided pursuant to Section 7.12, equal to


0.0018. The reinforcement is provided to resist tensile stresses. Design
efforts for the action associated with membrane (normal and shear forces)
and the effort associated with the flexural (bending moments, torsion and
shear) should be verified.
The reinforcement is provided in two directions and in a single
layer. They first analyze the section of the dome of 0.10 m.


ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3


ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3

The initial data are shown in the table below:

C d e s i g n t h e p u ' s o d e , e s p e s o r = 1 0 c m
Yi el di ng steel (fy) 4200.00kg/cm2
ResistancetopressureComConcrete(f'c) 210.00kg/cm2
Moduleofelasticityofconcrete(Ec) 218819.79kg/cm2
ThicknessoftheDome 0.10m
ThicknesspromedioDome,entareaensancham 0.125m
ComResistanceDesignofConcretepressure(f'dc)(19.2.11) 84.00kg/cm2
M i ni m um amount to ( 7. 12) 0.0018
Dri ve Reducti on Factor () 0.90

In both directions (radial and tangential) are worked with minimum amounts.
Review before the moments and shear effects was performed.
ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3

Radialreinforcement(MembraneActions)
EffortRadialDriveS11 5.85t/m2
Elementlengthtoassess 0.50m
Radi al Force Dri ve N DES1 165.00Kg
Steel area requi red 0.044cm2
Area of steel requi red to m i ni m um 0.900cm2
Steel used area 0.900cm2
Diameterbar 3/8
Bar area 0.710cm2
Bar Number 1.27
Number of bars to use 2.00
Separati on 0.250m
Separati on m axi m um 0.450m
U si ng separati on 0.250m
Rods are placed 3/8@0.25m
IsioREVAMONMENTOYOUANDCOrtan
MomentM11(Radial) 10.00kgm
Cant Efecti co 0.065m
amount necessary 0.00013
Area of steel requi red 0.0000041cm2
Rods are placed 3/8@0.25m
Shear V 13 ( Radi al ) 0.79Kg
Shear resi sti ng the proposed secti on 1184.02Kg
Noneedforshearreinforcement
TangentialReinforcement(MembraneActions)
TangentialEffortDriveS22 1.21t/m2
Elementlengthtoassess 0.40m
Tangenti al Force Dri ve N DES2 0.59Kg
Steel area requi red 0.000cm2
Area of steel requi red to m i ni m um 0.720cm2
Steel used area 0.720cm2
Diameterbar 3/8
Bar area 0.710cm2
Bar Number 1.01
Number of bars to use 1.00
Separati on 0.400m
Separati on m axi m um 0.450m
U si ng separati on 0.400m
Rods are placed 3/8@0.4m
IsioREVAMONMENTOYOUANDCOrtan
MomentM22(Tangential) 8.48kgm
Cant Efecti co 0.065m
amount necessary 0.00013
Area of steel requi red 0.0000051cm2
Rods are placed 3/8@0.4m
Shear V 23 ( Tangenti al ) 15.47Kg
Shear resi sti ng the proposed secti on 947.22Kg
Noneedforshearreinforcement

The next step will be to design the widening area of the dome section shall
be calculated to an average thickness of 12.5 cm.
ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3


ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3

C d e s i g n t h e p u ' s o d e , e s p e s o r = 1 5 c m
Yielding steel(fy) 4200.00kg/cm2
ResistancetopressureComConcrete(f'c) 210.00kg/cm2
Moduleofelasticityofconcrete(Ec) 218819.79kg/cm2
ThicknesspromedioDome,entareaensancham 0.125m
ComResistanceDesignofConcretepressure(f'dc)(19.2.11) 84.00kg/cm2
M i ni m um amount to ( 7. 12) 0.0018
Drive ReductionFactor() 0.90
ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3

Radialreinforcement(MembraneActions)
EffortRadialDriveS11 42.29tons/
Elementlengthtoassess 0.50m
Radi al Force Dri ve N des1 1479.56Kg
Steel area requi red 0.391cm2
Area of steel requi red to m i ni m um 1.125cm2
Steel used area 1.125cm2
Diameterbar 3/8
Bar area 0.710cm2
Bar Number 1.58
Number of bars to use 2.00
Separati on 0.250m
Separati on m axi m um 0.450m
U si ng separati on 0.250m
Rods are placed 3/8@0.25m
IsioREVAMONMENTOYOUANDCOrtan
MomentM11(Radial) 6.39kgm
Cant Efecti co 0.065m
amount necessary 0.00008
Area of steel requi red 0.0000026cm2
Rods are placed 3/8@0.25m
Shear V 13 ( Radi al ) 3.34Kg
Shear resi sti ng the proposed secti on 1184.02Kg
Noneedforshearreinforcement
TangentialReinforcement(MembraneActions)
TangentialEffortDriveS22 44.82tons/
Elementlengthtoassess 0.90m
Tangenti al Force Dri ve N DES2 1285.20Kg
Steel area requi red 0.340cm2
Area of steel requi red to m i ni m um 2,025cm2
Steel used area 2,025cm2
Diameterbar 3/8
Bar area 0.710cm2
Bar Number 2.85
Number of bars to use 3.00
Separati on 0.300m
Separati on m axi m um 0.450m
U si ng separati on 0.200m
Rods are placed 3/8@0.2m
IsioREVAMONMENTOYOUANDCOrtan
MomentM22(Tangential) 45.74kgm
Cant Efecti co 0.065m
amount necessary 0.00032
Area of steel requi red 0.0268371cm2
Rods are placed 3/8@0.2m
Shear V 23 ( Tangenti al ) 36.63Kg
Shear resi sti ng the proposed secti on 2131.24Kg
Noneedforshearreinforcement

3.3. Reservoir Design Wall (Walls).

Earthquake Resistant Structures Forces ACI 318M-08: the considerations


listed in Chapter 21 shall be taken.
ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3

According to Table 1613.5.2 of the Standard IBC 2006, we classify the site
in category "D", and according to Table R21.1.1 of ACI 318 Chapter 21-M-08,
must comply with section 21.9.

The wall of a reservoir works to resist efforts membrane in the radial


direction, in the tangential direction is more important to the effects
produced by the moments and shear. The design is given for both the outside
and inside.

De s i g n u r o M o d e l E x t e r i o r e s p e s o r = 2 0 c m
Yi el di ng steel (fy) 4200.00kg/cm2
ThicknessoftheMiddlepromuro 0.200m
ResistancetopressureComConcrete(f'c) 210.00kg/cm2
Moduleofelasticityofconcrete(Ec) 218819.79kg/cm2
M i ni m um amount to ( 21. 9. 2. 1) 0.0025
Dri ve Reducti on Factor () 0.90
ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3


ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3


ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3

Radialreinforcement(horizontal)intheExterior(EquityMembrane)
EffortRadialDriveS11 79.93tons/
Elementlengthtoassess 0.50m
Radi al Force Dri ve N des1 3265.00Kg
Steel area requi red 0.864cm2
Area of steel requi red to m i ni m um 2,500cm2
Steel used area 2,500cm2
Diameterbar 3/8
Bar area 0.710cm2
Bar Number 3.52
Number of bars to use 3.00
Separati on 0.167m
Separati on m axi m um 0.450m
U si ng separati on 0.150m
Rods are placed 3/8@0.15m
IsioREVAMONMENTOYOUANDCOrtan
MomentM11(Radial) 91.17kgm
Cant Efecti co 0.065m
amount necessary 0.00116
Area of steel requi red 0.376cm2
Rods are placed 3/8@0.15m
Shear V 13 ( Radi al ) 39.23Kg
Shear resi sti ng the proposed secti on 1872.10Kg
Noneedforshearreinforcement
Tangentialreinforcement(vertical)intheExterior(MembraneActions)
TangentialEffortDriveS22 128.75tons/
Elementlengthtoassess 0.90m
Tangenti al Force Dri ve N DES2 5581.93Kg
Steel area requi red 1,477cm2
Area of steel requi red to m i ni m um 4,500cm2
Steel used area 4,500cm2
Diameterbar 3/8
Bar area 0.710cm2
Bar Number 6.34
Number of bars to use 7.00
Separati on 0.129m
Separati on m axi m um 0.450m
U si ng separati on 0.125m
Rods are placed 3/8@0.125m
IsioREVAMONMENTOYOUANDCOrtan
MomentM22(Tangential) 813.74kgm
Cant Efecti co 0.065m
amount necessary 0.00610
Area of steel requi red 3.57cm2
Rods are placed 3/8@0.125 m
Shear V 23 ( Tangenti al ) 36.63Kg
Shear resi sti ng the proposed secti on 3369.79Kg
Noneedforshearreinforcement
ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3


ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3


ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3

Radialreinforcement(horizontal)intheInnerFace(MembraneActions)
EffortRadialDriveS11 38.61tons/
Elementlengthtoassess 0.50m
Radi al Force Dri ve N des1 3027.67Kg
Steel area requi red 0.801cm2
Area of steel requi red to m i ni m um 2,500cm2
Steel used area 2,500cm2
Diameterbar 3/8
Bar area 0.710cm2
Bar Number 3.52
Number of bars to use 4.00
Separation 0.125m
Separation m aximum 0.450m
Using separation 0.125m
Rods are placed 3/8@0.125m
IsioREVAMONMENTOYOUANDCOrtan
MomentM11(Radial) 95.40kgm
Cant Efecti co 0.065m
amount necessary 0.00121
Area of steel requi red 0.394cm2
Rods are placed 3/8@0.125m
Shear V 13 ( Radi al ) 40.38Kg
Shear resi sti ng the proposed secti on 1872.10Kg
Noneedforshearreinforcement
Tangentialreinforcement(vertical)intheInnerFace(MembraneActions)
TangentialEffortDriveS22 129.32tons/
Elementlengthtoassess 0.90m
Tangenti al Force Drive N DES2 5533.21Kg
Steel area requi red 1,464cm2
Area of steel requi red to m i ni m um 4,500cm2
Steel used area 4,500cm2
Diameterbar 3/8
Bar area 0.710cm2
Bar Number 6.34
Number of bars to use 7.00
Separation 0.129m
Separation m aximum 0.450m
Using separation 0.125m
Rods are placed 3/8@0.125m
IsioREVAMONMENTOYOUANDCOrtan
MomentM22(Tangential) 813.74kgm
Cant Efecti co 0.065m
amount necessary 0.00610
Area of steel requi red 3.57cm2
Rods are placed 3/8@0.125m
Shear V 23 ( Tangenti al ) 2116.54Kg
Shear resi sti ng the proposed secti on 3369.79Kg
Noneedforshearreinforcement
ANLISISYDISEODEUNRESERVORIOAPOYADAOFCONCRETOARMADO
PARAUNACAPACIDADDE115m3

Sap2000 Comments to use:


It will work with the impulsive spectrum, for the weight of the convective component
will have to scale the values as this weight needs another spectrum and would be
evaluated in a separate model (separate the impulsive component and the inertial
forces of the reservoir), but to work it in the same model we will: Rwc / Rwc = 1.65
/ 0.6 = 2.75, so the weight will be 55,678 x Wc
2.75 = 155.83 corresponding to a value for the springs of 51.78 t / m.
Spectra values vary for impulsive and convective components, but working with the
peak values.